STATEMENT OF WORK
FTQW 21-2001 Repair Roof Fall Protection
1.0 SCOPE
Work will include the repair and recertification of building roof fall protection systems. Work will also include repair of roof damage caused by the fall protection system. The end product will be fully functioning, certified fall protection systems which do not cause roof damage.
Contractor will furnish all labor, supplies, parts, transportation, tools, equipment, and facilities necessary to perform work required to restore operations in accordance with this Statement of Work and specifications.
2.0 DESCRIPTION OF WORK
This work includes the repair and recertification of roof fall protection systems on Buildings 1171, 1172, 1173, 3127, 3129, 3132, 3225, and 3225-1. All buildings have standing seam metal roofs.
Building locations are denoted on the map in Attachment 1.
Fall protection systems on the above facilities was accomplished under a single project in 2012, therefore share similar products/materials and design philosophy. The systems are primarily comprised of the Evolution Horizontal Lifeline system, with D-rings provided for smaller roof areas.
As-built drawings from this effort are included in Attachment 2, which should be field verified by the contractor.
The primary issues observed with the fall protection system are failed intermediate brackets. These brackets appear to have been damaged by the snow loads. Additionally, many of the mounting plates have loosened and have slid down the roof seam. This is not an all-inclusive list of issues and should be field verified by the contractor. The repaired system shall be designed and installed to properly accommodate snow and ice loads and prevent further damage to the roof. Any changes to the system shall be submitted as markups to the as-built drawings.
The primary roof issues observed are failed surface coatings, missing fasteners, and damaged caps or flashing due to repeated contact between the cable and the roof. This appears to be caused by either the use of improper intermediate brackets which do not hold the cable far enough from the roof, loss of cable tension, too few intermediate brackets, etc. Photos from the Roof Condition Report are included in Attachment 3. This is not an all-inclusive list of issues and should be field verified by the contractor. Damaged roof components shall be properly repaired or replaced. Areas requiring resurfacing shall be prepared to remove corrosion, primed, and painted according to manufacturer’s instructions to maintain warranty. Paint codes of existing roof colors are provided in Attachment 4.
The contractor will be required to file a waste management plan for the contract, to include the types of waste which will be generated and the approximate quantities. Recycling is encouraged to the widest extent possible. Prior to contract closeout, weight tickets, or other similar documentation, must be provided showing final disposal of all waste materials.
The contractor will be required to submit a safety plan/outline prior to beginning onsite work under this effort.
All contractors performing work on Eielson AFB are required to complete onsite hazardous waste training provided by 354 CES/CEIEC. Contractor training must be completed two weeks prior to field work start date. Please contact 377-1659 to schedule a training for handling hazardous wastes, including aerosol can management. All costs associated with waste disposal are the responsibility of the contractor. Empty aerosol cans are the only waste accepted at the base hazardous waste facility for disposal. All hazardous wastes must be managed in accordance with the requirements for large quantity generators (40 CFR 26.17) under the resource conservation recovery act. Hazardous waste and non-regulated waste manifests must be signed by a designated POC prior to shipment off-base.
Please coordinate signature through the base hazardous waste facility (377-1668). Provide weight tickets for recyclables and materials that go to off-base landfills to solid waste program.
General work tasks include:
• Evaluate existing fall protection systems.
• Repair fall protection systems, to ensure replacement of failed components and ensure systems will not cause subsequent roof damage.
• Certify fall protection systems.
• Repair roof damage caused by fall protection systems.
3.0 GOVERNMENT FURNISHED MATERIALS: None
4.0 INSTRUCTIONS TO THE CONTRACTOR:
4.1 Photography is restricted to personnel who have worked through the Contracting Officer to obtain required permissions.
4.2 Facilities will remain occupied and in use during the duration of the project.
Contractor may need to phase work in order to maintain adequate building access and parking availability. The contractor will be responsible for coordinating with the Government prior to starting work in an area. The contractor will be responsible for establishing traffic control around work areas, as needed.
4.3 The contractor will have access to the work sites during normal duty hours of
Monday – Friday, 7:00 a.m. – 3:00 p.m, with exceptions of federal holidays and 168th Wing Alternate Work Schedule off days (Attachment 5). Any work outside of these hours must be coordinated with and approved by the Contracting Officer (CO) or Contracting Officer Representative (COR) a minimum of two business days in advance.
4.4 The period of performance runs for 75 days. Material lead times will be considered should the period of performance need to be extended.
4.5 The Contractor shall keep the work area clean of all debris on a daily basis or more often as required. The Contractor shall keep storage areas clean and orderly at all times. The Contractor shall dispose of combustible wastes at the end of each work day and under no circumstances allow them to accumulate. Hazardous materials must be handled according to the contract specifications.
4.6 Access and General Protection/Security Policy and Procedures. This standard language is for contractor employees with an area of performance within Government controlled installation, facility, or area. The contractor shall comply with all applicable installation/facility access and local security policies and procedures, which may be obtained from the Contracting Officer’s Representative (COR). The contractor shall also provide all information required for background checks to meet installation access requirements to be accomplished by the local installation’s Security Forces, Director of Emergency Services or local Security Office. The contractor shall ensure compliance with all personal identity verification requirements as directed by DoD, HAF and/or local policy. Should the Force Protection Condition (FPCON) change, the Government may require changes in contractor security matters or processes.
4.7 For Contractors that do not require CAC, but require access to a DoD Facility and/or
Installation. Contractor and all associated sub-contractors employees shall comply with adjudication standards and procedures using the National Crime Information Center Interstate Identification Index (NCIC-III) and Terrorist Screening Database (TSDB) (AFI 31-101 and AFI 10-245), applicable installation, facility and area commander installation/facility access and local security policies and procedures (provided by government representative), or, at OCONUS locations, in accordance with status of forces agreements and other theater regulations.
4.8 AT Level I Training. This standard language is for contractor employees with an area of performance within a Government controlled installation, facility or area. All contractor employees, to include subcontractor employees, requiring access to Government Installations, Facilities and Controlled Access areas shall complete AT Level I awareness training within 10 calendar days after contract start date or effective date of incorporation of this requirement into the contract, whichever is applicable. Certificates of completion for each affected contractor employee and subcontractor employee will be maintained by the COR or Antiterrorism Representative. AT level I Awareness Training is available through Joint Knowledge Online (http://jko.jten.mil/) by completing course JS-US007.
5.0 ATTACHMENTS
Attachment 1: 168th Wing Map Attachment 2: As-built Drawings Attachment 3: Photos from 2019 Roof Conditions Report Attachment 4: Paint Color Codes Attachment 5: 168 WG Calendar Attachment 6: Submittal Register
XX September 2020
END OF STATEMENT
1073586514N Polygon
1073586514N Polygon
1073586514N Rectangle
1073586514N Polygon
1073586514N Polygon
1073586514N Polygon
1073586514N Polygon
1073586514N Polygon
1073586514N Polygon
STRUCTURAL ABBREVIATIONS
AB ANCHOR BOLT
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECTURAL
ATR ALL THREAD ROD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAIL
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRNG BEARING
BSMT BASEMENT
BTWN BETWEEN
C CAMBER
CIP CAST IN PLACE
CJ CONTROL OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DF/L DOUGLAS FIR-LARCH
DIA DIAMETER
DIAG DIAGONAL
DIST DISTANCE
DL DEAD LOAD
DN DOWN
DTL DETAIL
DWG DRAWING
(E) EXISTING
EA EACH
EF EACH FACE
EL ELEVATION
EN EDGE NAIL
EQ EQUAL
EW EACH WAY
EXT EXTERIOR
FF FINISH FLOOR
FN FIELD NAIL
FLR FLOOR
FDN FOUNDATION
FT FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GLB GLUE LAMINATED BEAM
GWB GYPSUM WALL BOARD
HDG HOT-DIP GALVANIZED
HDR HEADER
HF HEM-FIR
HT HEIGHT
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
ID INSIDE DIAMETER
IN INCH
INT INTERIOR
JST JOIST
JT JOINT
K KIP(S)
KSI KIPS PER SQUARE INCH
L ANGLE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LVL LAMINATED VENEER LUMBER
LWC LIGHT WEIGHT CONCRETE
MAX MAXIMUM
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NOM NOMINAL
NTE NOT TO EXCEED
NTS NOT TO SCALE
(N) NEW
OC ON CENTER
OD OUTSIDE DIAMETER
OPP OPPOSITE
OWJ OPEN WEB JOIST
PAF POWDER ACTUATED FASTENER
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PT PRESSURE TREATED
QTY QUANTITY
RAD RADIUS
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
REV REVISED, REVISION
SC SLIP CRITICAL
SHT SHEET
SHT'G SHEATHING
SIM SIMILAR
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
SQ SQUARE
T&B TOP AND BOTTOM
T&G TONGUE AND GROVE
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TOF TOP OF FOOTING
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCING
VICINITY MAP
N.T.S.
S0.01
STRUCTURAL DRAWING INDEX
S0.01:
STRUCTURAL NOTES
VICINITY MAP
SCOPE OF WORK
S1.01:
BUILDING 1171 ROOF FALL PROTECTION LAYOUT
S1.02:
BUILDING 1172 ROOF FALL PROTECTION LAYOUT
S1.03:
BUILDING 3132 ROOF FALL PROTECTION LAYOUT
S1.04:
BUILDING 1173 ROOF FALL PROTECTION LAYOUT
S1.05:
BUILDING 3127 ROOF FALL PROTECTION LAYOUT
S1.06:
BUILDING 3129 ROOF FALL PROTECTION LAYOUT
S1.07:
BUILDING 32251 ROOF FALL PROTECTION LAYOUT
S1.08:
BUILDING 3225 ROOF FALL PROTECTION LAYOUT
S8.01:
DETAILS
PROJECT SCOPE:
THESE STRUCTURAL DRAWINGS ARE FOR THE ROOF
FALL PROTECTION LAYOUT ON (8) BUILDINGS AT THE
PROJECT SITE. EXCLUDED FROM MILLER CONSULTING
ENGINEERS, INC. SCOPE OF SERVICES IS THE DESIGN
OF THE STANDING SEAM METAL ROOF PANELS
SUPPORTING THE FALL PROTECTION SYSTEM.
S1.01
S1.01
S1.01
DETAIL REFERENCE
DETAIL SECTION CUT
BUILDING OR WALL
SECTION CUT
S1.01
ELEVATION OF WALL
OR FRAME
REVISION SYMBOL
GRID LINES
ROTATE VIEW SYMBOL
NORTH ARROW
REFERENCE ELEVATION
SURFACE - STEPPED
TOS
EL. 100'-0"
SURFACE - SLOPE UP
SURFACE - SLOP DOWN
SURFACE - SLOPE
TWO DIRECTIONS
STRUCTURAL DRAWING SYMBOLS
GENERAL
THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND CORRELATION OF ALL ITEMS AND WORK
NECESSARY FOR COMPLETION OF THE PROJECT AS INDICATED BY THE CONTRACT DOCUMENTS. SHOULD ANY
QUESTION ARISE REGARDING THE CONTRACT DOCUMENTS OR SITE CONDITIONS, THE CONTRACTOR SHALL
REQUEST INTERPRETATION AND CLARIFICATION FROM THE ENGINEER BEFORE BEGINNING THE PROJECT. THE
ABSENCE OF SUCH REQUEST SHALL SIGNIFY THAT THE CONTRACTOR HAS REVIEWED AND FAMILIARIZED
HIMSELF WITH ALL ASPECTS OF THE PROJECT AND HAS COMPLETE COMPREHENSION THEREOF. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMANCE TO ALL SAFETY REGULATIONS DURING
CONSTRUCTION.
THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS OTHERWISE
SPECIFICALLY NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OR CONSTRUCTION LOADS.
ONLY THE CONTRACTOR SHALL PROVIDE ALL METHODS, DIRECTION AND RELATED EQUIPMENT NECESSARY TO
PROTECT THE STRUCTURE, WORKMEN AND OTHER PERSONS AND PROPERTY DURING CONSTRUCTION. THE
CONTRACTOR SHALL, AT HIS OWN EXPENSE, ENGAGE PROPERLY QUALIFIED PERSONS TO DETERMINE WHERE
AND HOW TEMPORARY PRECAUTIONARY MEASURES SHALL BE USED AND INSPECT SAME IN THE FIELD. ANY
MATERIAL NOT AS SPECIFIED OR IMPROPER MATERIAL INSTALLATION OR WORKMANSHIP SHALL BE REMOVED
AND REPLACED WITH SPECIFIED MATERIAL IN A WORKMANLIKE MANNER AT THE CONTRACTOR'S EXPENSE.
THESE PLANS, SPECIFICATIONS, ENGINEERING AND DESIGN WORK ARE INTENDED SOLELY FOR THE PROJECT
SPECIFIED HEREIN. MILLER CONSULTING ENGINEERS DISCLAIMS ALL LIABILITY IF THESE PLANS AND
SPECIFICATIONS OR THE DESIGN, ADVICE AND INSTRUCTIONS ATTENDANT THERETO ARE USED ON ANY
PROJECT OR AT ANY LOCATION OTHER THAN THE PROJECT AND LOCATION SPECIFIED HEREIN. OBSERVATION
VISITS TO THE JOB SITE AND SPECIAL INSPECTIONS ARE NOT PART OF THE STRUCTURAL ENGINEER'S
RESPONSIBILITY UNLESS THE CONTRACT DOCUMENTS SPECIFY OTHERWISE.
NON STRUCTURAL PORTIONS OF PROJECT, INCLUDING BUT NOT LIMITED TO PLUMBING, FIRE SUPPRESSION, ELECTRICAL, MECHANICAL, LAND USE, SITE PLANNING, EROSION CONTROL FLASHING AND WATER-PROOFING
ARE BEYOND THE SCOPE OF THESE DRAWINGS AND ARE PROVIDED BY OTHERS.
BUILDING CODE
ALL PHASES OF THE WORK SHALL CONFORM TO THE 2009 INTERNATIONAL BUILDING CODE, INCLUDING ALL
REFERENCE STANDARDS, UNLESS NOTED OTHERWISE.
DESIGN LOADS
DESIGN LOADS TO THE FALL PROTECTION SYSTEM HAVE BEEN PROVIDED BY EXCALIBUR & ASSOCIATES AND
ARE AS NOTED ON THE LAYOUT PLANS.
MISCELLANEOUS FALL PROTECTION COMPONENTS
ALL S-5! CLAMPS SHALL BE INSTALLED AS RECOMMENDED BY THE CLAMP MANUFACTURER BASED ON
STANDING SEAM ROOF TYPE.
ANALYSIS OF PROPRIETARY FALL PROTECTION COMPONENTS IS EXCLUDED FROM THE SCOPE OF WORK.
STRUCTURAL STEEL
ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE ASTM A992 FOR W-SECTIONS AND ASTM A36 FOR ALL
OTHER SECTIONS, PLATES AND BARS.
UNLESS NOTED OTHERWISE, ALL BOLTS TO BE TYPE 316 STAINLESS STEEL, WITH MATCHING NUTS. NUTS
SHALL BE TIGHTENED TO A SNUG TIGHT CONDITION.
ALL STRUCTURAL STEEL SHALL HAVE ONE COAT OF PRIMER AND ONE FINISH COAT OF RUST INHIBITING PAINT
(COLOR BY OWNER).
STRUCTURAL NOTES
EIELSON AIR FORCE BASE
FAIRBANKS, ALASKA
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
R O
O F
A L L
P
R O
T E
C T
I O
N
E I E
L S
N
I R
R
C E
B
S
E
E X
C A
L I B
U
S S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S0.01
STRUCTURAL NOTES
STRUCTURAL ABBREV.
STRUCTURAL SYMBOLS
VICINITY MAP
SCOPE OF WORK
SHEET INDEX
BCH
110621
10.12.11
R
E C
O R
D
D
R A
W I N
G S
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
S1.01
ROOF FALL PROTECTION LAYOUT
BUILDING 1171
3/32" = 1'-0"
MAXIMUM DESIGN CABLE TENSION
= 2,022 lbs (4,044 lbs ULTIMATE)
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
4 D-RING -SEE DETAIL 4/S8.01
2 2 2
MAXIMUM DESIGN CABLE TENSION
= 2,324 lbs (4,648 lbs ULTIMATE)
NOTES:
1. ACCESS LIFELINES AND D-RINGS
AT LOCATIONS DESIGNATED BY
ARROWS.
2. ACCESS LOWER REACHES
USING ROPE AND ROPE GRAB.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.01
BUILDING 1171
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
T
D D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
F
I E
H A
N G
E S
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
R
E C
O R
D
D
R A
W I N
G
S1.02
ROOF FALL PROTECTION LAYOUT PLAN
BUILDING 1172
1/4" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
S L
O P
E
D
O W
N
MAXIMUM DESIGN CABLE TENSION
= 2,701 lbs (5,402 lbs ULTIMATE)
(E) STANDING SEAM ROOF W/ SEAMS
AT 9" O.C. (DESIGNED BY OTHERS)
TYP.
NOTES:
1. ACCESS LIFELINES AT LOCATIONS
DESIGNATED BY ARROWS.
2. CROSS OVER TO OTHER LIFELINE
USING DOUBLE-LEG LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.02
BUILDING 1172
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
F
I E
A
N G
E S
R
E C
O R
D
D
R A
W I N
S1.03
ROOF FALL PROTECTION LAYOUT PLAN
BUILDING 3132
1/4" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
(E) STANDING SEAM ROOF W/ SEAMS
AT 24" O.C. (DESIGNED BY OTHERS)
2 2
MAXIMUM DESIGN CABLE TENSION
= 2,461 lbs (4,922 lbs ULTIMATE)
TYP.
NOTES:
1. ACCESS LIFELINES AT LOCATIONS
DESIGNATED BY ARROWS.
2. CROSS OVER TO OTHER LIFELINE
USING DOUBLE-LEG LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.03
BUILDING 3132
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
F
I E
A
N G
E S
R
E C
O R
D
D
R A
W I N
S1.04
ROOF FALL PROTECTION LAYOUT PLAN
BUILDING 1173
1/4" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
2 2
MAXIMUM DESIGN CABLE TENSION
= 2,529 lbs (5,058 lbs ULTIMATE)
TYP.
(E) STANDING SEAM ROOF W/ SEAMS
AT 24" O.C. (DESIGNED BY OTHERS)
NOTES:
1. ACCESS LIFELINES AT LOCATIONS
DESIGNATED BY ARROWS.
2. CROSS OVER TO OTHER LIFELINE
USING DOUBLE-LEG LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.04
BUILDING 1173
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
F
I E
A
N G
E S
R
E C
O R
D
D
R A
W I N
S1.05
ROOF FALL PROTECTION
BUILDING 3127
1/8" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
4 D-RING -SEE DETAIL 4/S8.01
TYP.
TYP.
2 23
TYP.
MAXIMUM DESIGN CABLE TENSION
= 2,541 lbs (5,082 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,541 lbs (5,082 lbs ULTIMATE)
TYP.
MAXIMUM DESIGN CABLE TENSION
= 2,578 lbs (5,156 lbs ULTIMATE)
(E) STANDING SEAM ROOF W/ SEAMS
AT 16" O.C. (DESIGNED BY OTHERS)
MAXIMUM DESIGN CABLE TENSION
= 2,140 lbs (4,280 lbs ULTIMATE)
ACCESS LIFELINES AND D-RINGS
USING LIFT AT LOCATIONS
DESIGNATED BY ARROWS.
SWITCH TO NEXT LIFELINE USING
DOUBLE-LEG LANYARD.
(AT ROOF
BELOW)
NOTES:
1. ACCESS LIFELINES AND D-RINGS
AT LOCATIONS DESIGNATED BY
ARROWS.
2. SWITCH TO NEXT LIFELINE USING
DOUBLE-LEG LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
ACCESS LOW ROOF
W/ LADDER OR LIFT
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.05
BULIDING 3127
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
F
I E
A
N G
E S
R
E C
O R
D
D
R A
W I N
S1.06
ROOF FALL PROTECTION LAYOUT
BUILDING 3129
3/32" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
SHORT CURVE BRACKET
-SEE DETAIL 1/S8.01 (SIM.)
MAXIMUM DESIGN CABLE TENSION
= 2,516 lbs (5,032 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,680 lbs (5,360 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,489 lbs (4,978 lbs ULTIMATE)
(E) STANDING SEAM ROOF W/ SEAMS
AT 18 1/2" O.C. (DESIGNED BY OTHERS)
(E) STANDING SEAM ROOF W/ SEAMS
AT 16 1/4" O.C. (DESIGNED BY OTHERS)
MAXIMUM DESIGN CABLE TENSION
= 2,680 lbs (5,360 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,798 lbs (5,596 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,835 lbs (5,670 lbs ULTIMATE)
MAXIMUM DESIGN CABLE TENSION
= 2,385 lbs (4,770 lbs ULTIMATE)
TYP.
MAXIMUM DESIGN CABLE TENSION
= 2,330 lbs (4,660 lbs ULTIMATE)
TYP.
TYP.
5 D-RING -SEE DETAIL 4/S8.01
ACCESS
POINT,
TYP.
NOTES:
1. ACCESS LIFELINES AND D-RINGS
AT LOCATIONS DESIGNATED BY
ARROWS.
2. CROSS OVER RIDGE TO ACCESS
ADJACENT LINE DOUBLE-LEG
LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.06
BUILDING 3129
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
F
I E
A
N G
E S
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
R
E C
O R
D
D
R A
W I N
S1.07
ROOF FALL PROTECTION LAYOUT PLAN
BUILDING 32251
1/4" = 1'-0"
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
2 2
MAXIMUM DESIGN CABLE TENSION
= 2,462 lbs (4,924 lbs ULTIMATE)
TYP.
(E) STANDING SEAM ROOF W/ SEAMS
AT 16" O.C. (DESIGNED BY OTHERS)
NOTES:
1. ACCESS LIFELINES AT LOCATIONS
DESIGNATED BY ARROWS.
2. CROSS OVER AT RIDGE USING
DOUBLE-LEG LANYARD.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.07
BUILDING 32251
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
R
E C
O R
D
D
R A
W I N
T
T E
R R
A
T
T E
R
S1.08
ROOF FALL PROTECTION LAYOUT
BUILDING 3225
3/32" = 1'-0"
N
KEYNOTES:
8mm 7 x 7 STAINLESS STEEL
EVOLUTION CABLE
END ANCHOR
-SEE DETAIL 2/S8.01
INTERMEDIATE BRACKET
-SEE DETAIL 1/S8.01
4 D-RING -SEE DETAIL 4/S8.01
90° CURVE BRACKET
-SEE DETAIL 3/S8.01
MAXIMUM DESIGN CABLE TENSION
= 2,467 lbs (4,934 lbs ULTIMATE)
(E) STANDING SEAM ROOF W/ SEAMS
AT 12" O.C. (DESIGNED BY OTHERS)
(E) STANDING SEAM ROOF W/ SEAMS
AT 12" O.C. (DESIGNED BY OTHERS)
MAXIMUM DESIGN CABLE TENSION
= 2,191 lbs (4,382 lbs ULTIMATE)
22 3 1
MAXIMUM DESIGN CABLE TENSION
= 2,340 lbs (4,680 lbs ULTIMATE)
NOTES:
1. ACCESS POINTS FOR D-RINGS
AT LOCATIONS DESIGNATED BY
ARROWS.
2. CROSS OVER THE RIDGE AT TOP
TO ACCESS OTHER LIFELINE.
LEGEND
DENOTES ACCESS POINT
USING LIFT.
DENOTES ACCESS POINT
USING LADDER.
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S1.08
BUILDING 3225
BCH
110621
10.12.11
A
C C
E S
S
P
O I N
D
E D
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
F
I E
A
N G
E S
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
R
E C
O R
D
D
R A
W I N
S8.01
BRACKET ANCHOR PLATE
TYPICAL INTERMEDIATE
1 1/2" = 1'-0"
10"
EVOLUTION STD. INTERMEDIATE
BRACKET W/ STIFFENER (AT SIM. USE
EVOLUTION SHORT CURVE BRACKET
PDESIGN = 1.58 kips
PULTIMATE = 3.15 kips
STANDING SEAM ROOF PANELS
DESIGNED BY OTHERS
STANDING SEAM
SPACING 'S'
PLATE
THICKESS
18.5" < S < 24" 14"
S < 18" 3/16"
(4) S-5! CLAMPS BELOW (S-5-U OR
S-5-S DEPENDING ON SEAM TYPE)
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
P
P
A
N
SEE SCHEDULE FOR
PLATE THICKNESS
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
1"
TYP.
T Y
P
S8.01
END BRACKET ANCHOR PLATE
1 1/2" = 1'-0"
10"
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
P
A
N
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
1"
TYP.
T Y
P
EVOLUTION END ANCHOR
(PART NO. 7240176) FASTENED
TO PLATE W/ 5/8" DIA. BOLT
STANDING SEAM ROOF PANELS
DESIGNED BY OTHERS
(5) S-5! CLAMPS BELOW (S-5-U OR
S-5-S DEPENDING ON SEAM TYPE)
1/4" PLATE
CABLE TENSION
FORCE PER PLAN
S8.01
90° CURVE ANCHOR PLATE
1 1/2" = 1'-0"
1" 1'-0 1/4"
FIELD VERIFY
1"
T Y
P
3/8" PLATE
CABLE TENSION
PER PLAN
EVOLUTION 90°
CURVE
(6) S-5! CLAMPS BELOW (S-5-U OR
S-5-S DEPENDING ON SEAM TYPE)
STANDING SEAM ROOF PANELS
DESIGNED BY OTHERS
S8.01
D-RING ANCHOR PLATE
1 1/2" = 1'-0"
10"
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
P
A
N
S T
A N
D I N
G
S
E A
M
S P
A C
I N
G
1"
TYP.
T Y
P
STANDING SEAM ROOF PANELS
DESIGNED BY OTHERS
(6) S-5! CLAMPS BELOW (S-5-U OR
S-5-S DEPENDING ON SEAM TYPE)
1/4" PLATE
M
A X
PULTIMATE = 5000 lbs
D-RING ANCHOR W/ ANCHOR PLAN
(PART NO. 2101630) FASTENED TO
PLATE W/ (2) 1/2" DIA. BOLTS
CABLE TENSION
PER PLAN
SHEET
ISSUE DATE:
DRAWN BY:
PROJECT NO:
SHEET CONTENT
CHECKED BY:
R E
V
D A
T E
D E
S C
R I P
T I O
N
COPYRIGHT 2011
Miller Consulting Engineers, Inc.
LINE IS 2 INCHES
AT FULL SCALE
R O
L L
P
R O
T E
C T
I O
N
E I E
L S
R
S
E
E X
C A
L I B
S
O C
I A
T E
S
E I E
L S
R
E
B
A S
E
F A
I R
B A
N K
S
A
L A
S K
A
S8.01
DETAILS
BCH
110621
10.12.11
RECORD DOCUMENTS
THESE RECORD DOCUMENTS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED
BY OTHERS. MILLER CONSULTING ENGINEERS, INC. HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS INFORMATION AND SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE INCORPORATED AS A RESULT OF ERRONEOUS
INFORMATION PROVIDED BY OTHERS.
OREGON
EXPIRES: 12 - 31 - 2012
E
N
G
I N
E
E
R
65401PE
S
T
R
U
CT
U
R
A
L
ARL
R
E C
O R
D
D
R A
W I N
Distress Summary
Building 1168, Aircraft Fabrication: This 21 year old inverted single-ply roof has vegetation growing in the paver joints and backed-out fasteners on the metal cap.
Building 1171, Fuels Maintenance: The fall arrest system cables are rubbing on the standing seams, several fasteners are backed-out and the expansion joint between sections A and B has a few holes on this 22 year old standing seam metal roof.
Building 1172, AGE Warm Storage: This standing seam metal roof is in good shape for being 23 years old. It only has broken plastic ridge end caps and a few backed-out fasteners for distresses.
Building 1173, Deicer Storage: This 23 year old standing seam metal roof is in good condition also. It has a few backed-out/ corroded fasteners and a little surface dete-rioration for distresses.
Building 1174, Fuel Station: All six penetrations are missing flashing boots on this 29 year old metal panel canopy.
Building 1176, Hangar: For only being 2 years old this single ply roof has several distresses. Numerous lumps under the membrane, some of which have created holes.
Also some of the base flashing has come loose and there is several areas of ponding.
Building 1180, LOX Storage: This 8 year old metal panel roof has some missing and misaligned foam panel closures.
Building 1191, AGE Parking: At 20 years old this modified bituminous roof is recom-mended for replacement. The substrate is exposed in several places, patches are de-teriorated and there are numerous ridges throughout the roof area.
Building 3127, Wing Headquarters: The 14 year old standing seam metal roof on this building is in great shape with only a few areas of surface deterioration.
Building 3128, Alert Garage: This 27 year old metal panel roof needs some panels replaced due to the fasteners corroding holes through some of the panels.
Building 3129, Operations: The metal panel sections of this roof are 17 & 23 years old and have backed-out/missing fasteners, surface deterioration, and the trees are rubbing on it on the north side. The new single-ply section has an abundance of abandoned cable laying on it and several lumps under the membrane. The older sec-tion has vegetation growing in the joints of the pavers that cover it.
Building 1171, Fuels Maintenance: The fall arrest system cables are rubbing on theBuilding 1171, Fuels Maintenance: The fall arrest system cables are rubbing on the standing seams, several fasteners are backed-out and the expansion joint between standing seams, several fasteners are backed out and the expansion joint be sections A and B has a few holes on this 22 year old standing seam metal roof.
Building 1172, AGE Warm Storage: This standing seam metal roof is in good shape u d g 7 , G Wa Sto age: s sta d g sea eta oo s good s ape for being 23 years old. It only has broken plastic ridge end caps and a few backed-for being 23 years old. It on out fasteners for distresses.
Building 1173, Deicer Storage: This 23 year old standing seam metal roof is in goodBuilding 1173, Deicer Storage: This 23 year old standing seam metal roof is in good condition also. It has a few backed-out/ corroded fasteners and a little surface dete-co d t o a so. t as a rioration for distresses.
Building 3127, Wing Headquarters: The 14 year old standing seam metal roof on this Building 3127, Wing Headquarters: The 14 year old standing seam metal building is in great shape with only a few areas of surface deterioration.
Building 3129, Operations: The metal panel sections of this roof are 17 & 23 years u d g 3 9, Ope at o s: e eta pa e sect o s o t s oo a e 7 & 3 yea s old and have backed-out/missing fasteners, surface deterioration, and the trees areold and have backed out/missing fasteners, surface deterioration, and the trees are rubbing on it on the north side. The new single-ply section has an abundance of ubb g o t o t e o t s de. e ew s g e p y sect o as a abu da ce o abandoned cable laying on it and several lumps under the membrane. The older sec-abandoned cable laying on it and several lumps under the membran tion has vegetation growing in the joints of the pavers that cover it.
Building 3130, Supply: This 27 year old membrane roof has vegetation growing in the joint of the ballast pavers, a few holes in the base flashing and a lead flashing sleeve that isn’t sealed.
Building 3131, HAZMAT: Vegetation is growing in the paver joints on this 28 year old modified bitumen roof.
Building 3132, Cold Storage: The only distress on this 25 year old metal panel roof is backed-out, missing or corroded fasteners.
Building 3133, Vehicle Maintenance: This 25 year old modified bituminous roof has a couple holes, a few improperly flashed penetrations, some loose base flashing and some debris for the surface granule deterioration.
Building 3180, Communications: The metal sections on this roof are distress free.
The single-ply sections have numerous distresses for only being 5 & 8 years old. The base flashing has several different distresses, the metal cap flashing also has several distresses and there is several areas of ponding due to the wrinkling of the membrane.
Building 3225, Civil Engineering: This 21 year old metal panel and single-ply roof is in good condition. The single-ply sections have some vegetation growing in the paver joints and the metal sections have a little surface deterioration.
Building 3325-1, CE Storage: The ridge cap on this 10 year old metal panel roof is deformed. Also a couple fasteners are corroded, the surface has a few scratches and a panel closure is misaligned.
Building 3345, Clinic: This 19 year old single-ply roof has some debris, a few lumps under the membrane and one base flashing reinforcement strip that is coming loose.
Building 3132, Cold Storage: The only distress on this 25 year old metal panel roof Building 3132, Cold Storage: The only distre is backed-out, missing or corroded fasteners.
Building 3225, Civil Engineering: This 21 year old metal panel and single-ply roof isu d g 3 5, C v g ee g: s yea o d eta pa e a d s g e p y oo s in good condition. The single-ply sections have some vegetation growing in the paver in good condition. The single ply sections have some vegetation joints and the metal sections have a little surface deterioration.
Building 3325-1, CE Storage: The ridge cap on this 10 year old metal panel roof isBuilding 3325 1, CE Storage: The ridge cap on this 10 year old metal panel roof is deformed. Also a couple fasteners are corroded, the surface has a few scratches and de o ed. so a coup e aste a panel closure is misaligned.
Building 1171, Fuels Maintenance
Section A & B
The fall arresting cable is causing surface deterioration on both sections.
Several fasteners are backed-out like this one or are missing on both sections.
Building 3127, Wing Headquarters
The only distress found is the surface deterioration on some of the standing seams from the fall arrest anchor sliding down.
Section C
The fall arresting cable is causing surface deterioration on the standing seams.
A few flashing and panel fasteners are either corroded, backed-out or missing.
ROOF DISTRESS LEGEND
DISTRESSES QUANTITY:
SQUARE FT OR LINEAR FT
DISTRESS DEFINITION:
DISTRESS SEVERITY:
DISTRESS TYPE:
DISTRESS NUMBER AND
APPROXIMATE LOCATION:
EXAMPLE:
BUILT-UP ROOFING SYSTEM
3 / BF / H / 2 / 14
3 = DISTRESS NUMBER 3
BF = BASE FLASHING DISTRESS
1 EM L 1 55
H = HIGH SEVERITY
2 = THERE ARE EXPOSED GAPS AT 2 EM M 1 5
THE TOP WHICH ARE NOT
COUNTERFLASHED OR THERE
ARE OPEN SIDE LAPS. 3 BF H 2 14
14 = THIS DISTRESS WAS
FOUND IN FOURTEEN LOCATIONS.
D I S
S E V
D E F
Q
Y
ROOF SYMBOLS LEGEND
H Hatch E Equipment P Penthouse S Skylight SC Solar Collector T Transformer V Ventilator
Antenna
#I Core Sample with Sample Identifier
Roof Vent
Ladder
Scupper
Chimney or Flue
Pitch Pan
Flashed Penetration
Lightning Rod
Roof Edge
Parapet or Adjacent Building
Expansion Joint or Roof Divider
Roof Drain
= Walkway = Pipe or Conduit = Cable e = Roof Edge or Eave p = Parapet ra = Rake v = Valley w = Adjacent Wall ej = Expansion Joint r = Ridge
PANEL DISTRESSES
Section Wide Surface Deterioration (SW) Degradation of factory applied finish on the panel, such as colored paint, clear coat, anodized finish; degradation of the field-applied coating; or metal corrosion. This defect should be used to characterize an entire roof section. For localized areas of surface deterioration, use the Localized Sur-face Deterioration distress.
SW -- Low
1. Applied finish exhibits chalking, fading, or scratching over the entire roof sec-tion, but underlying corrosion is not apparent.
SW -- Medium
1. Base metal or applied finish exhibits chalking, fading, or scratching over the entire roof section, requiring a coating or surface treatment repair.
SW -- High
1. Base metal exhibits corrosion over the entire roof section, requiring a roof re-placement.
By definition, count the square feet of the entire area of the roof section.
Localized Surface Deterioration (SD) Degradation of factory applied finish on the panel, such as colored paint, clear coat, anodized finish; degradation of the field ap-plied coating; or metal corrosion.
SD -- Medium
1. Localized loss of applied finish or localized metal corrosion.
2. Metal panel finish exhibits degradation caused by grease, solvent, or oil drip-pings.
SD -- High
1. For panel system that has mechanically interlocked seams, panel has corro-sion holes that require localized repair.
2. Metal panel finish exhibits degradation caused by grease, solvent or oil drip-pings that require panel replacement.
Note: Once any panel has a distress that requires panel replacement; do not count other distresses on that same panel.
Note: Due to mechanical seaming, mechanically interlocked panels are typically diffi-cult to replace, and localized repairs would likely be made in lieu of panel replacement.
For M-1, M-2, and H-1 defects, measure the square feet of defective panel area.
0:, 0:, w
'-..J w
SHE
RWI
N-
WIL
LIA
MS
She r·C olo r(i
m) 10/
/11
Ord et l 8
-00
INT
/EX
T
OTM
A
CRY
LIC
SEM
I-G
LO
SS
IND
M
AIN
T P
AR
T 1
ACR
YL
IC
m a0
G
RI
FF
IN
SHE
R-C
OL
OR
FO
R�
ULA
SAC
OL
ORA
NT
OZ
81-
Bl ac k
R2- Mar ocn
YJ
-O ee p
Ge ld
ONE
GA
LL
ON
W00
21J
DE
EP
Non R etu rna ble T int ed
Col or
C
FI
U T
I O
N a s s u r e o n �d t c n t c l o r
W
l) 'Y d e r e n o u g h p i c:
p l c
J b
.o d i t u r
K l n t a i n e g.
rr.
l b f o p l i c a t i o n f'1 i d l o t1i y v .o r-v i g h t y
-f l r
I" l l" i
111111 11111 111111 111111 11111 111111 Ill f"I
"'C
"'C rb
Q.
tl::J
1" I :!!
"' ':r"
1··
C" rb r-l\t
G" I C, " rb
S M T W T F S S M T W T F S S M T W T F S S M T W T F S 1 2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3
3 4 5 6 7 8 9 7 8 9 10 11 12 13 7 8 9 10 11 12 13 4 5 6 7 8 9 10 10 11 12 3 14 15 16 14 15 16 17 18 19 20 14 15 16 17 18 19 20 11 12 13 14 15 16 17 17 18 19 20 21 22 23 21 22 23 24 25 26 27 21 22 23 24 25 26 27 18 19 20 21 22 23 24 24 25 26 27 28 29 30 28 28 29 30 31 25 26 27 28 29 30
S M T W T F S S M T W T F S S M T W T F S S M T W T F S 1 1 2 3 4 5 1 2 3 1 2 3 4 5 6 7
2 3 4 5 6 7 8 6 7 8 9 10 11 12 4 5 6 7 8 9 10 8 9 10 11 12 13 14 9 10 11 12 13 14 15 13 14 15 16 17 18 19 11 12 13 14 15 16 17 15 16 17 18 19 20 21
16 17 18 19 20 21 22 20 21 22 23 24 25 26 18 19 20 21 22 23 24 22 23 24 28 26 27 28 23 24 25 26 27 28 29 27 28 29 30 25 26 27 28 29 30 31 29 30 31 30 31 Drill Rescheduled in April
S M T W T F S S M T W T F S S M T W T F S S M T W T F S 1 2 3 4 1 2 1 2 3 4 5 6 1 2 3 4
5 6 7 8 9 10 11 3 4 5 6 7 8 9 7 8 9 10 11 12 13 5 6 7 8 9 10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 14 15 16 17 18 19 20 12 13 14 15 16 17 18 19 20 21 22 23 24 25 17 18 19 20 21 22 23 21 22 23 24 25 26 27 19 20 21 22 23 24 25 26 27 28 29 30 24 25 26 27 28 29 30 28 29 30 26 27 28 29 30 31
Jan 1 - New Year's Day Jan 18 - Martin Luther King Day Feb 15 - President's Day July 5 - Indepedence Day (Observed)
Oct 11 - Columbus Day Nov 11 - Veteran's Day Nov 25 - Thanksgiving Day Dec 24 - Christmas Day (Observed) May 31 - Memorial Day Sep 6 - Labor Day
Dec 31 - New Year's Day (Observed)
168TH WING 2021 AWS/DRILL CALENDAR v1 CAO: 10 September 2020
DECEMBER 2021
Drill Rescheduled in Nov
FEDERAL HOLIDAYS
AUGUST 2021
Drill Rescheduled in Aug
SEPTEMBER 2021 OCTOBER 2021 NOVEMBER 2021
Drill Rescheduled in Jan
MAY 2021 JUNE 2021 JULY 2021
JANUARY 2021 FEBRUARY 2021 MARCH 2021 APRIL 2021
9 Hour Day AWS8 Hour Day
Weekend
FEDERAL HOLIDAYS
168 WG RSD
PROJECT NUMBER : PROJECT TITLE: SOLICITATION/CONTRACT NO.:
SCHEDULE OF MATERIAL SUBMITTALS Repair Roof Fall Protection, Multi Bldg
TO BE COMPLETED BY PROJECT ENGINEER TO BE COMPLETED BY CONTRACT ADMINISTRATOR
NO. OF COPIES REQUIRED
LI
NE
N
UM
BE
R
ITEM OR DESCRIPTION OF ITEM,
CONTRACT REFERENCE, TYPE OF
SUBMITTAL
CE
RT
IF
IC
AT
IO
N
OF
C
OM
PL
IA
NC
E
SH
OP
D
RA
W
IN
GS
SA
MP
LE
S
CO
LO
R
SE
LE
CT
IO
N
MA
NU
FA
CT
UR
ER
'S
R
EC
OM
ME
ND
AT
IO
NS
MA
NU
FA
CT
UR
ER
'S W
AR
RA
NT
Y
CA
TA
LO
G
DA
TA
OP
ER
AT
IN
G
IN
ST
RU
CT
IO
NS
OT
HE
R
RE
QU
IR
ED
S
UB
MI
SS
IO
N
DA
TE
DA
TE
R
EC
EI
VE
D
IN
C
ON
TR
AC
TI
NG
DA
TE
T O
CI
VI
L
EN
GI
NE
ER
IN
G
RE
TU
RN
S
US
PE
NS
E
DA
TE
SU
BM
IT
TA
L
NU
MB
ER
S
DATE CONTRACTOR
NOTIFIED
CO
NT
RA
CT
OR
R
ES
UB
MI
TT
AL
FI
NA
L
AP
PR
OV
AL
REMARKS
APPROVED DIS-
APPROVED
1 Anchors and Cables 1 1
2 Roof Paint 1 1 1
3 Signage 1
4 As-Built Markups 1
5 System Certification 1
FTQW 21-2001
AF FORM 66 (Computer Generated) PAGE 1 of 2
PROJECT NUMBER : PROJECT TITLE: SOLICITATION/CONTRACT NO.:
SCHEDULE OF MATERIAL SUBMITTALS Repair Roof Fall Protection, Multi Bldg
TO BE COMPLETED BY PROJECT ENGINEER TO BE COMPLETED BY CONTRACT ADMINISTRATOR
NO. OF COPIES REQUIRED
LI
NE
N
UM
BE
R
ITEM OR DESCRIPTION OF ITEM,
CONTRACT REFERENCE, TYPE OF
SUBMITTAL
CE
RT
IF
IC
AT
IO
N
OF
C
OM
PL
IA
NC
E
SH
OP
D
RA
W
IN
GS
SA
MP
LE
S
CO
LO
R
SE
LE
CT
IO
N
MA
NU
FA
CT
UR
ER
'S
R
EC
OM
ME
ND
AT
IO
NS
MA
NU
FA
CT
UR
ER
'S W
AR
RA
NT
Y
CA
TA
LO
G
DA
TA
OP
ER
AT
IN
G
IN
ST
RU
CT
IO
NS
OT
HE
R
RE
QU
IR
ED
S
UB
MI
SS
IO
N
DA
TE
DA
TE
R
EC
EI
VE
D
IN
C
ON
TR
AC
TI
NG
DA
TE
T O
CI
VI
L
EN
GI
NE
ER
IN
G
RE
TU
RN
S
US
PE
NS
E
DA
TE
SU
BM
IT
TA
L
NU
MB
ER
S
DATE CONTRACTOR
NOTIFIED
CO
NT
RA
CT
OR
R
ES
UB
MI
TT
AL
FI
NA
L
AP
PR
OV
AL
REMARKS
APPROVED DIS-
APPROVED
FTQW 21-2001
AF FORM 66 (Computer Generated) PAGE 2 of 2
| SOW |
| 2. FTQW212001 Atch 1 - Map |
| 3. FTQW212001 Atch 2 - As-Built Drawings |
| 4. FTQW212001 Atch 3 - Photos of Roof Damage 1 |
| 5. FTQW212001 Atch 4 - Paint Color Codes |
| Paint Chip 01 |
| Paint Chip 03 |
| Paint Chip 02 |
| 6. FTQW202001 Atch 5 - 168WG CY21 Calendar |
| 168WG AWS 2021 |
7. FTQW212001 Atch 6 - Submittal Register
File details come from the government source that posted it. Updated .