About this file

This document contains system specifications for an uninterruptible power supply (UPS) system procured by Jackson County for their 911 Call Center. The specification details a 93PM UPS system with a 60kW frame capacity and 20kW power rating, featuring two 20kW power modules configured with internal redundancy and internal battery configuration. The system operates on 208V or 220V, 4-wire input with 208V or 220V, 3 or 4-wire output capability. The UPS unit measures 74" x 35" x 42" and weighs 639 pounds, with an associated IBC-SW battery cabinet measuring 74" x 42" with 16.7-inch width and weighing 2,159 pounds. The battery system, manufactured by Eaton, is configured as a single cabinet with single string and provides an estimated runtime of 51 minutes at 77 degrees Fahrenheit. The combined matching system dimensions are 74" x 68" x 42".

The specification includes a 3-breaker sidecar with standard, MBS, and BIB monitored brake rating capabilities, an industrial gateway card, industrial relay card, top air exhaust configuration, and energy storage system (ESS) capability. A raised floor stand is required for both the UPS and battery cabinets. The system is not OSHPD rated, and battery installation will be performed on a line and match basis. No other pricing terms, set-asides, incumbent information, or funding sources are specified in this technical specification document.

View the file

Other files

File Type Posted
260011_ UPS for 911 and Data Center.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ENG Group, Inc.

ENG Group

UPM 1UPM 2

General Information: 93PM UPS

93PM System Specifications System Voltage: 208V or 220V 4 wire in, 208 or

220V 3 or 4 wire out UPS Frame Capacity: 60kW

Quantity of 20kW Power Modules: 2 UPS kW Rating: 20 Internal Redundant Configuration: Yes Internal Battery Configuration: Internal Batteries Input Feed: Single Feed ESS Included: Yes Communication: Industrial Gateway Card, Industrial

Relay Card, and EMP Accessories: None

Side Car: 3 Breaker Sidecar MBS Side Car Breaker Rating: Standard, MBS & BIB Montiored Exhaust Configuration: Top Air Exhaust Internal Estimated Runtime: No Internal Batteries UPS Dimensions (H" x W" x D"): 74 x 35 x 42 UPS Weight (lbs): 639

UPS System Dimensions

93PM Battery Cabinet Battery Cabinet: IBC-SW DC Voltage: 480 Battery Cabinet Weight (lbs): 2159 Battery Cabinet Width (in): 16.7 74" H x 42" D kW for Runtime Calculation: 20 Estimated Runtime (min) at 77 degrees F:

# of Cabinets/Strings: 1/1 Battery Manufacturer: Eaton Battery Installation: Line and Match OSHPD Rated: No

Combined Matching System Dimensions (H" x W" x D", excluding non-matching 74 x 68 x 42 matching panels):

UPS Accessories Floor Stand: Provide raised floor stand for UPS & battery cabinets.