21009 Bid Set - Stamped Drawings.pdf

PDF 42 MB Posted

Attached to
HEMLOCK FILTRATION PLANT HVAC UPGRADES
Solicitation number
C07230
Issued by
Jefferson County, New York

About this file

These documents are architectural and electrical engineering drawings for the Hemlock Filtration Plant HVAC Upgrades project located in Hemlock, New York, prepared by Architectura PC for the City of Rochester. The project involves comprehensive upgrades to the HVAC systems and electrical infrastructure of the second-floor laboratory space, including replacement of roof-mounted equipment such as chillers, fume hoods, fan coil units, exhaust fans, and a make-up air unit. The project will also include replacing existing lighting fixtures with LED alternatives. The project is estimated at $1,164,656 and will be executed through three separate lump sum contracts: General Construction, Mechanical Contractor, and Electrical Contractor.

The contract includes specific requirements such as an incentive program for employing qualified City residents, apprenticeship program participation, MWBE (Minority and Women-owned Business Enterprise) goals, and workforce requirements. The project is subject to New York State Wicks Law and will utilize bid documents available on BidNet. Bidders can obtain hard copies of documentation for a $60 specification deposit and $10 mailing fee from the City of Rochester's Bureau of Purchasing. The drawings detail extensive electrical and mechanical modifications, including new panelboards, variable frequency motor controllers, exhaust fan reconfigurations, and comprehensive lighting control systems with specifications for LED fixtures, vacancy sensors, and dimming capabilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A-101

A-101

# DESCRIPTION DATE

REVISIONS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

VAI/SBT

SBT

1/8" = 1'-0"

A-101

EXISTING, DEMO &

NEW UPPER LEVEL

PLAN & INTERIORS

Our lines. Your space.www.architecturapc.com

17 PITKIN STREET, SUITE 100

ROCHESTER, NEW YORK 14607 P: 585-442-8550

C O

N

TR

AC

T

D O

C U

M

EN

TS

03/10/2025

REG. EXP.: OCTOBER 31, 2026

CERTIFICATE NO. 2525243

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

VAI/SBT

SBT

1/8" = 1'-0"

A-102

EXISTING & DEMO

ROOF PLAN

Our lines. Your space.www.architecturapc.com

17 PITKIN STREET, SUITE 100

ROCHESTER, NEW YORK 14607 P: 585-442-8550

# DESCRIPTION DATE

REVISIONS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

VAI/SBT

SBT

1/8" = 1'-0"

A-103

ROOF PLAN AND

DETAILS

Our lines. Your space.www.architecturapc.com

17 PITKIN STREET, SUITE 100

ROCHESTER, NEW YORK 14607 P: 585-442-8550

C O

N

TR

AC

T

D O

C U

M

EN

TS

03/10/2025

# DESCRIPTION DATE

REVISIONS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

VAI/SBT

SBT

1/8" = 1'-0"

A-104

EXISTING, DEMO &

NEW SECOND FLR.

REFLECTED CEILING

PLAN

Our lines. Your space.www.architecturapc.com

17 PITKIN STREET, SUITE 100

ROCHESTER, NEW YORK 14607 P: 585-442-8550

C O

N

TR

AC

T

D O

C U

M

EN

TS

03/10/2025

# DESCRIPTION DATE

REVISIONS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

VAI/SBT

SBT

1/8" = 1'-0"

A-105

TEMPORARY

PROTECTION PLAN

AND DETAILS

Our lines. Your space.www.architecturapc.com

17 PITKIN STREET, SUITE 100

ROCHESTER, NEW YORK 14607 P: 585-442-8550

C O

N

TR

AC

T

D O

C U

M

EN

TS

03/10/2025

FIRE ALARM AUDIO/VISUAL INDICATING DEVICE -

MOUNTING HEIGHT AS PER NFPA 72 WITH INTENSITY AS INDICATED

FIRE ALARM VISUAL INDICATING DEVICE -

MOUNTING HEIGHT AS PER NFPA 72 WITH INTENSITY AS INDICATED

SMOKE DETECTOR

HEAT DETECTOR

MANUAL PULL STATION - 42" AFF TO CENTER OF HANDLE

FIRE ALARM CONTROL PANEL - 6' AFF TO TOP OF BOX

ADDRESSABLE INTERFACE MODULE

REMOTE TEST STATION

DUCT DETECTOR - DEVICE BY ELECTRICAL CONTRACTOR

MAGNETIC DOOR HOLD

DEVICE DESIGNATIONS:

# = INDICATES FIRE ALARM INTENSITY

E = ELEVATOR RECALL CONTROLS

DOUBLE DUPLEX RECEPTACLE - NEMA 5-20R - WALL MOUNTED - FLUSH

SPECIAL PURPOSE - SUBSCRIPT INDICATES NEMA TYPE -

WALL MOUNTED - FLUSH

NOTE: WALL MOUNTED DEVICES SHALL BE 18" AFF TO CENTER OF BOX, UNO.

SYMBOL DESIGNATIONS:

AC - MOUNT 6" ABOVE SINK OR COUNTERTOP TO BOTTOM OF BOX

CD - CORD DROP

CTL - CONTROLLED RECEPTACLE

F - FLOOR MOUNTED

GF - GROUND FAULT CIRCUIT INTERRUPTER

H - MOUNT HORIZONTALLY 6" ABOVE SINK OR COUNTERTOP TO BOTTOM OF BOX

IG - ISOLATED GROUND

R - REFRIGERATOR, MOUNT 42" AFF.

SP - SURGE PROTECTED

TS - TAMPER RESISTANT

USB - USB CHARGER

WP = WEATHER RESISTANT GROUND FAULT CIRCUIT INTERRUPTER WITH WEATHERPROOF

WHILE-IN-USE COVER

# - CIRCUIT NUMBER

COMBINATION STARTER/DISCONNECT -

5' AFF TO TOP OF BOX

JUNCTION BOX - WALL OR CEILING

JUNCTION BOX - RECESSED IN FLOOR

DRY TYPE TRANSFORMER - SIZE AS NOTED

DISCONNECT SWITCH - NON FUSED

5' AFF TO TOP OF BOX

DISCONNECT SWITCH - FUSED

5' AFF TO TOP OF BOX

MOTOR STARTER

EXISTING PANELBOARD - FLUSH MOUNTED

EXISTING PANELBOARD - SURFACE MOUNTED

PANELBOARD - FLUSH MOUNTED

PANELBOARD - SURFACE MOUNTED

CONTROL PANEL - FLUSH MOUNTED

CONTROL PANEL - SURFACE MOUNTED

HOMERUN TO PANELBOARD

EQUIPMENT ON SAME CIRCUIT BUT SEPARATELY CONTROLLED

PRIMARY ELECTRIC SERVICE

SECONDARY ELECTRIC CIRCUIT

P

S

VARIABLE FREQUENCY MOTOR CONTROLLER

EQUIPMENT CONNECTION FLEX CONDUIT

SINGLE POLE - WALL MOUNTED - FLUSH

NOTE: WALL MOUNTED SWITCHES SHALL BE 46" AFF TO CENTER OF DEVICE

SWITCH DESIGNATIONS:

3 - MULTI-SWITCH (3-WAY)

D - 0-10V DIMMER SWITCH

VS - VACANCY SENSOR

CEILING MOUNTED SPEAKER

NOTE: WALL MOUNTED DEVICES SHALL BE 18" AFF TO CENTER OF BOX, UNO

DEVICE DESIGNATIONS:

AC - MOUNT 6" ABOVE COUNTER TOP TO BOTTOM OF BOX

F - FLOOR MOUNTED

H - MOUNTED HORIZONTALY 6" ABOVE COUNTER TOP TO BOTTOM OF BOX

W - WALL MOUNTED, 48" AFF TO CENTER

# - NUMBER OF JACKS

FIRE ALARM

RECEPTACLESEQUIPMENT

DISTRIBUTION

SWITCHES

TECHNOLOGY

DUPLEX RECEPTACLE - NEMA 5-20R - WALL MOUNTED - FLUSH

1. CONTRACTORS ARE URGED TO INSPECT THE SITE BEFORE SUBMITTING A BID PROPOSAL TO

ENSURE KNOWLEDGE OF PROJECT REQUIREMENTS AND SITE CONDITIONS. IF NO CLARIFICATION IS REQUESTED, IT WILL BE CONSIDERED THAT THE CONTRACTORS ARE IN FULL UNDERSTANDING

OF PROJECT REQUIREMENTS.

2. PROVIDE LABOR, SUPERVISION, EQUIPMENT, MATERIALS, AND SERVICES REQUIRED FOR THE

COMPLETE INSTALLATION OF THIS WORK IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE,

AND LOCAL CODES, AUTHORITIES HAVING JURISDICTION, AND STANDARDS INCLUDING BUT NOT

LIMITED TO, ASHRAE, IBC, NEC, AND NFPA.

3. NOTHING CONTAINED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS SHALL BE

CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES OR

REGULATIONS.

4. THE USE OF THE WORD "PROVIDE" SHALL MEAN TO FURNISH, INSTALL AND CONNECT, READY TO

USE.

5. THE USE OF THE WORD "FURNISH" SHALL MEAN TO PROCURE AND DELIVER TO THE SITE.

6. THE USE OF THE WORD "INSTALL" SHALL MEAN TO PHYSICALLY PLACE INTO SERVICE AND

CONNECT, READY TO USE.

7. EQUIPMENT AND MATERIALS SHALL BE INSTALLED BY SKILLED TRADESMEN, FAMILIAR WITH THE COMPONENTS TO BE INSTALLED, AND IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY.

8. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL

OFFSETS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. THIS CONTRACTOR SHALL

CAREFULLY EXAMINE THE ARCHITECTURAL, STRUCTURAL, HEATING, VENTILATING AND

AIR-CONDITIONING, ELECTRICAL, PLUMBING, AND OTHER PROJECT DOCUMENTS AS MAY BE

NECESSARY FOR PROPER OPERATION OR INSTALLATION AND SHALL PROVIDE OFFSETS, FITTINGS, AND ACCESSORIES TO MEET PROJECT CONDITIONS.

9. DISCREPANCIES BETWEEN DRAWINGS OR BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE

REPORTED TO PROFESSIONAL IN WRITING. OBTAIN WRITTEN INSTRUCTIONS FROM

PROFESSIONAL AS TO THE MANNER IN WHICH TO PROCEED. NO DEPARTURES FROM THE

PROJECT DOCUMENTS SHALL BE MADE WITHOUT PRIOR WRITTEN ACCEPTANCE BY THE

PROFESSIONAL.

10. DIMENSIONS, CLEARANCES, AND LOCATIONS OF EQUIPMENT AND MATERIALS SHALL BE FIELD

VERIFIED PRIOR TO ORDERING, PROCURING AND FURNISHING SAME.

11. NO EXTRA COMPENSATION OR CHARGES WILL BE ACCEPTED DUE TO DIFFERENCES BETWEEN THE

ACTUAL MEASUREMENTS AND THOSE INDICATED ON THE PLAN. THOROUGHLY COORDINATE

WORK WITH SITE CONDITIONS AND OTHER TRADES, DETERMINE EXACT ROUTE AND LOCATION OF

EACH DUCT, PIPE, CONDUIT, ETC. BEFORE FABRICATION AND INSTALLATION.

12. INSTALL WORK SUBSTANTIALLY AS INDICATED. VERIFY LOCATIONS AND ELEVATIONS ON JOB SITE;

DO NOT DIRECTLY SCALE DRAWINGS. MAKE NECESSARY CHANGES IN ELEVATION, FITTINGS, OR

OFFSETS TO ACCOMMODATE OBSTACLES OR INTERFERENCES.

13. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DAMAGE TO THE BUILDING, PIPING OR

EQUIPMENT THAT IS THE RESULT OF WORK FOR INSTALLATION OF THIS CONTRACT.

14. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR PATCH AND REPAIR OF ALL SURFACES TO MATCH EXISTING MATERIALS AND ADJACENT FINISHES ASSOCIATED WITH INSTALLATION/REMOVAL

OF THIS WORK UNLESS SPECIFICALLY NOTED OTHERWISE.

15. WORK SHALL BE COMPLETED TO MAINTAIN ALL NECESSARY AND REQUIRED CLEARANCES,

ACCESSES, AND OPENINGS, SUCH THAT FULL FUNCTIONALITY, PROPER OPERATION, AND REPAIR

AND MAINTENANCE ARE ENSURED.

16. WHERE DEVICE HEIGHT OCCURS AT POINT OF CHANGE OF FINISH, THE DEVICE HEIGHT SHALL BE

ADJUSTED TO OCCUR IN ONE FINISH. ENSURE RESULTING HEIGHT DOES NOT EXCEED ADA

REQUIREMENTS.

17. WHERE DEVICE OCCURS IN BRICK, TILE, OR BLOCK WALLS, THEY SHALL BE MOUNTED AT A VERTICAL MASONRY JOINT & IN EITHER THE TOP OR BOTTOM HORIZONTAL JOINT, CLOSEST TO

THE MOUNTING HEIGHT. ENSURE RESULTING HEIGHT DOES NOT EXCEED ADA REQUIREMENTS.

18. UNLESS OTHERWISE NOTED, ALL MOUNTING HEIGHT DIMENSIONS LISTED ARE TO THE CENTER

LINE OF THE WALL BOX OR DEVICE.

19. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABELED AND

LISTED BY A CERTIFIED TESTING LABORATORY OR AGENCY.

20. DRAWINGS REPRESENT THE SCOPE OF WORK IN GENERAL ARRANGEMENT FORM AND ARE

INTENDED TO SHOW GENERAL ROUTING AND REQUIRED SIZES/CAPACITIES OF SYSTEM

COMPONENTS.

1. THE DEMOLITION PLANS AND NOTES HAVE BEEN PREPARED TO ASSIST THE CONTRACTORS IN IDENTIFYING THE AREAS AND ITEMS OF DEMOLITION AND RENOVATION ASSOCIATED WITH THIS PROJECT. THE INFORMATION PROVIDED IS NOT MEANT TO BE ALL-INCLUSIVE IN TERMS OF LISTING

EACH AND EVERY SPECIFIC TASK TO BE PERFORMED. EACH CONTRACTOR WILL THOROUGHLY

EXAMINE ALL CONTRACT DOCUMENTS PRIOR TO PERFORMING ANY WORK.

2. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS INDICATED ON THE DEMOLITION DRAWINGS AND DESCRIBED IN THE DEMOLITION NOTES. THE EXTENT OF THE DEMOLITION WORK

WILL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AND ENSURE WHETHER OR NOT

THE WORK IS INDICATED ON THE DRAWINGS.

3. EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS BEFORE

PERFORMING ANY WORK AND IMMEDIATELY NOTIFY THE ARCHITECT, IN WRITING, OF ANY

DISCREPANCIES WITH THE DRAWINGS.

4. ANY WORK PERFORMED AS PART OF THIS CONTRACT REQUIRING OR ALTERATION WILL BE THE

RESPONSIBILITY OF THE RESPECTIVE CONTRACTOR.

5. ALL ITEMS NOTED TO BE REMOVED TO BE DISPOSED OF OFF-SITE BY RESPECTIVE CONTRACTORS, UNLESS NOTED OTHERWISE. WHERE INDICATED ON THE DRAWINGS AND/OR IN THE NOTES AS

SALVAGE AND DELIVER TO OWNER. THE CONTRACTOR WILL CAREFULLY REMOVE INDICATED ITEMS

AND STORE THEM WHERE DIRECTED BY THE OWNER.

6. THE OWNER HAS THE OPTION TO RETAIN POSSESSION OF ANY REMOVED MATERIALS OR

EQUIPMENT. ALL SUCH ITEMS SHALL BE CAREFULLY REMOVED AND STORED AT THE SITE BY THE

CONTRACTOR WHERE DIRECTED BY THE OWNER. ANY MATERIALS OR EQUIPMENT NOT RETAINED

BY THE OWNER WILL BECOME THE PROPERTY OF THE CONTRACTOR AND PROMPTLY REMOVED

FROM SITE.

7. ANY CONTRACTOR REMOVING OR MODIFYING MATERIAL CONTAINING ASBESTOS OR SUSPECTED

OF CONTAINING ASBESTOS WILL NOTIFY THE OWNER AT ONCE AND STOP REMOVAL.

IDENTIFICATION AND/OR REMOVAL OF ASBESTOS CONTAINING MATERIAL WILL BE THE

RESPONSIBILITY OF THE OWNER.

8. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, TECHNOLOGY AND

PLUMBING DRAWINGS FOR DEMOLITION WORK BY RESPECTIVE CONTRACTORS. EACH

CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION ASSOCIATED WITH HIS CONTRACT AND SCOPE

OF WORK. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL

CONSTRUCTION AFFECTED BY HIS DEMOLITION. THE EXTENT OF PATCH AND REPAIR SHALL BE AS

REQUIRED TO RECEIVE THE SCHEDULED NEW WORK. ALL CONTRACTORS ARE RESPONSIBLE FOR

COORDINATION OF WORK WITH OTHER CONTRACTORS BEFORE PERFORMING ANY WORK.

9. ALL PATCH AND REPAIR WORK SHALL BE PERFORMED USING MATERIALS THAT MATCH THE

EXISTING ADJACENT CONSTRUCTION. WHERE PATCHING EXISTING MASONRY WALLS OR INFILLING BETWEEN WALLS WITH MASONRY TO MATCH EXISTING, "TOOTH-IN" NEW MASONRY TO EXISTING.

10. EACH CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING CONSTRUCTION SCHEDULED TO

REMAIN. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL

CONSTRUCTION AFFECTED BY THEIR DEMOLITION. EACH CONTRACTOR SHALL PATCH (SUBSTRATE

AND FINISHED SURFACES) ANY EXISTING FINISHES AFFECTED BY THEIR RESPECTIVE WORK.

11. EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. CONTRACTOR(S)

SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES

PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK.

12. REMOVAL IN ITS ENTIRETY INCLUDES HANGERS, ELECTRICAL, CONTROLS, ETC., TO LEAVE A LIKE

NEW OR MATCHING EXISTING CONDITION.

GENERAL DEMOLITION NOTES:

A, AMP AMPERE

ABN ABANDON

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERES INTERRUPTING CURRENT

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BIL BASIC IMPULSE LEVEL

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CONC CONCRETE

CONN CONNECTION

CT CURRENT TRANSFORMER

CU COPPER

DET DETAIL

DIA, Ø DIAMETER

DN DOWN

DWG DRAWING

E,(E) ELECTRIC, ELECTRICAL

EC ELECTRICAL CONTRACTOR

ELEV ELEVATION

EM,EMER EMERGENCY

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EX,EXIST EXISTING

EXH EXHAUST

EXT EXTERNAL

FA FIRE ALARM

FCU FAN COIL UNIT

FLA FULL LOAD AMPERES

FLEX FLEXIBLE

FLR FLOOR

FIN FINISHED

FT FEET

FU FUSE

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GR GRADE

GRD GROUND

HP HORSEPOWER

HZ HERTZ

INT INTERRUPTING

KA KILO AMPERE

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LA LIGHTNING ARRESTOR

L-N LINE TO NEUTRAL

MAX MAXIMUM

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MH MANHOLE

MIN MINIMUM

MLO MAIN LUG ONLY

MOV METAL OXIDE VARISTOR

MOD MOTOR OPERATED DAMPER

MVA MEGAVOLT AMPERES

NC NORMALLY CLOSED

NE NORMAL EMERGENCY

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OH OVERHEAD

P POLE

PFFB PROVISIONS FOR FUTURE BREAKER

PH, ɸ PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYLCHLORIDE

REQ'D REQUIRED

RGS RIGID GALVANIZED STEEL

RLA RUNNING LOAD AMPS

RES RESISTOR

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

RPM REVOLUTIONS PER MINUTE

RX REMOVE EXISTING

SEC SECOND

SYM SYMMETRICAL

TEMP TEMPERATURE

TRANS TRANSFORMER

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V VOLTS

VAC VOLTS ALTERNATING CURRENT

VM VOLT METER

VP VAPOR PROOF

W WIRE

WG WIRE GUARD

W/ WITH

W/O WITHOUT

WT WEIGHT

XFMR TRANSFORMER

DETAIL

SECTION

DETAIL, SECTION, & CONNECTION MARKS

DIRECTION INDICATORS

SECTION LETTER

SHEET DETAIL APPEARS ONSHEET DETAIL APPEARS ON

DETAIL NUMBER

POINT OF CONNECTION TO EXISTING

REMOVE EXISTING FROM OR TO THIS POINT GENERAL SYMBOL NOTES:

1. EXISTING DEVICES TO REMAIN ARE SHOWN IN LIGHT LINEWEIGHT.

2. EXISTING DEVICES TO BE REMOVED ARE SHOWN IN DASHED LINEWEIGHT.

3. NOT ALL ABBREVIATIONS & SYMBOLS MAY APPLY TO THIS PROJECT.

GENERAL NOTES:

X

X X

ABBREVIATIONS

J

J

T

VFC

S S

D

P

FACP

RTS

DH

S

LIGHTING FIXTURE - SEE FIXTURE SCHEDULE

LIGHTING FIXTURES

MOUNTING HEIGHTS DETAIL

PANEL

FINISHED FLOOR

2 3 4 D

W T

18"

46"

56"

78"

90"

X X

Y

ACM

120V SMOKE DAMPER CONNECTIONSD

EQUIPMENT CONNECTION - REFER TO SCHEDULE

M

MOTOR-STARTING SWITCH

DRAWING NOTE - REFER TO DRAWING NOTE LIST ON SHEET (NEW WORK)

FEEDER TAG - REFER TO FEEDER SCHEDULE ON DRAWING EX.XXX

DRAWING NOTE - REFER TO DRAWING NOTE LIST ON SHEET (DEMOLITION)

DRAWING CONVENTIONS

GROUND ROD

LIGHTNING AIR TERMINAL

LIGHTNING PROTECTION

VAV TRANSFORMER, 120VAC PRIMARY, 24VAC SECONDARY, CLASS II, 100VA.

MOUNT TO JUNCTION BOX ABOVE CEILING. PROVIDE PRIMARY FUSE AND

SINGLE-POLE SINGLE-THROW PRIMARY SNAP SWITCH.

24VAC WIRING

HVAC CONTROL POWER

T

DIRECTION ARROWS FOR EXIT SIGNS AS REQUIRED

WALL MOUNTED EXIT SIGN - SEE FIXTURE SCHEDULE

CEILING MOUNTED EXIT SIGN - SEE FIXTURE SCHEDULE

EMERGENCY BATTERY UNIT WITH HEADS- SEE FIXTURE SCHEDULE

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

N.T.S.

BRW

DSU

ABBREVIATIONS

GENERAL NOTES &

ELECTRICAL SYMBOLS,

E-000

FC-4

FC-3

FC-5

FC-2

LPG

(ETR)

LPC

(ETR)

LPB

(ETR)

HEF-5

HEF-6

HEF-4

HEF-3

(MOUNTED ON FUME

HOOD TO BE REMOVED)

HEF-1

(MOUNTED ON

FUME HOOD TO

BE REMOVED)

HEF-2

(MOUNTED ON

FUME HOOD TO

BE REMOVED)

HEF-7

VFD

MAU-1

HOOD H-2

LTG. & RECEP.

HOOD H-3

LTG. & RECEP.

HOOD H-4

LTG. & RECEP.

HOOD H-1

LTG. & RECEP.

2 2

S

S

S

SS

S

S

D 44 5 6

(ETR)

CHGP-1

CHGP-2

CHGP-1

CHGP-2

CEILING MOUNTED JELLY

JAR LIGHT FIXTURE WITH

RED LAMP

3 3 a,b a,b a,b a,b c,d c,d c,d c,dc,d c,dc,dc,d a b

3c 3d c d f,g f,g f,g h,i h,i h i f g j k j,k j,k j,k j,k a b a,b a,b e e e

HEF-1 (ETR)

LPA (ETR)

HEF-5 (ETR)

HEF-6 (ETR)

HEF-7 (ETR)

EF-8

EF-7 (ETR)

HEF-2 (ETR)

C M

C M

C M

C M

C M

C M

C M

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

AS INDICATED

BRW

DSU

DEMOLITION

FLOOR PLAN -

PARTIAL SECOND

ED-102

SCALE: 1/4"=1'-0"

PARTIAL SECOND FLOOR PLAN1

DEMO NOTES:

1. DISCONNECT AND REMOVE EXISTING FAN COIL UNIT POWER

BRANCH CIRCUITING BACK TO NEAREST ABOVE CEILING

JUNCTION BOX AND SAVE FOR REUSE.

2. DISCONNECT AND REMOVE EXISTING FUME HOOD POWER

BRANCH CIRCUITING BACK TO NEAREST ABOVE CEILING

JUNCTION BOX AND SAVE FOR REUSE.

3. DISCONNECT AND REMOVE EXISTING FUME HOOD POWER

BRANCH CIRCUITING BACK TO SOURCE.

4. DISCONNECT AND REMOVE EXISTING LUMINAIRE TO

ACCOMMODATE NEW DUCTWORK. SAVE AND PROTECT

LUMINAIRE FOR RELOCATION. DISCONNECT AND REMOVE

LIGHTING BRANCH CIRCUITING BACK TO NEAREST JUNCTION BOX

IN UNAFFECTED AREA AND SAVE FOR REUSE.

5. DISCONNECT AND REMOVE ALL EXISTING CEILING MOUNTED FIRE

ALARM DEVICES, PAGING DEVICES AND EXIT SIGNS TO

ACCOMMODATE CEILING REMOVAL. SAVE AND PROTECT DEVICES

AND EXIT SIGNS FOR RE-INSTALLATION. DISCONNECT AND

REMOVE BRANCH CIRCUITING BACK TO NEAREST ABOVE CEILING

JUNCTION BOX AND SAVE FOR REUSE.

6. DISCONNECT, REMOVE AND DISPOSE OF ALL EXISTING

FLUORESCENT LUMINAIRES WITHIN INDICATED AREA TO

ACCOMMODATE CEILING REMOVAL. DISCONNECT AND REMOVE

LIGHTING BRANCH CIRCUITING BACK TO NEAREST ABOVE

CEILING JUNCTION BOX AND SAVE FOR REUSE.

7. DISCONNECT AND REMOVE EXISTING DUCT SMOKE DETECTOR

TO ACCOMMODATE DUCT REMOVAL. DISCONNECT AND REMOVE

FIRE ALARM BRANCH CIRCUITING BACK TO NEAREST

NON-AFFECTED JUNCTION BOX AND SAVE FOR REUSE.

8. DISCONNECT AND REMOVE EXISTING CHILLED WATER GYLCOL

PUMP POWER BRANCH CIRCUITING BACK TO MOTOR CONTROL

CENTER 'MCC-1' IN FIRST FLOOR ELECTRICAL ROOM. RE-LABEL

BUCKET AS SPARE.

9. DISCONNECT AND REMOVE EXISTING CHILLED WATER GLYCOL

PUMP DISCONNECT AND ASSOCIATED POWER BRANCH

CIRCUITING BACK TO MOTOR CONTROL CENTER IN FIRST FLOOR

ELECTRICAL ROOM. RE-LABEL BUCKET AS SPARE. DISCONNECT

SHALL BE TURNED OVER TO OWNER.

10. DISCONNECT AND REMOVE EXISTING MAKE-UP AIR UNIT

DISCONNECT, VARIABLE FREQUENCY DRIVE AND ASSOCIATED

POWER BRANCH CIRCUITING BACK TO DISTRIBUTION PANEL

'PP1A' IN FIRST FLOOR ELECTRICAL ROOM. RE-LABEL EXISTING

CIRCUIT BREAKER AS SPARE. DRIVE SHALL BE TURNED OVER TO

OWNER.

11. DISCONNECT AND REMOVE EXISTING LIGHTING CONTROL

TOGGLE SWITCHES. EXISTING BACKBOX AND ASSOCIATED

BRANCH CIRCUITING SHALL BE EXISTING TO REMAIN.

12. DISCONNECT AND REMOVE CONTROL STATION FROM EXISTING

RECESSED BACKBOX AND REMOVE WIRING BACK TO MCC IN

FIRST FLOOR ELECTRICAL ROOM. EXISTING RECESSED BACKBOX

AND CONDUIT SHALL REMAIN FOR REUSE BY BMS.

WP

GFI

(ETR)

WP

GFI

(ETR)

WP

GFI

(ETR)

3 9

9 HEF-2

HEF-3

HEF-7

EF-8

CH-1

MAU-1

HEF-5

1HEF-6

HEF-1

6 9HEF-4

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

AS INDICATED

BRW

DSU

DEMOLITION

PARTIAL ROOF PLAN -

ED-103

SCALE: 1/4"=1'-0"

PARTIAL ROOF PLAN1

DEMO NOTES:

1. DISCONNECT AND REMOVE EXISTING HOOD EXHAUST FAN POWER

BRANCH CIRCUITING (FED FROM PANELBOARD 'LPB') BACK TO

STUBBED-UP CONDULET ON ROOF AND SAVE FOR REUSE.

2. DISCONNECT AND REMOVE EXISTING HOOD EXHAUST FAN POWER

BRANCH CIRCUITING BACK TO PANELBOARD 'LPB' ON SECOND FLOOR

IN ELEC. ROOM 212. EXISTING MOTOR STARTING SWITCH AND

CONTACTOR SHALL REMAIN FOR REUSE.

3. DISCONNECT AND REMOVE EXISTING MAKE-UP AIR UNIT POWER

BRANCH CIRCUITING BACK TO DISTRIBUTION PANELBOARD 'PP1-A' IN

FIRST FLOOR ELECTRICAL ROOM. RE-LABEL EXISTING BREAKER AS A

SPARE.

4. DISCONNECT AND REMOVE EXISTING CHILLER POWER BRANCH

CIRCUITING BACK TO DISTRIBUTION PANELBOARD 'PP1' IN FIRST

FLOOR ELECTRICAL ROOM. RE-LABEL EXISTING BREAKER AS A SPARE.

5. DISCONNECT AND REMOVE EXISTING HOOD EXHAUST FAN POWER

BRANCH CIRCUITING BACK TO MOTOR CONTROL CENTER 'MCC-1' IN

FIRST FLOOR ELECTRICAL ROOM. RE-LABEL BUCKET AS SPARE.

6. DISCONNECT AND REMOVE EXISTING HOOD EXHAUST FAN POWER

BRANCH CIRCUITING BACK TO MOTOR CONTROL CENTER 'MCC-2' IN

FIRST FLOOR ELECTRICAL ROOM. RE-LABEL BUCKET AS SPARE.

7. DISCONNECT AND REMOVE EXISTING EXHAUST FAN POWER BRANCH

CIRCUITING BACK TO PANELBOARD 'LPB' ON SECOND FLOOR AND

REMOVE EXISTING STARTER IN ELEC. ROOM 212.

8. DISCONNECT AND REMOVE LIGHTNING PROTECTION AIR TERMINALS

FROM EXISTING PIECE OF EQUIPMENT AND SAVE FOR REUSE.

DISCONNECT AND REMOVE CONDUCTORS BACK NEAREST NEAREST

MAIN CONDUCTOR CABLE CONNECTOR.

9. DISCONNECT AND REMOVE LIGHTNING PROTECTION AIR TERMINALS

FROM EXISTING PIECE OF EQUIPMENT. DISCONNECT AND REMOVE

CONDUCTORS BACK NEAREST NEAREST MAIN CONDUCTOR CABLE

CONNECTOR.

10. DISCONNECT AND EXTEND EXISTING POWER BRANCH CIRCUITING TO

NEW CONDENSER LOCATION. EXTEND EXISTING LIGHTNING

PROTECTION CABLE TO NEW LOCATION.

PP2A

(ETR)

PP2

(ETR)

PP1A

(ETR)

PP1

(ETR)

UP TO

SECOND

FLOOR

MCC-2 (ETR)

MCC-1 (ETR)

NORMAL

POWER

SWITCH

GEAR

(ETR)

GENERATOR

SELECTOR

(ETR)

ATS-2

(ETR)

ATS-1

(ETR)

EMERG.

POWER

SWITCH

GEAR

(ETR)

LPD

(ETR)

FA

C

P SIMPLEX

4007ES

(ETR)

GENERAL NOTES:

G1. REFER TO DRAWING E-102 FOR CONTINUATION OF PANELBOARD FEEDERS ON

SECOND FLOOR.

SCALE: 1/4"=1'-0"

PARTIAL FIRST FLOOR PLAN1

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

AS INDICATED

BRW

DSU

NEW WORK

FLOOR PLAN -

PARTIAL FIRST

E-101

DOWN TO

FIRST

FLOOR

PP3PP4

FC-4

FC-3

FC-5

FC-2

LPG

(ETR)

LPC

(ETR)

LPB

(ETR)

VFC VFC VFC VFCVFCVFCVFC VFC

CHGP-1

CHGP-2

MAU-1-SA

MAU-1-SB

HEF-1

HEF-2

EF-10

EF-11

H

S

S

S

SS

S

S

D 4 566

(ETR)

ACM ACM 8 (TYP. OF BOTH MAU-1

SUPPLY FANS)

CEILING MOUNTED JELLY

JAR LIGHT FIXTURE WITH

RED LAMP

D

D

D

HOOD LTG.

& RECEP.

33D a b

LA

a

LA

a

LA

a

LA

a

LA

a

LA

a

LA

b

LA

b

LA

b

LA

b

LA

b

LA

b

LB

b

LB

b

3 a

3D b

VS11

HOOD LTG.

& RECEP. 12

HOOD LTG.

& RECEP. 12

LA

LA

LA LA

LA LA LA

LA

LALA LA

M14

CP

M

WP

GHWP

M

WP

GHWP-1 (ETR)

LPA (ETR)

HEF-5 (ETR)

HEF-6 (ETR)

HEF-7 (ETR)

EF-7 (ETR)

(ETR)

C M

C M

C M

C M

C M

C M

RO

+48"

GLYCOL

MAKE-UP

PACKAGE

(GMU-1)

LPB-23 16

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

UP TO ROOF FOR PLATFORM

EQUIPMENT

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

UP TO ROOF FOR HOOD

EXHAUST FANS AND DAMPERS

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

UP TO ROOF FOR HOOD

EXHAUST FANS AND DAMPERS

HEF-3

DAMPER

HEF-6

DAMPER

HEF-5

DAMPER

HEF-7

DAMPER

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

1/8" = 1'-0"

BRW

DSU

NEW WORK

FLOOR PLAN -

PARTIAL SECOND

E-102

GENERAL NOTES:

G1. COORDINATE FINAL ROUTING AND INSTALLATION OF

PANELBOARD FEEDERS WITH OWNER PRIOR TO

ROUGHING-IN. PROPOSED ROUTE SHOWN FOR BIDDING

PURPOSES ONLY.

G2. REFER TO DRAWING E-101 FOR CONTINUATION OF

PANELBOARD FEEDERS ON FIRST FLOOR.

G3. ALL NEW FIRE ALARM DEVICES MUST BE U.L. LISTED FOR USE

WITH EXISTING, ADDRESSABLE, SIMPLEX 4007ES FIRE ALARM

CONTROL SYSTEM.

G4. UNLESS NOTED OTHERWISE, UTILIZE 2#12, 1#12 GND FOR ALL

BRANCH CIRCUITING.

G5. REFER TO WIRING DIAGRAMS ON DRAWING E-501 FOR

ADDITIONAL LIGHTING CONTROL SYSTEM REQUIREMENTS

AND INFORMATION.

SCALE: 1/4"=1'-0"

PARTIAL SECOND FLOOR PLAN1

#KEYED NOTES:

1. EXTEND AND RECONNECT EXISTING POWER CIRCUIT TO NEW

FAN COIL UNIT.

2. PROVIDE NEW 30-CIRCUIT, 125A MLO, 480/277V, SURFACE

MOUNTED, NEMA 3R, PANELBOARD AT LOCATION SHOWN.

PROVIDE FEEDER (4#1, 1#6 GND IN 2" C) BACK TO

PANELBOARD 'PP1A' IN FIRST FLOOR ELECTRIC ROOM.

PROVIDE NEW 125A-3P CIRCUIT BREAKER IN EXISTING

SQUARE I-LINE PANELBOARD; KAIC RATING OF NEW BREAKER

SHALL MATCH KAIC RATING OF EXISTING PANELBOARD.

3. PROVIDE NEW 30-CIRCUIT, 125A MLO, 480/277V, SURFACE

MOUNTED, NEMA 3R, PANELBOARD AT LOCATION SHOWN.

PROVIDE FEEDER (4#1, 1#6 GND IN 2"C) BACK TO

PANELBOARD 'PP2' IN FIRST FLOOR ELECTRIC ROOM.

PROVIDE NEW 125A-3P CIRCUIT BREAKER IN EXISTING

SQUARE D I-LINE PANELBOARD; KAIC RATING OF NEW

BREAKER SHALL MATCH KAIC RATING OF EXISTING

PANELBOARD.

4. PROVIDE NEW GLARE-FREE LED FLAT PANEL LUMINAIRES AT

LOCATIONS SHOWN WITHIN INDICATED AREA. EXTEND AND

MODIFY EXISTING LIGHT BRANCH CIRCUITING TO

ACCOMMODATE NEW LIGHTING CONTROLS. PROVIDE NEW

0-10V BRANCH CIRCUITING AND CONNECT TO DIMMING

SWITCHES INDICATED OR TO THE LOCAL DIMMING SWITCH IN

THE SPACE.

5. UPON COMPLETION OF ABOVE CEILING WORK, REINSTALL

ALL EXISTING CEILING MOUNTED FIRE ALARM AND PAGING

DEVICES, AS WELL AS ALL CEILING MOUNTED EXIT SIGNS,

BACK IN THEIR ORIGINAL LOCATIONS AND RECONNECT TO

EXISTING BRANCH CIRCUITING.

6. RELOCATE AND REINSTALL EXISTING LUMINAIRES TO

ACCOMMODATE NEW DUCTWORK.

7. PROVIDE NEW DUCT SMOKE DETECTOR IN NEW MAU-1 DUCT.

EXTEND AND RECONNECT EXISTING FIRE ALARM BRANCH

CIRCUITING FROM PREVIOUS DUCT DETECTOR LOCATION TO

NEW LOCATION.

8. PROVIDE FIRE ALARM FAN SHUTDOWN RELAYS TO

SHUTDOWN MAKE-UP AIR UNIT SUPPLY FANS IN THE EVENT

THE DUCT SMOKE DETECTOR GOES INTO ALARM.

9. PROVIDE NEW LINE VOLTAGE, 0-10V DIMMER SWITCH OR LINE

VOLTAGE, MULTI-WAY SWITCH WITH 0-10V DIMMER (TYPE AS

INDICATED) TO ALLOW USER TO CONTROL ON/OFF

OPERATION AND LIGHT LEVELS OF LUMINAIRES WITHIN THE

SPACE. PROVIDE NEW 2-GANG (ONE (1) DECORA, ONE (1)

BLANK) STAINLESS STEEL COVERPLATE.

10. PROVIDE NEW LINE VOLTAGE, MULTI-WAY SWITCH TO ALLOW

USER TO CONTROL ON/OFF OPERATION OF LUMINAIRES

WITHIN THE SPACE. PROVIDE NEW 2-GANG (ONE (1) DECORA,

ONE (1) BLANK) STAINLESS STEEL COVERPLATE.

11. PROVIDE NEW LINE VOLTAGE VACANCY SENSOR SWITCH TO

ALLOW FOR AUTOMATIC OFF, MANUAL-ON OPERATION OF

LUMINAIRES WITHIN THE SPACE. PROVIDE NEW 1-GANG

(DECORA) STAINLESS STEEL COVERPLATE.

12. EXTEND AND RECONNECT EXISTING POWER BRANCH

CIRCUITING TO NEW HOOD.

13. TRANSITION FEEDER RACEWAY FROM ELECTRICAL METAL

TUBING (EMT) CONDUIT TO RIGID METAL CONDUIT (RMC)

BEFORE ENTERING TANK ROOM.

14. PROVIDE MOTOR-STARTING SWITCH FOR HEF-3 AND LOCATE

ABOVE CEILING.

15. RE-LABEL EXISTING MOTOR STARTING SWITCH AND

CONTACTOR WITH NEW CONTROLLED LOAD AND CIRCUIT

INFORMATION.

16. PROVIDE NEW 20A-1P CIRCUIT BREAKER TO MATCH EXISTING

PANELBOARD CONSTRUCTION (SQUARE D) AND KAIC RATING.

17. APPROXIMATE LOCATION OF MOTORIZED DAMPER

ASSOCIATED WITH INDICATED ROOFTOP EXHAUST FAN.

REFER TO DETAIL 2/E-500 FOR WIRING REQUIREMENTS.

18. APPROXIMATE LOCATION OF MOTORIZED DAMPER

ASSOCIATED WITH INDICATED ROOFTOP EXHAUST FAN.

REFER TO DETAIL 1/E-500 FOR WIRING REQUIREMENTS.

RTS

ROUTED ABOVE

SUSPENDED CEILING

4'-0"

WP

GFI

(ETR)

WP

GFI

(ETR)

WP

GFI

(ETR)

WP

GFI

BUFFER

TANK

CHGP

CHGP

CH

CH

MAU

1-SA

MAU

1-SB

HEF

HEF

EF

HEF

HEF

1CATWALK

STRUCTURE

5 1

MAU-1

HEF

HEF

EF

LPB-47

1 5

7 APPROXIMATE

LOCATION OF

EXHAUST FAN

DAMPER

7 APPROXIMATE

LOCATION OF

EXHAUST FAN

DAMPER

EXISTING AIR

VENT BELOW

PLATFORM

(ETR)

M

WP

M

WP

M

WP

M

WP

LPC-9

LPC-9

LPC-9

LPC-9

LPB-32

LPB-35

LPB-33

1 5

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

DOWN TO FILTER ROOM

(LOCATED BENEATH PLATFORM)

E-500

M

WP

LPB-45

APPROXIMATE

LOCATION OF

MAKE-UP AIR

UNIT DAMPER

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

DOWN TO SECOND FLOOR

E-500

APPROXIMATE LOCATION OF

NEW RACEWAY PENETRATIONS

DOWN TO SECOND FLOOR

E-500

# DESCRIPTION DATE

REVISIONS

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

AS INDICATED

BRW

DSU

NEW WORK

PARTIAL ROOF PLAN -

E-103

#KEYED NOTES:

1. EXTEND EXISTING ROOFTOP LIGHTNING PROTECTION SYSTEM TO

PROTECT NEW ROOFTOP EQUIPMENT AND ASSOCIATED PLATFORM

SYSTEM. SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH NFPA 780 AND U.L. STANDARD 96A. PROVIDE NEW

U.L. MASTER LABEL FOR ENTIRE SYSTEM AND SUBMIT CERTIFICATE

TO OWNER UPON COMPLETION OF PROJECT. EXISTING AIR

TERMINALS AND GROUNDING CABLES APPEAR TO BE ALUMINUM;

FIELD VERIFY AND MATCH NEW WITH EXISTING. SUBMIT SYSTEM

DESIGN TO ENGINEER FOR REVIEW DURING SUBMITTAL PORTION OF

PROJECT.

2. PROVIDE 120V BRANCH CIRCUITING TO FACTORY MOUNTED,

UN-POWERED, GFI RECEPTACLE ON SIDE OF MAKE-UP AIR UNIT.

3. RE-ATTACH EXISTING ROOFTOP LIGHTNING PROTECTION EQUIPMENT

TO REPLACEMENT EQUIPMENT. SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH NFPA 780 AND U.L. STANDARD 96A.

PROVIDE NEW U.L. MASTER LABEL FOR ENTIRE SYSTEM AND SUBMIT

CERTIFICATE TO OWNER UPON COMPLETION OF PROJECT. EXISTING

AIR TERMINALS AND GROUNDING CABLES APPEAR TO BE ALUMINUM;

FIELD VERIFY AND MATCH NEW WITH EXISTING. SUBMIT SYSTEM

DESIGN TO ENGINEER FOR REVIEW DURING SUBMITTAL PORTION OF

PROJECT.

4. EXTEND AND RECONNECT EXISTING 120V POWER CIRCUIT TO

REPLACEMENT HOOD EXHAUST FAN AND NEW MOTORIZED DAMPER

(LOCATED BELOW ROOF). POWER CIRCUIT SHALL BE ROUTED

THROUGH NEW INTERPOSING RELAY PROVIDED BY BMS. REFER TO

DETAIL 2/E-500 FOR ADDITIONAL WIRING REQUIREMENTS.

5. REFER TO ELECTRIC EQUIPMENT AND CONTROL SCHEDULE ON

DRAWING E-700 FOR EQUIPMENT POWER REQUIREMENTS.

6. PROVIDE NEW 20A-1P CIRCUIT BREAKER TO MATCH EXISTING

PANELBOARD CONSTRUCTION (SQUARE D) AND KAIC RATING.

7. PROVIDE 120V BRANCHING CIRCUITING (2#12, 1#12 GND., IN 3/4" RMC

CONDUIT) TO EXHAUST FAN DAMPER MOUNTED IN ROOFTOP

DUCTWORK. BRANCH CIRCUIT SHALL BE ROUTED THROUGH DAMPER

CONTROL RELAY IN ASSOCIATED VARIABLE FREQUENCY MOTOR

CONTROLLER (VFC) INSIDE OF BUILDING. PROVIDE WEATHERPROOF,

LOCKABLE, MOTOR-STARTING SWITCH TO PROVIDE LOCAL MEANS OF

DISCONNECT. PROVIDE AN ADDITIONAL 1/2" RMC CONDUIT WITH

PULLSTRING FROM DAMPER DOWN TO VFC FOR LOW VOLTAGE

CONTROL CABLING. REFER TO DETAIL 3/E-500 FOR ADDITIONAL

WIRING REQUIREMENTS.

8. UTILIZE SPARE 20A-1P CIRCUIT BREAKER IN EXISTING PANELBOARD.

9. POWER AND CONTROL RACEWAYS FOR PLATFORM EQUIPMENT

SHALL BE ROUTED UP TO ROOF AT SAME LOCATION AS MECHANICAL

PIPING AND SHALL SHARE THE SAME G.C. FURNISHED AND INSTALLED

PIPE & RACEWAY VAULT. COORDINATE EXACT QUANTITY AND SIZE OF

RACEWAYS REQUIRED TO BE ROUTED THROUGH VAULT WITH G.C..

ONCE THE RACEWAYS EXIT THE VAULT THEY SHALL BE SUPPORTED

FROM BOTTOM SIDE OF PLATFORM.

10. PROVIDE 120V BRANCHING CIRCUITING (2#12, 1#12 GND., IN 3/4" RMC

CONDUIT) TO MAKE-UP AIR UNIT DAMPER. BRANCH CIRCUIT SHALL BE

ROUTED THROUGH DAMPER CONTROL RELAYS IN ASSOCIATED

SUPPLY FAN VARIABLE FREQUENCY MOTOR CONTROLLERS (VFC)

INSIDE OF BUILDING. PROVIDE WEATHERPROOF, LOCKABLE,

MOTOR-STARTING SWITCH TO PROVIDE LOCAL MEANS OF

DISCONNECT. PROVIDE AN ADDITIONAL 1/2" RMC CONDUIT WITH

PULLSTRING FROM DAMPER DOWN TO EACH SUPPLY FAN VFC FOR

LOW VOLTAGE CONTROL CABLING. REFER TO DETAIL 6/E-500 FOR

ADDITIONAL WIRING REQUIREMENTS.

11. POWER AND CONTROL RACEWAYS FOR FUME HOOD EXHAUST FANS

AND ASSOCIATED DAMPERS SHALL BE ROUTED THROUGH A G.C.

FURNISHED AND INSTALLED PIPE & RACEWAY VAULT. COORDINATE

EXACT QUANTITY AND SIZE OF RACEWAYS REQUIRED TO BE ROUTED

THROUGH VAULT WITH G.C..

GENERAL NOTES:

G1. ALL ROOF PENETRATIONS, FLASHING AND SEALING SHALL BE PROVIDED

BY THE GENERAL CONTRACTOR (G.C.).

SCALE: 1/4"=1'-0"

PARTIAL ROOF PLAN1

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

N.T.S.

BRW

DSU

WIRING DIAGRAMS

DETAILS &

E-500

SCALE: NONE

VFC CONTROLLED EXHAUST FAN DAMPER WIRING DIAGRAM3

VARIABLE FREQUENCY MOTOR CONTROLLER (VFC)

DISCHARGE DAMPER

CONTROL RELAY

OUTPUT

DAMPER END SWITCH

POSITION WHEN

DAMPER IS CLOSED

+24V (AUX. VOLTAGE OUTPUT +24VDC , MAX 250 mA)

PROGRAMMABLE DIGITAL INPUT (PERMISSIVE SIGNAL)

LINE (120V)

NEUTRAL

120V

MOTORIZED

DAMPER

LN

DAMPER

ACTUATOR

POWER

2#14 AWG

IN 1/2"C

2#12 AWG

IN 3/4"C

WEATHERPROOF,

LOCKABLE,

MOTOR-STARTING

SWITCH

TO BMS

RIB

120 VOLTS

TO BMS

CS

SCALE: NONE

BMS CONTROLLED EXHAUST FAN AND DAMPER WIRING DIAGRAM1

RIB

120 VOLTS

TO BMS

CS

SCALE: NONE

BMS CONTROLLED EXHAUST FAN (VIA CONTACTOR )

AND DAMPER WIRING DIAGRAM2

M

LOCKABLE

MOTOR-

STARTING

SWITCH

#DETAIL KEYED NOTES:

1. LOCKABLE MOTOR-STARTING SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

2. INTERPOSING RELAY (RELAY IN A BOX (RIB)) FURNISHED BY MECHANICAL

CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR. BMS WIRING BY

MECHANICAL CONTRACTOR.

3. CURRENT SWITCH FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED BY

ELECTRICAL CONTRACTOR. BMS WIRING BY MECHANICAL CONTRACTOR.

4. EXHAUST FAN PROVIDED WITH INTEGRAL DISCONNECT SWITCH. 120V MOTORIZED

DAMPER TO FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY

ELECTRICAL CONTRACTOR.

INTERPOSING

RELAY2

CURRENT

SWITCH3

EXHAUST

FAN & 120V

MOTORIZED

DAMPER

#DETAIL KEYED NOTES:

1. EXISTING LOCKABLE MOTOR-STARTING SWITCH WITH PILOT TO REMAIN.

2. INTERPOSING RELAY (RELAY IN A BOX (RIB)) FURNISHED BY MECHANICAL CONTRACTOR AND

INSTALLED BY ELECTRICAL CONTRACTOR. BMS WIRING BY MECHANICAL CONTRACTOR.

3. CURRENT SWITCH FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED BY

ELECTRICAL CONTRACTOR. BMS WIRING BY MECHANICAL CONTRACTOR.

4. EXHAUST FAN PROVIDED WITH INTEGRAL DISCONNECT SWITCH. 120V MOTORIZED DAMPER

TO FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL

CONTRACTOR.

5. EXISTING CONTACTOR TO REMAIN. REWIRE CONTROL CIRCUIT THROUGH NEW INTERPOSING

RELAY AS SHOWN.

EXISTING

LOCKABLE

MOTOR-

STARTING

SWITCH

INTERPOSING

RELAY2

CURRENT

SWITCH3

EXISTING

CONTACTOR5

TO BMS

EF

DM

EXHAUST

FAN & 120V

MOTORIZED

DAMPER

EF

DM

#DETAIL KEYED NOTES:

1. WEATHERPROOF,LOCKABLE, MOTOR-STARTING SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

2. VARIABLE FREQUENCY MOTOR CONTROLLER (VFC) PROVIDED BY ELECTRICAL CONTRACTOR.

3. ALL LOW VOLTAGE AND 120V POWER BRANCH CIRCUITING (WIRING & RACEWAY) ASSOCIATED WITH CONTROLLING AND POWERING MOTORIZED DAMPER SHALL BE FURNISHED, INSTALLED AND TERMINATED BY ELECTRICAL

CONTRACTOR.

4. DAMPER END SWITCH SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. END SWITCH SHALL BE WIRED INTO PERMISSIVE CONTROL CIRCUIT OF VFC.

1 2

RIB

120 VOLTS

TO BMS

CS

SCALE: NONE

BMS CONTROLLED PUMP (VIA CONTACTOR )

WIRING DIAGRAM4

M

#DETAIL KEYED NOTES:

1. EXISTING LOCKABLE MOTOR-STARTING SWITCH WITH PILOT TO REMAIN.

2. INTERPOSING RELAY (RELAY IN A BOX (RIB)) FURNISHED BY MECHANICAL CONTRACTOR AND

INSTALLED BY ELECTRICAL CONTRACTOR. BMS WIRING BY MECHANICAL CONTRACTOR.

3. CURRENT SWITCH FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED BY

ELECTRICAL CONTRACTOR. BMS WIRING BY MECHANICAL CONTRACTOR.

4. EXISTING CONTACTOR TO REMAIN. REWIRE CONTROL CIRCUIT THROUGH NEW INTERPOSING

RELAY AS SHOWN.

5. LOCKABLE MOTOR-STARTING SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

EXISTING

LOCKABLE

MOTOR-

STARTING

SWITCH

INTERPOSING

RELAY2

CURRENT

SWITCH3

EXISTING

CONTACTOR4

TO BMS

PUMP

LOCKABLE

MOTOR-

STARTING

SWITCH

VFC CONTROLLED MAKE-UP AIR UNIT DAMPER WIRING DIAGRAM5

VARIABLE FREQUENCY MOTOR CONTROLLER (VFC)

(MAU-1-SA)

DISCHARGE DAMPER

CONTROL RELAY

OUTPUT

DAMPER END SWITCH

POSITION WHEN

DAMPER IS CLOSED

(TYP.)

+24V (AUX. VOLTAGE OUTPUT +24VDC , MAX 250 mA)

PROGRAMMABLE DIGITAL INPUT (PERMISSIVE SIGNAL)

LINE (120V)

NEUTRAL

120V

MOTORIZED

DAMPER

LN

DAMPER

ACTUATOR

POWER

2#14 AWG

IN 1/2"C

2#12 AWG

IN 3/4"C

WEATHERPROOF,

LOCKABLE,

MOTOR-STARTING

SWITCH

#DETAIL KEYED NOTES:

1. WEATHERPROOF,LOCKABLE, MOTOR-STARTING SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

2. VARIABLE FREQUENCY MOTOR CONTROLLER (VFC) PROVIDED BY ELECTRICAL CONTRACTOR.

3. ALL LOW VOLTAGE AND 120V POWER BRANCH CIRCUITING (WIRING & RACEWAY) ASSOCIATED WITH CONTROLLING AND POWERING MOTORIZED DAMPER SHALL BE FURNISHED, INSTALLED AND TERMINATED BY ELECTRICAL CONTRACTOR.

4. PROVIDE, WIRE AND PROGRAM ADDRESSABLE FIRE ALARM CONTROL MODULE TO INITIATE A SHUT DOWN OF THE FAN IN THE EVENT THE ASSOCIATED DUCT SMOKE DETECTOR GOES INTO ALARM. MODULE SHALL BE MOUNTED WITHIN 3-FEET OF

CONTROLLER AND WIRED INTO PERMISSIVE CONTROL CIRCUIT OF VFC.

5. FREEZE STAT SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR.

FREEZE STAT SHALL BE WIRED INTO PERMISSIVE CONTROL CIRCUITS OF VFC'S.

6. DAMPER END SWITCH SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL

CONTRACTOR. END SWITCH SHALL BE WIRED INTO PERMISSIVE CONTROL CIRCUITS OF VFC'S.

2#12 AWG

IN 3/4"C

SCALE: NONE

FIRE ALARM FAN

SHUTDOWN RELAY

VARIABLE FREQUENCY MOTOR CONTROLLER (VFC)

(MAU-1-SB)

DISCHARGE DAMPER

CONTROL RELAY

OUTPUT

+24V (AUX. VOLTAGE OUTPUT +24VDC , MAX 250 mA)

PROGRAMMABLE DIGITAL INPUT (PERMISSIVE SIGNAL)

22#14 AWG

IN 1/2"C

FIRE ALARM FAN

SHUTDOWN RELAY

FREEZE STAT

WITH TWO (2)

SPDT CONTACTS

12" MIN.

POWER AND CONTROL

RACEWAYS

ROOF PIPE & RACEWAY VAULT, AS

MANUFACTURED BY RPH OR EQUIVALENT,

FURNISHED AND INSTALLED BY GENERAL

CONSTRUCTION CONTRACT.

SEAL WATERTIGHT AROUND

RACEWAYS.

ROOF RACEWAY VAULT PENETRATION6 SCALE: NONE

DAMPER END SWITCH WITH

TWO (2) SPDT CONTACTS

DAMPER END

SWITCH WITH

SPDT CONTACT

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

N.T.S.

BRW

DSU

WIRING DIAGRAMS

& LIGHTING CONTROL

LUMINAIRE SCHEDULE

E-501

SEQUENCE OF OPERATION:

VACANCY SENSOR: UPON ENTERING THE SPACE THE OCCUPANT SHALL BE REQUIRED TO MANUALLY TURN ON THE LUMINAIRES VIA THE LINE VOLTAGE VACANCY SENSOR SWITCH; THE SWITCH SENSOR SHALL NOT AUTOMATICALLY TURN ON THE LUMINAIRES. ONCE THE OCCUPANT HAS LEFT THE SPACE THE SWITCH

SENSOR SHALL TURN OFF THE LUMINAIRES AFTER 20 MINUTES OF INACTIVITY.

UNSWITCHED HOT

NEUTRAL

LUMINAIRES

LINE VOLTAGE

SENSOR SWITCH

SWITCHED

HOT

NEUTRAL

SYMBOL:

: LINE VOLTAGE VACANCY SENSOR SWITCH

VS

SCALE: NONE

LINE VOLTAGE SENSOR SWITCH WIRING DIAGRAM3

SEQUENCE OF OPERATION:

UPON ENTERING THE SPACE THE OCCUPANT SHALL BE REQUIRED TO MANUALLY TURN ON THE LUMINAIRES VIA THE LINE VOLTAGE, 0-10V DIMMING SWITCH. LUMINAIRES SHALL RETURN TO LAST DIMMING LEVEL WHEN INITIALLY TURNED ON AND THEN CAN BE MANUALLY RAISED OR LOWERED TO THE DESIRED LEVEL BY THE OCCUPANT. THE OCCUPANT MUST MANUALLY TURN

OFF THE LUMINAIRES WHEN LEAVING THE SPACE.

UNSWITCHED HOT

NEUTRAL

+0-10 VDC

LUMINAIRES

LINE VOLTAGE,

0-10V DIMMER

SWITCH

SWITCHED

HOT

NEUTRAL

COM

SYMBOL:

: LINE VOLTAGE, 0-10V DIMMER SWITCH

ON/OFF

D

SCALE: NONE

LINE VOLTAGE 0-10V DIMMER SWITCH WIRING DIAGRAM2

SEQUENCE OF OPERATION:

UPON ENTERING THE SPACE THE OCCUPANT SHALL BE REQUIRED TO MANUALLY TURN ON THE LUMINAIRES VIA A LINE VOLTAGE, MULTI-WAY SWITCH (DIMMING OR NON-DIMMING). LUMINAIRES SHALL RETURN TO LAST DIMMING LEVEL WHEN INITIALLY TURNED ON AND THEN CAN BE MANUALLY RAISED OR LOWERED TO THE DESIRED LEVEL BY THE OCCUPANT AT A MULTI-WAY SWITCH WITH 0-10V DIMMER. THE OCCUPANT MUST MANUALLY TURN OFF THE LUMINAIRES WHEN LEAVING THE

SPACE.

UNSWITCHED HOT

NEUTRAL

+0-10 VDC

LUMINAIRES

LINE VOLTAGE,

MULTI-WAY SWITCH

WITH 0-10V DIMMER

SWITCHED

HOT

NEUTRAL

COM

SYMBOL:

: LINE VOLTAGE, MULTI-WAY SWITCH

WITH 0-10V DIMMER

: LINE VOLTAGE, MULTI-WAY SWITCH

ON/OFF

LINE VOLTAGE,

MULTI-WAY

SWITCH

ON/OFF

TRAVELER WIRE

UNSWITCHED HOT

NEUTRAL

3D

SCALE: NONE

LINE VOLTAGE MULTI-WAY SWITCH WITH 0-10V DIMMING WIRING DIAGRAM1

LUMINAIRE SCHEDULE

TYPE

MANUFACTURER

(DESIGN MAKE) CAT. NUMBER (DESIGN MAKE) COLOR

TEMP.

MIN.

CRI LUMENS WATTAGE

DIMMING

(DOWN TO %) MOUNTING DESCRIPTION FINISH AREA USED

LA LITHONIA EPANL-2X4-6000LM-80CRI-35K-MIN1-EZT-M

VOLT 3500K 80 6,364 55 0-10 (1%) RECESSED 2'x4' LED, EDGE-LIT, GLARE-FREE, FLAT PANEL LUMINAIRE

WITH SATIN WHITE LENS WHITE VARIOUS

LB LITHONIA EPANL-2X2-3400LM-80CRI-35K-MIN1-EZT-M

VOLT 3500K 80 3,428 30 0-10 (1%) RECESSED 2'x2' LED, EDGE-LIT, GLARE-FREE, FLAT PANEL LUMINAIRE

WITH SATIN WHITE LENS WHITE VARIOUS

GENERAL NOTES:

1. ALL LUMINAIRES SHALL UTILIZE LED LAMPS.

2. ALL LUMINAIRES SHALL UTILIZE 120V.

C O

N

TR

AC

T

D O

C U

M

EN

TS

C

IT

Y O

F R

O C

H

ES

TE

R

H

EM

LO

C

K

FI

LT

R

AT

IO

N P

LA

N

T

R

IX

H

IL

L R

O

AD

, H

EM

LO

C

K, N

Y

03/10/2025

19606.05

KEY PLAN

DATE:

PROJECT #:

DRAWN BY:

CHECKED BY:

SCALE:

VERIFY SCALE

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING:

IF BAR IS NOT ONE (1) INCH LONG,

ADJUST SCALE ACCORDINGLY

0 1

H

VA

C U

PG

R

AD

ES

, N O

.:2

N

N.T.S.

BRW

DSU

SCHEDULES

E-700

ELECTRIC EQUIPMENT AND CONTROL SCHEDULE

GENERAL NOTES:

A. UNLESS NOTED OTHERWISE, ALL DEVICES PROVIDED BY THE ELECTRICAL CONTRACTOR.

B. ITEM ID INDICATES EQUIPMENT TAG USED ON FLOOR PLANS.

C. PROVIDE OVERLOADS, SIZE AS REQUIRED, BY THE DIVISION 23 CONTRACTOR.

D. REFER TO PLANS FOR CONTROL EQUIPMENT AND DISCONNECT LOCATIONS.

E. "NF" INDICATES NON-FUSED.

EQUIPMENT POWER SOURCE, PROTECTION & WIRING CONTROLLERS

DISCONNECT

SWITCH

REF.

NOTES

ITEM

IDITEM

ID NAME DRAWING

NUMBER HP KW PHASE SYSTEM

VOLTS FLA MCA

PANEL or

CONTROL

CENTER

OVER

CURRENT

PROTECTION

POWER WIRING FROM PANEL TO

CONTROL UNIT AND FROM

CONTROL UNIT TO EQUIPMENT

VA

R

IA

BL

E

FR

EQ

U

EN

C

Y M

O

TO

R C

O N

TR

O

LL

ER

FR

EE

ZE

S

TA

T

(P R

O

VI

D

ED

B Y

M

EC

H

C O

N

TR

AC

TO

R

FA

C

TO

R

Y M

O U

N

TE

D C

O N

TR

O

LS

M O

TO

R

-S

TA

R

TI

N G

S W

IT

C

H

C O

N

TR

O

LL

ED

B

Y

IN

TE

R

PO

SI

N G

R

EL

AY

(R

EL

AY

P R

O

VI

D

ED

B Y

BM

S)

FI

R

E

AL

AR

M

F

AN

S H

U

TD

O W

N R

EQ

U

IR

ED

C O

N

TR

O

LL

ER

N

EM

A

R

AT

IN

G

SW

IT

C H

A M

PS

FU

SE

S

IZ

E

N

EM

A R

AT

IN

G

PHASE/

NEUTRAL GROUND CONDUIT

CHGP-1 CHILLER GLYCOL PUMP E-103 5 3 460 7.6 PP3-1,3,5 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 CHGP-1

CHGP-2 CHILLER GLYCOL PUMP E-103 5 3 460 7.6 PP4-1,3,5 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 CHGP-2

MAU-1-SA MAKE-UP AIR UNIT E-103 7 1/2 3 460 11.0 PP3-2,4,6 20A-3P 3#12 1#12 3/4" X X X 3R -- -- -- 1,3,4,6 MAU-1-SA

MAU-1-SB MAKE-UP AIR UNIT E-103 7 1/2 3 460 11.0 PP4-2,4,6 20A-3P 3#12 1#12 3/4" X X X 3R -- -- -- 1,3,4,6 MAU-1-SB

CH-1 CHILLER E-103 3 460 47.4 52.5 PP3-7,9,11 70A-3P 3#4 1#10 1-1/4" X -- -- -- -- 1,4 CH-1

CH-2 CHILLER E-103 3 460 47.4 52.5 PP4-7,9,11 70A-3P 3#4 1#10 1-1/4" X -- -- -- -- 1,4 CH-2

HEF-1 HOOD EXHAUST FAN E-103 3 3 460 4.8 PP3-8,10,12 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 HEF-1

HEF-2 HOOD EXHAUST FAN E-103 3 3 460 4.8 PP4-8,10,12 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 HEF-2

HEF-3 HOOD EXHAUST FAN E-103 1/6 1 115 4.4 LPB-30 20A-1P 2#12 1#12 3/4" X X 1 -- -- -- 1,2,4,5 HEF-3

EF-10 GENERAL EXHAUST FAN E-103 3 3 460 4.8 PP3-13,15,17 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 EF-10

EF-11 GENERAL EXHAUST FAN E-103 3 3 460 4.8 PP4-13,15,17 20A-3P 3#12 1#12 3/4" X 3R 30 NF 3R 3,4 EF-11

H-1 HUMIDIFIER E-102 34 3 460 40.9 PP3-14,16,18 60A-3P 3#6 1#10 1" X -- 60 NF 3R 4 H-1

RO-1 RO SKID FOR HUMIDIFIER E-102 1/3 1 115 5.5 LPB-21 20A-1P 2#12 1#12 3/4" X X 3R -- -- -- 4,9 RO-1

GHWP-1 GLYCOL HEATING H.W. PUMP E-102 3/4 1 115 13.8 LPB-29 25A-1P 2#10 1#10 3/4" X X 3R -- -- -- 2,4,7 GHWP-1

CP-1 CLEAN STEAM COND. PUMP E-102 1/8 1 115 1.9 LPA-28 20A-1P 2#12 1#12 3/4" X X 3R -- -- -- 4,9 CP-1

RFERENCE NOTES:

1. PROVIDED WITH FACTORY MOUNTED DISCONNECT.

2. UTILIZE SPARE 20A-1P CIRCUIT BREAKER IN EXISTING PANELBOARD.

3. PROVIDE TYPE XHHW-2 CONDUCTORS BETWEEN VARIABLE FREQUENCY MOTOR CONTROLLER (VFC) AND EQUIPMENT. USE OF THHN CONDUCTORS BETWEEN PANEL AND VFC IS ACCEPTABLE.

4. PROVIDE RIGID METAL CONDUIT (RMC) CONDUIT FOR ALL POWER WIRING.

5. REFER TO DETAIL 1/E-500 FOR ADDITIONAL POWER WIRING REQUIREMENTS.

6. REFER TO DETAIL 5/E-500 FOR FREEZE STAT & FIRE ALARM FAN SHUTDOWN WIRING REQUIREMENTS

7. ROUTE BRANCH CIRCUITING THROUGH EXISTING CONTACTOR (FORMALLY USED BY HEF-1) TO ALLOW FOR BMS CONTROL. REFER TO DETAIL 4/E-500 FOR ADDITIONAL POWER WIRING REQUIREMENTS.

8. ROUTE BRANCH CIRCUITING THROUGH EXISTING CONTACTOR (FORMALLY USED BY HEF-2) TO ALLOW FOR BMS CONTROL. REFER TO DETAIL 4/E-500 FOR ADDITIONAL POWER WIRING REQUIREMENTS.

9. PROVIDE NEW U.L. LISTED 20A-1P CIRCUIT BREAKER TO MATCH EXISTING PANELBOARD CONSTRUCTION (SQUARE D) AND KAIC RATING

PANELBOARD PP3

LOCATION: FILTER ROOM PH W MAIN BUS AMP: 125A

VOLTAGE (L-L) 480 3 4 MAIN TYPE: MLO

VOLTAGE (L-N) 277 MAIN CIRCUIT BREAKER: --

MOUNTING: SURFACE FEEDER SIZE: REFER TO DRAWINGS

FED FROM: PP1A (FED FROM MCC-1) SHORT CIRCUIT RATING: 10,000 AIC

FEED THRU TYPE --

NOTES:

PANELBOARD SHALL HAVE NEMA 3R ENCLOSURE.

DESCRIPTION TRIP

AMPS POLES CKT

PHASE A

(AMPS)

PHASE B

(AMPS)

PHASE C

(AMPS) CKT POLES TRIP

AMPS DESCRIPTION

CHGP-1

20 3 1 7.6 11.0 2 3 20

MAU-1-SA-- -- 3 7.6 11.0 4 -- --

-- -- 5 7.6 11.0 6 -- --

CH-1

70 3 7 41.0 4.8 8 3 20

HEF-1-- -- 9 41.0 4.8 10 -- --

-- -- 11 41.0 4.8 12 -- --

EF-10

20 3 13 4.8 40.9 14 3 60

H-1-- -- 15 4.8 40.9 16 -- --

-- -- 17 4.8 40.9 18 -- --

SPACE 19 0.0 0.0 20 SPACE

SPACE 21 0.0 0.0 22 SPACE

SPACE 23 0.0 0.0 24 SPACE

SPACE 25 0.0 0.0 26 SPACE

SPACE 27 0.0 0.0 28 SPACE

SPACE 29 0.0 0.0 30 SPACE

TOTAL LOAD PER PHASE (AMPS) 110.1 110.1 110.1

TOTAL 3-PHASE LOAD (KVA) 91.5

TOTAL 3-PHASE LOAD (AMPS) 110.2

DEMAND FACTOR 70%

DEMAND 3-PHASE LOAD (AMPS) 77.1

PANELBOARD PP4

LOCATION: FILTER ROOM PH W MAIN BUS AMP: 125A

VOLTAGE (L-L) 480 3 4 MAIN TYPE: MLO

VOLTAGE (L-N) 277 MAIN CIRCUIT BREAKER: --

MOUNTING: SURFACE FEEDER SIZE: REFER TO DRAWINGS

FED FROM: PP2 (FED FROM MCC-2) SHORT CIRCUIT RATING: 10,000 AIC

FEED THRU TYPE --

NOTES:

PANELBOARD SHALL HAVE NEMA 3R ENCLOSURE.

DESCRIPTION TRIP

AMPS POLES CKT

PHASE A

(AMPS)

PHASE B

(AMPS)

PHASE C

(AMPS) CKT POLES TRIP

AMPS DESCRIPTION

CHGP-2

20 3 1 7.6 11.0 2 3 20

MAU-1-SB-- -- 3 7.6 11.0 4 -- --

-- -- 5 7.6 11.0 6 -- --

CH-2

70 3 7 41.0 4.8 8 3 20

HEF-2-- -- 9 41.0 4.8 10 -- --

-- -- 11 41.0 4.8 12 -- --

EF-11

20 3 13 4.8 0.0 14 SPACE

-- -- 15 4.8 0.0 16 SPACE

-- -- 17 4.8 0.0 18 SPACE

SPACE 19 0.0 0.0 20 SPACE

SPACE 21 0.0 0.0 22 SPACE

SPACE 23 0.0 0.0 24 SPACE

SPACE 25 0.0 0.0 26 SPACE

SPACE 27 0.0 0.0 28 SPACE

SPACE 29 0.0 0.0 30 SPACE

TOTAL LOAD PER PHASE (AMPS) 69.2 69.2 69.2

TOTAL 3-PHASE LOAD (KVA) 57.5

TOTAL 3-PHASE LOAD (AMPS) 69.3

DEMAND FACTOR 70%

DEMAND 3-PHASE LOAD (AMPS) 48.5

T000 Title Sheet
G-000 Site Plan
G-001 Phasing Plan
2025-03-05 Hemlock Lake - Contract Documents - Stamped
2025-03-10_Hemlock_Architectural CD-A101 - SS
2025-03-10_Hemlock_Architectural CD-A102- RF
2025-03-10_Hemlock_Architectural CD-A103 - RF
2025-03-10_Hemlock_Architectural CD-A104 - RCP
2025-03-10_Hemlock_Architectural CD-A105 - Details
230081.00_S100
Mechanical Set_Stamped
M-000
MD-102
MD-103
MD-202
M-102
M-103
M-202
M-203
M-500
M-501
M-600
M-601
M-700
M-701
MI-000
MI-600
MI-601
MI-602
Electrical Set_Stamped
E-000
E-000-E-000
ED-102
ED-102-ED-102
ED-103
ED-103-ED-103
E-101
E-101-E-101
E-102
E-102-E-102
E-103
E-103-E-103
E-500
E-500-E-500
E-501
E-501-E-501
E-700
E-700-E-700

File details come from the government source that posted it. Updated .