This document contains building mechanical specifications for a federal construction project. It outlines requirements for duct insulation, including specifications for sheet metal ductwork, insulation materials, and installation procedures. Materials must meet standards from ASTM International. Duct insulation is required for air distribution systems and must be installed after pressure testing is completed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
14 July 2020
Attachment #
Kimball Substation Stage 04 - 5ƛǾ мм .dzƛƭŘƛƴƎ aŜŎƘŀƴƛŎŀƭ Specifications
89503220BWA000032
WAPA 22 05 17-1 11/1/2019
KIMBALL SUBSTATION
SECTION 22 05 17 – SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
PART 1 - GENERAL
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY:
A. This Section includes:
1. Sleeves.
2. Grout.
1.03 REFERENCE STANDARDS:
A. Applicable Standards (Latest Edition):
1. ASTM International (ASTM):
a. ASTM A53/A53M - Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-
Coated Welded and Seamless.
b. ASTM C1107/C1107M - Specification for Packaged Dry, Hydraulic-Cement Grout
(Nonshrink).
1.04 SUBMITTALS:
A. Product data: For each type of product indicated.
PART 2 - PRODUCTS
2.01 SLEEVES:
A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.
B. Galvanized-Steel Wall Pipes: ASTM A53/A53M, Schedule 40, with plain ends and welded steel collar; zinc coated.
C. Galvanized-Steel-Pipe Sleeves: ASTM A53/A53M, Type E, Grade B, Schedule 40, zinc coated, with plain ends.
2.02 GROUT:
A. Standard: ASTM C1107/C1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
B. Characteristics: Nonshrink; recommended for interior and exterior applications.
C. Design Mix: 5,000-psi (34.5-MPa), 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
PART 3 - EXECUTION
3.01 SLEEVE INSTALLATION:
A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
B. Sleeves are not required for core-drilled holes.
END OF SECTION 22 05 17
WAPA 22 05 18-1 11/1/2019
SECTION 22 05 18 – ESCUTCHEONS FOR PLUMBING PIPING
PART 1 - GENERAL
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY:
A. This Section includes:
1. Escutcheons.
1.03 SUBMITTALS:
A. Product Data: For each type of product indicated.
PART 2 - PRODUCTS
2.01 ESCUTCHEONS:
A. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with chrome-plated finish and spring-clip fasteners.
B. One-Piece, Stamped-Steel Type: With chrome-plated finish and spring-clip fasteners.
C. Split-Plate, Stamped-Steel Type: With chrome-plated finish, concealed and exposed-rivet hinge, and spring-clip fasteners.
PART 3 - EXECUTION
3.01 INSTALLATION:
A. Install escutcheons for piping penetrations of walls and ceilings.
B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of insulated piping and with OD that completely covers opening.
1. Escutcheons for New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.
b. Insulated Piping: One-piece, stamped-steel type or split-plate, stamped-steel type with concealed hinge.
c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, stamped-steel type or split-plate, stamped-steel type with concealed hinge.
d. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, stamped-steel type or split-plate, stamped-steel type with concealed hinge.
3.02 FIELD QUALITY CONTROL:
A. Replace broken and damaged escutcheons and floor plates using new materials.
END OF SECTION 22 05 18
WAPA 22 05 29-1 11/1/2019
SECTION 22 05 29 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and DIVISION 01 Specification Sections, apply to this Section.
1.02 SUMMARY:
A. This Section includes:
1. Metal pipe hangers and supports.
2. Thermal-hanger shield inserts.
3. Fastener systems.
4. Pipe stands.
5. Pipe positioning systems.
1.03 RELATED REQUIREMENTS:
1. DIVISION 05 for structural-steel shapes and plates for trapeze hangers for pipe and equipment supports.
1.04 REFERENCE STANDARDS:
A. Applicable Standards (Latest Edition):
1. American Society of Civil Engineers/Structural Engineering Institute (ASCE/SEI):
a. ASCE/SEI 7 - Minimum Design Loads for Buildings and Other Structures.
2. American Welding Society (AWS):
a. AWS D1.1/D1.1M - Structural Welding Code - Steel.
3. ASME International (ASME):
a. ASME B31.9 - Building Services Piping.
b. 2007 ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing
Qualifications."
4. ASTM International (ASTM):
a. ASTM A36/A36M - Specification for Carbon Structural Steel.
b. ASTM A780 - Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings.
c. ASTM C533 - Specification for Calcium Silicate Block and Pipe Thermal
Insulation.
d. ASTM C552 - Specification for Cellular Glass Thermal Insulation.
e. ASTM C591 - Specification for Unfaced Preformed Rigid Cellular
Polyisocyanurate Thermal Insulation.
f. ASTM C1107 - Specification for Packaged Dry, Hydraulic-Cement Grout
(Nonshrink).
5. The International Association of Plumbing and Mechanical Officials (IAPMO):
a. IAPMO PS 42 - Pipe Alignment and Secondary Support Systems.
6. Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. (MSS):
a. MSS SP-58 - Pipe Hangers and Supports - Materials, Design and Manufacture.
7. Metal Framing Manufacturers Association, Inc. (MFMA):
a. MFMA-4 - Metal Framing Standards Publication.
b. MFMA-103 - Guidelines for the Use of Metal Framing.
8. The Society for Protective Coatings (SSPC):
SECTION 22 05 29 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT:
continued
WAPA 22 05 29-2 11/1/2019
a. SSPC-PA 1 - Paint Application Specification No. 1: Shop, Field, and Maintenance
Painting of Steel.
1.05 DEFINITIONS:
A. MSS: Manufacturers Standardization Society of the Valve and Fittings Industry, Inc.
1.06 PERFORMANCE REQUIREMENTS:
A. Delegated Design: Design trapeze pipe hangers and equipment supports, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
B. Structural Performance: Hangers and supports for plumbing piping and equipment shall withstand the effects of gravity loads and stresses within limits and under conditions indicated according to ASCE/SEI 7.
1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water.
2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
1.07 SUBMITTALS:
A. Product Data: For each type of product indicated.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following; include Product Data for components:
1. Trapeze pipe hangers.
2. Metal framing systems.
3. Pipe stands.
4. Equipment supports.
C. Delegated-Design Submittal: For trapeze hangers indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Detail fabrication and assembly of trapeze hangers.
2. Design Calculations: Calculate requirements for designing trapeze hangers.
D. Welding Procedure Specification (WPS) and Welder Performance Qualification Record
(WPQR)
1.08 QUALITY ASSURANCE:
A. Structural Steel Welding Qualifications: Qualify welding procedures, welders, and welding operators according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Pipe Welding Qualifications: Weld piping in accordance with qualified procedures using performance qualified welders and welding operators according to ASME Boiler and Pressure
Vessel Code.
PART 2 - PRODUCTS
2.01 METAL PIPE HANGERS AND SUPPORTS:
A. Carbon-Steel Pipe Hangers and Supports:
WAPA 22 05 29-3 11/1/2019
1. Description: MSS SP-58, Types 1 through 58 (except as noted in PART 3 -
EXECUTION), factory-fabricated components.
2. Galvanized Metallic Coatings: Pregalvanized or hot dipped.
3. Nonmetallic Coatings: Plastic coating, jacket, or liner.
4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.
5. Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel.
B. Stainless-Steel Pipe Hangers and Supports:
1. Description: MSS SP-58, Types 1 through 58 (except as noted in PART 3 -
EXECUTION), factory-fabricated components.
2. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.
3. Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
C. Copper Pipe Hangers:
1. Description: MSS SP-58, Types 1 through 58 (except as noted in PART 3 -
EXECUTION), copper-coated-steel, factory-fabricated components.
2. Hanger Rods: Continuous-thread rod, nuts, and washer made of copper-coated steel or stainless steel.
2.02 THERMAL-HANGER SHIELD INSERTS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Carpenter & Paterson, Inc.
2. PHS Industries, Inc.
3. Pipe Shields, Inc.; a subsidiary of Piping Technology & Products, Inc.
B. Insulation-Insert Material for Cold Piping: ASTM C552, Type II cellular glass with 100-psig
(688-kPa) or ASTM C591, Type VI, Grade 1 polyisocyanurate with 125-psig (862-kPa) minimum compressive strength and vapor barrier.
C. Insulation-Insert Material for Hot Piping: Water-repellent treated, ASTM C533, Type I calcium silicate with 100-psig (688-kPa); ASTM C552, Type II cellular glass with 100-psig
(688-kPa) or ASTM C591, Type VI, Grade 1 polyisocyanurate with 125-psig (862-kPa) minimum compressive strength.
D. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of pipe.
E. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.
F. Insert Length: Extend 2 inches (50 mm) beyond sheet metal shield for piping operating below ambient air temperature.
2.03 FASTENER SYSTEMS:
A. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated or stainless-steel anchors, for use in hardened Portland cement concrete; with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
2.04 PIPE STANDS:
A. High-Type, Single-Pipe Stand:
1. Description: Assembly of base, vertical and horizontal members, and pipe support, for roof installation without membrane penetration.
2. Base: Plastic or Stainless steel.
WAPA 22 05 29-4 11/1/2019
3. Vertical Members: Two or more cadmium-plated-steel or stainless-steel, continuous-thread rods.
4. Horizontal Member: Cadmium-plated-steel or stainless-steel rod with plastic or stainless-steel, roller-type pipe support.
B. High-Type, Multiple-Pipe Stand:
1. Description: Assembly of bases, vertical and horizontal members, and pipe supports, for roof installation without membrane penetration.
2. Bases: One or more; plastic.
3. Vertical Members: Two or more protective-coated-steel channels.
4. Horizontal Member: Protective-coated-steel channel.
5. Pipe Supports: Galvanized-steel, clevis-type pipe hangers.
2.05 PIPE POSITIONING SYSTEMS:
A. Description: IAPMO PS 42, positioning system of metal brackets, clips, and straps for positioning piping in pipe spaces; for plumbing fixtures in commercial applications.
2.06 MISCELLANEOUS MATERIALS:
A. Structural Steel: ASTM A36/A36M, carbon-steel plates, shapes, and bars; black and galvanized.
B. Grout: ASTM C1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications.
1. Properties: Nonstaining, noncorrosive, and nongaseous.
2. Design Mix: 5,000-psi (34.5-Mpa), 28-day compressive strength.
PART 3 - EXECUTION
3.01 HANGER AND SUPPORT INSTALLATION:
A. Metal Pipe-Hanger Installation: Comply with MSS SP-58. Install hangers, supports, clamps, and attachments as required to properly support piping from the building structure.
B. The following figure types given in Figure 1 of MSS SP-58 will not be acceptable: Types 5, 6, 7, 9, 10, 11, 12, 16, 19, 20, 23, 25, 27, 28, 29, and 30. However, Types 7, 9, 10, 10, 11, 19, and 23 may be used for nonferrous and plastic piping systems 2 inches and smaller.
C. Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-58. Arrange for grouping of parallel runs of horizontal piping, and support together on field-fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or install intermediate supports for smaller diameter pipes as specified for individual pipe hangers.
2. Field fabricate from ASTM A36/A36M, carbon-steel shapes selected for loads being supported. Weld steel according to AWS D1.1/D1.1M.
D. Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
E. Fastener System Installation:
1. Install mechanical-expansion anchors in concrete after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions. Do not use in lightweight concrete or in concrete slabs less than 4 inches thick. Powder actuated fasteners will not be permitted.
WAPA 22 05 29-5 11/1/2019
F. Pipe Positioning-System Installation: Install support devices to make rigid supply and waste piping connections to each plumbing fixture. See DIVISION 22 Plumbing Fixture Sections for requirements for pipe positioning systems for plumbing fixtures.
G. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories.
H. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.
I. Install lateral bracing with pipe hangers and supports to prevent swaying.
J. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 (DN 65) and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms and install reinforcing bars through openings at top of inserts.
K. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment.
L. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping.
M. Insulated Piping:
1. Attach clamps and spacers to piping.
a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation.
b. Piping Operating below Ambient Air Temperature: Use thermal-hanger shield insert with clamp sized to match OD of insert.
c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping.
2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.
a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
3. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees.
a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
4. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2 (DN 8 to DN 90): 12 inches (305 mm) long and 0.048 inch
(1.22 mm) thick.
5. Thermal-Hanger Shields: Install with insulation same thickness as piping insulation.
3.02 ADJUSTING:
A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches (40 mm).
3.03 HANGER AND SUPPORT SCHEDULE:
A. Specific hanger and support requirements are in sections specifying piping systems and equipment.
B. Comply with MSS SP-58 for pipe-hanger selections and applications that are not specified in piping system sections.
WAPA 22 05 29-6 11/1/2019
C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field-applied finish.
D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.
E. Use carbon-steel pipe hangers and supports, metal trapeze pipe hangers and metal framing systems and attachments for general service applications.
F. Use copper-plated pipe hangers and copper or stainless-steel attachments for copper piping and tubing.
G. Use padded hangers for piping that is subject to scratching.
H. Use thermal-hanger shield inserts for insulated piping and tubing.
I. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system sections, install the following types:
1. Exception: The following figure types given in Figure 1 of MSS SP-58 will not be acceptable: Types 5, 6, 7, 9, 10, 11, and 12. However, Types 7, 9, 10, and 11 may be used for nonferrous and plastic piping systems 2 inches and smaller.
2. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated, stationary pipes NPS 1/2 to NPS 30 (DN 15 to DN 750).
3. Carbon- or Alloy-Steel, Double-Bolt Pipe Clamps (MSS Type 3): For suspension of pipes NPS 3/4 to NPS 36 (DN 20 to DN 900), requiring clamp flexibility and up to
4-inches (100-mm) of insulation.
4. Steel Pipe Clamps (MSS Type 4): For suspension of cold and hot pipes NPS 1/2 to
NPS 24 (DN 15 to DN 600) if little or no insulation is required.
5. U-Bolts (MSS Type 24): For support of heavy pipes NPS 1/2 to NPS 30 (DN 15 to
DN 750).
6. Clips (MSS Type 26): For support of insulated pipes not subject to expansion or contraction.
7. Single-Pipe Rolls (MSS Type 41): For suspension of pipes NPS 1 to NPS 30 (DN 25 to
DN 750), from two rods if longitudinal movement caused by expansion and contraction might occur.
J. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system sections, install the following types:
1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to
NPS 24 (DN 24 to DN 600).
2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers NPS 3/4 to NPS 24 (DN 20 to DN 600) if longer ends are required for riser clamps.
K. Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system sections, install the following types:
1. Exception: The following figure type given in Figure 1 of MSS SP-58 will not be acceptable: Type 16.
2. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches (150 mm) for heavy loads.
3. Steel Clevises (MSS Type 14): For 120 to 450ºF (49 to 232ºC) piping installations.
4. Swivel Turnbuckles (MSS Type 15): For use with MSS Type 11, split pipe rings.
5. Steel Weldless Eye Nuts (MSS Type 17): For 120 to 450ºF (49 to 232ºC) piping installations.
L. Building Attachments: Unless otherwise indicated and except as specified in piping system sections, install the following types:
WAPA 22 05 29-7 11/1/2019
1. Exception: The following figure types given in Figure 1 of MSS SP-58 will not be acceptable: 19, 20, 23, 25, 27, 28, 29, 30, and 34.
2. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling.
3. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams.
4. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads are considerable and rod sizes are large.
5. Welded-Steel Brackets: For support of pipes from below or for suspending from above by using clip and rod. Use one of the following for indicated loads:
a. Light (MSS Type 31): 750 pounds (340 kg).
b. Medium (MSS Type 32): 1,500 pounds (680 kg).
c. Heavy (MSS Type 33): 3,000 pounds (1,360 kg).
6. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is required.
7. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to linear horizontal movement where headroom is limited.
M. Saddles and Shields: Unless otherwise indicated and except as specified in piping system sections, install the following types:
1. Steel-Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation.
3. Thermal-Hanger Shield Inserts: For supporting insulated pipe.
N. Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping system sections, install the following types:
1. Restraint-Control Devices (MSS Type 47): Where indicated to control piping movement.
2. Spring Cushions (MSS Type 48): For light loads if vertical movement does not exceed
1-1/4 inches (32 mm).
3. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41, roll hanger with springs.
4. Spring Sway Braces (MSS Type 50): To retard sway, shock, vibration, or thermal expansion in piping systems.
5. Variable-Spring Hangers (MSS Type 51): Preset to indicated load and limit variability factor to 25% to allow expansion and contraction of piping system from hanger.
6. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and limit variability factor to 25% to allow expansion and contraction of piping system from base support.
7. Variable-Spring Trapeze Hangers (MSS Type 53): Preset to indicated load and limit variability factor to 25% to allow expansion and contraction of piping system from trapeze support.
8. Constant Supports: For critical piping stress and if necessary to avoid transfer of stress from one support to another support, critical terminal, or connected equipment. Include auxiliary stops for erection, hydrostatic test, and load-adjustment capability. These supports include the following types:
a. Horizontal (MSS Type 54): Mounted horizontally.
b. Vertical (MSS Type 55): Mounted vertically.
c. Trapeze (MSS Type 56): Two vertical-type supports and one trapeze member.
O. Comply with MSS SP-58 for trapeze pipe-hanger selections and applications that are not specified in piping system sections.
WAPA 22 05 29-8 11/1/2019
P. Comply with MFMA-103 for metal framing system selections and applications that are not specified in piping system sections.
Q. Use mechanical-expansion anchors instead of building attachments where required in concrete construction.
R. Use pipe positioning systems in pipe spaces behind plumbing fixtures to support supply and waste piping for plumbing fixtures.
END OF SECTION 22 05 29
WAPA 22 05 53-1 11/1/2019
SECTION 22 05 53 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and DIVISION 01 Specification Sections, apply to this Section.
1.02 SUMMARY:
A. Section Includes:
1. Warning signs and labels.
2. Pipe labels.
3. Stencils.
4. Warning tags.
1.03 REFERENCES:
A. Applicable Standards (Latest Edition):
1. ASME International (ASME):
a. ASME A13.1 - Scheme for the Identification of Piping Systems.
1.04 ACTION SUBMITTALS:
A. Product Data: For each type of product indicated.
B. Samples: For color, letter style, and graphic representation required for each identification material and device.
C. Equipment Label Schedule: Include a listing of all equipment to be labeled with the proposed content for each label.
D. Valve numbering scheme.
E. Valve Schedules: For each piping system to include in maintenance manuals.
1.05 COORDINATION:
A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied.
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 - PRODUCTS
2.01 WARNING SIGNS AND LABELS:
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch (3.2 mm) thick, and having predrilled holes for attachment hardware.
B. Letter Color: Black.
C. Background Color: White.
D. Maximum Temperature: Able to withstand temperatures up to 160ºF (71ºC).
E. Minimum Label Size: Length and width vary for required label content, but not less than
2-1/2 by 3/4 inch (64 by 19 mm).
F. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than
24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.
G. Fasteners: Stainless-steel rivets or self-tapping screws.
SECTION 22 05 53 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT: continued
WAPA 22 05 53-2 11/1/2019
H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
I. Label Content: Include caution and warning information, plus emergency notification instructions.
2.02 PIPE LABELS:
A. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service, and showing flow direction.
B. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive.
C. Self-Adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing.
D. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping system service lettering to accommodate both directions, or as separate unit on each pipe label to indicate flow direction.
2. Lettering Size: At least 1-1/2 inches (38 mm) high.
2.03 STENCILS:
A. Stencils: Prepared with letter sizes according to ASME A13.1 for piping; and minimum letter height of 3/4 inch (19 mm) for access panel and door labels, equipment labels, and similar operational instructions.
1. Stencil Material: Fiberboard or metal.
2. Stencil Paint: Exterior, gloss, alkyd enamel or acrylic enamel black, unless otherwise indicated. Paint may be in pressurized spray-can form.
3. Identification Paint: Exterior, alkyd enamel or acrylic enamel in colors according to
ASME A13.1, unless otherwise indicated.
2.04 WARNING TAGS:
A. Warning Tags: Preprinted or partially preprinted, accident-prevention tags, of plasticized card stock with matte finish suitable for writing.
1. Size: Approximately 4 by 7 inches (100 by 178 mm).
2. Fasteners: Brass grommet and wire.
3. Nomenclature: Large-size primary caption such as "DANGER," "CAUTION," or "DO
NOT OPERATE."
4. Color: Yellow background with black lettering.
PART 3 - EXECUTION
3.01 PREPARATION:
A. Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants.
3.02 PIPE LABEL INSTALLATION:
A. Piping Color-Coding: Painting of piping is specified in architectural specifications.
B. Stenciled Pipe Label Option: Stenciled labels may be provided instead of manufactured pipe labels, at Installer's option. Install stenciled pipe labels with painted, color-coded bands or rectangles, complying with ASME A13.1, on each piping system.
1. Identification Paint: Use for contrasting background.
SECTION 22 05 53 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT: continued
WAPA 22 05 53-3 11/1/2019
2. Stencil Paint: Use for pipe marking.
C. Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces;
machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows:
1. Near each valve and control device.
2. Near each branch connection, excluding short takeoffs for fixtures and terminal units.
Where flow pattern is not obvious, mark each pipe at branch.
3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures.
4. At access doors, manholes, and similar access points that permit view of concealed piping.
5. Near major equipment items and other points of origination and termination.
6. Spaced at maximum intervals of 50 feet (15 m) along each run. Reduce intervals to 25 feet (7.6 m) in areas of congested piping and equipment.
D. Pipe Label Color Schedule:
1. Condensate:
a. Background Color: Yellow.
b. Letter Color: Black.
3.03 WARNING-TAG INSTALLATION:
A. Write required message on, and attach warning tags to, equipment and other items where required.
END OF SECTION 22 05 53
WAPA 23 05 13-1 11/01/2019
SECTION 23 05 13 – COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY:
A. Section includes general requirements for single-phase and polyphase, general-purpose, horizontal, small and medium, squirrel-cage induction motors for use on ac power systems up to 600V and installed at equipment manufacturer's factory or shipped separately by equipment manufacturer for field installation.
1.03 REFERENCE STANDARDS:
A. Applicable Standards (latest edition):
1. The Institute of Electrical and Electronics Engineers, Inc. (IEEE):
a. IEEE 841-2009 - Standard for Petroleum and Chemical Industry - Severe Duty
Totally Enclosed Fan-Cooled (TEFC) Squirrel Cage Induction Motors - Up to and
Including 370 kW (500 hp).
2. National Electrical Manufacturers Association (NEMA):
a. NEMA MG 1 - Motors and Generators.
1.04 COORDINATION:
A. Coordinate features of motors, installed units, and accessory devices to be compatible with the following:
1. Motor controllers.
2. Torque, speed, and horsepower requirements of the load.
3. Ratings and characteristics of supply circuit and required control sequence.
4. Ambient and environmental conditions of installation location.
PART 2 - PRODUCTS
2.01 GENERAL MOTOR REQUIREMENTS:
A. Comply with requirements in this Section except when stricter requirements are specified in
HVAC equipment schedules or Sections.
WAPA 23 05 13-2 11/01/2019
B. Comply with NEMA MG 1 unless otherwise indicated.
2.02 MOTOR CHARACTERISTICS:
A. Duty: Continuous duty at ambient temperature of 95º F and at altitude of 4,800 feet (1,463 m) above sea level.
B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor.
2.03 POLYPHASE MOTORS:
A. Description: NEMA MG 1, Design B, medium induction motor.
B. Efficiency: Energy efficient, as defined in NEMA MG 1.
C. Service Factor: 1.15.
D. Rotor: Random-wound, squirrel cage.
E. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust loading.
F. Temperature Rise: Match insulation rating.
G. Insulation: Class F.
H. Code Letter Designation:
1. Motors Smaller than 15 HP: Manufacturer's standard starting characteristic.
I. Enclosure Material: Cast iron for motor frame sizes 324T and larger; rolled steel for motor frame sizes smaller than 324T.
2.04 POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS:
A. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features coordinated with and approved by controller manufacturer.
1. Windings: Copper magnet wire with moisture-resistant insulation varnish, designed and tested to resist transient spikes, high frequencies, and short time rise pulses produced by pulse-width modulated inverters.
2. Bearing Protection: All motors operated on variable frequency drives shall be equipped with maintenance free, 360 degree circumferential conductive microfiber shaft grounding ring with a minimum two continuous rows of conductive micro fibers completely surrounding the motor shaft to discharge electrical shaft voltages away from the motor’s bearings to ground. Note: Friction/spring contact brushes shall not be acceptable.
WAPA 23 05 13-3 11/01/2019
3. Application Note: Motors up to 100HP shall be provided with a minimum of one shaft grounding ring as described above installed by the manufacturer internally to the motor or externally on the drive end. Grounding rings shall be provided and installed by the motor manufacturer or contractor and shall be installed in accordance with the manufacturer’s recommendations.
4. Energy- and Premium-Efficient Motors: Class B temperature rise; Class F insulation.
5. Inverter-Duty Motors: Class F temperature rise; Class H insulation.
6. Thermal Protection: Comply with NEMA MG 1 requirements for thermally protected motors.
B. Severe-Duty Motors: Comply with IEEE 841, with 1.15 minimum service factor.
2.05 SINGLE-PHASE MOTORS:
A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application:
1. Permanent-split capacitor.
2. Split phase.
3. Capacitor start, inductor run.
4. Capacitor start, capacitor run.
B. Multispeed Motors: Variable-torque, permanent-split-capacitor type.
C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading.
D. Motors 1/20 HP and Smaller: Shaded-pole type.
E. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range.
PART 3 - EXECUTION (NOT APPLICABLE)
END OF SECTION 23 05 13
WAPA 23 05 29-1 11/01/2019
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes:
1. Metal pipe hangers and supports.
2. Trapeze pipe hangers.
3. Metal framing systems.
4. Thermal-hanger shield inserts.
5. Fastener systems.
6. Pipe stands.
7. Equipment supports.
1.02 RELATED REQUIREMENTS:
1. DIVISION 05 for structural-steel shapes and plates for trapeze hangers for pipe and equipment supports.
2. SECTION 233113 - METAL DUCTS for duct hangers and supports.
1.03 REFERENCE STANDARDS:
A. Applicable Standards (Latest Edition):
1. American Society of Civil Engineers/Structural Engineering Institute (ASCE/SEI):
a. ASCE/SEI 7 - Minimum Design Loads for Buildings and Other Structures.
2. American Welding Society (AWS):
a. AWS D1.1/D1.1M - Structural Welding Code - Steel.
3. ASME International (ASME):
a. ASME B31.9 - Building Services Piping.
b. ASME Boiler and Pressure Vessel Code - Section IX, "Welding and Brazing
Qualifications."
4. ASTM International (ASTM):
a. ASTM A36/A36M - Specification for Carbon Structural Steel.
b. ASTM A780 - Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings.
c. ASTM C533 - Specification for Calcium Silicate Block and Pipe Thermal
Insulation.
d. ASTM C552 - Specification for Cellular Glass Thermal Insulation.
e. ASTM C591 - Specification for Unfaced Preformed Rigid Cellular
Polyisocyanurate Thermal Insulation.
f. ASTM C1107 - Specification for Packaged Dry, Hydraulic-Cement Grout
(Nonshrink).
5. Manufacturers Standardization Society of The Valve and Fittings Industry, Inc. (MSS):
a. MSS SP-58 - Pipe Hangers and Supports - Materials, Design and Manufacture.
b. MSS SP-69 - Pipe Hangers and Supports - Selection and Application.
c. MSS SP-89 - Pipe Hangers and Supports - Fabrication and Installation Practices.
6. Metal Framing Manufacturers Association, Inc. (MFMA):
a. MFMA-4 - Metal Framing Standards Publication.
b. MFMA-103 - Guidelines for the Use of Metal Framing.
7. The Society for Protective Coatings (SSPC):
a. SSPC-PA 1 - Paint Application Specification No. 1: Shop, Field, and Maintenance
Painting of Steel.
WAPA 23 05 29-2 11/01/2019
1.04 DEFINITIONS:
A. MSS: Manufacturers Standardization Society of the Valve and Fittings Industry, Inc.
1.05 PERFORMANCE REQUIREMENTS:
A. Delegated Design: Design trapeze pipe hangers and equipment supports, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
B. Structural Performance: Hangers and supports for HVAC piping and equipment shall withstand the effects of gravity loads and stresses within limits and under conditions indicated according to ASCE/SEI 7.
1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water.
2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
1.06 SUBMITTALS:
A. Product Data: For each type of product indicated.
B. Shop Drawings: Show fabrication and installation details and include calculations for the following; include Product Data for components:
1. Trapeze pipe hangers.
2. Metal framing systems.
3. Pipe stands.
4. Equipment supports.
C. Delegated-Design Submittal: For trapeze hangers indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Detail fabrication and assembly of trapeze hangers.
2. Design Calculations: Calculate requirements for designing trapeze hangers.
D. Welding Procedure Specification (WPS) and Welder Performance Qualification Record
(WPQR)
1.07 QUALITY ASSURANCE:
A. Structural Steel Welding Qualifications: Qualify welding procedures, welders, and welding operators according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Pipe Welding Qualifications: Weld piping in accordance with qualified procedures using performance qualified welders and welding operators according to ASME Boiler and Pressure
Vessel Code.
PART 2 - PRODUCTS
2.01 METAL PIPE HANGERS AND SUPPORTS:
A. Carbon-Steel Pipe Hangers and Supports:
1. Description: MSS SP-58, Types 1 through 58 (except as noted in PART 3 - Execution), factory-fabricated components.
2. Galvanized Metallic Coatings: Pre-galvanized or hot-dipped.
3. Nonmetallic Coatings: Plastic coating, jacket, or liner.
4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.
5. Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel.
WAPA 23 05 29-3 11/01/2019
2.02 TRAPEZE PIPE HANGERS:
A. Description: MSS SP-69, Type 59, shop- or field-fabricated pipe-support assembly made from structural carbon-steel shapes with MSS SP-58 carbon-steel hanger rods, nuts, saddles, and U-bolts.
2.03 METAL FRAMING SYSTEMS:
A. MFMA Manufacturer Metal Framing Systems:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Cooper B-Line, Inc.
b. Flex-Strut, Inc.
c. Powerstrut Corp.
d. Unistrut Corporation; Tyco International, Ltd.
2. Description: Shop- or field-fabricated pipe-support assembly for supporting multiple parallel pipes.
3. Standard: MFMA-4.
4. Channels: Continuous slotted steel channel with inturned lips.
5. Channel Nuts: Formed or stamped steel nuts or other devices designed to fit into channel slot and, when tightened, prevent slipping along channel.
6. Hanger Rods: Continuous-thread rod, nuts, and washer made of carbon steel or stainless steel.
7. Metallic Coating: Electroplated zinc, Hot-dipped galvanized, or Mill galvanized.
8. Paint Coating: Epoxy.
2.04 THERMAL-HANGER SHIELD INSERTS:
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Carpenter & Paterson, Inc.
2. PHS Industries, Inc.
3. Pipe Shields, Inc.; a subsidiary of Piping Technology & Products, Inc.
B. Insulation-Insert Material for Cold Piping: ASTM C552, Type II cellular glass with 100-psig
(688-kPa) or ASTM C591, Type VI, Grade 1 polyisocyanurate with 125-psig (862-kPa) minimum compressive strength and vapor barrier.
C. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of pipe.
D. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.
E. Insert Length: Extend 2 inches (50 mm) beyond sheet metal shield for piping operating below ambient air temperature.
2.05 FASTENER SYSTEMS:
A. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated or stainless-steel anchors, for use in hardened Portland cement concrete; with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
2.06 PIPE STANDS:
A. General Requirements for Pipe Stands: Shop- or field-fabricated assemblies made of manufactured corrosion-resistant components to support roof-mounted piping.
B. Compact Pipe Stand: One-piece plastic unit with integral-rod roller, pipe clamps, or V-shaped cradle to support pipe, for roof installation without membrane penetration.
C. Low-Type, Single-Pipe Stand: One-piece stainless-steel base unit with plastic roller, for roof installation without membrane penetration.
D. High-Type, Single-Pipe Stand:
WAPA 23 05 29-4 11/01/2019
1. Description: Assembly of base, vertical and horizontal members, and pipe support, for roof installation without membrane penetration.
2. Base: Plastic or Stainless steel.
3. Vertical Members: Two or more cadmium-plated-steel or stainless-steel, continuous-thread rods.
4. Horizontal Member: Cadmium-plated-steel or stainless-steel rod with plastic or stainless-steel, roller-type pipe support.
E. High-Type, Multiple-Pipe Stand:
1. Description: Assembly of bases, vertical and horizontal members, and pipe supports, for roof installation without membrane penetration.
2. Bases: One or more; plastic.
3. Vertical Members: Two or more protective-coated-steel channels.
4. Horizontal Member: Protective-coated-steel channel.
5. Pipe Supports: Galvanized-steel, clevis-type pipe hangers.
F. Curb-Mounted-Type Pipe Stands: Shop- or field-fabricated pipe supports made from structural-steel shapes, continuous-thread rods, and rollers, for mounting on permanent stationary roof curb.
2.07 EQUIPMENT SUPPORTS:
A. Description: Welded, shop- or field-fabricated equipment support made from structural carbon-steel shapes.
2.08 MISCELLANEOUS MATERIALS:
A. Structural Steel: ASTM A36/A36M, carbon-steel plates, shapes, and bars; black and galvanized.
B. Grout: ASTM C1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications.
1. Properties: Nonstaining, noncorrosive, and nongaseous.
2. Design Mix: 5,000-psi (34.5-MPa), 28-day compressive strength.
PART 3 - EXECUTION
3.01 HANGER AND SUPPORT INSTALLATION:
A. Metal Pipe-Hanger Installation: Comply with MSS SP-58. Install hangers, supports, clamps, and attachments as required to properly support piping from the building structure.
B. The following figure types given in Figure 1 of MSS SP-58 will not be acceptable: Types 5, 6, 7, 9, 10, 11, 12, 16, 19, 20, 23, 25, 27, 28, 29, and 30. However, Types 7, 9, 10, 11, 19, and 23 may be used for nonferrous and plastic piping systems 2 inches and smaller.
C. Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-58. Arrange for grouping of parallel runs of horizontal piping, and support together on field-fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or install intermediate supports for smaller diameter pipes as specified for individual pipe hangers.
2. Field fabricate from ASTM A36/A36M, carbon-steel shapes selected for loads being supported. Weld steel according to AWS D1.1/D1.1M.
D. Metal Framing System Installation: Arrange for grouping of parallel runs of piping, and support together on field-assembled metal framing systems.
E. Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
F. Fastener System Installation:
WAPA 23 05 29-5 11/01/2019
1. Install mechanical-expansion anchors in concrete after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions. Do not use in lightweight concrete or in concrete slabs less than 4 inches thick. Powder activated fasteners will not be permitted.
G. Pipe Stand Installation:
1. Pipe Stand Types except Curb-Mounted Type: Assemble components and mount on smooth roof surface. Do not penetrate roof membrane.
2. Curb-Mounted-Type Pipe Stands: Assemble components or fabricate pipe stand and mount on permanent, stationary roof curb. See DIVISION 07 for curbs.
H. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories.
I. Equipment Support Installation: Fabricate from welded-structural-steel shapes.
J. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.
K. Install lateral bracing with pipe hangers and supports to prevent swaying.
L. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 (DN 65) and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms and install reinforcing bars through openings at top of inserts.
M. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment.
N. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping.
O. Insulated Piping:
1. Attach clamps and spacers to piping.
a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation.
b. Piping Operating below Ambient Air Temperature: Use thermal-hanger shield insert with clamp sized to match OD of insert.
c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping.
2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.
a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
3. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees.
a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
4. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2 (DN 8 to DN 90): 12 inches (305 mm) long and 0.048 inch
(1.22 mm) thick.
5. Thermal-Hanger Shields: Install with insulation same thickness as piping insulation.
3.02 EQUIPMENT SUPPORTS:
A. Fabricate structural-steel stands to suspend equipment from structure overhead or to support equipment above floor.
B. Grouting: Place grout under supports for equipment and make bearing surface smooth.
C. Provide lateral bracing, to prevent swaying, for equipment supports.
WAPA 23 05 29-6 11/01/2019
3.03 METAL FABRICATIONS:
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations.
C. Field Welding: Comply with qualified procedures for shielded, metal arc welding; appearance and quality of welds; and methods used in correcting welding work; and with the following:
1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections so no roughness shows after finishing and so contours of welded surfaces match adjacent contours.
3.04 ADJUSTING:
A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches (40 mm).
3.05 PAINTING:
A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils
(0.05 mm).
B. Touchup: Cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal are specified in DIVISION 09.
C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A780.
3.06 HANGER AND SUPPORT SCHEDULE:
A. Specific hanger and support requirements are in Sections specifying piping systems and equipment.
B. Comply with MSS SP-58 for pipe-hanger selections and applications that are not specified in piping system Sections.
C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field-applied finish.
D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.
E. Use carbon-steel pipe hangers and supports, metal trapeze pipe hangers and metal framing systems and attachments for general service applications.
F. Use stainless-steel pipe hangers or fiberglass pipe hangers and stainless-steel or corrosion-resistant attachments for hostile environment applications.
G. Use copper-plated pipe hangers and copper or…