223102 Scope of Work.pdf

PDF 449 KB Posted

Attached to
223102 CBJTC Lodging Cart Storage Building
Solicitation number
ITB-09523
Issued by
Clay County, Florida

About this file

This document contains the Scope of Work for the CBJTC Lodging Cart Storage Building Project #223102, a state and local contract opportunity issued by the Florida Department of Military Affairs. The work consists of supplying and installing a 40' x 60' lightweight metal building with a vertical roof for lodging and golf cart storage, including a divider wall, three roll-up doors, and an electrical service panel to provide power for cart chargers, lighting, HVAC, and other requirements. The building must meet Florida Building Code, State Fire Marshal, and other local jurisdiction requirements. The estimated construction cost is $250,000. Contractors must obtain required permits and licenses, and the State Fire Marshal will provide the fire marshal permit. Bidders must submit qualification data and are subject to debarment and suspension regulations.

The pricing terms, set-asides, funding requirements, and other financial details are not explicitly stated in the provided information. However, the document indicates that the Construction Contractor is responsible for determining and including the cost of all required permits and fees in their bid proposal.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CBJTC Lodging Cart Storage Building

Project #223102

Scope of Work Base Bid

This work will consist of supplying and installing a 40” x 60” light weight metal building with a vertical roof for lodging and golfcart storage. Building is to have a divider wall from floor to ceiling to separate the cart storage from the supply storage with three roll-up doors. Building is to have electrical service panel to provide power for cart chargers, lighting, HVAC system and miscellaneous power requirements.

Scope of work to include but not be limited to the following:

• Provide 60' x 40'x12" enclosed pre-engineered metal structure with a vertical roof and 12' eaves. Per attached Building layout. (attached)

• Building legs are to be minimum 4' on center

• Building is to meet state minimum wind rating for its intended location.

• 24 Gauge minimum on building panels.

• Center divider wall is to be skinned on both sides.

• Manual Roll up doors are to be 10' x 10' and insulated.

• Provide 4" steel Sch 40 painted bollards with caps on both sides of each roll up doors.

• Provide 120 volt motorized continues duty exhaust fan on cart side of building.

• Provide 208/120 volt/200amp/3R/NF/2-Pole/SE Rated Service Disconnect mounted on a free-standing rack next to building. (Square D)

• Provide 208/120-volt, single phase 200-amp service, 36-circuit service rated Square D panel (or approved equal) with Main Breaker and all required breakers. (35 AIC)

• Provide underground service conduit and copper conductors from panel up to weather head on utility pole approximately 85' from building location. Underground conduit to be PVC and exterior conduit above ground to be GRC.

(sized per NEC).

• Provide and install electrical meter can on utility pole.

• Penetrations through the metal skin of the building shall be kept at a minimum and approved by CBJTC.

• Provide all required conduit, wire, boxes, electrical devices, LED light fixtures and misc.

material for a complete turnkey electrical system per attached drawing. All interior conduit above grade shall be EMT with steel set screw fittings and all interior device boxes to be 4" square with industrial covers. (Sized per NEC)

• Interior light fixtures are to be round UFO low bay style fixtures. 5000 kelvins in color.

Mount high as possible. Watt Stopper (or equal) wall and ceiling occupancy sensors.

CONTINUED ON NEXT PAGE

• Exterior light fixtures to be LED (Lithonia twsled pl50kmvoltpeddb m4 or equal)

• Provide wall mounted EM lighting Exit lights as required per code.

• Provide two 120-volt 20-amp cord reel and associated hardware to attach overhead incart bays. (Reel Craft Model H-7121 or equal)

• Every Receptacle inside the cart storage side of building shall be a dedicated circuit.

• Ceiling and all walls to be insulated with white laminated vinyl blanket insulation or equal

(Per ASTM E84 and UL723) Roof R-19 plus R-11 LS & Walls R-11 plus R-6.5 CI

• Install ½ plywood up to 4' from floor on all walls on the cart storage side of building. Install

1-1/2" 12 gauge angle metal support between up rights top and bottom for support of plywood attachment. Plywood joints are to have vertical support.

• Laundry storage side of the building to be conditioned (Mitsubishi MSZ- HM24NA/MSZ- MUZ-HM24NA or equal). Line set and condensate piping are to be run inside to the lowest point then turned outside at floor height through a PVC sleeve. Exterior line set to h a v e UV rated insulation and protective galv.metal cover from building to unit.

• Provide all required electrical grounding and bonding per NEC.

• Provide slopped concrete ramps at each door the entire width of the opening for cart and pedestrian entrance. Fiber concrete and doweled into existing slab.

• Contractor is to provide all required shop drawing, calculations, and necessary information to meet state and local code to obtain all necessary permits for this project.

• All material and installation shall be installed per state and local code.

• All material/equipment shall be submitted to CBJTC for approval before installed.