2026.08.26_Strasburg PD_IFB - Drawings.pdf
PDF 20 MB Posted
- Attached to
- Strasburg Police Station Renovation
- Solicitation number
- IFB-127933
- Issued by
- Scott County, Virginia
About this file
This is an Issued for Bid (IFB) drawings package for the Strasburg Police Station renovation project involving the Town of Strasburg, Virginia, and prepared by Dewberry Architects Inc. The project encompasses the full interior renovation of an existing bank building located at 115 West King Street, Strasburg, VA 22657 (6,380 gross square feet) for conversion into a new police station. The scope of work includes interior demolition, architectural renovations, structural upgrades, mechanical, electrical, plumbing, and low-voltage technology improvements, parking lot reconfiguration with 34 total parking spaces (including 2 ADA van-accessible spaces), security fencing, and related site work. A mandatory pre-bid meeting is scheduled for Thursday, September 17, 2026, at 10:00 AM at Strasburg Town Hall Council Chambers, with attendance required for bid eligibility. Sealed bids are due through the eVA website by 2:00 PM on Monday, October 19, 2026, with public opening and reading thereafter. Construction is anticipated to commence following issuance of the Notice to Proceed on or around November 10, 2026. The complete bidding documents include architectural, civil, structural, mechanical, electrical, plumbing, technology, and security drawings. Written questions must be submitted by Friday, September 25, 2026, directed to Roderick Williams, AIA, Dewberry Architects Inc., at 703-698-9076 or rwilliams@dewberry.com.
The project site comprises 0.549 acres (Tax Map/Parcel No. 025A3A168) in the Strasburg Historic District zoned for Community Commercial use, with a disturbed area of 0.10 acres (4,115 square feet). The property does not fall within any FEMA floodplain zone. The building is classified as Type IIB construction with Business Group B occupancy as primary use and Storage Group S-1 as secondary use, with a total building occupant load of 44 persons across first and second floors. The design incorporates compliance with the 2021 Virginia Uniform Statewide Building Code, Virginia Existing Building Code, Virginia Plumbing Code, International Building Code, NFPA-101 Life Safety Code, ADA accessibility standards, and Town of Strasburg Historic District Design Guidelines. The project is non-sprinklered, with provisions for fire extinguishers and fire alarm systems as required. Building envelope thermal performance targets include roof insulation (U-0.032), above-grade walls (U-0.104), and fenestration components meeting 2021 International Energy Conservation Code requirements for Climate Zone 4A. Plumbing fixtures include 2 water closets, 2 lavatories, 1 drinking fountain, and 1 service sink.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2026.08.26_Strasburg PD_IFB - Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL INTERIOR DESIGN CIVIL STRUCTURAL TECHNOLOGY MEP
8401 Arlington Blvd Fairfax, VA 22031
703.849.0100
DEWBERRY
13575 Heathcote Blvd Gainesville, VA 20155
703.468.2211
DEWBERRY
2610 Wycliff Road Raleigh, NC 27607
919.881.9939
DEWBERRY
401 Southwest Water St Peoria, IL 61602
309.282.8000
DEWBERRY
8401 Arlington Blvd Fairfax, VA 22031
703.849.0100
DEWBERRY
STRASBURG POLICE STATION
115 W King Street, Strasburg, VA 22657
ISSUED FOR BID
08.26.2026
8401 Arlington Blvd Fairfax, VA 22031
703.849.0100
DEWBERRY
In accordance with the Code of Virginia Section 2.2-3705.2 the documents herein contain critical security information that is exempt from disclosure because the disclosure of which may jeopardize the safety or security of its occupants.
APPROVALS
RECOMMENDATIONS FOR APPROVAL OF CONSTRUCTION
DIRECTOR - BUILDING DESIGN AND CONSTRUCTION DIVISION, DPWES DATE
CHIEF OF POLICE DATE
DEPUTY DIRECTOR DATE
DEPARTMENT OF PUBLIC WORKS AND ENVIRONMENTAL SERVICES
A101
SIM
APC-X
8' - 0"
A
X#XX 1HR
SF01
Area Name
150 SF
FIRST FLOOR
100' - 0"
PT-X
RB-X
CPT-X
NOTES: 22
ROOM NAME
ROOM NAME
A101
SIM
GB-01
Scale:
View Name 1/8" = 1'-0" 1/A101
A101
SIM
CALLOUT
BUILDING/WALL
SECTION
DETAIL SECTION
ROOM TAG
ROOM FINISH
TAG
CEILING TAG
DOOR / BORROWED
LITE TAG
WINDOW TAG
WALL TAG
FURNITURE,
CASEWORK, &
EQUIPMENT TAG
REVISION TAG
KEYNOTE TAG00 00 00.A1
AREA TO BE
ENLARGED SHEET REF.
PLAN / DETAIL
REF.
SECTION REF.
SHEET REF.
DETAIL REF.
SHEET REF.
LEVEL LINE
AREA SQUARE
FOOTAGE
ROOM NUMBER
EXTERIOR
ELEVATION
INTERIOR
ELEVATION
ELEVATION REF.
SHEET REF. A101
A101
1ELEVATION REF.
SHEET REF.
VIEW NAME
VIEW SCALE
VIEW DESIGNATION
VIEW REF/SHEET REF WHERE
VIEW IS REFERENCED
VIEW TITLE
WALL FINISH
BASE FINISH
FLOOR FINISH
AREA TAG
CEILING TYPE
CEILING HEIGHT
(ABOVE FINISH FLOOR)
LEVEL NAME
LEVEL ELEVATION
GRID LINE
NORTH INDICATOR
GRID NUMBER OR
LETTER
INDICATES PLAN NORTH
INDICATES TRUE NORTH
A101
SPOT ELEVATION
SYMBOL
NOTES
(AS NEEDED)
ROOM NUMBER
NEW DOOR EXISTING DOOR EXISTING DOOR
TO BE DEMOLISHED
WALL MOUNTED
LAVATORY
FLOOR MOUNTED
WATER CLOSET
WALL MOUNTED
TANKLESS WATER
CLOSET
COUNTER MOUNTED
LAVATORY
FLOOR MOUNTED
TANKLESS WATER
CLOSET
ELECTRIC WATER
COOLER
TOILET PARTITIONS
LOCKERS
SINGLE
DOUBLE
TRIPLE
QUAD
GRAB BARWALL MOUNTED
URINAL
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
/2
/2
:4
:0
A M
INDEX
TF
Checker
RW
08.26.2026
50165756
S T
R A
S B
U R
G P
O L
IC
E
S T
A T
IO
N
T O
W N
O F
S T
R A
S B
U R
G
IS
S
U E
D F
O R
B
ID
W
K in g S tr e e t, S tr a s b u rg
V
A
DEWBERRY
8401 Arlington Blvd Fairfax, VA 22031 703.849.0100
G-001
AB ANCHOR BOLT
ACST ACOUSTIC(AL)
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING,
ADJUSTABLE
AED AUTOMATED EXTERNAL
DEFIBRILLATOR
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANCH ANCHOR
ANOD ANODIZE(D)
AP ACCESS PANEL
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ASPH ASPHALT
AUTO AUTOMATIC
AVE AVERAGE
AWT ACOUSTICAL WALL TREATMENT
BAL SHT BALANCE SHEET
BC BRICK COLOR
BCS BABY CHANGING STATION
BD BOARD
BG BUMPER GUARD
BITUM BITUMINOUS
BLDG BUILDING
BLKG BLOCKING (WOOD)
BOT BOTTOM
BRDG BRIDGING
BRG BEARING
BRK PV BRICK PAVERS
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
CAB CABINET
CB CHALKBOARD
CC CUBICLE CURTAIN
CCT CUBICLE CURTAIN TRACK
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CH COAT HOOK
CIP CONC CAST-IN-PLACE CONCRETE
CJ CONTROL JOING, CONSTRUCTION
JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT, CASED OPENING
COL COLUMN
COMB COMBINATION, COMBINED
COMP COMPRESSIBLE
COMPT COMPARTMENT
CONC CONCRETE
CONC CTG CONCRETE COATING
COND CONDITION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPRS COMPRESSIBLE
CPT CARPET
CR CLOSET ROD
CRL CRASH RAIL
CRS COLD-ROLLED STEEL
CTR CENTER(S)
CUH CABINET UNIT HEATER
CUV CABINET UNIT VENTILATOR
CW CURTAINWALL
D DEEP, DEPTH, PENNY NAIL
DC DISPLAY CASE
DET DETAIL
DETN DETENTION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DECORATIVE PANEL
DR DOOR
DS DOWNSPOUT
DWG DRAWING(S)
EHD ELECTRIC HAND DRYER
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EMER EMERGENCY
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FLASH FLASHING
FLP FLOOR PATTERN
FLR FLOOR
FRP FIBER REINFORCED PLASTIC
FTG FOOTING
FURG C FURRING CHANNEL
FURN FURNACE
FWC FABRIC WALLCOVERING
GA GAGE, GAUGE
GALV GALVANIZED
GB GRAB BAR
GFRC GLASS-FIBER REINFORCED
CONCRETE
GL GLASS
GL BLK GLASS BLOCK
GLZ CMU GLAZED CONCRETE MASONRY UNIT
GRFG GLASS-FIBER REINFORCED GYPSUM
GT GROUT
GWH GAS FIRED WATER HEATER
GYP BD GYPSUM WALL BOARD
H HIGH, HATCH (ROOF)
HB HOSE BIB
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
ID INSIDE DIAMETER, INSIDE
DIMENSION
IF INSIDE FACE
INCL INCLUDED
INSUL INSULATION
INT INTERIOR
INV INVERT
JT JOINT
KD KNOCKED DOWN
KOP KNOCK OUT PANEL
L LONG, ANGLE
LAM LAMINATE(D)
LAV LAVATORY
LH LEFT HAND
LINO LINOLEUM
LKR LOCKER
LL LIVE LOAD, LOW LEVEL
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LVL LEVEL
LVR LOUVER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKERBOARD
MBH MOB/BROOM HOLDER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MI MIRROR
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODEL, MODULE, MODULAR
MSB MOP SERVICE BASIN
MT MOUNT
MTL METAL
NDU NEEDLE DISPOSAL UNIT
NIC NOT IN CONTRACT, NOISE ISOLATION
CLASS
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER, OUTSIDE
DIMENSION
OF OUTSIDE FACE
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFD OVERFLOW DRAIN
OFOI OWNER FURNISHED OWNER
INSTALLED
OH OVERHEAD
OH DR OVERHEAD DOOR
OP OPERABLE PARTITION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OS OVERFLOW SCUPPER
PC PORTLAND CEMENT, POINT
OF CURVE, POLYCARBONATE
PCC PRECAST CONCRETE
PERIM PERIMETER
PJ PROJECTOR
PL PLATE, PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PT PAINT
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER &
RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVG PAVING
R RISER, RADIUS, THERMAL
RESISTANCE (R-VALUE)
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN, ROAD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RF RESILIENT FLOORING
RFG ROOFING
RFM REMOVABLE FLOOR MAT
RH RIGHT HAND
RO ROUGH OPENING
RSF RESINOUS FLOORING
RST REINFORCING STEEL
RTF RESILIENT TILE FLOORING
RV ROOF VENT, ROOF VENTILATOR
SC SEALED CONCRETE
SCHED SCHEDULE
SCR SHOWER CURTAIN ROD
SCWD SOLID CORE WOOD DOOR
SD SOAD DISPENSER
SECT SECTION
SF STOREFRONT
SH SHINGLES, SINGLE HUNG (WINDOW)
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SOG SLAB ON GRADE
SPCG SPACING
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS SERVICE SINK , SOLID SURFACING
SST STAINLESS STEEL, SHOWER SEAT
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PL STEEL PLATE
STL RF DK STEEL ROOF DECK
STL TR STEEL TRUSS
STN STAIN
STRUCT STRUCTURAL
SUSP SUSPEND
SV SHEET VINYL
SWP SHEET WALL PROTECTION
SYMM SYMMETRICAL
SYNTH SYNTHETIC
T TILE, TREAD
T&G TONGUE AND GROOVE
T/S TUB/SHOWER
TB TOWEL BAR, TACKBOARD
TC TOILET COMPARTMENT
TD TRENCH DRAIN
TER TERRAZZO
THK THICK
TOB TOP OF BEAM
TOC TOP OF CONCRETE, TOP OF CURB
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF SLAB, TOP OF STEEL
TOW TOP OF WALL
TPH TOILET PAPER HOLDER
TR TOWEL RACK
TS TUBE STEEL, TRANSITION STRIP
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDE, WEST
WC WALL COVERING
WD WOOD, WOOD DOOR
WDW WINDOW
WP WALL PATTERN, WATERPROOFING
WT WEIGHT, WINDOW TREATMENT
WWF WELDED WIRE FABRIC
STANDARD ABBREVIATIONS
STANDARD DETAILING SYMBOLS
STANDARD DRAFTING SYMBOLS
SHEET INDEX
SHEET NO. SHEET NAME
GENERAL
G-000 COVER
G-001 INDEX
G-002 CODE ANALYSIS
G-003 CODE & LIFE SAFETY PLAN
G-004 ADA STANDARDS
CIVIL
C-001 COVER SHEET
C-002 EXISTING CONDITIONS & DEMOLITION PLAN
C-003 SITE PLAN
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES
S-100 STRUCTURAL FOUNDATION PLAN AND DETAILS
S-110 SECOND FLOOR PLAN
S-120 ROOF FRAMING PLAN
S-200 STRUCTURAL BRACE FRAME ELEVATIONS AND DETAILS
S-201 STRUCTURAL BRACE FRAME STANDARD DETAILS
S-700 STRUCTURAL STANDARD DETAILS
S-701 STRUCTURAL STANDARD DETAILS
ARCHITECTURAL
ASD-101 ARCHITECTURAL DEMOLITION SITE PLAN
AS-101 ARCHITECTURAL SITE PLAN
AD-101 FIRST FLOOR DEMOLITION PLAN
AD-102 FIRST FLOOR DEMOLITION RCP
AD-111 SECOND FLOOR DEMOLITION PLAN
AD-112 SECOND FLOOR DEMOLITION RCP
AD-121 ROOF DEMOLITION PLAN
AD-201 DEMOLITION EXTERIOR ELEVATIONS
AD-202 DEMOLITION EXTERIOR ELEVATIONS
A-101 FIRST FLOOR ANNOTATION PLAN
A-102 FIRST FLOOR DIMENSION PLAN
A-103 FIRST FLOOR REFLECTED CEILING PLAN
A-104 FIRST FLOOR FINISH PLAN AND SCHEDULE
A-111 SECOND FLOOR ANNOTATION PLAN
A-112 SECOND FLOOR DIMENSION PLAN
A-113 SECOND FLOOR REFLECTED CELIING PLAN
A-114 SECOND FLOOR FINISH PLAN
A-121 ROOF PLAN
A-201 EXTERIOR ELEVATIONS
A-202 EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-311 WALL SECTIONS
A-321 ENLARGED PLAN AND SECTION DETAILS
A-410 ENLARGED PLANS & INTERIOR ELEVATIONS
A-411 ENLARGED PLANS & INTERIOR ELEVATIONS
A-412 ENLARGED PLANS & INTERIOR ELEVATIONS
A-413 ENLARGED PLANS & INTERIOR ELEVATIONS
A-431 MILLWORK DETAILS
A-432 MILLWORK DETAILS
A-450 ENLARGED STAIR AND RAMP DETAILS
A-501 ROOF DETAILS
A-601 DOOR SCHEDULES, ELEVATIONS, AND DETAILS
A-602 DOOR HEAD, JAMB, AND SILL DETAILS
A-603 DOOR HARDWARE SCHEDULE
A-604 DOOR HARDWARE SCHEDULE
A-611 GLAZING SCHEDULES, ELEVATIONS, AND DETAILS
A-631 WALL PARTITIONS, ASSEMBLIES, AND DETAILS
INTERIORS
I-101 FIRST FLOOR FURNITURE & EQUIPMENT
I-102 FIRST FLOOR SIGNAGE PLAN
I-111 SECOND FLOOR FURNITURE & EQUIPMENT
I-112 SECOND FLOOR SIGNAGE PLAN
I-301 SIGNAGE SCHEDULE
PLUMBING
P-001 PLUMBING SYMBOLS, ABBREVIATIONS & NOTES
P-101 FIRST FLOOR PLUMBING PLAN
P-102 SECOND FLOOR PLUMBING PLAN
P-501 PLUMBING DETAILS
MECHANICAL
M-001 MECHANICAL SYMBOLS, ABBREVIATIONS & NOTES
M-002 MECHANICAL CALCULATIONS
M-101 FIRST FLOOR MECHANICAL PLAN
M-102 SECOND FLOOR MECHANICAL PLAN
M-103 ROOF MECHANICAL PLAN
M-401 MECHANICAL ENLARGED PLANS AND SECTIONS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
ELECTRICAL
E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS & NOTES
ES-101 ELECTRICAL EXTERIOR PLANS
ED-101 ELECTRICAL DEMOLITION PLANS
EL-101 ELECTRICAL LIGHTING PLANS
EP-101 ELECTRICAL POWER PLANS
ES-102 ELECTRICAL EXTERIOR PHOTOMETRICS PLAN
EF-101 ELECTRICAL FIRE ALARM PLANS
E-501 ELECTRICAL DETAILS
E-701 ELECTRICAL RISER & SCHEDULES
TECHNOLOGY
TT-001 LEGEND SHEET - TELECOM
TD-111 FIRST FLOOR PLAN DEMOLITION - TECHNOLOGY
TD-121 SECOND FLOOR PLAN DEMOLITION - TECHNOLOGY
TT-111 FIRST FLOOR PLAN - TELECOM
TT-112 FIRST FLOOR RCP - TELECOM
TT-121 SECOND FLOOR PLAN - TELECOM
TT-122 SECOND FLOOR RCP - TELECOM
TT-401 LARGE SCALE PLANS - TELECOM
TT-501 DETAILS - TELECOM
TT-502 DETAILS - TELECOM
TT-503 DETAILS - TELECOM
TT-601 BLOCK DIAGRAMS - TELECOM
TT-602 BLOCK DIAGRAMS - AV
TT-603 BLOCK DIAGRAMS - AV
SECURITY
TY-001 LEGEND SHEET - SECURITY
TY-101 SITE PLAN - SECURITY
TY-111 FIRST FLOOR PLAN - SECURITY
TY-112 FIRST FLOOR RCP - SECURITY
TY-121 SECOND FLOOR PLAN - SECURITY
TY-122 SECOND FLOOR RCP - SECURITY
TY-401 LARGE SCALE PLANS - SECURITY
TY-501 DETAILS - SECURITY
TY-502 DETAILS - SECURITY
TY-503 DETAILS & SCHEDULES - SECURITY
TY-601 BLOCK DIAGRAMS - SECURITY
PROJECT LOCATION
VICINITY MAP
LOCATION MAP
PROJECT LOCATION
NO. DESCRIPTION DATE
08/27/26
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
/2
/2
:5
:4
A
M
CODE ANALYSIS
EA
Checker
RW
08.26.2026
50165756
S T
R A
S B
U R
G P
O L
IC
E
S T
A T
IO
N
T O
W N
O F
S T
R A
S B
U R
G
IS
S
U E
D F
O R
B
ID
W
K in g S tr e e t, S tr a s b u rg
V
A
DEWBERRY
8401 Arlington Blvd Fairfax, VA 22031 703.849.0100
G-002
GENERAL INFORMATION
PROJECT NAME:
STRASBURG POLICE STATION
BUILDING LOCATION:
115 W KING STREET,
STRASBURG, VA 22657
CONSTRUCTION:
EST. YEAR OF COMPLETION 2026
OCCUPANCY:
PRIMARY - BUSINESS
OTHERS - ASSEMBLY, STORAGE, UTILITY & MISCELLANEOUS
BUILDING GROSS SQUARE FOOTAGE:
TOTAL: 6,380 GSF
BUILDING DESCRIPTION:
THIS PROJECT INCLUDES THE FULL INTERIOR RENOVATION OF AN EXISTING BANK BUILDING FOR USE AS A NEW POLICE STATION FOR THE TOWN OF STRASBURG POLICE DEPARTMENT. THE SCOPE OF WORK INCLUDES ARCHITECTURAL, INTERIOR, MECHANICAL, ELECTRICAL, PLUMBING, TELECOM, AND SECURITY
UPGRADES TO THE EXISTING BUILDING.
APPLICABLE CODE AND CRITERIA
• 2021 (VUSBC) VIRGINIA UNIFORM STATEWIDE BUILDING CODE
• 2021 (VEBC) VIRGINIA EXISTING BUILDING CODE
• 2021 (VPC) VIRGINIA PLUMBING CODE
• 2021 (IBC) INTERNATIONAL BUILDING CODE
• 2021 (IEBC) INTERNATIONAL EXISTING BUILDING CODE
• 2021 (NFPA-101) LIFE SAFETY CODE
• 2021 (IMC) INTERNATIONAL MECHANICAL CODE
• 2021 (IPC) INTERNATIONAL PLUMBING CODE
• 2020 (NEC) NATIONAL ELECTRICAL CODE
• 2021 (IECC) INTERNATIONAL ENERGY CONSERVATION CODE
• 2021 (IFC) INTERNATIONAL FIRE CODE
• 2010 (ADA) ICC/ANSI A117.1 ACCESSIBILITY CODE
• TOWN OF STRASBURG HISTORIC DISTRICT DESIGN GUIDELINES
REVIEWED PER 2021 VIRGINIA EXISTING BUILDING CODE
CHAPTER 4 – ACCESSIBILITY
404.2 ALTERATIONS
SHALL COMPLY WITH CHAPTER 11 OF THE VCC.
EXCEPTION 2. - ACCESSIBLE MEANS OF EGRESS REQUIRED BY CHAPTER 10 OF VCC ARE NOT REQUIRED
TO BE PROVIDED IN EXISTING FACILITIES.
404.3 ALTERATIONS AFFECTING AN AREA CONTAINING A PRIMARY FUNCTION
WHERE AN ALTERATION AFFECTS THE ACCESSIBILITY TO, OR CONTAINS AN AREA OF PRIMARY FUNCTION, THE ROUTE TO THE PRIMARY FUNCTION SHALL BE ACCESSIBLE.
404.10 TOILET ROOMS
ALTER EXISTING TOILET TO BE ACCESSIBLE OR PROVIDE AN ACCESSIBLE FAMILY OR ASSISTED-USE
TOILET IN ACCORDANCE WITH SECTION 1109.2.1 OF THE VCC.
CHAPTER 4 – ACCESSIBILITY
CHAPTER 6 – ALTERATIONS
601.1 GENERAL
EXCEPT AS MODIFIED IN CHAPTER 9 OR THIS CHAPTER, ALTERATIONS TO ANY BUILDING OR STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS OF THE VCC FOR NEW CONSTRUCTION. ALTERATIONS SHALL BE SUCH THAT THE EXISTING BUILDINGS OR STRUCTURES IS NO LESS CONFORMING TO THE PROVISIONS OF THE VCC THAN THE EXISTING BUILDING OR STRUCTURE WAS PRIOR TO THE ALTERATION. PORTIONS OF THE BUILDING OR STRUCTURE NOT BEING ALTERED SHALL NOT BE REQUIRED TO COMPLY WITH THE
REQUIREMENTS OF THE VCC.
EXCEPTION 1 - ANY STAIRWAY REPLACING AN EXISTING STAIRWAY SHALL NOT BE REQUIRED TO COMPLY WITH THE REQUIREMENTS OF SECTION 1011 OF THE VCC WHERE THE EXISTING SPACE AND
CONSTRUCTION DOES NOT ALLOW A REDUCTION IN PITCH OR SLOPE.
EXCEPTION 2 - HANDRAILS OTHERWISE REQUIRED TO COMPLY WITH SECTION 1011.11 OF THE VCC SHALL NOT BE REQUIRED TO COMPLY WITH THE REQUIREMENTS OF SECTION 1014.6 OF THE VCC GRADING FULL EXTENSION OF THE HANDRAILS WHERE SUCH EXTENSIONS WOULD BE HAZARDOUS DUE
TO PLAN CONFIGURATION.
601.2.2 LEVEL 2 ALTERATION
COMPLY WITH SECTIONS 602 AND 603.
603 ALTERATION - LEVEL 2
LEVEL 2 ALTERATIONS AS DESCRIBED IN SECTION 601.2.2 SHALL COMPLY WITH THE REQUIREMENTS OF
THIS SECTION.
603.3 COMPLIANCE
ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
REQUIREMENTS OF THE VCC.
EXCEPTION 4 - THE MINIMUM CEILING HEIGHT OF THE NEWLY CREATED HABITABLE AND OCCUPIABLE
SPACES AND CORRIDORS SHALL BE 7 FEET.
603.7 STRUCTURAL
STRUCTURAL ELEMENTS AND SYSTEMS WITHIN BUILDINGS UNDERGOING LEVEL 2 ALTERATIONS SHALL
COMPLY WITH SECTIONS 603.7 THROUGH 603.7.6.
REVIEWED PER 2018 VIRGINIA INTERNATIONAL BUILDING CODE
302.1 OCCUPANCY CLASSIFICATION
PRIMARY USE AND OCCUPANCY GROUP:
BUSINESS GROUP B
OTHER USES AND OCCUPANCY GROUPS:
STORAGE GROUP S-1
303.1.2 SMALL ASSEMBLY SPACES
THE FOLLOWING ROOMS AND SPACES SHALL NOT BE CLASSIFIED AS ASSEMBLY OCCUPANCIES:
1. A ROOM OR SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50
PEOPLE AND ACCESSORY TO ANOTHER OCCUPANCY SHALL BE CLASSIFIED AS A GROUP B
OCCUPANCY OR AS PART OF THAT OCCUPANCY.
2. A ROOM OR SPACE USED FOR ASSEMBLY PURPOSES THAT IS LESS THAN 750 SQUARE FEET IN AREA
AND ACCESSORY TO ANOTHER OCCUPANCY SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY OR
AS PART OF THAT OCCUPANCY.
311.1.1 ACCESSORY STORAGE SPACES
A ROOM OR SPACE USED FOR STORAGE PURPOSES THAT IS ACCESSORY TO ANOTHER OCCUPANCY
SHALL BE CLASSIFIED AS PART OF THAT OCCUPANCY.
312.2 PRIVATE GARAGES AND CARPORTS
PRIVATE GARAGES AND CARPORTS SHALL COMPLY WITH SECTION 406.3.
CHAPTER 3 - USE AND OCCUPANCY CLASSIFICATION
CHAPTER 4 - CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS
BASED ON USE AND OCCUPANCY
406.3 PRIVATE GARAGE AND CARPORTS
PRIVATE GARAGES AND CARPORTS SHALL COMPLY WITH SECTIONS 406.2 AND 406.3.
406.3.1 CLASSIFICATION
PRIVATE GARAGES AND CARPORTS SHALL BE CLASSIFIED AS GROUP U OCCUPANCIES. EACH PRIVATE
GARAGE SHALL BE NOT GREATER THAN 1,000 SQUARE FEET.
406.3.2 SEPARATION
FOR OTHER THAN PRIVATE GARAGES ADJACENT TO DWELLING UNITS, THE SEPARATION OF PRIVATE
GARAGES FROM OTHER OCCUPANCIES SHALL COMPLY WITH SECTION 508.
502.1 ADDRESS IDENTIFICATION
NEW BUILDINGS SHALL BE PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. THE ADDRESS IDENTIFICATION SHALL BE LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY. ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRACT WITH THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC NUMBERS OR ALPHABETICAL LETTERS.
NUMBERS SHALL NOT BE SPELLED OUT. EACH CHARACTER SHALL BE A MINIMUM OF 4 INCHES HIGH WITH A MINIMUM STROKE WIDTH OF ½ INCH. WHERE REQUIRED BY THE FIRE CODE OFFICIAL, ADDRESS IDENTIFICATION SHALL BE PROVIDED IN ADDITIONAL APPROVED LOCATIONS TO FACILITATE EMERGENCY RESPONSE. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC WAY, A MONUMENT, POLE OR OTHER APPROVED SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE.
PROVIDED: BUILDING IDENTIFICATION PROVIDED ON ENTRANCE CANOPY ALONG W. KING STREET
503.1.2 BUILDINGS ON SAME LOT.
TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING WHERE THE BUILDING HEIGHT, NUMBER OF STORIES OF EACH BUILDING AND THE AGGREGATE BUILDING AREA OF THE BUILDINGS ARE WITHIN THE LIMITATIONS SPECIFIED IN SECTIONS 504 AND 506. THE PROVISIONS OF THIS CODE APPLICABLE TO THE AGGREGATE
BUILDING SHALL BE APPLICABLE TO EACH BUILDING.
504.2 MIXED OCCUPANCY
IN A BUILDING CONTAINING MIXED OCCUPANCIES IN ACCORDANCE WITH SECTION 508, NO INDIVIDUAL OCCUPANCY SHALL EXCEED THE HEIGHT AND NUMBER OF STORY LIMITS SPECIFIED IN THIS SECTION FOR
THE APPLICABLE OCCUPANCIES.
504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE
OCCUPANCY ALLOWABLE HEIGHT (TYPE IIB CONSTRUCTION, NON-SPRINKLERED)
BUSINESS 55 FEET
STORAGE 55 FEET
PROPOSED: XX FEET (EXISTING)
504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
OCCUPANCY ALLOWABLE HEIGHT (TYPE IIB CONSTRUCTION, NON-SPRINKLERED)
BUSINESS 3 STORIES
STORAGE 2 STORIES
PROPOSED: 2 STORIES (EXISTING)
506.2 ALLOWABLE AREA FACTOR
OCCUPANCY ALLOWABLE HEIGHT (TYPE IIB CONSTRUCTION, NON-SPRINKLERED)
BUSINESS 23,000 SQUARE FEET
STORAGE 17,500 SQUARE FEET
PROPOSED: 6,900 SQUARE FEET
506.2.2 MIXED-OCCUPANCY BUILDINGS
THE ALLOWABLE AREA OF EACH STORY OF A MIXED-OCCUPANCY BUILDING SHALL BE DETERMINED IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF SECTION 508.4.2 FOR SEPARATED OCCUPANCIES.
508.2 ACCESSORY OCCUPANCIES
ACCESSORY OCCUPANCIES ARE THOSE OCCUPANCIES THAT ARE ANCILLARY TO THE MAIN OCCUPANCY OF THE BUILDING OR PORTION THEREOF. ACCESSORY OCCUPANCIES SHALL COMPLY WITH THE PROVISIONS
OF SECTIONS 508.2.1 THROUGH 508.2.4.
508.4 SEPARATED OCCUPANCIES
BUILDING OR PORTIONS OF BUILDING THAT COMPLY WITH THE PROVISION OF THIS SECTION SHALL BE
CONSIDERED AS SEPARATED OCCUPANCIES.
OCCUPANCY ADJACENCY REQUIRED SEPARATION (NON-SPRINKLERED)
BUSINESS (B) & STORAGE (S-1) NO SEPARATION REQUIRED
508.4.4.1 CONSTRUCTION
REQUIRED SEPARATIONS SHALL BE FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707.
509.1 INCIDENTAL USES
CONFIRM WITH MEP
CHAPTER 5 - GENERAL BUILDING HEIGHTS AND AREAS
601 - FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
BUILDING ELEMENTS TYPE IIB CONSTRUCTION
PRIMARY STRUCTURAL FRAME 0 HOURS
EXTERIOR BEARING WALLS: 0 HOURS
INTERIOR BEARING WALLS: 0 HOURS
FLOOR CONSTRUCTION 0 HOURS
ROOF CONSTRUCTION 0 HOURS
602 CONSTRUCTION CLASSIFICATION
BUILDING CONSTRUCTION MATERIAL: TYPE IIB (EXISTING)
603.1 ALLOWABLE MATERIALS
COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS TYPE I OR II CONSTRUCTION IN THE
FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3.
CHAPTER 6 - TYPES OF CONSTRUCTION
705.2 PROJECTIONS
CORNICES, EAVE OVERHANGS, EXTERIOR BALCONIES AND SIMILAR PROJECTIONS EXTENDING BEYOND THE EXTERIOR WALL SHALL CONFORM TO THE REQUIREMENTS OF THIS SECTION AND SECTION 1405.
EXCEPTION 1 - BUILDINGS ON THE SAME LOT AND CONSIDERED AS PORTIONS OF ONE BUILDING IN
ACCORDANCE WITH SECTION 705.3 ARE NOT REQUIRED TO COMPLY WITH THIS SECTION FOR
PROJECTIONS BETWEEN THE BUILDINGS.
PROVIDED: EXISTING BUILDING AND CARPORT CONNECTED BY EXISTING COVERED WALKWAY.
705.3 BUILDINGS ON THE SAME LOT
FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND OPENING PROTECTION, PROJECTIONS AND ROOF-COVERING REQUIREMENTS, BUILDINGS ON THE SAME LOT SHALL BE ASSUMED TO HAVE AN IMAGINARY LINE BETWEEN THEM. WHERE ARE NEW BUILDING IS TO BE ERECTED ON THE SAME LOT AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING PROTECTION OF THE EXISTING
BUILDING MEET THE CRITERIA AS SET FORTH IN SECTIONS 705.5 AND 705.8.
EXCEPTION 1 - TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE EITHER REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING IF THE AGGREGATE AREA OF SUCH BUILDINGS IS WITHIN THE LIMITS SPECIFIED IN CHAPTER 5 FOR A SINGLE BUILDING. WHERE THE
BUILDINGS CONTAIN DIFFERENT OCCUPANCY GROUPS OR ARE OF DIFFERENT TYPES OF
CONSTRUCTION, THE AREA SHALL BE THAT ALLOWED FOR THE MOST RESTRICTIVE OCCUPANCY OR
CONSTRUCTION.
705.5 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION
DISTANCE
FSD TYPE OF CONSTRUCTION REQUIRED SEPARATION
X ≥ 30 ALL 0
SECTION 707 FIRE BARRIERS
CHAPTER 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
802.1 INTERIOR WALL AND CEILING FINISH
THE PROVISIONS OF SECTION 803 SHALL LIMIT THE ALLOWABLE FIRE PERFORMANCE AND SMOKE
DEVELOPMENT OF INTERIOR WALL AND CEILING FINISH MATERIALS BASED ON OCCUPANCY
CLASSIFICATION.
802.2 INTERIOR FLOOR FINISH
THE PROVISION OF SECTION 804 SHALL LIMIT THE ALLOWABLE FIRE PERFORMANCE OF INTERIOR FLOOR
FINISH MATERIALS BASED ON OCCUPANCY CLASSIFICATION.
802.3 DECORATIVE MATERIALS AND TRIM
DECORATIVE MATERIALS AND TRIM SHALL BE RESTRICTED BY COMBUSTIBILITY, FIRE PERFORMANCE OR
FLAME PROPAGATION PERFORMANCE CRITERIA IN ACCORDANCE WITH SECTION 806.
TABLE 803.13 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY - FOR NON-SPRINKLERED
OCCUPANCY INTERIOR EXIT PASSAGEWAYS CORRIDOR ROOMS
GROUP B CLASS A CLASS B CLASS C
GROUP S CLASS B CLASS B CLASS C
CHAPTER 8 - INTERIOR FINISHES
903.2 WHERE REQUIRED
APPROVED AUTOMATIC SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL BE PROVIDED IN
THE LOCATIONS DESCRIBED IN SECTIONS 903.2.1 THROUGH 903.2.12.
903.2.9 GROUP S-1
AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS CONTAINING A
GROUP S-1 OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET (1115 M2).
2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE STORIES ABOVE GRADE PLANE.
3. THE COMBINED AREA OF ALL GROUP S-1 FIRE AREAS ON ALL FLOORS, INCLUDING ANY
MEZZANINES, EXCEEDS 24,000 SQUARE FEET (2230 M2).
4. A GROUP S-1 FIRE AREA USED FOR THE STORAGE OF COMMERCIAL MOTOR VEHICLES WHERE THE
FIRE AREA EXCEEDS 5,000 SQUARE FEET (464 M2).
PROVIDED: EXISTING BUILDING IS NON-SPRINKLERED. NONE OF THE CONDITIONS LISTED IN SECTION
903.2.9 OR OTHERWISE IN SECTIONS 903.2.1 THROUGH 903.2.12 ARE APPLICABLE TO THIS PROJECT. THE
PROPOSED BUILDING WILL NOT INCLUDE THE INSTALLATION OF AN AUTOMATIC SPRINKLER SYSTEM.
SECTION 905 – STANDPIPE SYSTEMS IS NOT REQUIRED.
SECTION 906 – PORTABLE FIRE EXTINGUISHERS
1. PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED IN ALL OF THE FOLLOWING LOCATIONS: IN
GROUPS B AND S OCCUPANCIES.
2. WITHIN 30 FEET DISTANCE OF TRAVEL FROM COMMERCIAL COOKING EQUIPMENT IN AREAS WHERE
FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE STORE, USED OR DISPENSED.
3. ON EACH FLOOR OF THE STRUCTURE UNDER CONSTRUCTION
4. WHERE REQUIRED BY THE IBC SECTIONS INDICATED IN TABLE 906.1
906.3 906.3 FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS
LOW HAZARDMODERATE HAZARD HIGH HAZARD
MIN.-RATED EXTINGUISHER 2-A 2-A 4-A
MAX. FA PER UNIT OF A 3,000 SF 1,500 SF 1,000 SF
MAX. FA FOR EXTINGUISHER 11,250 SF 11,250 SF 11,250 SF
MAX. DISTANCE OF TRAVEL 75 FEET 75 FEET 75 FEET
906.9 EXTINGUISHER INSTALLATION
THE INSTALLATION OF PORTABLE FIRE EXTINGUISHERS SHALL BE IN ACCORDANCE WITH SECTIONS 906.9.1
THROUGH 906.9.3.
907.2 WHERE REQUIRED - NEW BUILDINGS AND STRUCTURES
AN APPROVED FIRE ALARM SYSTEM INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE AND NFPA 72 SHALL BE PROVIDED IN NEW BUILDINGS AND STRUCTURES IN ACCORDANCE WITH SECTIONS
907.2.1 THROUGH 907.2.23 AND PROVIDE OCCUPANT NOTIFICATION IN ACCORDANCE WITH SECTION 907.5, UNLESS OTHER REQUIREMENTS ARE PROVIDED BY ANOTHER SECTION OF THIS CODE.
CHAPTER 9 - FIRE PROTECTION & LIFE SAFETY SYSTEMS
1003.2 CEILING HEIGHT
THE MEANS OF EGRESS SHALL HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES ABOVE THE
FINISHED FLOOR.
EXCEPTION: ALLOWABLE CEILING HEIGHT OF 7 FEET PER SECTION 603.3 OF THE VECC.
1003.3 PROTRUDING OBJECTS
PROTRUDING OBJECTS ON CIRCULATION PATHS SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
1003.3.1 THROUGH 1003.4.
1004.2.1 INTERVENING SPACES OR ACCESSORY AREAS.
WHERE OCCUPANTS EGRESS FROM ONE OR MORE ROOMS, AREAS OR SPACES THROUGH OTHERS, THE DESIGN OCCUPANT LOAD SHALL BE THE COMBINED OCCUPANT LOAD OF INTERCONNECTED ACCESSORY OR INTERVENING SPACES. DESIGN OF EGRESS PATH CAPACITY SHALL BE BASED ON THE CUMULATIVE PORTION OF OCCUPANT LOADS OF ALL ROOMS, AREAS OR SPACES TO THAT POINT ALONG THE PATH OF
EGRESS TRAVEL.
1004.4 MULTIPLE OCCUPANCIES.
WHERE A BUILDING CONTAINS TWO OR MORE OCCUPANCIES, THE MEANS OF EGRESS REQUIREMENTS SHALL APPLY TO EACH PORTION OF THE BUILDING BASED ON THE OCCUPANCY OF THAT SPACE. WHERE TWO OR MORE OCCUPANCIES UTILIZE PORTIONS OF THE SAME MEANS OF EGRESS SYSTEM, THOSE EGRESS COMPONENTS SHALL MEET THE MORE STRINGENT REQUIREMENTS OF ALL OCCUPANCIES THAT
ARE SERVED.
1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
FUNCTION OF SPACE OCC. LOAD FACTOR NUMBER OF OCCUPANTS
BUSINESS AREAS 150 GROSS 35
ACCESSORY STORAGE AREAS & MECH 300 GROSS 7
PARKING GARAGE 200 GROSS 2
TOTAL BUILDING OCCUPANT LOAD = 44 OCCUPANTS
1005.3.1 STAIRWAYS
THE CAPACITY OF MEANS OF EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH STAIRWAYS BY A MEANS OF EGRESS CAPACITY FACTOR OF 0.3 INCH PER OCCUPANT. WHERE STAIRWAYS SERVE MORE THAN ONE STORY, ONLY THE OCCUPANT LOAD OF EACH STORY CONSIDERED INDIVIDUALLY SHALL BE USED IN CALCULATING THE REQUIRED CAPACITY OF THE
STAIRWAYS SERVING THAT STORY.
EXCEPTION - SECTION 601.1 EXCEPTION 1 OF THE 2021 VECC.
PROVIDED: EXISTING STAIR TO REMAIN WITH NO ALTERATIONS.
1005.3.2 OTHER EGRESS COMPONENTS
THE CAPACITY, IN INCHES, OF MEANS OF EGRESS COMPONENTS OTHER THAN STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF
EGRESS CAPACITY FACTOR OF 0.2 INCH (5.1 MM) PER OCCUPANT.
1005.7.1 DOORS.
DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE
TWO EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN TABLE 1006.2.1. THE CUMULATIVE OCCUPANT LOAD FROM ADJACENT ROOMS, AREAS OR SPACES SHALL BE
DETERMINED IN ACCORDANCE WITH SECTION 1004.2.
EXCEPTION 1 - THE NUMBER OF EXITS FROM FOYERS, LOBBIES, VESTIBULES OR SIMILAR SPACES NEED NOT BE BASED ON CUMULATIVE OCCUPANT LOADS FOR AREAS DISCHARGING THROUGH SUCH SPACES, BUT THE CAPACITY OF THE EXITS FROM SUCH SPACES SHALL BE BASED ON APPLICABLE CUMULATIVE
OCCUPANT LOADS.
EXCEPTION 3 - UNOCCUPIED MECHANICAL ROOMS AND PENTHOUSES ARE NOT REQUIRED TO COMPLY
WITH THE COMMON PATH OF EGRESS TRAVEL DISTANCE MEASUREMENT.
TABLE 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY (NON-SPRINKLERED)
OCCUPANCY MAX. OCC. LOAD OF SPACE MAX. COMMON PATH OF TRAVEL (FEET)
B 50 100 FEET (OL<30) 75 FEET (OL>30)
S 29 100 FEET (OL<30) 75 FEET (OL>30)
U 50 100 FEET (OL<30) 75 FEET (OL>30)
PROVIDED: 44 TOTAL BUILDING OCCUPANTS, MAX. COMMON PATH OF TRAVEL = 60'-0''
TABLE 1006.3.3 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY
REQUIRED: 2 EXITS
PROVIDED: 3 EXITS (FIRST FLOOR) & 1 EXIT (SECOND FLOOR)
1006.3.4 SINGLE EXITS
A SINGLE EXIT OR ACCESS TO A SINGLE EXIT SHALL BE PERMITTED FROM ANY STORY OR OCCUPIED ROOF
WHERE ONE OF THE FOLLOWING CONDITIONS EXIST:
1. THE OCCUPANT LOAD, NUMBER OF DWELLING UNITS AND EXIT ACCESS TRAVEL DISTANCE DO NOT
EXCEED THE VALUES IN TABLE 1006.3.4(1) OR 1006.3.4(2).
TABLE 1006.3.4 STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES
STORY OCCUPANCY MAX OCCUPANT LOAD PER STORY MAX. EXIT ACCESS TRAVEL DISTANCE
SECOND B, S 29 75 FEET
PROVIDED: SECOND STORY: OCCUPANT LOAD OF 12 OCCUPANTS AND A MAX TRAVEL DISTANCE OF 60'-0.''
1007.1.1 TWO EXITS OR EXIT ACCESS DOORWAYS
WHERE TWO EXITS, EXIT ACCESS DOORWAYS, EXIT ACCESS STAIRWAYS OR RAMPS, OR ANY COMBINATION THEREOF, ARE REQUIRED FROM ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN THEM.
INTERLOCKING OR SCISSOR STAIRWAYS SHALL BE COUNTED AS ONE EXIT STAIRWAY.
REQUIRED: AREA DIAGONAL = 93'-4'' / 2 = 46'-8''
PROVIDED: DISTANCE BETWEEN EXIT 1 AND EXIT 2 = 48'-0'' (EXISTING)
1010.1 GENERAL
DOORS IN THE MEANS OF EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS 1010.1.1 THROUGH 1010.3.4. EXTERIOR EXIT DOORS SHALL ALSO COMPLY WITH THE REQUIREMENTS OF SECTION 1022.2.
DOORS, GATES AND TURNSTILES PROVIDED FOR EGRESS PURPOSES IN NUMBERS GREATER THAN
REQUIRED BY THIS CODE SHALL COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
DOORS IN THE MEANS OF EGRESS SHALL BE READILY DISTINGUISHABLE FROM THE ADJACENT
CONSTRUCTION AND FINISHES SUCH THAT THE DOORS ARE EASILY RECOGNIZABLE AS DOORS. MIRRORS OR SIMILAR REFLECTING MATERIALS SHALL NOT BE USED ON MEANS OF EGRESS DOORS. MEANS OF EGRESS DOORS SHALL NOT BE CONCEALED BY CURTAINS, DRAPES, DECORATIONS OR SIMILAR MATERIALS.
1010.1.1 SIZE OF DOORS
THE REQUIRED CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM CLEAR OPENING WIDTH OF 32 INCHES (813 MM). THE CLEAR OPENING WIDTH OF DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). THE MINIMUM CLEAR OPENING
HEIGHT OF DOORS SHALL BE NOT LESS THAN 80 INCHES (2032 MM).
1010.1.2 EGRESS DOOR TYPES
EGRESS DOORS SHALL BE OF THE SIDE-HINGED SWINGING DOOR, PIVOTED DOOR, OR BALANCED DOOR
TYPES.
EXCEPTION 1 - PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE AREAS WITH AN OCCUPANT
LOAD OF 10 OR LESS.
CHAPTER 10 - MEANS OF EGRESS
1102.1 DESIGN
BUILDINGS AND FACILITIES SHALL BE DESIGNED AND CONSTRUCTED TO BE ACCESSIBLE IN ACCORDANCE
WITH THIS CODE AND ICC A117.1.
1104.1 SITE ARRIVAL POINTS
AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE SITE SHALL BE PROVIDED FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE PARKING, ACCESSIBLE PASSENGER LOADING ZONES, AND PUBLIC STREETS OR
SIDEWALKS TO THE ACCESSIBLE BUILDING ENTRANCE SERVED.
1104.2 WITHIN A SITE.
AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
1104.3.1 EMPLOYEE WORK AREAS
COMMON USE CIRCULATION PATHS WITHIN EMPLOYEE WORK AREAS SHALL BE ACCESSIBLE ROUTES.
1104.4 MULTISTORY BUILDING AND FACILITIES
AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT EACH ACCESSIBLE STORY, MEZZANINE AND OCCUPIED
ROOFS IN MULTILEVEL BUILDINGS AND FACILITIES.
EXCEPTION 2 - STORIES, MEZZANINES OR OCCUPIED ROOFS THAT DO NOT CONTAIN ACCESSIBLE ELEMENTS OR OTHER SPACES AS DETERMINED BY SECTION 1108 OR 1109 ARE NOT REQUIRED TO BE
SERVED BY AN ACCESSIBLE ROUTE FROM AN ACCESSIBLE LEVEL.
PROVIDED: EXISTING BUILDING IS NOT EQUIPPED WITH AN ELEVATOR. PROJECT DOES NOT INCLUDE ADDING AN ELEVATOR TO THE EXISTING BUILDING. PROJECT DOES NOT INCLUDE ACCESSIBLE ELEMENTS
OR SPACES OUTLINED IN SECTION 1108 OR 1109.
1105.1 PUBLIC ENTRANCES
IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY SECTIONS 1105.1.1 THROUGH 1105.1.7, AT LEAST 60
PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
PROVIDED: PUBLIC ENTRANCE IS ACCESSIBLE.
1110.2 TOILET AND BATHING FACILITIES
EACH TOILET ROOM AND BATHING ROOM SHALL BE ACCESSIBLE. WHERE A FLOOR LEVEL IS NOT REQUIRED TO BE CONNECTED BY AN ACCESSIBLE ROUTE, THE ONLY TOILET ROOMS OR BATHING ROOMS PROVIDED WITHIN THE FACILITY SHALL NOT BE LOCATED ON THE INACCESSIBLE FLOOR. EXCEPT AS PROVIDED FOR IN SECTIONS 1110.2.2 THROUGH 1110.2.6, AT LEAST ONE OF EACH TYPE OF FIXTURE, ELEMENT, CONTROL, OR
DISPENSER IN EACH ACCESSIBLE TOILET ROOM AND BATHING ROOM SHALL BE ACCESSIBLE.
1110.4 KITCHENS AND KITCHENETTES
WHERE KITCHENS AND KITCHENETTES ARE PROVIDED I INACCESSIBLE SPACES OR ROOMS, THEY SHALL BE
ACCESSIBLE.
1110.5.1 MINIMUM NUMBER (OF DRINKING FOUNTAINS)
NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN
SHALL COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS,
1110.10 STORAGE
WHERE FIXED OR BUILT-IN STORAGE ELEMENTS SUCH AS CABINETS, COATS HOOKS, SHELVES, MEDICINE CABINETS, LOCKERS, CLOSETS AND DRAWERS ARE PROVIDED IN REQUIRED ACCESSIBLE SPACES, AT
LEAST 5 PERCENT, BUT NOT LESS THAN ONE OF EACH TYPE SHALL BE ACCESSIBLE.
1110.13.2 SALES AND SERVICE COUNTERS AND WINDOWS.
WHERE COUNTERS OR WINDOWS ARE PROVIDED FOR SALE OR DISTRIBUTION OF GOODS OR SERVICES, AT LEAST ONE OF EACH TYPE OF COUNTER AND WINDOW PROVIDED SHALL BE ACCESSIBLE. WHERE SUCH COUNTERS OR WINDOWS ARE DISPERSED THROUGHOUT THE BUILDING OR FACILITY, ACCESSIBLE
COUNTERS OR WINDOWS SHALL ALSO BE DISPERSED.
1110.15 CONTROLS, OPERATING MECHANISMS AND HARDWARE.
CONTROLS, OPERATING MECHANISMS AND HARDWARE INTENDED FOR OPERATION BY THE OCCUPANT, INCLUDING SWITCHES THAT CONTROL LIGHTING AND VENTILATION AND ELECTRICAL CONVENIENCE OUTLETS, IN ACCESSIBLE SPACES, ALONG ACCESSIBLE ROUTES OR AS PARTS OF ACCESSIBLE ELEMENTS
SHALL BE ACCESSIBLE.
CHAPTER 11 - ACCESSIBILITY
THIS PROJECT IS REVIEWED UNDER VIRGINIA ENERGY CONSERVATION CODE (2021).
CLIMATE ZONE - 4A (SECTION C301.1) NON RESIDENTIAL
PER VECC TABLE C402.1.3 AND TABLE C402.4 STRASBURG POLICE STATION ENVELOPE IS REVIEWED AND THE
SUMMARY OF ENVELOPE THERMAL REQUIREMENTS ARE SHOWN BELOW.
ENERGY CONSERVATION CODE REVIEW PER VECC 2021
ROOF - INSULATION ENTIRELY
ABOVE ROOF DECK
U - 0.032 R - 30ci
WALLS - ABOVE GRADE (MASS)
SLAB ON GRADE - UNHEATED
FIXED WINDOWS
OPERABLE FENESTRATION
ENTRANCE DOORS
SHGC (PF < 0.2)
U - 0.104 R - 9.5ci
F - 0.52
R - 15 FOR 24 INCHES
U - 0.36
U - 0.45
U - 0.63
U - 0.36
BUILDING ENVELOPE THERMAL VALUE BUILDING MATERIAL
1010.1.2.1 DIRECTION OF SWING
SIDE-HINGED SWINGING DOORS, PIVOTED DOORS AND BALANCED DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE
PERSONS.
TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE (NON-SPRINKLERED)
OCCUPANCY MAX. TRAVEL DISTANCE (FEET)
B 200 S-1 200
TABLE 1020.2 CORRIDOR FIRE-RESISTANCE RATING
OCCUPANCY OCCUPANT LOAD SERVED BY CORRIDOR WITHOUT SPRINKLER SYSTEM
B, S GREATER THAN 30 1 HOUR
CHAPTER 10 - MEANS OF EGRESS (CONT'D)
REVIEWED PER 2021 VIRGINIA PLUMBING CODE
TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
CHAPTER 4 – FIXTURES, FAUCETS AND FIXTURE FITTINGS
CLASSIFICATION WATER CLOSETS LAVATORIES BATHTUBS/
SHOWERS
DRINKING
FOUNTAINS
OTHER
BUSINESS 1/25 FOR FIRST 50
1/50 FOR REMAINDER
1/40 FOR FIRST 80
1/80 FOR REMAINDER
- 1/100 1 SERVICE SINK
REQUIRED 2 2 - 1 1 SERVICE SINK
PROVIDED - 1 1 SERVICE SINK3 3
WALLS - BELOW GRADE U - 0.119
R - 7.5ci
1 1
2 2
SB SB
UP
1 1
1 1
1 1
1 11
1 1
1 1
1 1
1 1
FEC-1
PATH
CODE PLAN LEGEND
AREA OF SPACE/AREA PER OCCUPANT
OCCUPANT LOAD
OCCUPANCY USE TYPE
FIRE EXTINGUISHER CABINET - FULLY RECESSED
TRAVEL DISTANCE
(SEE EGRESS PATH SCHEDULE)
1-HR FIRE RATED WALL
2-HR FIRE WALL
MAX. NUMBER OF OCCUPANTS ALLOWED PER
CODE THRU AN EGRESS DOOR / EGRESS STAIR
NUMBER OF OCCUPANTS GOING THRU
AN EGRESS DOOR OR THRU AN EGRESS
STAIR
SMOKE PARTITIONS
FEC-2
FEC-3
FIRE EXTINGUISHER CABINET - SEMI RECESSED
FIRE EXTINGUISHER - WALL MOUNTED
Area Name
150 SF / 150 SF
BUSINESS
3631 SF / 150 SF
CHIEF OF POLICE
ADMIN ASST.
ADMIN ASST. /
ACCRED MGR. VESTIBULE
LOBBYDATA ENTRY
CORRIDOR
CAPTAIN
GEN. BLDG
SUPPLY STOR.
HIGH DENS.
STOR.
PATROL LT.
OFFICE
PATROL SGTS
COURT PREP /
LACTATION
ELEC ROOM
TEMP EVIDENCE
NARCOTICS
EVIDENCE STOR:
GEN / PROP
PATROL EQUIPT
STOR ROOM
EVID. DROP /
BAG + TAG
INTAKE
STAFF LOBBY MAIN STAFF
BREAK
R.R.
R.R.
INTERVIEW &
CITIZEN REPORT
ROOM
COPY / PRINT
EXIT 1
EXIT 2
EXIT 3
93'-4'' AREA DIAGONAL
93'-4'' / 2 = 46'-8''
2021 VCC SECTION 301.1.2
STAFF BREAK AREA CATEGORIZED
AS SMALL ASSEMBLY SPACE AND
HAS BEEN CLASSIFIED AS BUSINESS
GROUP OCCUPANCY
STORAGE - 1
107 SF / 300 SF
STORAGE - 1
559 SF / 300 SF
PATH A
PATH C
PATH D
PATH B
CORRIDOR
OCCUPANCY TYPE
BUSINESS
STORAGE - 1
FEC-1
FEC-2
FEC-2
X X
X X
X X
X
X
MECH
CID SECURE
STORAGE
HARD
INTERVIEW
R.R.
SECURE VEST.
CID LIEUT.
COMPUTER
FORENSIC ROOM
TELECOM
BUSINESS
1219 SF / 150 SF
STORAGE - 1
568 SF / 300 SF
PATH E
FEC-1
FIRST FLOOR
0' - 0"
SECOND FLOOR
11' - 10"
ROOF
20' - 4"
C.1 DA B.1 B.2
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
/2
/2
:5
:5
A
M
CODE & LIFE
SAFETY PLAN
EA
Checker
RW
08.26.2026
50165756
S T
R A
S B
U R
G P
O L
IC
E
S T
A T
IO
N
T O
W N
O F
S T
R A
S B
U R
G
IS
S
U E
D F
O R
B
ID
W
K in g S tr e e t, S tr a s b u rg
V
A
DEWBERRY
8401 Arlington Blvd Fairfax, VA 22031 703.849.0100
G-003
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
Egress Path Schedule
PATH NAME PATH LENGTH
PATH A 95'-3"
PATH B 74'-4"
PATH C 53'-8"
PATH D 39'-1 1/2"
PATH E 57'-11"
Scale: 1/8" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
Scale: 1/8" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
Scale: 1/8" = 1'-0"
BUILDING SECTION LIFE SAFETY PLAN
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
/2
/2
:5
:5
A
M
ADA STANDARDS
TF
RW / LP
RW
08.26.2026
50165756
S T
R A
S B
U R
G P
O L
IC
E
S T
A T
IO
N
T O
W N
O F
S T
R A
S B
U R
G
IS
S
U E
D F
O R
B
ID
W
K in g S tr e e t, S tr a s b u rg
V
A
DEWBERRY
8401 Arlington Blvd Fairfax, VA 22031 703.849.0100
G-004
PROJ. FILE# 50165756
C-001
SP-787
TOWN OF STRASBURG POLICE STATION
VICINITY MAP
SCALE: 1" = 400'
APPLICANT/DEVELOPER/OWNER
CIVIL ENGINEER / SURVEYOR
CONTACT: ALVARO DE LA VEGA
(703) 468-2246 adelavega@dewberry.com
COUNTY REVISIONS
DATENO. DESCRIPTION BY
DISTRICT 6
SHENANDOAH COUNTY, VIRGINIA
DATE: AUGUST 12, 2025
Dewberry Engineers Inc.
13575 HEATHCOTE BLVD.
SUITE 130
GAINESVILLE, VA 20155-6693
PHONE: 703.468.2211
FAX: 703.468.2212
INFORMATION
SURVEY AND TOPOGRAPHIC
MINOR SITE PLAN
SHEET INDEX
SITE INFORMATION:
- SITE ADDRESS: 174 E KING ST STRASBURG, VA 22657
- TAX MAP/PARCEL NO.: 025A3A168
- SITE AREA: 0.549 AC.
- ZONING: CC, COMMUNITY COMMERCIAL
STRASBURG HISTORIC DISTRICT
- EXISTING USE: VACANT
- PROPOSED USE: TOWN OF STRASBURG POLICE STATION
SETBACKS:
FRONT = 0 FT (FROM R/W)
REAR = 25 FT (FROM LOT LINE)
SIDE = 0 FT (FROM R/W)
SIDE = 25 FT (FROM LOT LINE)
DISTURBED AREA: 0.10 ACRES (4,115 SF)
TOWN OF STRASBURG
174 E KING ST
STRASBURG, VA 22657
RESPONSIBLE LAND DISTURBER
TBD
FLOODPLAIN NOTE:
THIS PROPERTY DOES NOT FALL WITHIN ANY FLOODPLAIN ZONE AS
SHOWN ON FIRM COMMUNITY PANEL # 51171C0180C
EFFECTIVE DATE: 7/16/03
07.01.2026REVISED PARKING LAYOUT & FENCE LINE
08.26.2026ISSUE FOR BID
C-002
1"=20'
CW
CW
E X
IS
TI
N G
C O
N D
IT
IO
N S
D
E M
O
LI
TI
O
N P
LA
N
LEGEND
DEMOLITION NOTES:
Drawn By
Plan Number
Checked By
Designed By
File Number
SP-787
Sheet
Scale
Date
S
TR
A S
B U
R G
P O
LI
C
E S
TA
TI
O N
To w n of
S tr as bu rg , V irg in ia
REVISIONS
DATENO. DESCRIPTION BY
D ew be rr y E ng in ee rs
In c.
H
E A
TH
C
O
TE
B
LV
D
S U
IT
E
G A
IN
E
S V
IL
LE
, V A
-6
P H
O N
E : 7
.4
.2
FA
X
: 7
.4
.2
08/19/2025
07.01.2026REVISED PARKING LAYOUT & FENCE LINE
08.26.2026ISSUE FOR BID
GENERAL NOTES:
SITE INFORMATION:
- SITE ADDRESS: 174 E KING ST STRASBURG, VA 22657
- TAX MAP/PARCEL NO.: 025A3A168
- SITE AREA: 0.549 AC.
- ZONING: CC, COMMUNITY COMMERCIAL
STRASBURG HISTORIC DISTRICT
- EXISTING USE: VACANT
- PROPOSED USE: TOWN OF STRASBURG POLICE STATION
DISTURBED AREA: 0.10 ACRES (4,115 SF)
STOP
STOP
STOP
STOP
C-003
1"=20'
CW
CW
S
IT
E P
LA
N
LEGEND
PAVEMENT DETAIL
CG-2 CURB DETAIL
PARKING TABULATION:
EXISTING ULTIMATE
STANDARD SPACES 28 32
HANDICAP SPACES 0 0
H.C. VAN ACCESS SPACES 2 2
TOTAL SPACES 30 34
NET = 4 ADDITIONAL SPACES
Drawn By
Plan Number
Checked By
Designed By
File Number
SP-787
Sheet
Scale
Date
S
TR
A S
B U
R G
P O
LI
C
E S
TA
TI
O N
To w n of
S tr as bu rg , V irg in ia
REVISIONS
DATENO. DESCRIPTION BY
D ew be rr y E ng in ee rs
In c.
H
E A
TH
C
O
TE
B
LV
D
S U
IT
E
G A
IN
E
S V
IL
LE
, V A
-6
P H
O N
E : 7
.4
.2
FA
X
: 7
.4
.2
08/19/2025
07.01.2026REVISED PARKING LAYOUT & FENCE LINE
08.26.2026ISSUE FOR BID
CONCRETE PAD DETAIL
PAVEMENT & PAVEMENT MARKING PLAN
SITE PLAN
DEAD LOADS
SECOND FLOOR (ASSUMED) 30 PSF
ROOF (ASSUMED) 15 PSF
SUSPENDED COLLATERAL LOAD SECOND FLOOR 10 PSF
SUSPENDED COLLATERAL LOAD ROOF 10 PSF
LIVE LOADS
GROUND FLOOR 100 PSF
SECOND FLOOR 65 PSF
ROOF 20 PSF
ROOF SNOW LOAD
GROUND SNOW (Pg) (COUNTY WEBSITE) 100 PSF FLAT ROOF SNOW (Pf) 84.0 PSF EXPOSURE FACTOR (Ce) 1.0
SNOW IMPORTANCE FACTOR (I) 1.2
THERMAL FACTOR (Ct) 1.0
WIND LOAD DESIGN DATA
BASIC WIND SPEED (3 SEC. GUST) 123 MPH
RISK FACTOR IV
WIND EXPOSURE B
INTERNAL PRESSURE COEFFICIENT +/- 0.18
SEISMIC LOAD DESIGN DATA
SEISMIC IMPORTANCE FACTOR 1.5
MAPPED SPECTRAL RESPONSE ACCELERATION
(SS) 0.150 g (S1) 0.051 g
SITE CLASS (ASSUMED) DEFAULT PER ASCE 7-22
SPECTRAL RESPONSE COEFFICIENT
(SDS) 0.120 g (SD1) 0.072 g
SEISMIC DESIGN CATEGORY C
BASIC SEISMIC-FORCE RESISTING SYSTEM:
STEEL SYSTEM NOT SPECIFICALLY DETAILED
FOR SEISMIC RESISTANCE 3.0
DESIGN BASE SHEAR (N-S) 0.06 W
DESIGN BASE SHEAR (E-W) 0.06 W
ANALYSIS PROCEDURE:
EQUIVALENT LATERAL FORCE PROCEDURE
TORNADO LOAD DESIGN DATA
RISK CATEGORY IV
Ae 4,000 FT2
VT 50 MPH
VT<60 MPH, THEREFORE DESIGN FOR TORNADO LOADS IS NOT REQUIRED PER
ASCE 7-22, SECTION 32.5.2
BUILDING LOADS AND FACTORS PER
2021 VIRGINIA CONSTRUCTION CODE
WIND COMPONENT AND CLADDING PRESSURES
BUILDING COMPONENT
WALL
ROOF
SURFACE
EFFECTIVE AREA (SF)
MAXIMUM PRESSURE (PSF)
-28.1
-21.5
-34.7
-21.5
-25.9
-23.7
-43.4
-28.1
-65.4
-28.1
COORDINATION:
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH, AND COORDINATED
WITH CIVIL, MECHANICAL, ELECTRICAL, PLUMBING, ARCHITECTURAL, AND OTHER
CONTRACT DOCUMENTS.
2. OPENINGS IN SLABS, WALLS, ROOFS, ETC. SHOWN ON THE STRUCTURAL DRAWINGS ARE
FOR REFERENCE ONLY AND ARE NOT INTENDED TO DEFINE THE EXACT LOCATION, SIZE,
ELEVATIONS, FIRE RATING, OR ANY OTHER PROPERTY OF THE OPENING UNLESS
OTHERWISE NOTED. THE STRUCTURAL DRAWINGS ARE NOT INTENDED TO SHOW ALL
OPENINGS AND PENETRATIONS WITHIN OR THROUGH THE STRUCTURE. THE
CONTRACTOR SHALL COORDINATE ALL OPENINGS AND PENETRATIONS WITH THE
ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS.
3. COORDINATE THE EXACT SIZE AND LOCATION OF ALL SLEEVES AND OPENINGS THROUGH
CONCRETE SLABS AND CONCRETE WALLS WITH CIVIL, MECHANICAL, PLUMBING, AND
ELECTRICAL DRAWINGS. SLEEVES SHALL BE ASTM A 53 SCHEDULE 40 STEEL WITH A
DIAMETER NOT GREATER THAN 12 INCHES AND SHALL BE GALVANIZED AFTER CUTTING.
4. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL EXISTING CONDITIONS
INCLUDING ANY EXISTING CONSTRUCTION AND REPORT ANY DISCREPANCIES WITH THE
CONSTRUCTION DOCUMENTS BEFORE PROCEEDING WITH THE WORK.
EXISTING STRUCTURES:
1. CONTRACTOR IS RESPONSIBLE FOR DOCUMENTING ALL EXISTING CONDITIONS PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IF AN ITEM IN QUESTION IS BELIEVED TO HAVE
BEEN DAMAGED DURING CONSTRUCTION AND THERE IS NO PHOTOGRAPHIC PROOF OF
ITS STATE PRIOR TO CONSTRUCTION, THE CONTRACTOR IS RESPONSIBLE FOR
REPAIRING OR REPLACING TO THE SATISFACTION OF THE ARCHITECT AND OWNER AT
THE SOLE EXPENSE OF THE CONTRACTOR AND/OR HIS SUB-CONTRACTORS.
2. SIZES, ELEVATIONS, AND DIMENSIONS OF EXISTING STRUCTURAL AND ARCHITECTURAL
ELEMENTS ARE BASED ON EXISTING DRAWINGS PROVIDED BY THE OWNER AND/OR FIELD
MEASUREMENTS AND ARE FOR GENERAL REFERENCE ONLY. THE CONTRACTOR SHALL
VERIFY ACTUAL CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ENGINEER
BEFORE STARTING WORK.
3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE AND MAINTAIN ANY
AND ALL WORK NECESSARY TO PROTECT EXISTING FACILITIES AND UTILITIES THIS
INCLUDES, BUT IS NOT LIMITED TO, BUILDINGS, UNDERGROUND UTILITIES, PIPING,
POWER, CONDUIT, COMMUNICATION LINES, PAVEMENT, SIDEWALKS, DRAINAGE
STRUCTURES, TREES, AND PLANTED AREAS. ANY DAMAGE TO EXISTING FACILITIES
SHALL BE REPAIRED TO THE SATISFACTION OF THE ARCHITECT AND OWNER AT THE
SOLE EXPENSE OF THE CONTRACTOR.
4. THE CONTRACTOR SHALL VERIFY ANY CONFLICTS WITH EXISTING UTILITIES. IF A
CONFLICT IS ENCOUNTERED, CONTRACTOR SHALL IMMEDIATELY NOTIFY ARCHITECT AND
OWNER AND A RESOLUTION SHALL BE REACHED BEFORE WORK PROCEEDS IN THE
AFFECTED AREA.
5. NO STAGING OF EQUIPMENT OR VEHICLES OUTSIDE OF MARKED AREAS SHALL BE
PERMITTED WITHOUT WRITTEN PERMISSION OF THE OWNER.
GENERAL:
1. THE GENERAL STRUCTURAL NOTES ARE INTENDED TO AUGMENT THE DRAWINGS AND
SPECIFICATIONS. SEE DRAWINGS AND SPECIFICATIONS FOR REQUIREMENTS IN
ADDITION TO GENERAL NOTES. SHOULD CONFLICTS EXIST BETWEEN THE DRAWINGS,
SPECIFICATIONS, AND GENERAL STRUCTURAL NOTES, THE STRICTEST PROVISION SHALL
GOVERN.
2. UNLESS NOTED OTHERWISE, CONSTRUCTION MEANS AND METHODS SHALL BE SOLELY
THE RESPONSIBILITY OF THE CONTRACTOR.
3. THE STRUCTURE, OR STRUCTURES, DEFINED BY THESE DRAWINGS CONFORM TO THE
2021 VIRGINIA EXISTING BUILDING CODE AND HAVE BEEN DESIGNED AS COMPLETE
STRUCTURES TO RESIST THE LOADS LISTED IN "BUILDING LOADS AND FACTORS PER 2021
VIRGINIA CONSTRUCTION CODE" BOX ON THIS SHEET. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CONSTRUCTION LOADS AND OTHER LOADS IMPOSED ON THE
PARTIALLY COMPLETED STRUCTURE(S). THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE DESIGN OF SHORING, BRACING, FORMWORK, ERECTION AIDS, AND OTHER NON-
PERMANENT SUPPORTING ELEMENTS UTILIZED FOR CONSTRUCTION. THE CONTRACTOR
SHALL PROVIDE TEMPORARY BRACING IN ALL DIRECTIONS UNTIL ALL PERMANENT
CONNECTIONS ARE MADE.
4. THE CONTRACTOR SHALL NOT SCALE DIMENSIONS FROM THE DRAWINGS.
5. ALL DETAILS AND SECTIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED TO
BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO SIMILAR CONDITIONS ELSEWHERE.
6. THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS,
PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTION SHALL TAKE ALL NECESSARY PRECAUTIONS TO
MAINTAIN AND ENSURE INTEGRITY OF THE STRUCTURE AT ALL STAGES OF
CONSTRUCTION.
7. ALL PRODUCTS AND MATERIALS REQUIRED FOR THE WORK SHALL BE INSTALLED IN
ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS AND
RECOMMENDATIONS FOR INSTALLATION IN APPLICATIONS INDICATED, INCLUDING ALL
ACCESSORIES, ATTACHMENTS, AND THE LIKE.
8. ALL WORK SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF THE 2021 VIRGINIA
BUILDING CODE, AS WELL AS REQUIREMENTS OF THE TOWN OF STRASBURG AND ALL
OTHER AUTHORITIES HAVING JURISDICTION.
REINFORCED CONCRETE:
1. UNLESS NOTED OTHERWISE, ALL CONCRETE WORK, DETAILING, FABRICATION, AND
PLACING OF REINFORCING AND CONCRETE SHALL BE GOVERNED BY THE LATEST
REVISIONS OF:
A. ACI 301, ACI 315, AND ACI 318.
B. CRSI RECOMMENDED PRACTICE OF PLACING REINFORCING BARS.
C. ACI 306 AND ACI 305 FOR COLD AND HOT WEATHER CONCRETING, RESPECTIVELY.
2. ALL CONCRETE SHALL BE NORMAL WEIGHT WITH A MAXIMUM UNIT WEIGHT OF 150
POUNDS PER CUBIC FOOT. CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE
STRENGTH, AS SPECIFIED BELOW, FOR THE RESPECTIVE AREAS:
A. COLUMN FOOTINGS 3,000 PSI
B. WALL FOOTINGS 3,000 PSI
C. SUSPENDED SLABS 4,000 PSI
D. EXTERIOR SLAB/FOUNDATION 4,500 PSI
3. PLACE 1/2" EXPANSION JOINT MATERIAL BETWEEN EDGES OF SLABS AND VERTICAL
SURFACES U.N.O.
4. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, AND SHALL BE GRADE 60 U.N.O.
5. REINFORCING STEEL INDICATED TO BE WELDED SHALL CONFORM TO ASTM A 706 AND
SHALL BE GRADE 60.
6. WELDED WIRE FABRIC SHALL BE NEW BILLET STEEL, COLD DRAWN CONFORMING TO
ASTM SPECIFICATIONS A 1064 AND SHALL BE PROVIDED IN FLAT SHEETS.
7. REINFORCING BAR LAP SPLICES AND HOOK DIMENSIONS SHALL BE AS REQUIRED PER THE
SCHEDULE ON SHEET S-001 U.N.O.
FOUNDATIONS
1. FOUNDATION DESIGN IS BASED ON ASSUMED ALLOWABLE BEARING PRESSURE OF
1,500 PSF (ASSUMED PER 2021 IBC TABLE 1806.2)
2. ALL COMPACTED FILL, EXCAVATION, SUBGRADES, AND BEARING SURFACES SHALL BE
OBSERVED AND TESTED BY A GEOTECHNICAL ENGINEER REGISTERED IN THE
COMMONWEALTH OF VIRGINIA (OR A QUALIFIED GEOTECHNICAL TECHNICIAN WORKING
UNDER THE DIRECT SUPERVISION OF A REGISTERED ENGINEER) TO VERIFY SPECIFIED
GEOTECHNICAL CONFORMANCE REQUIREMENT.
3. THE STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR SUBSURFACE
CONDITIONS ENCOUNTERED IN THE FIELD CONTRARY TO THOSE ASSUMED FOR DESIGN.
4. GEOTECHNICAL ENGINEER OR THEIR AUTHORIZED REPRESENTATIVE SHALL CONFIRM THE
PRESENCE OF SOILS SUITABLE FOR SUPPORT OF THE DESIGN BEARING PRESSURE AT
COLUMN AND WALL FOOTING SUBGRADES. AT MINIMUM, THE FOUNDATION BEARING
PRESSURE SHALL BE PROBED WITH A SMALL DIAMETER PROBE ROD IN ORDER TO IDENTIFY
SOFT AREAS. DYNAMIC CONE PENETROMETER (DCP) TESTS SHALL BE PERFORMED IN
ACCORDANCE WITH ASTM STP-399. THE DCP TESTS SHALL EXTEND FROM THE FOUNDATION
BEARING ELEVATION TO A MINIMUM DEPTH OF 4 FEET OR TWO TIMES THE FOOTING WIDTH,
WHICHEVER IS DEEPER. HAND AUGER BORINGS SHALL BE PERFORMED IN CONJUNCTION
WITH THE TESTING TO DOCUMENT A VISUAL DESCRIPTION OF THE SOIL TYPES. THE HAND
AUGER TEST BORINGS SHALL BE LOCATED AT EACH COLUMN FOOTING AND SPACED NO
GREATER THAN 25 FEET ALONG CONTINUOUS WALL FOOTINGS.
5. UNLESS NOTED OTHERWISE, FOUNDATION SUBGRADES REQUIRING UNDERCUT SHALL BE
FILLED FROM THE ELEVATION OF UNDERCUT TO THE ORIGINAL DESIGN SUBGRADE
ELEVATION WITH LEAN CONCRETE, MINIMUM 500 PSI FLOWABLE FILL.
6. WHENEVER POSSIBLE, FOUNDATION CONCRETE SHALL BE PLACED IMMEDIATELY AFTER
EXCAVATION SO THAT ACCUMULATION OF WATER IN THE EXCAVATION OR DRYING OF
FOUNDATION SOILS CAN BE AVOIDED.
7. CONTRACTOR SHALL CONTROL SITE GROUNDWATER AND/OR SURFACE WATER BY ALL
MEANS NECESSARY TO MAINTAIN A WATER LEVEL ONE FOOT BELOW SLAB SUBGRADE SO
AS TO NOT DAMAGE FOUNDATION EXCAVATIONS.
8. ANY SUBGRADE SOILS WHICH HAVE BEEN WEAKENED DUE TO SATURATION OR
DISTURBANCE SHALL BE RECOMPACTED OR REMOVED AND REPLACED WITH STRUCTURAL
FILL AS DIRECTED BY GEOTECHNICAL…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .