This is an Oil Analysis Report prepared by Amalina Technologies for a York chiller (Model CH-1, Comp, Sump) located at ACCO Granite Bay for the U.S. Coast Guard. The sample was drawn on June 3, 2026, at 6:51:29 PM from York K Oil (967511) and tested the same day. The report documents fluid condition monitoring results using TriVector analysis methodology.

The analysis identified abnormally high water content at 236 ppm, which exceeds the alarm range of 200-500 ppm, triggering a primary alert. The diagnosis suspects water infiltration from environmental exposure, condensation, process operations, or wash-down activities. Recommended actions include increased monitoring at half the normal sampling frequency and verification of seal integrity, breather function, and cooler system coupling condition. Additional test parameters show acceptable levels for most metallic wear indicators (Iron 0.1 ppm, Copper 1 ppm, Tin 1.2 ppm) and contamination metrics including ISO 4406 codes of 21/19/14 and particle counts. The Fe Wear Severity Index is rated at 3. Viscosity measurements at 40°C and 100°C (35.8 cSt and 6.4 cSt respectively) and Total Acid Number of 0 mg KOH/g indicate acceptable oil quality aside from the water contamination issue. Oil samples are retained for two months following analysis completion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asset Information

Site: Oil Analysis Lab Location: ACCO Granite Bay → USCG Asset: CH-1 → Comp → Sump Serial Number: SFJM-798100 Manufacturer: York Model:

Component Type: Chiller, CFC No ISO Asset Operating:

Sample Information

Oil: York K Oil(967511) Oil Operating:

Draw Date: Jun 3, 2026, 6:51:29 PM Top up:

Notes:

Diagnosis/Recommendation

Observations:

Water is abnormally high Diagnostics:

• Suspect water source to be environment, condensation, process, or wash down.

Actions:

• Monitor. Resample at half of normal sampling frequency. Check integrity of seals, breather, or cooler system coupling.

Additional Recommendations:

Test Performed by: Released by: Lab Supervisor:

Test Results

TriVector Parameter Current Sample Unit

Sample ID 5933895-107587

Draw Date Jun 3, 2026, 6:51:29 PM Test Date Jun 3, 2026, 6:57:31 PM

Released Date Jun 3, 2026, 6:59:08 PM Oil York K Oil(967511)

Asset Operating hours

Component Operating hours

Oil Operating hours

Oil Changed No Filter Changed Unknown

Top up litres

Alarm Code

Iron 0.1 ppm

Chrome 0 ppm

Nickel 0.1 ppm

Aluminium 0.5 ppm

Lead 0 ppm

Copper 1 ppm

Tin 1.2 ppm

Fatigue >20µm 61 part./ml

Non-Metallic >20µm 32 part./ml

Large Fe 0.07 ppm

Oil Analysis Report

Amalina Technologies Released Date: Jun 3, 2026, 6:59:08 PM

1 / 3

Oil samples are retained for a total of two (2) months after analysis has been completed.

TruVu 360 - All rights reservedPrinted On: Jun 3, 2026, 7:00:00 PM

TriVector Parameter Current Sample Unit

Fe Wear Severity Index 3

Total Fe < 100u 0 ppm

Silicon 0.7 ppm

Sodium 0 ppm

Potassium 0.1 ppm

ISO 4406 Code (>4µm) 21

ISO 4406 Code (>6µm) 19

ISO 4406 Code (>14µm) 14

Cnts >4 10347 part./ml

Cnts >6 2521 part./ml

Cnts >14 126 part./ml

Cutting >20µm 10 part./ml

Sliding >20µm 32 part./ml

Water 236 ppm

Large Fe % 0.2

Molybdenum 0 ppm

Calcium 0 ppm

Magnesium 0.1 ppm

Phosphorus 0 ppm

Zinc 0.6 ppm

Boron 0.2 ppm

TAN 0 mg KOH/g

Visc 40 35.8 cSt

Visc 100 6.4 cSt

Triggered Limits (Current Sample)

ID Parameter Limit Type Direction Alarm Range Reference Value Last Value Test Value

1 Water Absolute ↑ 200 → 500 0 236

Oil Analysis Report

Amalina Technologies Released Date: Jun 3, 2026, 6:59:08 PM

2 / 3

LNF Images

Cutting Sliding Non Metallic Fiber

Oil Analysis Report

Amalina Technologies Released Date: Jun 3, 2026, 6:59:08 PM

3 / 3

File details come from the government source that posted it. Updated .