Asbestos Survey FY20 Infrastructure Reset Demo Buildings

Marine Corps Base Camp Lejeune Project # 20-0001

Package C

Report Prepared By:

Christopher B. Walker

The Walker Group Architecture, Inc September 28th, 2020

WGA Project No. – 2001.IR20

Project Information

The Walker Group Architecture, Inc. was contracted by Camp Lejeune to conduct an asbestos sampling survey for Buildings/Structures: AS721, AS4128, G642, G699, RR3, RR15, RR16, RR26, RR49, RR51, RR92, RR95, SRR186, STC911, SVL328, TC608, TC754, TC760, TC761, TC672, TC775, TC806, TC806, TC807, TC813, TC817, TC828, TC829, TC836, TC837, TC838, TC839, TC942, TC1004, TC1006, TC1019, TC1026, TC1027, TC1060, TC1061, TC1062, TC1063, TC1142, TC1143, TC1160, TC1161, TC1162, TP445, VL331. Buildings/Structures AS2004, SRR80, SVL335, and TC811 were also contracted for a survey however, the structure did not contain any suspect materials to sample after site investigation. The specified buildings or structures are slated for demolition on board Marine Corps Base Camp Lejeune. An asbestos survey has been requested prior to disturbance of any potential asbestos containing materials (ACM).

Scope of Services

A. The survey was performed on 07/31/14, 02/02/18, 02/08/18, 02/17/18, 03/17/18, 04/16/19, 04/18/19, 04/22/20, 04/23/20, 04/2820, 05/13/20, 05/14/20 by Christopher B.

Walker (NC Accredited Inspector #12878, expires January 31, 2021). The sampling was conducted in general accordance with the U.S. Environmental Protection Agency (EPA) requirements as defined in the asbestos Hazards Emergency Response Act (40 CFR Part 763) guidelines (AHERA) and in general accordance with the North Carolina Health Hazards Control Unit (NCHHCU).

B. The survey was conducted to identify the presence of asbestos containing materials (ACM) prior to repairs to the building.

C. The building was assessed to determine homogenous areas (groups of materials appearing to have been installed in the same general time period and uniform in color and texture).

D. As per AHERA, sufficient samples were collected from random locations of each homogenous area, with the number of samples based on the following criteria:

a. Thermal Insulation Materials (piping, breeching, boiler insulation, etc.) – A minimum of (3) samples are required. Patch areas (less than 6 square or liner feet) may have (2) sample collected.

b. Surfacing Materials (plaster, fireproofing, etc.) – A minimum of (7) samples are to be taken for areas greater than 5,000 square feet, five (5) samples for areas greater than 1,000 square feet, but less than 5,000 square feet, three

(3) samples for areas less than 1,000 square feet, two (2) samples for patching materials.

c. Miscellaneous Materials (flooring, adhesives, roofing, wallboard, etc.) – A minimum of (2) samples are required.

If any one sample of a material from a homogenous area is found to be positive, then that material is considered positive, regardless of results of other samples of that material, within that area.

Samples

A. The Walker Group Architecture collected suspect samples and shipped them to EMSL Analytical, Inc. (NVLAP Accredited Laboratory 102104-0) for PLM (polarized Light Microscopy) analysis. In an effort to reduce cost, the Walker Group instructed the laboratory to Stop Analysis at the first positive sample for each suspect material HGA and not to analyze the remaining samples from the same HGA.

AS721

Findings

A. Building Description and Findings (Inspected 04-16-19)

AS721 is a wood gazebo structure. The building exterior is painted wood and the roof is wood framed with asphalt shingles.

B. Laboratory Results

Material Material Type

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles/Felt Misc. Roof NF Non-Detected N/A

Based on the sample analysis, none of the materials were found to be Asbestos Containing Materials.

Building AS4128

A. Building Description and Findings (Inspected 04/28/20)

Building AS4128 is an operational storage building. The building exterior is cmu masonry with a wood framed roof and asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc. Roof NF Non-Detected N/A

Exterior Door/Window Caulk Misc Exterior Doors/Windows

NF Non-Detected N/A

Building G642

A. Building Description and Findings (Inspected 04-22-20)

Building G642 is a wood storage building. The building exterior is wood siding and the roof is wood framed with asphalt shingles.

Location Friabilit y Laboratory Result Approx.Quantit y

Asphalt shingles/felt Misc. Roof NF Non-Detected N/A

Based on the sample analysis, none of the materials were found to be Asbestos Containing

Building G699

A. Building Description and Findings (Inspected 02-08-18)

Building G699 is a storage building. The building exterior is CMU block and has a wood framed roof with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Door Caulk Misc Exterior NF Non-Detected N/A

Building RR3

A. Building Description and Findings (Inspected 04-23-20)

Building RR3 is an abandoned cafeteria building. The building exterior is brick masonry. Interior partitions are wood framed with gypsum board/plaster and the roof is wood framed with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Gypsum Board/Joint Compound Misc. Interior Walls NF Non-Detected N/A

Plaster Walls/Ceilings Surf. Interior Walls/Ceiling

NF Non-Detected N/A

12x12 Cream VCT/Mastic Misc Interior Floor NF Non-Detected SF Gray Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A 2x2 Acoustical Ceiling Tile Misc Ceilings NF Non-Detected N/A Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A Exterior Door Caulk Misc Exterior Doors NF Non-Detected N/A Exterior Window Caulk Misc Exterior Window NF Non-Detected N/A Expansion Joint at Loading Dock Misc Loading Dock NF Non-Detected N/A Gray Roof Sealant at Vents Misc Roof Vents NF 10% Chrysotile 54LF Black Sealant at Cupola Base Misc Cupola NF Non-Detected N/A Black Sealant at Roof Vents Misc Roof Vents NF 3% Chrysotile 20LF White Sealant at Cupola Misc Cupola NF Non-Detected N/A

Based on the sample analysis, the following materials were found to be Asbestos Containing Materials.

Gray Sealant at Roof Vents Black Sealant at Roof Vents

Additional items were found to be asbestos containing materials on previous government provided reports. See attached Appendix A for further information.

ACM Materials found in previous government report in area of work:

- Pipe Insulation, Aircell – approx. 30LF

- Pipe Insulation Debris- approx. 6SF

- Exterior Door Caulking- approx. 160LF

- Transite Panel- approx. 1SF

- Gasket Material- 1EA

- Roofing Material Attic Debris- approx. 10SF

Materials found to contain asbestos in current inspection report and government provided inspection report should all be considered for the purpose of any demolition/renovation activities and disturbance.

Building RR15

Building RR15 is an operation steam maintenance building. The building exterior is a is brick and cmu masonry. Interior partitions are cmu and the roof is concrete framed with a built-up roof system.

Location Friability Laboratory Result Approx.Quantity

Exterior Window Caulk Misc. Exterior Windows

NF 3% Chrysotile 250LF

Exterior Door Caulk Misc. Exterior Doors NF 3% Chrysotile 34LF White Residual Caulk at Door Misc. Exterior Doors NF Non-Detected SF Roof Flashing Misc. Roof NF 8% Chrysotile 175SF Built Up Roof Misc. Roof NF Non-Detected N/A Tar Sealant Near ladder Misc. Exterior wall near ladder NF 8% Chrysotile 2SF

Based on the sample analysis, the following materials were found to be Asbestos

Exterior Window Caulk Exterior Door Caulk Roof Flashing Tar Sealant Near ladder

Building RR16

A. Building Description and Findings (Inspected 04-18-19)

Building RR16 is an abandoned storage building. The building exterior is wood and wood siding. Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles/Tar Paper Misc Exterior NF Non-Detected N/A

Window Caulk Misc Exterior NF Non-Detected N/A Exterior Building Felt Behind Siding

Misc Exterior NF Non-Detected N/A purpose of any demolition/renovation activities and disturbance.

ACM Materials found in previous government report in area of work:

-Asphalt Shingles/Tar Paper – approx. 423SF -Black roof sealant at north & south bottom course – approx. 60LF

Building RR49

A. Building Description and Findings (Inspected 04-20-20)

Building RR49 is an abandoned event building. The building exterior is masonry with a textured finish. Interior partitions are wood framed with gypsum board/plaster and the

Location Friability Laboratory Result Approx.Quantity

Exterior Stucco Surf. Exterior Walls NF Non-Detected N/A

Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Textured Ceiling Surf. Ceilings F Non-Detected N/A Exterior Window Caulk Misc Exterior

Windows NF 15% Chrysotile 368LF

Gray Roof Sealant at Vents Misc Roof NF 15% Chrysotile 2SF

Asphalt Shingle/Felt Misc Roof NF Non-Detected N/A

Exterior Window Caulk Gray Roof Sealant at Vents

- Silver Roof Sealant – approx. 64LF

Building RR51

Building RR51 is an abandoned office/storage building. The building exterior is masonry with a textured finish. Interior partitions are wood framed with gypsum board/plaster and the roof is wood framed with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Exterior Stucco Surf. Exterior Walls NF Non-Detected N/A

Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Rubber Base/Mastic Misc. Interior Walls NF Non-Detected N/A Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A

Exterior Window/Door Caulk Misc Exterior Caulk NF Non-Detected N/A

- Exterior Caulk at Aluminum Replacement Windows – approx. 480LF

Building RR92

A. Building Description and Findings (Inspected 05-13-20)

Building is a wood framed boat shelter/dock with wood paneling on walls and an asphalt shingle roof.

Asphalt Shingles Misc. Roof NF Non-Detected N/A

Building RR95

A. Building Description and Findings (Inspected 03-17-18)

Building RR95 is a public toilet at the weapons training range. The building is a concrete structure.

No Suspect Materials found during inspection N/A N/A N/A N/A N/A

Building STC911

Building STC911 is a fitness facility with indoor playing courts. The building exterior is CMU block with an E.I.F.S. finish system. The roof consists of asphalt shingles. The interior walls and ceiling consist of a high impact gypsum board on furring and CMU block.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Exterior EIFS System Surface Exterior Wall F Non-Detected N/A Interior Gypsum/joint Compound Misc Interior Walls F Non-Detected N/A 12x12 white VCT Misc Floors NF Non-Detected N/A Rubber base/mastic Misc Floors NF Non-Detected N/A

Building SVL328

Building SVL328 is a range support building. The building is a wood framed structure with wood exterior/interior walls and metal panel roofing.

No Suspect Materials found during inspection N/A N/A N/A N/A N/A

Building TC608

A. Building Description and Findings (Inspected 07-31-14)

a. Building TC608 is an operation laundry building. The building consists of pre-engineered steel frame, metal wall panels, and a metal roof. There is a freestanding sewing room within the building which consists of wood framing, gypsum board walls, and gypsum board ceiling.

A. Laboratory Results

Location Friability Laboratory Result Approx.Quantity

Exterior Window Caulk Misc. Exterior Windows NF Non-Detected N/A

Exterior caulk at pipe penetrations

Misc. Exterior Walls NF Non-Detected N/A

Mastic at Duct Fittings, Laundry Machines

Misc. Interior Sewing room above ceiling

NF Non-Detected N/A

Black VCT/Mastic with cream specks

Misc. Interior Bathroom, and Sewing room

NF Non-Detected N/A

Gypsum Board/ Joint Compound

Misc. Interior Bathroom F Non-Detected N/A

Black Rubber Base/ Mastic

Misc. Interior Bathroom NF Non-Detected N/A

Based on the sample analysis, none of the sampled materials were detected to contain asbestos.

Building TC754

Building TC754 is an abandoned office building. The building exterior is masonry with a textured finish. Interior partitions are wood framed with gypsum board/plaster and the

Location Friability Laboratory Result Approx.Quantity

Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A 2x2 ACT Surf. Ceilings F Non-Detected N/A 12x12 Gray VCT/Mastic Misc Interior Floor NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior

Windows/doors NF Non-Detected N/A

Asphalt Shingles Misc Roof NF Non-Detected N/A Blue 12x12 VCT/Mastic Misc. Interior Floor NF Non-Detected N/A Exterior Wall Expansion Joint Misc. Exterior Wall NF 5% Chrysotile 20LF

Exterior Wall Expansion Joint

Building TC760

B. Building Description and Findings (Inspected 02-02-18)

Building TC760 is a storage facility. The building consists of a pre-engineered metal building structure with exterior metal panels at the walls and roof. The interior is metal framed and metal panel walls with concrete floors.

C. Laboratory Results

Location Friability Laboratory Result Approx.Quantity

Concrete Expansion Joint Misc Exterior wall NF Non-Dectected N/A

Roof sealant at exhaust fan Misc Roof NF Non-Dectected N/A Gray metal roof sealant Misc Roof NF Non-Dectected N/A

Containing Materials

Building TC761

A. Building Description and Findings (Inspected 02-02-18)

Building TC761 is a storage facility. The building consists of a pre-engineered metal

Window glazing Misc Windows NF Non-Detected N/A

Concrete expansion joints Misc Exterior walls NF Non-Detected N/A Gray roof sealant Misc Roof NF Non-Detected N/A Black sealant at exhaust fans Misc Roof NF Non-Detected N/A

Containing Materials

ACM Materials found in previous government report in area of work:

-Black roofing sealant at ridge vents – approx. 80 sf -Window glazing material – approx. 210 lf -Silver roofing sealant-roof coating throughout – approx. 1,000 sf

Building TC762

Building TC762 is a storage facility. The building consists of a pre-engineered metal

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound Misc Interior Wall NF Non-Detected N/A

Concrete expansion joint Misc Exterior wall NF 3% Chrysotile 1,268LF Roof sealant at exhaust fan Misc Roof NF Non-Detected N/A Roof sealant Misc Roof NF Non-Detected N/A Rubber base/mastic Misc Floor NF Non-Detected N/A 2x2 ACT Misc Ceiling F Non-Detected N/A

Containing Materials:

Concrete expansion joint

-Silver roofing sealant – roof coating throughout – approx. 9,000 sf

Building TC806

Building TC806 is an administrative office. The building exterior is cmu cavity walls.

The roof consists of wood framing and asphalt shingles. Interior walls are steel stud framed and cmu. The building has a gypsum board ceiling throughout.

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound Misc Interior Walls F Non-Detected N/A

Roofing sealant at exhaust fans Misc Roof NF Non-Detected N/A VCT cream with specks Misc Floor NF Non-Detected N/A Door/window caulk Misc Door/Window NF Non-Detected N/A Asphalt shingles/felt Misc Roof NF Non-Detected N/A Concrete expansion joint Misc Exterior Wall NF Non-Detected N/A

-Roofing sealant at vents and pips, patching – approx. 4 sf

Materials found to contain asbestos in current inspection report and

Building TC807

Building TC807 is an academic instruction facility. The building exterior is cmu cavity walls. The roof consists of wood framing and asphalt shingles. Interior walls are steel stud framed and cmu. The building has a gypsum board ceiling throughout.

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound Misc Interior Wall F Non-Detected N/A

Door/window sealant Misc Door/Window NF Non-Detected N/A Roofing sealant at exhaust fans Misc Roof NF Non-Detected N/A

VCT cream with specks Misc Floor NF Non-Detected N/A

-Roofing sealant at cyclical vents – approx. 16 sf

Building TC813

Building TC813 is a masonry bathroom building with a concrete floor, and wood roof system with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Gypsum Board/Joint Compound Misc Interior NF Non-Detected N/A

Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A

Building TC817

Building TC817 is a storage warehouse. The building exterior is CMU block and has a wood framed roof with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof exhaust fan mastic Misc Roof NF 8% Chrysotile 4SF Exterior expansion joint Misc Walls NF 4% Chrysotile 40LF Cloth expansion joint at attic HVAC unit Misc Ceiling NF 60% Chrysotile 4SF Gypsum/joint compound Misc Walls F Non-Detected N/A

Roof exhaust fan mastic Exterior expansion joint Cloth expansion joint at attic HVAC unit

Building TC828

A. Building Description and Findings (Inspected 04-20-20)

Building TC828 is an abandoned office building. The building exterior is masonry.

Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

12x12 Cream VCT/Mastic Misc. Interior Floors NF Non-Detected N/A

Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Asphalt Shingles/Felt Misc Roof NF Non-Detected SF

Rubber Base/Mastic Misc Interior Walls NF Non-Detected SF

Roof Sealant at Vents Misc Roof NF 5% Chrysotile 24LF

Roof Sealant at Vents

- Black Sealant at Roof Vents – approx. 5LF

- Transite Panel in attic- approx. 3SF

Building TC829

Building TC829 is a recruit barracks facility. The building exterior is cmu cavity walls.

framed and cmu. The building has a drop down acoustical ceiling.

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound Misc Interior Walls F <1% Chrysotile 4,000SF

Transite panel in attic Misc Ceiling NF 15% Chrysotile 12SF

Roofing sealant at exhaust fans Misc Roof NF <1% Chrysotile 6SF

Exterior door caulk Misc Exterior Door NF Non-Detected N/A

Gypsum/joint compound

Transite panel in attic

Roofing sealant at exhaust fans

Building TC836

C. Building Description and Findings (Inspected 02-02-18)

Building TC836 is a recruit barracks facility. The building exterior is cmu cavity walls.

D. Laboratory Results

Location Friability Laboratory Result Approx.Quantity

Concrete expansion joint interior Misc Exterior wall NF Non-Detected N/A

Gypsum/joint walls/ceiling Misc Interior wall/ceiling F Non-Detected N/A

VCT 1 light cream & mastic Misc Floor NF Non-Detected N/A

VCT 2 darker cream & mastic Misc Floor NF Non-Detected N/A

Exterior door/window sealant Misc Exterior door/window NF Non-Detected N/A

Roofing sealant at exhaust fans Misc Roof NF Non-Detected N/A

Additional items were found to be asbestos containing materials on previous government provided reports. See attached Appendix A for further information.

-Roofing sealant at ridge vents – approx. 55 sf

Building TC837

A. Building Description and Findings (Inspected 05-14-20)

Building TC837 is an abandoned academic instruction facility. The building exterior is cmu cavity walls. The roof consists of wood framing and asphalt shingles. Interior walls are steel stud framed and cmu. The building has a gypsum board ceiling throughout.

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound (older original ceiling)

Misc Interior Ceiling

NF <1% Chrysotile 110SF

Exterior Door/window sealant Misc Door/Window NF Non-Detected N/A Exterior Wall Expansion Joint Misc Exterior Walls NF Non-Detected N/A

Mastic at Roof Vents Misc Roof NF Non-Detected N/A

Penetrations 2x2 ACT Misc Ceiling NF Non-Detected N/A

Gypsum/joint compound (older original ceiling)

-Roofing sealant at cyclical vents – approx. 6 sf

Building TC838

Building TC838 is a recruit barracks facility. The building exterior is cmu cavity walls.

Material Material Type

Location Friability Laboratory Result Approx.Quantity

Joint/Gypsum board Misc Interior wall F Non-Detected N/A

Exterior door/window caulk Misc Exterior door/window NF Non-Detected N/A

2x2 ACT Misc Ceiling F Non-Detected N/A

Cream ACT Misc Ceiling F Non-Detected N/A

Concrete Expansion joint Misc Exterior Wall NF Non-Detected N/A

Roof sealant at exhaust fans Misc Roof NF Non-Detected N/A Asphalt shingles Misc Roof NF Non-Detected N/A

-Roofing sealant at ridge vents – approx. 24 sf

Building TC839

Building TC839 is an administrative office. The building exterior is cmu cavity walls.

Location Friability Laboratory Result Approx.Quantity

Gypsum/joint compound Misc Interior Wall F Non-Detected N/A

Exterior window caulk Misc Exterior window NF Non-Detected N/A

2x2 ACT Misc Ceiling F Non-Detected N/A

Concrete Expansion joint Misc Exterior Wall NF Non-Detected N/A

Roof sealant at exhaust fans Misc Roof NF Non-Detected N/A

Building TC942

Building TC942 is a storage facility. The building is a steel structure with a wood framed ceiling, wood/gypsum interior walls, and drop-in acoustical ceiling tiles.

Location Friability Laboratory Result Approx.Quantity

Transite panel in attic Misc Ceiling NF 10% Chrysotile 12SF

Roof sealant Misc Roof NF 6% Chrysotile 2,290SF Gypsum/joint compound Misc Walls F Non-Detected N/A 2x2 ACT Misc Ceiling F Non-Detected N/A Window Glazing Misc Ceiling NF 3% Chrysotile 3SF

Transite panel in attic

Roof sealant at exhaust fan Window Glazing

Building TC1004

A. Building Description and Findings (Inspected 02-08-18 and 02-17-18)

Building TC1004 is an IT/Comm Center. The building exterior is CMU block and has a wood framed roof with asphalt shingles. The interior walls are gypsum board with a drop-in acoustical tile ceiling.

Material Material Type

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof mastic at exhaust fan Misc Roof NF 3% Chrysotile 12SF Exterior expansion joint Misc Exterior Wall NF Non-Detected N/A Exterior door caulk Misc Exterior Wall NF Non-Detected N/A Transite Panel in attic Misc Attic NF 15% Chrysotile 12SF VCT/Mastic Misc Floor NF Non-Detected N/A Rubber Base/Mastic Misc Floor NF Non-Detected N/A Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A 2x2 ACT Misc Ceiling F Non-Detected N/A

Notes: TSI-Thermal Systems Insulation Surface-Surfacing Material Misc.- Miscellaneous Material F-Friable NF-Non-Friable

-Exterior caulking at expansion joints – approx. 40 lf

Roof mastic at exhaust fan

Transite Panel in attic

Building TC1006

Building TC1006 is a Classroom facility. The building exterior is CMU block and has a wood framed roof with asphalt shingles. The interior walls and ceiling are gypsum board.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof exhaust mastic Misc Roof NF Non-Detected N/A Exterior expansion joint material

Misc Exterior Walls NF 4% Chrysotile 40LF

Door/window caulk Misc Walls NF Non-Detected N/A Gypsum/joint compound Misc Walls F Non-Detected N/A 12x12 cream w/brown specks VCT/mastic

Misc Floors NF Non-Detected N/A

Transite panel debris in attic Misc Ceiling NF 10% Chrysotile 5SF

Exterior expansion joint material Transite panel debris in attic

-Exterior caulking at northwest entry door – approx. 16 lf

Building TC1019

Building TC1019 is a Battery Headquarters facility. The building exterior is CMU block and has a wood framed roof with asphalt shingles. The interior walls and ceiling are gypsum board.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof exhaust fan mastic Misc Roof NF Non-Detected N/A Expansion joint Misc Walls NF 2% Chrysotile 40LF Exterior door/window caulk Misc Exterior Walls NF 6% Chrysotile 350LF Gypsum/joint compound Misc Walls F Non-Detected N/A 12x12 cream VCT/mastic Misc Floors NF <1% Chrysotile 3,500SF Rubber floor mastic Misc Floors NF Non-Detected N/A

Expansion joint Exterior door/window caulk 12x12 cream VCT/mastic

Building TC1026

Building TC1026 is an Administrative office facility. The building exterior is CMU block

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof exhaust fan mastic Misc Roof NF Non-Detected N/A Expansion joint Misc Walls NF 4% Chrysotile 40LF Exterior door/window caulk Misc Exterior Walls NF Non-Detected N/A

12x12 gray VCT/mastic Misc Floors NF <1% Chrysotile 4,000SF

12x12 gray VCT/mastic

-Gray roofing sealant at westside vents – approx. 3 sf

Building TC1027

Building TC1027 is an Academic Instruction facility. The building exterior is CMU block

Location Friability Laboratory Result Approx.Quantity

Roof exhaust fan mastic Misc Roof NF 10% Chrysotile 2SF

Expansion joint Misc Walls NF 4% Chrysotile 40LF Exterior door/window caulk Misc Exterior Walls NF 5% Chrysotile 80LF

12x12 black VCT/mastic Misc Floors NF Non-Detected N/A

Roof exhaust fan mastic

Building TC1060

A. Building Description and Findings (Inspected 02-17-18)

Building TC1060 is a bachelor enlisted quarters building. The building exterior is CMU block and has a wood framed roof with asphalt shingles. The interior walls are gypsum board with popcorn texture, gypsum board ceilings.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof mastic at exhaust fan Misc Roof NF 3% Chrysotile 2SF Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Beige VCT Misc Floor NF Non-Detected N/A Popcorn ceiling texture Surface Ceiling F Non-Detected N/A

Exterior door/window caulk Misc Exterior Wall NF Non-Detected N/A Rubber Base/Mastic Misc Floor NF Non-Detected N/A Exterior expansion joint Misc Exterior Wall NF 5% Chrysotile 40LF

Building TC1061

Building TC1061 is a bachelor enlisted quarters building. The building exterior is CMU

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof mastic at exhaust fan Misc Roof NF 3% Chrysotile 2SF Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Beige VCT Misc Floor NF Non-Detected N/A Popcorn ceiling texture Surface Ceiling F Non-Detected N/A

Exterior door/window caulk Misc Exterior Wall NF Non-Detected N/A

Exterior expansion joint Misc Exterior Wall NF 5% Chrysotile 40LF

Building TC1062

Building TC1062 is a bachelor enlisted quarters building. The building exterior is CMU block and has a wood framed roof with asphalt shingles. The interior walls are gypsum

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof mastic at exhaust fan Misc Roof NF Non-Detected N/A Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Beige VCT Misc Floor NF Non-Detected N/A Popcorn ceiling texture Surface Ceiling F Non-Detected N/A Exterior door/window caulk Misc Exterior Wall NF Non-Detected N/A

Exterior expansion joint Misc Exterior Wall NF 3% Chrysotile 40LF

Building TC1063

Building TC1063 is a bachelor enlisted quarters building. The building exterior is CMU

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof mastic at exhaust fan Misc Roof NF 3% Chrysotile 3LF Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Beige VCT Misc Floor NF Non-Detected N/A Popcorn ceiling texture Surface Ceiling F Non-Detected N/A Exterior door/window caulk Misc Exterior Wall NF 3% Chrysotile 40LF

Exterior expansion joint Misc Exterior Wall NF 5% Chrysotile 36LF

Roof mastic at exhaust fan

Building TC1142

Building TC1142 is an abandoned office building. The building exterior is masonry.

Interior partitions are wood framed with gypsum board/plaster and the roof is wood framed with asphalt shingles.

Location Friability Laboratory Result Approx.Quantity

12x12 Cream VCT/Mastic Misc Interior Floor NF Non-Detected N/A

Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior

Doors/Windows NF Non-Detected N/A

Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A Textured Ceiling Surf. Ceilings F Non-Detected N/A Roof Sealant at Vents Misc. Roof NF Non-Detected N/A

Building TC1143

Building TC1143 is an Academic Instruction facility. The building exterior is CMU block

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Roof exhaust fan mastic Misc Roof NF Non-Detected N/A Expansion joint Misc Walls NF Non-Detected N/A Exterior door/window caulk Misc Exterior Walls NF Non-Detected N/A Gypsum/joint compound Misc Walls F Non-Detected N/A 12x12 cream VCT/mastic Misc Floors NF Non-Detected N/A Spray texture on gypsum ceiling Surface Ceiling F Non-Detected N/A

-Roofing sealant at ridge vents – approx. 12 sf

Building TC1160

Building TC1160 is an abandoned lodging facility. The building exterior is masonry.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A

Window/Door Caulk Misc Exterior Doors/Windows

NF Non-Detected N/A

Carpet Mastic/Felt Misc Under Carpet NF Non-Detected N/A Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A

Additional items were found to be asbestos containing materials on previous

- Residual Mastic – approx. 5SF

Building TC1161

Building TC1161 is an abandoned lodging facility. The building exterior is masonry.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A

Window/Door Caulk Misc Exterior Doors/Windows

NF Non-Detected N/A

Carpet Mastic/Felt Misc Under Carpet NF Non-Detected N/A

- Exterior Caulking – approx. 204LF

- Gray Roof Sealant at Vents- approx. 5SF

Building TC1162

Building TC1162 is an abandoned lodging facility. The building exterior is masonry.

Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A

Window/Door Caulk Misc Exterior Doors/Windows

NF Non-Detected N/A

Carpet Mastic/Felt Misc Under Carpet NF Non-Detected N/A

- Black Roof Sealant at Vents – approx. 8SF

- Caulking Material at Expansion Joints- approx. 80LF

Building TP445

Building TP445 is an unoccupied storage building. The building exterior walls are wood framed, and the roof is wood with asphalt shingles. There are no interior partitions and the interior ceiling is gypsum board.

Location Friability Laboratory Result Approx.Quantity

Exterior Window Caulk Misc Exterior NF Non-Detected N/A

Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior

Wall/Ceilings NF Non-Detected N/A

Building VL331

Building VL331 is a public toilet building. The building exterior walls are cmu block with a wood framed, asphalt shingle roof. The interior walls are cmu block with gypsum board ceiling.

Location Friability Laboratory Result Approx.Quantity

Asphalt Shingles Misc Roof NF Non-Detected N/A

Exterior window caulk Misc Exterior NF Non-Detected N/A Mastic at roof exhaust Misc Roof NF Non-Detected N/A Gypsum/Joint Compound Misc Interior F Non-Detected N/A

Disposal

A. In accordance with the NCHHCU regulations, asbestos containing materials (ACM) waste should be taken to an approved landfill. All demolition/renovation work must be performed in accordance with NESHAP asbestos regulations, 40CFR61, Subpart M, and OSHA Regulations 29 CFR 1926.1101. Any disturbance should be conducted in accordance with federal, state, and local regulations.

Recommendations

A. Any demolition/renovation work in which ACM is disturbed must be in compliance with, EPA, OSHA and the state of North Carolina regulations.

Abatement work shall be conducted by NC Accredited asbestos workers under the supervision of a NC accredited asbestos supervisor. The contractor conducting asbestos abatement activities must notify the North Carolina Department of Health and Human Services (HHS) ten (10) days prior to the disturbance of ACM if it is friable and greater than or equal to 160 square feet, 260 linear feet or 35 cubic feet.

B. If additional suspect materials are discovered during demolition/renovation, they should be classified presumed to be asbestos-containing until sampling by a state of North Carolina licensed Asbestos Building Inspector personnel and analysis by a NVLAP-Accredited and state of North Carolina licensed laboratory can be performed.

See attached for Accreditations, Asbestos Lab Results and Chain of Custody. If further information is required, please contact me at 1-252-636-8778

Report Prepared by:

Christopher B. Walker North Carolina Asbestos Inspector Accreditation# 12878 The Walker Group Architecture, Inc., PO Box 541, New Bern, NC 28560

DRAWING NO.DATE

DRAWN BY

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING RR3

MCB CAMP LEJEUNE

1/64"=1'-0"

05-11-12

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\RR3\RR3-1.dwg

GROUP

ARCHITECTURE

WALKER

th e

N

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

BLACK AND GRAY ROOF SEALANT AT MECHANICAL ROOF VENTS - APPROX. 74LF

AutoCAD SHX Text *SEE GOV'T ASBESTOS REPORT AND PLAN FOR ADDITIONAL ASBESTOS CONTAINING MATERIAL LOCATIONS

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING RR15

MCB CAMP LEJEUNE

1/16"=1'-0"

05-18-20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\RR15\RR15.dwg

GROUP

ARCHITECTURE

WALKER

th e

N

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

EXTERIOR WINDOW CAULK - APPROX. 250LF

AutoCAD SHX Text

AutoCAD SHX Text

EXTERIOR DOOR CAULK - APPROX. 34LF

AutoCAD SHX Text

AutoCAD SHX Text

SILVER ROOF FLASHING - APPROX. 175SF

AutoCAD SHX Text

AutoCAD SHX Text

TAR SEALANT - APPROX. 2SF

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS LOCATED IN EXTERIOR WINDOW CAULK. APPROX. 250LF

AutoCAD SHX Text

ASBESTOS LOCATED IN EXTERIOR DOOR CAULK. APPROX. 34LF

AutoCAD SHX Text

ASBESTOS LOCATED IN TAR SEALANT. APPROX. 2SF

ASBESTOS LOCATED IN SILVER ROOF FLASHING AT ROOF PENETRATIONS ABOVE. APPROX. 175SF

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING RR26

MCB CAMP LEJEUNE

3/16"=1'-0"

05-27-20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\RR26\RR26.dwg

GROUP

ARCHITECTURE

WALKER

th e

N

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

ROOF SEALANT AT BRICK CHIMNEY ABOVE - APPROX. 6LF

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING RR49

MCB CAMP LEJEUNE

N.T.S

05/08/20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\RR49\RR49.dwg

GROUP

ARCHITECTURE

WALKER

th e

N

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ROOF SEALANT AT MECHANICAL VENTS ON ROOF - APPROX. 2SF

AutoCAD SHX Text

ASBESTOS LOCATED IN WINDOW CAULKING. TYP.

DRAWING NO.

GROUP

ARCHITECTURE

WALKER

th e DATE

DRAWN BY

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING TC754

MCB CAMP LEJEUNE

N.T.S

05-27-20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC754\TC754.dwg

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR WALL EXPANSION JOINT, APPROX. 20LF

ASBESTOS IDENTIFIED IN EXTERIOR WALL EXPANSION JOINT, APPROX. 20LF

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC762\TC762-1.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC762

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text ASBESTOS IDENTIFIED AT INT. CONC. EXPANSION JOINTS THROUGHOUT FLOOR AND AT PERIMETER. TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED AT INTERIOR CONCRETE SLAB EXPANSION JOINTS, APPROX. 1,268LF.

AutoCAD SHX Text

AutoCAD SHX Text ASBESTOS WAS IDENTIFIED IN 2016 CAMP LEJEUNE SURVEY AT THE SILVER ROOFING SEALANT- ROOF COATING THROUGHOUT. APPROX. 9,000SF

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC817\TC817.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC817

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN CLOTH EXPANSION JOINT MATERIAL AT ATTIC HVAC UNIT PIPING

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF EXHAUST FAN MASTIC, APPROX. 4SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN CLOTH EXPANSION JOINT AT ATTIC HVAC UNIT, APPROX. 4SF.

ARCHITECTURE

WALKER

th e DATE

DRAWN BY

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING TC828

MCB CAMP LEJEUNE

N.T.S

05-11-20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC828\TC828.dwg

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF SEALANT AT EXHAUST VENT

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOFING SEALANT AT EXHAUST FANS, APPROX. 24LF.

AutoCAD SHX Text

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC829\TC829.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC829

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text ASBESTOS IDENTIFIED IN GYPSUM BOARD/JOINT COMPOUND AT WALLS AND CEILINGS. TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN GYPSUM/JOINT COMPOUND AT WALLS/CEILINGS, APPROX. 4,000SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN TRANSITE PANEL IN ATTIC, APPROX. 12SF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOFING SEALANT AT EXHAUST FANS, APPROX. 6SF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF SEALANT AT EXHAUST VENTS, TYPICAL OF (3) VENTS.

ASBESTOS IDENTIFIED IN TRANSITE PANEL DEBRIS IN ATTIC.

ARCHITECTURE

WALKER

th e DATE

DRAWN BY

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

BUILDING TC837

MCB CAMP LEJEUNE

N.T.S

03-27-20

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC837\TC837.dwg

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN GYPSUM BOARD/JOINT COMPOUND, APPROX. 110SF.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC942\TC942-1.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC942

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text ASBESTOS IDENTIFIED IN TRASITE PANELING. TYPICAL FOR (4) AREAS NEAR OLD VENT LOCATIONS.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN TRANSITE PANEL IN ATTIC, APPROX. 12SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF SEALANT, APPROX. 2,290SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN WINDOW GLAZING, APPROX. 3SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN WINDOW GLAZING MATERIAL.

ASBESTOS IDENTIFIED IN ROOF SEALANT NEAR RIDGE AND SURROUNDING AREA.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1004\TC1004.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1004

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT (3) EXHAUST VENTS.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHAUST FAN, APPROX. 12SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN TRANSITE PANEL IN ATTIC, APPROX. 12SF.

AutoCAD SHX Text

AutoCAD SHX Text ASBESTOS WAS IDENTIFIED IN 2016 CAMP LEJEUNE SURVEY IN THE EXTERIOR CAULKING AT EXPANSION JOINTS. APPROX. 40LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN TRANSITE PANELING DEBRIS IN ATTIC

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1006\TC1006.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1006

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT MATERIAL, TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT MATERIAL, APPROX. 40LF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN TRANSITE PANEL DEBRIS IN ATTIC, APPROX. 5SF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text ASBESTOS WAS IDENTIFIED IN 2014 CAMP LEJEUNE ASBESTOS SURVEY AT EXTERIOR CAULKING AT NORTHWEST ENTRY DOOR. APPROX. 16LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR CAULK FROM 2104 CAMP LEJEUNE SURVEY.

ASBESTOS IDENTIFIED IN MISCELLANEOUS TRANSITE PANEL ATTIC DEBRIS. APPROX. 5SF.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1019\TC1019.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1019

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

VCT PREVIOUSLY REMOVED IN THIS AREA

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXPANSION JOINT, APPROX. 40LF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR DOOR/WINDOW CAULK, APPROX. 350LF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN 12X12 CREAM VCT/MASTIC APPROX. 3,500SF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT MATERIAL, TYPICAL.

ASBESTOS IDENTIFIED IN EXTERIOR DOOR AND WINDOW CAULK, TYPICAL.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1026\TC1026.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1026

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT MATERIAL, TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXPANSION JOINT, APPROX. 40LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN 12X12 GRAY VCT/MASTIC, APPROX. 4,000SF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text ASBESTOS WAS IDENTIFIED IN 2014 CAMP LEJEUNE ASBESTOS SURVEY AT GRAY ROOFING SEALANT AT WESTSIDE VENTS. APPROX. 3SF.

ASBESTOS IDENTIFIED IN GRAY ROOFING SEALANT AT WESTSIDE VENTS FROM 2104 CAMP LEJEUNE SURVEY.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1027\TC1027.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1027

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR DOOR/WINDOW CAULK. TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF EXHAUST FAN MASTIC, APPROX. 2SF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXPANSION JOINT, APPROX. 40LF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR DOOR/WINDOW CAULK, APPROX. 80LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT MATERIAL, TYPICAL.

ASBESTOS IDENTIFIED IN ROOF EXHAUST FAN MASTIC. TYPICAL.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1060\TC1060.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1060

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF, TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHAUST FAN, APPROX. 2SF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF.

ASBESTOS IDENTIFIED IN ROOF EXHAUST MASTIC. APPROX. 2SF. TYPICAL AT ROOF EXHAUST VENTS.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1061\TC1061.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1061

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF, TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHAUST FAN, APPROX. 2SF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF.

ASBESTOS IDENTIFIED IN ROOF EXHAUST MASTIC. APPROX. 2SF. TYPICAL AT ROOF EXHAUST VENTS.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1062\TC1062.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1062

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINTS. APPROX. 40LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 40LF.

SCALE

PROJECT NO

ASBESTOS LOCATION PLAN

MCB CAMP LEJEUNE

1/16"=1'-0"

CBW

20-0001

G:\Projects\2020\2001.IR20\Drawings\100%\Package C\TC1063\TC1063.dwg

GROUP

ARCHITECTURE

WALKER

th e

BUILDING TC1063

3-24-18

AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP

AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.

AutoCAD SHX Text 252-636-8992(fax)

AutoCAD SHX Text

PO BOX 541, NEW BERN, NC 28563

AutoCAD SHX Text c

AutoCAD SHX Text 252-636-8778

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINTS, TYPICAL.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHAUST FAN, APPROX. 3LF.

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR DOOR/WINDOW CAULK, APPROX. 40LF.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN EXTERIOR EXPANSION JOINT, APPROX. 36LF.

AutoCAD SHX Text

ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHAUST FANS. TYPICAL.

ASBESTOS IDENTIFIED IN EXTERIOR DOOR/WINDOW CAULK, TYPICAL.

EMSL Analytical, Inc.

706 Gralin Street Kernersville, NC 27284

Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com

021902921EMSL Order:

Customer ID: WALK85

Customer PO:

Project ID:

Attention: Phone:Chris Walker (252) 636-8778

Fax:The Walker Group Architecture (252) 636-8992

Received Date:PO Box 541 04/29/2019 12:30 PM

Analysis Date:New Bern, NC 28563 05/02/2019 - 05/03/2019

Collected Date: 04/18/2019

Project: Bldg AS721

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

021902921-0001

None DetectedNon-fibrous (Other)92%Glass8%Black/Green

Fibrous

Heterogeneous

Asphalt Shingles/ Felt

021902921-0002

None DetectedNon-fibrous (Other)95%Cellulose

Glass

<1%

5%

Gray/Black/Green

Fibrous

Heterogeneous

Asphalt Shingles/ Felt

Analyst(s)

Nicole Shutts (1)

Scott Combs (1)

Stephen Bennett, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim

Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321

Initial report from: 05/03/2019 15:30:35

Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 5/3/2019 3:30 PM

Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com

022002693EMSL…