2026-11-09 AGCS - Admininistration - Bid Issue - Electrical.pdf
PDF 2 MB Posted
- Solicitation number
- US.261299
- Issued by
- Chester County, Pennsylvania
About this file
This electrical construction bid document outlines the electrical work required for the Avon Grove Charter School's State Road Administration Renovation Project located in London Grove Township, Chester County, Pennsylvania. The project scope includes installation of lighting fixtures and controls, panelboards, wiring devices, fire alarm systems, and support for general, mechanical, plumbing, and low-voltage cabling work. The electrical contractor is responsible for coordinating work between multiple vendors, including security vendors, telecom vendors, and audio/visual vendors who will be hired directly by the owner through state contracts. A mandatory pre-bid conference was scheduled for November 20, 2026, at 3:30 PM at the State Road Campus, with attendance required for all prime contract bidders. Sealed electronic bids were due December 15, 2026, at 2:30 PM prevailing time via PennBid, with public opening and reading at 3:00 PM the same day at Avon Grove Charter School, 110 E. State Road, West Grove, Pennsylvania 19390.
The project is subject to the Pennsylvania Prevailing Wage Act and requires prevailing minimum wage rates as promulgated by the Secretary of Labor & Industry. The electrical construction work involves multiple lighting fixture types with varying specifications including LED recessed troffers, pendant fixtures, linear fixtures, and downlights with 0-10V dimming capabilities. The electrical contractor must provide full interior and exterior lighting illumination calculations as part of submittal review if fixtures other than the basis of design are proposed. Two existing electrical panels require modifications, with specific circuit breaker replacements noted. Total estimated loads include Phase A at 23.37 kVA, Phase B at 19.61 kVA, and Phase C at 24.21 kVA for one panel, and Phase A at 25.39 kVA, Phase B at 23.99 kVA, and Phase C at 23.85 kVA for the new panel. A satisfactory corporate surety bond equal to the contract amount is required, and all prime contract bidders must register on www.pennbid.net to submit bids.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MATERIAL PROVIDED BY DEMOLISHED BY INSTALLED BY LOW VOLTAGE WIRING BY
120V POWER, BACKBOX
AND CONDUIT BY
PROGRAMMING/ HEAD END
TERMINATIONS
CARD ACCESS (CARD READERS, DOOR CONTACTS, LOCAL DOOR
ALARMS, ETC)
SECURITY VENDOR SECURITY VENDOR SECURITY VENDOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR SECURITY VENDOR
DOOR HARDWARE (LATCH RETRACTION, STRIKES, POWER
SUPPLIES, DOOR OPENERS, ETC)
GENERAL CONTRACTOR ELECTRICAL CONTRACTOR GENERAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR -
INTRUSION & MONITORING DEVICES & EQUIPMENT SECURITY VENDOR SECURITY VENDOR SECURITY VENDOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR SECURITY VENDOR
CCTV CAMERAS, CABLES, CCTV NETWORK SWITCHES, NVR, ETC. SECURITY VENDOR SECURITY VENDOR SECURITY VENDOR TELECOM VENDOR ELECTRICAL CONTRACTOR SECURITY VENDOR
CABLE TRAY, LADDER RACK ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR - ELECTRICAL CONTRACTOR -
DATA RACKS, PATCH PANELS, PATCH CABLES TELECOM VENDOR - TELECOM VENDOR TELECOM VENDOR ELECTRICAL CONTRACTOR TELECOM VENDOR
NETWORK SWITCHES (EXCEPT FOR CCTV SYSTEM) OWNER - OWNER - ELECTRICAL CONTRACTOR OWNER
FIBER CABLES, FIBER SHELVES, PATCH CABLES TELECOM VENDOR - TELECOM VENDOR TELECOM VENDOR ELECTRICAL CONTRACTOR TELECOM VENDOR
DATA JACKS, CAT6A CABLING, FACEPLATES, RACKS, ETC. TELECOM VENDOR TELECOM VENDOR TELECOM VENDOR TELECOM VENDOR ELECTRICAL CONTRACTOR TELECOM VENDOR
WIRELESS ACCESS POINTS OWNER OWNER OWNER TELECOM VENDOR ELECTRICAL CONTRACTOR OWNER
CLASSROOM & OFFICE TELEPHONES OWNER OWNER OWNER TELECOM VENDOR ELECTRICAL CONTRACTOR OWNER
PUBLIC ADDRESS (PA) SYSTEM, SPEAKERS, AMPLIFIERS, ETC. ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR
WIRELESS CLOCKS (DIGITAL WITH MESSAGING) ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR
AUDIO/VISUAL (PROJECTORS, SCREENS, MONITORS, CABLES) A/V VENDOR A/V VENDOR A/V VENDOR A/V VENDOR ELECTRICAL CONTRACTOR A/V VENDOR
POWER, LIGHTING, FIRE ALARM ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR
NOTES:
2. THE TELECOMM, SECURITY AND A/V VENDORS WILL BE HIRED WITH STATE-CONTRACTS DIRECT WITH THE OWNER. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL NECESSARY COORDINATION OF WORK BETWEEN PARTIES ABOVE.
CONTRACTOR RESPONSIBILITY CHART
1. THIS CHART SHALL SUPERSEDE ANY OTHER LOCATIONS DESCRIBING CONTRACTOR RESPONSIBILITIES.
LUMENS WATTS COLOR HOURS@L70 TYPE
A1 FINELITE HPR-SL-ANR-2X4-H-835-DCO-96LG-120V-SC-FC-10%-XX-96LG 120V 5,241 35.2 3500K 100,000@L90 LED 0-10V DIMMING RECESSED 10 YEARS 2X4 LED ARCHITECTURAL CENTER-CHANNEL LENSED TROFFER WITH FLAT SIDE LENSES. FIXTURE SHALL BE A MAX OF 4" DEEP. FIXTURE SHALL HAVE SMOOTH FLAT IMPACT MODIFIED ACRYLIC DIFFUSER AND HINGED DOOR. CONTRACTOR SHALL COORDINATE MOUNTING WITH SPECIFED CEILING TYPE.
A2 FINELITE HPR-SL-ANR-2X2-B-835-DCO-96LG-120V-SC-FC-10%-XX-96LG 120V 4,314 30 3500K 100,000@L90 LED 0-10V DIMMING RECESSED 10 YEARS SAME AS FIXTURE TYPE "A1", EXCEPT FIXTURE TO BE 2'X2' AND REDUCED LUMEN OUTPUT.
B4 JLC-TECH TBSL-MW-4-24-D-X-W 120V 2,740 21.4 4000K - LED 0-10V DIMMING CEILING GRID 5 YEARS 1" WIDE X 4' LONG LED T-GRID FIXTURE. FIXTURE SHALL BE CERTIFIED BY ARMSTRONG FOR DIRECT INSTALL INTO ARMSTRONG CEILINGS WITHOUT
ADDITIONAL MOUNTING SUPPORTS. FIXTURE SHALL BE MADE IN USA .
C1 HE WILLIAMS 4DRTL-L20-835-DIM1-UNV-LM-OF-CC 120V 1,794 19.8 3500K 55,000 LED 0-10V DIMMING RECESSED 5 YEARS 4.5" LED ROUND RECESSED DOWNLIGHT FIXTURE WITH MEDIUM DISTRIBUTION AND DIE-CAST ALUMINUM FRAME WITH PRISMATIC, ACRYLIC LENS. FIXTURE SHALL HAVE A MAXIMUM DEPTH OF 5-3/4". FIXTURE FINISH SHALL BE SELECTED BY THE ARCHITECT.
D"X" FINELITE HP-X-P-ID-8'-S-H-835-WSO-F-96LG-120V-DC-FC-10%-FA50--XX-FE-FB 120V
436/LF↑
775/LF↓
10/LF 3500K 100,000@L90 LED 0-10V DIMMING PENDANT 10 YEARS
2.5"W x 2.5"D LINEAR PENDANT DIRECT/INDIRECT LED FIXTURE WITH ACRYLIC LENSES. NOMINAL FIXTURE LENGTH IS INDICATED BY "X" IN THE FIXTURE TYPE, AS SHOWN ON DRAWINGS.FIXTURES SHALL BE A CONTINUOUS RUN OF AS INDICATED ON THE DRAWINGS. FIXTURE SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM BODY, WITH SINGLE PIECE EXTRUDED FLUSH FROSTED WHITE SNAP-IN DIFFUSER..
E1 EMERGI-LITE LX-1/2-N-R-M-UA-C 120V - 1.5 - - LED - WALL/CEILING 5 YEARS
LED EDGE-LIT EXIT SIGN, AC-ONLY RECESSED AND UNIVERSAL MOUNT WITH UNIVERSAL FIELD INSTALLED ARROWS. CONTRACTOR SHALL DETERMINE THE NUMBER OF 1 AND 2 FACE SIGNS ON THE PROJECT AND SHALL DETERMINE THE ARROWS BASED ON THE CONTRACT DRAWINGS.
F 'X' LUMINII LIN-XXX"-HE64MO-F-DHS-XX-XX-CJB 120V 281/FT 3.8/FT 3500K - LED 0-10V DIMMING RECESSED 7 YEARS
LOW-PROFILE LED PERIMETER FIXTURE. FIXTURE IS TO BE MAXIMUM 5/8" DEEP, WITH MUD-IN FLANGE ON ONE SIDE, AND ATTACHMENT TO HARD SURFACE ON OTHER SIDE, WITH OVERALL FIXTURE WITH OF APPROX. 3". PROVIDE FIXTURE WITH CONTINUOUS RUN LENGTHS, INCLUDING CORNER FITTINGS, WITH THE NECESSARY QUANTITY OF POWER SUPPLIES. ALL NECESSARY CABLES AND COMPONENTS SHALL BE PROVIDED FOR COMPLETE
INSTALLATION.
G 'X' LUMINII LIN-XXX"-HE64SO-F-DHS-XX-XX-CJB 120V 397/FT 2.9/FT 3500K - LED 0-10V DIMMING RECESSED 7 YEARS LOW-PROFILE LED LINEAR FIXTURE. FIXTURE IS TO BE MAXIMUM 0.88" DEEP, WITH RECESS MOUNT IN GYPSUM BOARD CEILING, FIXTURES TO BE CONDTINUOUS FOR LENGTH OF FIXTURE SHOWN ON PLANS, WITH THE REMOTE POWER SUPPLY. ALL NECESSARY CABLES AND COMPONENTS SHALL BE PROVIDED FOR COMPLETE INSTALLATION. ARCHITECT TO SELECT FINISH FOR STANDARD OR PREMIUM FINISH OPTIONS.
H4 COLUMBIA CVT4-LSCS-MV 120V 6,500 46 4000K 100,000 LED NON-DIMMING SURFACE 5 YEARS 4' VAPORTITE FIXTURE WITH SWITCHABLE LUMEN OUTPUT. FIXTURE TO BE IP65 RATED WITH POLYCARBONATE HOUSING AND FROSTED POLYCARBONATE
LENS, AND STAINLESS STEEL LATCHES.
DS1 HE WILLIAMS 4DRTL-L20-840-SCA10-DIM1-UNV-LW-OF-CC-WET/CC 120V 1,352 19.8 4000K 55,000 LED 0-10V DIMMING RECESSED 5 YEARS 4.5" LED ROUND RECESSED DOWNLIGHT FIXTURE WITH WIDE DISTRIBUTION, SLOPED CEILING ADAPTER (10 DEGREES), AND DIE-CAST ALUMINUM FRAME WITH PRISMATIC, ACRYLIC LENS. FIXTURE SHALL HAVE A MAXIMUM DEPTH OF 5-3/4". FIXTURE FINISH SHALL BE SELECTED BY THE ARCHITECT. FIXTURE
SHALL BE UL LISTED FOR WET LOCATIONS.
DS2 HE WILLIAMS 4DRTL-L20-840-DIM1-UNV-LW-OF-CC-WET/CC 120V 1,352 19.8 4000K 55,000 LED 0-10V DIMMING RECESSED 5 YEARS SAME AS FIXTURE TYPE "DS1", EXCEPT FIXTURE WILL BE WITHOUT SLOPED CEILING ADAPTER.
DS3 TBD TBD 120V TBD TBD 4000K - LED - - - TO BE DETERMINED (TBD)
SS1 INSIGHT PS3-SO-40K-20-SM-120-DIM-CC-VS-IHL 120V 1,316 12 4000K 75,000 LED 0-10V DIMMING SURFACE 5 YEARS SURFACE MOUNTED LED 20 DEGREE ADJUSTABLE SPOT LIGHT WITH 4" DIAMETER WITH INTEGRAL DRIVER, VISOR, AND INTEGRAL HEX LOUVER. FIXTURE SHALL HAVE DIE-CAST ALUMINUM HOUSING AND TEMPERED GLASS LENS. FIXTURE SHALL BE UL LISTED FOR WET LOCATION AND IP66 RATED. FIXTURE
FINISH SHALL BE SELECTED BY THE ARCHITECT.
LIGHTING FIXTURE SCHEDULE
WARRANTYMOUNTING REMARKSLIGHT ENGINE DRIVER
FIXTURE
TYPE
IN ORDER FOR A FIXTURE TO BE CONSIDERED EQUAL BY THE ENGINEER, THE FIXTURE QUALITY, AESTHETICS, AND PERFROMANCE MUST BE FULLY EQUAL. FULL INTERIOR AND EXTERIOR LIGHTING ILLUMINATION CALCULATIONS FOR EACH SPACE WILL BE REQUIRED TO BE PROVIDED AS PART OF THE SUBMITALL REVIEW PROCESS, IF OTHER THAN BASIS OF DESIGN
FIXTURES ARE SUBMITTED.
MANUFACTURER CATALOG NUMBER VOLTS
OCCUPANCY
SENSOR
VACANCY
SENSOR
DAYLIGHT
SENSOR
OTHER
AUTOMATIC SHUT
OFF BY
WALL CONTROLS LIFE SAFETY EMERGENCY LIGHTING SEQUENCE LOCATION
C01 YES - - -
OCCUPANCY
SENSOR
4-BUTTON DIGITAL SWITCH(ES) (ON, OFF, RAISE, LOWER )
CONTROLLED WITH NORMAL LIGHTING. ON TO 100%
DURING POWER OUTAGE.
LIGHTS ON BY OCCUPANCY SENSOR. LIGHTS OFF BY
OCCUPANCY SENSOR OR USER. LIGHTS DIMMED BY USER.
THE "ON" FUNCTION OF THE DIMMER SHALL RECALL THE LAST
DIMMED SETTING.
OPEN OFFICES, NURSES STATION
C02 - YES - -
VACANCY
SENSOR
4-BUTTON DIGITAL SWITCH(ES) (ON, OFF, RAISE, LOWER ) -
LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR
USER. LIGHTS DIMMED BY USER. THE "ON" FUNCTION OF THE
DIMMER SHALL RECALL THE LAST DIMMED SETTING.
OFFICES
C03 YES - - -
OCCUPANCY
SENSOR
- - LIGHTS ON AND OFF BY OCCUPANCY SENSOR. CORRIDOR AND VESTIBULES
C04 YES - - -
OCCUPANCY
SENSOR
1-BUTTON DIGITAL SWITCH (ON/OFF) WITH INTEGRAL
SENSOR AT SWITCH.
LIGHTS ON AND OFF BY OCCUPANCY SENSOR. MANUAL OFF
BY USER IF DESIRED.
INDIVIDUAL TOILET ROOMS
C05 - YES - -
VACANCY
SENSOR
1-BUTTON DIGITAL SWITCH (ON/OFF) WITH INTEGRAL
SENSOR AT SWITCH.
LIGHTS ON BY USER. LIGHTS OFF BY VACANCY SENSOR OR
USER.
STORAGE, UTILITY ROOMS
LIGHTING CONTROL SCHEDULE
1 1 20 LIGHTING, INTERIOR BUILDING 1050 800 (E)LIGHTS LOBBY 20 1 2
3 1 20 LIGHTING, INTERIOR BUILDING 1050 800 (E)LIGHTS LOBBY 20 1 4
5 1 20 (E)LIGHTS VESTIBULE-LOBBY 900 360 (E)RECEPTACLES B156 20 1 6
7 1 20 (E)RECEPTACLES, B154, B160 720 720 (E)FAN B156, RECPT. B156, B152, B154 20 1 8
9 1 20 LIGHTING, EXTERIOR OVERHANG 314 360 (E)RECEPTACLE CLERICAL 20 1 10
11 1 20 (E)RECEPTACLE, LOBBY 360 720 (E)RECEPTACLES, B158, B159, B160 20 1 12
13 1 20 (E)RECEPTACLE, A158 540 900 RECEPTACLES, GREETER/RECEPTION RM. 101 20 1 14
15 1 20 RECEPTACLE, COPIER RM. 101 1200 900 RECEPTACLES, GREETER/RECEPTION RM. 101 20 1 16
17 1 20 RECEPTACLES, OFFICE RM. 103 900 900 RECEPTACLES, OFFICE RM. 104 20 1 18
19 1 20 RECEPTACLES, TV'S IN RMS 103&104 AND RECPT. RM. 105 720 540 RECEPTACLES, WAITING RM. 106, ADMIN. RM. 107 20 1 20
21 1 20 RECEPTACLES, CORRIDOR 540 540 RECEPTACLES, RR RM. 08 20 1 22
23 1 20 RECEPTACLE, COPIER RM. 110 1200 0 RECEPTACLES, ROOMS 111,112&113 20 1 24
25 1 20 RECEPTACLE, MICROWAVE, KITCHENETTE RM. 111 1600 1200 RECEPTACLE, REFRIGERATOR, KITCHENETTE RM. 111 20 1 26
27 1 20 SPARE 0 1260 RECEPTACLES, OFFICE RM. 114 20 1 28
29 1 20 (E)LIGHTS, A158 800 720 RECEPTACLES, MOTHER'S ROOM RM. 115 20 1 30
31 1 20 RECEPTACLES, RECEPTION RM. 116 720 720 RECEPTACLES, OFFICE RM. 119 20 1 32
33 1 20 (E)LIGHTS, LIBRARY 800 900 RECEPTACLES, OFFICE RM. 118 20 1 34
35 1 20 (E)LIGHTS, SECURITY, POST 800 800 (E)LIGHTS, A160, A161, A163 20 1 36
37 1 20 (E)RECEPTACLES, A163, A165 540 800 (E)REFRIGERATOR A163 20 1 38
39 1 20 RECEPTACLES, RR RM. 121 540 360 (E)RECEPTACLES, LIBRARY 20 1 40
41 1 20 (E)RECEPTACLES, LIBRARY 360 360 RECEPTACLES, COTS RM. 122 20 1 42
5890 4444 5320 5680 5120 3860
PHASE A: 11.57 kVA
PHASE B: 9.56 kVA
PHASE C: 9.18 kVA
TOTAL: 30.31 kVA
CKT
NO
AMPREMARKS A A B C REMARKS
NOTES: CIRCUIT BREAKERS SHOWN AS SHADED/GRAY ARE TO REPLACE EXISTING 2-
POLE CIRCUIT BREAKERS THAT WILL BE SPARE AFTER DEMOLITION. PROVIDE AND
INSTALL NEW 1-POLE CIRCUIT BREAKERS AS SHOWN, TO MATCH EXISTING TYPE AND
RATING TO MATCH EXISTING SQUARE D CIRCUIT BREAKERS.
LOCATION:
MAIL 109
CKT
NO
C
PANEL SCHEDULE FOR EXISTING PANEL: "F" SECTION #1
120/208V, 3PH, 4W, 225A BUS,
225A MLO, 10,000A RMS
RECESSED/FLUSH
MOUNTED
CIRCUIT
POLE
AMP B
CIRCUIT
POLE
43 1 20 (E)SHOW CASE LIGHTS/VESTIBULE RECEPTACLE 360 750 (E) LOAD 20 1 36
45 1 20 RECEPTACLE, REFRIGERATOR, NURSES STATION RM. 120 1500 750 (E) LOAD 20 1 38
47 1 20 RECEPTACLES, NURSES STATION RM. 120 900 6360
49 1 20 SPARE 0 6360
51 1 20 SPARE 0 6360
53 1 20 MAIN ENTRANCE DOOR OPENERS 800 2400
55 1 20 (E)SIGN STATE ROAD 750 2400
57 1 20 (E)MASTER CLOCK 500 750 (E) LOAD 20 1 44
59 1 20 (E)FEEZER RECEPTACLE 1000 750 (E) LOAD 20 1 46
61 1 20 (E) LOAD 750 750 (E) LOAD 20 1 48
63 1 20 (E) LOAD 750 750 (E) LOAD 20 1 50
65 1 20 (E) LOAD 750 750 (E) LOAD 20 1 52
67 1 20 (E) LOAD 750 750 (E) LOAD 20 1 54
69 1 20 (E) LOAD 750 750 (E) LOAD 20 1 56
71 1 20 (E) LOAD 750 750 (E) LOAD 20 1 58
73 6000 750 (E) LOAD 20 1 60
75 6000 750 (E) LOAD 20 1 62
77 6000 3000
79 1 20 SPARE 0 3000
81 1 20 SPARE 0 0
83 1 20 SPARE 0 0
8610 9500 10200 14760 10110 14010
PHASE A: 23.37 kVA
PHASE B: 19.61 kVA
PHASE C: 24.21 kVA
TOTAL: 67.19 kVA
(E)CC-1
35 2
(E)CC-2 [NOT USED] 35 2
CIRCUIT
POLE
(E)CLAB PANEL1003
CKT
NO
(E)CLAB RTU 1 70 3
(E) LOAD 30
C A B C REMARKS AMP
NOTES: CIRCUIT BREAKERS SHOWN AS SHADED/GRAY ARE TO REPLACE EXISTING 2-
POLE CIRCUIT BREAKERS THAT WILL BE SPARE AFTER DEMOLITION. PROVIDE AND
INSTALL NEW 1-POLE CIRCUIT BREAKERS AS SHOWN, TO MATCH EXISTING TYPE AND
RATING TO MATCH EXISTING SQUARE D CIRCUIT BREAKERS.
LOCATION:
MAIL 109
PANEL SCHEDULE FOR EXISTING PANEL: "F" SECTION #2
120/208V, 3PH, 4W, 225A BUS,
225A MLO, 10,000A RMS
WITH FEED-THRU LUGS
RECESSED/FLUSH
MOUNTED
CKT
NO
CIRCUIT
POLE
AMP REMARKS A B
EQUIPMENT
NAME
V-Ф-Hz HP/VA/A WIRE AND CONDUIT
CIRCUIT
BREAKER
PANEL;CKT #(S)
STARTER/
DISCONNECT
FURNISHED BY MC,
INSTALLED BY EC
STARTER/
DISCONNECT
FURNISHED BY EC,
INSTALLED BY EC
THERMAL MOTOR
SWITCH
FURNISHED BY EC,
INSTALLED BY EC
REMARKS
CC-1 208-1-60 .4 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-2 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-3 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-4 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-5 208-1-60 .6 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-6 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-7 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-8 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-9 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-10 208-1-60 .4 MCA 3/4"C-2#12+1#12GND 2P-15A AM;7,9 - - UNIT MOUNT -
CC-11 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-12 208-1-60 .4 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-13 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-14 208-1-60 .4 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-15 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-16 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-17 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-18 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CC-19 208-1-60 .3 MCA 3/4"C-2#12+1#12GND 2P-15A AM;8,10 - - UNIT MOUNT -
CUH-6 120-1-60 .5 FLA 3/4"C-2#12+1#12GND 1P-15A AM;11 UNIT MOUNT - -
CUH-7 120-1-60 .5 FLA 3/4"C-2#12+1#12GND 1P-20A AM;11 UNIT MOUNT - -
DOAS-1 208-3-60 59.5 MCA 1"C-3#4+1#8GND 3P-70A AM;2,4,6 UNIT MOUNT - - UNIT PROVIDED WITH MANUFACTURER'S WIRED RECEPTACLE
EF-5 120-1-60 1/15 HP 3/4"C-2#12+1#12GND 1P-20A AM;12 UNIT MOUNT - - -
EF-6 120-1-60 1/6 HP 3/4"C-2#12+1#12GND 1P-20A AM;12 UNIT MOUNT - - -
EWH-1 120-1-60 12.5 A 3/4"C-2#12+1#12GND 1P-20A AM;22 UNIT MOUNT - - -
IHRU-2-1 208-1-60 1.9 A 3/4"C-2#12+1#12GND 2P-15A AM;13,15 - - UNIT MOUNT UNITS SERVED CC-1 TO CC-5
IHRU-2-2 208-1-60 1.9 A 3/4"C-2#12+1#12GND 2P-15A AM;13,15 - - UNIT MOUNT UNITS SERVED CC-6 TO CC-11
IHRU-2-3 208-1-60 1.9 A 3/4"C-2#12+1#12GND 2P-15A AM;13,15 - - UNIT MOUNT UNITS SERVED CC-12 TO CC-15
IHRU-2-4 208-1-60 1.9 A 3/4"C-2#12+1#12GND 2P-15A AM;13,15 - - UNIT MOUNT UNITS SERVED CC-16 TO CC-19
IWH-1A 120-1-60 29.2A 3/4"C-2#8+1#10GND 1P-40A AM;14 - - UNIT MOUNT -
IWH-1B 120-1-60 29.2A 3/4"C-2#8+1#10GND 1P-40A AM;16 - - UNIT MOUNT -
IWH-2A 208-1-60 39.9A 3/4"C-2#6+1#10GND 2P-50A AM;17,19 - - UNIT MOUNT -
IWH-2B 208-1-60 39.9A 3/4"C-2#6+1#10GND 2P-50A AM;18,20 - - UNIT MOUNT -
IWH-2C 208-1-60 39.9A 3/4"C-2#6+1#10GND 2P-50A AM;21,23 - - UNIT MOUNT
OHRU-2 208-3-60 64.2 MCA 1"C-3#4+1#8GND 3P-80A AM;1,3,5 - UNIT MOUNT - REFER TO DETAIL 3/E402
RCP-2 120-1-60 8.3 FLA 3/4"C-2#12+1#12GND 1P-20A AM;24 - - UNIT MOUNT -
MECHANICAL EQUIPMENT - ELECTRICAL DATA SCHEDULE
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP A B C A B C AMP POLE NO
1 7704 7140 2
3 7704 7140 4
5 7704 7140 6
7 420 420 8
9 420 420 10
11 1 15 CUH-6 AND CUH-7 60 768 EF-5 AND EF-6 20 1 12
13 912 3504 IWH-1A *40 1 14
15 912 3504 IWH-1B *40 1 16
17 2394 2394 18
19 2394 2394 20
21 2394 1500 EWH-1 20 1 22
23 2394 996 RCP-2 20 1 24
25 1 20 HVAC CONTROL PANEL 500 0 SPARE 20 1 26
27 1 20 SPARE 0 0 SPARE 20 1 28
29 1 20 SPARE 0 0 SPARE 20 1 30
31 1 20 SPARE 0 0 SPARE 20 1 32
33 1 20 SPARE 0 0 SPARE 20 1 34
35 1 20 SPARE 0 0 SPARE 20 1 36
37 1 20 SPARE 0 0 SPARE 20 1 38
39 1 20 SPARE 0 0 SPARE 20 1 40
41 1 20 SPARE 0 0 SPARE 20 1 42
11930 11430 12552 13458 12564 11298
PHASE A: 25.39 KVA
PHASE B: 23.99 KVA
PHASE C: 23.85 KVA
TOTAL: 73.23 KVA
SURFACE MOUNT
LOCATION:
UTILITY 113
REMARKS REMARKS
PANEL SCHEDULE FOR NEW PANEL: "AM"
208/120 V, 3PH, 4W, 225A BUS,
225A M.L.O. WITH DOUBLE LUGS, 10,000A RMS
3 80 70 3
IWH-2B *50 2
OHRU-2
152 CC-1 TO CC-10 CC-11 TO CC-19 15
DOAS-1
2 *50 IWH-2C
2 15 IHRU-2-1 TO IHRU-2-4
IWH-2A*502