23 6313 BSD-Existing Central Air Conditioner Replacement Project Manual.pdf
PDF 93 KB Posted
- Attached to
- Jefferson RCE HVAC System Replacements
- Solicitation number
- 645-DOTRFQ-3203-2027
- Issued by
- Jasper County, Iowa
About this file
This is a technical specification document for the Existing Central Air Conditioner Replacement project issued by the Iowa Department of Transportation as part of the Jefferson RCE HVAC System Replacements opportunity. The specification details the requirements for packaged, factory-assembled outdoor air conditioning units suitable for replacement of existing central air conditioning systems. The document establishes performance standards, product specifications, and installation requirements, including references to industry standards such as AHRI 210/240, ASHRAE standards, NEMA guidelines, and UL certification requirements. Key product requirements include a minimum SEER rating of 14, aluminum fin condenser coils with copper tubing, weatherproof motors with overload protection, and factory-wired control panels with solid-state speed variation controls for condenser fan motors. The specification mandates compliance with manufacturer installation instructions and submission of product data, shop drawings, manufacturer's instructions, and operation and maintenance documentation prior to installation.
The document establishes quality assurance requirements specifying that manufacturers must have a minimum of three years of documented experience in producing air conditioning equipment and that installers must have at least three years of experience in performing this type of work. All products requiring electrical connections must be listed and classified by Underwriters Laboratories as suitable for the specified purpose. The specification requires condenser coils to be air-tested under water to 425 psig and vacuum dehydrated with a nitrogen holding charge. Additional requirements include proper delivery, storage, and handling procedures in accordance with manufacturer specifications, with particular attention to protection of coils and units from physical damage on site.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
/ 5509 Standard Specifications 23 6313 - 1 EXISTING CENTRAL AIR
CONDITIONER REPLACEMENT
(05-21-2019)
SECTION 23 6313
EXISTING CENTRAL AIR CONDITIONER REPLACEMENT (05-21-2019)
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Manufactured units.
B. Casing.
C. Condenser coils.
D. Fans and motors.
E. Controls.
1.02 REFERENCE STANDARDS
A. AHRI 210/240 - Standard for Performance Rating of Unitary Air-Conditioning and Air-Source
Heat Pump Equipment; 2008, Including All Addenda.
B. ASHRAE Std 15 - Safety Standard for Refrigeration Systems; 2013.
C. ASHRAE Std 20 - Methods of Testing for Rating Remote Mechanical-Draft Air-Cooled
Refrigerant Condensers; 1997 (R2006), with Errata 2014.
D. ASHRAE Std 90.1 I-P - Energy Standard for Buildings Except Low-Rise Residential Buildings;
2013, Including All Amendments and Errata.
E. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2014.
F. NEMA MG 1 - Motors and Generators; 2014.
G. UL 207 - Standard for Refrigerant-Containing Components and Accessories, Nonelectrical;
Current Edition, Including All Revisions.
1.03 SUBMITTALS
A. Product Data: Provide rated capacities, weights, accessories, electrical requirements, and wiring diagrams.
B. Shop Drawings: Indicate components, assembly, dimensions, weights and loading, required clearances, and location and size of field connections. Include schematic layouts showing condenser, refrigeration compressors, cooling coils, refrigerant piping and accessories required for complete system.
C. Manufacturer's Instructions: Submit manufacturer's complete installation instructions.
D. Operation and Maintenance Data: Include start-up instructions, maintenance instructions, parts lists, controls, and accessories.
E. Maintenance Materials: Furnish the following for Iowa Department of Transportation's use in maintenance of project.
1.04 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Installer Qualifications: Company specializing in performing the work of this section with minimum 3 years of experience.
C. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated.
1.05 DELIVERY, STORAGE, AND HANDLING
A. Comply with manufacturer's installation instruction for rigging, unloading and transporting units.
B. Protect units on site from physical damage. Protect coils.
dconroy Highlight dconroy Highlight dconroy Highlight dconroy Highlight dconroy Highlight
/ 5509 Standard Specifications 23 6313 - 2 EXISTING CENTRAL AIR
CONDITIONER REPLACEMENT
(05-21-2019)
PART 2 PRODUCTS
2.01 PERFORMANCE REQUIREMENTS
2.02 MANUFACTURED UNITS
A. Provide packaged, factory assembled, pre-wired unit, suitable for outdoor use consisting of casing, condensing coil and fans, integral sub-cooling coil liquid accumulator.
B. Construction and Ratings: In accordance with AHRI 210/240 and UL 207. Testing shall be in accordance with ASHRAE Std 20.
C. Performance Ratings: Energy Efficient Rating (EER)/Coefficient of Performance (COP) not less than prescribed by ASHRAE Std 90.1 I-P, in combination with compressor units.
D. Minimum SEER ratingof 14.
2.03 CASING
A. House components in welded steel frame with steel panels with weather resistant, baked enamel finish.
B. Mount starters, disconnects, and controls in weatherproof panel provided with full opening access doors. Provide mechanical interlock to disconnect power when door is opened.
C. Provide removable access doors or panels with quick fasteners.
2.04 CONDENSER COILS
A. Coils: Aluminum fins mechanically bonded to seamless copper tubing. Provide sub-cooling circuits. Air test under water to 425 psig, and vacuum dehydrate. Seal with holding charge of nitrogen.
B. Coil Guard: Expanded metal with lint screens.
C. Configuration: Single refrigeration circuit with receiver.
2.05 FANS AND MOTORS
A. Vertical discharge direct driven propeller type condenser fans with fan guard on discharge, equipped with roller or ball bearings with grease fittings extended to outside of casing.
B. Weatherproof motors suitable for outdoor use, single phase permanent split capacitor or 3 phase, with permanent lubricated ball bearings and built-in current and thermal overload protection.
2.06 CONTROLS
A. Provide factory wired and mounted control panel, NEMA 250, containing fan motor starters, fan cycling thermostats, compressor interlock, and control transformer.
B. Provide solid state control to vary speed of one condenser fan motor in response to refrigerant condensing pressure.
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturer's instructions.
END OF SECTION