This document provides details on a federal solicitation for construction services. The solicitation number 89503220BWA000032_AMD0001 is being issued by the Department of Energy Western Area Power Administration for construction work at the Kimball Substation Stage 04 project. The attachment referenced in the file provides supplemental drawings for the solicitation, which seeks contractor services to perform construction activities at the specified substation. No other details are included in the document regarding response dates, pricing requirements, or other terms for the opportunity.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25 August 2020
Attachment B
Kimball Substation Stage 04
- Drawings AMD0001
89503220BWA000032
PROJECT DRAWINGS
KIMBALL SUBSTATION
STAGE 04
SECTION C
DESCRIPTION/SPECIFICATIONS
Spec. No. 976
NEBRASKA
STAGE 04
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAWINGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. KB 0015 Rev. A – Location and Vicinity Map
ELECTRICAL:
2. KB 0001 Rev. I EI – Switching Diagram (Existing Installation)
3. KB 0001 Rev. J – Switching Diagram
4. KB 1000 Rev. D EI – General Arrangement Plan (Existing Installation)
5. KB 1000 Rev. E – General Arrangement Plan
6. KB 1001 Rev. C EI – 115kV Bus Structure “Y” Area Plan (Existing Installation)
7. KB 1002 Rev. C EI – Transformer KY1A and 34.5kV Bus Structure “X” Area Plan (Existing Installation)
8. KB 1003 Rev. G EI – Grounding, Buried Cable and Trench Plan (Existing Installation)
9. KB 1011 – Transformer KY1A and 34.5kV Bus Structure “X” Area Plan
10. KB 1012 – 115kV Transformer Bus Area Plan
11. KB 1013 – 115kV Bay Y2 Area Plan
12. KB 1014 – 115kV Bay Y1 Area Plan
13. KB 1015 – 115kV Bays Y4 and Y6 Area Plan
14. KB 1016 – 115kV Bays Y3 and Y5 Area Plan
15. KB 1100 – Equipment and Material Index
16. KB 1101 – Substation Signs
17. KB 1110 Rev. B EI – 115kV and Transformer Area Sections A-A, B-B and C-C (Existing Installation)
18. KB 1110 Rev. C – 115kV and Transformer Area Sections A-A and B-B
19. KB 1111 Rev. E EI – Transformer KY1A and 34.5kV Bus Structure “X” Sections (Existing Installation)
20. KB 1111 Rev. F – 34.5kV Bus Structure “X” Sections
21. KB 1112 – Transformer KY1A and 12.47kV Area Sections
22. KB 1113 – 115kV Bays Y1 and Y2 Section L-L
23. KB 1114 – 115kV Bays Y1 and Y2 Section M-M
24. KB 1115 – 115kV Bay Y4 Section N-N
25. KB 1116 – 115kV Bay Y4 Section O-O
26. KB 1117 – 115kV Bay Y6 Section P-P
27. KB 1118 – 115kV Bay Y6 Section Q-Q
28. KB 1119 – 115kV Area Sections R-R and S-S
29. KB 1120 – 115kV Area Sections T-T thru W-W and Detail A
30. KB 1500 – General Grounding Plan
31. KB 1511 – Transformer KY1A and 34.5kV Bus Structure “X” Area Grounding Plan
32. KB 1512 – 115kV Transformer Bus Area Grounding Plan
33. KB 1513 – 115kV Bay Y2 Area Grounding Plan
34. KB 1514 – 115kV Bay Y1 Area Grounding Plan
35. KB 1515 – 115kV Bays Y4 and Y6 Area Grounding Plan
36. KB 1516 – 115kV Bays Y4 and Y6 Area Grounding Plan
37. KB 1600 – Station Service Wiring Diagram
38. KB 1601 – Station Service Distribution Panel DWA Wiring Diagram
39. KB 1610 – Station Service 240/120V Equipment Wiring Diagram
40. KB 1700 – General Conduit Plan
41. KB 1711 – Transformer KY1A and 34.5kV Bus Structure “X” Area Conduit Plan https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx
PROJECT DRAWINGS
42. KB 1712 – 115kV Transformer Bus Area Conduit Plan
43. KB 1713 – 115kV Bay Y2 Area Conduit Plan
44. KB 1714 – 115kV Bay Y1 Area Conduit Plan
45. KB 1715 – 115kV Bays Y4 and Y6 Area Conduit Plan
46. KB 1716 – 115kV Bays Y4 and Y6 Area Conduit Plan
47. KB 1720 – Pull Box PB1 Plan and Sections
48. KB 1721 – Pull Box PB2 Plan and Sections
49. 31 2043 – Bollard Details
CIVIL & SITE DRAWINGS:
50. KB 0023 – Topography
51. KB 2011 Rev. A (EI) – Grading and Vicinity Map (Existing Installation)
52. KB 2051 Rev. A – Civil Site Plan
53. KB 2052 Rev. A – Civil Grading plan
54. KB 2053 Rev. A – Civil Grading at Service Building Details
55. KB 2054 Rev. A – Civil Sections
56. KB 2055 Rev. A – Civil Details
FOUNDATION AND STRUCTURAL DRAWING INDEX:
57. KB 2015 Rev. C – Foundation/Structural Data and Drawings Index
CONCRETE:
58. KB 2000 Rev. E (EI) – Foundations General Plan (Existing Installation)
59. KB 2000 Rev. F – Foundations General Plan
60. KB 2211 – Transformer KY1A and 34.5kV Bus Structure “X” Area Foundation Plan
61. KB 2212 – 115kV Transformer Bus Area Foundation Plan
62. KB 2213 – 115kV Bay Y2 Area Foundation Plan
63. KB 2214 – 115kV Bay Y1 Area Foundation Plan
64. KB 2215 – 115kV Bays Y4 and Y6 Area Foundation Plan
65. KB 2216 – 115kV Bays Y3 and Y5 Area Foundation Plan
66. KB 2001 Rev. E – Foundations Concrete Outline and Reinforcement
67. KB 2300 Rev. B – Foundations Outline and Reinforcement
68. KB 2302 – Foundations Outline and Reinforcement
69. KB 2303 – Foundations Outline and Reinforcement
70. KB 2304 – Foundations Outline and Reinforcement
71. KB 2305 – Foundations Outline and Reinforcement
72. KB 2306 Rev. A – Foundations Outline and Reinforcement
73. KB 2307 – Foundations Outline and Reinforcement
CABLE TRENCH:
74. KB 2002 Rev. C – Cable Trench Type C Outline and Reinforcement
75. KB 2500 – Cable Trench Plan
76. KB 2501 – Cable Trench Sections
STEEL STRUCTURES:
77. KB 2550 Rev. A – Anchor Bolts
78. KB 2004 Rev. A (EI) – Steel Structures 115kV Bus Structure (Existing Installation)
79. KB 2008 Rev. B – 34.5kV Bus Structure
80. KB 2009 Rev. A (EI) – 115kV Capacitor Support (Existing Installation)
81. KB 2601 (EI) – 12.47kV Transformer Support – Type I (Existing Installation)
82. KB 2602 – 115kV Take-Off Structure Type II Elevations
83. KB 2603 – 115kV Take-Off Structure Type II Assemblies and Connections
84. KB 2605 – 115kV Bus Tower Elevations
85. KB 2606 – 115kV Bus Tower Assemblies and Connections
86. KB 2607 – Bus Frames
87. KB 2608 – Tee Poles
88. KB 2609 – Bus Poles
89. KB 2610 – Equipment Supports
90. KB 2611 – Equipment and Bus Support Type I Elevations
91. KB 2612 – Equipment and Bus Support Type I Sections and Details
92. KB 2613 – Station Service Equipment Support Frame Elevation
93. KB 2614 – Station Service Equipment Support Frame Sections and Details
94. KB 2615 – Fuse Disconnect Switch Support Steel Design and Details
PROJECT DRAWINGS
95. KB 2616 – Switch Supports
96. KB 2925 – Switch Operating Platforms Steel Design and Details
97. KB 2926 – Equipment Cabinet Platforms Steel Design and Details
STRINGING REQUIREMENTS:
98. KB 2010 Rev. C (EI) – Stringing Requirement (Existing Installation)
99. KB 2010 Rev. E – Stringing Requirement
SERVICE BUILDING:
100. KB 3000 Rev. B (EI) – Service Building General Arrangement (Existing Installation)
101. KB 3001 Rev. B (EI) – Service Building Plans, Elevations, and Sections (Existing Installation)
102. KB 3002 (EI) – Service Building Plans, Elevations and Sections (Existing Installation)
103. KB 3010-1 – Architectural Floor Plan
104. KB 3010-2 – Architectural Battery Room Bridge Crane
105. KB 3011-1 – Architectural Reflected Ceiling Plan
106. KB 3012 – Architectural Exterior Elevations
107. KB 3013 – Architectural Building Sections
108. KB 3014 – Architectural Detailed Sections
109. KB 3015 – Architectural Detailed Sections
110. KB 3016 – Architectural Details
111. KB 3017 – Architectural Hollow Metal Door Details
112. KB 3200 – Structural General Structural Notes, Abbreviations and Reference Drawings
113. KB 3201 – Structural Building Foundation Plan
114. KB 3202 – Structural Drilled Pier & Grade Beam Schedules
115. KB 3203 – Structural Form Saver & Threaded Dowel Details
116. KB 3204 – Structural Drilled Pier & Grade Beam Plan
117. KB 3205 – Structural Internal Form Saver & Dowel Plan
118. KB 3206 – Structural External Form Saver & Dowel Plan
119. KB 3207 – Structural Slab Reinforcement Plan
120. KB 3208 – Structural Foundation Sections & Details
121. KB 3209 – Structural Roof Framing Plan
122. KB 3210 – Structural Foundation Requirements
123. KB 3211 – Structural Building Foundation Sections
124. KB 3212 – Structural Foundation Sections & Details
125. KB 3213 – Structural Foundation Sections & Details
126. KB 3214 – Structural Foundation/Cable Entry Details
127. KB 3215 – Structural Foundation/Cable Entry Details
128. KB 3216 – Structural Foundation/Cable Entry Details
129. KB 3217 – Structural Typical Wood-Framed Wall (Sh 1 of 2)
130. KB 3218 –Structural Typical Wood-Framed Wall (Sh 2 of 2)
131. KB 3219 – Structural Equipment Mounting Details
132. KB 3220 – Structural External Perimeter Drain & Sump System
133. 31 2051 Rev. B – Structural Building Entry Platforms
134. KB 3300 – Mechanical General Notes
135. KB 3301 – Mechanical Floor Plan
136. KB 3302 – Mechanical Schedules
137. KB 3303 – Mechanical Details I
138. KB 3304 – Mechanical Details II
139. KB 3305 – Mechanical Controls
140. KB 3306 – Mechanical Sections
141. KB 3400 – Electrical Power Plan
142. KB 3401 – Electrical Lighting Plan
143. KB 3402 – Electrical Security Plan
144. KB 3403 – Electrical Distribution Panels DHA, DHB
145. KB 3404 – Electrical Wiring Devices Schematic
146. KB 3405 – Electrical Luminaire and Equipment Schedules
CONTROLS:
147. KB T600-1 – Control Cable List (Sh. 1 of 2)
148. KB T600-2 – Control Cable List (Sh. 2 of 2)
149. KB 4010 – Service Building Arrangement, Conduit, and Grounding
PROJECT DRAWINGS
150. KB 6100 – 125VDC Distribution Panels BHA1 & BHA2 Wiring Diagram
TRANSMISSION LINE STEEL POLE STRUCTURES:
151. 43 168T 2200 – 168T Steel Pole Structures Outline and Design Loads
152. 43 2206 Rev. H – Maintenance Provisions Outlines
153. 43 2210 Rev. J – Maintenance Provisions Details
154. 41 2701 Rev. C – Fall Protection Anchorage Plates
155. 41 9027-2 Rev. A – Aerial Patrol Mile Marker and Structure Number Signs (Sh. 2 of 3)
TRANSMISSION LINE WOOD POLE STRUCTURES:
156. 41 6118 Rev. B – Type 3TA-1 69kV and 115kV 3-Pole Tension Structure
157. 41 6116 Rev. B EI – Type ST-1 69kV and 115kV Tangent and Angle Tension Structure (Existing Installation)
158. 41 6047 Rev. F – Guy Assembly and Details
159. 41 6071 Rev. A – Guying Requirements for Single Pole Construction with Overhead Groundwire
160. 41 6125 Rev. A - Type 3TA-1 Structures Standard Guy Arrangement
161. 41 6138 Rev. B - Typical Details for Dead End Tees
EXISTING TRANSMISSION LINE STRUCTURES (FOR REMOVAL):
162. 41 6010 Rev. D EI – Type HS 115kV Suspension Structure (Existing Installation)
163. 41 6118 Rev. B EI – Type 3TA-1 69kV 3-Pole Tension Structures (Existing Installation)
PLAN AND PROFILES:
164. ARH-SD 1900 EI – Archer-Sidney 115kV Transmission Line Kimball Sub Approach Spans (Existing
Installation)
165. ARH-SD T400 – Archer-Sidney 115kV Transmission Line Kimball Sub Shoo Fly Detail
166. ARH-SD 4029 Rev. A EI – Archer-Sidney 115kV Transmission Line P&P Sta. 3250+00 to Sta. 3362+00
(Existing Installation)
167. ARH-SD 4029-1 – Archer-Sidney 115kV Transmission Line P&P Sta. 3250+00 to Sta. 3362+00
168. ARH-SD 4029-2 – Archer-Sidney 115kV Transmission Line P&P
169. ARH-SD T401 – Archer-Sidney 115kV Transmission Line Kimball Sub Shoo Fly P&P
170. ARH-SD T402 – Archer-Sidney 115kV Transmission Line Kimball City Shoo Fly P&P
TRANSMISSION ELECTRICAL:
171. ARH-SD 1003 – Archer-Sidney 115kV Transmission Line Material Quantities
172. ARH-SD 1004 – Archer-Sidney 115kV Transmission Line Vibration Dampers
173. 41 1012 Rev. C – Wood Pole Structures Grounding Details
174. 41 1018 Rev. C – Steel And Concrete Pole Structures OGW Assembly
175. 41 1019 Rev. D – Wood Pole Structures Overhead Ground Wire Assembly
176. 41 1022 Rev. C – Tension Insulator Assemblies Single String
177. 41 1024 Rev. B – Horizontal Post Insulator Assemblies
178. 41 9029 Rev. B – Aerial Patrol Warning Signs And Marker Ball
179. 41 9026 Rev. C – Aerial Patrol Warning Signs Detail And Locations
COMMUNICATIONS:
180. KB 4051 – Comm Area Floor Plan
181. KB 4052 – Comm Cable Ladder Plan
182. KB 4053 – Comm Grounding Plan
183. KB 7050 – Comm Rack Elevations
184. KMW 7252 EI – 20’ X 10’ Radio Building ES1020-9 (Existing Installation)
GEOLOGY:
185. KB 8000 – Borehole Location Plan
186. KB 8001 – Subsurface Exploration Penetration Resistance and Log PR 90-1
187. KB 8002 – Subsurface Exploration Penetration Resistance and Log PR 90-2
188. KB 8003 – Subsurface Exploration Penetration Resistance and Log PR 90-3
189. KB 8004 – Boring Log No. BH-1
190. KB 8005 – Boring Log No. BH-2
191. KB 8006 – Boring Log No. BH-3
192. KB 8007 – Description of Symbols and Abbreviations
164a. ARH-SD 1901 - Archer-Sidney 115kV Transmission line Kimball Sub Approach Spans
S
U
I T
A
B
L
E
F
O
R
C
N
S
T
R
U
C
T
I
N
A
M a y p m
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
RURAL ELECTRIC NO.1
KB 343
DISC SW WX3A 34.5KV
RURAL ELECTRIC NO.1
KB 341
DISC SW YX3A 34.5KV
RURAL ELECTRIC NO.1
KB 342
PCB JX3A 34.5KV
RURAL ELECTRIC NO.1
KB 345
DISC SW YX3B 34.5KV
TRANSFORMER KY1A
KB 269
DISC SW YY2A 115KV
SIDNEY LINE
KB 161
DISC SW WY1A 115KV
RURAL ELECTRIC NO.3
KB 443
DISC SW WX4A 34.5KV
RURAL ELECTRIC NO.3
KB 441
DISC SW YX4A 34.5KV
RURAL ELECTRIC NO.3
KB 442
PCB JX4A 34.5KV
RURAL ELECTRIC NO.3
KB 445
DISC SW YX4B 34.5KV
RURAL ELECTRIC NO.2
KB 543
DISC SW WX5A 34.5KV
RURAL ELECTRIC NO.2
KB 541
DISC SW YX5A 34.5KV
RURAL ELECTRIC NO.2
KB 542
PCB JX5A 34.5KV
RURAL ELECTRIC NO.2
KB 545
DISC SW YX5B 34.5KV
SIDNEY/ARCHER LINE
KB 162
PCB JY1A 115KV
ARCHER LINE
KB 163
DISC SW WY1B 115KV
SIDNEY LINE
KB 169
DISC SW YY1A 115KV
SIDNEY LINE
VY1A1
CCVT 115KV
SIDNEY LINE
VY1A2
CCVT 115KV
SIDNEY LINE
VY1A3
CCVT 115KV
SIDNEY LINE CCVT VY1A
EY1A
SECONDARY FUSE
SIDNEY LINE
VY1B1
CCVT 115KV
SIDNEY LINE CCVT VY1B1
EY1B
SECONDARY FUSE
TRANSFORMER/SIDNEY LINE
KB 262
PCB JY2A 115KV
SIDNEY LINE
KB 263
DISC SW WY2B 115KV
TRANSFORMER KY1A
VY2A1
CCVT 115KV
TRANSFORMER KY1A
VY2A2
CCVT 115KV
TRANSFORMER KY1A
VY2A3
CCVT 115KV
TRANSFOMER CCVT VY2A
EY2A
SECONDARY FUSE
TRANSFORMER BUS
KB 261
DISC SW WY2A 115KV
TRANSFORMER/KIMBALL
KB 462
PCB JY4A 115KV
TRANSFORMER BUS
KB 463
DISC SW WY4B 115KV
CITY OF KIMBALL LINE
KB 469
DISC SW YY4A 115KV
CITY OF KIMBALL LINE
VY4A1
CCVT 115KV
CITY OF KIMBALL LINE
VY4A2
CCVT 115KV
CITY OF KIMBALL LINE
VY4A3
CCVT 115KV
CITY OF KIMBALL CCVT VY4A
EY4A
SECONDARY FUSE
CITY OF KIMBALL LINE
VY4B1
CCVT 115KV
CITY OF KIMBALL CCVT VY4B1
EY4B
SECONDARY FUSE
CITY OF KIMBALL LINE
KB 461
DISC SW WY4A 115KV
ARCHER/CITY OF KIMBALL
KB 662
PCB JY6A 115KV
CITY OF KIMBALL LINE
KB 663
DISC SW WY6B 115KV
ARCHER LINE
KB 669
DISC SW YY6A 115KV
ARCHER LINE
VY6A1
CCVT 115KV
ARCHER LINE
VY6A2
CCVT 115KV
ARCHER LINE
VY6A3
CCVT 115KV
ARCHER LINE CCVT VY6A
EY6A
SECONDARY FUSE
ARCHER LINE
VY6B1
CCVT 115KV
ARCHER LINE CCVT VY6B1
EY6B
SECONDARY FUSE
ARCHER LINE
KB 661
DISC SW WY6A 115KV
GROUND FAULT CIRCUIT
VW1A1
VT 12.47KV
GROUND FAULT CIRCUIT
VW1A2
VT 12.47KV
GROUND FAULT CIRCUIT
VW1A3
VT 12.47KV
GROUND FAULT CIRCUIT
RW1A
RESISTOR 208V
GROUND FAULT CIRCUIT
EW1B
TERMINAL BLOCKS
KY1A
KB 123
INT SW WW1A 12.47KV
KY1A
KB 121
FUSE DISC FW1A 12.47KV
STATION SERVICE XFMR
KW1A
PRIMARY FEED
STATION SERVICE XFMR
KY4A1
ALTERNATE FEED
KY4A1
KB 421
FUSE DISC FY4A1 115KV
STATION SERVICE
SSA
400A 240V
STATION SERVICE
SSB
400A 240V
STATION SERVICE
ATS
400A 240V
STATION SERVICE
DWA
240/120V
LIGHTING
LCU
CONTACTOR
STATION SERVICE
SSC
400A 240V
STATION SERVICE
MDP
600A 240V
RURAL ELECTRIC
VX3A1
VT 34.5KV
RURAL ELECTRIC
VX3A2
VT 34.5KV
RURAL ELECTRIC
VX3A3
VT 34.5KV
RURAL ELECTRIC VT VX3A
EX3A
SECONDARY FUSE
RURAL ELECTRIC
QX3A1
CT 34.5KV
RURAL ELECTRIC
QX3A2
CT 34.5KV
RURAL ELECTRIC
QX3A3
CT 34.5KV
RURAL ELECTRIC CT QX3A
EX3B
TERM BLOCKS FOR QX3A
S
U
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
AutoCAD SHX Text
WESTERN AREA POWER ADMINISTRATION
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF ENERGY
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text S:\projects\Substations\Kimball\Kimball.04\Drawings\DesignDrawings\C3D\kb_0023.dwg Last Saved By: Diekman, Corey on 1/21/2020 4:35 PM Last Saved By: Diekman, Corey on 1/21/2020 4:35 PMDiekman, Corey on 1/21/2020 4:35 PM on 1/21/2020 4:35 PM1/21/2020 4:35 PM
AutoCAD SHX Text
HEADQUARTERS - LAKEWOOD, COLORADO
AutoCAD SHX Text
KIMBALL SUBSTATION
AutoCAD SHX Text
NEBRASKA
AutoCAD SHX Text
TOPOGRAPHY
AutoCAD SHX Text
C. DIEKMAN
AutoCAD SHX Text
G. CRAWFORD
AutoCAD SHX Text
JANUARY 21, 2020
AutoCAD SHX Text
KB
AutoCAD SHX Text
AutoCAD SHX Text
CIVIL ENGINEERING MANAGER
AutoCAD SHX Text SITE CONTROL: 502 NORTH 500205.77 500205.77 EAST 642222.98 642222.98 ELEV 4800.13 4800.13 BRASS USBR CAP IN CONCRETE 500 NORTH 500129.54 500129.54 EAST 642358.44 642358.44 ELEV 4800.05 4800.05 SET 3/4"X30" REBAR AND ALUM WAPA CAP
AutoCAD SHX Text PROJECTION NEBRASKA STATE PLANE COORDINATES (GRID) DATUM HORIZONTAL: NAD83(2011) VERTICAL: NAVD88 UNITS US SURVEY FEET
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
SET 3/4"X30" REBAR & ALUM. WAPA CAP
AutoCAD SHX Text
BOUNDARY LINE
AutoCAD SHX Text
FENCE LINE
AutoCAD SHX Text
SECTION AND 1/4 SECTION LINE
AutoCAD SHX Text
FACILITY FENCE
AutoCAD SHX Text
LAND SURVEYOR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text 1"=50'-0"
AutoCAD SHX Text
XREF(S) =
AutoCAD SHX Text
XR
AutoCAD SHX Text
KB_9510
AutoCAD SHX Text
FOUND MONUMENT (AS NOTED)
AutoCAD SHX Text
WAPA BC IN CONC.
AutoCAD SHX Text
WAPA BC IN CONC.
AutoCAD SHX Text
WAPA BC IN CONC.
AutoCAD SHX Text
WAPA BC IN CONC.
AutoCAD SHX Text
SECTION CORNER 2-1/2 ALUM. CAP L.S. 300
AutoCAD SHX Text
USBR BC IN CONC.
AutoCAD SHX Text
CATTLE WATER
AutoCAD SHX Text 28 27 33 34
AutoCAD SHX Text
EXISTING WAPA YARD
AutoCAD SHX Text
EXISTING COMM. SITE
AutoCAD SHX Text
COUNTY ROAD 73
AutoCAD SHX Text
UNDERGROUND ELECTRIC LINE
AutoCAD SHX Text
UNDERGROUND WATER LINE
AutoCAD SHX Text
UNDERGROUND GAS LINE
denton Suitable for Construction
I T
A
B
N
S
T
R
U
C
T
I p
LEGEND
o ___________ FOUND MONUMENT CAS NOTED)
• ___________ SET MONUMENT
-- ________ SLOPE DIRECTION OF FINISHED
GRADE ELEVATION
SG ___________ SUBGRADE ELEVATION
FG ___________ FINISHED GRADE ELEVATION
EOA __________ EDGE OF ASPHALT
EOC __________ EDGE OF CONCRETE
TOC __________ TOP OF CONCRETE
EOSW __________ EDGE OF SIDEWALK
ETW __________ EDGE OF TRAVEL WAY
PC ___________ POINT OF CURVE
PT ___________ POINT OF TANGENT
POC __________ POINT ON CURVE
PCC __________ POINT OF COMPOUND CURVE
PRC __________ POINT OF REVERSE CURVE
HP ___________ HJGH POINT
LP ___________ LOW POINT
GB ___________ GRADE BREAK
AP ___________ ANGLE POINT
FL ___________ FLOWLINE
RCP ___________ REINFORCED CONCRETE PIPE
HDPE __________ HIGH DENSITY POLYETHYLENE PIPE
FES __________ FLARED END SECTION
XING __________ CROSSING
£ ___________ CENTERLINE
--- - - - --- BOUNDARY LINE
-- X --X -- X -- CHAINLINK FENCE
- X -- X -- X -- EXISTING FENCE LINE
----0----0----0 EXISTING BARBWIRE FENCE LINE
---- SECTION AND 1/4 SECTION LINE
- - -1400- - - EXISTING CONTOUR (5' MAJOR)
------------ EXISTING CONTOUR Cl' MINOR)
----1400---- CONTOUR (5' MAJOR)
- - - - - - - - -- CONTOUR C 1' MINOR> ------------------------------- SURFACE BOUNDARY
--------+--- FL
--w--w--w-- EXISTING WATERLINE
--G--G--G-- EXISTING GAS LINE
�• NNNN N N NN ■::] CULVERT
t----------1 EXISTING CULVERT
E4 ------- 10' BERM WITH FENCE
TOPOGRAPHY ___________________ KB 0023
CONCRETE ENCASED
DUCT BANK SECTION ______________ KB 1731
FOUNDATION/STRUCTURAL DATA AND
DRAWING INDEX ________________ KB 2000
GRADING PLAN __________________ KB 2052
GRADING AT SERVICE
BUILDING DETAILS ______________ KB 2053
SECTIONS _____________________ KB 2054
DETAILS _____________________ KB 2055
NOTES
1- GRADING ELEVATIONS ARE SHOWN TO FINISHED GRADES- SUBGRADE
IS 6" BELOW FINISHED GRADE_
2 _ SLOPE GRADES UNIFORMLY BETWEEN ELEVATIONS -
3_ ENTIRE AREA OF SUBSTATION YARD TO A DISTANCE OF 8'-0"
OUTSIDE OF FENCE, IS TO HAVE 3" WASHED CRUSHED ROCK OVER
6" NDOT ROAD BASE_
4_ PLACE RIPRAP ON INLET AND OUTLET AS DIRECTED- ON OUTLETS
RIPRAP CONSISTS OF 1 '-0" MINIMUM DEPTH, AND BEDDED IN 6"
SAND AND GRAVEL.
5_ INSTALL STRAW EROSION CONTROL BLANKET ON ALL DISTURBED
GRADED SLOPES.
6_ ATTACH 12" HDPE FLARED END SECTIONS ON INLETS AND OUTLETS
OF ALL 12" HDPE.
EXPLANATION
Q INDICATES REVISIONS
UPDATED DRAWING SCALE BLOCK FROM 1"=30'
TO 1"=40'. UPDATED CATTLE GUARD LABEL
AND UPDATED ACCESS ROAD LABEL IN LEGEND
UPDATED REFERENCE DRAWINGS FID _
UNITED STATES DEPARTMENT OF ENERGY
WESTERN AREA POWER ADMINISTRATION HEADQUARTERS - LAKEWOOD, COLORADO
KIMBALL SUBSTATION
NEBRASKA
CIVIL
SITE PLAN
DESIGNED �E�R1._C�F�NCH II _ _ APPROVED GINA CRA\1/FORD ______ _
CIVIL ENGINEERING MANAGER
I
4795.22 Brass Cap
WAPA BC
I
I
I
I
I
I
X X
I / I /
��t=;;�+J..l!:".�-,r-
=x==vx==,-- X
I
X
X X
PROPERTY LINE =x--x--x
'--........ ::::,,. =x==vx= 'X-.----"'==x==x= x�x x x
4 STI<AND
BARBWIRE FENCE
1' INSIDE PROPERTY LINE
HP=4800.00
�t-4798
FL=4795.66
LEGEND
o ___________ FOUND MONUMENT IAS NOTED!
•-----------SET MONUMENT
-- ________ SLOPE DIRECTION OF FINISHED
GRADE ELEVATION
EOVG __________ EDGE OF VALLEY GUTTER ELEVATION
SG ___________ SUBGRADE ELEVATION
FG ___________ FINISHED GRADE ELEVATION
EOA __________ EDGE OF ASPHALT
EOC __________ EDGE OF CONCRETE
TQC __________ TOP OF CONCRETE
EOSW __________ EDGE OF SIDEWALK
ETW __________ EDGE OF TRAVEL WAY
PC ___________ PQINT OF CURVE
PT ___________ POINT OF TANGENT
POC __________ POINT ON CURVE
PCC __________ POINT OF COMPOUND CURVE
PRC __________ POINT OF REVERSE CURVE
HP ___________ HIGH POINT
LP ___________ LOW POINT
GB ___________ GRADE BREAK
AP ___________ ANGLE POINT
FL ___________ FLOWLINE
RCP ___________ REINFORCED CONCRETE PIPE
HOPE __________ HIGH DENSITY POLYETHYLENE PIPE
FES __________ FLARED END SECTION
XING __________ CROSSING
t ___________ CENTERLINE
--- - - - --- BOUNDARY LINE
-- X -- X -- X -- CHAINLINK FENCE
-- X -- X -- X -- EXISTING FENCE LINE
----0-----0---- EXISTING BARBWIRE FENCE LINE
---- SECTION AND 1/4 SECTION LINE
- - -1400- - - EXISTING CONTOUR 15' MAJOR)
------------ EXISTING CONTOUR 11' MINOR)
----1400---- CONTOUR 15' MAJOR)
CONTOUR I 1 ' MINOR l
------------------------------- SURFACE BOUNDARY
------;,-------;,--- FL
--w--w--w-- EXISTING WATERLINE
--G--G--G-- EXISTING GAS LINE
�- ■ ■ ■ ■ ■ ■ ■ ■ ■1 CULVERT
�----------:J EXISTING CULVERT
F4 ______ _ 10' GRAVEL BERM WITH FENCE
TOPOGRAPHY ___________________ KB 002
CONCRETE ENCASED
DUCT BANK SECTION ______________ KB 1731
FOUNDATION/STRUCTURAL DATA AND
DRAWING INDEX ________________ KB 2000
SITE PLAN ____________________ KB 2051
GRADING AT SERVICE
BUILDING DETAILS ______________ KB 2053
SECTIONS _____________________ KB 2054
DETAILS _____________________ KB 2055
NOTES
1. GRADING ELEVATIONS ARE SHOWN TO FINISHED GRADES. SUBGRADE
IS 6" BELOW FINISHED GRADE.
2. SLOPE GRADES UNIFORMLY BETWEEN ELEVATIONS.
3. ENTIRE AREA OF SUBSTATION YARD TO A DISTANCE OF 8'-0"
OUTSIDE OF FENCE, IS TO HAVE 3" WASHED CRUSHED ROCK OVER
6" NDOT ROAD BASE.
4. PLACE RIPRAP ON INLET AND OUTLET AS DIRECTED. ON OUTLETS
RIPRAP CONSISTS OF 1 '--0" MINIMUM DEPTH, AND BEDDED IN 6"
SAND AND GRAVEL.
5. INSTALL STRAW EROSION CONTROL BLANKET ON ALL DISTURBED
GRADED SLOPES.
6. ATTACH 12" STEEL FES ON INLETS AND OUTLETS OF ALL 12"
HOPE.
EXPLANATION
Q INDICATES REVISIONS
UPDATED DRAWING SCALE BLOCK FROM 1 "=30'
TO 1 "=40' , UPDATED CATTLE GUARD LABEL
AND UPDATED ACCESS ROAD LABEL IN LEGEND
UPDATED REFERENCE DRAWINGS FID.
SUPERSEDES DWG NO. KB-2011A CIN PART>
KIMBALL SUBSTAION
NEBRASKA
CIVIL
GRADING PLAN
DESIGNED FREDERICK FRENCH II _ _ APPROVED GINA CRAWFORD ______ _
;i;
C w
QJ
a (/J
- a <t .0 " E
I/
O N o a N .o
N"' a, C � 0 c 2 O 00
- .0 C �
" 00 QJ u w "O' W 0
- L
FINISHED
FLOOR EL= 100'-00"
BUILDING FOUNDATION
SEE SERVICE BUILDING
STRUCTURAL DRAWINGS
���6� H
��= 100'-00"
BUILDING FOUNDATION
SEE SERVICE BUILDING
STRUCTURAL DRAWINGS�
CL cii XREF CSl:
VARIES
BUILDING
ENTRY PAD
SEE SERVICE
BUILDING
STRUCTURAL DRAWINGS� FG EL = 99'-2" AT BUILDIN"._ _ � --------
13'-6"
SCALE: 1 "=1 '
13'-6"
FINISHED GRADE
GRADING AT BUILDING, TYP
DETAIL B
SCALE: 1 "=1'
13'-6"
3" WASHED CRUSHED ROCK
OVER 6" NDOT ROAD BASE
SUBGRADE
FG EL = 98'-6""
AT GRADE BREAK
3" WASHED CRUSHED ROCK
OVER 6" NDOT ROAD BASE
SUBGRADE
13'-6"
4-SIDES,
1YP
13'-6"
4-SIDES, 1YP
-;;,/,�y/'!'.:,vy.
BLDG PAD
FG EL FLAT
(SEE GRADING PLAN>
PLAN
BLDG PAD
SLOPE FG ELEVATION
DOWN FROM
BLDG SEE DETAILS A, B, C
BLDG PAD FG EL
FLAT (SEE GRADING
PLAN> B, C
SECTION AND TYPICAL GRADING
AT BUILDING PAD
DETAIL D
1''=1'
LEGEND
EL ELEVATION
----- FINISHED GRADE ELEVATION FG _____ SUBGRADE GRADE ELEVATION SG _____ EXISTING GROUND ELEVATION
��===== GRADE BREAK
EARTHFILL
3,, WASHED CRUSHED ROCK
OVER 6" NDOT ROAD BASE
NOTE
ELEVATION 100'-0"=CFG @ BLDGl+10". 1. FINISHED FLOOR
REFERENCE DRAWINGS
TOPOGRAPHY - - - - -
CONCRETE ENCASED
__ KB 0023
DUCT BANK SECTION ______ _
FOUNDATION/STRUCTURAL DATA AND
DRAWING INDEX_____
_ __ KB GRADING PLAN - - -
_____ KB 2054 SECTIONS________________
KB 2055 DETAILS ____________________ _
EXPLANATION
Q INDICATES REVISIONS
A
8-12-20 UPDATED REFERENCE DRAWINGS FID.
A7-FF
UNITED ST
EA
ATEP8W��™l�l4iNf���ATION WESTEH��Do�fRTERS _ LAKEWOOD COLORADO
KIMBALL SUBSTATION
NEBRASKA
GRADING AT SERVICE
BUILDING DETAILS
DESIGNED �E�R_I_C�F��_!I_ - - APPROVED %½�TL �����RING MANAGER - -
MAY 15, 2020 KB 2053
.0 •• L'tJ V V o>> 0 0 E<ll 7� -00 -o
_g--' E o, ,_ 3 7� O' 0 "'" �:i:l �"1 V .o >-" L/ � 0 00"1 �� Co, .3 ,::
/3 �� 0 o "C C /c,, V Viii •• V a.= 3 0
2 0 Ee,_-"' 0 .,. .0 •• E
�� ON-0 0 N .o E N"'
�/ 00 C,,C � a c �
SECTION A-A (2051)
4815�-
-B-
3.
-10
14(-oo s-o
14-
- B-. ---
I
I ____ I ____ I ____
I ____ I ---�
I s_
_ 1 p.---�
I
I
I
I
I
I
I l
-----s oo
.o o
-_s- 1·------------4815
3.00' P.q.c 3. o· P.C.C VALIEY GUTTER
VALLEY GU TER
u
� 4810-t-----+-+---t----t-�00 �-t-----+----+-+-----+----t-----+------+----+------+----+-----+------+-----+------+-----t-----+----t-----+------+----+-----+----t-t----,--+------+----+------+-t----+------t-4810
WO --'O �, ::;� ::;�
�e f5� f5�
4805-t-----+-+---t----t--+--l-----+----+-+-----+----+-----+-------t----+-----+----+-----+------+t----+------+----+-----+----t-----+------+----+-----+--�(D,"" ...... ,__�(D."'"..+-------t----+-----+-l----+------t-4805 a.111 Q. II
EXIi TING �e �e
�¼ii���� J:1<2:!°�S& B r�� ES & E
GROIND v-FENCE
FINISHED G1:C,.D7' '
-- � WR 6fHi_D_ �------ ---- ----------
0-'-P-.- � --c-_ - ,��.d � o
�uri�R� l,��
E 5 FINISHEJ
I / �A I �7 Tf
..ElliISHED_GRADE \
--,-r--/--,- """"""=-uc -t------.1;;;2,·· .c!
r =E'L rFr,Esc----t-t -----t-----i-4500
. II ,,.._... 33.40' ~ --i', VALL� o �� r��\
0 5% I ------------- ---------- - - !',·.\ 2.0% 7.4% (NOTE 9)7 r��· 0)1
�1� ;�PRAP
::s,.,,,,'\\,,'f� :::,y�i· ):JD� @l .5% (NOTE � \ \ · . , . . · . � - -+ 1 e1,g.2• -1.-
183.10'1 ~ I 1�.00' 5-60· 14Jo· vAI�E o ; �fJrn
FL 3.00' P P.C
VALLEY GUT
:�7
NOTE
FINISHED GI
1- ---1.2% ,.....- \\� \\'g'<',.,,:,y �\ .OD" P.f.C
VALLEY GUTirER 'o w ai n. Ol
�1 w �-g
WO --'O (D CX)
<.> II ""�
NO E 5 & E
5& 8
} FI !SH ED
GR JJE
�� �-7 32 !l-o' ~
2" HOPE �.5% (NOTE
�\\'..-\\\� '1/,\1/\\\/ "'-12" �EL FES...,,/
·NO-T -9
---.... .... r--
��\c � •a;
w" n. Ol
�1
:.00'--1'-=f
VALLEY GUT
CNOTE
p::,-,.,, ,;, /
EXIST
_[GROUN
.e - - ·�\ 0)
I 183.J
3_; • P.C.C VALIEY GUTTER
NG
b FL �.00" P.P.C
,VAL EY GUTTER=
r- ____ -j-u� SHED GRAD E ---------- ---------- ------ -----
0.5
��� ���� ��� S\�f'' \/,,\Y ,\<\\·;'.,) i%�� t:0'5\'K\\'? ���\
1/
/.-:�\y_ �\;:'.<0 �\\::<y,.,, '" \ \c;'\ \c(\\ ;:'.,�\%\ r:��� ��\\:S,;\\ t<0�'\S':
u\\\;,v \/,\ /�\))'/\\\;(
SECTION B-B (2051)
���\y_,\' �0\" w a. Cl :,:
8.00' 10.00' 35.22' I
1q.OO'
6"-9" RIPRAP
<O ...
:::,"": :::,"! o:<Xl o:<Xl wa> wa> ,nr-- ,nr--
a. II a. II OC> OC> t-L,.. t-L,..
V-.
FENCE
,NOTE 5
&-B i, ,i�ncu 12'
STEEL FES
_ !',·.\ •• 1;8% GR
I D E !NOTE 9l 6.,_9, RIPRAP s:'-0,��� $:��;,� B\\"' �,,% �R:!F; JYi:- v:..\\':(\\ ' "! < NOTE 9 l \ ".'.,\ "\\Y\�\)) :\\ �'0\f -;_;\ \"(,,,<,1/ ,, � ,, �1/);-;;..\� y:;,-,>::-\\ ;/, / '::;_'0:\ \\\�'<✓< 1 1 "/,>;:-);-;;..\\),, � 1�
-230 -220 -210 -200 -190 -180 -170 -160 -150 -140 -130 -120 -110 -100 -90 -80 -70 -60 -50 -40 -30 -20 -10 10 20 30 40 50
SECTION C-C (2051)
4815�-----------------------------�4815
387.50' ~
3.00 P.C.C
VALLE GUTTER
8.00' 10.00' .23' 10.,0· 15.00'
6"-9" RIPRAP
4810 +-----+----t---- +-+----t--t- - +--+---+---+-----+4810
<O ...
:::,+ :::e "' o:<Xl o:<Xl wa> wa> a,r-- a,r--4805 +-----+----+---=t.rY�-�1-d--1---+--+--
n. II n. II f2� f2�
CX)
�� <( :'\ 4805 ClW
EXPLANATION
Q INDICATES REVISIONS
0 � ;
ON
o-"'"' �g
II
NOTES
1. PROVID E BOLTS TH RU THE HOPE PIPE AT INLET END S, TH IS APPL YS
TO ALL HD PE PIPE TH AT EXIT TH E YARD .
2. INSTALL 12" STEEL FES AT INLET AND OUTLET OF 12" HOPE PIPES.
3. ENSURE ALL HOPE PIPE ARE BOND ED TO GROUND ING GRID .
4. PLACE 6"-9" RIPRAP PER CONSTRUCTION STAND ARD AS D IRECTED .
6"-9" RIPRAP CONSISTS OF 1 '-0" MINIMUM DEPTH.
5. WASHED CRUSH ED ROCK WILL CONSIST OF ¾" FRACTURED FACED ROCK
WITH A MIN. OF TWO FRACTURED FACES.
6. SEE D ETAIL "A" (2055).
7. SEE D ETAIL "B" C2055l.
8. SEE D ETAIL "C" C2055l.
9. SEE D ETAIL "D " (2055l.
10. SEE D ETAIL "E" (2055).
TOPOGRAPHY ___________________ KB 0023
CONCRETE ENCASED
DUCT BANK SECTION ______________ KB 1731
FOUNDATION/STRUCTURAL DATA AND
DRAWING INDEX ________________ KB 2000
SITE PLAN ____________________ KB 2051
GRADING PLAN __________________ KB 2052
GRADING AT SERVICE
BUILDING DETAILS ______________ KB 2053
DETAILS _____________________ KB 2055
KIMBALL SUBSTAION
NEBRASKA
CIVIL
SECTIONS
� '.g 10 0 10 20
�u 1,,,,,,,,,1 I I 30 vi I
�-� SCALE OF FEET
LL w 0: X
DESIGNED FREDERICK FRENCH II _ _ APPROVED QIN� �A!!:OB!') ______ _
CIVIL ENGINEERING MANAGER
111=10 1 -011
0/ VERT SCALE:1''=5' CA
E
MAY 15, 2020 KB 2054
���XR�E�F�C�S�l,--,-k�b_�9�5�1�0- [�S�,\�p-r-a�je-c�t-s�\S�u�b -s�ta�t�i- o -n s�\�K�im�b- a� l �l �...,,..o�d -e�l\�C�i-v�i l�3���k�b-_�9�51�0�.�dw_g_J....,...kb�_�9�5�00.-[�S�:\_p _r _a�je -c �t���S�u�b -st�a �t�i-o n- s��=;m�b-a � l �l �...,.,...a�d e....,.,.l\�k���9�5�0�0-.d�w-g-l-------------------------------------------------------------'-....&--"._ ________ _. ______ = ___ ....._ ....... =-.............. ___.
0:::
X
;i;
C
C
C w
QJ
lJ w a
(/J
.'3 a, � lJ a
J i a, C w
C oo a <t .Q " E
O N D 0 N-"
N>< a, C � 0 c�
2� C � W(fl
QJ u w lJ· w 0
LOCKNUT, lYP
DETAIL "B"
RIPRAP
SCALE:1"-1'
DETAIL "A"
12" HOPE & 6"-9" RIPRAP
SCALE:1"=1'
FINISHED GRADE
{OUTLET)
GROUND
3" lYP
1/2" GALV BOLT
(2 PLACES)
( 3" FROM END OF
PIPE I , SEE NOTE 1
it 12" HDPE
DETAIL "D"
12" HOPE CULVERT GRATING TO BE
INSTALLED ON INLET SIDE
SCALE: 1"-10'
DETAIL "C"
CRUSHED ROCK SURFACING TYP
SCALE:1"-1'
3.00'
P .C.C. VALLEY GUTTER
DETAIL "E"
3.0' LONGITUDINAL
P.C.C. VALLEY GUTTER
SCALE:1"-1'
LEGEND
FG _____ FINISHED GRADE ELEVATION
SG _____ SUBGRADE GRADE ELEVATION
EG _____ EXISTING GROUND ELEVATION
HOPE ____ HIGH-DENSITY POLYETHYLENE PIPE
RCP ____ REINFORCED CONCRETE PIPE
FES ----- FLARED END SECTION
t ______ CENTERLINE
� %,)),-,\\\;(;{ EARTHFILL
3" WASHED CRUSHED ROCK OVER 6" NDOT ROAD BASE
6"-9" RIPRAP W/ 6" SAND AND GRAVEL BEDDING
NOTES
1. PROVIDE BOLTS THRU THE HOPE PIPE AT INLET ENDS, THIS APPL YS
TO ALL HOPE PIPE THAT EXIT THE YARD.
2. ENSURE ALL HDPE PIPE ARE BONDED TO GROUNDING GRID.
3. PLACE 6"-9" RIPRAP PER CONSTRUCTION STANDARD AS DIRECTED.
6"-9" RIPRAP CONSISTS OF 1 '-0" MINIMUM DEPTH.
4. WASHED CRUSHED ROCK WILL CONSIST OF ¾" FRACTURED FACED ROCK
WITH A MIN. OF lWO FRACTURED FACES.
TOPOGRAPHY ___________________ KB 0016
CONCRETE ENCASED
DUCT BANK SECTION ______________ KB 1731
FOUNDATION/STRUCTURAL DATA AND
DRAWING INDEX ________________ KB 2000
SITE PLAN ____________________ KB 2051
GRADING PLAN __________________ KB 2052
GRADING AT SERVICE
BUILDING DETAILS ______________ KB 2053
SECTIONS _____________________ KB 2054
NOTES
(3.0' P.C.C. VALLEY GUTTER)
1. FIBER-REINFORCED PORTLAND CEMENT CONCRETE (P.C.C.)
SHALL HAVE THE FOLLOWING CHARACTERISTICS: 4000
PSI MIN. COMPRESSIVE STRENGTH@ 28 DAYS, MIN. 6
SACKS OF CEMENT PER CUBIC YARD WITH A MAX.
WATER/CEMENT RATIO OF 0.45, AIR ENTRAINMENT 6%
±1.5%, SLUMP AT 1 TO 4 INCHES.POLYPROPYLENE FIBERS
SHALL BE ADDED TO THE P.C.C. PER THE MANUFACTURER'
RECOMMENDATIONS.
2.LONGITUDINAL VALLEY GUTTER SHALL HAVE EXPANSION
JOINTS EVERY 30 FEET AND
WEAKENED PLANE JOINTS EVERY 10 FEET.
3. AGGREGATE BASE SHALL BE ENGINEERED TYPE 2, CLASS B,
COMPACTED TO A MINIMUM OF 95%.
EXPLANATION
Q INDICATES REVISIONS
UPDATED REFERENCE DRAWINGS FID.
UNITED STATES DEPARTMENT OF ENERGY
WESTERN AREA POWER ADMINISTRATION
HEADQUARTERS - LAKEWOOD COLORADO
KIM BALL SU BSTATION
NORTH DAKOTA
CIVIL
DETAILS
DESIGNED FREDERICK FRENCH II _ _ APPROVED GINA CRAWFORD ______ _
CIVIL ENGINEERING MANAGER
�,5-
XR
E C< F
S l�:--------------------------------------------------------------------------------------ic�
A Ei.L.......::M�A�Y�l�5�,�2�0�20;:_...1 __ ....!.:K�B:!.... __ L..�2�0�5�5:!.....J
I T
A
B
N
S
T
R
U
C
T
I p
O F
A p r
:1 a m
S
U
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
B
AutoCAD SHX Text 12-16-19
AutoCAD SHX Text
A7-MV
AutoCAD SHX Text
REVISED FOR STAGE 04 WORK.
AutoCAD SHX Text
EXPLANATION
AutoCAD SHX Text
INDICATES STAGE 04 WORK
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
1. GALVANIZE ALL MATERIAL AFTER FABRICATION. GALVANIZE ALL MATERIAL AFTER FABRICATION. 2. BOLTS 5/8"o HOLES 11/16" UNLESS NOTED. BOLTS 5/8"o HOLES 11/16" UNLESS NOTED. 3. ALL BEAM SEAT AND CLIP ANGLES L 3x2 1/2x3/8, 3" ALL BEAM SEAT AND CLIP ANGLES L 3x2 1/2x3/8, 3" O.S.L. FROM COLUMN UNLESS NOTED. 4. ALL PLATES 1/4" UNLESS NOTED. ALL PLATES 1/4" UNLESS NOTED. 5. PROVIDE BEVELED WASHERS FOR ALL BOLTS IN SLIPPED PROVIDE BEVELED WASHERS FOR ALL BOLTS IN SLIPPED FLANGES. 6. PROVIDE CONNECTIONS FOR FUTURE EXTENSIONS. PROVIDE CONNECTIONS FOR FUTURE EXTENSIONS. 7. "X" DIMENSIONS WILL BE FILLED IN WHEN APPROVED "X" DIMENSIONS WILL BE FILLED IN WHEN APPROVED DATA FOR EQUIPMENT IS RECEIVED. ADDITIONAL STRUCTURE MODIFICATIONS MAY BE NECESSARY FOR MOUNTING SWITCHES.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text "X"
AutoCAD SHX Text "X"
AutoCAD SHX Text 2'-3"
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text "X"
AutoCAD SHX Text 11"
AutoCAD SHX Text 11"
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I u g p
EI
EI
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
S
U
I T
A
B
N
S
T
R
U
C
T
I p
I T
A
B
N
S
T
R
U
C
T
I p
U
I T
A
B
N
S
T
R
U
C
T
I p
HVAC LEGEND
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BACKDRAFT DAMPER
ACCESS DOOR (AD)
ACCESS PANEL (AP)
DAMPERS:
FIRE (F) -
SMOKE (S) -
FIRE SMOKE (F/S) -
SECURITY BARS
FLEXIBLE DUCT
CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS
ELBOW
RISE IN RESPECT TO
AIR-FLOW
DROP IN RESPECT TO
AIR-FLOW
SQUARE OR RECTANGULAR
TO ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
RECTANGULAR DUCT
SECTION
RETURN AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR
DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
THERMOSTAT
CARBON DIOXIDE SENSOR
HUMIDISTAT
LINEAR SLOT DIFFUSER
VARIABLE AIR VOLUME
TERMINAL BOX
FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN
IN PARENTHESIS
EMERGENCY SHUT-OFF
SWITCH
MOTOR
FAN CONTROL PANEL
AIRFLOW ARROW
BREATHING AIR DROP
COMPRESSED AIR DROP
SUPPLY AIR OR OUTSIDE AIR
ROUND DUCT SECTION
RETURN AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT
SECTION
DIFFERENTIAL PRESSURE
SENSOR
STATIC PRESSURE SENSOR
OCCUPANCY SENSOR
ROUND & RECTANGULAR
DUCT TAKEOFF
CARBON MONOXIDE SENSOR
HS HYDROGEN SENSOR
CURRENT TRANSMITTERCT
BDD BACKDRAFT DAMPER
PIPE LINE ACCESSORIES
3-WAY VALVE
2-WAY VALVE
ANGLE VALVE
AUTOMATIC AIR VENT
ASSEMBLY
BACKFLOW PREVENTION
ASSEMBLY
BALANCING VALVE /
CIRCUIT SETTER
BALL VALVE
BLIND FLANGE
BUTTERFLY VALVE
CHECK VALVE
FLEX CONNECTION
FLOW ARROW
FLOW METER
GATE VALVE
GLOBE VALVE
HOSE GATE DRAIN VALVE
INSULATING FLANGE
MANUAL AIR VENT ASSEMBLY
- SEE SPECIFICATIONS FOR
APPROPRIATE VALVE TYPE
METER
MOTORIZED CONTROL VALVE
OUTSIDE SCREW & YOKE
VALVE
PIPE WITH HEAT TRACE
PLUG VALVE
PRESSURE GUAGE
SELF CONTAINED PRESSURE
REDUCING (REGULATING)
VALVE
PUMP
REDUCER (CONCENTRIC)
RELIEF, SAFETY OR THERMAL
RELIEF VALVE
REMOVABLE CAP
REMOVABLE PLUG
STRAINER
SUCTION DIFFUSER
TEST CONNECTION
THERMOMETER
UNION
Y-TYPE STRAINER
SPRING RETURN CLOSED
BALL VALVE
PIPE SYMBOLS
PIPE ELBOW
PIPE DOWN
PIPE UP
PIPE CONTINUATION
PIPELINE ABBREVIATIONS
MECHANICAL ABBREVIATIONS GENERAL NOTES:
CONSTRUCTION INTERFACE
DEMOLITION
EXISTING
NEW
EXISTING
EXISTING
NEW
DEMOLITION
AIR DISTRIBUTION
DEVICE IDENTIFICATION
AIR FLOW NECK SIZE
QUANTITY
SYSTEM TYPE SPEC. TYPE
SA-A
(2)175-8Ø
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS
APPLICABLE TO PROJECT. SEE PLANS FOR SPECIFIC SYMBOLS AND
ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM
ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL
SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED
BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL,
CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
5. UNLESS OTHERWISE INDICATED MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO
UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN
MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE,
EQUIPMENT, OR PIPE INSULATION UNLESS NOTED OTHERWISE.
9. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET
METAL SIZE SHALL BE AIR OPENING DIMENSION PLUS THE THICKNESS OF
ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT
INSTALLED, AIR OPENING SIZE AND SHEET METAL SIZE SHALL BE THE SAME.
10. LOCATE TRANSFER AIR DUCTS AND OPENINGS 24" ABOVE HIGHEST CEILING
ELEVATION UNLESS OTHERWISE NOTED.
11. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND
ARCHITECTURAL PLANS.
12. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND
COORDINATE WITH OTHER DEVICES LOCATED ON WALLS. COORDINATE WITH
ARCHITECTURAL WALL FINISHES.
13. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH STRUCTURAL
DRAWINGS AND SPECIFICATIONS.
14. CONTRACTOR SHALL AIR BALANCE ALL GRILLES AND EQUIPMENT TO CFM'S
SHOWN ON PLANS.
15. MOUNT ALL OVERHEAD MECHANICAL EQUIPMENT AND FIXTURES WEIGHING 31
POUNDS OR MORE TO SUPPORTS THAT SHALL RESIST FORCES OF 0.5 TIMES
THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE
EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.
BLWDN BLOWDOWN
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
COND CONDENSATE DRAIN
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
DI DEIONIZED WATER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
MW MAKEUP WATER (AFTER BACKFLOW
PREVENTER)
N NITROGEN
NG NATURAL GAS
O OXYGEN
PCR PUMPED CONDENSATE RETURN
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
V VACUUM
IA INSTRUMENT AIR
IH INFRARED HEATER
IN. W.C INCHES WATER COLUMN
LAT LEAVING AIR TEMPERATURE
LR LONG RADIUS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MFR MANUFACTURER
MJ MECHANICAL JOINT
MW MAKE-UP WATER (AFTER BACKFLOW
PREVENTER)
NC NORMALLY CLOSED (FAIL POSITION)
NG NATURAL GAS
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
OD OVERFLOW DRAIN
PB PARALLEL BLADE
PCW PROCESS COLD WATER
PFX PLATE AND FRAME HEAT EXCHANGER
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
RA RETURN AIR
RED REDUCER-REDUCING
RG REFRIGERANT HOT GAS DISCHARGE
RL REFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SHR SHORT RADIUS
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
ST STEAM TRAP
STM STEAM
SW SOCKET WELD
TA TRANSFER AIR
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB WET BULB
WE WELD END
WN WELD NECK
12"Ø ROUND DUCT DIMENSION
24x12 RECTANGULAR DUCT DIMENSION (INCHES)
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
AS AIR SEPARATOR
BBO BOILER BLOW-OFF
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BP BOOSTER PUMP
BS BRANCH SELECTOR (VRF SYSTEM)
CF CEILING FAN
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CRU CONTROL ROOM UNIT
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
DB DRY BULB
DH DEHUMIDIFIER
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
ER EXHAUST REGISTER
ERU ENERGY RECOVERY UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FCU FAN COIL UNIT
FD FEEDWATER
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
HWB HEATING HOT WATER BOILER
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
I.E. INVERT ELEVATION
4/03/2020
CU-1
CRU-2
CU-2
CU-3
CRU-3
EF-1
255-16x16
EA-A
HS
LVR-2
150-12x12
150-10x10
SA-B
150-12x12
RA-C
ERU-1
12x12 OA
1/4" RS
1/4" RS
1/4" RS
1/4" RL
1/4" RL
1/4" RL
5/8" COND
5/8" COND
5/8" COND
CRU-1
1" COND
10x10 EA11
A
C
B
14LVR-1
255-12x18
CONCRETE
SLAB
CONCRETE
SLAB
CONCRETE
SLAB
CONCRETE SLAB
CD-1
CD-2
GENERAL NOTES:
KEYED NOTES:
1. CONTRACTOR SHALL LOCATE EQUIPMENT
SUCH THAT ALL REQUIRED MAINTENANCE
CLEARANCE/ACCESS ARE COORDINATED
WITH WORK BY OTHER TRADES.
1. FURNISH AND INSTALL MACURCO GD-6
HYDROGEN SENSOR OR APPROVED EQUAL.
INSTALL HYDROGEN SENSOR AT MOUNTING
ELEVATION PER MANUFACTURER'S
RECOMMENDATIONS. INTERLOCK WITH EF-1
AND ERU-1. REFER TO CONTROL
SCHEMATIC ON SHEET 3305 FOR DETAILS.
2. WALL MOUNT CONTROL ROOM UNIT 9'-0"
AFF. INSTALL PIPING PER DETAIL 2 ON DWG
3303 AND SECTION A ON DWG 3306.
3. INSTALL CONDENSING UNIT ON
MANUFACTURER'S STANDARD 12" EQUIPMENT
STAND ON CONCRETE PAD WITH HILTI KWIK
BOLT3 EXPANSION ANCHORS 3/8"Ø WITH 3
1/2" EMBEDMENT INTO CONCRETE.
4. INSTALL LOUVER AT 8'-2" AFF.
CONTRACTOR TO VERIFY LOUVER IS
INSTALLED BELOW SOFFIT. REFER TO DETAIL
1 ON DWG 3303.
5. INSTALL EXHAUST FAN AT 6'-10" AFF.
REFER TO DETAIL 3 ON DWG 3303 AND
SECTION A ON DWG 3306. COORDINATE
MOUNTING LOCATION WITH FINAL APPROVED
CRANE AND TROLLEY.
6. INSTALL ENERGY RECOVERY UNIT AT 9'-5"
AFF. REFER TO SECTIONS B AND C ON
DWG 3306.
7. PROVIDE WITH MANUFACTURER STANDARD
10"x10" 45° EA WEATHERHOOD, GREENHECK
MODEL WTHD-10 OR APPROVED EQUAL.
PROVIDE WITH BACKDRAFT DAMPER AND BIRD
SCREEN PER DETAIL 1 ON DWG 3304.
MOUNT AT UNDERSIDE OF SOFFIT.
8. PROVIDE STANDALONE PROGRAMMABLE
THERMOSTAT. MOUNT AT 4'-8" AFF.
9. CONDENSATE PIPE SHALL EXTEND PAST
CONCRETE SLAB TO DRAIN ON GRAVEL
SURFACING. TURN DOWN TO SPLASH BLOCK.
10. FURNISH AND INSTALL OCCUPANCY SENSOR,
WATTSTOPPER MODEL DT355 OR APPROVED
EQUAL. MOUNT ON CEILING.
11. PROVIDE LINESET COVER FOR REFRIGERANT
PIPING THROUGH SOFFIT TO INDOOR UNIT.
REFER TO SECTION A ON DWG 3306.
12. PROVIDE WITH MOTORIZED DAMPER AT INLET
OF LOUVER PER DETAIL 1 ON SHEET 3303.
13. MOUNT BATTERY ROOM UNIT AT 7'-6" AFF.
INSTALL PIPING PER DETAIL 2 ON DWG 3303
AND SECTION A ON DWG 3307.
14. INSTALL LOUVER AT 1'-0" AFF. REFER TO
DETAIL 1 ON DWG 3303.
SCALE IN FEET
0 2' 4' 8'
N O R
THMECHANICAL FLOOR PLAN
4/03/2020
HEAT PUMP SCHEDULE
TAG NO. SERVICE
SENSIBLE
COOLING
CAPACITY (MBH)
COOLING
CAPACITY TOTAL
(MBH)
HEATING
CAPACITY
(MBH)
COMPRESSOR
TYPE
EFFICIENCY
(EER)
RATED
OUTDOOR
DB (°F)
REFRIGERANT
TYPE
ELECTRICAL
WEIGHT
(LBS)
SIZE
(H X W X D) (IN) REMARKS
VOLT PH. MCA
CU-1 BATTERY ROOM 15.76 21.4 25.4 INVERTER 12.5 95 R410A 230 1 17.5 108 30-5/16 x 35-7/16 x 12-5/8 1,2,3,4,5 CU-2 CONTROL ROOM 15.76 21.4 25.4 INVERTER 12.5 95 R410A 230 1 17.5 108 30-5/16 x 35-7/16 x 12-5/8 1,2,3,4,5 CU-3 CONTROL ROOM 15.76 21.4 25.4 INVERTER 12.5 95 R410A 230 1 17.5 108 30-5/16 x 35-7/16 x 12-5/8 1,2,3,4,5
CONTROL ROOM UNIT SCHEDULE
TAG NO. LOCATION
ALTITUDE
(FT.)
TOTAL
AIRFLOW
(CFM)
COOLING HEATING ELECTRICAL
WEIGHT
(LBS) REMARKSSENSIBLE
CAPACITY
(MBTUH)
EAT
DB
(°F)
LAT
DB
(°F)
LAT
DB
(°F)
HEATING
CAPACITY
(MBH)
VOLTS PHASE
CRU-1
BATTERY
ROOM 4800 1140 16.88 80.1 55 85 25.4 230 1 27 1,2,3,4
CRU-2
CONTROL
ROOM 4800 1140 16.88 80.1 55 85 25.4 230 1 27 1,2,3,4
CRU-3
CONTROL
ROOM 4800 1140 16.88 80.1 55 85 25.4 230 1 27 1,2,3,4
FAN SCHEDULE
MARK
AREA
SERVED
SERVICE
USED FOR FAN TYPE
ALT
(FT.)
AIRFLOW
(CFM)
FAN
SPEED
(RPM)
SPEED
CONTROL
EXTERNAL
STATIC
PRESSURE
(IN. W.G.)
SOUND
LEVEL
(LWA)
MIN.
MOTOR
HP
MOTOR
TYPE
STARTER /
DISCONNECT
PROVIDED BY
VOLTS PHASE
ROOF/WALL
OPENING
WEIGHT
(LBS) REMARKS
EF-1
BATTERY
ROOM
HYDROGEN
EXHAUST SIDEWALL 4800 255 1598 VARIABLE 0.25 48 0.066667 TENV MANUFACTURER 115 1 8.5 x 8.5 27 1,2,3,4
LOUVER SCHEDULE
TAG SERVICE
SIZE
(INXIN)
AIRFLOW
(CFM)
PRESSURE
DROP
(IN.W.C)
INTERLOCK
ACTUATOR
TYPE VOLTS PHASE REMARKS
LVR-1 BATTERY ROOM 18x12 255 0.13 EF-1 BELIMO 120 1 1,3,4,5 LVR-2 CONTROL ROOM 12x12 150 0.13 ERU-1 BELIMO 120 1 1,2,4,5
NOTES:
1. PROVIDE WITH BIRD SCREEN.
2. CONTROLS CONTRACTOR TO INSTALL 24 VOLT ACTUATOR AND INTERLOCK WITH ENERGY RECOVERY UNIT.
3. CONTROLS CONTRACTOR TO INSTALL 24 VOLT ACTUATOR AND INTERLOCK WITH EXHAUST FAN.
4. PROVIDE LOUVER WITH INTEGRAL FLANGE AND INSTALL ACCORDING TO DETAIL 1 ON SHEET 3303.
5. REFER TO SPECIFICATION SECTION 23 31 13 - METAL DUCTS FOR DAMPER REQUIREMENTS.
NOTES:
1. PROVIDE WITH BACKDRAFT DAMPER AND BIRD SCREEN.
2. PROVIDE WITH MANUFACTURER'S UNIT MOUNTED DISCONNECT ACCORDING TO ELECTRICAL SPECIFICATIONS.
3. PROVIDE MOTOR STARTER WITH AUXILiARY 120V SET OF DRY CONTACTS TO BE INTERLOCKED WITH DAMPER AND HYDROGEN SENSOR CIRCUIT. COORDINATE WITH
ELECTRICAL CONTRACTOR.
4. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME
AND MARK.
NOTES:
1. ELECTRICAL TO PROVIDE DISCONNECT PER ELECTRICAL SPECIFICATIONS.
2. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME AND MARK.
3. PROVIDE WITH LOW AMBIENT KIT.
4. HEATING CAPACITY RATED AT 47° F.
5. PROVIDE ON CONCRETE EQUIPMENT PAD WITH 12" STAND PER ARCH DRAWINGS.
NOTES:
1. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE
ENERGY STAR NAME AND MARK.
2. MOUNT UNITS ON WALL PER MANUFACTURER'S RECOMMENDATIONS.
3. POWER PROVIDED BY OUTDOOR UNIT, CONNECT PER MANUFACTURER'S RECOMMENDATIONS.
4. PROVIDE WITH MANUFACTURER'S STANDARD REMOTE PROGRAMMABLE THERMOSTAT.
DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)
TAG DESCRIPTION MOUNTING
THROW
PATTERN
BASIS OF DESIGN:
REMARKS
MFR.
MODEL
NO.
A EXHAUST AIR GRILLE WALL - TITUS 350-FL 1,2,3
B
SQUARE SUPPLY AIR
GRILLE SURFACE - TITUS 301-FL 1,2,3
C
RECTANGULAR RETURN
AIR GRILLE SURFACE - TITUS 350-FL 1,2,3
NOTES:
1. DIFFUSER SIZES ARE NOTED IN DRAWINGS.
2. COLOR SHALL MATCH ACOUSTICAL CEILING TILES OR WALL. COORDINATE WITH
ARCH PLANS.
3. PROVIDE PRODUCT BY BASIS OF DESIGN MANUFACTURER OR APPROVED EQUAL.
ENERGY RECOVERY UNIT SCHEDULE 2/2
TAG NO.
COOLING HEATING
APPROX. UNIT
WEIGHT (LBS)
UNIT ELECTRICAL
REMARKS
EAT DB
(°F)
EAT WB
(°F)
LAT
DB
(°F)
LAT WB
(°F)
TOTAL CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EAT
(°F)
LAT
(°F)
TOTAL CAPACITY
(MBH) VOLTS PHASE MOP MCA
ERU-1 94.7 60.2 80.1 60.3 0.15 0.15 -3.6 51 20.085 230 115 1 15 6.4 1,2,3,4,5,6
NOTES:
1.
PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR
NAME AND MARK.
2 2" MERV 8 FILTERS FOR OUTDOOR AND EXHAUST AIR OPENINGS PROVIDED BY MANUFACTURER.
3. PROVIDE ENERGY RECOVERY UNIT IN CONFIGURATION WITH END CONNECTIONS.
4. THE ENERGY RECOVERY UNIT SHALL BE PROVIDED FROM THE FACTORY WITH AN INTEGRAL CONTROL CENTER INCLUDING A SINGLE NON-FUSED
DISCONNECT, 24 VAC TRANSFORMER, TERMINAL STRIP, AND FAN STARTERS (CONTACTOR AND OVERLOAD).
5. PROVIDE WITH INTERNAL BACKDRAFT DAMPERS.
6. STANDARD SINGLE POINT POWER TO BE…