21-0416-Safety Office-dwg-67.pdf

PDF 1 MB Posted

Attached to
Base Safety Office Spaces Building 67
Solicitation number
N4008521R0074
Issued by

View the file

Other files

File Type Posted
AMND 0001 210416.pdf PDF
SUBMITTAL REGISTER.pdf PDF
RFP 210416.pdf PDF
21-0416 Reference DWG E4E6 bldg 67.pdf PDF
PWD DIV 01 SPECS 042016.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

139 138 137

146 147 148 150 151

108107

123 122

121 112 113

119 118 155 117

125129

133134

128 127

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

TITLE PAGE

AutoCAD SHX Text T-1

AutoCAD SHX Text

AutoCAD SHX Text

BLDG. 67 REMODEL OFFICES

AutoCAD SHX Text

AutoCAD SHX Text T1

AutoCAD SHX Text Title page

AutoCAD SHX Text

AutoCAD SHX Text A1

AutoCAD SHX Text Demo Plan

AutoCAD SHX Text

AutoCAD SHX Text A2

AutoCAD SHX Text New Work

AutoCAD SHX Text

AutoCAD SHX Text A3

AutoCAD SHX Text

FINISH PLAN

AutoCAD SHX Text

AutoCAD SHX Text A4

AutoCAD SHX Text

CEILING PLAN

AutoCAD SHX Text

AutoCAD SHX Text A5

AutoCAD SHX Text

FLOORING PLAN

AutoCAD SHX Text

AutoCAD SHX Text M1

AutoCAD SHX Text

MECHANICAL PLAN

AutoCAD SHX Text

AutoCAD SHX Text E1

AutoCAD SHX Text

ELECTRICAL DENI

AutoCAD SHX Text

AutoCAD SHX Text E2

AutoCAD SHX Text

ELECTRICAL SPECS

AutoCAD SHX Text

AutoCAD SHX Text E3

AutoCAD SHX Text

RECEPTACLE PLAN

AutoCAD SHX Text

AutoCAD SHX Text E4

AutoCAD SHX Text

LIGHTING PLAN

AutoCAD SHX Text

SECTION/DETAIL NUMBER

AutoCAD SHX Text

SHEET NUMBER WHERE DETAIL IS SHOWN

AutoCAD SHX Text

SHEET NUMBER WHERE DETAIL IS TAKEN

AutoCAD SHX Text

%%UBLDG. 67

AutoCAD SHX Text 1st FLOOR PLAN

AutoCAD SHX Text SCOPE OF WORK: The contractor shall provide all material, labor, equipment, and supervision : The contractor shall provide all material, labor, equipment, and supervision required to accomplish the following: General description - This scope of work is to be accomplished at Bldg. 67 located on - This scope of work is to be accomplished at Bldg. 67 located on Virginia Dare Drive at Camp Lejeune, North Carolina. The contractor shall paint, carpet and install suspended ceiling system in the office area for Base Safety. Detailed requirements and specifications - The contractor shall take his own field - The contractor shall take his own field measurements in determining required materials and costs for the following: SPECIFICATIONS: SUBMITTALS: 1. Contractor shall make electronic copies of all submittals, including the approved Contractor shall make electronic copies of all submittals, including the approved transmittal sheets, and provide two (2) CD/DVD's containing all submittals for the project. The CD/DVD's shall be marked "Complete Submittal Package - Contract #______." SPECIAL SCHEDULING AND ACCESS: 1. Access and scheduling to the work area shall be arranged through Contracting Officer's Access and scheduling to the work area shall be arranged through Contracting Officer's Representative for the OICC office, and Mr. Ron Farris, the tenant of the building. Mr. Ron Farris, (910) 451-2071. 2. The office area will be unoccupied. There is some scattered furniture in area the tenant The office area will be unoccupied. There is some scattered furniture in area the tenant will be responsible for remove unwanted furniture. HAZARDOUS MATERIALS: None Identified None Identified SPECIAL CONDITIONS: None Identified None Identified ENVIRONMENTAL REQUIREMENTS: None Identified None Identified NOTES: 1. The measurements and quantities furnished here are for reference only. The contractor The measurements and quantities furnished here are for reference only. The contractor is responsible for actual field verification prior to bidding, ordering materials and during every step of construction for existing surfaces, dimensions and conditions. 2. Repair, refinish areas damaged or disturbed by new work to be provided under this Repair, refinish areas damaged or disturbed by new work to be provided under this contract. 3. Properly remove, haul, and dispose of all debris. The contractor shall not utilize the Properly remove, haul, and dispose of all debris. The contractor shall not utilize the dumpster provided by Camp Lejeune for the occupants of the buildings.

108107

123 122

121 112 113

119 118 155 117

154124

2 2

2 2

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

DEMO PLAN

AutoCAD SHX Text A-1

AutoCAD SHX Text

AutoCAD SHX Text

%%UDEMO\ PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text DEMO CARPET THROUGHOUT WORK AREA DEMO SUSPENDED CEILING SYSTEM DEMO SUSPENDED CEILING TILE DEMO WALLS DEMO DOOR AND DOOR JAMBS. DEMO BATHROOM STALLS

AutoCAD SHX Text %%uPHOTO RM121

AutoCAD SHX Text

PH1

AutoCAD SHX Text A1

AutoCAD SHX Text A1

NO SCALE

108107

123 122

121 112 113

119 118 155 117

AutoCAD SHX Text INSTALL GYPSUM-BOARD see photo PH2 NEW WALL NEW DOOR EXISTING DOOR DOUBLE ACTING ALUMINUM GLASS ENTRANCE DOOR

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text

MEN'S

AutoCAD SHX Text

WOMEN'S

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

NEW WORK

AutoCAD SHX Text A-2

AutoCAD SHX Text

AutoCAD SHX Text

DOOR SCHEDULE

AutoCAD SHX Text

%%UFLOOR PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text

PH2

AutoCAD SHX Text %%uPHOTO

AutoCAD SHX Text

PH2

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

CABINET

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text

PH3

AutoCAD SHX Text %%uPHOTO

AutoCAD SHX Text

PH3

AutoCAD SHX Text A2

AutoCAD SHX Text A2

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text B

AutoCAD SHX Text

DOOR SCHEDULE

AutoCAD SHX Text

DOOR

AutoCAD SHX Text

JAMB

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

HARDWARE

AutoCAD SHX Text A

AutoCAD SHX Text

WOOD, FLAT PANEL, OAK VENEER, WOOD CORE

AutoCAD SHX Text

14 GAGE METAL JAMB

AutoCAD SHX Text 3'-0" X 6'-8" X 1-3/4"

AutoCAD SHX Text HINGES: GRADE 1, 4.5 STAINLESS STEEL, BALL BEARING HINGES/ LOCKSET: GRADE 1, LEVER, KEYED ENTRY-(BEST STYLE, INTERCHANGEABLE CORE, SMALL FORMAT), KEYED TO MACH EXISTING, SATIN NICKEL FINISH/ FLOOR MOUNTED DOOR STOP

AutoCAD SHX Text B

AutoCAD SHX Text

ALUMINUM FRAMED, GLASS ENTRY DOOR, WIDE STILE, COLOR ANODIC COATING, GLAZING 8

AutoCAD SHX Text

ALUMINUM, COLOR ANODIC

AutoCAD SHX Text 3'-0" X 6'-8" X 1-3/4"

AutoCAD SHX Text CENTER PIVOT: DOUBLE ACTING/ CONCEALED OVERHEAD CLOSER, DOUBLE ACTING/ PUSH BARS, BACK TO BACK PUSH

Construct of new partition wall: 1. The new walls shall be constructed with The new walls shall be constructed with 3-5/8”-20 gauge metal studs 16” on -20 gauge metal studs 16” on on center. Brace wall to structural member a minimum of every 5-feet. Insulate with R15 bat mineral insulation. 2. The new walls shall extend above the The new walls shall extend above the existing suspended ceiling a minimum of 2-inches. 3. Install 5/8-inch fire retardant gypsum Install 5/8-inch fire retardant gypsum board. 3.1. Tape and finish the gypsum board Tape and finish the gypsum board to a level 4 finish (smooth finish). 3.2. All drywall sanding shall be done All drywall sanding shall be done with a drywall dustless vacuum system to limit airborne dust. 4. Install new oak base board. on new Install new oak base board. on new walls and areas repaired.

108107

123 122

121 112 113

119 118 155 117

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

FINISH PLAN

AutoCAD SHX Text A-3

AutoCAD SHX Text

AutoCAD SHX Text

%%UFLOOR PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CABINET

1. Replace suspended ceiling system as shown on ceiling plan A4. Replace suspended ceiling system as shown on ceiling plan A4. 2. Replace suspended ceiling tile throughput work area. Replace suspended ceiling tile throughput work area. 3. Replace flooring through out work area. Ceramic tile in bathrooms to Replace flooring through out work area. Ceramic tile in bathrooms to remain. 4. Paint Paint Preparation: 1. Repair all surfaces to provide a solid foundation for painting: Blistering, Repair all surfaces to provide a solid foundation for painting: Blistering, cracking, flaking and peeling or other deteriorated coatings shall be removed. Damaged areas such as, but not limited to, nail holes, cracks, chips, and spalls shall be repaired with suitable material to match adjacent undamaged areas. Edges of chipped paint shall be feather edged and sanded smooth. 2. All slick (enamel and other high gloss surfaces) surfaces shall be All slick (enamel and other high gloss surfaces) surfaces shall be roughened and primed to ensure adhesion. 3. Apply interior / exterior finish surfacing compound as appropriate to any Apply interior / exterior finish surfacing compound as appropriate to any damaged surfaces to match surrounding finishes. 4. Paint all previously painted objects behind portable objects and surfaces Paint all previously painted objects behind portable objects and surfaces mounted articles that can be readily detached by removal of fasteners, such as screws and bolts. All objects and articles shall be reinstalled. 5. Remove and reinstall all electrical/data switch and receptacle covers, to Remove and reinstall all electrical/data switch and receptacle covers, to insure all previously painted surfaces are repainted. Work Not Included 1. Do not include painting when factory-finishing or installer-finishing is Do not include painting when factory-finishing or installer-finishing is specified for such items as (but not limited to) metal toilet enclosures, acoustic materials, finished mechanical and electrical equipment including light fixtures, switch-gear and distribution cabinets, and similar items of work. 2. Do not paint over code-required labels, such as Underwriters' Laboratories Do not paint over code-required labels, such as Underwriters' Laboratories or Factory Mutual, or any equipment identification, performance rating, name or nomenclature plates. Prime: 1. All new and repaired surfaces shall be primed with the appropriate primer All new and repaired surfaces shall be primed with the appropriate primer per application. Paint: 2. All finish colors shall match as close as possible the existing colors unless All finish colors shall match as close as possible the existing colors unless otherwise noted in the project area description section. 3. All paints shall be factory-mixed and shall be ready for application directly All paints shall be factory-mixed and shall be ready for application directly from the manufacturer's original container. Mixing and thinning in the field shall be allowed only with prior approval of the OICC. 4. Finished surfaces shall be free from runs, drops, ridges, waves laps brush Finished surfaces shall be free from runs, drops, ridges, waves laps brush marks and variations in colors. 5. Apply additional coats when undercoats, stains or other conditions show Apply additional coats when undercoats, stains or other conditions show through final paint or finish coat, until paint film is of uniform finish, color and appearance. 5.1. Interior Walls: Apply (2) coats of egg-shell / satin finish acrylic Interior Walls: Apply (2) coats of egg-shell / satin finish acrylic latex paint. 5.2. Doors, base board and built in shelving: Apply 3 coats of poly Doors, base board and built in shelving: Apply 3 coats of poly urethane. Apply additional coats if needed to ensure and even sheen. 5.3. Trim : Apply (2) coats of semi-gloss acrylic latex paint.Trim : Apply (2) coats of semi-gloss acrylic latex paint.

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

CEILING PLAN

AutoCAD SHX Text A-4

AutoCAD SHX Text

AutoCAD SHX Text

%%UFLOOR PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CABINET

Suspended Ceiling 1. Install new suspended ceiling system. Install new suspended ceiling system. 1.1. The suspended ceiling system: The suspended ceiling system: 1.1.1. Ceiling Height: 8'-10.5" even with top of windows. Ceiling Height: 8'-10.5" even with top of windows. 1.1.1. Grid system; 15/16” tee grid Grid system; 15/16” tee grid tee grid 1.1.2. Ceiling panel; 24” x 24” x 5/8” Mineral fiber, fissured flat panel Ceiling panel; 24” x 24” x 5/8” Mineral fiber, fissured flat panel x 24” x 5/8” Mineral fiber, fissured flat panel x 5/8” Mineral fiber, fissured flat panel Mineral fiber, fissured flat panel with a Class “A” UL fire rating. A” UL fire rating. UL fire rating. 1.2. Provide acoustical work complete with necessary fastenings, Provide acoustical work complete with necessary fastenings, hold down clips, and other accessories required for a complete installation. Do not expose mechanical fastenings in the finished work. Lay out 12 gage wire hangers 4-feet on center. Provide 8 gage wire hangers to support framing around beams, ducts, columns, grilles, and other penetrations through ceilings. Keep main runners and carrying channels clear of abutting walls and partitions. Provide at least two main runners for each ceiling span. Wherever required to bypass an object with the hanger wires, install a sub-suspension system so that all hanger wires will be plumb. 1.3. Install hangers plumb and not pressing against insulation Install hangers plumb and not pressing against insulation covering ducts and pipes. Where lighting fixtures are supported from the suspended ceiling system, provide hangers at a minimum of four hangers per fixture and located not more than 6 inch from each corner of each fixture. 1.4. Provide wall molding where ceilings abut vertical surfaces. Miter Provide wall molding where ceilings abut vertical surfaces. Miter corners where wall moldings intersect or install corner caps. Secure wall molding not more than 3 inch from ends of each length and not more than 16 inch on centers between end fastenings. Provide wall molding springs at each acoustical unit.

AutoCAD SHX Text

VINYL FLOOR TILE CARPET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

FLOORING PLAN

AutoCAD SHX Text A-5

AutoCAD SHX Text

AutoCAD SHX Text

%%UFLOOR PLAN

AutoCAD SHX Text

NO SCALE

CARPET: 1. All new carpet shall meet the following specs: All new carpet shall meet the following specs: 1.1. Surface Texture: Level or textured loop Surface Texture: Level or textured loop 1.2. Yarn content: Yarn content: 1.3. General: 6,6 Antron© Nylon, solution and/or yarn dyed. General: 6,6 Antron© Nylon, solution and/or yarn dyed. Nylon, solution and/or yarn dyed. 1.4. Primary Backing: Primary Backing: 1.5. Yarn Weight: 22 oz. per sq. yd. minimum. Yarn Weight: 22 oz. per sq. yd. minimum. 1.6. Primary Backing: Reinforced synthetic Primary Backing: Reinforced synthetic Reinforced synthetic 1.7. Secondary Backing: Fiberglass reinforced thermoplastic composite Secondary Backing: Fiberglass reinforced thermoplastic composite Fiberglass reinforced thermoplastic composite 1.8. Bonding Agent: Premium Vinyl Bonding Agent: Premium Vinyl Premium Vinyl 1.9. Size: 24” x 24”. Size: 24” x 24”. 24” x 24”. x 24”. . 1.10. Static Coefficient of Friction: ASTM C-1028: Passes ADA Static Coefficient of Friction: ASTM C-1028: Passes ADA requirements 1.11. Static Propensity: AATCC 134: 3.0 KV or less Static Propensity: AATCC 134: 3.0 KV or less 1.12. Flooring Radiant Panel: ASTM E-648 or NFPA 253: Class 1 Flooring Radiant Panel: ASTM E-648 or NFPA 253: Class 1 1.13. Antimicrobials: Antimicrobials are an EPA registered pesticide. If Antimicrobials: Antimicrobials are an EPA registered pesticide. If antimicrobials are utilized in the product, the manufacturer must submit 3rd party certification seal indicating no health hazard to the end user or occupants. Test ASTM E 2471 - 05 should indicate NEGATIVE for antimicrobials. Adhesives are exempt from this section. 1.14. WARRANTY: Flooring contractor shall provide a 5-year warranty for WARRANTY: Flooring contractor shall provide a 5-year warranty for defects in materials and workmanship. Flooring manufacturer shall provide a 25 year non-prorated limited warranty against excessive surface wear and static, de-lamination, edge ravel, zippering, and backing resiliency loss. VCT: 2. Install 1/8" thick, commercial grade, 12”x12”, vinyl composite floor tile Install 1/8" thick, commercial grade, 12”x12”, vinyl composite floor tile x12”, vinyl composite floor tile , vinyl composite floor tile throughout the work area. 3. Preparation for vinyl floor tile installation: Preparation for vinyl floor tile installation: 3.1. Examine surfaces on which vinyl floor tile is to be installed to Examine surfaces on which vinyl floor tile is to be installed to insure that the floor is clean and free of oil, waxy films, paint, dust and substances that prevent adhesion, leave floor dry and cured, free of residue from curing or cleaning agents. 3.2. Correct conditions which will impair proper installation, including Correct conditions which will impair proper installation, including trowel marks, pits, dents, protrusions, cracks or joints. Fill cracks, joints depressions, and other irregularities in concrete with leveling compound. Do not use adhesive for filling or leveling purposes. Do not use leveling compound to correct imperfections which can be corrected by spot grinding. Trowel to smooth surface free of trowel marks, pits, dents, protrusions, cracks or joint lines. 4. Install new 1/8" thick commercial grade vinyl composite floor Install new 1/8" thick commercial grade vinyl composite floor 4.1. Install in accordance with manufacturer's instructions for application Install in accordance with manufacturer's instructions for application and installation. 4.2. Tile Layout: No tile shall be less than (6 inches) and of equal width Tile Layout: No tile shall be less than (6 inches) and of equal width at walls. Place tile pattern in alternate direction. 4.3. Roll tile floor with a minimum (100 pound) roller. Roll tile floor with a minimum (100 pound) roller. 4.4. Install 4-inch vinyl cove base throughout the work area. Install 4-inch vinyl cove base throughout the work area. 5. Clean, seal, wax and buff all newly installed 12 inch VCT floor tile, after Clean, seal, wax and buff all newly installed 12 inch VCT floor tile, after tile has had ample curing time (per manufacture's specifications).

108107

123 122

121 112 113

119 118 155 117

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

MECHANICAL PLAN

AutoCAD SHX Text M1

AutoCAD SHX Text

AutoCAD SHX Text

%%UMECHANICAL PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CABINET

Mechanical: Demo: 1. Remove supply air vent and demo flex duct all the way back to Remove supply air vent and demo flex duct all the way back to existing hard duct. 2. Install new vent in center of room. Install new vent in center of room. a. Install flex duct from hard pipe to location in the center of the Install flex duct from hard pipe to location in the center of the room. b. Install new 2x2 lay in ceiling vent with foil back insulation. Install new 2x2 lay in ceiling vent with foil back insulation. c. Vent shall be like other vents in the space. Vent shall be like other vents in the space. 3. Open air return air grills are to remain in place in wall areas.Open air return air grills are to remain in place in wall areas.

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

ELECTRICAL NOTES

AutoCAD SHX Text E-2

AutoCAD SHX Text

1. ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA 70, THE NORTH CAROLINA STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND DEVICES SHALL BE NEW CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. EQUIPMENT SHALL BE SUITABLE FOR ITS APPLICATION (E.G. WHEN INSTALLED OUTDOORS, IT SHALL BE WEATHERPROOF, ETC.) 3. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS AND THE CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER. 4. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY FAMILIARIZING HIMSELF WITH ANY CONTRACTUAL REQUIREMENTS AS MAY BE SET FORTH IN THE OTHER DIVISIONS OF THE PROJECT SPECIFICATIONS. 5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE CONTRACTOR SHALL BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM, SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL CIRCUITS SHALL BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE SPECIFIC REQUIREMENTS OF EQUIPMENT. 6. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT. 7. ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUT OF DOORS, BUT SHALL BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE SHALL BE REPLACED AT NO ADDITIONAL COST. 8. DO NOT SCALE ELECTRICAL DRAWINGS. FIELD VERIFY ALL DO NOT SCALE ELECTRICAL DRAWINGS. FIELD VERIFY ALL DIMENSIONS. 9. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR SHALL ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION. 10. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE. IF NOT DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE CONTRACTING OFFICER PRIOR TO ROUGH-IN. 11. RACEWAYS AND DUCTS PENETRATING RATED FLOOR, CEILING OR RACEWAYS AND DUCTS PENETRATING RATED FLOOR, CEILING OR WALL ASSEMBLIES SHALL BE PROPERLY SEALED IN ACCORDANCE WITH THE CORRESPONDING UNDERWRITERS LABORATORIES (OR OTHER APPROVED THIRD PARTY TESTING AGENCY) APPROVED AND LISTED FIRESTOPPING MATERIALS AND MANUFACTURER APPROVED INSTALLATION TECHNIQUES COMPLYING WITH ALL APPLICABLE CODES. 12. ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE IF ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE IF APPLICABLE, MATCH EXISTING RACEWAY INSTALLATION METHODS AND ROUTINGS AT OR NEAR EXISTING FACILITIES. 13. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS SHALL BE RUN STRAIGHT AND TRUE. RUN PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL. 14. SURFACE MOUNTED PANELBOARDS, JUNCTION AND PULL BOXES, SURFACE MOUNTED PANELBOARDS, JUNCTION AND PULL BOXES, RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR WALLS SHALL BE SUPPORTED BY SPACERS TO PROVIDE A 1/4" MINIMUM CLEARANCE BETWEEN THE WALL AND EQUIPMENT. 15. CONDUCTOR SIZING IS BASED ON 75 DEGREE C. COPPER NEC CONDUCTOR SIZING IS BASED ON 75 DEGREE C. COPPER NEC RATINGS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY FOR EVALUATION/CORRECTION. 16. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR SHALL COORDINATE THE NAMEPLATE RATINGS OF ALL EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT. 17. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT SHALL BE RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS. 18. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS, FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE CONTRACTING OFFICER IF SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN SERVICE. 19. EXISTING CIRCUITING WHERE SHOWN IS FOR CONVENIENCE EXISTING CIRCUITING WHERE SHOWN IS FOR CONVENIENCE PURPOSES ONLY. VERIFICATION OF EXISTING WIRING DESTINATION, TERMINATION AND ADDITIONS OF NEW LOADS IS THE RESPONSIBILITY OF THE CONTRACTOR. 20. ABANDONED POWER WIRING, RACEWAYS AND CONDUCTORS, SHALL ABANDONED POWER WIRING, RACEWAYS AND CONDUCTORS, SHALL BE REMOVED BACK TO THEIR SOURCE. THE ACCESSIBLE PORTIONS OF ABANDONED CABLES (VOICE, DATA, VIDEO, ALARM, ETC.) SHALL BE REMOVED. 21. THE EXISTING ELECTRICAL SYSTEMS DEPICTED ON THESE THE EXISTING ELECTRICAL SYSTEMS DEPICTED ON THESE DRAWINGS HAVE BEEN COMPILED FROM GOVERNMENT RECORD DRAWINGS AND LIMITED FIELD VERIFICATION OF THE EXISTING CONDITIONS FOR THE PURPOSE OF INDICATING THE WORK REQUIRED AND ARE BELIEVED TO BE CORRECT. NOTWITHSTANDING, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, POINTS OF ACCESS AND FIELD CONDITIONS AFFECTING HIS WORK. 22. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE DRAWINGS.

108107

123 122

121 112 113

119 118 155 117

154124

154124

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

SS

AutoCAD SHX Text 3 3

AutoCAD SHX Text 1B-3

AutoCAD SHX Text

SS

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

ELECTRICAL DEMO

AutoCAD SHX Text E-1

AutoCAD SHX Text

AutoCAD SHX Text

%%UELEC. PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text 1B-2

AutoCAD SHX Text 1R-20

AutoCAD SHX Text 1R-20

AutoCAD SHX Text 1A-12

AutoCAD SHX Text 1A-30

AutoCAD SHX Text

SS

AutoCAD SHX Text 3 3

AutoCAD SHX Text 1B-3

AutoCAD SHX Text SEE REFERENCE DRAWINGS E-4 & E-6 PANEL LOCATIONS: PANEL A, RM122 PANEL B, RM122 PANEL R, RM133 PANEL L, RM133

AutoCAD SHX Text Demolition: Existing Office - 1. Remove the indicated 29ea 2' x 4' fluorescent light fixtures to Remove the indicated 29ea 2' x 4' fluorescent light fixtures to include raceway, conductors, and supports back to the first junction box in the area. 2. Remove the indicated 8ea switches to include raceway, Remove the indicated 8ea switches to include raceway, conductors, and supports back to the first junction box. 3. Remove the existing dual head emergency light to include Remove the existing dual head emergency light to include raceway, conductors and supports. Retain the emergency light for relocation. 4. Remove the existing horn/strobe fire alarm annunciator. Remove the existing horn/strobe fire alarm annunciator. Coordinate the removal and relocation of the annunciator with MCB Camp Lejeune Fire Department.

Combine neighboring dual T-comm outlers into single quad outlet re-route conduit, combine dual T-com outler into single quad outlet where possible

108107

123 122

121 112 113

119 118 155 117

115103

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1A-10

AutoCAD SHX Text 1A-6

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

RECEPTACLE PLAN

AutoCAD SHX Text E-3

AutoCAD SHX Text

AutoCAD SHX Text Lighting/Power: Large Office - 1. Install 9ea 2' x 4' LED troffers, 4800 lumens, 4000K color Install 9ea 2' x 4' LED troffers, 4800 lumens, 4000K color temperature, and minimum 80 color rendering index where indicated. Install 6ea 3-way switches where indicated. The lighting shall be switched in 3 rows as numbered. 2. Install relocated dual head emergency light to the column at the Install relocated dual head emergency light to the column at the door. Small Offices and Corridor - 1. Install 8ea 2' x 4' LED troffers, 3000 lumens, 4000K color Install 8ea 2' x 4' LED troffers, 3000 lumens, 4000K color temperature, and minimum 80 color rendering index where indicated. Install 3ea single pole switches where indicated. 2. Install 5ea 2' x 2' LED troffers, 2000 lumens, 4000K color Install 5ea 2' x 2' LED troffers, 2000 lumens, 4000K color temperature, and minimum 80 color rendering index where indicated. Install 2ea 3-way switches where indicated. 3. Install 1ea single pole switch in room 115 where indicated. Install 1ea single pole switch in room 115 where indicated. 4. Install 5ea 125V 20A receptacle where indicated.Install 5ea 125V 20A receptacle where indicated.

AutoCAD SHX Text Data Room 154: o Pull back all existing cabling fed in walls being demoed. Pull back all existing cabling fed in walls being demoed. o Home run conduit will need to be re-routed to newly constructed locations Home run conduit will need to be re-routed to newly constructed locations indicated on map. Pull box may be required if there are more than (2) 90 degree turns. Do not make a turn in a pull box. Reinstall existing cabling back into relocated conduit locations. o Contractor must be a telecommunications professional with a minimum of 3 Contractor must be a telecommunications professional with a minimum of 3 years experience installing components of telecommunications infrastructure. o Contractor will need to test each telecommunications outlet prior to removing Contractor will need to test each telecommunications outlet prior to removing faceplates to document bad jacks. Provide test reports to Base Telephone. o Contractor will need to reinstall old faceplates, insure labeling is correctly intact, Contractor will need to reinstall old faceplates, insure labeling is correctly intact, and re-test the reinstalled faceplates/telecommunications outlets. Anything that was good prior to being removed will need to be in working order after work is complete. Base Telephone will be responsible to repair anything that was bad prior to contractor removal. Provide final test reports to Base Telephone for approval.

Reroute existing conduit from demolished walls. Reinstall cabling.

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

SSS

AutoCAD SHX Text 3 3 3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SSS

AutoCAD SHX Text 3 3 3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

REMODEL OFFICES

AutoCAD SHX Text

PROJECT# XXXXXXXXXXXXXXXX

AutoCAD SHX Text

CONTRACT# N40085-10B-XXXX-XXXX

AutoCAD SHX Text

DWG: DAVID DELEONARD

AutoCAD SHX Text

USMC CAMP LEJEUNE

AutoCAD SHX Text

BLDG# 67

AutoCAD SHX Text

SHEET OF 11 OF 11 OF 11 11

AutoCAD SHX Text

LIGHTING PLAN

AutoCAD SHX Text E-4

AutoCAD SHX Text

AutoCAD SHX Text

%%ULIGHTING PLAN

AutoCAD SHX Text

NO SCALE

A-2X4 LED TROFFER 4800 LUMENS 4000K COLOR TEMPERATURE CRI 80 MINIMUM B-2X4 LED TROFFER 3000 LUMENS 4000K COLOR TEMPERATURE CRI80 MINIMUM C-2X2 LED TROFFER 2000 LUMENS 4000K COLOR TEMPERATURE CRI 80 MINIMUM

Sheets and Views
67-1 TITLE PAGE
67-2 A-1 DEMO
67-3 A-2 NEW WORK
67-4 A-3 FINISH PLAN
67-5 A-4 CEILING PLAN
67-6 A-5 FLOORING PLAN
67-7 MECHANICAL PLAN
67-8 E1 ELECTRICAL NOTES
67-9 E2 ELECTRICAL DEMO
67-10 E3 RECEPTACLE
67-11 E-4 LIGHTING PLAN

File details come from the government source that posted it. Updated .