2026-05-28_TILLAMOOK_COUNTY_COURTHOUSE_FOR BID - DRAWINGS.pdf
PDF 2 MB Posted
- Attached to
- Invitation to Bid for roofing project
- Solicitation number
- S-C00290-00017138
- Issued by
- Tillamook County, Oregon
About this file
This is a set of architectural drawings for a roofing project at the Tillamook County Courthouse, prepared for a competitive bidding process by Tillamook County, Oregon. The project consists of a comprehensive roofing renewal of the existing in-service low-slope roofing assembly using an adhered system. Sealed bids are to be submitted to the Tillamook County Board of Commissioners' Office, attention Isabel Gilda, at 201 Laurel Avenue, Tillamook, Oregon 97141. The drawings serve as the technical documentation required for bidders to develop accurate proposals for the roofing replacement work.
The contract is subject to Oregon's prevailing wage law (ORS 279C.800 to 279C.870), and bidders are not required to be pre-qualified under ORS 279b.120. Complete project documents are available for review at oregonbuys.gov/bso. These architectural drawings provide the detailed specifications and site conditions necessary for contractors to assess the scope of work and submit competitive bids for the courthouse roofing renewal project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES - PROJECT
1.
2.
3.
4.
5.
6.
A.
B.
C.
D.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
ALL WORK IS TO COMPLY WITH CODES LISTED IN THE CODE SUMMARY TABLE ON THIS SHEET
CLASSIFICATION OF WORK:
LEVEL 2 CLASSIFICATION OF WORK
THE CONTRACTOR IS RESPONSIBLE TO CHECK THE PLANS AND IS TO NOTIFY THE ARCHITECT OF ANY
CONFLICTING INFORMATION PRIOR TO THE START OF CONSTRUCTION.
WRITTEN DIMENSIONS HAVE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE
DRAWINGS. WHERE DIMENSIONS IN DRAWINGS DIFFER FROM EXISTING CONDITIONS. NOTIFY
ARCHITECT FOR CLARIFICATION OF DETAILING ADJUSTMENT FROM TO PROCESSING WITH WORK
HANDRAILS ARE REQUIRED ON ALL INTERIOR OR EXTERIOR STAIRS, UNO.
COLUMN DIMENSIONS ARE AS FOLLOWS:
COLUMNS: TO CENTERLINE OF COLUMN
WOOD WALLS: FACE OF FRAMING UNLESS NOTED OTHERWISE
CONCRETE: FACE OF FINISHED CONCRETE
FLOORS: FINISHED FLOOR ELEVATION (FFE)
READ DRAWINGS IN CONJUNCTION WITH PROJECT MANUAL(SPECIFICATIONS).
DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON SITE.
DRAWINGS HAVE BEEN PRODUCED FROM AVAILABLE RECORD DOCUMENTS AND LIMITED FIELD
OBSERVATION. CONTRACTOR TO BRING DISCREPANCIES BETWEEN CERTA DOCUMENTS AND ACTUAL
PROJECT CONDITIONS TO THE IMMEDIATE ATTENTION OF THE ARCHITECT / CONSULTANT AND
REQUEST A REVIEW WHEN DISCREPANCIES ARE DISCOVERED.
EXECUTION OF THE CONTRACT BY THE CONTRACTOR IS A REPRESENTATION THAT THE CONTRACTOR HAS VISITED THE SITE, BECOME GENERALLY FAMILIAR WITH THE LOCAL CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND CORRELATED PERSONAL OBSERVATIONS WITH REQUIREMENTS
OF THE CONTRACT DOCUMENTS.
CONTRACT DRAWINGS ARE COMPLIMENTARY, AND WHAT IS REQUIRED BY ANY ONE SHALL BE BINDING AS IF REQUIRED BY ALL. BEFORE STARTING EACH PORTION OF THE WORK, CAREFULLY STUDY AND COMPARE THE VARIOUS DRAWINGS AND OTHER CONTRACT DOCUMENTS RELATIVE TO THAT PORTION OF THE WORK, AS WELL AS INFORMATION FURNISHED BY OWNER. TAKE FIELD MEASUREMENTS OF ANY EXISTING CONDITIONS RELATED TO THAT PORTION OF THE WORK AND OBSERVE CONDITIONS AT
THE SITE AFFECTING IT. THESE OBLIGATIONS ARE FOR THE PURPOSE OF FACILITATING
CONSTRUCTION BY THE CONTRACTOR AND NOT FOR THE PURPOSE OF DISCOVERING ERRORS,
OMISSIONS, OR INCONSISTENCIES IN THE CONTRACT DOCUMENTS; HOWEVER, REPORT ERRORS,
OMISSIONS, OR INCONSISTENCIES DISCOVERED BY THE CONTRACTOR PROMPTLY TO THE
CONSULTANT AS A REQUEST FOR INTERPRETATION IN THE FORM PROVIDED IN THE PROJECT MANUAL.
REPETITIVE FEATURES, REGARDLESS OF ORIENTATION, NOT SHOWN ON DRAWINGS SHALL BE
COMPLETELY PROVIDED AS IF DRAWN IN FULL.
REPORT DISCREPANCIES IN CONTRACT DOCUMENTS TO ARCHITECT / CONSULTANT FOR
CLARIFICATION PRIOR TO COMMENCING WORK.
IMMEDIATELY NOTIFY ARCHITECT/ CONSULTANT UPON DISCOVERY OF ADDITIONAL UNFORESEEN
DAMAGE TO EXISTING CONSTRUCTION SCHEDULED TO REMAIN AND THAT IS OUTSIDE THE CONTRACT.
REQUEST A REVIEW. DO NOT COMMENCE RELATED WORK TO NEARBY WORK WITHOUT CONSULTANT
APPROVAL.
TRADE CONTRACTORS ARE RESPONSIBLE, FOR THE LAYOUT OF THEIR OWN WORK, AND TO SEE THAT THEIR WORK COMES TOGETHER WITH THAT OF OTHERS WITH THE DESIGN INTENT IDENTIFIED IN THE
DOCUMENTS. REPORT DISCREPANCIES ON DRAWINGS TO CONSULTANT FOR DECISIONS.
TRADE CONTRACTORS MUST ASSURE THEMSELVES THAT THEY HAVE THE LATEST DRAWINGS ISSUED
FOR CONSTRUCTION THE GENERAL CONTRACTOR IS TO MAINTAIN A WORKING SET IN THE
CONTRACTOR SITE OFFICE AND MAKE IT AVAILABLE FOR SUB-CONTRACTOR USE.
EMPLOY ORIGINAL JOURNEYMAN TRADESMAN OR ORIGINAL INSTALLERS OF NEW WORK TO PERFORM
CUTTING AND PATCHING OF NEW WORK. (IF APPLICABLE)
ALL RECONSTRUCTED WALLS TO MATCH (E) STUD FRAMING SIZING, SPACING, AND ANCHORING
PATTERNS, VERIFY EACH IS CONSISTENT WITH THE ORIGINAL DESIGN DOCUMENTS.
ALL REPAIRED, EXPOSED INSULATION IS TO HAVE A FLAME SPREAD RATING OF LESS THAN 25 AND A
SMOKE DENSITY RATING OF LESS THAN 450.
HANDRAILS ARE REQUIRED ON ALL INTERIOR OR EXTERIOR STAIRS, U.N.O. NOTIFY CONSULTANT IF
FOUND TO BE MISSING.
EXISTING BUILDING HEIGHT AND AREAS ARE NOT TO BE CHANGED.
EXISTING EMERGENCY LIGHTING AND EXIT PATHS TO BE MAINTAINED.
ABBREVIATIONS:
AL. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
BLDG. BUILDING
BOT. BOTTOM
COL. COLUMN
C.M.U. CONCRETE MASONRY UNIT
CONC. CONCRETE
CONT. CONTINUOUS
CONSTR. CONSTRUCTION
C/W COMPLETE WITH
DIA. DIAMETER
DIM. DIMENSION
DWG. DRAWING
D.S. DOWNSPOUT
EA. EACH
EL. ELEVATION
ELEC. ELECTRICAL
EQ. EQUAL
EQUIP. EQUIPMENT
EXIST. EXISTING
EXT. EXTERIOR
F.C. FIBER CEMENT
F.D. FLOOR DRAIN
FIN. FINISH
F.R.T.W. FIRE-RETARDANT TREATED WOOD
FURR FURRING OR FURRED
GA. GAUGE
GALV. GALVANIZED
G.W.B. GYPSUM WALL BOARD
GYP. GYPSUM
HORIZ. HORIZONTAL
INT. INTERIOR
INSUL. INSULATION
MAX. MAXIMUM
MEMB. MEMBRANE
MIN. MINIMUM
MISC. MISCELLANEOUS
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O.C. ON CENTER
PLY PLYWOOD
OSB ORIENTED STRAND BOARD
P.T. PRESSURE TREATED
POLY. POLYETHYLENE
R RADIUS
REF. REFERENCE
REINF. REINFORCED
REQ'D REQUIRED
REV. REVERSED
R.D. ROOF DRAIN
R.W.A. RAINWATER LEADER
S.A.M. SELF ADHERED MEMBRANE
SEAL. SEALANT
SECT. SECTION
SIM. SIMILAR
SPEC. SPECIFICATION
S.O.G. SLAB-ON-GRADE
SST STAINLESS STEEL
STRUC. STRUCTURAL
T&G TONGUE AND GROOVE
T.B.A. TO BE CONFIRMED
TEMP. TEMPERATURE
T.O.W. TOP OF WALL
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
W/ WITH
W/O WITHOUT
W.R.B. WEATHER-RESISTIVE BARRIER
& AND
@ AT
# NUMBER / POUNDS
± PLUS OR MINUS
L ANGLE
ENCLOSURE COMPONENT GENERAL NOTES:
1.
2.
1.
2.
3.
4.
1.
2.
3.
MEMBRANE INSTALLATION:
CLEAN AND PREPARE SURFACE PRIOR TO INSTALLATION OF ALL MEMBRANES IN ACCORDANCE TO
MANUFACTURERS' RECOMMENDATIONS OR AS DIRECTED BY CONSULTANT. APPLY PRIMERS TO
ACHIEVE FULL ADHESION.
PROVIDE SADDLE FLASHING AT INTERSECTIONS AT BALCONY/ROOF PARAPET AND WALL; BALCONY
EDGE TO WALL AND ALL SIMILAR TYPE TRANSITIONS THAT MAY OCCUR WITHIN THE BUILDING
ENVELOPE ASSEMBLIES.
METAL FLASHING:
FORM JOINTS ARE TO BE S-LOCK OR STANDING SEAMS UNLESS OTHERWISE APPROVED; FORM
INTERNAL & EXTERNAL CORNERS IN METAL FLASHINGS WITH JOINT ASSEMBLY SHOWN IN
DRAWINGS.
TERMINATE METAL FLASHINGS WITH UPFOLDED 1/2 IN. HIGH END DAMS OR KICKERS.
INSTALL METAL HEAD FLASHINGS WITH UPFOLDED END DAMS OVER WINDOWS AND DOORS.
EXTEND FLASHING AS DETERMINED BY CONSULTANT. CONTRACTOR TO FIELD VERIFY THAT METAL
HEAD FLASHING DOES NOT INTERFERE WITH OPERATION OF WINDOWS, DOORS OF ACCESS
PANELS
FORM FLASHINGS WITH 15° SLOPE TO DRAIN U.N.O.
EXTERIOR OPENINGS AND PENETRATIONS:
NO CONCERTED EFFORT HAS BEEN MADE BY CONSULTANT TO QUANTIFY THE EXTERIOR FIXTURES, SUCH AS LIGHT FIXTURES, CONVENIENCE RECEPTACLES, EXHAUST VENTS, PIPE PENETRATIONS, HOSE BIBS, ELECTRICAL OR METERS, ETC. CONTRACTOR SHALL PERFORM OWN QUANTITY
SURVEY.
INSTALL SEALANT JOINT WITH BACKER ROD AROUND INTERIOR PERIMETER OF OPENINGS FOR AIR
BARRIER CONTINUITY.
FORM EXTERIOR PERIMETER SEALANT JOINTS 3/8 IN. WIDE WITH CLOSED CELL BACKER ROD U.N.O.
MAINTAIN JOINT WIDTH:DEPTH RATIO OF 2:1.
REFERENCE SYMBOLS / LEGEND
DELTA REVISION INDICATOR
CLOUD AROUND REVISION
BUILDING SECTION
CBS-000
SIM
CBS-000
CBS-000
SIM
SECTION DETAIL NUMBER
DRAWING NUMBER
WHERE DRAWING IS
REFERENCED
DETAIL
NUMBER
SHEET
NUMBER
DETAIL REFERENCE(S)
DETAIL TITLE
1/4" = 1'-0" 1
DETAIL
NUMBER
TITLE REFERENCE
DRAWING NUMBER
WHERE DETAIL IS DRAWN
REVISION CLOUD
N
PROJECT NORTH ARROW
(DIRECTION USER DEFINED)
NORTH
BATT INSULATION
(EXISTING SHOWN)
EXISTING CONSTRUCTION
SCHEDULED TO REMAIN
GYPSUM SHEATHING
CONTINUOUS SEALANT BEAD
SEALANT APPLICATION OVER
BACKER ROD
INTERMITTENT SOLID LUMBER
CONTINUOUS SOLID LUMBER
DRAWING TERMS:
A.
B.
C.
D.
E.
F.
G.
H.
DEMOLISH: COMPLETELY REMOVE AND LEGALLY DISPOSE OF OFF-SITE.
NEW (ITEM): A TERM USED ON DRAWINGS TO INDICATE THAT AN ITEM IS PROVIDED AS NEW WORK.
ASSUME ALL WORK NOT NOTED AS EXISTING IS NEW UNLESS ADDRESSED BY ALLOWANCES AND/OR
ALTERNATES.
PROTECT (ITEM): A TERM USED ON DRAWINGS TO INDICATE AN ITEM REQUIRES PROTECTION FROM
THE WORK.
REMOVE (ITEM): A TERM USED ON DRAWINGS TO INDICATE A SPECIFIC ITEM TO BE DETACHED
FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSED OF OFF-SITE, UNLESS INDICATED
OTHERWISE TO BE REMOVED, SALVAGED, AND REINSTALLED.
REMOVE AND REINSTALL (ITEM): A TERM USED ON DRAWINGS TO INDICATE A SPECIFIC ITEM TO BE DETACHED FROM EXISTING CONSTRUCTION, PREPARED FOR REUSE, AND REINSTALLED BACK IN ITS
EXISTING LOCATION.
RELOCATE (ITEM): A TERM USED IN DRAWINGS TO INDICATE AN EXISTING ITEM THAT HAS BEEN
REMOVED, AND TO BE REINSTALLED IN A NEW LOCATION.
SALVAGE (ITEM): CAREFULLY DETACH FROM EXISTING CONSTRUCTION, IN A MANNER TO PREVENT
DAMAGE READY FOR REUSE. INCLUDE FASTENERS OR BRACKETS NEEDED FOR REATTACHMENT IN
ORIGINAL LOCATION OR ELSEWHERE.
(E) OR EXISTING TO REMAIN (ITEM): A TERM USED ON DRAWINGS TO INDICATE EXISTING ITEMS OF
CONSTRUCTION THAT ARE NOT BE REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE
REMOVED, SALVAGED, OR REMOVED AND REINSTALLED. EXISTING TO REMAIN IS INDICATED BY
GRAPHIC LINETYPE SYMBOL.
DELTA REVISION INDICATOR
CLOUD AROUND REVISIONPRIMARY SCOPE ELEMENTS & GENERAL CONDITIONS
• NO DEFERRED SUBMITTALS OR DELEGATED DESIGN ELEMENTS ARE ANTICIPATED
DEFERRED SUBMITTALS
CODE SUMMARY
CONSTRUCTION TYPE:
TYPE II-B, PER 2025 OSSC TABLE 601
STRUCTURE ORIGINALLY CONSTRUCTED CIRCA 1932. ASSUMED TO BE CONSTRUCTED PER THE
1930 EDITION OF THE ICBO / UNIFORM BUILDING CODE WITH LOCAL AMENDMENTS
OCCUPANCY CLASSIFICATION:
MIXED OCCUPANCY: ASSEMBLY A-3 (OSSC SECTION 303.4), BUSINESS B (OSSC SECTION 304)
ACCESSORY OCCUPANCY: INSTITUTIONAL GROUP I-3 (OSSC SECTION 308.4)
FIRE DETECTION AND SUPPRESSION:
EXISTING SMOKE DETECTION AND FIRE ALARM SYSTEMS TO REMAIN IN-SERVICE.
NFPA 13
EGRESS:
EXISTING PATHWAYS TO THE PUBLIC WAY TO REMAIN IN-SERVICE AND UNOBSTRUCTED
THROUGHOUT THE COURSE OF THE WORK.
PARKING:
NO CHANGE
BUILDING FOOTPRINT:
NO CHANGE
PROJECT TEAM
PHONE:
CONTACT:
EMAIL:
TILLAMOOK COUNTY COURTHOUSE
201 LAUREL AVENUE
TILLAMOOK, OR 97141
503-842-3404
RACHEL HAGERTY, CHIEF OF STAFF
rachel.hagerty@tillamookcounty.gov
PHONE:
CONTACT:
EMAIL:
ARCHITECT:
CERTA BUILDING SOLUTIONS
2715 SE 8TH AVE, SUITE 100
PORTLAND, OR 97202
888-952-3787
DAN RUNDLE
DRUNDLE@CERTASOLUTIONS.COM
DAN RUNDLE
ARCHITECT
OWNER
TAX LOT NO: 1S0930BC 02900
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
GENERAL CONDITIONS:
PROJECT MOBILIZATION SHALL INCLUDE ALL CONTRACTOR AND SUBCONTRACTOR MOBILIZATION
COSTS.
PROJECT GENERAL REQUIREMENTS AND ALL MISCELLANEOUS COSTS ASSOCIATED WITH THE
COMPLETION OF THE WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, DEMOLITION AND DISPOSAL;
WATER DAMAGE REMEDIATION; CLADDING REHABILITATION OR REPLACEMENT AS APPLICABLE;
WINDOW REHABILITATION AS APPLICABLE; ROOF REHABILITATION; AND PROJECT CLEAN UP.
CARRY PRICING FOR APPROPRIATE SITE SUPERVISION, PROJECT MANAGEMENT, OFFICE SERVICES, ON-SITE TEMPORARY OFFICE, MATERIAL STORING AND STAGING, FULL-TIME WEATHER PROTECTION, SCAFFOLDING, STAGING AND ACCESS, TEMPORARY SHORING, TEMPORARY FENCING SAFEGUARDS, PEDESTRIAN PROTECTION, WORK FACILITIES, CONSTRUCTION OFFICES, UTILITY COST, SECURITY
SUBMITTALS, RFI ’S, MOCK-UPS, PROJECT PROGRESS MEETINGS, RECORD DRAWINGS, ETC.
THE CONTRACTOR SHALL PROVIDE AFTER-HOURS AND WEEKEND SECURITY TO GUARD
CONSTRUCTION AT THE CONTRACTORS COST AND DISCRETION.
CONTRACTOR SHALL PROVIDE AN ORGANIZATIONAL CHART WITH THE PROPOSAL FOR STAFFING THE PROJECT. STAFFING MUST INCLUDE A PROJECT MANAGER, A SITE SUPERINTENDENT, AND AT LEAST
ONE FULL-TIME QUALITY CONTROL INSPECTOR.
CARRY ALLOWANCES FOR APPLICABLE TRADE PERMITS AND CGL INSURANCE.
LIMITED TRADE WORK WILL REQUIRE PERMITS. ALL SUCH WORK SHALL BE DONE UNDER PERMITS AS
REQUIRED BY THE CITY OF TILLAMOOK. INCLUDE ALL COST NECESSARY FOR SUBMISSION
DOCUMENTS REQUIRED TO PERMIT AND COMPLETE THIS PROJECT INCLUDING ALL NECESSARY AS- BUILTS, SHORING AND SURVEYS. PERMITS ARE EXPECTED TO BE REQUIRED FOR EACH INDIVIDUAL BUILDING (AS OPPOSED TO A SINGLE PERMIT FOR THE ENTIRE PROJECT) AND COSTS ARE TO BE
CARRIED AS SUCH.
CONTRACTOR SHALL MAINTAIN ALL INSURANCE COVERAGES IDENTIFIED IN THE CONTRACT.
EVERY EFFORT SHALL BE MADE BY THE CONTRACTOR TO NOT RELOCATE OCCUPANTS DURING THE DURATION OF THE CONSTRUCTION. CONTRACTOR IS RESPONSIBLE TO MAINTAIN FULL ACCESS TO
THE BUILDING DURING THE WORK UNLESS SPECIFICALLY APPROVED BY THE OWNER.
IT WILL BE THE CONTRACTOR ’S RESPONSIBILITY TO KEEP THE ENTIRE JOBSITE SAFE AND CLEAN
DURING THIS CONSTRUCTION. DAILY CLEAN-UP WILL BE REQUIRED THROUGHOUT THE
CONSTRUCTION PERIOD.
CONTRACTOR TO SUPPLY ALL DUMPSTERS AND DUMP FEES NECESSARY TO COMPLETE PROJECT.
ALL SUBCONTRACTOR CONTRACTS MUST BE SIGNED AND IN EFFECT PRIOR TO THE START OF
CONSTRUCTION. PROOF OF EXECUTED SUBCONTRACTOR AGREEMENTS SHALL BE PRESENTED BY
THE CONTRACTOR TO THE ASSOCIATION PRIOR TO ANY CONSTRUCTION OR STAGING TAKING PLACE.
UPON REINSTATEMENT OF PERMANENT STRUCTURAL LOAD SYSTEMS, REMOVE AND DISPOSE OF ANY
TEMPORARY SHORING MATERIALS IN PLACE PRIOR TO OR USED DURING THE COURSE OF
CONSTRUCTION PER LOCAL REQUIREMENTS.
PROVIDE ALL NECESSARY STAGING, HOARDING, AND WEATHER PROTECTION TO PERFORM THE
WORK WITHIN THE BASE COST.
PROVIDE ALL NECESSARY PREPARATIONS TO PERFORM THE WORK WITHIN THE BASE COST.
WATER AND WEATHER ENTRY INTO THE BUILDING THROUGHOUT THE DURATION OF CONSTRUCTION IS NOT TO OCCUR. CONTRACTOR SHALL BEAR ALL ASSOCIATED REPAIR COSTS SHOULD THIS OCCUR.
PRIMARY SCOPE ELEMENTS
THE PRIMARY REPAIR ELEMENTS OUTLINED WITHIN THE SCOPE OF REPAIR INCLUDE:
A. COMPREHENSIVE REROOFING OF EXISTING ASSEMBLY. EXISTING ROOF ASSEMBLY, COPINGS, AND TRANSITIONAL ELEMENTS TO BE DEMOLISHED. NEW CONVENTIONALLY INSULATED LOW-SLOPE
ROOF TO BE PROVIDED.
THIS SCOPE DOES NOT ADDRESS UNFORESEEN STRUCTURAL DEFICIENCIES, MECHANICAL SYSTEMS, OR
OTHER BUILDING SYSTEMS NOT DIRECTLY IMPACTED BY THE PROPOSED ENVELOPE RENEWALS.
CONSTRUCTION DOCUMENTS WERE NOT AVAILABLE FOR REFERENCE. ASSUMPTIONS WERE MADE
ABOUT THE EXISTING ROOFING ASSEMBLY TO THE BEST OF OUR ABILITY BASED ON FIELD
OBSERVATIONS AND NON-DESTRUCTIVE MOISTURE SCANNING AT SELECT AREAS NOTED IN THE PHOTO APPENDIX. THIS DOCUMENT MAY BE MODIFIED AS NECESSARY TO REFLECT EXISTING CONDITIONS AND
CORRESPONDING RECOMMENDATIONS AFTER EXISTING CONDITIONS ARE CONFIRMED DURING THE
CONSTRUCTION PHASE.
GOVERNING CODES:
BUILDING: 2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
2021 OREGON EXISTING BUILDING CODE (OEBC)
ENERGY: 2021 OREGON ZERO ENERGY READY COMMERCIAL ENERGY CODE (OEESC)
ELECTRICAL: 2023 OREGON ELECTRICAL CODE
MECHANICAL: 2022 OREGON MECHANICAL SPECIALTY CODE (OMSC)
PLUMBING: 2023 OREGON PLUMBING CODE (OPC)
SITE
SITE
THIS DESIGN IS IN CONFORMANCE WITH THE PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS
OF OEESC TABLE 5.5-4, AND AS NOTED BELOW FOR EACH BUILDING COMPONENT AND / OR
PORTION OF THE BUILDING.
BUILDING ELEMENTS (PER TABLE C402.1.3)
A.
B.
EXPOSED INSULATION MATERIALS, INCLUDING FACINGS AND VAPOR BARRIERS, SHALL HAVE A FLAME SPREAD INDEX NOT TO EXCEED 25 AND A SMOKE DENSITY NOT TO EXCEED 450, AND SHALL BE IN
SUBSTANTIAL CONTACT WITH THE WALL OR CEILING SURFACE.
ALL INSULATION SHALL STRICTLY CONFORM TO THE REQUIREMENTS OF UL LISTING WHERE USED IN UL
RATED ASSEMBLIES
4C MARINE
GROUP B (BUSINESS) + GROUP I-3 (INSTITUTIONAL)
GENERAL INSULATION AND ENERGY CODE NOTES:
R-30 CI-MIN
GENERAL NOTES - ENERGY CONSERVATION
REQUIRED
(GROUP B)
PROVIDED
(GROUP B)
ROOF ASSEMBLIES
R-30CIINSUL. ENTIRELY ABOVE DECK
CONSTRUCTION COMPONENT
2025 OREGON ENERGY EFFICIENCY SPECIALTY
CODE (ASHRAE 90.1-2022)APPLICABLE ENERGY CODE:
CLIMATE ZONE (TABLE C301.1):
OCCUPANCY TYPE(S) (IBC 302.1) :
STRUCTURAL - ROOF UPLIFT FORCES
GOVERNING CODE: OSSC 2022, ASCE 7-16
WIND SPEED: 130 MPH (TILLAMOOK COUNTY SPECIAL WIND REGION)
RISK CATEGORY: III
EXPOSURE: C
FLAT ROOF UPLIFT PRESSURES (ULTIMATE):
ZONE 3: -92.2 PSF
ZONE 2: -92.2 PSF
ZONE 1: -69.9 PSF
ZONE 1':-40.25 PSF
EDGE ZONE a = 21'-0" CORNER ZONE b = 7'-0" a
ZONE 3
ZONE 3 ZONE 3
ZONE 3
ZONE 2
ZONE 1
ZONE 1'
b
ISSUE DATE:
PROJECT NO.:
CHECKED BY:
ISSUED
FOR
BID
REVISIONS
www.certasolutions.com
TM
bu ild in g so lu tio ns
C E
R T
A
These drawings and their content are the property of CERTA BUILDING SOLUTIONS and are to be utilized on this project. Reproduction of any part of this material, without the express written permission of CERTA BUILDING SOLUTIONS is prohibited.
CO
PY
RI
G
H T
DRAWN BY:
C:
\U se rs\
Br itta ny Ma rlin \A pp Da ta\ Lo ca l\A uto de sk \R ev it\A uto de sk R ev it 2
6\C oll ab or ati on Ca ch e\N
8A
JR
R5
XL
3G
Q2 U\
1f9 6-c0
-4 f8e
-8
7-ac f0d f\6 c6 d-aa e2 -4 b9 f-b
4-cb
3ff d5 1.r vt
G000
2026-05-28
OR24-084
0 L
AU
RE
L A
VE
NU
E, T
ILL
AM
OO
K, O
R
COVER SHEET
OR
-08 4 -
TI
LL
AM
OO
K
CO
UN
TY
C
OU
RT
HO
US
E
- R
OO
F O
NL
Y
DJR
BI
D
SE
T
BW, BM
DRAWING INDEX
SHEET NUMBER SHEET NAME
01 - GENERAL
G000 COVER SHEET
02 - ARCHITECTURAL
A100 ROOF PLAN & TYP DETAILS
A300 ROOFING DETAILS
A301 ROOFING DETAILS
OWNER:
OWNER CONTACT:
CERTA PROJECT MANAGER:
PROJECT ADDRESS:
PROPERTY ID:
ZONING:
JURISDICTION:
PROJECT DATA
TILLAMOOK COUNTY
RACHEL HAGERY
DAN RUNDLE, drundle@certasolutions.com
210 LAUREL AVENUE, TILLAMOOK, OR 97141
02900
P, PUBLIC
TILLAMOOK
N.T.S
LOCATION MAP 2N.T.S
VICINITY MAP 3
OR24-084 - TILLAMOOK COUNTY COURTHOUSE - ROOF ONLY
210 LAUREL AVENUE, TILLAMOOK, OR 97141
ISSUED ON: 2026-05-28
NN N
N.T.S
PROJECT IMAGE 1
A300
A300
A300
A301
A200
A2003A200 3
A200
A301
A300
A2004 4 A301
A301
A301
A301
SL
OP
E
SLOPE
(E) RTUS
(E) OVERFLOW SCUPPER
SL
OP
E 1/4
"/F T
SLOPESLOPE
SLOPE 1/4"/FT SLOPE 1/4"/FT
SL
OP
E 1/4
"/F T
A300
RETROFIT DRAIN (E) OVERFLOW DRAIN
RETROFIT DRAIN
A301
SL
OP
E
SL
OP
E
SL
OP
E
SL
OP
E
SL
OP
E
SL
OP
E
RI
DG
E
SL
OP
E
SL
OP
E
A300
A300
A301
A301
A300
A300
A300
A300
A300
A301
A301
A300
A300 4 A300
A300
A300
A301
A301
EXISTING ANTENNA TO REMAIN.
PRESERVE EXISTING CURB AND
ENCAPSULATE WITH FULLY REINFORCED
PMMA FLASHING
EXISTING ABANDONED
CURB CONDITIONS.
REMOVE AS PART OF
WORK.
ENSURE NO
PINHOLES
FOLD AND BUTTON
PUNCH
NOTE(S):
THIS DETAIL IS CONCEPTUAL AND DESCRIBES DESIGN INTENT. IT DOES NOT PURPORT TO
SHOW ALL CONDITIONS. ALL FLASHING JOINTS AND TERMINATIONS TO BE PERMANENTLY
WATERTIGHT.
FULLY SEAL
ALL LAP
JOINTS
1/2 IN. VERT. FOLDED
END DAMS (NO PINHOLES
ALLOWED) OR SOLDERED
END DAMS
CHAMFER CORNERS
15° TYP
MI
N
3 3 /16
SLOPE
BRAKE FLASHING UPPER LEG
AT WINDOW HEAD TO ALLOW
FOR FLAT INSTALLATION OVER
NAILING FIN
AFFIX WITH BUTTON
PUNCH OR SIMILAR
ANCHORAGE AT LAP
15° TYP
1 1 /2"
1 1
/2"
SLOPE
BRAKE FLASHING UPPER LEG AT WINDOW
HEAD TO ALLOW FOR FLAT INSTALLATION
OVER NAILING FIN
1/2 IN. VERT. FOLDED
END DAMS (NO PINHOLES
ALLOWED) OR SOLDERED
END DAMS
CHAMFER CORNERS
SIZE TO ENSURE 1/2" GAP AT TOP
OF CLADDING, AND TO ENSURE 1"
MIN. COVERAGE OVER CLADDING,
U.N.O.
TWO (2) BEADS OF
SEALANT
15° SLOPE
1/2" HEMMED DRIP
EDGE BENT AT 45°
ANGLE
SIZE TO RECIEVE
TRIM AT CORNERS
3"
V.I.F. 1"
8.5" PRE-FINISHED
BACKER PLATE
4" LAP
4" MIN. HORIZ. LAP
BEDDING IN SEALANT
PRE-FINISHED BACKER PLATE
TWO (2) BEADS
OF SEALANT -
EACH SIDE
4" LAP
1/4"
15° MIN
SEE DETAIL FOR
PROFILE
6" MIN
(3) CONTINUOUS BEADS OF
NON SKINNING BUTYL
SEALANT. FULLY SEAL LAP
BAYONET CUT
TYPICAL LINEAR FLASHING
SPLICE AT COPING
LOW SIDE IF
SLOPED
HIGH SIDE
IF SLOPED
6" LAP
FULLY WATERPROOFED
COPING BELOW
FULLY SEALED, PREFABRICATED CORNER SOLDIER
OR BUTTON PUNCH CONNECTION. MOCK-UP
REQUIRED TO BE APPROVED BEFORE
INSTALLATION
FASTENERS PER SPECIFIC DETAIL. FASTENERS TO
BE GASKETED HEX HEAD NON-CORROSIVE
MATCHING COPING MATERIAL, UNO. HOLES TO BE
PRE-DRILLED (OVERSIZED OR SLOTTED) TO
ALLOW FOR EXPANSION AND CONTRACTION OF
COPING.
3'-0" MAX AT PREFORMED CORNERS EA SIDE
AT EXTERIOR SIDE,
CONTINUOUS SHEET METAL
CLEAT
NOTE(S):
THIS DETAIL IS CONCEPTUAL AND DESCRIBES DESIGN INTENT. IT DOES
NOT PURPORT TO SHOW ALL CONDITIONS. ALL FLASHING JOINTS AND
TERMINATIONS TO BE PERMANENTLY WATERTIGHT.
2 3
INSTALL PARTS 2-4 AFTER SPLIT SHROUD (PART
1) IS INSTALLED AROUND LINE-SET. FULLY
SOLDER ALL JOINTS, PROTECT LINE-SET
INSULATION FROM HEAT DURING INSTALLATION
STAINLESS STEEL SPLIT SHROUD TO ALLOW FOR
FLASHING LINE-SET IN PLACE WITHOUT
DISCONNECTION. FULLY SOLDER ALL JOINTS,
PROTECT LINE-SET INSULATION FROM HEAT
DURING INSTALLATION
NOTE(S):
THIS DETAIL IS CONCEPTUAL AND DESCRIBES DESIGN INTENT. IT
DOES NOT PURPORT TO SHOW ALL CONDITIONS. ALL FLASHING
JOINTS AND TERMINATIONS TO BE PERMANENTLY WATERTIGHT.
1. EXTEND ROOFING MEMBRANE UP AND
OVER PERIMETER PARAPET CONDITION - CUT
OPENING FOR SCUPPER AND SET INTO
SEALANT
FULLY SOLDERED, SHOP FABRICATED,
24 GAUGE STAINLESS STEEL
THROUGH-PARAPET SCUPPER
MOCK-UP REQUIRED TO BE APPROVED
BEFORE INSTALLATION
3"4"
6"
12" 3"
4"
2. SET SCUPPER INTO SEALANT
3. ADHERED STRIPPING PLIES
AT FLANGES OF SCUPPER
24 GA STAINLESS STEEL RING
WITH 2" FLASHING FLANGE -
OVERSIZE 3/4" LENGTH AND WIDTH
FOR 3/8" SEAL BETWEEN RING AND
OUTSIDE DIMENSION OF SCUPPER SIMILAR
TO SMACNA FIG. 1-30
2"
ISSUE DATE:
PROJECT NO.:
CHECKED BY:
ISSUED
FOR
BID
REVISIONS
www.certasolutions.com
TM
bu ild in g so lu tio ns
C E
R T
A
These drawings and their content are the property of CERTA BUILDING SOLUTIONS and are to be utilized on this project. Reproduction of any part of this material, without the express written permission of CERTA BUILDING SOLUTIONS is prohibited.
CO
PY
RI
G
H T
DRAWN BY:
C:
\U se rs\
Br itta ny Ma rlin \A pp Da ta\ Lo ca l\A uto de sk \R ev it\A uto de sk R ev it 2
6\C oll ab or ati on Ca ch e\N
8A
JR
R5
XL
3G
Q2 U\
1f9 6-c0
-4 f8e
-8
7-ac f0d f\6 c6 d-aa e2 -4 b9 f-b
4-cb
3ff d5 1.r vt
A100
2026-05-28
OR24-084
0 L
AU
RE
L A
VE
NU
E, T
ILL
AM
OO
K, O
R
ROOF PLAN & TYP
DETAILS
OR
-08 4 -
TI
LL
AM
OO
K
CO
UN
TY
C
OU
RT
HO
US
E
- R
OO
F O
NL
Y
DJR
BI
D
SE
T
BW, BM
1/8" = 1'-0"
ROOF PLAN - NEW 1N
3" = 1'-0"
TYPICAL FLASHING JOINERY 3
3" = 1'-0"
TYPICAL COPING FLASHING AND LINEAR FLASHING LAP JOINT 2 3/8" = 1'-0"
SHROUD PENETRATION SEQUENCE 4
3" = 1'-0"
SCUPPER ISO. 5
1.
2.
A.
3.
4.
A.
CONTRACTOR SHALL MAINTAIN A RECORD OR "AS-BUILT" SET OF DRAWINGS, CLEARLY IDENTIFYING SUCH
DISCREPANCIES BETWEEN THE DRAWINGS AND THE AS-CONSTRUCTED CONDITIONS.
EDGE METAL AND DRIP ELEMENTS SHALL BE REPLACED AS PART OF THE WORK. PROVIDE MINIMUM 24
GAUGE PREFINISHED SHEET STEEL FLASHINGS PER THE DETAILS.
EDGE METAL SHALL BE ANCHORED INTO SOLID FRAMING IN COMPLIANCE WITH ANSI/SPRI ES-1.
SALVAGE HVAC SHROUDS AT EXISTING CURBS FOR REINSTALLATION AFTER COMPLETION OF THE NEW ROOF.
SHEET METAL COMPONENTS DIRECTLY RELATED TO THE NEW ROOFING SYSTEM SHALL BE REPLACED PER
THE DETAILS AND SPECIFICATIONS.
SHEET METAL NOT INCLUDED IN THE DETAILS SHALL BE INCLUDED AS PART OF THE BASE BID, AND AS
SURVEYED BY THE CONTRACTOR IN THE FIELD.
SCOPE OF REPAIR NOTES
07 5216 - MINERAL WOOL CANT
07 5216 - SBS CAP SHEET
07 5216 - SBS BASE SHEET
2"
1" 3"R1
NOTES:
1. REMOVE (E) METAL CLADDING AT SHORT PARAPETS
(E) MASONRY WALL
07 5216 - 22 GA PREFINISHED G90 GALV
SHEET STEEL COPING - INTERLOCK WITH
CLEAT - FABRICATION SHALL BE TESTED
TO MEET OR EXCEED ANSI/SPRI ES-1
07 5216 - 8" WIDE SPLICE PLATE W/ DUAL
NON-CURING SEALANT STRIPS AT EACH
JOINT
07 6200 - HIGH TEMP SELF-ADHERED
ROOF UNDERLAYMENT STRIPPING PLY
OVER DOWNWARD FACING
FASTENERS/ANCHORS
FASTEN IN THIRD FULL HOLE FROM DRIP - DO NOT
OVERTIGHTEN TO MAINTAIN 3/8" NEEDED GAP PER
GAF DETAIL
07 6200 - HIGH TEMP SELF-ADHERED
ROOF UNDERLAYMENT07 5216 - HIGH TEMP SELF-ADHERED ROOF
UNDERLAYMENT - DEGRANULATE CAP SHEET AT
LAP OVER SBS ROOF 2"
06 1600 - 5/8" GYPSUM SHEATHING
CONTINUOUS STRIP OF SELF-ADHERING
AIR/VAPOR BARRIER MEMBRANE
07 5216 - MINERAL WOOL CANT
07 5216 - SBS CAP SHEET
(E) CONCRETE PARAPET
07 5216 - SBS BASE SHEET
2"
1" 3"
8" M
IN
07 6200 - SHEET METAL
COUNTERFLASHING
R1
07 9200 - SEALANT BEAD
07 4113 - AEP SPAN 12" 24GA PRESTIGE
PANEL HORIZONTAL SIDING ATTACHED
WITH Z METAL CLOSURE PER MFR
07 2500 - FLUID APPLIED FLASHING
07 4113 - VERT GALV Z-GIRTS @ 24" OC
07 5216 - MINERAL WOOL CANT
07 5216 - SBS CAP SHEET
07 2500 - SELF ADHERED MEMBRANE
8" M
IN
07 6200 - STAINLESS STEEL SURFACE
MOUNTED COUNTER FLASHING W/
GUM LIP PROFILE
07 9200 - SEALANT GUM LIP
07 5216 - CONTINUOUS TERMINATION BAR AND
SEALANT - FASTENED @ 8" OC MAX THROUGH
BUTYL TAPE
1" 3"
2.6
2.6
R1
07 5216 - SBS BASE SHEET
(E) MASONRY OR MASS WALL SUBSTRATE TO REMAIN
STAINLESS STEEL, GASKETED, MASONRY ANCHORS AT 10 IN. OC, TYP.
(E) CONCRETE ROOF STRUCTURE
TO REMAIN
07 5216 - TAPERED RIGID INSULATION (R-30 MIN)
07 5216 - 1/2" HD INSULATIVE COVER BOARD
07 5216 - SBS BASE SHEET
07 5216 - SBS CAP SHEET
07 5216 - AIR & VAPOR BARRIER ROOF MEMBRANE
R1
OUTSIDE
INSIDE
FACTORY-PRIMED GYPSUM COVERBOARD
SLOPE 1/4: 12 TO DRAIN (MIN.)
07 5216 - SBS PRIMER
07 5216 - MINERAL WOOL CANT
07 5216 - SBS CAP SHEET
(E) PENTHOUSE
07 5216 - SBS BASE SHEET
2"
1" 3"R1
R1
07 6200 - 22 GA CONT GALV CLEAT -
ANCHOR PER ANSI/SPRI ES-1
07 7100 - 22 GA PREFINISHED G90 GALV SHEET STEEL
COPING - INTERLOCK WITH CLEAT - FABRICATION
SHALL BE TESTED TO MEET OR EXCEED ANSI/SPRI
ES-1
SELF-ADHERING HIGH-TEMPERATURE RESISTANT
UNDERLAYMENT
07 9200 - SEALANT BEAD
07 9200 - SEALANT BACKER ROD
(E) EXTERIOR BRICK MASONRY WALL
07 6200 - SHEET METAL SCUPPER W/ WELDED
JOINTS & SLOPED TO EXTERIOR - SET IN
SEALANT
- SEE SMACNA FIG. 1-30
07 6200 - SHEET METAL SCUPPER
FLANGE
07 7100 - ANCHOR PLATE @ 5'-0" OC
CONT. BASE PLY INTO SCUPPER
ROUGH OPENING
07 6200 - STAINLESS STEEL REGLET COUNTERFLASHING
07 9200 - SEALANT BACKER ROD
07 5216 - SBS BASE FLASHING SHEET
2X PT BLOCKING
ANCHOR INTO (E) DECK
1" 4"
2"
07 5216 - MINERAL WOOL CANT
07 5216 - SBS BASE SHEET
07 5216 - PMMA MEMBRANE
07 5216 - PMMA MEMBRANE
07 5216 - SBS CAP SHEET
07 5216 - MINERAL WOOL CANT
DE-GRANULATE TOP SHEET
UNDER COPING TO ALLOW
HIGH-TEMP SAM
ADHERANCE
SELF-ADHERING HIGH-TEMPERATURE
RESISTANT UNDERLAYMENT OVER
FASTENERS
(E) WOOD BLOCKING - REPLACE WITH PT
AS NEEDED
R1
MASTIC - SCUPPER IS TO BE SET INTO BITUMINOUS MASTIC OVER
SBS BASE PLY
AIR/VAPOR BARRIER MEMBRANE -
TRANSITION FROM ROOF DECK TO
THE TOP OF THE SCUPPER
ROUGH OPENING
PRIME HORIZONTAL LEG OF COPING - SET IN
MASTIC AND FASTEN PER ANSI/SPRI ES-1
07 6200 - HIGH TEMP SELF-ADHERED
ROOF UNDERLAYMENT
THIN BRICK VENEER - SOLDIER COURSE
5/8" CEMENT BOARD
07 2500 - VAPOR PERMEABLE FLUID
APPLIED WRB
07 5216 - SBS CAP SHEET
(E) MASONRY WALL
07 5216 - SBS BASE SHEET
ELASTOMERIC ROOF SEALANT
06 1600 - 5/8" GYPSUM SHEATHING
07 5216 - 22 GA PREFINISHED G90 GALV SHEET STEEL
COPING - INTERLOCK WITH CLEAT - FABRICATION SHALL
BE TESTED TO MEET OR EXCEED ANSI/SPRI ES-1
07 5216 - SBS BASE SHEET
07 5216 - SBS BASE STRIPPING PLY
07 5216 - SBS CAP SHEET
SET COPING IN FULL BED OF MASTIC
4".07 5216 - ELASTOMERIC ROOFING SEALANT
07 9200 - SEALANT BEAD
SAW CUT REGLET INTO (E) MASONRY WALLS -
MIN 3/4" DEEP OR 1/4" GREATER THAN
HORIZONTAL LEG OF REGLET
07 6200 - SHEET METAL FLASHING
07 5216 - CONTINUOUS TERMINATION BAR AND
SEALANT - FASTENED @ 8" OC MAX THROUGH
BUTYL TAPE
1" 3"R1
SIM
(E) STRUCTURE - GC TO REVIEW CONDITION W/
ARCHITECT AFTER ROOF IS REMOVED
8 I N.
M
IN
ISSUE DATE:
PROJECT NO.:
CHECKED BY:
ISSUED
FOR
BID
REVISIONS
www.certasolutions.com
TM
bu ild in g so lu tio ns
C E
R T
A
These drawings and their content are the property of CERTA BUILDING SOLUTIONS and are to be utilized on this project. Reproduction of any part of this material, without the express written permission of CERTA BUILDING SOLUTIONS is prohibited.
CO
PY
RI
G
H T
DRAWN BY:
C:
\U se rs\
Br itta ny Ma rlin \A pp Da ta\ Lo ca l\A uto de sk \R ev it\A uto de sk R ev it 2
6\C oll ab or ati on Ca ch e\N
8A
JR
R5
XL
3G
Q2 U\
1f9 6-c0
-4 f8e
-8
7-ac f0d f\6 c6 d-aa e2 -4 b9 f-b
4-cb
3ff d5 1.r vt
A300
2026-05-28
OR24-084
0 L
AU
RE
L A
VE
NU
E, T
ILL
AM
OO
K, O
R
ROOFING DETAILS
OR
-08 4 -
TI
LL
AM
OO
K
CO
UN
TY
C
OU
RT
HO
US
E
- R
OO
F O
NL
Y
DJR
BI
D
SE
T
BW, BM
3" = 1'-0"
2-PLY SBS MEMBRANE - PARAPET DETAIL W/ NEW COPING AT CONC WALL 5
3" = 1'-0"
2-PLY SBS MEMBRANE - TALL PARAPET DETAIL W/ (E) FLASHING AT CONC WALL 2
3" = 1'-0"
2-PLY SBS MEMBRANE - ROOF TO WALL - CONCRETE WALL AND DECK 8
3" = 1'-0"
TYPICAL CONCRETE ROOF ASSEMBLY 1
3" = 1'-0"
2-PLY SBS MEMBRANE - ROOF PENTHOUSE TRANSITION 3
3" = 1'-0"
2-PLY SBS MEMBRANE - THRU-WALL OVERFLOW SCUPPER 7
3" = 1'-0"
COPING AT TOP OF BRICK FACADE TO UPPER ROOF 6 3" = 1'-0"
COPING AT TOP OF METAL PANEL TO UPPER ROOF 9
3" = 1'-0"
ROOF TO WALL TRANSITION AT BRICK 4
MULTI-PIECE LINE-SET SHROUD - SEE
DETAIL SEQUENCE
REMOVABLE SCREEN
(E) LINE-SET AND INSULATION
FILL INSIDE OF SHROUD BETWEEN
LINE-SET AND SHROUD WALLS
WITH SPRAY FOAM BEFORE CAP IS
INSTALLED
MAXELL M.A.P - SELF-ADHESIVE
RUBBER PIPE SEALER - SIZE TO
MATCH TOTAL LINESET DIA
1" 3" 07 5216 - SBS BASE SHEET
SET BOTTOM FLANGE OF SHROUD
IN ROOFING SEALANT
MI
N
8" C
LE
AR
AN
CE
R1R1
07 5216 - SBS CAP SHEET
07 5216 - FULLY-REINFORCED LIQUID
APPLIED FLASHING MEMBRANE
07 5216 - PMMA PASTE
07 5216 - FULLY-REINFORCED LIQUID
APPLIED FLASHING MEMBRANE
G90 GALV - UNISTRUT PIPE STANCHION
07 5216 - PMMA PASTE
NOTES:
1. REFERENCE SPECIFICATION FOR MEMBRANE ADHESIVE TYPE, AND INSULATION/COVER BOARD TYPE AND ATTACHMENT METHOD.
2. PREPARE AND CLEAN PIPE PRIOR TO APPLYING FLASHING.
8"
WEDGE ANCHOR EXPANSION BOLTS -
CONTRACTOR TO VERIFY LOCATION OF
REINFORCING BEFORE DRILLING AND
INSTALLING ANCHORS
2" POLYURETHANE FOAM THERMAL
BREAK BLOCK (BOD: ARMATHERM
500-080)
DO NOT PROVIDE THERMAL BREAK AT
THE BASE OF FALL PROTECTION
ANCHORS, TYP.
R1 R1
07 5216 - FULLY-REINFORCED LIQUID
APPLIED FLASHING MEMBRANE
(E) PIPE PENETRATION
SEAL AIR/VAPOR BARRIER
MEMBRANE TO PENETRATION
07 5216 - PMMA PASTE
NOTES:
1. REFERENCE SPECIFICATION FOR MEMBRANE ADHESIVE TYPE, AND INSULATION/COVER BOARD TYPE AND ATTACHMENT METHOD.
2. PREPARE AND CLEAN PIPE PRIOR TO APPLYING FLASHING.
8"
8"
R1 R1
(E) HVAC SHROUD -
REMOVE & REINSTALL
07 6200 - 24ga G90 GALV COUNTER FLASHING
NEW FRT LVL FRAMING AS NEEDED TO ELEVATE
CURB AS PART OF INCREASED HEIGHT OF ROOF
DUE TO INSULATION. CONNECT TO LOWER CURB
W/ LTP5 PLATES - ANCHOR INSIDE CORNERS WITH
A34 ANGLES
100% BUTYL SELF-ADHERED
FLASHING MEMBRANE - LAP DOWN 2"
07 6200 - 24 GA BACK ANGLE
SET IN SEALANT
(E) CURB FRAMING TO REMAIN
07 5216 - MINERAL WOOL CANT
07 5216 - SBS BASE SHEET
07 5216 - SBS CAP SHEET
07 6200 - SST GASKETED FASTENERS
1" 3" R1 R1
ROOF SYSTEM
STAINLESS STEEL HOSE CLAMP TO FASTEN LINE-SET COVER
INSIDE PENETRATION FLASHING
UV RESISTANT PVC PROTECTIVE INSULATION COVER FOR
LINESET - LENGTH SHALL BE SUFFICIENT TO COVER LINE-SET
COMPLETELY FROM PIPE BOOT TO OUTDOOR UNIT CONNECTIONS
(BASIS OF DESIGN: AIREX MANUFACTURING E-FLEX GUARD)
OUTDOOR HVAC UNIT
OUTDOOR HVAC UNIT PAD OR MOUNT
HVAC LINE-SET PENETRATION BOOT OVERVIEW
EXTERIOR
INTERIOR
SEAL LINESETS AT INSIDE END OF PENETRATION
WITH APPROVED COMPATIBLE ACRYLIC BASED
FLASHING TAPE
A301
HVAC LINE-SET WITH INSULATION FULLY TAPED AND
SEALED (BOD: ISOTECH UV LINESET OR OTHER
FORMICARY CORROSION RESISTANT LINESET) - ONLY ONE
LINESET PER PIPE PENETRATION IS ALLOWED
SEAL ENDS OF LINESET INSULATION TO EXPOSED
LINESET PIPING W/ SIKAFLEX 521 UV SEALANT
(E) LARGE HVAC EQUIP TO
REMAIN
SEAL AIR/VAPOR BARRIER
MEMBRANE TO CURB
07 5216 - CONTINUOUS TERMINATION BAR
AND SEALANT - FASTENED @ 8" OC MAX
THROUGH BUTYL TAPE
(E) CURB FRAMING TO REMAIN
07 2500 - 100% BUTYL SELF-ADHERED FLASHING
MEMBRANE - LAP DOWN OVER BAR
07 5216 - MINERAL WOOL CANT4"
M
IN
07 6200 - SHEET METAL FLASHING
07 9200 - SEALANT BEAD
07 5216 - SBS CAP SHEET
1" 3" R1
07 5216 - SBS BASE SHEET
R1
NOTES:
1. REFERENCE SPECIFICATION FOR MEMBRANE ADHESIVE TYPE,
AND INSULATION/COVER BOARD TYPE AND ATTACHMENT METHOD.
07 5216 - RETROFIT ROOF DRAIN/OVERFLOW
W/ STRAINER BASKET - SEALED TO (E) PIPE
FASTENER(S) & STRESS PLATE(S)
12" O.C. AROUND SUMP AREA
SLOPE = 1/2:12
DRAIN BOWL & CLAMP
(E) DRAIN LEADER
CONNECTION HUB
R-
M
IN
07 5216 - SBS BASE SHEET
07 5216 - PMMA MEMBRANE
07 5216 - SBS CAP SHEET
06 1000 - 2X4 PT FRAMING
07 2000 - HFO CC SPRAY-FOAM INSULATION - ENSURE
INSTALLED DEPTH (~1.5") DOES NOT INTERFERE WITH
DRAIN INSTALL
07 2000 - HFO CC SPRAY-FOAM INSULATION ~4"
DEPTH
6" 4"
STRAINER & CLAMPING RING
07 5216 - 2-PLY SBS CAP PLY
07 5216 - SBS BASE PLY
FULLY REINFORCED LIQUITEC POLYUREA
FLASHING MEMBRANE - EXTEND INTO
PREPARED DRAIN BOWL
SLOPED RIGID ROOF INSULATION
OVERHEAD VIEW
1'-4".
6" LAP
4'-0".OVERFLOW DRAIN - CONNECT TO (E) PRIMARY
DRAINAGE DOWNSTREAM OF LAST
HORIZONTAL OFFSET BELOW THE ROOF - DEGRANULATE
AT PMMA OVERLAP
R1(E) EXTERIOR BRICK MASONRY WALL
07 9200 - SEALANT BACKER ROD
FLUID APPLIED VAPOR OPEN WRB OVER
BRICK
07 9200 - SEALANT GUM LIP
(E) STRUCTURE
GALV END CHANNEL SUPPORT FOR METAL PANEL - FASTEN
TO Z-FURRING W/ HORIZONTAL STRUTS PER MFR
REQUIREMENTS
AEP SPAN 12" 24GA PRESTIGE PANEL HORIZONTAL
SIDING ATTACHED WITH Z METAL CLOSURE PER MFR
PRE-FINISHED VERTICAL SHEET METAL CORNER FLASHING
W/GUM LIP - FASTEN W/ GASKETED FASTENERS PER MFR'S
REQUIREMENTS
VERT GALV Z-GIRTS @ 24" OC
PROVIDE NEW DOOR: CURRIES / ASSA ABLOY
SERIES 707, 16 GAUGE, WITH A SERIES 346
WATER-SHEDDING DRIP AT THE HEAD
CONDITION. FIELD PAINTED, WITH SHERWIN-
WILLIAMS DTM PRO INDUSTRIAL PAINT
07 6200 - SHEET METAL FLASHING
FILL CAVITY WITH
SEALANT
R1
07 5216 - MINERAL WOOL CANT
07 5216 - SBS CAP SHEET
07 5216 - SBS BASE SHEET
08 5300 - PVC SHIM
NEW 4X PPT WOOD SILL
NEW ALUMINUM STYLE SADDLE THRESHOLD PEMKO OR EQUAL
1.
2.
A.
3.
4.
A.
CONTRACTOR SHALL MAINTAIN A RECORD OR "AS-BUILT" SET OF DRAWINGS, CLEARLY IDENTIFYING SUCH
DISCREPANCIES BETWEEN THE DRAWINGS AND THE AS-CONSTRUCTED CONDITIONS.
EDGE METAL AND DRIP ELEMENTS SHALL BE REPLACED AS PART OF THE WORK. PROVIDE MINIMUM 24
GAUGE PREFINISHED SHEET STEEL FLASHINGS PER THE DETAILS.
EDGE METAL SHALL BE ANCHORED INTO SOLID FRAMING IN COMPLIANCE WITH ANSI/SPRI ES-1.
SALVAGE HVAC SHROUDS AT EXISTING CURBS FOR REINSTALLATION AFTER COMPLETION OF THE NEW ROOF.
SHEET METAL COMPONENTS DIRECTLY RELATED TO THE NEW ROOFING SYSTEM SHALL BE REPLACED PER
THE DETAILS AND SPECIFICATIONS.
SHEET METAL NOT INCLUDED IN THE DETAILS SHALL BE INCLUDED AS PART OF THE BASE BID, AND AS
SURVEYED BY THE CONTRACTOR IN THE FIELD.
SCOPE OF REPAIR NOTES
NOTES:
1. REMOVE (E) METAL CLADDING AT SKYLIGHT
(E) SKYLIGHT HOUSING - REMOVE AND
REINSTALL AS PART OF ROOFING
RENEWAL
07 6200 - 24ga G90 GALV COUNTER FLASHING
NEW FRT LVL FRAMING AS NEEDED TO ELEVATE
CURB AS PART OF INCREASED HEIGHT OF ROOF DUE
TO INSULATION. CONNECT TO LOWER CURB W/ LTP5
PLATES - ANCHOR INSIDE CORNERS WITH A34
ANGLES
100% BUTYL SELF-ADHERED FLASHING
MEMBRANE - LAP DOWN 2"
07 6200 - 24 GA BACK ANGLE
SET IN SEALANT
(E) CURB FRAMING TO REMAIN
07 5216 - MINERAL WOOL CANT
07 5216 - SBS BASE SHEET
07 5216 - SBS CAP SHEET
07 6200 - SST GASKETED FASTENERS
R1
3" = 1'-0"
2-PLY SBS MEMBRANE - EQUIPMENT STANCHION PENETRATION - CONCRETE 3
3" = 1'-0"
07 5216 - 2-PLY SBS MEMBRANE - LINE-SET SHROUD PENETRATION 2 3" = 1'-0"
2-PLY SBS MEMBRANE PLUMBING STACK PENETRATION - CONCRETE 4
3" = 1'-0"
CURB CONDITION - REMOVE AND RESET MECHANICAL UNIT 5
3" = 1'-0"
2-PLY SBS MEMBRANE - TYPICAL ROOF TRANSITION @ SKYLIGHT 11
3/4" = 1'-0"
HVAC LINESET PENETRATION AT ROOF 6
ISSUE DATE:
PROJECT NO.:
CHECKED BY:
ISSUED
FOR
BID
REVISIONS
www.certasolutions.com
TM
bu ild in g so lu tio ns
C E
R T
A
These drawings and their content are the property of CERTA BUILDING SOLUTIONS and are to be utilized on this project. Reproduction of any part of this material, without the express written permission of CERTA BUILDING SOLUTIONS is prohibited.
CO
PY
RI
G
H T
DRAWN BY:
C:
\U se rs\
Br itta ny Ma rlin \A pp Da ta\ Lo ca l\A uto de sk \R ev it\A uto de sk R ev it 2
6\C oll ab or ati on Ca ch e\N
8A
JR
R5
XL
3G
Q2 U\
1f9 6-c0
-4 f8e
-8
7-ac f0d f\6 c6 d-aa e2 -4 b9 f-b
4-cb
3ff d5 1.r vt
A301
2026-05-28
OR24-084
0 L
AU
RE
L A
VE
NU
E, T
ILL
AM
OO
K, O
R
ROOFING DETAILS
OR
-08 4 -
TI
LL
AM
OO
K
CO
UN
TY
C
OU
RT
HO
US
E
- R
OO
F O
NL
Y
DJR
BI
D
SE
T
BW, BM
3" = 1'-0"
CURB CONDITION - MECHANICAL UNIT TO REMAIN IN-SERVICE 9
3" = 1'-0"
2-PLY SBS MEMBRANE - RETROFIT ROOF DRAIN - CONCRETE 1
3" = 1'-0"
METAL PANEL CORNER TRIM AT BRICK - PLAN 7
3" = 1'-0"
SWING DOOR SILL - ROOF TRANSITION 8
| G000 - COVER SHEET |
| A100 - ROOF PLAN & TYP DETAILS |
| A300 - ROOFING DETAILS |
| A301 - ROOFING DETAILS |
File details come from the government source that posted it. Updated .