216007B TC SOB-ADDENDUM 02 29july2026 ISSUED 171-23058-rlo.pdf

PDF 8 MB Posted

Attached to
171/23058. RLO; Travere City S. O. B. - Bathroom Upgrades
Solicitation number
RFQ 171 260000000366 4
Issued by
Grand Traverse County, Michigan

About this file

This Addendum No. 2, issued July 29, 2026, provides clarifications, revisions, and rejections to the construction documents for the Traverse City State Office Building Bathroom & Plumbing Upgrade Project (File #171/23058.RLO) located at 701 S. Elmwood, Traverse City, Michigan. The addendum addresses nine items affecting plumbing, mechanical, masonry, and door specifications. Key clarifications include: new exhaust fans at main toilet rooms are designed above main chase areas with new openings per drawing A300; the new ELEVATE roof system installed in 2023 by Versatile Roofing Systems remains under warranty; Unit Masonry specification 04 20 00 applies only if repair/replacement/modification of existing masonry is required; wood door cuts shall be revised to plain sliced or quarter sliced walnut to closely match existing conditions with field coordination required; and a substitution request for Gerber plumbing faucets and fittings has been rejected in favor of originally specified products consistent with Department of Technology, Management & Budget inventory statewide. Additional technical revisions address door frame specifications, plumbing line routing for hot and cold water systems, mechanical system balancing requirements for new radiant ceiling panels and air outlets, fire penetration details for radiant panel supply and return lines, and the addition of fire dampers to exhaust air ductwork where it penetrates existing rated pipe chases.

The addendum requires bidders to acknowledge receipt on their bid proposal forms, with failure to do so potentially resulting in bid disqualification. All items are incorporated into the Construction Documents and shall be included in bid proposals. The document includes comprehensive architectural, plumbing, and mechanical drawing sheets (A101, P200-P207, M200-M207, M300-M302) detailing room finish schedules, door types and frames, overall plumbing and mechanical systems, floor-by-floor plans, ventilation riser diagrams, and equipment schedules. The project scope encompasses bathroom and plumbing upgrades across multiple levels of the state office building, with coordination required between plumbing, mechanical, and architectural trades for proper installation and field verification of existing conditions before demolition commences.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

803 cherry street manistee, mi 49660 ■ t: 231.723.4195 ■ thompson.kendra@sbcglobal.net ■ www.kendrathompson-architects.com kendra c.

THOMPSON

architects, p.c.

ADDENDUM NO. 2

TRAVERSE CITY STATE OFFICE BUILDING DATE: 7/29/2026

BATHROOM & PLUMBING UPGRADE PROJECT SOM: File #171/23085.RLO 701 S. ELMWOOD TRAVERSE CITY, MI KTA: Job #216007B

The following items are changes, additions, deletions and/or clarifications of the drawings and specifications, and shall be included in the Bid Proposal. All of items will be a part of the Construction Documents. Acknowledge receipt of this Addendum in the appropriate space on the Bid Proposal form. Failure to do so may result in disqualification of the bid.

Item No. 1: RFI-02: Exhaust Fans

Clarification: New exhaust fans at main toilet rooms are designed to be located above main chase area with new openings. Refer to drawing A300.

Clarification: New ELEVATE roof system is under warranty and was installed in 2023 by Versatile Roofing Systems (t: 231.834.9576 - Grant, MI).

Item No. 2: RFI-02: Specification 04 20 00 Unit Masonry

Clarification: Specification 04 20 00 Unit Masonry has been incorporated into the specifications should construction work require any repair/replacement/modification of existing masonry intended to remain as outlined with design intent.

Item No. 3: RFI-03: Wood Doors – Specification Section 08 14 16

Revise: Wood door cut to be revised to plain sliced or quarter sliced. Design intent it to closely match existing. Contractor to coordinate in field for Design Professional review.

Item No. 4: Substitution Request 01: Plumbing Faucets

Rejected: Substitution of plumbing faucets and fittings using Gerber products has been rejected.

Originally specified products shall be provided as these will be consistent with DTMB inventoried and installed products at various other facilities statewide.

Item No. 5: Door Schedule: Door Frames – Drawing Sheet A101

Clarification: Typical man door frames are to be wood frames as detailed. Refer to revised Door Schedule Sheet A101.

Item No. 6: Plumbing: Piping – Refer to Drawing Sheets P200, P201, 202, 204, 205, 206 and P207 – Overall

Plumbing Levels and North and South Wing Enlarged Bathroom Plans

Revise: Revise routing of 3/4inch hot water, cold water, and hot water recirculating lines shown for existing sinks. Separate risers are to extend from the ground level, up existing closets and tie into existing sinks.

803 cherry street manistee, mi 49660 ■ t: 231.723.4195 ■ thompson.kendra@sbcglobal.net ■ www.kendrathompson-architects.com

Addendum No. 2 TC SOB Bath & Plmb’g Project 7/29/2026

Item No. 7: Mechanical: System Balancing

Clarification: New hydronic hot water supply and return lines shall be balanced and adjusted for new radiant ceiling panels.

Clarification: New air outlet terminals and associated VAV boxes shall be balanced to cfm noted on drawings/diffusers. TAB contractor shall include recording and balancing new air outlets hot water supply and return.

Item No. 8: Mechanical: Radiant Ceiling Panel – Refer to Drawing Sheets M200, M203, M301 and M302

Mechanical Overall Ground Level – Alt #1 and Alt #2, Mechanical Details, and Radiant Ceiling Panel Schedule Clarification: Radiant ceiling panel has been located to accommodate lighting fixtures and ceiling grid layout.

Clarification: Radiant ceiling panel shall provide heating to the space as well as through exhaust air and shall comply with meeting set point as required.

Add: Add HILTI fire penetration detail for hot water supply and return lines penetrating fire-rated walls.

Revise: Revise radiant ceiling panel schedule to include Price Model RPM with revised BTU/h output capacity.

Item No. 9: Mechanical: Fire Dampers – Refer to Drawing Sheets M201, M202, M204, M205, M206, M207 and M300 Mechanical Floor Plans and Mechanical Ventilation Riser Diagram

Add: Add fire dampers to exhaust air ductwork where penetrating existing rated pipe chase.

END OF ADDENDUM NO. 2

Attachment: RFI #02-03 Substitution #01

Drawings Sheet A101, P200, P201, P202, P204, P205, P206, P207, M200, M201, M202, M203, M204, M205, M206, M207, M300, M301 and M302

2x4 WOOD NAILER

WOOD FRAME BY

DOOR TYPE - REFER

TO DOOR SCHEDULE

1x4 WOOD CASING - CUSTOM

5/8" GYP. BRD.

3-1/2" METAL STUDS @ 16" O.C.

DOOR MANUFACTURER

5/8" GYP. BRD.

31 2

5 8

5 8

SHIM

1x4 WOOD CASING - CUSTOM

WOOD DOOR STOP

2" 5

8"5 8"

2x4 WOOD NAILER

WOOD FRAME BY

DOOR TYPE - REFER

TO DOOR SCHEDULE

5/8" GYP. BRD.

3-1/2" METAL STUDS @ 16" O.C.

DOOR MANUFACTURER

5/8" GYP. BRD.

PROFILE TO MATCH EXIST'G.

WOOD DOOR STOP

SHIM

PROFILE TO MATCH EXIST'G.

PROFILE TO MATCH EXIST'G.

1x4 WOOD CASING - CUSTOM

(45 d. MITER TO JAMB CASING)

SOUND ATTENUATION BLANKET

SOUND ATTENUATION BLANKET

SEE

SCHEDULE

S

EE

S C H

ED

U

LE

BA

SEE

SCHED.

S

EE

S C H

ED

PREFAB ACCESS

PANEL W/INTREGAL

FRAME & SCREW

KEY LOCK

2"

SEE

2"

S

EE

S C

H

ED

U

LE

" SCHEDULE

TYPICAL MATERIAL/THRESHOLD TRANSITIONS

DOOR (WHERE APPLICABLE)

ADA METAL TRANSITION STRIP

SEALED CONCRETE

CARPET TO HARD TILE TRANSITION CARPET TO SEALED CONC. TRANSITION

HARD TILE TO HARD TILE TRANSITION

CARPET AS SPECIFIED

CENTERLINE OF DOOR LEAF

HARD TILE AS SPECIFIED

CENTERLINE OF DOOR LEAF

CARPET AS SPECIFIED

CENTERLINE OF DOOR LEAF DOOR (WHERE APPLICABLE)

ADA METAL TRANSITION STRIP

CERAMIC TILE AS SPECIFIED

DOOR (WHERE APPLICABLE)

FLUSH METAL TRANSITION STRIP

HARD TILE AS SPECIFIED

3 8

EQ. EQ.

EQ. EQ. EQ. EQ.

3 8 " 3 8

"5/8" GYP. BRD.

1/2" FURR'G.

EXIST'G. C.M.U.

EXIST'G. C.M.U.

TO REMAIN

ACCESS PANEL -

SEE DOOR SCHEDULE

1 8

" V

.I.

F.

1 8 " V

.I.

F.

FINISH C.M.U. @

OPN'G. SMOOTH

5/8" GYP. BRD.

1/2" FURR'G.

EXIST'G. C.M.U.

BY ACCESS DOOR

MANUFACTURER

ACCESS PANEL -

SEE DOOR SCHEDULE

8"6" V.I.F.

8" V.I.F.

FINISH C.M.U. @

OPN'G. SMOOTH

STEEL FRAME

5/8" GYP. BRD.

3-1/2" METAL STUDS @ 16" O.C.

EXPOSED CONSTRUCTION

31 2

5 8

METAL STUD

@ JAMB & SILL

ACCESS PANEL -

SEE DOOR SCHEDULE

EXPOSED CONSTR.

FRAMED METAL

STUD OPEN'G.

5/8" GYP. BRD.

3-1/2" METAL STUDS @ 16" O.C.

EXPOSED CONSTRUCTION

2" 5

8"

EXPOSED CONSTR.

FRAMED METAL

STUD OPEN'G.

BY ACCESS DOOR

MANUFACTURER

ACCESS PANEL -

SEE DOOR SCHEDULE

STEEL FRAME DR. SCHEDULES

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/23058.RLO

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

A101

DRAWING TITLE

KCT PROJECT NO.DRAWN

KCT

REVIEWED

KCT

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

ROOM FINISH &

1 FACILITY ASSESSMENT/SD CONCEPTS 6/6/2025

2 SD REV. #01 6/25/2025

3 SD REV. #02 7/16/2025

4 DD 7/30/2025

5 CD - 50% REVIEW SET: VOID 8/27/2025

6 DESIGN DEVELOPMENT SET 9/24/2025

7 CD - 50% REVIEW SET 4/29/2026

8 CD - 90% REVIEW SET 6/5/2026

9 BCC PLAN REVIEW SET 6/17/2026

10 BID SET 6/26/2026

11 ADDENDUM NO. 2 7/29/2026

11 ADDENDUM NO. 1 7/22/2026

JUNE 2025

KT-216007C

DOOR TYPES:

SCALE: 3" = 1'-0"

JAMB1

A101 SCALE: 3" = 1'-0"

HEAD2

A101

FRAME TYPES:

FRAME

TYPEMAT. GLASS

DOOR

LOCATIOND

O O

R N

O

DOOR SCHEDULE

TYPE

DETAIL

MAT. GLASS HEAD JAMB SILL HARDW. RATING REMARKS

A - WDWD

B HMHM

B - HMHM

- WDWD -

A - 1 WDWD -

B - HMHM -

B

SIZE

A - 1 WDWD -

A - 1 WDWD

FIRE

LO

C A

TI

O N

LE

V

EL

-G

3'-0" x 6'-8" x 1 3/4"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

18" x 32"

24" x 24"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

A 1 -A

WDWD

- WDWD

A

-SMOKE-

2/A101 1/A101

ROOM FINISH SCHEDULE

026 STORAGE

UTR

STORAGE

STORAGE

OFFICE

CORRIDOR

STAFF SHOWER RM

CORRIDOR139

R O

O M

N O

NAME

STAIR #1S-1

ROOM

EXIST'G. TO REMAIN @4" VINYL @ RENOV.

BASE MT'L

WALL FLOOR

MT'L MT'L

WALL CL'G

REMARKS

UTR

UTR

UTR

WORK AREA

UTR

148 STORAGE

GYP. BOARD, PAINT

150 JANITOR CLOSET

6" H.T., COVED

EXIST'G. CONSTR. @

LO

C A

TI

O N

EXIST'G. EXPOSED,

HT-1

SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

EXIST'G. TERRAZZO

SCOPE IS LIMITED TO INFILL @ EXIST'G. TOIL RM DOOR ONLY

LE

V

EL

-1

LE

V

EL

-2

LE

V

EL

-3

152 WORK AREA

LE

V

EL

-4

026A STORAGE #026

025A UTR #025

STAFF SHOWER #008008A

145A

151A

143A UTR #143

UTR #145

WORK AREA #151

151B

142A

152A

140A UTR #140

UTR #142

152B

18" x 32"

24" x 24"

LE

V

EL

-1

LE

V

EL

-2

LE

V

EL

-3

330A OFFICE#330

LE

V

EL

-4

LE

V

EL

-G

EXIST'G. TERRAZZO EXIST'G. TO REMAIN

PAINT

4" VINYL @ NEW WALL

AREA ONLY

EXIST'G. EXPOSED/G.B.

@ NEW WALL ONLY, PAINT SCOPE IS LIMITED TO NEW G.B. WALL/DOOR & PAINTING OF ENTIRE AREA

EXIST'G. GLAZED CMU

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN

EXIST'G. VINYL W.B.

TO REMAIN

EXIST'G. CARPET TILES

TO REMAIN

2'X2' ACT-1/GYP. BD.

BLKHD, PAINT6" H.T., COVED HT-1

2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

027 STAFF HALL CPT-1 2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

4" VINYL - MATCH

EXIST'G, PAINT GYP. BOARD, PAINT

STAFF BREAK AREA035 GYP. BOARD, PAINT EXIST'G. 2'X2' ACT

TO REMAIN

4" VINYL @ RENOV.

AREA ONLY SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

4" WOOD - MATCH

EXIST'G, PAINT

CPT-1 @ RENOV. AREA;

EXIST'G CPT OTHERWISE

LOBBY100

4" WOOD - MATCH

EXIST'G, PAINT

GYP. BD. BLKHD, PAINT;

EXIST'G. ACT TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

CPT-1 GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1

2'X2' ACT-1

2'X2' ACT-1

CPT-1 GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET/OFFICE

EA

S T

W

IN

G N O

R

TH

W

IN

G

MEETING ROOM122

EXIST'G. TO REMAIN @4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

CORRIDOR138

6" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

S O

U

TH

W

IN

G

248 STORAGE

250 JANITOR CLOSET

LOBBY200

4" WOOD - MATCH

EXIST'G, PAINT

GYP. BD. BLKHD, PAINT;

EXIST'G. ACT TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET/OFFICE

EA

S T

W

IN

G

UTR

STORAGE

STORAGE

OFFICE

CORRIDOR239

EXIST'G. TO REMAIN @4" VINYL @ RENOV.

UTR

UTR

WORK AREA

UTR

EXIST'G. CONSTR. @

252 WORK AREA

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1

2'X2' ACT-1

2'X2' ACT-1

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

N O

R

TH

W

IN

G

OFFICE222

EXIST'G. TO REMAIN @4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

CORRIDOR238

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

S O

U

TH

W

IN

G

348 STORAGE

350 JANITOR CLOSET

LOBBY300

4" WOOD - MATCH

EXIST'G, PAINT

CPT-1 @ RENOV. AREA;

EXIST'G CPT OTHERWISE

GYP. BD. BLKHD, PAINT;

EXIST'G. ACT TO REMAIN

SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET/OFFICE EA

S T

W

IN

G

OFFICE330

GYP. BD/PLAST.,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT EXIST'G. CPT TO REMAIN

RECONFIGURE 2'X2' ACT CEIL'G NEAR DOOR #334A TO MATCH EXIST'G.;

OFFICE331

PAINT ENTIRE EXIST'G. EAST & NORTH WALL AREAS

4" WOOD - MATCH

EXIST'G, PAINT

EXIST'G. CARPET TILES

TO REMAIN

EXIST'G. CARPET TILES

TO REMAIN

GYP. BOARD @ RENOV.

WALLS, PAINT

EXIST'G. ACT TO

REMAIN, PAINT SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

MEETING ROOM334

4" WOOD - MATCH

EXIST'G, PAINT

GYP. BOARD @ RENOV.

AREA, PAINT SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.GYP. BD. BLKHD, PAINT;

EXIST'G. ACT TO REMAIN

UTR

STORAGE

STORAGE

OFFICE

CORRIDOR339

EXIST'G. TO REMAIN @4" VINYL @ RENOV.

UTR

UTR

WORK AREA

UTR

EXIST'G. CONSTR. @

352 WORK AREA

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1

2'X2' ACT-1

2'X2' ACT-1

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

N O

R

TH

W

IN

G

OFFICE322

EXIST'G. TO REMAIN @4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

CORRIDOR338

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

S O

U

TH

W

IN

G

LOBBY400

4" WOOD @ WORK

AREA-MATCH EXIST'G.

EXIST'G. CARPET

TO REMAIN

REALIGN EXIST'G. ACT

@ WORK AREA

GYP. BD. @ WORK AREA,

PAINT - MATCH EXIST'G.

EA

S T

UTR

STORAGE

STORAGE

OFFICE

CORRIDOR439

EXIST'G. TO REMAIN @4" VINYL @ RENOV.

UTR

UTR

WORK AREA

UTR

EXIST'G. CONSTR. @

452 WORK AREA

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1/GYP. BD.

BLKHD, PAINT

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

6" H.T., COVED HT-1

6" H.T., COVED HT-1 2'X2' ACT-1

2'X2' ACT-1

2'X2' ACT-1

GYP. BD. BLKHD,

PAINT

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINT

GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

N O

R

TH

W

IN

G

MEETING422

EXIST'G. TO REMAIN @4" VINYL @ RENOV. EXIST'G. CONSTR. @ GYP. BD/PLAST @ RENOV.

CLOS. WALLS, PAINT RENOV. CLOS., PAINTCLOSET RENOV. CLOSET SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

CORRIDOR438

4" WOOD - MATCH

EXIST'G, PAINT GYP. BD/PLAST., PAINTEXIST'G. CARPET TILES

TO REMAIN

EXIST'G. 2'X2' ACT

TO REMAIN SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

S O

U

TH

W

IN

G

SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.

- 1 -

- - SMOKE

SMOKE

SMOKE

HMHM -- 5- - SMOKE

SMOKE

SMOKE-

SMOKE

SMOKE

B HMHM

B - HMHM

- WDWD -

A - 1 WDWD -

B - HMHM -

B

A - 1 WDWD -

A - 1 WDWD

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

18" x 32"

24" x 24"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

A

245A

251A

243A UTR #243

UTR #245

251B

242A

252A

240A UTR #240

UTR #242

252B

18" x 32"

24" x 24"

- - SMOKE

SMOKE

SMOKE

HMHM -- 5- - SMOKE

SMOKE

SMOKE-

SMOKE

SMOKE

A

HMHM

B - HMHM

- WDWD -

A - 1 WDWD -

B - HMHM -

B

A - 1 WDWD - -

A - 1 WDWD -

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

18" x 32"

24" x 24"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

A

345A

351A

343A UTR #343

UTR #345

351B

342A

352A

340A UTR #340

UTR #342

352B

18" x 32"

24" x 24"

- - SMOKE

SMOKE

SMOKE

HMHM -- 5- - SMOKE

SMOKE

SMOKE-

SMOKE

SMOKE

B -3'-0" x 6'-8" x 1 3/4" 1 WDWD - 4348A STORAGE #348

- WDWD - -3'-0" x 6'-8" x 1 3/4" A 21 SMOKE

B HMHM

B - HMHM

- WDWD -

A - 1 WDWD -

B - HMHM -

B

A - 1 WDWD - -

A - 1 WDWD -

3'-0" x 7'-0" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

18" x 32"

24" x 24"

3'-0" x 6'-8" x 1 3/4"

3'-0" x 7'-0" x 1 3/4"

A

445A

451A

443A UTR #443

UTR #445

451B

442A

452A

440A UTR #440

UTR#442

452B

18" x 32"

24" x 24"

- - SMOKE

SMOKE

SMOKE

HMHM -- 5- - SMOKE

SMOKE

SMOKE-

SMOKE

SMOKE

4/A101 3/A101

CPT-1

CPT-1

CPT-1

CPT-1

CPT-1

CPT-1

WORK AREA #151

WORK AREA #152

WORK AREA #152

WORK AREA #251

WORK AREA #251

WORK AREA #252

WORK AREA #252

WORK AREA #351

WORK AREA #351

WORK AREA #352

WORK AREA #352

WORK AREA #451

WORK AREA #451

WORK AREA #452

WORK AREA #452

GYP. BOARD, PAINT

GYP. BOARD, PAINT SOLID SURF. WINDOW SILL

GYP. BOARD, PAINTCPT-1 @ RENOV. AREA;

EXIST'G CPT OTHERWISE

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

GYP. BOARD, PAINT

GYP. BOARD, PAINT

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

CPT-1 @ RENOV. AREA;

EXIST'G CPT OTHERWISE GYP. BOARD, PAINT

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

GYP. BOARD, PAINT

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

SOLID SURF. WINDOW SILL

CPT-1

CPT-1

EXIST'G. EXIST'G. EXIST'G.EXIST'G.

GYP. BOARD, PAINT

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

CPT-1

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

EXIST'G. EXIST'G. SCOPE IS LIMITED TO WORK AREA ONLY; PATCH/REPAIR TO MATCH EXIST'G.EXIST'G. TO REMAIN-

CONC. PATCH @ DEMO.

EXIST'G. TO REMAIN-

PATCH @ DEMO AREA

EXIST'G. TO REMAIN,

REWORK AS REQ'D.

PAINT ENTIRE EXIST'G. OFFICE NORTH WALL

PAINT ENTIRE EXIST'G. OFFICE NORTH WALL

EXIST'G. EXIST'G. EXIST'G. EXIST'G.

EXIST'G. EXIST'G. EXIST'G. EXIST'G.

EXIST'G. EXIST'G. EXIST'G. EXIST'G.

SCALE: 3" = 1'-0"

JAMB3

A101 SCALE: 3" = 1'-0"

HEAD4

A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

4/A101 3/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

2/A101 1/A101

4/A101 3/A101

4/A101 3/A101

4/A101 3/A101

4/A101 3/A101

4/A101 3/A101

4/A101 3/A101

2/A101 1/A101

SCALE: 3" = 1'-0"

JAMB5

A101 SCALE: 3" = 1'-0"

HEAD6

A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

6/A101 5/A101

1 2 3 4 5 6

7 8 9 10 11

12 13 14 15 16 17

D

E

F

G

C

B

A

EXT'G

SAN

EXT'G

SAN

EXT'G

SAN

EXT'G HWS

EXT'G HWR

EXT'G F.P.

EX

T'

G F

.P

TUNNEL

ELEV.

EWH-1

EWH-2

EX

T'

G

" C W

3" CW3" CW

2" C

W

3" SAN

4" S

AN

1- 1/

2" C

W

3/4" HWR3/4" HWR

C.O.

W

W

C.O.

C.O.

C.O.

W

S

S

S 2

S

EXT'G CW, HW UP

TO REMAIN

1- 1/

2" C

W

1-1/2" CW 1-1/2" CW

2" CW 2" CW

4" SAN 4" SAN

1- 1/

4" H

W

4" SAN4" SAN

4" S

AN

4" SAN

C.O.

C.O. 4" SAN 4" SAN 4" SAN6" SAN

4" S

AN

4"

S

AN

2" C

W

2" C

W

2" CW2" CW 2" CW

1-1/4" HW1-1/4" HW

2" H

W

3" CW2" CW

RP-1

2" HW2" HW

3/ 4"

H W

R

3/4" HWR 3/4" HWR

1-1/4" HW

1- 1/

4" H

W 3/

4" H

W R

2" H

W

1-1/4" HW

3/ 4"

H W

R

3/4" HWR 3/4" HWR

1-1/4" HW1-1/4" HW

6" SAN

8" WYE WHERE ALL

SANITARY LINES

MEET. TIE NEW 8"

SAN TO EXT'G 8" SAN

TIE NEW 3" CW TO NEW 3"

SHUT-OFF VALVE. TIE TO

EXT'G 3" CW LINE IN TUNNEL

EXT'G HWS,

HWR, & F.P.

RISERS TO

REMAIN

2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR

4" SAN RISER

3" V UP

3" SAN UP TO FD

(V.I.F.)

EXT'G ST DOWN BELOW

GRADE (V.I.F.) TO REMAIN

4" SAN RISER

3" V UP

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR

2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

4" SAN FROM ABOVE

3" VENT UP4" SAN FROM ABOVE

3" VENT UP

1" CW UP

1" HW UP

3/4" HWR

3" SAN RISER

3" V UP

TIE EXT'G SAN

TO NEW SAN TIE EXT'G

CW, HW TO

NEW MAINS

TIE NEW SAN

TO EXT'G SAN

(VERIFY SIZE

IN FIELD)

TIE NEW

CW/HW TO

UPPER

FIXTURES IF

ALT #1 IS

NOT

APPROVED

TIE NEW SAN

TO EXT'G SAN

(VERIFY SIZE

IN FIELD)

TIE NEW 4" SAN TO EXT'G

SAN (VERIFY SIZE IN FIELD)

THE CONTRACTOR SHALL VERIFY THE

SANITARY, COLD WATER, AND HOT

WATER SERVICES TO THE GROUND

FLOOR IN THIS AREA. TIE THE EXT'G

FIXTURES TO THE NEW SANITARY, COLD

WATER, AND HOT WATER SERVICES.

VERIFICATION IN FIELD IS REQUIRED.

1" CW

1" HW

3/4" HWR

2-1/2" CW

2-1/2" HW

TO WH'S

W

W

1 2 3 4 5 6

7 8 9 10 11

12 13 14 15 16 17

D

E

F

G

C

B

A

WC-1

S-1LAV-1

WC-1

LAV-1

SH-1

18A

U.T.R. U.T.R.

16 15

495028293031323334

37 36

43 1

MECHANICAL ROOM

MAINTENANCE SHOP

S-3

J.C.

TELE

STOR

STOR STOR

STAIR #1

S-2 20

J.C.

CONFERENCE

ELEV.

EXIST'G.EXIST'G.SHWR.

EXIST'G.

STOR.

NEW

U.T.R.

STAFF

RENOV'D

EXIST'G.

NEW

NEW

EXT'G STORM RISER

TO REMAIN TYP.

(VERIFY IN FIELD)

W

W

W

S1

S

S

S

S

EXT'G ST RISER TO REMAIN

4" SAN DOWN

4" SAN DOWN

EXT'G ST RISER TO REMAIN

CW, HW, SAN FED

FROM BELOW

(TYP. OF ALT #2)

HWR & HW DOWN

TO EWH'S

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR UP

4" SAN RISER

3" V UP

2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR UP

4" SAN RISER

3" V UP

1" CW UP

1" HW UP

3/4" HWR DOWN

SERVICES FROM

TUNNEL BELOW

SERVICES FROM

TUNNEL BELOW

SERVICES FROM

TUNNEL BELOW

TIE THE EXT'G FIXTURES TO THE NEW SANITARY,

COLD WATER, AND HOT WATER SERVICES IN

TUNNEL. VERIFICATION IN FIELD IS REQUIRED.

IF ALT #1 IS ACCEPTED, NEW FIXTURES WILL BE

REQUIRED, SEE FIXTURE SCHEDULE FOR MORE

INFORMATION.

VERIFICATION IN FIELD IS REQUIRED.

RE-LOCATED EWH

3" SAN IN CEILING

ROUTE TO RISER S-1

3" SAN IN CEILING

ROUTE TO RISER S-1

INVESTIGATION IS

REQUIRED TO

DETERMINE IF THIS

SANITARY ROUTE IS

ACCEPTABLE AND

CONSTRUCTIBLE

INVESTIGATION IS

REQUIRED TO

DETERMINE IF THIS

SANITARY ROUTE IS

ACCEPTABLE AND

CONSTRUCTIBLE

3" V UP

3" V UP

W

W

CONTRACTOR TO VERIFY

EXT'G SERVICES IN THIS

LOCATION AND INCLUDE

NEW CW, HW, SAN, AND

VENTING FOR PLUMBING

FIXTURES

3/4" HW/CW/

HWR UP

A2A2

3/4" HW/CW/HWR FROM

BELOW TIE NEW HW/CW TO

EXT'G SINK

A2A2

P200

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

PLUMBING

OVERALL TUNNEL &

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL TUNNEL LEVEL - ALT #1 & ALT #2 SHOWN

N JUNE 2026

KT-216007C

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL GROUND LEVEL - ALT #1 & ALT #2 SHOWN

N

GROUND LEVELS

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

12 13 14 15 16 17

D

E

F

G

C

B

A

WC-2

LAV-1

EWC-1

LAV-1

WC-2 WC-2

LAV-1 LAV-1

WC-2

J.C.

LOBBY

100A

STOR.

CONF.

CONF.

I.T.

STAFF

STAIR

S-2

ELEVATOR

J.C.

LOBBY

100A

STOR.

CONF.

CONF.

I.T.

STAFF

STAIR

S-2

ELEVATOR

119 115

127125

111 109

107 105 103 101

129 137

100B

STAFF

U.T.R.

135 134

116104

136 128

106 108

126 124

U.T.R.

114 118

UTRUTR

100A

NEW NEW

EXIST'G. EXIST'G.

ELEV.

UTR UTR

NEWNEW

AREA

NEW

WORK

AREA

NEW

WORK

144141

EXT'G STORM RISER

TO REMAIN (VERIFY

IN FIELD)

W2

W xLAV xWC xLAVxWC

W

S

S3

S

S

S

EXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP EXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

1-1/4" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

1" CW

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

3" SAN RISER

3" V UP

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

1-1/4" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3/4" CW UP

1" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

TIE NEW CW, HW, SAN,

AND VENTING TO EXT'G

SINK AS WELL

TIE NEW CW, HW, SAN,

AND VENTINT TO EXT'G

SINK AS WELL

3" SAN DOWN

3" V UP

3" SAN DOWN

W

W

3/4" HW/CW/

HWR UP

A2A2

3/4" HW/CW/HWR FROM BELOW

TIE NEW HW/CW TO EXT'G SINK

A2A2

1 2 3 4 5 6

7 8 9 10 11

12 13 14 15 16 17

D

E

F

G

C

B

A

TRAVERSE CITY

WC-2

LAV-1

EWC-1

LAV-1

WC-2 WC-2

LAV-1 LAV-1

WC-2

217219

215 209211

225 227

229 237

233 235 234

228236

206 208

226 224

210 212

214 216 218

UTRUTR

NEW NEW 241

200A

U.T.R. U.T.R.

EXIST'G. EXIST'G.

UTR

NEW

UTR

NEW244

AREA

NEW

WORK

AREA

NEW

WORK

OFFICE

OFFICE

MEETING RM.

MEETING RM.

LOBBY

200A

STOR.

I.T.

J.C.

STAIR

S-2

ELEVATOR

EXT'G STORM RISER

TO REMAIN (VERIFY

IN FIELD)

W

W xLAV xWC xLAV xWC

W

S

S3

S

S

S

3" SANEXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP EXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

1" CW UP

3/4" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

1" CW

1-1/2" CW UP

1-1/4" HW UP

3/4" HWR DOWN

3" V UP

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

1" CW UP

3/4" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

3/4" CW UP

3/4" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

TIE NEW CW, HW, SAN,

AND VENTING TO EXT'G

SINK AS WELL

3" SAN DOWN

3" V UP

3" SAN DOWN

W

W

3/4" HW/CW/

HWR UP

A2A2

3/4" HW/CW/HWR FROM BELOW

TIE TO EXT'G SINK

A2A2

TIE NEW CW, HW, SAN,

AND VENTINT TO EXT'G

SINK AS WELL

P201

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL FLOOR LEVEL - 1

N JUNE 2026

KT-216007C

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL FLOOR LEVEL - 2

N

PLUMBING

OVERALL FLOOR

LEVELS 1 & 2

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195

12 13 14 15 16 17

D

E

F

G

C

B

A

TRAVERSE CITY

WC-2

LAV-1

EWC-1

LAV-1

WC-2 WC-2

LAV-1 LAV-1

WC-2

317319 315

311 309 307

305 303

300 304

336 328 326

306 308 310

322324

314312 316

318301 302

UTRUTR

NEW NEW

MTG. ROOM

EXIST'G.

STOR.

UTR

NEW

UTR

NEW

AREA

NEW

WORK

ROOM

LOBBY

300A

I.T.

OFFICE

WELLNESS

ROOM

MEETING

UTR

J.C.

AREA

NEW

WORK

STAIR

S-2

ELEVATOR

STO.

EXT'G STORM RISER

TO REMAIN (VERIFY

IN FIELD)

W2

W xLAV xWC

U.T.R.

EXIST'G.

xLAV xWC

W

W

S

S

S

S

S

EXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP EXT'G ST RISER TO REMAIN

4" SAN DOWN

3" V UP

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

3" SAN RISER

3" V UP

1" CW

1" CW FROM BELOW

3/4" HW FROM BELOW

3/4" HWR DOWN

1-1/4" CW UP

1" HW UP

3/4" HWR DOWN

3" V UP

1-1/4" CW UP

1" HW UP

3/4" HWR DOWN

3" V UP

TIE NEW PLM'G

SERVICES TO EXT'G

U.T.R. FIXTURES

1" CW FROM BELOW

3/4" HW FROM BELOW

3/4" HWR DOWN

3" SAN RISER

3" V UP

CW UP TO EWC-1,

2" SAN FROM EWC-1 ABOVE

ROUTE 2" SAN IN

CEILING OF THIRD

FLOOR TO RISER

3/4" CW FROM BELOW

3/4" HW FROM BELOW

3/4" HWR DOWN

3" SAN RISER

3" V UP

3" SAN DOWN

3" V UP

3" SAN DOWN

3" V UP

W

W

3/4" HW/CW.

HWR UP

A2A2

3/4" HW/CW/HWR FROM BELOW

A2A2

1 2 3 4 5 6

7 8 9 10 11

12 13 14 15 16 17

D

E

F

G

C

B

A

TRAVERSE CITY

WC-2

LAV-1 LAV-1

WC-2 WC-2

LAV-1 LAV-1

WC-2

419 415417 405407409

MTG. RM. 427

402400401403

437429

410408406404

426428 424

414412 416

MTG. RM.

UTR UTR STOR.

NEW NEW

STOR. UTR

NEW

UTR

NEW

AREA

NEW

WORK

LOBBY

400A

MECH.

OFFICE

STAIR

S-2

ELEVATOR

AREA

NEW

WORK

EWC-1

1-1/2" V

W

S

S

S

S

S

EXT'G ST RISER TO REMAIN

3" SAN DOWN

3" VTR EXT'G ST RISER TO REMAIN

3" SAN DOWN

3" VTR

1-1/4" CW FROM BELOW

1" HW HW FROM BELOW

3/4" HWR DOWN

3" V UP

CW FROM BELOW

1-1/4" CW FROM BELOW

1" HW HW FROM BELOW

3/4" HWR DOWN

3" V UP

NEW 3" VENT FLOOR

PENETRATION. NEW

3" VTR PENETRATION

NEW 3" VENT FLOOR

PENETRATION. NEW

3" VTR PENETRATION

NEW 3" VENT FLOOR PENETRATION.

NEW 3" VTR PENETRATION.

VERIFY MECH ROOM FLOOR PENETRATION IN

FIELD AS THIS WILL NEED TO BE RE-ROUTED

SO AS TO NO BE IN THE MIDDLE OF THE ROOM

3" SAN DOWN

3" VTR

SEE ENLARGED FLOOR PLAN

FOR CW, HW ROUTING

3" SAN DOWN

3" VTR

SEE ENLARGED FLOOR PLAN

FOR CW, HW ROUTING

W

W

3/4" HW/CW/HWR FROM BELOW

TIE NEW HW/CW TO EXT'G SINK

A2A2

A2A2

3/4" HW/CW/HWR FROM

BELOW TIE NEW HW/CW TO

EXT'G SINK

P202

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL FLOOR LEVEL - 3

N JUNE 2026

KT-216007C

SCALE: 1/8" = 1'-0"

PLUMBING OVERALL FLOOR LEVEL - 4

N

PLUMBING

OVERALL FLOOR

LEVELS 3 & 4

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 xLAV xWC's xSS

PD-2

PD-2

PD-3

PD-3

xWC xLAV xUR xWC xLAV xSS

PD-2

PD-2

PD-2

PD-3

PD-3

OFFICE

CORRIDOR

UTR

UTR

STORAGE

141 STAFF

AREA

WORK

WC-2

LAV-1 LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

3" VENT UP

W

3/4" HW/CW/

HWR UP

A2A2

UTR

OFFICE

UTR

STORAGE

MTG.

AREA

WORK

CORRIDOR

WC-2

LAV-1

LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S

3" VENT UP

SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

W

3/4" HW/CW/HWR FROM BELOW

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

A2A2

EWC-1

J.C.

LOBBY

100A

STOR.

I.T.

STAFF

STAIR

S-2

ELEVATOR

J.C.

LOBBY

100A

STOR.

I.T.

STAFF

STAIR

S-2

ELEVATOR

129 137

STAFF

136 128

100A

EXIST'G. EXIST'G.

ELEV.

W

S

3/4" CW UP

1" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

TIE NEW CW, HW, SAN,

AND VENTING TO EXT'G

SINK AS WELL

xSS

PD-3

EXT'G CW, HW, SAN, VENTING

TO BE DEMO'D AND REPLACED

FOR xSS AND xS. TIE NEW CW, HW, SAN, AND VENTING

SERVICES TO xSS AND xS.

xS

TUNNEL SPACE:

1. DEMO AND REMOVE THE FOLLOWING:

1.1. EXT'G SANITARY LINES BACK TO THE EXT'G MAIN BUILDING SEWER OUTLET.

1.2. EXT'G VENTING LINES THROUGHOUT THE ENTIRE TUNNEL SPACE.

1.3. EXT'G COLD WATER LINES BACK TO THE EXISTING SHUT-OFF VALVE AS SHOWN ON

THE DRAWING. DEMO THE EXISTING SHUT-OFF VALVE AND PREPARE TO INSTALL

NEW 3" BALL VALVE.

1.4. EXT'G HOT WATER LINE BACK TO THE EXISTING WATER HEATERS. DEMO AND

REMOVE EXT'G WATER HEATERS.

2. EXISTING ITEMS THAT SHALL REMAIN: EXISTING STORM; EXISTING FIRE PROTECTION.

BATHROOM GROUPS & JANITOR CLOSET:

DEMO AND REMOVE EXISTING PLUMBING FIXTURES ALONG WITH ASSOCIATED HOT WATER,

COLD WATER LINES, VENTING, WALL SUPPORTS, ETC. SANITARY SHALL BE DEMO'D AND

CAPPED SO AS TO REMAIN FLUSH WITH FINISHED FLOOR.

CHASES:

1. DEMO AND REMOVE THE FOLLOWING EXISTING RISERS FROM TOP MOST FLOOR TO

TUNNEL SPACE BELOW: SANITARY, COLD WATER, HOT WATER, AND VENTING.

2. EXISTING STORM SHALL REMAIN; OTHER EXISTING RISERS NOT MENTIONED HERE BUT

FOUND IN CHASE TO REMAIN. CONTRACTOR SHALL VERIFY WITH THE ENGINEER IF ANY

QUESTIONS OR CONCERNS ARE FOUND BEFORE DEMOLITION WORK STARTS.

HOSE BIBS:

1. DEMO AND REMOVE ALL EXISTING COLD WATER PIPING LEADING FROM THE EXISTING

HOSE BIB BACK. INVESTIGATIVE DEMO WILL HAVE TO OCCUR; THE CONTRACTOR WILL

HAVE TO VERIFY IN FIELD WHERE THE COLD WATER LINE IS COMING FROM (TYP. FOR

ALL HOSE BIBS). DEMO TO THIS POINT SHOWN ON PLANS AND PREPARE TO TIE IN NEW

3/4" CW HERE (TYP. FOR ALL HOSE BIBS)

PD-1

PD-2

PD-3

PD-4

PLMG DEMOLITION KEYED NOTES PD-#

THE CONTRACTOR SHALL VERIFY ALL EXISTING SERVICES: SANITARY LINES, COLD/HOT WATER LINES, STORM LINES, AND VENTING PRIOR TO COMMENCING DEMOLITION WORK. THIS INCLUDES VERIFYING IN THE EXISTING TUNNEL, CEILING, AND CHASE SPACES. ANY QUESTIONS OR CONCERNS

REGARDING CONSTRUCTABILITY OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT, OWNER, AND/OR ENGINEER (IN WRITING) BEFORE BIDDING THE PROJECT.

P204

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

JUNE 2026

KT-216007C

PLUMBING

FIRST LEVEL - NORTH

SOUTH & EAST WINGS

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

SCALE: 1/4" = 1'-0"

FIRST LEVEL NORTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

FIRST FLOOR NORTH WING - FLOOR PLAN

SCALE: 1/4" = 1'-0"

FIRST LEVEL SOUTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

FIRST LEVEL SOUTH WING - FLOOR PLAN

PLUMBINGPLUMBING

PLUMBINGPLUMBING

SCALE: 1/8" = 1'-0"

FIRST LEVEL EAST WING - FLOOR PLAN

PLUMBING

SCALE: 1/4" = 1'-0"

FIRST LEVEL EAST WING - DEMO PLAN

PLUMBING

NO SCALE

KEY PLAN

xSS xTS

PD-2

PD-2

PD-2

PD-3

PD-3

xHS xUR xWC xLAV xSS

PD-2

PD-2

PD-2

PD-3

PD-3

OFFICE

UTR

UTR

243 STOR.

OFFICE

AREA

WORK

CORRIDOR

WC-2

LAV-1 LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

3" V UP

W

3/4" HW/CW/

HWR UP

A2A2

UTR

UTR

OFFICE

CORRIDOR

OFFICE

STOR.

AREA

WORK

WC-2

LAV-1

LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S

3" VENT UP

xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3" SAN DOWN

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

W

3/4" HW/CW/HWR FROM BELOW

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

A2A2

EWC-1

229 237

200A

EXIST'G.

OFFICE

MEETING RM.

MEETING RM.

LOBBY

200A

STOR.

I.T.

J.C.

STAIR

S-2

ELEVATOR

W

S

3" SAN

3/4" CW UP

3/4" HW UP

3/4" HWR DOWN

3" SAN RISER

3" V UP

TIE NEW CW, HW, SAN,

AND VENTING TO EXT'G

SINK AS WELL

xSS

PD-3

EXT'G CW, HW, SAN, VENTING TO

BE DEMO'D AND REPLACED FOR

xSS. TIE NEW CW, HW, SAN, AND VENTING SERVICES TO xSS.

TUNNEL SPACE:

1. DEMO AND REMOVE THE FOLLOWING:

1.1. EXT'G SANITARY LINES BACK TO THE EXT'G MAIN BUILDING SEWER OUTLET.

1.2. EXT'G VENTING LINES THROUGHOUT THE ENTIRE TUNNEL SPACE.

1.3. EXT'G COLD WATER LINES BACK TO THE EXISTING SHUT-OFF VALVE AS SHOWN ON

THE DRAWING. DEMO THE EXISTING SHUT-OFF VALVE AND PREPARE TO INSTALL

NEW 3" BALL VALVE.

1.4. EXT'G HOT WATER LINE BACK TO THE EXISTING WATER HEATERS. DEMO AND

REMOVE EXT'G WATER HEATERS.

2. EXISTING ITEMS THAT SHALL REMAIN: EXISTING STORM; EXISTING FIRE PROTECTION.

BATHROOM GROUPS & JANITOR CLOSET:

DEMO AND REMOVE EXISTING PLUMBING FIXTURES ALONG WITH ASSOCIATED HOT WATER,

COLD WATER LINES, VENTING, WALL SUPPORTS, ETC. SANITARY SHALL BE DEMO'D AND

CAPPED SO AS TO REMAIN FLUSH WITH FINISHED FLOOR.

CHASES:

1. DEMO AND REMOVE THE FOLLOWING EXISTING RISERS FROM TOP MOST FLOOR TO

TUNNEL SPACE BELOW: SANITARY, COLD WATER, HOT WATER, AND VENTING.

2. EXISTING STORM SHALL REMAIN; OTHER EXISTING RISERS NOT MENTIONED HERE BUT

FOUND IN CHASE TO REMAIN. CONTRACTOR SHALL VERIFY WITH THE ENGINEER IF ANY

QUESTIONS OR CONCERNS ARE FOUND BEFORE DEMOLITION WORK STARTS.

HOSE BIBS:

1. DEMO AND REMOVE ALL EXISTING COLD WATER PIPING LEADING FROM THE EXISTING

HOSE BIB BACK. INVESTIGATIVE DEMO WILL HAVE TO OCCUR; THE CONTRACTOR WILL

HAVE TO VERIFY IN FIELD WHERE THE COLD WATER LINE IS COMING FROM (TYP. FOR

ALL HOSE BIBS). DEMO TO THIS POINT SHOWN ON PLANS AND PREPARE TO TIE IN NEW

3/4" CW HERE (TYP. FOR ALL HOSE BIBS)

PD-1

PD-2

PD-3

PD-4

PLMG DEMOLITION KEYED NOTES PD-#

THE CONTRACTOR SHALL VERIFY ALL EXISTING SERVICES: SANITARY LINES, COLD/HOT WATER LINES, STORM LINES, AND VENTING PRIOR TO COMMENCING DEMOLITION WORK. THIS INCLUDES VERIFYING IN THE EXISTING TUNNEL, CEILING, AND CHASE SPACES. ANY QUESTIONS OR CONCERNS

REGARDING CONSTRUCTABILITY OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT, OWNER, AND/OR ENGINEER (IN WRITING) BEFORE BIDDING THE PROJECT.

P205

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

JUNE 2026

KT-216007C

PLUMBING

SECOND LEVEL - NORTH

SOUTH & EAST WINGS

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

SCALE: 1/4" = 1'-0"

SECOND LEVEL NORTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

SECOND FLOOR NORTH WING - FLOOR PLAN

SCALE: 1/4" = 1'-0"

SECOND LEVEL SOUTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

SECOND LEVEL SOUTH WING - FLOOR PLAN

PLUMBINGPLUMBING

PLUMBINGPLUMBING

SCALE: 1/8" = 1'-0"

SECOND LEVEL EAST WING - FLOOR PLAN

PLUMBING

SCALE: 1/4" = 1'-0"

SECOND LEVEL EAST WING - DEMO PLAN

PLUMBING

xSS xTS

PD-2

PD-2

PD-2

PD-3

PD-3

xTS xUR xWC xLAV xSS

PD-2

PD-2

PD-2

PD-3

PD-3

OFFICE

UTR

UTR

343 STOR.

OFFICE

AREA

WORK

CORRIDOR

WC-2

LAV-1 LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

3" UP

W

3/4" HW/CW/

HWR UP

A2A2

UTR

UTR

OFFICE

CORRIDOR

OFFICE

STOR.

AREA

WORK

WC-2

LAV-1

LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S

3" VENT UP

SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

W

3/4" HW/CW/HWR FROM

BELOW

A2A2

EWC-1

ROOM

LOBBY

300A

I.T.

OFFICE

WELLNESS

UTR

J.C.

STAIR

S-2

ELEVATOR

STO.

xWC U.T.R.

EXIST'G.

W

W

S

CW UP TO EWC-1,

2" SAN FROM EWC-1 ABOVE

ROUTE 2" SAN IN

CEILING OF THIRD

FLOOR TO RISER

3/4" CW FROM BELOW

3/4" HW FROM BELOW

3/4" HWR DOWN

3" SAN RISER

3" V UPxSS

PD-3

EXT'G CW, HW, SAN, VENTING TO

BE DEMO'D AND REPLACED FOR

xSS. TIE NEW CW, HW, SAN, AND VENTING SERVICES TO xSS. TUNNEL SPACE:

1. DEMO AND REMOVE THE FOLLOWING:

1.1. EXT'G SANITARY LINES BACK TO THE EXT'G MAIN BUILDING SEWER OUTLET.

1.2. EXT'G VENTING LINES THROUGHOUT THE ENTIRE TUNNEL SPACE.

1.3. EXT'G COLD WATER LINES BACK TO THE EXISTING SHUT-OFF VALVE AS SHOWN ON

THE DRAWING. DEMO THE EXISTING SHUT-OFF VALVE AND PREPARE TO INSTALL

NEW 3" BALL VALVE.

1.4. EXT'G HOT WATER LINE BACK TO THE EXISTING WATER HEATERS. DEMO AND

REMOVE EXT'G WATER HEATERS.

2. EXISTING ITEMS THAT SHALL REMAIN: EXISTING STORM; EXISTING FIRE PROTECTION.

BATHROOM GROUPS & JANITOR CLOSET:

DEMO AND REMOVE EXISTING PLUMBING FIXTURES ALONG WITH ASSOCIATED HOT WATER,

COLD WATER LINES, VENTING, WALL SUPPORTS, ETC. SANITARY SHALL BE DEMO'D AND

CAPPED SO AS TO REMAIN FLUSH WITH FINISHED FLOOR.

CHASES:

1. DEMO AND REMOVE THE FOLLOWING EXISTING RISERS FROM TOP MOST FLOOR TO

TUNNEL SPACE BELOW: SANITARY, COLD WATER, HOT WATER, AND VENTING.

2. EXISTING STORM SHALL REMAIN; OTHER EXISTING RISERS NOT MENTIONED HERE BUT

FOUND IN CHASE TO REMAIN. CONTRACTOR SHALL VERIFY WITH THE ENGINEER IF ANY

QUESTIONS OR CONCERNS ARE FOUND BEFORE DEMOLITION WORK STARTS.

HOSE BIBS:

1. DEMO AND REMOVE ALL EXISTING COLD WATER PIPING LEADING FROM THE EXISTING

HOSE BIB BACK. INVESTIGATIVE DEMO WILL HAVE TO OCCUR; THE CONTRACTOR WILL

HAVE TO VERIFY IN FIELD WHERE THE COLD WATER LINE IS COMING FROM (TYP. FOR

ALL HOSE BIBS). DEMO TO THIS POINT SHOWN ON PLANS AND PREPARE TO TIE IN NEW

3/4" CW HERE (TYP. FOR ALL HOSE BIBS)

PD-1

PD-2

PD-3

PD-4

PLMG DEMOLITION KEYED NOTES PD-#

THE CONTRACTOR SHALL VERIFY ALL EXISTING SERVICES: SANITARY LINES, COLD/HOT WATER LINES, STORM LINES, AND VENTING PRIOR TO COMMENCING DEMOLITION WORK. THIS INCLUDES VERIFYING IN THE EXISTING TUNNEL, CEILING, AND CHASE SPACES. ANY QUESTIONS OR CONCERNS

REGARDING CONSTRUCTABILITY OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT, OWNER, AND/OR ENGINEER (IN WRITING) BEFORE BIDDING THE PROJECT.

P206

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

JUNE 2026

KT-216007C

PLUMBING

THIRD LEVEL - NORTH

SOUTH & EAST WINGS

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

SCALE: 1/4" = 1'-0"

THIRD LEVEL NORTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

THIRD FLOOR NORTH WING - FLOOR PLAN

SCALE: 1/4" = 1'-0"

THIRD LEVEL SOUTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

THIRD LEVEL SOUTH WING - FLOOR PLAN

PLUMBINGPLUMBING

PLUMBINGPLUMBING

SCALE: 1/8" = 1'-0"

THIRD LEVEL EAST WING - FLOOR PLAN

PLUMBING

SCALE: 1/4" = 1'-0"

THIRD LEVEL EAST WING - DEMO PLAN

PLUMBING

xSS xLAV xWC

PD-2

PD-2

PD-2

PD-3

PD-3

xWC xLAV xSS xWC xLAV

PD-2

PD-2

PD-2

PD-3

PD-3

OFFICE

UTR

UTR

STOR.

STAFF

AREA

WORK

CORRIDOR

WC-2

LAV-1

LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

S xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)SAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

3" VTR

W

3/4" HW/CW/HWR FROM

BELOW

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

A2A2

UTR

UTR

OFFICE

CORRIDOR

MTG.

STOR.

444 AREA

WORK

WC-2

LAV-1

LAV-1

WC-2

1- 1/

2" V

CW/HW RISERS, SEE WATER

RISER DIAGRAM, SHEET P300

SSAN RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

xSTORM RISER TO REMAIN

(VERIFY LOCATION IN FIELD)

VENT RISER. SEE SANITARY

RISER DIAGRAM, SHEET P300

3/4" HWR UP

3" SAN DOWN

3" VTR

3/4" HW/CW/HWR FROM BELOW

TIE NEW CW, HW, SAN,

VENTING TO EXT'G SINK

W

A2A2

436437429 LOBBY

400A

MECH.

OFFICE

STAIR

S-2

ELEVATOR

EWC-1

1-1/2" V

W 3

S

CW FROM BELOW

NEW 3" VENT FLOOR PENETRATION.

NEW 3" VTR PENETRATION.

VERIFY MECH ROOM FLOOR PENETRATION IN

FIELD AS THIS WILL NEED TO BE RE-ROUTED

SO AS TO NO BE IN THE MIDDLE OF THE ROOM

436437 400A

ELEV.

DEMO xEWC AND

PREPARE TO INSTALL

NEW EWC

TUNNEL SPACE:

1. DEMO AND REMOVE THE FOLLOWING:

1.1. EXT'G SANITARY LINES BACK TO THE EXT'G MAIN BUILDING SEWER OUTLET.

1.2. EXT'G VENTING LINES THROUGHOUT THE ENTIRE TUNNEL SPACE.

1.3. EXT'G COLD WATER LINES BACK TO THE EXISTING SHUT-OFF VALVE AS SHOWN ON

THE DRAWING. DEMO THE EXISTING SHUT-OFF VALVE AND PREPARE TO INSTALL

NEW 3" BALL VALVE.

1.4. EXT'G HOT WATER LINE BACK TO THE EXISTING WATER HEATERS. DEMO AND

REMOVE EXT'G WATER HEATERS.

2. EXISTING ITEMS THAT SHALL REMAIN: EXISTING STORM; EXISTING FIRE PROTECTION.

BATHROOM GROUPS & JANITOR CLOSET:

DEMO AND REMOVE EXISTING PLUMBING FIXTURES ALONG WITH ASSOCIATED HOT WATER,

COLD WATER LINES, VENTING, WALL SUPPORTS, ETC. SANITARY SHALL BE DEMO'D AND

CAPPED SO AS TO REMAIN FLUSH WITH FINISHED FLOOR.

CHASES:

1. DEMO AND REMOVE THE FOLLOWING EXISTING RISERS FROM TOP MOST FLOOR TO

TUNNEL SPACE BELOW: SANITARY, COLD WATER, HOT WATER, AND VENTING.

2. EXISTING STORM SHALL REMAIN; OTHER EXISTING RISERS NOT MENTIONED HERE BUT

FOUND IN CHASE TO REMAIN. CONTRACTOR SHALL VERIFY WITH THE ENGINEER IF ANY

QUESTIONS OR CONCERNS ARE FOUND BEFORE DEMOLITION WORK STARTS.

HOSE BIBS:

1. DEMO AND REMOVE ALL EXISTING COLD WATER PIPING LEADING FROM THE EXISTING

HOSE BIB BACK. INVESTIGATIVE DEMO WILL HAVE TO OCCUR; THE CONTRACTOR WILL

HAVE TO VERIFY IN FIELD WHERE THE COLD WATER LINE IS COMING FROM (TYP. FOR

ALL HOSE BIBS). DEMO TO THIS POINT SHOWN ON PLANS AND PREPARE TO TIE IN NEW

3/4" CW HERE (TYP. FOR ALL HOSE BIBS)

PD-1

PD-2

PD-3

PD-4

PLMG DEMOLITION KEYED NOTES PD-#

THE CONTRACTOR SHALL VERIFY ALL EXISTING SERVICES: SANITARY LINES, COLD/HOT WATER LINES, STORM LINES, AND VENTING PRIOR TO COMMENCING DEMOLITION WORK. THIS INCLUDES VERIFYING IN THE EXISTING TUNNEL, CEILING, AND CHASE SPACES. ANY QUESTIONS OR CONCERNS

REGARDING CONSTRUCTABILITY OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT, OWNER, AND/OR ENGINEER (IN WRITING) BEFORE BIDDING THE PROJECT.

P207

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

JUNE 2026

KT-216007C

PLUMBING

FOURTH LEVEL - NORTH

SOUTH & EAST WINGS

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

SCALE: 1/4" = 1'-0"

FOURTH LEVEL NORTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

FOURTH FLOOR NORTH WING - FLOOR PLAN

SCALE: 1/4" = 1'-0"

FOURTH LEVEL SOUTH WING - DEMO. PLAN

SCALE: 1/4" = 1'-0"

FOURTH LEVEL SOUTH WING - FLOOR PLAN

PLUMBINGPLUMBING

PLUMBINGPLUMBING

SCALE: 1/8" = 1'-0"

FOURTH LEVEL EAST WING - FLOOR PLAN

PLUMBING

SCALE: 1/4" = 1'-0"

FOURTH LEVEL EAST WING - DEMO PLAN

PLUMBING

12 13 14 15 16 17

D

E

F

G

C

B

A

EXT'G 2" HWS/HWR

EXT'G 3"

HWS/HWR

18A

U.T.R. U.T.R.

16 15

495028293031323334

39 38 37 36

43 1

MECHANICAL ROOM

MAINTENANCE SHOP

S-3

J.C.

TELE

STOR

STOR STOR

STAIR #1

S-2 20

J.C.

CONFERENCE

ELEV.

EXIST'G.EXIST'G.

SHWR.

EXIST'G.

STOR.

NEW

STAFF

RENOV'D

EXIST'G.

NEW

TIE NEW HWHS/R

TO EXT'G HWHS/R

EXT'G

HWS/HWR

RISER

6"Ø EA

RE-USE EXT'G

EA WALL CAP

TIE NEW HWHS/R

TO EXT'G HWHS/R

MATCH EXT'G

PIPE SIZE (V.I.F.)

EXT'G EF

EXT'G EXH. WALL CAP

EXT'G 24X16" SAEXT'G 26X16" SA

EXT'G 24X16" RA

EXT'G 20X16" SA

EXT'G 20X16" RA

EF-1

ALT #1

6"Ø EA WALL CAP. COORD. COLOR W/ ARCH

(TYP.); MIN. 3'-0" FROM OPERABLE WINDOWS.

CONFIRM PENETRATION SIZE AND LOCATION

WITH ARCHITECT BEFORE STARTING WORK.

6"Ø EA

RP-1

T-STAT

RP-1

T-STAT

RP-1

RP-1

A2

1-1/4" HWS/R

EF-2

ALT#2

A2

TIE TO EXISTING

FIRE DAMPER (FD)

SUPPLY AIR DIFF/REG, SD-X, SR-X

RETURN AIR GRILLE, RG-X

SOLID ROUND DUCT

SUPPLY AIR DUCT, SA

RETURN AIR DUCT, RA

MECHANICAL SYMBOLS

VOLUME DAMPER

FLEX DUCT

EQUIPMENT, PIPING, DUCTWORK, ETC., TAGGED WITH

A PRECEDING 'x' IS EXISTING. EXAMPLE, 'x6"Ø' IS

"EXISTING 6" ROUND".

TYPICALTYP.

EXHAUST AIR GRILLE, EG-X

EXHAUST AIR DUCT, RA

M200

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

MECHANICAL

OVERALL

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

JUNE 2026

KT-216007C

SCALE: 1/8" = 1'-0"

MECHANICAL OVERALL GROUND LEVEL - ALT #1 & ALT #2 SHOWN

N

GROUND LEVEL

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195

12 13 14 15 16 17

D

E

F

G

C

B

A

EXT'G

40X10" SA

EXT'G

36X8" SA EXT'G 24X8" SA EXT'G 16X8" SA

EXT'G

SR

EXT'G VAV

EXT'G RAEXT'G RAEXT'G VAV

EXT'G SR

EXT'G

40X10" SA

EXT'G

36X8" SAEXT'G 24X8" SAEXT'G 16X8" SA

EXT'G

80X10" SA

EXT'G RA

IN PLENUM

EXT'G

36X16"

SA UP

EXT'G

36X16"

RA UP

EXT'G

36X16"

SA UP

EXT'G

36X16"

RA UP

EXT'G RA

IN PLENUM

SD-1

50 CFM

J.C.

LOBBY

100A

STOR.

CONF.

CONF.

I.T.

STAFF

STAFF

STAIR

S-2

ELEVATOR

J.C.

LOBBY

100A

STOR.

CONF.

CONF.

I.T.

STAFF

STAFF

STAIR

S-2

ELEVATOR

119 115

127125

111 109

107 105 103 101

129 137

100B

STAFF

U.T.R.

133 135 134

116104

136 128

106 108

126 124

U.T.R.

114 118

100A

EXIST'G. EXIST'G.

ELEV. 144

EXT'G

HWS/HWR

RISEREXT'G

HWS/HWR

RISER

EXT'G

HWS/HWR

RISER

8X6" EA UP

xVAV-112

150 CFM

xVAV-125

150 CFM

SD-1

50 CFM

SD-1

50 CFMEG-1

(TYP. OF 2)

SD-1

50 CFM

EG-1

(TYP. OF 2)

SD-1

50 CFM

SD-1

50 CFM

8X6"

EA UP

A2

FD

FD

FD FD

A2

1 2 3 4 5 6

7 8 9 10 11

12 13 14 15 16 17

D

E

F

G

C

B

A

TRAVERSE CITY

EXT'G

40X10" SA

EXT'G

36X8" SA EXT'G 24X8" SA EXT'G 16X8" SA

EXT'G

SR

EXT'G VAVEXT'G RAEXT'G RA

xVAV-226

150 CFM

EXT'G VAV

EXT'G SR

EXT'G

40X10" SA

EXT'G

36X8" SAEXT'G 24X8" SAEXT'G 16X8" SA

EXT'G

80X14" SA

EXT'G RA

IN PLENUM

EXT'G RA

IN PLENUM

217219

215 209211

225 227

229 237

233 235 234

228236

206 208

226 224

210 212

214 216 218

200A

U.T.R. U.T.R.

EXIST'G. EXIST'G.

A209

A-210

OFFICE

OFFICE

MEETING RM.

MEETING RM.

LOBBY

200A

STOR.

I.T.

J.C.

STAIR

S-2

ELEVATOR

A208

EXT'G

HWS/HWR

RISER

EXT'G

HWS/HWR

RISER

8X8" EA

DOWN

SD-1

50 CFM

SD-1

50 CFM

EG-1

(TYP. OF 2)

SD-1

50 CFM

SD-1

50 CFM

EG-1

(TYP. OF 2)

SD-1

50 CFM

SD-1

50 CFM

8X8" EA

DOWN

xVAV-213

150 CFM

A2

FD

FD

FD FD

A2

TIE TO EXISTING

FIRE DAMPER (FD)

SUPPLY AIR DIFF/REG, SD-X, SR-X

RETURN AIR GRILLE, RG-X

SOLID ROUND DUCT

SUPPLY AIR DUCT, SA

RETURN AIR DUCT, RA

MECHANICAL SYMBOLS

VOLUME DAMPER

FLEX DUCT

EQUIPMENT, PIPING, DUCTWORK, ETC., TAGGED WITH

A PRECEDING 'x' IS EXISTING. EXAMPLE, 'x6"Ø' IS

"EXISTING 6" ROUND".

TYPICALTYP.

EXHAUST AIR GRILLE, EG-X

EXHAUST AIR DUCT, RA

M201

DRAWING TITLE

KCT PROJECT NO.DRAWN

EHT

REVIEWED

DAR

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

UPGRADE PROJECT FOR:

MICHIGAN

MI FILE NO. 171/21349.GAG

STATE OF

OFFICE BLDG.

701 S. ELMWOOD - TRAVERSE CITY, MI

BATHROOM & PLUMBING

1 DESIGN DEVELOPMENT SET 9/24/2025

2 CD 50% REVIEW SET 4/29/2026

3 CD 90% REVIEW SET 6/5/2026

4 BCC PLAN REVIEW SET 6/17/2026

5 BID SET 6/26/2026

6 ADDENDUM #1 7/22/2026

7 ADDENDUM #2 7/29/2026

SCALE: 1/8" = 1'-0"

MECHANICAL OVERALL FLOOR LEVEL - 1

N JUNE 2026

KT-216007C

SCALE: 1/8" = 1'-0"

MECHANICAL OVERALL FLOOR LEVEL - 2

N

MECHANICAL

OVERALL FLOOR

LEVELS 1 & 2

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

12 13 14 15 16 17

D

E

F

G

C

B

A

TRAVERSE CITY

EXT'G

40X10" SA

EXT'G

36X8" SA EXT'G 24X8" SA EXT'G 16X8" SA

EXT'G

SR

EXT'G VAVEXT'G RAEXT'G RAEXT'G VAV

EXT'G SR

EXT'G

40X10" SA

EXT'G

36X8" SAEXT'G 24X8" SAEXT'G 16X8" SA

EXT'G

80X14" SA

EXT'G RA

IN PLENUM

EXT'G RA

IN PLENUM

317319 315

311 309 307

305 303

300 304

336 328 326

306 308 310

322324

314312 316

318301 302

MTG. ROOM

EXIST'G.

STOR.

A-212

A-213

ROOM

LOBBY

300A

I.T.

OFFICE

WELLNESS

ROOM

MEETING

UTR

J.C.

STAIR

S-2

ELEVATOR

STO.

NEW HI/LOW

EWC

A-211

EXT'G

HWS/HWR

RISER

EXT'G

HWS/HWR

RISER

EXT'G

HWS/HWR

RISER

10X8" EA

DOWN

SD-1

50 CFM

SD-1

50 CFM

EG-1

(TYP. OF 2)

SD-1

50 CFM

SD-1

50 CFM

EG-1

(TYP. OF 2)

SD-1

50 CFM

SD-1

50 CFM

10X8" EA

DOWN

xVAV-326

150 CFM

xVAV-313

150…