This is a temperature controls upgrade study report prepared for the Commonwealth of Kentucky's Finance and Administration Cabinet regarding Western State Hospital's building management system (BMS) infrastructure improvements. The report evaluates 36 buildings across the hospital campus to identify modifications required for existing HVAC equipment and new BMS component additions, with the goal of implementing a hospital-wide BMS utilizing open-source software and BACnet MS/TP compatible building controllers. The study was conducted through multiple site visits to survey mechanical systems, interviews with maintenance and engineering staff, and review of available drawings. The project encompasses central plant facilities (chiller, boiler, and electrical buildings), the main hospital complex (Buildings 55-63 with multiple floors and zones), support facilities including cafeteria, kitchen, laundry, nursing facilities, and auxiliary buildings. Historical data indicates that BMS installation typically yields approximately 5% energy savings. The assessment recommends BMS integration for 26 of the 36 buildings evaluated, with specific controller installations, sensor additions, equipment modifications, and removal of legacy Andover Controls systems.
The opinion of cost and phasing document outlines a 13-phase implementation plan with estimated costs ranging from $350,000 to $975,000 per phase, totaling approximately $10.6 million for complete campus-wide BMS integration. Phase 1 addresses the central chiller plant ($560,000), while subsequent phases target the boiler plant, main hospital buildings (Phases 2-9 totaling $6.4 million), nursing facility buildings, kitchen and cafeteria operations, and ancillary facilities. Each phase specifies detailed work descriptions including building controller installation, removal of obsolete control panels (TCP-40_1, TCP-40_2, TCP-57_1, TCP-60_1, and TCP-2 series controllers), installation of BACnet-compatible devices for thermostats, fan coil units, unit ventilators, exhaust fans, pump controllers, and motorized dampers. Nine buildings were excluded from BMS integration due to abandonment, limited HVAC equipment, or storage-only use. The study was dated December 29, 2022, with document stamps indicating reviews on September 9, 2024, and October 21, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
FRANKFORT, KENTUCKY
WESTERN STATE HOPSITAL
TEMPERATURE CONTROLS UPGRADE
STUDY
Prepared for:
Finance and Administration Cabinet
Frankfort, Kentucky
Prepared by:
Louisville, Kentucky
December 29, 2022
09/09/24 10/21/24
Western State Hospital Temperature Controls Upgrade
TABLE OF CONTENTS
I. INTRODUCTION
II. SITE PLAN WITH BUILDING NUMBERS
III. BUILDING TEMPERATURE CONTROL INFORMATION
IV. BUILDING ASSESSMENT
A. Central Plant: Chiller (Building 39) B. Central Plant: Boiler Building (Building 40) C. Central Plant: Electrical Building (Building 41) D. Cafeteria (Building 48) E. Kitchen (Building 49) F. Kitchen Storage and Art Studio (Building 50) G. Shipping and Fabrics (Building 51) H. Western State Nursing Facility (Building 30) I. Western State Nursing Facility (Building 31) J. Western State Nursing Facility (Building 32) K. Western State Nursing Facility (Building 33) L. Genesis (Building 20) M. Dairy Barn (Building 3) N. Welding Shop (Building 4) O. Paint Shop (Building 10) P. Transportation and Gym (Building 14) Q. EVS (Building 15) R. Equipment / Storage (Building 18) S. Maintenance (Building 21) T. Storage (Building 22) U. Chapel (Building 28) V. Laundry (Building 36) W. Bus Stop (Building 65) X. Storage (Building 66) Y. Guardian Services (Building 78) Z. Storage Barn (Building 100) AA. Front Guard Shack (Building 162) BB. Generators
V. OPINION OF COST/PHASING DOCUMENT
I. INTRODUCTION
The Commonwealth of Kentucky has retained BCCLT to evaluate the Building Management System (BMS) capabilities including a web-based system that allows monitoring and/or control. It is anticipated that most of the Project buildings will ultimately be part of the BMS with the extent of equipment control being determined by the equipment complexity. A building management system will allow central monitoring of multiple campus building HVAC systems. Having access to the status and control of the buildings’ HVAC equipment can reduce maintenance and energy costs by eliminated the need to visit a site to troubleshoot and/or adjust set points. System performance can improve by monitoring operation and end user input in real time. Historical data indicates that with the installation of a building management system, energy savings of approximately 5% can be expected.
BCCLT has reviewed the applicable 36 buildings for equipment complexity related to the BMS integration through multiple site visits to survey the mechanical systems with facility personal. Information was attained through these site visits, interviews of maintenance and engineering staff, and review of available drawings. Fire and Security systems were not included in this scope of work. See following for locations of buildings evaluated.The purpose of this report is to evaluate, identify, and recommend, modifications required for existing equipment for additions of new BMS components for a hospital campus wide BMS system. Each building to receive a building management system will require a building controller with open source software, and is BACnet MS/TP compatible. The building controller will allow the facility personal or engineering staff to view and command unitary and field controller installed in each site. This is accomplished through a web-based browser, so no direct communication or fiber lines are required between buildings. The chart below summarizes the BMS architecture and each building and the various equipment and BMS recommendations
BACnet
C
A A
H
A H
A A
H
A
A A C
CHA
CH
C CA
CA A
CH
CH A
H A
A H A
A A V C
A A
A HAC
WSH BUILDING TEMPERATURE CONTROL INFORMATION
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
3 3-G Dairy Barn N/A N/A N/A Abandoned / Hazardous
Steam Heater (Abandoned) N/A Steam heater. Requires a steam line to operate. Steam line currently not available
Exhaust Fan (x1) Unknown / Unknown Exhausts air out of the building through a wall
Louver (x1) Unknown / Unknown wall mounted louver Improvies air flow in the building
Air Handler Unit (Heat Pump) Airquest / PHB048NIHE Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Exhaust Fan (x1) Unknown / Unknown Exhausts air out of the building through a wall
Louver (x1) Unknown / Unknown wall mounted louver Improvies air flow in the building
Thermostat (x1) Unknown / Unknown allows occupants to create an area temperature set point
Unit Heaters (x5) Unknown / Unknown Boils water into vapor to be used to condition the air in the building
Radiator (x1) Unknown / Unknown Heats a space using the heat from hot water
Packaged Terminal Air Conditioner (PTAC) Unknown / Unknown Allows an occupant to control the temperature of a space without affecting other spaces of a building
Split System Heat Pump (Outdoor) (x2) Bryant / 223APA048-A Outdoor unit using refrigerant to expell or absorb heat
Split System Air Handler Unit (Indoor) (x2) Bryant / FY4ANF048 Indoor unit using refrigerant to condition air
Unit Heater (x4) Unknown / Unknown Allows for a space to be heated using different sources
Exhaust Fan (x2) Unknown / Unknown Exhausts air out through a wall
Packaged Terminal Air Conditioner (PTAC) (x4) Unknown / Unknown Allows an occupant to control the temperature of a space without affecting other spaces of a building
Louver (x2) Unknown / Unknown wall mounted louver Improvies air flow in the building
Air Handler Unit (x3) Unknown / Unknown Conditions air in the EVS building
Condensing Unit (x1) York / HDEC-T048SA Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Thermostat (x3) Unknown / Unknown allows occupants to create an area temperature set point
18 18-G Equipment / Storage N/A N/A N/A For Storage
Furance (x8) CARRIER / 58MXA120-F-17120 Used to condition air for heating
Furance (x1) CARRIER / 58MXA120-F-17116 Used to condition air for heating
Coils (x8) CARRIER / CK5AXA060024ABAA Used to expell heat and humidity from a space to cool it
Coils (x1) CARRIER / CK5AXA048021ABAA Used to expell heat and humidity from a space to cool it
Condensing Unit (x3) TRANE / 38ARD0125 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Condensing Unit (x2) TRANE / 38BRG0603 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Condensing Unit (x1) TRANE / 38BRG0483 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Condensate Pump (x3) Unknown / Unknown Pumps condensate to suitable destination
Thermostat (x5) Unknown / Unknown allows occupants to create an area temperature set point
Temperature Sensor (x5) Unknown / Unknown Takes temperature readings of an area and relays info back to its associated thermostat
Exhaust Fan (x3) GREENHECK / SP-228 Exhausts air out of the roof
Exhaust Fan (x1) GREENHECK / SP-250 Exhausts air out of the roof
Exhaust Fan (x1) GREENHECK / GB-100-4 Exhausts air out of the roof
Exhaust Fan (x1) GREENHECK / SP-224 Exhausts air out of the roof
Radiator (x1) Unknown / 4ft, 11,000 BTU/hr Conditions the air in a space using hot water
Radiator (x1) Unknown / 5ft, 8,200 BTU/hr Conditions the air in a space using hot water
Radiator (x1) Unknown / 5ft, 13,400 BTU/hr Conditions the air in a space using hot water
Radiator (x1) Unknown / 8ft, 16,500 BTU/hr Conditions the air in a space using hot water
Radiator (x1) Unknown / 11ft, 27,400 BTU/hr Conditions the air in a space using hot water
Radiator (x1) Unknown / 16ft, 42,000 BTU/hr Conditions the air in a space using hot water
Unit Heaters (x3) Unknown / 52,400 BTU/hr Allows for a space to be heated using different sources (This case steam heat)
Unit Heaters (x5) Unknown / 41,000 BTU/hr Allows for a space to be heated using different sources (This case steam heat)
Unit Heaters (x3) Unknown / 32,600 BTU/hr Allows for a space to be heated using different sources (This case steam heat)
Unit Heaters (x4) Unknown / 30,000 BTU/hr Allows for a space to be heated using different sources (This case steam heat)
Unit Heaters (x1) Unknown / 21,000 BTU/hr Allows for a space to be heated using different sources (This case steam heat)
Convertor (x1) Unknown / 75 GPM Allows for water expell (condense) heat that is transferred to other equipment
Condensate Pump (x1) Unknown / 3000ft2 EDR to pump condensate from the converter
Compression Tanks (x2) Unknown / 50 Gallon Capacity control the pressure within the high pressure steam system
Hot Water Pump (x1) Unknown / Unknown Used to pump hot water into the convertor
Thermostats (x2) Unknown / Unknown allow a manual set point temperature for a space
21-R Maintenance Exhaust Fan (x1) Unknown / Unknown Exhausts air out the roof
Radiator Units (x2) Unknown / Unknown Allows for a space to be heated using steam heat
Exhaust Fan (x1) Unknown / Unknown Exhausts air through a wall
Louver (x1) Unknown / Unknown wall mounted louver Improvies air flow in the building
Mini Split Air Handler Units (x3) (Indoor) Gree / VIR36HP230V1SAH Indoor air handler conditions air by using R410A
Mini Split (x3) (Outdoor) Gree / VIR36HP230V1AO Outdoor compressor operating with R410A to condition indoor air
Exhaust Fans (x3) Unknown / Unknown Exhausts air out of the sanctuary (x2), and out through a wall (x1)
Louver (x3) Unknown / Unknown wall mounted louver Improvies air flow in the building
Air Handler Unit (x1) Trane / Mod. 17 Conditions air in the Recreation Hall
Fan Coil Unit (x1) 600 cfm, 4.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x1) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhuast Fan (x4) 137 cfm, 1/20 HP Exhausts air out of the roof
Storage Building
Facility Services
Rehab
Paint Shop
4 4-G
14-1
Storage
Gym
10-G Paint Shop
Houses Gym and Transportation
Store furniture
15-G EVS
20-R
20-G
30-G Recreation Hall
Genesis
Genesis
Chapel
22-G
Houses cleaning service
Services and meetings
Transportation
20-1 Genesis
21-G Maintenance
14-G
Storage
28-G
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Exhaust Fan (x1) 850 cfm, 1/4 HP Exhausts air out of the roof
Fan Coil Units (x7) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x15) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x9) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x10) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Fan Coil Units (x8) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x17) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x10) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Fan Coil Units (x7) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x16) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 4.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x1) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Exhaust Fan (x1) 4150 cfm, 1/2 HP Exhausts air out the roof
Exhaust Fan (x1) Greenheck / GB-120-4 Exhausts air out the roof
Exhaust Fan (x5) Unknown / Unknown Exhausts air out the roof
Secondary Circuit Pump (x1) Taco / Inline Mod. 1641 Pump delivers Hot/Cold Water to Zone 1 (Building 30)
Secondary Circuit Pump (x1) Taco / Inline Mod. 1638 Pump delivers Hot/Cold Water to Zone 2 (Building 32)
Secondary Circuit Pump (x1) Taco / Mounted Centrifugal Size 4010 / 60 ft. Hd Pump delivers Hot/Cold Water to Zone 3 (Building 31)
Secondary Circuit Pump (x1) Taco / Mounted Centrifugal Size 4010 / 70 ft. Hd Pump delivers Hot/Cold Water to Zone 4 (Building 33)
Standby Secondary Circuit Pump (x1) Aurora / Vertical Split Case Series 410, Model 413 Standby Pump delivers Hot/Cold Water to either Zone 3 or 4 (Buildings 31 and 33)
Fan Coil Units (x6) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
32-1 ROOF Fan Coil Units (x4) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x8) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x15) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhuast Fan (x1) 850 cfm, 1/4 HP Exhausts air out an outside wall
Fan Coil Units (x8) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x17) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x8) 230 cfm, 1.52 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 305 cfm, 2.12 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x16) 400 cfm, 2.66 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 4.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 4.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 1100 cfm, 7.1 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhuast Fan (x1) 4150 cfm, 1/2 HP Exhausts air out the roof
Exhuast Fan (x6) Unknown / Unknown Exhausts air out the roof
Unit Heater (x4) Reznor / UDAS-100 Allows for a space to be heated using different sources (This case steam heat)
Unit Heater (x4) Reznor / UDAS-60 Allows for a space to be heated using different sources (This case steam heat)
Boiler & Accessories (x1) Laars Pennent / 1000 Generates either hot water or steam to be used in the laundry building
Louvers (x2) Unknown / Unknown wall mounted louver Improvies air flow in the building
Storage Tanks (x3) Unknown / Unknown Stores hot water for the boiler system
32-PR
32-G
33-G
33-1
33-2
31-G
32-1
32-2 WSNF/Aux Kitchen
WSNF
WSNF
WSNF
WSNF
WSNF
36 36-G
Houses 145 long term patients
32-R Roof
Houses 145 long term patients
Laundry Wash and dry laundry
Houses 145 long term patients
WSNF
WSNF
33-R Roof
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Chiller (x1) Daikin / WSC087LBC40R/E3612 Vapor-compression chiller reducing the temperature of water
Chiller (x1) McQuay / WSC087-BAABC Vapor-compression chiller reducing the temperature of water
Variable Frequency Drive (VFD) (x9) Armstrong / DRV 80 Used to vary the speed of motors in various equipment
Pump (x2) (WSNF) Weg Nema / 040180T3E324T Backup pump for forcing water to the nursing home
Pump (x1) (Cooling Tower Pump #6) Baldor - Reliance / EM2539T-G, 40E245X166G1 Pump circulating water meant for the cooling tower
Pump (x1) (Cooling Tower Pump #7) Baldor - Reliance / EM2539T-G, 40E245X166G1 Pump circulating water meant for the cooling tower
Pump (x1) (Main Hospital Pump #11) Baldor - Reliance / 0107475738-000010, MP36G52 Pump for forcing water to the main hospital
Pump (x1) (Main Hospital Pump #10) Baldor - Reliance / 0107475738-000010, MP36G52 Pump for forcing water to the main hospital
Heat Exchanger (x1) (Main WSH/WSNF Heat Exchangers) Mueller / AT805 B-20 Pump for forcing water to the nursing home
Heat Exchanger (x1) (Backup WSH/WSNF Heat Exchangers) Mueller / AT805 B-20 Backup pump for forcing water to the nursing home
Condensate Pump (x1) Unknown / Unknown Pumps condensate from the chillers away from the chillers
Bluegrass Kesco / MGT-150-2 SNGL/NC/10% CROSSLI
Pentair Water USA / 2900S NXT
Chemical Feeder Tower Unknown / Unknown Stores chemicals
Cooling Tower (x1) (3 Cell) BAC / 15270 Evaporative cooling providing chilled water to a chiller
Cooling Tower (x1) (2 Cell) BAC / 15270-2 Evaporative cooling providing chilled water to a chiller
Boiler (x3) Cleaver Brooks / CB300 3 Cleaver Brooks Boilers generate HWS for Campus
Hot Water Unit Heater (x3) Modine / HS-165 Generates heat for the Central Plant during the colder months
Surge Tank (x1) Cleaver Brooks / SRG-1400 Used to equalize pressure in a water system and store water
Deareator (x1) Cleaver Brooks / BM-36 used to remove dissolved gasses from water supply to prevent deterioration of HVAC equipment
Electric Water Heater (x2) Markel / 3420 Series Used to heat the Boiler room during the winter time
Condensate Pump (x1) Bell and Gossett / Unknown (480V, 3φ) Pump used to force condensate to move in the condensate line
Condensate Punp (x3) Bell and Gossett / Unknown (208V, 1φ) Pump used to force condensate to move in the condensate line
PTAC (x3) Carrier / 525E A/C units to condition the air in the Boiler Room
Louver (x6) Amer Warm / LE-31 wall mounted louver Improvies air flow in the building (originaly automated)
Louver (x2) Amer Warm / LE-31 wall mounted louver Improvies air flow in the building (originaly automated)
Exhaust Fan (x1) Greenheck / SBE-3L42 Exhausts air out of a wall
Exhaust Fan (x1) Greenheck / SBE-1H20 Exhausts air out of a wall
Steam Pressure Reducer Valve (x27+) Unknown / Unknown valve to regulate steam pressure in a steam system
Oil Tank (x1) Unknown / Unknown Used to store fuel for the boilers in the Central Plant
Blowdown Conditioner (x1) Unknown / Unknown Conditions boiler waste condensate
Sample Cooler (x1) Cleaver Brooks / SC-42 used to cool enough steam to create a small sample of water for quality analysis
Flash Tank (x1) Unknown / Unknown Collects condensate form various drain lines.
Whistle (x1) Unknown / Unknown Used to signal operators to an issue in the system
Cleaver Brooks / WMG236637
Performance Products / MGT-120-2 TW-ALT NXT W/MORYL
Culligan / S1112SEA076
Bluegrass Kesco / MGT-300-2 TW-ALT NXT W/CLACK
Fuel Oil Pump Set (x1) Unknown / Unknown Used to transport fuel from original location to equipment location
Thermostat (x2) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Heat Exchanger (x2) Unknown / Unknown Exchanges heat for the Kitchen and WSNF
Temperature Control Panel (TCP-40_1) Unknown / Unknown Communicates with other panels and Building Management System
Temperature Control Panel (TCP-40_2) Andover Controls / PS120/240-AC85U Communicates with other panels and Building Management System
Exhaust Fan (x1) Greenheck / GB-120 Exhausts air out of the roof
Exhaust Fan (x1) Greenheck / G-90 Exhausts air out of the roof
Outdoor Heat Pump (x1) Daikin / RMXS48LVJU Outdoor unit using refrigerant to expell or absorb heat
Branch Provider Box (x1) Daikin / BPMKS048A2U Allows refrigerant to flow into multiple indoor air handler units from a common heat pump or condenser
Indoor Air Handler Unit (x2) Daikin / FTXS24LVJU Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x2) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Thermostat (x1) Unknown / Unknown to create manual temperature set points
Thermostat (x1) Unknown / Unknown Idler thermostat for nighttime operation
48-1 Mechanical Mezzanine Air Handler Unit (x2) Trane / Climate Changer L-14 B conditions air using hot water and cold water
48-R Roof Exhaust fans (x2) Unknown / Unknown Exhausts air out of the roof
Booster Pump (x2) Marathon / Unknown Assists supply water to Buildings 48-51
Temperature Control Panel (TCP-49-1) Andover Controls / i2 887 Receives and sends out signals from booster pumps in the Building 49 Pump Room to BMS
Air Handler Unit (x3) Trane / Climate Changer L-6 B conditions air using hot water and cold water
Fan Coil Unit (x1) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhaust Fans (x2) Unknown / Unknown Exhausts air out the roof
Thermostats (x4) Unknown / Unknown Allows for occupants to create a set point temperature for a space
49-R Roof Exhaust Fans (x4) Unknown / Unknown Exhausts air out of the roof
Routing Piping to B48-51, B55-63
Water Softener System (x1) Forces minerals in tap water out by using resin beads as a filter (for WSNF and Kitchen)
Has steam line to dishwasher
Electrical Room
40-R
Building 49 Pump Room
40-G
49-PR
Forces minerals in tap water out by using resin beads as a filter
39-R
3-Boilers (Some equipment may be in Building 39)
Water Softener System (x1)
2-Chillers
Cafeteria
As per Rusty, this equipment services Buildings 39-41
Forces minerals in tap water out by using resin beads as a filterWater Softener System (x1)
39-G Chiller Room
Roof
Boiler Room
Roof
48-G
Kitchen49-G
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Fan Coil Unit (x1) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x1) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x1) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x8) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Fan Coil Unit (x1) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x4) 1000 cfm, 6.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Unit (x2) 1200 cfm, 7.9 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x7) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Fan Coil Unit (x4) Unknown / Unknown Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x4) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Fan Coil Units (x10) Unknown / Unknown Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x9) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-55-B DX) Andover Controls / i2 804 Receives data from Building 55 Basement, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) 1000 cfm, 13 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) AAF - Herman Nelson / AH (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x9) 200 cfm,1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x13) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Carrier / 24ACB760A320 Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-55-G DX) Andover Controls / i2 804 Receives data from Building 55 Ground Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) 1000 cfm, 13 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x11) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x20) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-55-1 DX) Andover Controls / i2 804 Receives data from Building 55 First Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) 1250 cfm, 16 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x10) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x22) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-55-2 DX) Andover Controls / i2 804 Receives data from Building 55 Second Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) 1250 cfm, 16 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x9) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x22) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-55-3 DX) Andover Controls / i2 804 Receives data from Building 55 Third Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) 1250 cfm, 16 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x8) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x19) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Exhaust Fan (x1) 3100 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 200 cfm Exhausts air from multiple floors up to and out of the roof
55-3
OIG
Pharmacy
Ward
55-R Roof
Offices & Wards
55-G
Office
Overflow
55-1
Ward
55-2
50-G
50-1 Art Studio
51-G Shipping
51-1 Art Area
55-B Multi Needs
Kitchen Storage
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-56-B DX) Andover Controls / i2 804 Receives data from Building 56 Basement, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x16) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi / PKA-A18HA7 (Room B18) Air handler unit conditions air for data room on specified floor
Thermostat (x13) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-56-G DX) Andover Controls / i2 804 Receives data from Building 56 Ground Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x10) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi / PKFY-P12NHMU-E2 (Room G16) Air handler unit conditions air for data room on specified floor
Thermostat (x17) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-56-1 DX) Andover Controls / i2 804 Receives data from Building 56 First Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x12) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x18) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-56-2 DX) Andover Controls / i2 804 Receives data from Building 56 Second Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x11) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi / PKFY-P12NHMU-E2 (Room 214) Air handler unit conditions air for data room on specified floor
Thermostat (x17) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-56-3 DX) Andover Controls / i2 804 Receives data from Building 56 Third Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (900 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x11) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi / PKFY-P12NHMU-E2 (Room 314) Air handler unit conditions air for data room on specified floor
Thermostat (x17) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Exhaust Fan (x1) 1000 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 2100 cfm Exhausts air from multiple floors up to and out of the roof
Condensing Unit (x1) Mitsubishi / PUMY-P36NKMU1 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Condensing Unit (x1) Mitsubishi / PUZ-A18NKA7 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Booster Pump (x5) Unknown / Unknown Assists supply water to Buildings 55-59
Temperature Control Panel (TCP-57_2) Andover Controls / INFILINK 200 Send and Receive data from buildings 55-59
Temperature Control Panel (TCP-60_2) Andover Controls / INFILINK 200 Send and Receive data from buildings 60-63
Temperature Control Panel (TCP-2 B57) Andover Controls / i2 804 Send data to booster pumps for buildings 55-59, Receive data from Supply and Return DHWS/R and Pressure
Pentair Water USA / CH30953
Culligan / MY05ZTA-29NT
Unit Ventilator (x1) AAF - Herman Nelson / AV (1000 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Temperature Control Panel (TCP-57-G DX) Andover Controls / i2 804 Receives data from Building 57 Ground Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Fan Coil Units (x18) Unknown / Unknown Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Thermostat (x18) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-57-1 DX) Andover Controls / i2 804 Receives data from Building 57 First Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (1000 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x18) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x20) Unknown / Unknown Allows for occupants to create a set point temperature for a space
56-3
56-2
56-G
Offices
56 Roof
57-G Offices
Nursing Hall
57-1
Ward
Ward
Overflow Ward
57-PR Building 57 Pump Room
56-1
Roof
56-B Infirmary
Ward
OIG
Nursing Staff Offices
Office
Routing Piping to B55-59
Offices, Number and types of Fan Coil Units were not available on existing documents
Forces minerals in tap water out by using resin beads as a filterWater Softener System (x1)
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-57-2 DX) Andover Controls / i2 804 Receives data from Building 57 Second Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (1000 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x15) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x18) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Payne / PA17NA060-C Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-57-3 DX) Andover Controls / i2 804 Receives data from Building 57 Third Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AV (1000 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x13) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Thermostat (x19) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Exhaust Fan (x1) 150 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 990 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 1650 cfm Exhausts air from multiple floors up to and out of the roof
Condenser (x1) Bryant / 123ANA048-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-58-G DX) Andover Controls / i2 804 Receives data from Building 58 Ground Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (650 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) 1250 cfm, 16 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x16) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 400 cfm, 2.3 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 800 cfm, 5.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi PKFY-P12NHMU-E2 (Room G18) Air handler unit conditions air for data room on specified floor
Thermostat (x21) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 123ANA048-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-58-1 DX) Andover Controls / i2 804 Receives data from Building 58 First Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (650 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x16) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x3) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 1000 cfm, 6.8 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi PKFY-P12NHMU-E2 (Room 117) Air handler unit conditions air for data room on specified floor
Exhaust Fan (x1) Unknown / Unknown Exhausts air from single floor out a window
Thermostat (x21) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 123ANA048-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-58-2 DX) Andover Controls / i2 804 Receives data from Building 58 Second Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) 750 cfm, 10 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) AAF - Herman Nelson / AH (650 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x18) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi PKFY-P12NHMU-E2 (Room 215) Air handler unit conditions air for data room on specified floor
Exhaust Fan (x1) GREENHECK / BCF-106-4 Exhausts air from single floor out a window
Thermostat (x24) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 123ANA048-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-58-3 DX) Andover Controls / i2 804 Receives data from Building 58 Third Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) 750 cfm, 10 gpm UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Unit Ventilator (x1) AAF - Herman Nelson / AH (650 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x18) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 600 cfm, 3.4 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Air Handler Unit (x1) Mitsubishi PKFY-P12NHMU-E2 (Room 325) Air handler unit conditions air for data room on specified floor
Exhaust Fan (x1) GREENHECK / BCF-106-4 Exhausts air from single floor out a window
Thermostat (x22) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Exhaust Fan (x1) 880 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 1200 cfm Exhausts air from multiple floors up to and out of the roof
Exhaust Fan (x1) 200 cfm Exhausts air from multiple floors up to and out of the roof
Condensing Unit (x1) Mitsubishi / PUMY-P48NKMU1 Transfers heat from outside air by compressing refrigerant and pumping it though condenser coils
Roof57 Roof
58 Roof
Offices
Roof
58-2
58-3 CSP Offices
58-G Canteen
58-1 Medical Records Offices
57-3 CSP
57-2
Western State Hospital
BUILDING # SECTION BUILDING NAME / ADDRESS EQUIPMENT MFG. / MODEL (OR SELECTED SPECS) DESCRIPTION DESCRIPTION / NOTES
REPLACEMENT / ADDITION
PRIORITY
DDC
RECOMMENDATION
Condenser (x1) Bryant / 187ANA060-B Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-59-G DX) Andover Controls / i2 804 Receives data from Building 59 Ground Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (750 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x7) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x1) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x2) 400 cfm, 2.5 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhaust Fan (x2) Unknown / Unknown Exhausts air from single floor out a window
Thermostat (x10) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 123ANA036-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-59-1 DX) Andover Controls / i2 804 Receives data from Building 59 First Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (750/375 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to mix with Return air to service the floor
Fan Coil Units (x8) 200 cfm, 1.6 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Fan Coil Units (x4) 300 cfm, 2.0 gpm Fan Coil Unit operating using hot and cold water supply to heat or chill a space
Exhaust Fan (x1) Unknown / Unknown Exhausts air from single floor out a window
Thermostat (x14) Unknown / Unknown Allows for occupants to create a set point temperature for a space
Condenser (x1) Bryant / 123ANA036-A Outdoor Condensing Unit outfitted with Andover Controller for specificed floor
Temperature Control Panel (TCP-59-2 DX) Andover Controls / i2 804 Receives data from Building 59 Second Floor, sends out controls for dedicated condenser, and sends data back to TCP-57_1
Unit Ventilator (x1) AAF - Herman Nelson / AH (750/400 cfm, 6.0 gpm) UV located at outside wall to draw Outside Air to…