21-09-29-1908-7 VA-Switchgear_Sealed.pdf

PDF 28 MB Posted

Attached to
6150--674A4-19-101 Replace Primary Medium Voltage Switchgear Federal contract opportunity
Solicitation number
36C25722B0014
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

This document outlines a federal contract opportunity to replace primary medium voltage switchgear. The solicitation is number 36C25722B0014 to replace the existing medium voltage switchgear in Building 133 at the Doris Miller VA Medical Center in Waco, Texas. The NAICS code for this procurement is 238210, with a small business size standard of $16.5 million. The magnitude of the project is estimated between $2 million and $5 million. This opportunity is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17.

View the file

Other files for this federal contract opportunity

Other files attached to 6150--674A4-19-101 Replace Primary Medium Voltage Switchgear, newest first.
File Type Posted
251010 ADVANCED UTILITY METERING SYSTEM_ADD1.pdf PDF
Answers 36C25722B0014 Replace Primary MV Switchgear Waco VAMC RFI-Questions - 1-66.pdf PDF
36C25722B0014 0006.docx DOCX document
261313 MEDIUM-VOLTAGE CIRCUIT BREAKER SWITCHGEAR_ADD1r1.pdf PDF
SELF-PERFORMED CALCULATIONS.pdf PDF
Revised Bid Schedule SECTION B.pdf PDF
36C25722B0014 0004.docx DOCX document
OSHA - EMR requirement.pdf PDF
Pre-Bid site visit sign in sheet 674A4-19-101.pdf PDF
36C25722B0014 0003.docx DOCX document
36C25722B0014 0002.docx DOCX document
36C25722B0014 0001.docx DOCX document
Waco Electrical Feeder Drw.pdf PDF
36C25722B0014_1.docx DOCX document
21-09-30_VA Switchgear Specifications_Sealed.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

VA - AE REPLACE PRIMARY MV

SWITCHGEAR

4800 MEMORIAL DRIVE

WACO, TEXAS, 76711

PROJECT No. 674A4-19-101

MENDEZNGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

U.S. Department of Veterans Affairs

LOCATION MAP

SCALE: NTS

SITE

9/29/2021

BEVERLY DRIVE

IN

D

U

STR

IAL BLVD

BUILDING

NO.216

FFE=559.75

BUILDING

NO.17

BUILDING

NO.14

±26'

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

GAS / PETROLEUM

COMMUNICATIONS

LEGEND OF U.G. UTILITY TYPES

ELECTRIC / POWER

SANITARY SEWER

STORM DRAIN

ABANDONED UTILITY

UNKNOWN UTILITY

ATMOS

VAMC

VAMC (FUEL LINE)

ONCOR

VAMC

VAMC

CITY OF WACO

VAMC

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

QL"B"

QL"B"

QL"B"

QL"B"

QL"B"

QL"C"/"D"

ATMOS

VAMC

VAMC (FUEL LINE)

QL"C"/"D"

ONCOR

VAMC

QL"C"/"D"

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"C"/"D"

VAMC

QL"C"/"D"

CITY OF WACO

VAMC

QL"C"/"D"

LEGEND OF UTILITY SYMBOLS

END CAP

QUALITY LEVEL CHANGE

TEST HOLE

UTILITY CONTINUATION

CATV CABINET

CATV HANDHOLE

CATV PEDESTAL

FIBER HANDHOLE

TELEPHONE CABINET

TELEPHONE HANDHOLE (VAULT)

TELEPHONE MANHOLE

TELEPHONE PEDESTAL

TELEPHONE POLE

TELEPHONE POLE W/RISER

ELECTRIC HANDHOLE

ELECTRIC JUNCTION BOX (CABINET)

ELECTRIC MANHOLE

ELECTRIC POLE (POWER)

ELECTRIC POLE W/RISER

LIGHT POLE

TRANSMISSION POLE

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

POTABLE WATER

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"B"

SIGNAL HANDHOLE/BOX

SIGNAL POLE

GAS MANHOLE

GAS METER

GAS TEST STATION

GAS VALVE

GAS VENT PIPE (GAS RISER)

STORM SEWER INLET

STORM SEWER MANHOLE

STORM SEWER OUTFALL

WASTE WATER CLEANOUT

WASTE WATER MANHOLE

FIRE HYDRANT

WATER MANHOLE

WATER METER

WATER VALVE

WATER VAULT

SDMH

RIM=561.90

FL 12" RCP NW=558.02

MATCHLINE: SEE SHEET C1.1

±92 SF OF STAIRS

TO BE REMOVED

REF. AD102 FOR

DETAILS

±26 LF

EXISTING FENCE

TO BE REMOVED

2-EXISTING

ELECTRIC

TRANSFORMERS

TO BE REMOVED

(REF. E2.2)

ALT. 4 - EXISTING COOLING

TOWERS TO BE REMOVED. 1' OF

EXISTING FOUNDATION TO BE

REMOVED AND DIRT FILLED UP

TO EXISTING GROUND

ELEVATION. CONTRACTOR TO

CUT AND CAP ANY EXPOSED

UTILITY LINES.

ALT. 5 - ±20LF CHILL

WATER LINE TO BE

REMOVED, CUT

AND CAP.

ALT. 2 - ±124 OHE

CONDUCTORS TO BE REMOVED

AFTER IT HAS BEEN PLACED

OUT OF SERVICE.

(REF. ENLARGE SITE PLAN E2.2)

ALT. 1 & 2 - ±11 SF - EXISTING VA

POLE AND ELECTRICAL

STRUCTURE TO BE REMOVED

(REF. ENLARGED SITE PLAN E2.2)

CAUTION:

CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY

AND HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO

NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.

THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE

ACCURACY OF THE LOCATION OF UNDERGROUND UTILITIES. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL

EXISTING UTILITIES BY VERIFYING THE FOR LOCATION OF ALL

UTILITIES, AT LEAST 2 WORKING DAYS PRIOR TO BEGINNING

CONSTRUCTION.

TRENCH EXCAVATION SAFETY PROTECTION:

CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY

RETAINED EMPLOYEE OR STRUCTURAL

DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT CONSULTANT, IF

ANY, SHALL REVIEW THESE PLANS, AVAILABLE GEOTECHNICAL

INFORMATION, AND THE ANTICIPATED INSTALLATION SITE(S)

WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT

CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION

SYSTEMS, PROGRAMS AND/OR PROCEDURES. THE

CONTRACTOR'S IMPLEMENTATION OF THE SYSTEMS, PROGRAMS

AND/OR PROCEDURES SHALL PROVIDE FOR ADEQUATE TRENCH

EXCAVATION SAFETY PROTECTION THAT COMPLIES WITH, AS A

MINIMUM, OSHA STANDARDS FOR TRENCH EXCAVATIONS.

SPECIFICALLY, CONTRACTOR AND/OR CONTRACTOR'S

INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY CONSULTANT

SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN ACCORDANCE

WITH OSHA STANDARDS GOVERNING THE PRESENCE AND

ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH

EXCAVATION.

NOTE: ALL ELECTRICAL

POWER LINES MUST BE

COORDINATED WITH VA

PRIOR TO DEMOLITION.

ANY POWER OUTAGES

MUST BE STAGED AND

PLANNED WITH THE VA.

NOTE: ALL ELECTRICAL

POWER LINES MUST BE

COORDINATED WITH VA

PRIOR TO DEMOLITION.

ANY POWER OUTAGES

MUST BE STAGED AND

PLANNED WITH THE VA.

D

U

STR

IAL BLVD

IN

D

U

STR

IAL BLVD

BUILDING

NO.17

BUILDING

NO.15

BUILDING

NO.16

BUILDING

NO.133

IN

D

U

STR

IAL BLVD

BUILDING

NO.16

BUILDING

NO.15

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

GAS / PETROLEUM

COMMUNICATIONS

LEGEND OF U.G. UTILITY TYPES

ELECTRIC / POWER

SANITARY SEWER

STORM DRAIN

ABANDONED UTILITY

UNKNOWN UTILITY

ATMOS

VAMC

VAMC (FUEL LINE)

ONCOR

VAMC

VAMC

CITY OF WACO

VAMC

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

QL"B"

QL"B"

QL"B"

QL"B"

QL"B"

QL"C"/"D"

ATMOS

VAMC

VAMC (FUEL LINE)

QL"C"/"D"

ONCOR

VAMC

QL"C"/"D"

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"C"/"D"

VAMC

QL"C"/"D"

CITY OF WACO

VAMC

QL"C"/"D"

LEGEND OF UTILITY SYMBOLS

END CAP

QUALITY LEVEL CHANGE

TEST HOLE

UTILITY CONTINUATION

CATV CABINET

CATV HANDHOLE

CATV PEDESTAL

FIBER HANDHOLE

TELEPHONE CABINET

TELEPHONE HANDHOLE (VAULT)

TELEPHONE MANHOLE

TELEPHONE PEDESTAL

TELEPHONE POLE

TELEPHONE POLE W/RISER

ELECTRIC HANDHOLE

ELECTRIC JUNCTION BOX (CABINET)

ELECTRIC MANHOLE

ELECTRIC POLE (POWER)

ELECTRIC POLE W/RISER

LIGHT POLE

TRANSMISSION POLE

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

POTABLE WATER

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"B"

SIGNAL HANDHOLE/BOX

SIGNAL POLE

GAS MANHOLE

GAS METER

GAS TEST STATION

GAS VALVE

GAS VENT PIPE (GAS RISER)

STORM SEWER INLET

STORM SEWER MANHOLE

STORM SEWER OUTFALL

WASTE WATER CLEANOUT

WASTE WATER MANHOLE

FIRE HYDRANT

WATER MANHOLE

WATER METER

WATER VALVE

WATER VAULT

MATCHLINE: SEE SHEET C1.1

MATCHLINE: SEE THIS SHEET

MATCHLINE: SEE THIS SHEET

ALT. 3- ±815SF-EXISTING

SWITCHGEAR

FOUNDATION TO BE

REMOVED

(REF. ENLARGED SITE

PLAN E2.2)

±80LF

SAWCUT & DEMOLISH

ASPHALT & NEW ASPHALT

TO MATCH EXISTING

PAVEMENT SECTION

ALT. 2 - ±171LF - OHE

CONDUCTORS TO BE REMOVED

AFTER IT HAS BEEN PLACED

OUT OF SERVICE.

(REF. ENLARGE SITE PLAN E2.2)

ALT. 1 & 2 - ±4 SF -

EXISTING VA POLE AND

RISER TO BE REMOVED

(REF. ENLARGED SITE

PLAN E2.2)

EXISTING DUCTBANKS/

CONDUITS TO BE

ABANDONED

(REF. ENLARGED SITE

PLAN E2.2)

NOTE: ALL ELECTRICAL

POWER LINES MUST BE

COORDINATED WITH VA

PRIOR TO DEMOLITION.

ANY POWER OUTAGES

MUST BE STAGED AND

PLANNED WITH THE VA.

NOTE: ALL ELECTRICAL

POWER LINES MUST BE

COORDINATED WITH VA

PRIOR TO DEMOLITION.

ANY POWER OUTAGES

MUST BE STAGED AND

PLANNED WITH THE VA.

CAUTION:

CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY

AND HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO

NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.

THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE

ACCURACY OF THE LOCATION OF UNDERGROUND UTILITIES. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL

EXISTING UTILITIES BY VERIFYING THE FOR LOCATION OF ALL

UTILITIES, AT LEAST 2 WORKING DAYS PRIOR TO BEGINNING

CONSTRUCTION.

TRENCH EXCAVATION SAFETY PROTECTION:

CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY

RETAINED EMPLOYEE OR STRUCTURAL

DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT CONSULTANT, IF

ANY, SHALL REVIEW THESE PLANS, AVAILABLE GEOTECHNICAL

INFORMATION, AND THE ANTICIPATED INSTALLATION SITE(S)

WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT

CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION

SYSTEMS, PROGRAMS AND/OR PROCEDURES. THE

CONTRACTOR'S IMPLEMENTATION OF THE SYSTEMS, PROGRAMS

AND/OR PROCEDURES SHALL PROVIDE FOR ADEQUATE TRENCH

EXCAVATION SAFETY PROTECTION THAT COMPLIES WITH, AS A

MINIMUM, OSHA STANDARDS FOR TRENCH EXCAVATIONS.

SPECIFICALLY, CONTRACTOR AND/OR CONTRACTOR'S

INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY CONSULTANT

SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN ACCORDANCE

WITH OSHA STANDARDS GOVERNING THE PRESENCE AND

ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH

EXCAVATION.

BEVERLY DRIVE

D

U

STR

IAL BLVD

5.2'

5.5'

12' 8'

7'

6'

6'

BUILDING

NO.216

FFE=559.75

BUILDING

NO.17

BUILDING

NO.14

REF. ENLARGED SITE PLAN,

SHEET E2.2

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

GAS / PETROLEUM

COMMUNICATIONS

LEGEND OF U.G. UTILITY TYPES

ELECTRIC / POWER

SANITARY SEWER

STORM DRAIN

ABANDONED UTILITY

UNKNOWN UTILITY

ATMOS

VAMC

VAMC (FUEL LINE)

ONCOR

VAMC

VAMC

CITY OF WACO

VAMC

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

QL"B"

QL"B"

QL"B"

QL"B"

QL"B"

QL"C"/"D"

ATMOS

VAMC

VAMC (FUEL LINE)

QL"C"/"D"

ONCOR

VAMC

QL"C"/"D"

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"C"/"D"

VAMC

QL"C"/"D"

CITY OF WACO

VAMC

QL"C"/"D"

LEGEND OF UTILITY SYMBOLS

END CAP

QUALITY LEVEL CHANGE

TEST HOLE

UTILITY CONTINUATION

CATV CABINET

CATV HANDHOLE

CATV PEDESTAL

FIBER HANDHOLE

TELEPHONE CABINET

TELEPHONE HANDHOLE (VAULT)

TELEPHONE MANHOLE

TELEPHONE PEDESTAL

TELEPHONE POLE

TELEPHONE POLE W/RISER

ELECTRIC HANDHOLE

ELECTRIC JUNCTION BOX (CABINET)

ELECTRIC MANHOLE

ELECTRIC POLE (POWER)

ELECTRIC POLE W/RISER

LIGHT POLE

TRANSMISSION POLE

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

POTABLE WATER

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"B"

SIGNAL HANDHOLE/BOX

SIGNAL POLE

GAS MANHOLE

GAS METER

GAS TEST STATION

GAS VALVE

GAS VENT PIPE (GAS RISER)

STORM SEWER INLET

STORM SEWER MANHOLE

STORM SEWER OUTFALL

WASTE WATER CLEANOUT

WASTE WATER MANHOLE

FIRE HYDRANT

WATER MANHOLE

WATER METER

WATER VALVE

WATER VAULT

MATCHLINE: SEE SHEET C2.1

PROPOSED 6" CONCRETE PAD

REF M3.1

ONCOR

UNDERGROUND

ELECTRICAL

DESIGN.

CONTRACTOR TO

COORDINATE WITH

ONCOR ON

CONNECTIONS.

FR

O

N T

TIE-IN 3' NORTH OF

TOWER WALLS. REF

SHEET E4.0, FOR

CONTINUATION

CAUTION:

CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY

AND HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO

NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.

THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE

ACCURACY OF THE LOCATION OF UNDERGROUND UTILITIES. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL

EXISTING UTILITIES BY VERIFYING THE FOR LOCATION OF ALL

UTILITIES, AT LEAST 2 WORKING DAYS PRIOR TO BEGINNING

CONSTRUCTION.

TRENCH EXCAVATION SAFETY PROTECTION:

CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY

RETAINED EMPLOYEE OR STRUCTURAL

DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT CONSULTANT, IF

ANY, SHALL REVIEW THESE PLANS, AVAILABLE GEOTECHNICAL

INFORMATION, AND THE ANTICIPATED INSTALLATION SITE(S)

WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT

CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION

SYSTEMS, PROGRAMS AND/OR PROCEDURES. THE

CONTRACTOR'S IMPLEMENTATION OF THE SYSTEMS, PROGRAMS

AND/OR PROCEDURES SHALL PROVIDE FOR ADEQUATE TRENCH

EXCAVATION SAFETY PROTECTION THAT COMPLIES WITH, AS A

MINIMUM, OSHA STANDARDS FOR TRENCH EXCAVATIONS.

SPECIFICALLY, CONTRACTOR AND/OR CONTRACTOR'S

INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY CONSULTANT

SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN ACCORDANCE

WITH OSHA STANDARDS GOVERNING THE PRESENCE AND

ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH

EXCAVATION.

PROPOSED DRYWELL

REF M3.1

UTILITY NOTES:

1. LOCATION FOR NEW ONCOR ELECTRIC STRUCTURE.

SEE SHEET E2.2 FOR CONTINUATION.

2. EXISTING REUSABLE METERING POLE.

SEE SHEET E2.2.

3. NEW ELECTRIC DUCT BANKS. SEE SHEET E2.2 FOR TYPE

AND DETAILS.

4. PROPOSED STAIRS, REF SHEET S2.0.

5. [OMIT]

6. CONTRACTOR VERIFY DEPTH AND LOCATION OF ALL

EXISTING UTILITIES WITH CAUTION.

7. SEE ELECTRICAL MANHOLE. SEE SHEET E2.2.

PAVING NOTES:

8. SAWCUT & DEMOLISH ±101 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF. DETAIL 8 ON SHEET C2.1]

9. SAWCUT, REMOVE AND REPLACE REQUIRED WIDTH

SECTION OF CURB. CONTRACTOR CAN USE

DESECRATION TO PRESERVE OR REMOVE CURB

SECTION DURING CONSTRUCTION.

10. SAWCUT & DEMOLISH ±400 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF. DETAIL 8 AND 11 ON SHEET C2.1.]

11. SAWCUT & DEMOLISH REQUIRED AREA FOR ELECTRIC

MANHOLE. REPLACE WITH NEW ASPHALT AFTER

INSTALLATION.

12. SAWCUT, REMOVE, & RESTORE SIDEWALK SECTIONS

TO NEW CONDITIONS AS REQUIRED FOR INSTALLATION.

13. SAWCUT & DEMOLISH ±95 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

14. SAWCUT & DEMOLISH ±17 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

15. SAWCUT & DEMOLISH ±25 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

16. CONDUITS CABLES AND TERMINATIONS ON LINE SIDE

OF PAD MOUNTED METERING PROVIDED BY ONCOR.

17. PAD MOUNTED METERING PROVIDED BY ONCOR.

PROPOSED CMU STRUCTURE

REF S7.0 & S7.1

PROPOSED ELEC STRUCTURE

REF E4.1

PROPOSED CHAIN LINK

FENCE TO BE INSTALLED AS

PER MANUFACTURERS

SPECIFICATIONS ON TOP OF

EXISTING FOUNDATION.

U

STR

IAL BLVD

IN

D

U

STR

IAL BLVD

BUILDING

NO.17

BUILDING

NO.15

BUILDING

NO.16

BUILDING

NO.133

IN

D

U

STR

IAL BLVD

BUILDING

NO.16

BUILDING

NO.15

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

GAS / PETROLEUM

COMMUNICATIONS

LEGEND OF U.G. UTILITY TYPES

ELECTRIC / POWER

SANITARY SEWER

STORM DRAIN

ABANDONED UTILITY

UNKNOWN UTILITY

ATMOS

VAMC

VAMC (FUEL LINE)

ONCOR

VAMC

VAMC

CITY OF WACO

VAMC

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

QL"B"

QL"B"

QL"B"

QL"B"

QL"B"

QL"C"/"D"

ATMOS

VAMC

VAMC (FUEL LINE)

QL"C"/"D"

ONCOR

VAMC

QL"C"/"D"

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"C"/"D"

VAMC

QL"C"/"D"

CITY OF WACO

VAMC

QL"C"/"D"

LEGEND OF UTILITY SYMBOLS

END CAP

QUALITY LEVEL CHANGE

TEST HOLE

UTILITY CONTINUATION

CATV CABINET

CATV HANDHOLE

CATV PEDESTAL

FIBER HANDHOLE

TELEPHONE CABINET

TELEPHONE HANDHOLE (VAULT)

TELEPHONE MANHOLE

TELEPHONE PEDESTAL

TELEPHONE POLE

TELEPHONE POLE W/RISER

ELECTRIC HANDHOLE

ELECTRIC JUNCTION BOX (CABINET)

ELECTRIC MANHOLE

ELECTRIC POLE (POWER)

ELECTRIC POLE W/RISER

LIGHT POLE

TRANSMISSION POLE

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

POTABLE WATER

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"B"

SIGNAL HANDHOLE/BOX

SIGNAL POLE

GAS MANHOLE

GAS METER

GAS TEST STATION

GAS VALVE

GAS VENT PIPE (GAS RISER)

STORM SEWER INLET

STORM SEWER MANHOLE

STORM SEWER OUTFALL

WASTE WATER CLEANOUT

WASTE WATER MANHOLE

FIRE HYDRANT

WATER MANHOLE

WATER METER

WATER VALVE

WATER VAULT

MATCHLINE: SEE SHEET C2.1

REF. ENLARGED SITE

PLAN, SHEET E2.2

EXISTING

MANHOLE "P"

MATCHLINE: SEE THIS SHEET

MATCHLINE: SEE THIS SHEET

EXISTING

MANHOLE "A"

REF. ENLARGED SITE

PLAN, SHEET E2.2

REF. ENLARGED SITE

PLAN, SHEET E2.2

REF. ENLARGED SITE

PLAN, SHEET E2.2

CAUTION:

CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY

AND HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO

NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.

THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE

ACCURACY OF THE LOCATION OF UNDERGROUND UTILITIES. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL

EXISTING UTILITIES BY VERIFYING THE FOR LOCATION OF ALL

UTILITIES, AT LEAST 2 WORKING DAYS PRIOR TO BEGINNING

CONSTRUCTION.

TRENCH EXCAVATION SAFETY PROTECTION:

CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY

RETAINED EMPLOYEE OR STRUCTURAL

DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT CONSULTANT, IF

ANY, SHALL REVIEW THESE PLANS, AVAILABLE GEOTECHNICAL

INFORMATION, AND THE ANTICIPATED INSTALLATION SITE(S)

WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT

CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION

SYSTEMS, PROGRAMS AND/OR PROCEDURES. THE

CONTRACTOR'S IMPLEMENTATION OF THE SYSTEMS, PROGRAMS

AND/OR PROCEDURES SHALL PROVIDE FOR ADEQUATE TRENCH

EXCAVATION SAFETY PROTECTION THAT COMPLIES WITH, AS A

MINIMUM, OSHA STANDARDS FOR TRENCH EXCAVATIONS.

SPECIFICALLY, CONTRACTOR AND/OR CONTRACTOR'S

INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY CONSULTANT

SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN ACCORDANCE

WITH OSHA STANDARDS GOVERNING THE PRESENCE AND

ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH

EXCAVATION.

UTILITY NOTES:

1. LOCATION FOR NEW ONCOR ELECTRIC STRUCTURE.

SEE SHEET E2.2 FOR CONTINUATION.

2. EXISTING REUSABLE METERING POLE.

SEE SHEET E2.2.

3. NEW ELECTRIC DUCT BANKS. SEE SHEET E2.2 FOR TYPE

AND DETAILS.

4. PROPOSED STAIRS, REF SHEET S2.0.

5. [OMIT]

6. CONTRACTOR VERIFY DEPTH AND LOCATION OF ALL

EXISTING UTILITIES WITH CAUTION.

7. SEE ELECTRICAL MANHOLE. SEE SHEET E2.2.

PAVING NOTES:

8. SAWCUT & DEMOLISH ±101 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF. DETAIL 8 ON SHEET C2.1]

9. SAWCUT, REMOVE AND REPLACE REQUIRED WIDTH

SECTION OF CURB. CONTRACTOR CAN USE

DESECRATION TO PRESERVE OR REMOVE CURB

SECTION DURING CONSTRUCTION.

10. SAWCUT & DEMOLISH ±400 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF. DETAIL 8 AND 11 ON SHEET C2.1.]

11. SAWCUT & DEMOLISH REQUIRED AREA FOR ELECTRIC

MANHOLE. REPLACE WITH NEW ASPHALT AFTER

INSTALLATION.

12. SAWCUT, REMOVE, & RESTORE SIDEWALK SECTIONS

TO NEW CONDITIONS AS REQUIRED FOR INSTALLATION.

13. SAWCUT & DEMOLISH ±95 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

14. SAWCUT & DEMOLISH ±17 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

15. SAWCUT & DEMOLISH ±25 L.F. OF ASPHALT & NEW

ASPHALT TO MATCH EXISTING PAVEMENT SECTION.

[REF DETAIL 8 ON SHEET C2.1.]

16. CONDUITS CABLES AND TERMINATIONS ON LINE SIDE

OF PAD MOUNTED METERING PROVIDED BY ONCOR.

17. PAD MOUNTED METERING PROVIDED BY ONCOR.

MENDEZ NGINEERINGE

12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

GAS / PETROLEUM

COMMUNICATIONS

LEGEND OF U.G. UTILITY TYPES

ELECTRIC / POWER

SANITARY SEWER

STORM DRAIN

ABANDONED UTILITY

UNKNOWN UTILITY

ATMOS

VAMC

VAMC (FUEL LINE)

ONCOR

VAMC

VAMC

CITY OF WACO

VAMC

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

QL"B"

QL"B"

QL"B"

QL"B"

QL"B"

QL"C"/"D"

ATMOS

VAMC

VAMC (FUEL LINE)

QL"C"/"D"

ONCOR

VAMC

QL"C"/"D"

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"C"/"D"

VAMC

QL"C"/"D"

CITY OF WACO

VAMC

QL"C"/"D"

LEGEND OF UTILITY SYMBOLS

END CAP

QUALITY LEVEL CHANGE

TEST HOLE

UTILITY CONTINUATION

CATV CABINET

CATV HANDHOLE

CATV PEDESTAL

FIBER HANDHOLE

TELEPHONE CABINET

TELEPHONE HANDHOLE (VAULT)

TELEPHONE MANHOLE

TELEPHONE PEDESTAL

TELEPHONE POLE

TELEPHONE POLE W/RISER

ELECTRIC HANDHOLE

ELECTRIC JUNCTION BOX (CABINET)

ELECTRIC MANHOLE

ELECTRIC POLE (POWER)

ELECTRIC POLE W/RISER

LIGHT POLE

TRANSMISSION POLE

AT&T (FO/DUCT)

VAMC (FO/DUCT)

VAMC (TELE)

POTABLE WATER

CITY OF WACO

VAMC (WATER)

VAMC (CHILLED)

VAMC (STEAM)

QL"B"

SIGNAL HANDHOLE/BOX

SIGNAL POLE

GAS MANHOLE

GAS METER

GAS TEST STATION

GAS VALVE

GAS VENT PIPE (GAS RISER)

STORM SEWER INLET

STORM SEWER MANHOLE

STORM SEWER OUTFALL

WASTE WATER CLEANOUT

WASTE WATER MANHOLE

FIRE HYDRANT

WATER MANHOLE

WATER METER

WATER VALVE

WATER VAULT

7 8

4 ELECTRICAL VAULT

N.T.S.

9 PMU PAD DIMENSIONS

N.T.S.

10 VA PMU PAD DETAIL

N.T.S.

*NOTE: SEE ELECTRICAL SHEET E2.2 FOR

LOCATIONS CORRESPONDING TO

SEGMENT TAGS, EG. SEGMENT 'A', ETC.

11 PAVEMENT TERMINUS

N.T.S.

NO SEAL

REQUIRED

DN

UP

E

E

D

D

C

C

B

B

A

A

MV SWITCH GEAR

1A-100

105'-6"

PATH OF TRAVEL

EX

IT

EXIT

87'-6"

COMMON PATH

OF TRAVEL

5 OCCUPANTS

6 OCCUPANTS

NIC

NIC

NIC

NIC

OPEN TO

BELOW

UP

E

E

D

D

C

C

B

B

A

A

NIC

NIC

NIC

OPEN TO

ABOVE

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

NO

T

F

OR CONSTRUCT

I O N

N O

T

FOR C O N S T R UCT

I O N

R

E V I EW S E T

R

E V I E W S

E

T

CONSTRUCTION

DOCUMENTS

100%

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

1 FIRST LEVEL LIFE SAFETY PLAN

SCALE: 1/8" = 1'-0"

N

2 BASEMENT LEVEL LIFE SAFETY PLAN

SCALE: 1/8" = 1'-0"

N

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AP100

AutoCAD SHX Text

AutoCAD SHX Text

LIFE SAFETY PLANS

UP

DN

UP

AP103

AP103

E

E

D

D

C

C

B

B

A

A

MV SWITCH GEAR

1A-100

1A-101

1A-102

1A-103

1A-104

6' -0

C

O N

TR

AC

TO

R

F

IE

LD

V

ER

IF

Y

OPEN TO

BELOW

NIC

NIC

NIC

NIC

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

1 FIRST LEVEL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

N

DEMOLITION FLOOR PLAN

KEYNOTES

1. DEMOLISH AND REMOVE EXISTING WALL.

2. DEMOLISH AND REMOVE EXISTING DOOR AND

FRAME.

3. DEMOLISH AND REMOVE EXISTING STAIRS

SLAB, HANDRAIL, AND GUARDRAIL.

4. CONTRACTOR TO LOCATE NEAREST EXISTING

VERTICAL POST BEYOND THE 6' DIMENSION

AND REMOVE PORTION OF EXISTING

GUARDRAIL,

5. DEMOLISH AND REMOVE EXISTING

OVERHEAD COILING DOOR AND ALL

ASSOCIATED HARDWARE AND ELECTRICAL

CONNECTION. INFILL WITH NEW MATERIALS

TO MATCH EXISTING BRICK, CMU, AND STONE

WAINSCOT.

6. DEMOLISH AND REMOVE EXISTING

MECHANICAL EQUIPMENT, REFER M2.1

7. DEMOLISH AND REMOVE EXISTING

ELECTRICAL EQUIPMENT, REFER E3.1

8. DEMOLISH AND REMOVE EXISTING COOLING

TOWERS, REFER C1.0, M2.1A.

9. NEAREST EXISTING VERTICAL POST TO

REMAIN, AND USE AS STARTING POST FOR

NEW GUARDRAIL, CONTRACTOR VERIFY

LOCATION AND PROVIDE UPDATED

DIMENSION TO VA AND ARCHITECT.

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AD102

AutoCAD SHX Text

FIRST LEVEL DEMOLITION FLOOR PLAN

UP

E

E

D

D

C

C

B

B

A

A

MV SWITCH GEAR

1A-100

5'-2"

1A-101

1A-102

1A-103

1A-104

2' -1

0"

1'-4"

K2

OPEN TO

BELOW

5' -6

21'-6"

AP104

4"

11 2" C

LR

41 2"

AP103

AP104

AP104

AP104

6' -0

AP103

ROOM FINISH SCHEDULE

Number ROOM NAME FLOOR

N S E W

WALLS

MATL HEIGHT

CEILING

NOTES

1A-100 MV SWITCH GEAR -- PT-1 -- -- --

DOOR AND FRAME SCHEDULE

MARK

WD HGT THK

SIZE

DOOR

MATL EL

FRAME

FIRE

RATING

LABEL SET

NO

HARDWARE

NOTES

1 3'-0" 7'-0" 1 3/4"

3 EXISTING DOOR AND FRAME, PROVIDE PANIC HARDWARE

1 3/4"7'-0"

--1 90 MIN

90 MIN

MATL EL

HOLLOW METAL

HOLLOW METAL

HEAD JAM

DETAIL

1,2/AP701 6/AP701

14/AP701 15/AP701

PT-1 PT-1 PT-1

4'-0" HOLLOW METAL

HOLLOW METAL1

D O

O R

H

EI

G H

T

DOOR

WIDTH2" 2"

2"

D O

O R

H

EI

G H

T

DOOR

WIDTH

DOOR ELEVATION FRAME ELEVATION

PROVIDE PANIC HARDWARE

PROVIDE PANIC HARDWARE

EXISTING DOOR AND FRAME, PROVIDE PANIC HARDWARE

2 HR. RATED PARTITION AS

SHOWN WITH UNFACED

ACOUSTICAL BATTS

DECK

2 LAYERS 5/8"

GYP BD (BOTH

SIDES) SCHEDULED CLG

STEEL RUNNER

CHANNEL

3-5/8" STUDS

AT 16" OC

2 HR. RATED PARTITION

WITH 6" STUDS IN LIEU OF

3-5/8" STUDS

2 HR. RATED PARTITION WITH 6"

STUDS UNFACED ACOUSTICAL

BATTS IN LIEU OF 3-5/8" STUDS

PROVIDE UL ASSEMBLY

HW-D-0042 TO DECK

2 HR. RATED PARTITION

UL # 419K1

K2

K3

K4

BASE AS

SCHEDULEDFINISH

FLOOR

FIRE STOPPING

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

1 FIRST LEVEL FLOOR PLAN

SCALE: 1/4" = 1'-0"

N

FLOOR PLAN

KEYNOTES

1. EXISTING FIRE RISER

2. FAN COIL UNIT, REFER MECHANICAL M3.1.

3. CONDENSING UNIT, REFER MECHANICAL

M3.1.

4. SWITCH GEAR, REFER ELECTRICAL E4.1.

5. ELECTRICAL PANEL, REFER ELECTRICAL

E4.1.

6. ELECTRICAL EQUIPMENT, REFER

ELECTRICAL E4.1.

7. STAIR SLAB, HANDRAIL, AND GUARDRAIL,

REFER STRUCTURAL S2.0

8. EXISTING TO REMAIN 4" RAISED

HOUSEKEEPING PAD.

9. 1 1/2" PIPE RAILING.

10. USE NEAREST EXISTING VERTICAL POST

AS FIRST POST FOR NEW GUARDRAIL.

11. CONTINUOUS 8" KICK PLATE AT BOTTOM.

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AP101

AutoCAD SHX Text

FIRST LEVEL FLOOR PLAN

E D C B A

8' -0

8'

-0

6' -0

6'

-8 1 2"

7'-0"8'-0"6'-53 8"

2X4 LED FIXTURE

CEILING LEGEND

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

1 FIRST LEVEL REFLECTED CEILING PLAN

SCALE: 1/4" = 1'-0"

N

REFLECTED CEILING PLAN

GENERAL NOTES

1. SURFACE MOUNT 2X4 LED FIXTURE

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AP102

AutoCAD SHX Text

REFLECTED CEILING PLAN

E D C B A

2 1 3

AP104

'-0

C

O N

TR

AC

TO

R

F

IE

LD

V

ER

IF

Y

10'-4"

CONTRACTOR FIELD VERIFY

EDCBA

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

BUILDING ELEVATION KEYNOTES

1. WALL INFILL TO MATCH EXISTING

BRICK, CMU, AND STONE WAINSCOT.

CONTRACTOR TO VERIFY, MATERIAL,

COLOR, AND TEXTURE WITH

ARCHITECT AND VA PRIOR TO

INSTALLING.

2. EXISTING RAMP TO REMAIN.

3. EXISTING RAMP, HANDRAIL, AND

GUARDRAIL TO REMAIN.

4. STAIR SLAB, HANDRAIL, AND

GUARDRAIL, REFER STRUCTURAL S2.0.

1 SOUTH ELEVATION

SCALE: 1/4" = 1'-0"

2 NORTH ELEVATION

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AP103

AutoCAD SHX Text

BUILDING ELEVATIONS

EXISTING GUARDRAIL

EXISTING

CONCRETE

BEAM

1 1/2" STEEL PIPE,

MATCH EXISTING

GUARDRAIL HIEGHT

5' -0

" F

IE

LD

V

ER

IF

Y

2"

8"

STEEL KICK PLATE,

INSTALLED ON

WALK SIDE

2'-9" 2'-9"

5'-6"

2"

CLR

6'-0"

AP103

8"1"75

8"

1/2" EXTERIOR SHEATHING

4" CMU VENEER

MASONRY ANCHOR

EXISTING EXTERIOR

WALL BEYOND

1" AIR GAP

THROUGH WALL

FLASHING WITH

END DAMS

BASE FLASHING

EXTERIORINTERIOR

1 1/2 RIGID INSULATION

SEALANT

1'-2"

WEEPS

MODULAR BRICK VENEER

STONE WAINSCOT

C O

N

TR

AC

TO

R F

IE

LD

V

ER

IF

Y

7 5/8" CMU FULLY GROUTED

AND DOWELED INTO

EXISTING ADJACENT CMU

2"

NON-SHRINK GROUT

10'-4" FIELD VERIFY

1' -2

35 8"

7 5/8" CMU FULLY GROUTED

AND DOWELED INTO

EXISTING ADJACENT CMU

MODULAR BRICK VENEERMASONRY ANCHOR

EXISTING EXTERIOR WALL

1" AIR GAPVAPOR BARRIER

1 1/2 RIGID INSULATION

EXTERIOR

INTERIORAP103

75 8" 1"

11 2"

ENDDAMN FLASHING

5' -0

1'

-2

1' -2

1'

-2

1' -2

1 1/2" PIPE RAIL

31 4"

EXISTING

CONCRETE BEAM

4"

8" STEEL KICK PLATE

PRIME ARCHITECTS

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

TELEPHONE: (866) 266-8071

FAX: (866) 226-9969

www.prime-arch.com

MENDEZ NGINEERINGE

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

9/28/2021

3 SECTION DETAIL

SCALE: 1 1/2" = 1'-0"

4 PLAN DETAIL

SCALE: 1 1/2" = 1'-0"

1 ELEVATION

SCALE: 1/4" = 1'-0"

2 SECTION

SCALE: 1/4= 1'-0"

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Department of Veterans Affairs Certified

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location: 4800 MEMORIAL DRIVE, WACO, TEXAS 76711

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

REPLACE PRIMARY MV SWITCH GEAR

AutoCAD SHX Text 674A4-19-101

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SEPTEMBER 29, 2021

AutoCAD SHX Text Site: DORIS MILLER VA MEDICAL CENTER

AutoCAD SHX Text

AutoCAD SHX Text

GEORGE WOKOMA

AutoCAD SHX Text

100% SUBMITTAL - ISSUED FOR CONSTRUCTION

AutoCAD SHX Text

AutoCAD SHX Text

AP104

AutoCAD SHX Text

AutoCAD SHX Text

DTC

AutoCAD SHX Text

RM

DETAILS

FIRE PROTECTION NOTESCODE COMPLIANCE VALVES

HYDRANTS & YARD PIPING

GENERAL & AREA SPECIFIC SYMBOLS

OH2

SUPERVISORY & ALARM DEVICES

SPRINKLER HEADS

MISC. SYSTEM ACCESSORIES & APPURTENANCES

ALARM & SYSTEM VALVES

O 'C

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

FP1.1

FIRE PROTECTION NOTES, SYMBOLS

AND ABBREVIATIONS

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

09/22/2021

E D C B A

DEMO NOTES :

GENERAL NOTES:

0" 2'-0" 4'-0" 8'-0"

SCALE 1/4" = 1'

LEGEND

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

FP2.1

FIRE PROTECTION FIRST LEVEL

DEMOLITION PLAN

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

1 FIRE PROTECTION UPPER LEVEL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

UP

E D C B A

KEYED NOTES :

0" 2'-0" 4'-0" 8'-0"

SCALE 1/4" = 1'

LEGEND

GENERAL NOTES:

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

FP3.1

FIRE PROTECTION FIRST LEVEL

FLOOR PLAN

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

1 FIRE PROTECTION FIRST LEVEL FLOOR PLAN

SCALE: 1/4" = 1'-0"N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

GENERAL ABBREVIATIONS

HVAC PIPING

HVAC EQUIPMENT

HVAC SYMBOL SCHEDULE

1.

2.

3.

4.

5.

6.

7.

CODE COMPLIANCE

MECHANICAL GENERAL NOTES

MECHANICAL GENERAL NOTES -

RENOVATIONS

S

L

S

L

REFRIGERANT PIPING DETAIL

EVAPORATOR ABOVE CONDENSER

NOT TO SCALE

OIL TRAP

TRAPS AND/OR HEAT EXCHANGER PER MFG

INSTRUCTIONS

SLOPE HORIZONTAL TOWARD CONDENSER

SERVICE VALVE WITH GAUGE TAP (TYP)

FILTER DRYER

LIQUID INDICATOR

INSTALL TXV (IF SHIPPED LOOSE) AND

SENSING BULB PER MFG INSTRUCTIONS

RISE IN SUCTION PIPING TO TOP LEVEL OF EVAP COIL

D-X COIL IN

AHU

AIR-COOLED

CONDENSING UNIT

NOTES:

1. ALL LINES TO BE SIZED AS RECOMMENDED BY EQUIPMENT MFG.

2. MAINTAIN ALL UNIT CLEARANCES PER INSTALLATION INSTRUCTIONS.

3. PIPING SHALL NOT INTERFERE WITH MAINTENANCE PANELS.

4. SECURE PIPING AND INSULATE PER SPECIFICATION.

CONDENSATE DRAIN

CONCRETE

COVER OVER

DRYWELL

FILL UP TO TOP WITH

3/4" TO 1 1/2" WASHED

RIVER GRAVEL.

2" DIA. HOLES 1'-0" O.C.

VERTICALLY. 4 HOLES ON

EACH LEVEL.

WRAP PIPE WITH

FILTER FABRIC

REF PLANS

DRY WELL DETAIL -

PERFORATED PVC PIPE

NOT TO SCALE

REF PLANS

PERFORATED PVC PIPE

REF PLANS

'A' = MAXIMUM STATIC PRESSURE +1"

'B' = 1" MINIMUM

NOTES:

1. DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE

NIPPLE ON THE UNIT DRAIN PAN CONNECTION.

2. FITTINGS MAY BE ROTATED AS REQUIRED TO ALLOW FOR

CLEARANCE WITH OTHER ADJACENT EQUIPMENT AS LONG AS

THE VERTICAL AXIS REMAINS PLUMB. (ADDITIONAL FITTINGS,

I.E., ELLS MAY BE REQUIRED OTHER THAN SHOWN HERE).

SIZES AS SHOWN ON PLANS

UNION, TYP.

THREADED CAPPED TEE

VENT

SLOPE AND ROUTE

TO DRAIN

UNIT

BASE

RAIL

COOLING

UNIT

"A"

"B"

POSITIVE PRESSURE CONDENSATE

DRAIN PIPING

NOT TO SCALE

MENDEZ NGINEERING

Registration # F-14070

12950 Country Parkway, Suite 120

San Antonio, Texas 78216

Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

M1.1

MECHANICAL NOTES, SYMBOLS AND

ABBREVIATIONS

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

DEMO NOTES :

UP

G F E D C B A

216-CWP1216-CWP3

216-CWP2

216-CHP1

216-CHP2

216-CHP3

AIR COMPRESSOR

216-CHP5

216-CHP4

MENDEZ NGINEERING

Registration # F-14070

12950 Country Parkway, Suite 120

San Antonio, Texas 78216

Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

M2.0A

MECHANICAL LOWER LEVEL

DEMOLITION PLAN - ALTERNATE BID

LEGEND

GENERAL NOTES:

0" 2'-0"

4'-0" 8'-0"

SCALE 1/4" = 1'

MECHANICAL LOWER LEVEL DEMOLITION PLAN - ALTERNATE

SCALE: 1/4" = 1'-0"

N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

DN

E D C B A

216-FC3

216-FC2

216-FC1

EXPANSION TANK

FD

216-FC4

DEMO NOTES :

LEGEND

GENERAL NOTES:

0" 2'-0"

4'-0" 8'-0"

SCALE 1/4" = 1'

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

M2.1

MECHANICAL LOWER LEVEL

DEMOLITION PLAN - BASE BID

MENDEZ NGINEERING

Registration # F-14070

12950 Country Parkway, Suite 120

San Antonio, Texas 78216

Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

MECHANICAL FIRST LEVEL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

N

ALL WORK ON THIS

SHEET IS BASE BID.

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

DEMO NOTES :

DN

UP

F

E

E

D

D

C

C

B

B

A

A

216-FC3

216-FC2

216-FC1

216-FC4

EXPANSION TANK

216-CCU3

216-CT3

216-CT2

216-CT1

CHILLER

VFD

ROLL-UP DOOR

(TYPICAL)

FD

MENDEZ NGINEERING

Registration # F-14070

12950 Country Parkway, Suite 120

San Antonio, Texas 78216

Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

M2.1A

MECHANICAL UPPER LEVEL

DEMOLITION PLAN - ALTERNATE BID

LEGEND

GENERAL NOTES:

0" 2'-0"

4'-0" 8'-0"

SCALE 1/4" = 1'

MECHANICAL UPPER LEVEL DEMOLITION PLAN - ALTERNATE

SCALE: 1/4" = 1'-0"

N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

UP

E D C B A

FD

CU-1

FCU-1

KEYED NOTES :

CONTROLS SYMBOLS LEGEND

DIGITAL OUTPUT - START/STOP

DIGITAL INPUT ANALOG INPUT

ANALOG OUTPUT

DO

DI

AI

AO

T SPACE TEMPERATURE SENSOR

LOW VOLTAGE OR CONTROLS

WIRING

WIRING BY OTHERS

(HIGH VOLTAGE OR FIRE ALARM)

BAS COMM WIRING

CONTROLS SCOPE OF WORK

CONTROLS ASSOCIATED WITH FCU-1/CU-1.

CONTROLS ASSOCIATED WITH ELECTRIC UNIT HEATERS, EUH-1 & EUH-2

GENERAL CONTRACTOR SHALL PROVIDE NEW DEVICES TO INTEGRATE INTO EXISTING DIRECT-DIGITAL CONTROL SYSTEM AS

INDICATED ON THE DRAWINGS. INCLUDE A COMPLETE AND WORKING DIRECT-DIGITAL CONTROL SYSTEM. INCLUDE ALL

ENGINEERING, PROGRAMMING, CONFIGURATION/SETUP HARDWARE AND SOFTWARE, CONTROLS AND INSTALLATION

MATERIALS, INSTALLATION LABOR, START-UP, TRAINING, FINAL PROJECT DOCUMENTATION AND WARRANTY.

ALL NEW DEVICES SHALL BE NATIVE BACNET. ALL NEW BACNET DEVICES AND COMPONENTS SHALL BE LISTED BY BACNET

TESTING LABORATORIES.

THIS FACILITY’S EXISTING DIRECT-DIGITAL CONTROL (DDC) SYSTEM IS A SCHNEIDER ELECTRIC INET BACNET SYSTEM. THE

EXISTING SYSTEM’S TOP-END COMMUNICATIONS IS VIA BACNET. THE CONTRACTOR SHALL OBSERVE THE

CAPABILITIES, COMMUNICATION NETWORK, SERVICES, SPARE CAPACITY OF THE EXISTING CONTROL SYSTEM AND ITS ECC

PRIOR TO BEGINNING WORK.

THIS CAMPUS HAS STANDARDIZED ON AN EXISTING STANDARD ASHRAE STANDARD 135, BACNET/IP CONTROL SYSTEM

SUPPORTED BY A PRESELECTED CONTROLS SERVICE COMPANY. THIS ENTITY IS REFERRED TO AS THE “CONTROL SYSTEM

INTEGRATOR”. THE CONTROL SYSTEM INTEGRATOR IS RESPONSIBLE FOR ECC SYSTEM GRAPHICS AND EXPANSION. IT ALSO

PRESCRIBES CONTROL SYSTEM-SPECIFIC COMMISSIONING/VERIFICATION PROCEDURES TO THE CONTRACTOR. IT LASTLY

PROVIDES LIMITED ASSISTANCE TO THE CONTRACTOR IN ITS COMMISSIONING/VERIFICATION WORK.

1. THE GENERAL CONTRACTOR OF THIS PROJECT SHALL DIRECTLY HIRE THE CONTROL SYSTEM INTEGRATOR IN A CONTRACT

SEPARATE FROM THE CONTRACT PROCURING THE CONTROLS CONTRACTOR.

2. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONTROL SYSTEM INTEGRATOR. THE CONTRACTOR SHALL

INTEGRATE THE ASHRAE STANDARD 135, BACNET/IP CONTROL NETWORK(S) WITH THE CONTROL SYSTEM INTEGRATOR’S

B-AWS THROUGH AN ETHERNET CONNECTION PROVIDED BY EITHER THE CONTROL SYSTEM INTEGRATOR OR VA.

3. THIS CONTRACTOR IS RESPONSIBLE FOR ALL DEVICE MOUNTING AND WIRING.

AI

T

ROOM 1A-100

SPACE TEMPERATURE

AI

T

ROOM 1A-104

SPACE TEMPERATURE

TEMPERATURE MONITORING SEQUENCE OF OPERATION

THE SPLIT SYSTEM HVAC UNIT (FCU-1/CU-1) SERVING ROOM 1A-100 (SWITCHGEAR) AND ELECTRIC UNIT HEATERS SERVING ROOM A1-104 (STORAGE AREA)

SHALL HAVE STAND-ALONE CONTROLS.

SPACE TEMPERATURES SHALL BE MONITORED FOR EQUIPMENT FAILURE AND FREEZE PROTECTION BY THE EXISTING SCHNEIDER BMS.

FCU-1/CU-1 MONITORING

IF SPACE TEMPERATURE RISES ABOVE 90 DEG. F. (ADJ.) IN ROOM 1A-100 FOR A PERIOD > 5 MIN (ADJ.), AN ALARM SHALL BE GENERATED AT THE BMS.

FREEZE PROTECTION MONITORING

IF SPACE TEMPERATURE DROPS BELOW 35 DEG. F.(ADJ.) IN ROOM 1A-104 FOR A PERIOD > 5 MIN (ADJ.), AN ALARM SHALL BE GENERATED AT THE BMS.

GENERAL NOTES:GENERAL NOTES:

LEGEND

0" 2'-0"

4'-0" 8'-0"

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

M3.1

MECHANICAL LOWER LEVEL FLOOR

PLAN - BASE BID

MENDEZ NGINEERING

Registration # F-14070

12950 Country Parkway, Suite 120

San Antonio, Texas 78216

Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

MECHANICAL FIRST LEVEL FLOOR PLAN

SCALE: 1/4" = 1'-0"

N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

PLUMBING ABBREVIATIONS PLUMBING GENERAL NOTES

CODE COMPLIANCE

PLUMBING SYMBOL SCHEDULE

HB

FPHB

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

P1.1

PLUMBING NOTES, SYMBOLS AND

ABBREVIATIONS

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

DN

E D C B A

DEMO NOTES :

GENERAL NOTES:

LEGEND

0" 2'-0" 4'-0" 8'-0"

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

P2.1

PLUMBING FIRST LEVEL DEMOLITION

PLAN

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

1 PLUMBING FIRST LEVEL DEMOLITION PLAN

SCALE: 1/4" = 1'-0"N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

MV SWITCH GEAR

DN

DN

UP

E D C B A

MV SWITCH GEAR

1A-100

1A-101

1A-102

1A-103

1A-104

FS-1

KEYED NOTES :

GENERAL NOTES:

0" 2'-0" 4'-0" 8'-0"

SCALE 1/4" = 1'

O N

N

EL

L

RO

BE

RT

SO

N

, I N

C

P3.1

PLUMBING FIRST LEVEL PLAN

MENDEZ NGINEERING

Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com

E

Austin 811 Barton Springs Road, Suite 900, Austin, Texas 78704 p: 512.478.7286 f: 512.478.7441 San Antonio 4040 Broadway, Suite 300, San Antonio, Texas 78209 p: 210.224.6032 f: 210.224.6453

1 PLUMBING FIRST LEVEL FLOOR PLAN

SCALE: 1/4" = 1'-0"N

Engineering Firm:

O'CONNELL ROBERTSON

Firm Registration No. F-2708

CIRCUITING

EMERGENCY POWER SYSTEMS

FIRE ALARM

SITE ELECTRICAL

POWER

ELECTRICAL GENERAL REQUIREMENTS & RESTRICTIONS

1. NO WIRING SHALL BE INSTALLED IN STAIRWELLS, EXIT PASSAGEWAYS, HOISTWAYS OR ELEVATOR MACHINE ROOMS EXCEPT THAT EXCLUSIVELY USED TO SERVE THOSE

AREAS.

2. ALL PENETRATIONS THROUGH RATED PARTITIONS SHALL BE FIRE-STOPPED USING METHODS & MATERIALS COMPLYING WITH THE SPECIFICATIONS FOR THIS PROJECT.

3. LIGHT SWITCHES AND RECEPTACLES FROM EMERGENCY POWER SYSTEMS AND NORMAL POWER SYSTEMS SHALL NOT BE COMBINED IN THE SAME BOXES OR RACEWAY

SYSTEMS.

4. ALL CIRCUITS TO ROOF MOUNTED EQUIPMENT SHALL BE INSTALLED ABOVE CEILING THEN UP THROUGH ROOF CURBS UNLESS NOTED OTHERWISE. NO CONDUITS SHALL BE RUN ON, ACROSS, OR ABOVE THE ROOF, EXCEPTING FINAL CONNECTIONS TO EQUIPMENT NOT EXCEEDING 3-FEET MAXIMUM IN LENGTH.

5. WHERE POSSIBLE AVOID BACK-TO-BACK INSTALLATIONS OF OUTLETS.

This is the start of the file's text. The full file is on GovTribe.