2026-09-23 TESD - Bid Package 1- HVAC Renovations and Upgrades - Bid Issue - Electrical.pdf
PDF 1 MB Posted
- Attached to
- TESD Bid Package 1 - HVAC Renovations and Upgrades at BES, DES, NEES, VFMS, CHS & WVAB (Project # 26-016.01)
- Solicitation number
- US.254475
- Issued by
- Chester County, Pennsylvania
About this file
This electrical schedule document provides detailed specifications for HVAC renovation and upgrade work at six facilities for the Tredyffrin/Easttown School District (TESD), including Beaumont Elementary School (BES), Devon Elementary School (DES), New Eagle Elementary School (NEES), Valley Forge Middle School (VFMS), Conestoga High School (CHS), and West Valley Administration Building (WVAB). The document contains mechanical equipment electrical data schedules specifying equipment names, voltage ratings, wire and conduit requirements, circuit breaker panel assignments, starters/disconnects, and smoke detector quantities for numerous rooftop units (RTUs), air handling units (AHUs), exhaust fans (EFs), and other HVAC equipment across multiple facility locations. The schedules also detail panel configurations for various existing and new electrical panels (designated as PPN, GB, PP3-2, CS, LPMA, LPM, CM, CM1, PP-CR2, LGB, and PBR) with specified amperage ratings, bus configurations, and individual circuit allocations for mechanical equipment, lighting, receptacles, and other building systems. The project involves electrical work coordination including conduit and wiring extensions, fire alarm system modifications, control system integrations, and panel replacements to support the HVAC system upgrades.
The document serves as the electrical portion of the bid package specifications for Bid Package 1 with an electronic bid deadline of 2:00 P.M. on Tuesday, October 27, 2026, and bid opening on the PennBid website. Proposal guaranties of 10 percent are required for mechanical, electrical, plumbing, and general construction work. Plans and specifications became available on September 23, 2026, through the PennBid website at no cost. The electrical work outlined includes installation of new electrical panels with surge protection, equipment starters and disconnects, modifications to existing fire alarm circuits for duct smoke detectors, and extensive wiring and conduit work to support the mechanical equipment replacements and upgrades throughout the six school district facilities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIPMENT
NAME
V-Ф-Hz HP/WATTS/A WIRE AND CONDUIT
CIRCUIT
BREAKER
PANEL;CKT #(S)
STARTER/ DISCONNECT
BY MC/PC
INSTALLED BY EC
STARTER/ DISCONNECT
BY EC
SUPPLY
SMOKE
DETECTOR
QUANTITY
RETURN SMOKE
DETECTOR
QUANTITY
REMARKS
RTU-2 208-3-60 48 FLA 1"C-3#4+1#8GND 70/3 PPN;2,4,6 UNIT MOUNTED - - (1) EXISTING - RTU-3 208-3-60 28 FLA (E)3/4"C-3#6+1#10GND (E)50/3 PPN;1,3,5 UNIT MOUNTED - - (1) EXISTING SPLICE/EXTEND CONDUIT AND WIRING TO RTU AS NEEDED.
RTU-4 208-1-60 21 FLA 3/4"C-2#10+1#10GND 30/2 PPN;20,22 UNIT MOUNTED - - (1) EXISTING -
MECHANICAL EQUIPMENT - ELECTRICAL DATA SCHEDULE
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 SPACE - 1 18
19 20
21 22
23 (E)PANEL OUTLET 20 1 24
25 26
27 28
29 30
3 70 RTU-2 RTU-3 3
40 (E)AHU-1 GYM 3
3 20 (E)CU-3 FAC, STAFF LOUNGE
LOCATION: FIRST FLOOR
REMARKS REMARKS
PANEL SCHEDULE FOR PANEL: "PPN"
208/120 V, 3PH, 4W, 225A BUS,
225A M.L.O., 65,000A RMS
GE A SERIES
3 20 (E)UV-11, MUSIC RM
3 20
(E)UV-10, MUSIC RM
RTU-4 30
SPARE
(E)TEMP WELDER
SPARE 20
V-Ф-Hz HP/WATTS/A WIRE AND CONDUIT
CIRCUIT
BREAKER
PANEL;CKT #(S)
STARTER/ DISCONNECT
BY MC/PC
INSTALLED BY EC
STARTER/ DISCONNECT
BY EC
SUPPLY
SMOKE
DETECTOR
QUANTITY
RETURN
SMOKE
DETECTOR
QUANTITY
REMARKS
AHU-9 208-3-60 13.7 FLA 3/4"C-3#12+1#12GND 20/3 PP3-2;1,3,5 UNIT MOUNTED - - 1
DEMO DUCT SMOKE DETECTORS, MAINTAIN FIRE ALARM WIRING TO BE EXTENDED TO NEW DUCT SMOKE DETECTORS, RELOCATE ASSOCIATED IAM RELAYS AND REMOTE TEST SWITCHES.
AHU-10 208-3-60 13.7 FLA 3/4"C-3#12+1#12GND 20/3 PP3-2;8,10,12 UNIT MOUNTED - - 1 DEMO DUCT SMOKE DETECTORS, MAINTAIN FIRE ALARM WIRING TO BE EXTENDED TO NEW DUCT SMOKE DETECTORS, RELOCATE ASSOCIATED IAM RELAYS AND REMOTE TEST SWITCHES.
AHU-11 208-3-60 13.7 FLA 3/4"C-3#12+1#12GND 20/3 PP3-2;14,16,18 UNIT MOUNTED - (1) EXISTING - -
EF-5 208-3-60 7 FLA (E)3/4"C-3#12+1#12GND (E)20/3 GB;26,28,30 UNIT MOUNTED - - - SPLICE/EXTEND CONDUIT AND WIRING TO UNIT AS NEEDED.
EF-27-2 480-3-60 12.9 FLA 3/4"C-3#10+1#10GND 25/3 MCC2;2-2 UNIT MOUNTED - - -
REPLACE C/B IN MCC WITH SIEMENS MFG ED-FRAME 3P-25A C/B WITH LINE/LOAD LUGS RATED 65kA RMS MCC2;2-2.
PROVIDE MCC DISCONNECT WITH EARLY BREAK AUXILARY CONTACTS FOR VFD SHUTDOWN WITH AUXILARY 3/4"C-2#12
FROM VFD CONTACTS TO MCC2;2-2.
MECHANICAL EQUIPMENT - ELECTRICAL DATA SCHEDULE
1 2
3 4
5 (E) SPACE - 1 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 (E) GYM SECURITY LIGHTS 20 1 36
37 1 20 (E) MECHANICAL RM. RECS (E) ANDOVER CONTROL 20 1 38
39 1 20 (E) MECHANICAL RM. LIGHTS (E) UH 1&2 20 1 40
41 1 20 (E) MECHANICAL RM. LIGHTS EF-11 MECHANICAL RM 20 1 42
CIRCUIT
POLE
AMP
CKT
NO
CKT
NO
CIRCUIT
POLE
AMP
(E) WATER HEATER GIRLS LR
(E)AHU 5, SERVES GYM A
(E)AHU 6, SERVES LOCKER ROOMS
(E)AHU 7, SERVES WRESTLING ROOM
(E)AHU 8, SERVES GYM LOBBY AND STORAGE
(E) PANEL B-1
(E) WATER HEATER- BOYS LR
(E)EF-10, SERVES GIRLS LOCKER ROOM
(E)EF-9, SERVES BOYS LOCKER ROOM
(E)AHU 4, SERVES GYM A
(E) WATER HEATER-BOYS LR
EF-5/GIRLS LOCKER ROOM
SURFACE MOUNTED
LOCATION:
GYM MEZZANINE
REMARKS REMARKS
PANEL SCHEDULE FOR EXISTING PANEL: "GB"
208/120 V, 3PH, 4W, 400A BUS,
400A MLO
WESTINGHOUSE TYPE PRL3
30 2
1 (E)TRAINING RM WATER COOLER 20 1 2
3 (E)TRAINING RM WATER COOLER 20 1 4
5 (E)RECS ATHELTIC OFFICE 20 1 6
7 8
9 10
11 1 20 (E)RECS ATHELTIC OFFICE 12
13 1 20 (E)BATTING CAGE 14
15 1 20 SPARE 16
17 1 20 (E)SCOREBOARD 18
19 (E)DRYER #1 20 1 20
21 (E)REC LAUNDRY 20 1 22
23 (E)PUMP LAUNDRY 20 1 24
25 26
27 28
29 30
CIRCUIT
POLE
REMARKS
CKT
NO
AMP
LOCATION: 118
CKT
NO
PANEL SCHEDULE FOR EXISTING PANEL: "PP3-2"
120/208V, 3PH, 4W, 100A BUS,
100A MLO, 65,000A RMS
WESTINGHOUSE TYPE PRL1
RECESSED MOUNTED
CIRCUIT
POLE
AHU-11 GIRLS LOCKER ROOM 20
AHU-10 GYM B 20
REMARKS
AHU-9 GYM B
(E)PANEL "WT"
(E)GYM PARTITION
(E)DRYER #2
AMP
320(E)EF 6
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 1 20 SPARE SPARE 20 1 2
3 1 20 SPARE SPARE 20 1 4
5 1 20 SPARE SPARE 20 1 6
7 1 20 (E) WIREMOLD COMP.RM.245 (E) WIREMOLD COMP. RM 245 20 1 8
9 1 20 (E) WIREMOLD COMP.RM.245 (E) WIREMOLD COMP. RM 245 20 1 10
11 1 20 (E) WIREMOLD COMP.RM.245 (E) WIREMOLD COMP. RM 245 20 1 12
13 1 20 (E) RECEPT.COMP.RM 245 (E) WIREMOLD COMP. RM 245 20 1 14
15 1 20 (E) RECEPT. LIBRARY (E) WIREMOLD COMP. RM 245 20 1 16
17 1 20 (E) RECEPT. LIBRARY (E) WIREMOLD QUITE STUDY 247E 20 1 18
19 1 20 (E) RECEPT. LIBRARY (E) WIREMOOLD COMP. RM 245 20 1 20
21 1 20 (E) WIREMOLD A/V RM 245 (E) WIREMOOLD COMP. RM 245 20 1 22
23 1 20 (E) WIREMOLD A/V RM 245 (E) WIREMOOLD COMP. RM 245 20 1 24
25 1 20 (E) WIREMOLD A/V RM 245 (E) RECEPT. COMP. RM 245A PROJECTOR 20 1 26
27 1 20 (E) RECEPT 245 (E) RECEPT. COMP. RM 245 20 1 28
29 1 20 (E) RECEPT 245 (E) PROJECTOR 245B 20 1 30
31 1 20 (E) 245 (E) WIREMOLD A/V RM 245 20 1 32
33 1 20 (E)POWER POLE (E) WIREMOLD CONF./ CR 245 20 1 34
35 1 20 (E) COUNTER LIGHT QUADS (E) WIREMOLD CONF./ CR 245 20 1 36
37 1 20 (E) COUNTER QUAD RECPT SPARE 20 1 38
39 1 20 (E) TEMP LASER PRINTER QUAD SPARE 20 1 40
41 1 20 (E) TEMP LASER PRINTER DUPLEX PREPARED SPACE - 1 42
SURFACE MOUNTEDLOCATION: SGR 247B
REMARKS REMARKS
PANEL SCHEDULE FOR NEW PANEL: "CS"
120/208V, 3PH, 4W, 225A BUS
60A M.C.B, 22,000A RMS
INTEGRAL SURGE PROTECTION,
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 1 20 (E) LIBRARY CHANDELIER (1) (E) LIGHTING-LIBRARY READING 20 1 2
3 1 20 (E) LIBRARY CHANDELIER (2) (E) LIGHTING-LIBRARY READING 20 1 4
5 1 20 (E) LIBRARY CHANDELIER (2) (E) LIGHTING-LIBRARY READING 20 1 6
7 1 20 (E) LIBRARY ENTRY DISPLAY CASE (E) LIGHTING-LIBRARY READING 20 1 8
9 1 20 (E) LIGHTING LIBRARY OFFICE (E) LIGHTING - BOOKSTACKS 20 1 10
11 1 20 (E) LTG.-LIBRARY CENTER READ (E) LIGHTING - BOOKSTACKS 20 1 12
13 1 20 (E) LTG. -LIBRARY INFO.DESK (E) LIGHTING -COMP. RM 20 1 14
15 1 20 (E) LIGHTING - DARKROOM (E) LIGHTING A/V CR & CONE 20 1 16
17 1 20 (E) LIGHTING -PHOTO STUDIO (E) LIBRARY - CHANDELIER 20 1 18
19 1 20 (E) LIGHTING GALLERY LOBBY (E) EX. COURTYARD LIGHTS 20 1 20
21 1 20 (E) LIGHTING- CORRIDOR (E) GALLERY EXT. FLOODLIGHTS 20 1 22
23 1 20 SPARE SPARE 20 1 24
25 1 20 SPARE (E) CONTROL FOR EM INTERPHASE CKT 8 20 1 26
27 1 20 SPARE (E) OLD LIGHTS LIBRARY WALL 20 1 28
29 1 20 (E) SERVER RM A/C (E) VAV'S 1 THRU 11 20 1 30
31 SPARE 20 1 32
33 SPARE 20 1 34
35 1 20 SPARE SPARE 20 1 36
37 1 - PREPARED SPACE PREPARED SPACE - 1 38
39 1 - PREPARED SPACE PREPARED SPACE - 1 40
41 1 - PREPARED SPACE PREPARED SPACE - 1 42
LOCATION: ELEC 277
REMARKS REMARKS
PANEL SCHEDULE FOR NEW PANEL: "LPMA"
208/120 V, 3PH, 4W, 225A BUS,
225A M.L.O, 22,000A RMS
SURFACE MOUNTED
2 20 (E) IDF AC
1 1 20 SPARE (E) RECEPT. LIBRARY 247D 20 1 2
3 1 20 SPARE SPARE 20 1 4
5 1 20 SPARE SPARE 20 1 6
7 1 20 SPARE SPARE 20 1 8
9 1 20 SPARE (E) RECEPT. LIBRARY 247B 20 1 10
11 1 20 (E) RECEPT. LIBRARY 247B (E) BOOK SECURITY SENSORS 20 1 12
13 1 20 (E) COPIER (E) RECEPT. LIBRARY 247B 20 1 14
15 1 20 SPARE (E) RECEPT. LIBRARY 247D 20 1 16
17 (E) RECEPT. LIBRARY 247D 20 1 18
19 (E) COPIER 20 1 20
21 1 20 (E) RECEPT.LIBRARY 247C SPARE 20 1 22
23 1 20 (E) BOOK SECURITY SENSORS (E) RECEPT LIBRARY 246C 20 1 24
25 1 20 (E) RECEPT @ RTU-1 (E) EF-5 & MOD 20 1 26
27 1 20 (E) RECEPT @RTU-2 (E) MAIN FA PANEL 20 1 28
29 1 20 (E) TRI-M CARD READER (E) LIBRARY EXPANSION 247D RECEPT COLUMN 20 1 30
31 1 20 (E) EF-6 SERVER RM (E) LIBRARY EXPANSION 247D RECEPT COLUMN 20 1 32
33 1 20 (E) EF-8 MACH.RM 247E (E) LIGHTING RMS 247C, 247D 20 1 34
35 1 20 SPARE SPARE 20 1 36
37 1 - PREPARED SPACE PREPARED SPACE - 1 38
39 1 - PREPARED SPACE PREPARED SPACE - 1 40
41 1 - PREPARED SPACE PREPARED SPACE - 1 42
CKT
NO
CIRCUIT
POLE
AMP
LOCATION:
ELEC 277
REMARKS REMARKS
(E) COPIER202
PANEL SCHEDULE FOR NEW PANEL: "LPM"
208/120 V, 3PH, 4W, 225A BUS,
225A M.L.O, 22,000A RMS
CIRCUIT
POLE
SURFACE MOUNTED
CKT
NO
AMP
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 1 20 (E) SERVER 273 (E) FRIDGE/MICROWAVE 20 1 2
3 1 20 SPARE (E) RECEPT SERVER 273 20 1 4
5 1 20 (E) RECEPT SERVER 273 (E) RECEPT SERVER 273 20 1 6
7 1 20 SPARE (E) RECEPT SERVER 273 20 1 8
9 1 20 (E) RECEPT. LIBRARY (E) WIREMOLD PHOTO CR 201 20 1 10
11 1 20 (E) WIREMOLD PHOTO CR 201 (E) WIREMOLD PHOTO CR 201 20 1 12
13 1 20 (E) WIREMOLD PHOTO CR 201 (E) WIREMOLD PHOTO CR 201 20 1 14
15 1 20 (E) WIREMOLD LIBRARY 247D (E) WIREMOLD PHOTO CR 201 20 1 16
17 1 20 (E) WIREMOLD LIBRARY 247D (E) WIREMOLD PHOTO CR 201 20 1 18
19 1 20 (E) WIREMOLD LIBRARY 247D (E) WIREMOLD LIBRARY 247D 20 1 20
21 1 20 (E) RECEPT. LIBRARY 274B (E) RECEPT. LIBRARY 274D 20 1 22
23 1 20 (E) RECEPT. LIBRARY 274B (E) RECEPT. LIBRARY 274D 20 1 24
25 1 20 (E) RECEPT. LIBRARY 274B (E) RECEPT. LIBRARY 274D 20 1 26
27 1 20 (E) RECEPT. LIBRARY 274B (E) RECEPT. LIBRARY 274D 20 1 28
29 1 20 (E) RECEPT. LIBRARY 274B (E) RECEPT. LIBRARY 274D 20 1 30
SURFACE MOUNTEDLOCATION: IDF 273A
REMARKS REMARKS
PANEL SCHEDULE FOR NEW PANEL: "CM"
208/120 V, 3PH, 4W, 225A BUS,
225A M.C.B., 22,000A RMS
INTEGRAL SURGE PROTECTION, FEED THRU LUGS
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
31 1 20 (E) RECEPT. LIBRARY 247B (E) WIREMOLD LIBRARY 247C 20 1 32
33 1 20 (E) RECEPT. LIBRARY 247 (E) WIREMOLD LIBRARY 247C 20 1 34
35 1 20 SPARE (E) WIREMOLD LIBRARY 247C 20 1 36
37 1 20 (E) RECEPT. LIBRARY 247B (E) RECEPT SERVER 247B 20 1 38
39 1 20 (E) RECEPT. LIBRARY 247B (E) RECEPT SERVER 247B 20 1 40
41 1 20 (E) RECEPT. LIBRARY 247B (E) RECEPT SERVER 247B 20 1 42
43 1 20 (E) RECEPT. LIBRARY 247B (E) RECEPT SERVER 247B 20 1 44
45 1 20 (E) RECEPT. LIBRARY 247B (E) RECEPT SERVER 247B 20 1 46
47 1 20 (E) HELP DESK (E) RECEPT SERVER 247B 20 1 48
49 1 20 (E) HELP DESK (E) IDF RECEPTACLE BY RACK 20 1 50
51 1 20 EXISTING LOAD SPARE 20 1 52
53 1 20 SPARE SPARE 20 1 54
55 1 20 SPARE SPARE 20 1 56
57 1 - PREPARED SPACE PREPARED SPACE - 1 58
59 1 - PREPARED SPACE PREPARED SPACE - 1 60
61 1 - PREPARED SPACE PREPARED SPACE - 1 62
63 1 - PREPARED SPACE PREPARED SPACE - 1 64
65 1 - PREPARED SPACE PREPARED SPACE - 1 66
67 1 - PREPARED SPACE PREPARED SPACE - 1 68
69 1 - PREPARED SPACE PREPARED SPACE - 1 70
71 1 - PREPARED SPACE PREPARED SPACE - 1 72
SURFACE MOUNTED
LOCATION: LIBRARY IDF
2ND FLOOR
REMARKS REMARKS
PANEL SCHEDULE FOR NEW PANEL: "CM1"
208/120 V, 3PH, 4W, 225A BUS,
225A MLO, 22,000A RMS
V-Ф-Hz HP/WATTS/A WIRE AND CONDUIT
CIRCUIT
BREAKER
PANEL;CKT #(S)
STARTER/ DISCONNECT
BY MC/PC
INSTALLED BY EC
STARTER/ DISCONNECT
BY EC
SUPPLY
SMOKE
DETECTOR
QUANTITY
RETURN
SMOKE
DETECTOR
QUANTITY
REMARKS
RTU-2E 208-3-60 48 FLA 1"C-3#4+1#8GND 70/3 PP-CR2;1,3,5 UNIT MOUNTED - - (1) RELOCATE PROVIDE NEW SAMPLING TUBE FOR (REL) DUCT DETECTOR.
MECHANICAL EQUIPMENT - ELECTRICAL DATA SCHEDULE
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 2
3 4
5 6
7 1 20 (E)OUTSIDE RECEPT BY RTU-2E SPACE - 1 8
9 1 20 (E)HVAC RM SUMP PUMP RECEPT (E)LARGE GROUP ROOM PROJECTOR 15 1 10
11 1 20 (E)HVAC ROOM SPARE (IN SUMP BOX) SPACE - 1 12
30 3RTU-2E LARGE GROUP RM703
LOCATION: LARGE GROUP
STORAGE
REMARKS REMARKS
PANEL SCHEDULE FOR EXISTING PANEL: "PP-CR2"
208/120 V, 3PH, 4W, 225A BUS,
125A M.L.O.
GE SERIES A
SPARE
V-Ф-Hz HP/WATTS/A WIRE AND CONDUIT
CIRCUIT
BREAKER
PANEL;CKT #(S)
STARTER/ DISCONNECT
BY MC/PC
INSTALLED BY EC
STARTER/ DISCONNECT
BY EC
SUPPLY
SMOKE
DETECTOR
QUANTITY
RETURN
SMOKE
DETECTOR
QUANTITY
REMARKS
CC-1 208-1-60 - 3/4"C-3#12+1#12GND - - - - - - WIRED TO HP-1
HP-1 208-1-60 14.6 MCA 3/4"C-2#12+1#12GND 15/2 LGB; 28,30 - WALL MOUNT - - -
HV-1 208-3-60 8 FLA 3/4"C-3#12+1#12GND 15/3 PBR;17,19,21 UNIT MOUNTED - - 1 -
MECHANICAL EQUIPMENT - ELECTRICAL DATA SCHEDULE
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 1 20 EXISTING LOAD EXISTING LOAD 20 1 2
3 1 20 EXISTING LOAD EXISTING LOAD 20 1 4
5 1 20 (E)SCORE BOARD EXISTING LOAD 20 1 6
7 1 20 EXISTING LOAD EXISTING LOAD 20 1 8
9 1 20 SPARE SPARE 20 1 10
11 1 20 EXISTING LOAD SPARE 20 1 12
13 1 20 SPARE (E)LIGHTS 20 1 14
15 1 - SPACE (E)LIGHTS 20 1 16
17 1 - SPACE (E)LIGHTS 20 1 18
19 1 - SPACE SPACE - 1 20
21 1 - SPACE SPACE - 1 22
23 1 30 EXISTING LOAD SPACE - 1 24
25 EXTERIOR RECEPTACLE AT CU 20 1 26
27 28
29 30
LOCATION:
BOY'S GYMNASIUM
REMARKS REMARKS
PANEL SCHEDULE FOR EXISTING PANEL: "LGB"
208/120 V, 3PH, 4W, 100A BUS,
100A M.L.O., 65,000A RMS
EASTCOAST PANELBOARD WITH SIEMENS C/B
(E)GYM ROOF TOP UNIT RTU-1535
CC-1/HP-1 GYM OFFICE 15
CKT CIRCUIT CIRCUIT CKT
NO POLE AMP AMP POLE NO
1 1 20 (E)HALLWAY CHARGER RECEPTACLE SPARE 20 1 2
3 1 20 SPARE (E)RECEPT THIS ROOM 20 1 4
5 1 20 (E)HALLWAY CHARGER RECEPTACLE 6
7 1 20 SPARE 8
9 1 - SPACE 10
11 1 - SPACE SPACE - 1 12
13 1 - SPACE SPACE - 1 14
15 1 - SPACE SPACE - 1 16
17 SPACE - 1 18
19 SPACE - 1 20
21 SPACE - 1 22
23 1 - SPACE 24
25 1 - SPACE 26
27 1 - SPACE SPACE - 1 28
29 SPACE - 1 30
31 SPACE - 1 32
33 SPACE - 1 34
35 1 - SPACE SPACE - 1 36
37 1 - SPACE SPACE - 1 38
39 1 - SPACE SPACE - 1 40
41 1 - SPACE SPACE - 1 42
(E)WELDING RECEPTACLE 30 2
HV-1 BOYS LOCKER ROOM TEAM ROOM153
(E)H & V UNIT - ROOM 17203
LOCATION: BASEMENT
MECHANICAL ROOM
REMARKS REMARKS
PANEL SCHEDULE FOR EXISTING PANEL: "PBR"
208/120 V, 3PH, 4W, 225A BUS,
225A M.L.O., 65,000A RMS
EASTCOAST PANELBOARD WITH SIEMENS C/B
(E)H & V UNIT - ROOM 42 KITCHEN 20 3