2026-03-25_CTSI - Broadband Remodel_Bulletin 1.pdf
PDF 5 MB Posted
- Solicitation number
- S-X21600-00016771
- Issued by
- Oregon
About this file
This document is a comprehensive set of architectural and engineering construction drawings (Bulletin 1, dated March 24, 2026) for the Broadband Remodel Project being undertaken by the Confederated Tribes of the Siletz Indians at their facility located at 107 SE Swan Avenue, Siletz, Oregon 97380. The project, identified as JMFMRC Project #250910, involves comprehensive renovation of Level 1 spaces including demolition of existing partitions, casework, and mechanical/plumbing systems; installation of new walls to create an IT room with server racks and a new pantry; installation of new HVAC mini-split heat pump systems with dehumidification; addition of plumbing for a new kitchen sink; and electrical infrastructure upgrades including lighting, power distribution, and control systems. The design is being managed by Jackola Engineering & Architecture, P.C., with project management by Julian Bushman-Copp, RA, and engineering by Andrew Hanson (Structural), Blake Bartusiak (Mechanical), and Chase Hallstrom (Electrical). The drawings include detailed architectural floor plans, reflected ceiling plans, floor finish schedules, mechanical HVAC plans with equipment specifications, plumbing supply and waste/vent plans, and full electrical lighting and power plans with fixture and equipment schedules.
The project scope encompasses interior renovation with significant infrastructure modifications including two Samsung 12,000 BTU mini-split heat pump systems (models AR12DXFAMWKXCV and AR12DXFAMWKNCV), FEHOM 150 pint dehumidifiers with condensate management, new gypsum wall board ceiling systems with seismic bracing requirements, vinyl plank flooring, acoustic ceiling tiles, and comprehensive electrical wiring for lighting and power circuits. All work must comply with 2025 Oregon Mechanical Specialty Code, 2023 Oregon Plumbing Specialty Code, 2025 Oregon Energy Efficiency Specialty Code, and applicable fire-rated assembly requirements. The mechanical contractor is responsible for field verification of existing conditions, coordination with owner for service interruptions, testing and balancing of HVAC systems, and replacement of all filters following construction. Specific requirements include minimum concrete compressive strength of 4,000 PSI for any new concrete curbing, insulation of all water lines, seismic bracing for suspended ceilings exceeding 1,000 square feet, and proper coordination between all trades to avoid conflicts with structural members, existing utilities, and fire suppression systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP_SiletzBroadbandRemodel_2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
G-001
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
TITLE SHEET
JMFMRC
P R
O J E
C T
:2
BROADBAND REMODEL
CONFEDERATED TRIBES OF THE SILETZ INDIANS
107 SE SWAN AVE
SILETZ, OR 97380
SITE LOCATION MAPSITE VICINITY MAP
IMAGE SOURCE: HTTPS://EARTH.GOOGLE.COM/ IMAGE SOURCE: HTTPS://EARTH.GOOGLE.COM/
S
ITE
S
ITE
PROJECT INFORMATION:
OWNER / DEVELOPER
CONFEDERATED TRIBES OF SILETZ INDIANS
107 SE SWAN AVE
SILETZ, OR 97380
ATTN: SYD SOMES
EMAIL : SYDNEYS@CTSI.NSN.US
TEL: 541-351-0141
DESIGN PROFESSIONALS
JACKOLA ENGINEERING & ARCHITECTURE, P.C.
702 JEFFERSON STREET
VANCOUVER, WA 98660
PROJECT MANAGER: JULIAN BUSHMAN-COPP, RA
ARCHITECT: JULIAN BUSHMAN-COPP, RA
STRUCTURAL ENGINEER: ANDREW HANSON, PE
MECHANICAL ENGINEER: BLAKE BARTUSIAK, PE
ELECTRICAL DESIGNER: CHASE HALLSTROM
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
G-002
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
GENERAL
INFORMATION
JMFMRC
P R
O J E
C T
:2
INDEX OF DRAWINGS
SHEET NUMBER SHEET NAME ISSUE DATE CURRENT REVISION REVISION DATE
TITLE
G-001 TITLE SHEET 03/17/2026
G-002 GENERAL INFORMATION 03/17/2026
ARCHITECTURAL
A-001 ARCHITECTURAL TITLE SHEET 03/17/2026
AD111 LEVEL 1 DEMOLITION PLAN 03/17/2026
AD121 LEVEL 1 DEMOLITION REFLECTED CEILING PLAN 03/17/2026
A-111 LEVEL 1 FLOOR PLAN 03/17/2026 1 03/24/26
A-121 LEVEL 1 REFLECTED CEILING PLAN 03/17/2026
A-131 LEVEL 1 FLOOR FINISH PLAN 03/17/2026
A-511 SECTION DETAILS 03/17/2026
A-601 DOOR SCHEDULES 03/17/2026
MECHANICAL
M-001 MECHANICAL TITLE SHEET 03/17/2026 1 03/24/26
M-111 LEVEL 1 HVAC PLAN 03/17/2026
M-141 ROOF HVAC PLAN 03/17/2026
M-601 MECHANICAL SCHEDULES & DETAILS 03/17/2026
PLUMBING
P-001 PLUMBING TITLE SHEET 03/17/2026 1 03/24/26
PD-111 LEVEL 1 PLUMBING DEMOLITION PLAN 03/17/2026
P-111 LEVEL 1 DOMESTIC SUPPLY PLAN 03/17/2026
P-121 LEVEL 1 WASTE & VENT PLAN 03/17/2026
P-601 PLUMBING SCHEDULES & DETAILS 03/17/2026
ELECTRICAL
E-001 ELECTRICAL TITLE SHEET 03/17/2026
ED111 LEVEL 1 ELECTRICAL DEMOLITION PLAN 03/17/2026
E-111 LIGHTING PLAN 03/17/2026
E-121 POWER PLAN 03/17/2026 1 03/24/26
E-601 ELECTRICAL SCHEDULES 03/17/2026 1 03/24/26
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
A-102
LEVEL 1 DISCIPLINE DESIGNATOR
LEVEL 2 DISCIPLINE DESIGNATOR
LEVEL SEQUENCE NUMBER
PLAN TYPE SEQUENCE NUMBER
SHEET TYPE DESIGNATOR
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-001
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
ARCHITECTURAL
TITLE SHEET
JMFMRC
P R
O J E
C T
:2
ARCHITECTURAL SHEET INDEX
A-001 ARCHITECTURAL TITLE SHEET
AD111 LEVEL 1 DEMOLITION PLAN
AD121 LEVEL 1 DEMOLITION REFLECTED CEILING PLAN
A-111 LEVEL 1 FLOOR PLAN
A-121 LEVEL 1 REFLECTED CEILING PLAN
A-131 LEVEL 1 FLOOR FINISH PLAN
A-511 SECTION DETAILS
A-601 DOOR SCHEDULES
SHEET WHERE ITEM IS CUT
ITEM IDENTIFICATION
A-XXX
XX
A-XXX
XX
XX
A-XXX
XX
A-XXX
DETAIL
ELEVATION
ROUGH WOOD
SECTION
XXX
X
UNDISTURBED EARTH
WALL TYPE
REVISION NUMBER
ROOM NUMBER
DOOR NUMBER
WINDOW TYPE
PLYWOOD
METAL
RIGID INSULATION
BATT INSULATION
FINISHED WOOD
STRUCTURAL FILL
BLOCKING
SAND, PLASTER, GROUT
AND&
ANGLEL
AT@
CENTERLINECL
CHANNELu
DIAMETERO
PLATEPL
ABBREVIATIONS SYMBOLS & MATERIALS
SYMBOLS USED AS
ABBREVIATIONS
A
AFF
ACT
ADJ
AB
ALUM
ALT
ANOD
APPROX
ARCH
ASSY
B
BSMT
BATH
BM
BRG
BEDRM
BET
BLDG
BO
BOT
BN
BS
BOS
C
CPT
CLG
CT
CLR
CLST
COL
CONC
CONST
CONT
CONTR
CORR
CJ
CMU
CFCI
D
DEMO
DTL
DIA
DIM
DW
DIV
DL
DR
DN
DS
DWG
DF
D
E
EA
E
ELEC
ELEV
EQ
EQUIP
EXIST
EXP
EJ
EXT
F
FOB
FOC
FOM
ABOVE FINISH FLOOR
ACOUSTICAL CEILING TILE
ADJUSTABLE
ANCHOR BOLT
ALUMINUM
ALTERNATE
ANODIZED
APPROXIMATE
ARCHITECT
ASSEMBLY
BASEMENT
BATHROOM
BEAM
BEARING
BEDROOM
BETWEEN
BUILDING
BOTTOM OF
BOTTOM
BOUNDARY NAILING
BOTH SIDES
BOTTOM OF STRUCTURE
CARPET
CEILING
CERAMIC TILE
CLEAR
CLOSET
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
CONTRACT, CONTRACTOR
CORRIDOR
CONTROL JOINT
CONCRETE MASONRY UNIT
CONTACTOR FURNISHED CONTRACTOR INSTALLED
DEMOLISH, DEMOLITION
DETAIL
DIAMETER
DIMENSION
DISHWASHER
DIVISION
DEAD LOAD
DOOR
DOWN
DOWNSPOUT
DRAWING
DRINKING FOUNTAIN
DRYER
EACH
EAST
ELECTRIC
ELEVATION, ELEVATOR
EQUAL
EQUIPMENT
EXISTING
EXPANSION
EXPANSION JOINT
EXTERIOR
FACE OF BRICK
FACE OF CONCRETE
FACE OF MASONRY
FOS
FIN
FF
FEC
FL
FLR
FD
FT
FTG
FND
FURN
FUT
FBO
FRP
G
GA
GALV
GEN
GL
GWB
GYPC
H
HALL
HDW
HVAC
HT
HM
HORIZ
HWT
HR
I
IBC
INCL
INFO
ID
INSUL
INT
J
JAN
JC
JT
K
KIT
KO
L
LBL
LAM
LNDRY
LAV
LVL
LL
LR
LOC'N
M
MFR
MAS
MO
FACE OF STUDS
FINISH
FINISH FLOOR
FIRE EXTINGUISHER/AND
OR CABINET
FLASHING
FLOOR
FLOOR DRAIN
FOOT, FEET
FOOTING
FOUNDATION
FURNITURE
FUTURE
FURNISHED BY OTHERS
FIBER REINFORCED PANEL
GAUGE
GALVANIZED
GENERAL
GLASS
GYPSUM WALL BOARD
GYPCRETE
HALLWAY
HARDWARE
HEATING, VENTILATING, & AIR
CONDITIONING
HEIGHT
HOLLOW METAL
HORIZONTAL
HOT WATER TANK
HOUR
INTERNATIONAL BUILDING CODE
INCLUDE, INCLUDED (ING)
INFORMATION
INSIDE DIAMETER
INSULATE,INSULATION
INTERIOR
JANITOR
JANITOR'S CLOSET
JOINT
KITCHEN
KNOCK OUT
LABEL
LAMINATED
LAUNDRY
LAVATORY
LEVEL
LIVE LOAD
LIVING ROOM
LOCATION
MANUFACTURER
MASONRY
MASONRY OPENING
MATERIAL
MAXIMUM
MECHANICAL, MECHANICAL ROOM
METAL
MINIMUM
MIRROR
MISCELLANEOUS
NOMINAL
NORTH
NOT APPLICABLE
NOT IN CONTRACT
NOT TO SCALE
NUMBER
ON CENTER
OFFICE
OPENING
OPPOSITE
OUTSIDE DIAMETER
OUTSIDE FACE
OWNER FURNISHED CONTRACTOR INSTALLED
OFWNER FURNISHED OWNER INSTALLED
OUT TO OUT
PAINT, PAINTED
PANEL
PHASE
PLASTIC
PLASTIC LAMINATE
PLATE
PLYWOOD
POLYVINYL CHLORIDE
PREFINISHED
PROPERTY
PREMANUFACTURED
QUANTITY
RADIUS
RAIN WATER LEADER
REFERENCE
REINFORCE, REINFORCEMENT
REFLECTED CEILING PLAN
REQUIRED
REQUEST FOR INFORMATION
REVISION
RISER
ROOF DRAIN
ROOM
ROUGH OPENING
SCHEDULE
SECTION
SAFETY GLASS
SHEATHING
SIMILAR
SLAB ON GRADE
SOUTH
SPECIFICATION
SQUARE
STANDARD
STEEL
STORAGE
STRUCTURAL
SQUARE FEET
SUSPENDED
SELF ADHERED MEMBRANE
MATL
MAX
MECH
MTL
MIN
MIRR
MISC
N
NOM
N
NA
NIC
NTS
NO
O
OC
OFF
OPG
OPP
OD
OF
OFCI
OFOI
O/O
P
PNT
PNL
PH
PLAS
P-LAM
PL
PLYWD
PVC
PF
PROP
PMF
Q
QTY
R
RAD
RWL
REF
REINF
RCP
REQ'D
RFI
REV
R
RD
RM
RO
S
SCHED
SEC
SG
SHTG
SIM
SOG
S
SPEC
SQ
STD
STL
STOR
STRUCT
SF
SUSP
SAM
NORTH ARROW
STEEL
GRAVEL
BRICK VENEER
POURED CONCRETE
CONCRETE BLOCK VENEER
EIFS
KEY NOTE
DEMOLITION NOTE
FINISH TAG
XX
X
X
X
X
SPRAYFOAM INSULATION
DISTURBED EARTH
TELEPHONE
TELEVISION
TEMPERED, TEMPORARY
TONGUE AND GROOVE
TOP OF BRICK
TOP OF SLAB
TOP OF WALL
TOP OF MASONRY
TREAD
TYPICAL
UPWARD ACTING SECTIONAL DOOR
UNIFORM BUILDING CODE
UNLESS NOTED OTHERWISE
UTILITY
VAPOR BARRIER
VENEER
VERTICAL
VERTICAL GRAIN
VINYL COMPOSITION TILE
WAINSCOT
WATER CLOSET
WINDOW
WATERPROOF (ING)
WEATHER RESISTANT BARRIER
WELDED WIRE FABRIC
WELDED WIRE MESH
WEIGHT
WEST, WASHER
WITH
WASHER / DRYER
T
TEL
TV
TEMP
T&G
TOB
TOS
TOW
TOM
T
TYP
U
UAS
UBC
UNO
UTIL
V
VB
VNR
VERT
VG
VCT
W
WSCT
WC
WIN
WP
WRB
WWF
WWM
WT
W
W/
W/D
X.XX - S
X'-X"
ROOM FINISH KEY
CLG
FLR
SILL
WALL S
WALL
E
WALL N
WALL
W
NOTES
BASE
NOTES
EQUIPMENT TAG
CONCRETE MASONRY UNITS
X
1 1
B
B
C
C
D
D
2 2
3 3
4 4
OFFICE
CONFERENCE
OFFICE
R.R.
HALL
300A
R.R.
FOYER
IT ROOM
KITCHEN
HALL
300A
HALL
300A
CLOSET
CLOSET
OFFICE
304 7
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
AD111
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1
DEMOLITION
PLAN
JMFMRC
P R
O J E
C T
:2
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 DEMOLITION PLAN
LEVEL 1 DEMO KEYNOTES
1 REMOVE EXISTING DOOR, AND FRAME
2 DEMO (E) PARTION BETWEEN KITCHEN AND I.T. ROOM
3 DEMO (E) CASEWORK. (E) APPLICANCES TO BE RELOCATED TO NEW
PANTRY
4 REMOVE (E) BOOKSHELF, SALVAGE TO OWNER
5 REMOVE EXISTING WINDOW
6 NOT INCLUDED IN SCOPE OF WORK
7 (E) FIBER OPTIC POINT OF ENTRY TO REMAIN
8 (E) WATER HEATER TO REMAIN
9 (E) PIPE, DEMO AND RELOCATE PER PLUMBING
10 ALL LV WIRING TO BE REMOVED OR RELOCATED BY OWNER'S
VENDOR. REMOVE PLYWOOD ON WALLS AS POSSIBLE. GC TO
COORDINATE WORK WITH OWNER.
2 2
3 3
4 4
A
A
B
B
C
C
D
D
1 1
A
A
1 1
B
B
C
C
D
D
2 2
3 3
4 4
IT ROOM
OFFICE
CONFERENCE
FOYER
HALL
300A
R.R.
PANTRY
OFFICE
R.R.
HALL
300A
KITCHEN
CLOSET
CLOSET
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
AD121
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1
DEMOLITION
REFLECTED
CEILING PLAN
JMFMRC
P R
O J E
C T
:2
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 DEMOLITION REFLECTED CEILING PLAN
LEVEL 1 DEMO RCP KEYNOTES
1 DEMO (E) GWB CEILING
DEMO ALL LIGHT FIXTURES
REMOVE ALL ASSOCIATED ELECTRICAL WIRES, BACK TO PANEL
2 NOT INCLUDED IN SCOPE OF WORK
1 1
B
B
C
C
D
D
2 2
3 3
4 4
IT ROOM
OFFICE
CONFERENCE
HALL
300A
HALL
300A
R.R.
FOYER
R.R.
301 PANTRY
OFFICE
" M
IN
CLOSET
CLOSET
MECH
307A
(E)I.1I4.2
"3
I4.1
307A
3' - 8"
(E)E.1
(E)I.1
I4.1
8 1
A-511
SIM
A-511
SIM
M
IN
'X' INDICATES FIRE RATED
LOCATION DESIGNATION
SOUND INSULATION (WHEN PRESENT)
ASSEMBLY HT. (IF NOT FULL HT.)
KEY FOR ASSEMBLY TYPES
A6.1X - S
0'-0"
INTERIOR WALL INFILL
SCALE: 1 1/2" = 1'
(E)I.1
EXTERIORINTERIOR
EXTERIOR WALL IFILL
SCALE: 1 1/2" = 1'
(E)E.1
INTERIOR WALL
SCALE: 1 1/2" = 1'
I4.2
INTERIOR WALL ON 6" CURB
SCALE: 1 1/2" = 1'
I4.1
WALL ASSEMBLY APPROX. WIDTH
GWB (THICKNESS TO MATCH EXISTING)
VAPOR BARRIER (TIE INTO EXISTING)
BATT INSULATION
2X STUD (SIZE TO MATCH EXISTING)
PLYWD SHEATHING (THICKNESS TO MATCH EXISTING)
WEATHER BARRIER (TIE INTO EXISTING)
FINISH (MATERIAL AND PAINT TO MATCH EXISTING
DIRECTLY ADJACENT)
FINISH PER PLAN
NUMBER IN WIDTH SERIES
LOCATION DESIGNATIONS
E: EXTERIOR WALL TYPE
I: INTERIOR WALL TYPE
R: FLOOR TYPE
F: ROOF TYPE
INTERIORINTERIOR
GWB (THICKNESS TO MATCH EXISTING)
2X WOOD STUD @ 16" O.C. (SIZE TO MATCH EXISTING)
GWB (THICKNESS TO MATCH EXISTING)
INTERIORINTERIOR
5/8" GWB
2x4 WOOD STUD @ 16" O.C.
5/8" GWB
FINISH PER PLAN
FINISH PER PLAN
FINISH PER PLAN
FINISH PER PLAN
6"x 6" CONCRETE CURB @ FINISH FLOOR, FINISH PER PLAN
INTERIORINTERIOR
5/8" GWB
2x4 WOOD STUD @ 16" O.C.
5/8" GWB
FINISH PER PLAN
FINISH PER PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-111
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1 FLOOR
PLAN
JMFMRC
P R
O J E
C T
:2
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 PLAN
LEVEL 1 FLOOR PLAN KEYNOTES
1 NEW SERVER RACKS, O.F.O.I.
2 ADD KEYCARD ACCESS TO NEW DOOR OPENING
3 (E) WATER HEATER
4 NOT INCLUDED IN SCOPE OF WORK
5 THRESHOLD TO BE ON TOP OF 6" CONCRETE CURB
6 INFILL (E) WINDOW OPENING TO MATCH (E) EXTERIOR WALL
ASSEMBLY DIRECTLY ADJACENT. PAINT TO MATCH (E)
EXTERIOR WALL ADJACENT
7 (E) FIBER OPTIC POINT OF ENTRY
8 GIS RACK, O.F.C.I.
9 END OF NEW WALL TO BE ALIGNED WITH EXISTING
10 ALIGN NEW WALL WITH EXISTING FINISH SURFACE
11 INSERT GAS FIRE SUPPRESSION SYSTEM. STAND-ALONE
SYSTEM TO BE DESIGN-BUILT BY FIRE SUPPRESSION
CONTRACTOR.
1 1/2" = 1'-0"
ASSEMBLIES
1 BULLETIN 1 03/24/26
1 1
B
B
C
C
D
D
2 2
3 3
4 4
IT ROOM
OFFICE
CONFERENCE
FOYER
HALL
300A
R.R.
PANTRY
OFFICE
R.R.
HALL
300A
PT-1
8' - 0"
ACT-1
7' - 6"
CLOSET
CLOSET
302 1
BOS
(E)SLOPED
CEILING
(E )S
LO
P
E
IL
IN
G
(E)SLOPED
CEILING
(E )S
LO
P
IL
IN
G
(TYP.)
CEILING PLAN LEGEND
GWB-1
GYPSUM WALL BOARD
PT-1
X'-X"
HEIGHT A.F.F.
FINISH, REFER TO FINISH SCHEDULE
ACT-1
ACOUSTIC CEILING TILE
CEILING TAG LEGEND
2"
3"
2"
CHANNEL MOLDING
FASCIA
MOLDING
POP RIVET THIS
SIDE ONLY
STABILIZER BAR, OR OTHER
SUITABLE SYSTEM, TO KEEP
PERIMETER COMPONENTS FROM
SPREADING APART.
MAIN BEAM
MAIN BEAMS OR
CROSS TEES
SEISMIC SEPARATION JOINT
SEISMIC DETAILS
PERIMETER
SUPPORT WIRES # 12
NOTES:
1. CEILING AREAS OVER 1,000 SF MUST HAVE
HORIZONTAL RESTRAINT WIRE OR RIGID BRACING
2. USE HEAVY DUTY GRID SYSTEM
3. USE PERIMETER SUPPORT WIRES
4. CEILINGS WITHOUT RIGID BRACING MUST HAVE 2"
OVERSIZED TRIM RINGS FOR SPRINKLERS AND
OTHER PENETRATIONS
5. GRID MUST BE ATTACHED TO 2 ADJACENT WALLS,
OPPOSITE WALLS MUST HAVE 3/4" CLEARANCE
6. MIN 2" WALL MOLDING
"ATTACHED""UNATTACHED"
ANGLE
MOLDING
8" M
AX.
8" M
AX.
MIN
1 1/2
3/4"MIN AT UNATTACHED WALLS
MIN 2"
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-121
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1
REFLECTED
CEILING PLAN
JMFMRC
P R
O J E
C T
:2
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 REFLECTED CEILING PLAN
LEVEL 1 RCP KEYNOTES
1 NOT INCLUDED IN SCOPE OF WORK
2 PATCH AND PAINT (E) GWB TO ACCOMIDATE FOR WING WALL
3 ALL LIGHTING, PER ELECTRICAL
1 1/2" = 1'-0"
HUNG CEILING DETAILS - SEISMIC
1 1
VCT-1
N/A
PT-1
PT-1
PT-1
PT-1
RB-1
B
B
C
C
D
D
2 2
3 3
4 4
IT ROOM
PANTRY
A-1312
MECH
307A
VS-1
N/A
PT-1
PT-1
PT-1
PT-1
VS-1
LVP-1
N/A
PT-1
PT-1
PT-1
PT-1
RB-1
LA
M
-2
CPT-1
LVP-1
LAM-1
LAM-2
LAM-1
A-131
Sim
39" 39" 39"
1. COUNTERTOP PER INTERIOR DRAWINGS
2. 3/4" MDF BACK SPLASH LAMINATE CLAD
3. CABINET AND DRAWER PULLS, STAINLESS STEEL
4. 3/4" MELAMINE COVERED ADJUSTABLE SHELF
ON RECESSED STANDARDS
5. USE CONCEALED EUROPEAN HINGES
6. FLUSH OVERLAY LAMINATE DOORS AND
DRAWER FRONTS, SEE INT. ELEVATIONS
7. 3/4" MELAMINE FACING - ALL EXPOSED
INTERIOR SURFACES
9. BASE FINISHED AS SCHEDULED
P E
R E
LE
V
A T
IO
N
S
1' - 0"
2' - 0"
P E
R E
LE
V
A T
IO
N
S
8. DRAWER BODIES 1/2" MELAMINE FACED W/
FULL EXTENSION GLIDES
/2
/8
/2
/1
(E) CARPET
EXISTING SUB FLOOR
VINYL TRANSITION STRIP
LVP RESILIENT FLOORING
EQ EQ
TRANSITION @
CENTERLINE OF DOOR @
DOOR LOCATIONS
(E) CARPET
EXISTING SUB FLOOR
VINYL TRANSITION STRIP
VCT
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-131
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1 FLOOR
FINISH PLAN
JMFMRC
P R
O J E
C T
:2
FINISH SCHEDULE (SUBMIT FINISH SAMPLES FOR OWNER APPROVAL, TYPICAL)
TAG KEY COLOR MANUFACTURER STYLE NOTE
ACT-1 ACOUSTICAL CEILING TILE WHITE ARMSTRONG 24 x 48 ITEM NO 1943 TECHZONE WITH ULTIMA FIELD PANELS, SQUARE LAY-IN
CPT-1 EXISTING CARPET EXISTING EXISTING EXISTING EXISTING
LAM-1 LAMINATE CABINETRY 931-WG LIGHT ASH LAMINART VENEER ART WEATHERD GRAIN FINISH FLAT CUT/RANDOM MATCHED
LAM-2 LAMINATE COUNTERTOP P271 CA FRESH MIST ABORITE ADD MATCHING EDGE BANDING
LVP-1 VINYL PLANK NOLV252005 GRADE TAS CONTRACT LEVELS 2.5 20 MIL GLUE DOWN USE MANUFACTURE RECOMENDED GLUE AND SUBFLOOR PREP
PT-1 PAINT SW7005 PURE WHITE SHERWIN WILLIAMS SATIN
RB-1 RUBBER BASE 110 BROWN ROPPE 700 SERIES 4" STANDARD TOE BASE 5/8"
VCT-1 VINYL COMPOSITE TILE (ANTI-STATIC) 51953 EXCELON SDT PEARL WHITE ARMSTRONG 12"x12"x1/8"
VS-1 VINYL SHEET 952 BEACHY ROPPE OBSIDIAN VINYL SHEET 6" FLASH COVE BASE WITH STAINLESS STEEL CAP
FLOOR
WIN
SILL
WALL
WALL
WALL
WALL
NOTES
BASE
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 FLOOR FINISH PLAN
ROOM FINISH KEY
FINISH PLAN KEYNOTES
1 REFRIGERATOR FROM EXISTING KITCHENETTE
2 MATCH PAINT WHERE NEW WALL MEETS EXISTING, OTHERWISE
BREAK COLOR AT INSIDE CORNER WHEN POSSIBLE
3 PROVIDE FINISH PANEL FOR EXPOSED ENDS OF UPPERS AND BASE
CABS
3/8" = 1'-0"
PANTRY
3/4" = 1'-0"
CABINET SECTION
1 1/2" = 1'-0"
TRANSITION-CPT-1/LVP-1
1 1/2" = 1'-0"
TRANSITION CPT-1/VCT-1
(E) SLAB
(N) CONCRETE CURB W/ #4 CONTINUOUS BAR
THROUGH CENTER OF CURB
6"
TYP
R 1"
#4X6" REBAR WITH 3" MINIMUM EMBED DEPTH WITH
HILTI-HY 200-R V3 EPOXY @ 48" O.C. AND EACH END/CORNER
E M
B E
D D
E P
T H
PRESSURE TREATED SILL PLATE WITH
SIMPSON 3" LONG PDPA POWER-
DRIVEN PINS @ 16" ON CENTER
2X DOUGLAS FIR/LARCH #2
STUDS @ 16" ON CENTER
NOTES:
1. ENSURE PROJECT CONCRETE MIX DESIGN MEETS THE FOLLOWING CRITERIA:
a. 28-DAY MINIMUM COMPRESSIVE STRENGTH - 4000 PSI
b. SLUMP (MAXIMUM/MINIMUM) - 5 INCHES/3 INCHES
c. MAXIMUM WATER TO CEMENT RATIO - 0.45
d. MAXIMUM AIR CONTENT PERCENTAGE - 3%
2. ALL REINFORCING BARS SHALL BE DEFORMED BARS AT LEAST GRADE 60.
3. PROVIDE A MINIMUM CLEAR COVER OF 3/4" FOR ALL REINFORCING BARS.
4. PRESSURE TREATED SILL TO MEET THE PRESERVATION REQUIREMENTS OF
AWPA U1
WALL FINISH PER PLAN
(E) ROOF FRAMING
B: PERP TO ROOF FRAMING
KEY CURB INTO (E) SLAB
DROPPED CEILING PER PLAN
EXISTING ROOF FRAMING
/2
G
A P
2X BLOCKING @ 24" O.C.
DS CLIPS @ 16" O.C.
TO FIRST FASTENER
16"
A: PAR TO ROOF FRAMING
DROPPED CEILING PER PLAN
TO FIRST FASTENER
16"
DS CLIPS @ 16" O.C.
/2
G
A P
SDPW19600 SCREW TO EACH
FRAMING MEMBER (24" O.C. MAX)
/4
/4
SDPW19600 SCREW TO EACH
BLOCKING MEMBER (24" O.C. MAX)
NOTE: DO NOT PENETRATE BOTTOM SURFACE OF (E) SLAB
WATERPROOFING AND SUBSLAB PLUMBING.
EXISTING SIDING
METAL OVER BLOCK, PAINTED TO
MATCH EXISTING FLASHING/SIDING
MOUNTING BLOCK
FOR PENETRATION
FIXTURE (ROOF DRAIN
NOZZLE SHOWN AS
EXAMPLE)
FLASHING, PAINTED TO MATCH
EXISTING FLASHING/SIDING
SIDING MANUFACTURER
APPROVED SEALANT AROUND
PERIMETER OF BLOCK
NOTE:
1. SEE PLUMBING FOR EXTERIOR PLUMBING FIXTURES.
2. SEE ELECTRICAL FOR EXTERIOR ELECTRICAL FIXTURES.
EXISTING SIDING
METAL FLASHING, PAINTED TO MATCH EXISTING FLASHING/SIDING
WRB, WRAP OVER FLASHING
BACKER ROD
AND SEALANT
METAL OVER BLOCK, PAINTED TO MATCH EXISTING FLASHING/SIDING
MOUNTING BLOCK
(FACE OF BLOCK TO BE FLUSH WITH FACE OF SIDING)
PENETRATION FIXTURE FASTENED TO BLOCK (ROOF
DRAIN NOZZLE, ELECTRICAL BOX, HOSE BIB, ETC.)
SIDING MANUFACTURER APPROVED SEALANT AND
BACKER ROD
A
A
ELEVATION SECTION A
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-511
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
SECTION
DETAILS
P R
O J E
C T
:2
1 1/2" = 1'-0"
NEW CURB AND WALL SUPPORT DETAIL
1 1/2" = 1'-0"
SIDING PENETRATION DETAIL
INTERIOR FLUSH
PANEL DOOR
S E
E S
C H
E D
U
LE
SEE SCHEDULE
WD - WOOD
DOOR
WD TRIM TO MATCH EXISTING
WD JAMB
INSULATE ALL VOIDS, SHIM
AS REQ'D FOR INSTALLATION
PERIMETER SEAL TYP.
WALL TYPE PER PLAN
WD TRIM TO MATCH EXISTING
DOOR
WD JAMB
INSULATE ALL VOIDS, SHIM
AS REQ'D FOR INSTALLATION
PERIMETER SEAL TYP.
WALL TYPE PER PLAN
WD TRIM TO MATCH EXISTING WD TRIM TO MATCH EXISTING
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
A-601
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
DOOR
SCHEDULES
JMFMRC
P R
O J E
C T
:2
DOOR SCHEDULE
DOOR FROM TO SIZE FIRE RATING ELEVATION TYPE DOOR MAT. FRAME MAT. GLAZING/LITES HARDWARE DOOR STOP (W:WALL, F:FLOOR) REMARKS
307 HALL 300A IT ROOM 307 3' 0" x 6' 8" x 1 3/4" N/A A WD WD N/A HDW-1
STOREROOM
W KEYCARD ACCESS
307A MECH 307A IT ROOM 307 2' 6" x 6' 6" x 1 3/4" N/A A WD WD N/A HDW-1
STOREROOM
W PLACED ON 6" CONCRETE CURB
0 4' 8'2' 1/4" = 1'-0"
DOOR LEGEND
DOOR HARDWARE
HDW HARDWARE
HDW-1 STOREROOM 1 1/2 PR BUTTS
1 LOCKSET ANSI F86/
BHMA D
1 WALL STOP
1 SET SILENCERS
GENERAL NOTES:
1. HARDWARE:
HINGES: BY STANLEY, HAGER OR APPROVED
EQUAL.
LOCKSETS: BY SARGENT, ADAMS-RITE, SCHLAGE
OR APPROVED EQUAL .
CLOSER: BY LCN, DORMA OR APPROVED EQUAL.
WEATHERSTRIPPING, THRESHOLD, AND
SWEEP: BY PEMKO OR APPROVED EQUAL
KEYWAY - TO BE MATCH EXISTING
2. CONTRACTOR RESPONSIBLE TO NOTIFY
DESIGNER OF SUBSTITUTIONS FOR NOTED
HARDWARE.
3. DOOR & DOOR HARDWARE SUBMITTAL
REQUIRED.
4. HOLLOW METAL DOORS: 18 GAUGE METAL.
HOLLOW METAL DOOR FRAMES: 16 GAUGE
AND WELD UP.
HARDWARE COLOR: BRUSHED STAINLESS STEEL
1 1/2" = 1'-0"
INT. WD JMB DTL
1 1/2" = 1'-0"
INT. WD HD DTL
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
C
LT
CHWS
DV-E
CWR
CWS
HWR
HWS
DV-I
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
DIRECT VENT - EXHAUST
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
DIRECT VENT - INTAKE
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
CAP
REF-HG REFRIGERANT-HOT GAS
PLUMBING AND PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL DRAWING SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPE RISE
PIPE DROP
PIPE TEE
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
Room
16"x8"
16"/8"
(E)
B
D
C
16"Ø
E/A
O/A
T/A
L/A
R/A
S/A
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
THROW-150FPM/ 100FPM/ 50FPM
NECK SIZE / MODULE SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG
(WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG
(WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR
SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR
RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG
(DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE) NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM LENGTH) /
NECK SIZE
DUCT BEING
DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE
AIR DUCT RISE
ROUND RETURN/TRANSFER
AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF
AIR DUCT RISE
ROUND EXHAUST/RELIEF
AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
G-E/A GREASE EXHAUST AIR
S-E/A SMOKE EXHAUST AIR
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
FLUE EXHAUST GAS FLUE
C/A COMBUSTION AIR
S-O/A CONDITIONED OUTSIDE AIR
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
AC AIR CONDITIONING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
BP BOILER PUMP
CC COOLING COIL
CH CHILLER
CT COOLING TOWER
CU CONDENSING UNIT
CWP CONDENSER WATER PUMP
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DCP DOMESTIC WATER CIRCULATING PUMP
DF DUCT FURNACE
DH DUCT HEATER
EF EXHAUST FAN
EH ELECTRIC HEATER
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
F FURNACE
FC FAN COIL
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HP HEAT PUMP
HS HYDRAULIC SEPARATOR
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HRV HEAT RECOVERY VENTILATOR
MAU MAKE-UP AIR UNIT
P PUMP
RF RETURN FAN
RTU ROOF TOP UNIT
SD SLIM DUCT
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
WH WATER HEATER
WM WALL MOUNT
EQUIPMENT ABBREVIATIONS
48"x2 1/2"
400LS-1
8"x8"/24"x24" 300*S-1
400* 12"Ø/---
S-1
LINEAR BAR GRILLE
LINEAR SLOT DIFFUSER
PERFORATED DIFFUSER
WITH DEFLECTORS
ROUND DIFFUSER WITH
ADJUSTABLE PATTERNS
LOUVERED DOUBLE
DEFLECTION GRILLE
12"x10"/---
500S-2
TYPE (SEE SCHEDULE)
10"Ø/24"x24" H-5/7/1422
400*S-2
3-CONE DIFFUSER
THROW PATTERN
MAX NC RATING
1 / 4' - 0" /9"/5"
200LS-2
8' - 0" AFF
1 / 4' - 0" /9"/5"
200LS-2
18' - 0"
1 / 4' - 0" /9"/5"
200LS-2
SECTION TOTAL TRACK LENGTH
12"x10"/24x12 500R-2
LOUVERED GRILLE
12"x10"/24x24
500R-2
EGGCRATE RETURN
GRILLE
BOTTOM OF EQUIPMENT
ELEVATION
590 lb
RTU-XX
4.0 ton
RTU-XX
115 CFH
RTU-XX
HEATING COIL FLOW
OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY ROOFTOP UNIT
PIPE ACCESSORY TAGS
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
EQUIPMENT ID
SYMBOL
BBB
INLET COLLAR DAMPER
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
VAV-XX
10' - 0"
(E)VAV-XX
VAV-XX
Htg: 3.7 GPM
VAV-XX
GWR GEOTHERMAL WATER RETURN
GWS GEOTHERMAL WATER SUPPLY
BUILDING MECHANICAL SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES:
• 2025 OREGON MECHANICAL SPECIALTY CODE
• 2023 OREGON PLUMBING SPECIALTY CODE
• 2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
CODE COMPLIANCE
PIPING INSULATION SCHEDULE - INTERNATIONAL ENERGY CONSERVATION CODE
FLUID OPERATING
TEMPERATURE RANGE AND
USAGE [°F]
CONDUCTIVITY
[BTU-IN/HR-FT2-°F]
MEAN RATING
TEMPERATURE [°F]
INSULATION CONDUCTIVITY NOMINAL PIPE OR TUBE SIZE [INCHES]
< 1
1 TO
< 1-1/2
1-1/2
TO < 4
4 TO < 8 >=8
141 - 200
105 - 140
40 - 60
0.25 - 0.29
0.21 - 0.28
0.21 - 0.27
1.5
1.0
0.5
1.5
1.0
0.5
2.0
1.5
1.0
2.0
1.5
1.0
2.0
1.5
1.0
F
S
M
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
PIPE SYMBOLS
DAMPER TAGS
MECHANICAL CONTROL DEVICE TAGS
ABBREVIATIONS
1. INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE BY A
LICENSED CONTRACTOR PER THE STATE BUILDING, MECHANICAL
ENERGY, FIRE, PLUMBING AND HEALTH CODES, AND REGULATIONS
AS ADOPTED BY LOCAL JURISDICTIONS.
2. ALL EQUIPMENT SHALL BE THE CAPACITY AND TYPE AS SHOWN ON
THE EQUIPMENT SCHEDULE AND SHALL BE THE LISTED
MANUFACTURER AND MODEL NUMBER OR SHALL BE AN EQUAL
APPROVED BY THE OWNER/ENGINEER.
3. CONTRACTOR IS TO BRING UP THE DISCREPANCIES AND ITEMS
WHICH ARE NOT SPECIFICALLY CALLED FOR OR SHOWN BUT ARE
REQUIRED FOR A COMPLETE MECHANICAL SYSTEM. ALL SUCH
ITEMS REQUIRED FOR A COMPLETE SYSTEM READY FOR THE
OWNER'S BENEFICIAL USE SHALL BE FURNISHED AND INSTALLED
INCLUDING ALL SUCH DISCREPANCY ITEMS MENTIONED ABOVE,
AT NO ADDITIONAL COST TO THE OWNER AND PER LOCAL CODES,
MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE
STANDARDS WITH THE ARCHITECT/ENGINEER'S APPROVAL.
4. ALL EQUIPMENT SUPPLIED FOR THESE SPECIFICATIONS SHALL BE
FREE FROM DEFECTS IN MATERIAL, WORKMANSHIP, AND TITLE,
AND SHALL BE OF THE KIND AND QUALITY DESCRIBED HEREIN. IF
IT APPEARS WITHIN ONE YEAR FROM DATE OF FINAL ACCEPTANCE
THAT EQUIPMENT DOES NOT MEET THE WARRANTIES ABOVE, THE
CONTRACTOR SHALL IMMEDIATELY CORRECT ANY DEFECT AND
SHALL RESTORE THE SYSTEM TO THE ORIGINAL SATISFACTORY
CONDITIONS AT HIS EXPENSE. THE FOREGOING WARRANTY IS
EXCLUSIVE AND IN LIEU OF OTHER WARRANTIES, WHETHER
WRITTEN, ORAL, IMPLIED, OR STATUTORY. NO WARRANTY OR
MERCHANT ABILITY OF FITNESS FOR PURPOSE SHALL APPLY (THE
WARRANTY SHALL START FROM THE TIME OF
ARCHITECT/ENGINEER'S FINAL ACCEPTANCE).
5. COORDINATE THE CONSTRUCTION SCHEDULE WITH THE GC AND
PERFORM ALL REQUIRED WORK IN STRICT ACCORDANCE WITH
THE OWNER'S SCHEDULE.
6. MECHANICAL CONTRACTOR SHALL PAY FOR AND OBTAIN ALL
REQUIRED PERMITS AND CERTIFICATES REQUIRED BY THE
AUTHORITIES HAVING JURISDICTION.
7. HVAC NOTES:
A. PROVIDE FLEXIBLE CONNECTION IN ALL DUCTS CONNECTING
TO AIR MOVING EQUIPMENT AS CLOSE TO FAN AS POSSIBLE.
FLEXIBLE CONNECTION SHALL CONSIST OF 6" OR MORE OF
AIR TIGHT, FIRE PROOF FLEXIBLE NEOPRENE COATED WOVEN
FIBROUS GLASS MATERIAL. VENT FABRICS, INC. OR
APPROVED EQUAL.
B. ALL MAIN TRUNK AND BRANCH TAKEOFF DUCTWORK SHALL
BE SHEET METAL. FLEXIBLE DUCT IS ALLOWED ON LAST 6'
SERVING GRDs. FIBERGLASS DUCTWORK SHALL NOT BE
USED.
C. ALL SUPPLY & RETURN FLEXIBLE DUCTS CONNECTING TO
GRILLES, REGISTERS AND DIFFUSERS SHALL BE CONSTRUCTED
OF DOUBLE LAMINATION OF POLYESTER ENCAPSULATED
STEEL WIRE HELIX FOR INNER CORE HIGH DENSITY
FIBERGLASS INSULATION AND GRAY POLYESTER FILM WITH
SPIRAL REINFORCEMENTS, EQUAL TO ATCO-70 SERIES (MIN.
POS. PRESS. = 6' W.C. NEG. PRESS. = 0.75" W.C. & R=5.79).
D. SEAL ALL DUCTWORK JOINTS PER SMACNA CLASS C FOR
SYSTEMS UP TO 2 IN W.G. AND SEAL ALL JOINTS AND SEAMS
PER SMACNA CLASS B FOR SYSTEMS GREATER THAN 2 IN W.G.
E. ALL EQUIPMENT, DUCTWORK AND PIPING SHALL BE
STRUCTURALLY SUPPORTED AND SECURELY FASTENED TO
BUILDING STRUCTURE IN AN ACCEPTABLE MANNER TO
OWNER, ARCHITECT, ENGINEER AND LOCAL JURISDICTION
AND SHALL BE SEISMICALLY BRACED PER THE SMACNA
AND/OR REQUIRED BY LOCAL JURISDICTIONS.
F. PROVIDE LOCKABLE VOLUME DAMPERS IN ALL TAKEOFFS.
G. DUCT HANGERS, SUPPORTS AND METHODS OF INSTALLATION
SHALL CONFORM TO ASHRAE & SMACNA
RECOMMENDATIONS.
H. DUCT SIZES SHOWN ON PLANS INDICATE INSIDE FREE AREA.
I. ALL DUCTWORK SHALL BE CLASS-1 AIR DUCT AS APPROVED
BY U.L.-181.
J. ALL SQUARE ELBOWS SHALL HAVE TURNING VANES.
K. DUCT INSULATION SHALL BE PROVIDED PER DUCT
INSULATION SCHEDULE ON M0.00.
8. ALL FIRE RATED STRUCTURE SHALL BE FIRE DAMPERED AS
REQUIRED BY THE JURISDICTION.
9. FLEXIBLE DUCTS SHALL HAVE MAXIMUM 6 FEET LENGTH UNLESS
SHOWN OTHERWISE AND SHALL NOT PENETRATE THROUGH ANY
FIRE RATED WALLS. DO NOT INSTALL FLEXIBLE DUCTS WITHIN 6
FEET OF HEATING ELEMENT.
10. HVAC SYSTEM SHALL BE STARTED UP AND FUNCTIONALLY TESTED
BY MECHANICAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL CONFIRM THAT ALL HVAC SYSTEMS ARE READY FOR
TESTING, ADJUSTING, AND BALANCING. HVAC SYSTEMS SHALL BE
TESTED, ADJUSTED, AND BALANCED (TAB) BY CONTRACTOR
CERTIFIED BY THE AABC, NEBB, OR OTHER APPROVED AGENCY.
REFRIGERATION PIPING SHALL BE TESTED UNDER PRESSURE AND
PROVEN TO BE LEAK FREE. REFRIGERATION SYSTEM SHALL BE
STARTED UP AND BROUGHT DOWN TO DESIGN TEMPERATURE.
11. MECHANICAL, HVAC, AND PLUMBING ELEMENTS SHALL AT NO
TIME COME IN CONTACT WITH CEILING CONSTRUCTION EXCEPT
AS NECESSARY PENETRATIONS MAY REQUIRE. ESCUTCHEONS
SHALL BE USED ON ALL VISIBLE PENETRATIONS
12. ACCESS SHALL BE PROVIDED BY GC AS REQUIRED FOR
INSTALLATION AND MAINTENANCE OF MECHANICAL,ELECTRICAL,
AND OTHER ELEMENTS WITHIN CEILING SPACE AND AS REQUIRED
BY CODE. LOCATIONS FOR SPECIAL ACCESS DOORS, HATCHES,
ETC. SHALL BE COORDINATED WITH OTHER TRADES.
13. INSPECTIONS, AS REQUIRED BY LOCAL AUTHORITIES, SHALL BE
COORDINATED BY GC PRIOR TO CLOSING OF CEILING.
14. SHOP DRAWINGS FOR ALL RELATED TRADES (PLUMBING, HVAC)
SHALL BE SUBMITTED FOR REVIEW/APPROVAL PRIOR TO
MANUFACTURING AND INSTALLATION.
15. ALL HVAC ELEMENTS SHALL MATCH ADJACENT WALL OR CEILING
FINISH COLOR, INSTALLED FLUSH AND TRUE AND CENTERED
WITHIN THE CEILING GRID. LOCATIONS SHALL BE PER APPROVED
MECHANICAL PLANS.
16. INSULATION OF COLD WATER LINES SHALL BY PROVIDED TO
PREVENT CONDENSATION DAMAGE AND IN OBSERVANCE OF
ENERGY CONSERVATION PRACTICES, HOT WATER HEATING LINES
SHALL BE INSULATED - SEE SPECIFICATIONS.
17. CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE
SENSORS IN ACCESSIBLE SPACES AT 4'-0" AND UNITS IN ALL OTHER
SPACES AT 5'-0". UNITS AT 5' SHALL BE MOUNTED ALIGNED
VERTICALLY WITH LIGHT SWITCHES WHERE APPLICABLE.
LOCATIONS PER MECHANICAL PLAN AND TO BE COORDINATED BY
GC WITH OTHER TRADES.
18. ALL BROCHURES, OPERATING MANUALS, CATALOGS, SHOP
DRAWINGS, ETC. SHALL BE TURNED OVER TO THE OWNER AT JOB
COMPLETION. ALL PRODUCT WARRANTY REGISTRATION CARDS,
APPLICATIONS, AND CERTIFICATES SHALL BE COMPLETED AND
TURNED OVER TO THE OWNER.
19. THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON
HVAC EQUIPMENT AFTER ALL DUST PRODUCING CONSTRUCTION
HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.
GENERAL MECHANICAL NOTES
V-E/A VENTILATION EXHAUST AIR
D-E/A DRYER EXHAUST AIR
RTU-XX
VAV-XX
TEMPERATURE & HUMIDITY SENSOR
TEMPERATURE SENSOR
THERMOSTAT
SENSOR
MANUAL SWITCH
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
NITROGEN DIOXIDE SENSOR
HUMIDITY SENSOR
HUMIDISTAT
CONTROLLER
LOW VOLT TIMER
NATURAL GAS
CONDENSATE DRAINAGECD
NG
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
M-102
LEVEL 1 DISCIPLINE DESIGNATOR
LEVEL 2 DISCIPLINE DESIGNATOR
LEVEL SEQUENCE NUMBER
PLAN TYPE SEQUENCE NUMBER
SHEET TYPE DESIGNATOR
SILETZ, OREGON
ANNUAL DESIGN CONDITIONS: ASHRAE FUNDAMENTALS 2025
WEATHER STATION - NEWPORT SOUTH BEACH JETTY, OR WMO# 994026
ELEVATION: 7' LAT: 44.62N LONG: 124.05W
WINTER: 32.0 (99.6%)
SUMMER: 65.4 DRY BULB (0.4%)
57.9 WET BULB (0.4%)
INDOOR DESIGN CONDITIONS:
WINTER: 70 ± 2º F
SUMMER: 75 ± 2º F
HVAC DESIGN CRITERIA
DUCT INSULATION SCHEDULE
DUCT SYSTEM
SUPPLY AIR
OUTSIDE AIR
FRESH AIR
MIN. R-12 INSULATION & VAPOR
BARRIER. PRE-ENGINEERED
Q-DUCT OR SIMILAR
OUTSIDE BUILDING ENVELOPE,
EXPOSED TO ENVIRONMENT
OUTSIDE BUILDING ENVELOPE,
WITHIN BUILDING
WITHIN THE BUILDING
ENVELOPE
RETURN AIR
RELIEF AIR
TRANSFER AIR
GENERAL EXHAUST AIR
MIN. R-12 INSULATION & VAPOR
BARRIER. PRE-ENGINEERED
Q-DUCT OR SIMILAR
MIN. R-6 INSULATION & VAPOR
BARRIER
MIN. R-6 INSULATION & VAPOR
BARRIER
MIN. R-6 INSULATION & VAPOR
BARRIER WHERE UNCONDITIONED
MIN. R-6 INSULATION WHERE
UNCONDITIONED
GREASE EXHAUST AIR N/A N/A
MIN. R-6 GREASE DUCT FIRE
INSULATION. FYREWRAP ELITE
OR SIMILAR
RETURN AIR
PLENUMS @ GRILLES
N/A
LINE GRILLE PLENUM AND FIRST 6
FT OF DUCT MIN. R-6 INSULATED
LINE GRILLE PLENUM AND FIRST 6
FT OF DUCT MIN. R-6 INSULATED
REMARKS:
1. ALL DUCT DIMENSIONS INDICATE INSIDE FREE DIMENSIONS AND DO NOT INCLUDE INSULATION THICKNESS.
2. THE 6' OF EXHAUST DUCT NEAREST TO THE EXTERIOR TO BE INSULATED WITH MIN. R-6 INSULATION (1 1/2" THICKNESS, 0.24 K VALUE).
2021 INTERNATIONAL ENERGY CONSERVATION CODE NOTES
1. PROVIDE COMMISSIONING PLAN IN ACCORDANCE WITH INTERNATIONAL ENERGY CONSERVATION CODE SECTION C408.2.1.
2. PROVIDE COMMISSIONING COMPLIANCE REPORT IN ACCORDANCE WITH INTERNATIONAL ENERGY CONSERVATION CODE SECTION
C407.3.1 & C407.3.2.
3. PROVIDE SYSTEMS TESTING AND BALANCING IN ACCORDANCE WITH INTERNATIONAL ENERGY CONSERVATION CODE SECTION
C408.2.2.
A. PROVIDE TAB REPORT FOR ALL AIR MOVING EQUIPMENT TO ENGINEER OF RECORD. ALL AIRFLOWS INDICATED ON PLANS ARE
UNDER NORMAL OPERATING CONDITIONS WITH ALL SYSTEMS RUNNING IN OCCUPIED MODE AT MINIMUM OUTSIDE AIR.
4. PROVIDE SYSTEMS, EQUIPMENT, AND CONTROLS FUNCTIONAL TESTING IN ACCORDANCE WITH INTERNATIONAL ENERGY
CONSERVATION CODE SECTION C408.2.3.
5. PROVIDE SUPPORTING DOCUMENTATION IN ACCORDANCE WITH INTERNATIONAL ENERGY CONSERVATION CODE CHAPTER 1
CHECKLIST, INCLUDING OPERATION AND MAINTENANCE MANUALS, HVAC CONTROL SYSTEM MAINTENANCE AND CALIBRATION
INFORMATION, HVAC CONTROL SEQUENCE OF OPERATIONS, COMMISSIONING REPORT, AND RECORD DRAWINGS.
6. PROVIDE OWNER SYSTEMS OPERATION TRAINING IN ACCORDANCE WITH INTERNATIONAL ENERGY CONSERVATION CODE SECTION
C103.6.
7. MOTORS SHALL COMPLY WITH SECTION C403.8 OF THE INTERNATIONAL ENERGY CONSERVATION CODE. FOR ADDITIONAL DETAILS, SEE EQUIPMENT SCHEDULES CONTAINED WITHIN THIS DRAWING SET.
8. SYSTEMS SHALL BE INSULATED AS PRESCRIBED IN SECTION C403.12. FOR ADDITIONAL DETAILS, SEE DUCTWORK AND PIPING
SPECIFICATION MATRICES CONTAINED WITHIN THIS DRAWING SET.
PROJECT GENERAL NOTES
* REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.
* THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
FIELD VERIFYING, PRIOR TO FINAL BID, ALL EXISTING
CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS
WITHIN TENANT SPACE AND WITHIN CLOSE PROXIMITY OF
TENANT SPACE.
* WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF
CONSTRUCTION, PREVENT CONSTRUCTION DEBRIS FROM
ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO
START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
* COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT,
LIGHTS, CABLE TRAY, STRUCTURE, AND EQUIPMENT TO
PREVENT CONFLICTS.
* THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE
CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY
THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE
REASONABLY ANTICIPATED INCLUDING, BUT NOT LIMITED TO
ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND
OTHER SYSTEMS INVOLVED ON THIS PROJECT.
* FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING
SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF
APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING
BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODE
AND INTERNATIONAL MECHANICAL CODE.
* ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0"
FROM EDGE OF ROOF.
* LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT
AWAY FROM THE SPACE ABOVE ELECTRICAL PANELS.
TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
* FIRE SEAL AROUND DUCT AND PIPING PENETRATIONS OF FIRE
RATED WALLS. REFER TO SPECIFICATION.
* PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND
DUCTS THROUGH FOUNDATIONS, FLOORS, WALLS, AND ROOF.
* ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT
TO MECHANICAL EQUIPMENT.
* REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C.
CONDENSATE DRAIN PIPING.
* PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF
FLOW UNTIL ANOTHER SIZE IS SHOWN.
* FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT
SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES,
AND SPECIFICATIONS.
* INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE
RESPECTIVE MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS, AT A LEVEL OF QUALITY AND WORKMANSHIP
CONSISTENT WITH THE SPECIFICATIONS.
* LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS
INDICATED ON THE DRAWING, ARE APPROXIMATE AND
SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL
BE COORDINATED WITH ALL OTHER TRADES TO AVOID
INTERFERENCE IN THE FIELD.
* INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS
PRACTICAL IN ROOMS WITHOUT CEILINGS U.N.O.
MECHANICAL SHEET INDEX
M-001 MECHANICAL TITLE SHEET
M-111 LEVEL 1 HVAC PLAN
M-141 ROOF HVAC PLAN
M-601 MECHANICAL SCHEDULES & DETAILS
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
M-001
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
MECHANICAL
TITLE SHEET
BBEW
P R
O J E
C T
:2
HVAC GENERAL NOTES
* CONTRACTOR SHALL LOCATE THERMOSTATS AND
TEMPERATURE SENSORS AT 4'-0" AFF, A MAXIMUM OF 8"
FROM LIGHT SWITCH.
* PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF
MECHANICAL EQUIPMENT. COORDINATE SIZES WITH
MECHANICAL EQUIPMENT SELECTED.
* ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE
RATED FOR PRESSURE CLASS OF 2" W.G. UNLESS NOTED
OTHERWISE.
* THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS
ON HVAC EQUIPMENT AFTER ALL DUST PRODUCING
CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE
FINAL PUNCH.
ENG INEER
R E
G
IS
TERE D P R O F E SS
I O
N A
L
OREGON
102276PE
EXPIRES: 12/31/2025
M A R. 1 4 , 2 0 2 3
B
AL
A
K
E
JO S E P H BA RT U
S I
2 2
3 3
4 4
A
A
B
B
C
C
D
D
1 1
WM-1
WM-2
R.R.
FOYER
R.R.
CLOSET
CLOSET
PANTRY
OFFICE
HALL
300A
CONFERENCE
MECH
307A
IT ROOM
OFFICE
KEYNOTES
1 PROVIDE FEHOM 150 PINT DEHUMIDIFIER WITH CONDENSATE
PUMP OR OWNER APPROVED ALTERNATE.
2 1KW ELECTRIC WALL HEATER BY ELECTRICAL CONTRACTOR.
3 ONE THERMOSTAT SETPOINT TO BE 5°F HIGHER TO ACT AS
BACKUP.
0 4' 8'2' 1/4" = 1'-0"1
LEVEL 1 HVAC PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
M-111
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
LEVEL 1 HVAC
PLAN
BBEW
P R
O J E
C T
:2
ENG INEER
R E
G
IS
TERE D P R O F E SS
I O
N A
L
OREGON
102276PE
EXPIRES: 12/31/2025
M A R. 1 4 , 2 0 2 3
B
AL
A
K
E
JO S E P H BA RT U
S I
3 3
4 4
A
A
B
B
C
C
D
D
1 1
HP-1
HP-2
(E)CU
(E)CU
KEYNOTES
1 MOUNT HEAT PUMPS ON ROOF PER DETAIL 1 ON SHEET M-601.
0 4' 8'2' 1/4" = 1'-0"1
ROOF HVAC PLAN
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
M-141
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
ROOF HVAC
PLAN
BBEW
P R
O J E
C T
:2
ENG INEER
R E
G
IS
TERE D P R O F E SS
I O
N A
L
OREGON
102276PE
EXPIRES: 12/31/2025
M A R. 1 4 , 2 0 2 3
B
AL
A
K
E
JO S E P H BA RT U
S
PRE MOULDED
RUBBER ROOF JACK,
UV RESISTANT TYP.
(4)
(4) 1/4"x3-1/2"L
SIMPSON SDS
SCREWS.
WELD BOOT TO
TPO.
SEAL ALL
JOINTS
SIZE FRAME PER
MANUFACTURERS
RECCOMENDATIONS FOR UNIT
SIZE AND QUANTITY. BASIS OF
DESIGN: DIVERSITECH
QSMS1801
MECHANIC
AL UNIT
BOLT UNIT TO
STAND. WITH
1/4"Ø STAINLESS
STEEL 300 SERIES
BOLTS, AND RESIN
WASHER TO
PREVENT PAINT
SCRATCHING AND
RUSTING
ANTI VIBRATION
PAD
DATE:
JACKOLA ENGR. & ARCH., P.C.
WITHOUT THE WRITTEN CONSENT OF
MAY NOT BE USED OR REPRODUCED
IS PROPRIETARY. THIS DOCUMENT
THE INFORMATION CONTAINED HEREIN
REVISIONS:
FOR CONSTRUCTION
KALISPELL
406-755-3208
BOZEMAN
406-586-0707
VANCOUVER
360-852-8746
DRAWN: CHECKED:
info@jackola.com jackola.com
M-601
03/17/2026
B R
O A
D B
A N
D R
E M
O D
E L
C O
N F
E D
E R
A T
E D
T R
IB
E
S O
F T
H E
S
IL
E T
Z I N
D
IA
N S
S E
S W
A N
A V
E
S
IL
E T
Z
O R
MECHANICAL
SCHEDULES &
DETAILS
BBEW
P R
O J E
C T
:2
MINI-SPLIT HEAT PUMP SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN SYSTEM INTERLOCK
QTY
COOLING COMPRESSOR RATED OPERATING RANGE
EER SEER HSPF COP
UNIT
WEIGHT
ELECTRICAL DATA
REMARKSMANUFACTURER MODEL NO. INDOOR UNIT NOMINAL CAP
REFRIGERANT MOTOR
HEATING
COOLING
FLA MCA MOCP VOLT PHTYPE CHARGE RLA MIN MAX
HP-1 OUTDOOR UNIT SAMSUNG AR12DXFAMWKXCV WM-1 1 12,000 Btu/h R-32 25 lb 9 A -5.0 °F 14.0 °F 115 °F 13.5 24 9 1.76 71 lb 10 A 12 A 20 A 230 V 1
HP-2 OUTDOOR UNIT SAMSUNG AR12DXFAMWKXCV WM-2 1 12,000 Btu/h R-32 25 lb 9 A -5.0 °F 14.0 °F 115 °F 13.5 24 9 1.76 71 lb 10 A 12 A 20 A 230 V 1
MINI-SPLIT DUCTLESS FAN COIL SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN SYSTEM INTERLOCK
SUPPLY
AIRFLOW
FAN
EVAPORATOR
COOLING COIL
CONDENSER
HEATING COIL ACCESSORIES
UNIT
WEIGHT REMARKSMANUFACTURER MODEL NO. HEAT PUMP
MOTOR
NOMINAL CAP NOMINAL CAP
POWERED BY
OUTDOOR
UNITQTY POWER
WM-1 INDOOR UNIT SAMSUNG AR12DXFAMWKNCV HP-1 375 CFM 1 27 W 12,000 Btu/h 12,000 Btu/h Yes 23 lb
WM-2 INDOOR UNIT SAMSUNG AR12DXFAMWKNCV HP-2 375 CFM 1 27 W 12,000 Btu/h 12,000 Btu/h Yes 23 lb
REMARKS:
1. ALL UNITS TO BE SUPPLIED WITH STANDS.
NTS1
HVAC UNIT STAND DETAIL
ENG INEER
R E
G
IS
TERE D P R O F E SS
I O
N A
L
OREGON
102276PE
EXPIRES: 12/31/2025
M A R. 1 4 , 2 0 2 3
B
AL
A
K
E
JO S E P H BA RT U
S
WV
CA
CD
CW
F-CW
H-CW
S-CW
HW
HW 140°
HWC
HWC 140°
GV
GW
NG
OV
OW
V
W
RW
RWO
COMBINATION WASTE& VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRC
HOT WATER RECIRC 140°
GREASE VENT
GREASE WASTE
NATURAL GAS
SAND/OIL VENT
SAND/OIL WASTE
SANITARY VENT
SANITARY SEWER
RAIN WATER
RAIN WATER OVERFLOW
CAP
PLUG
2"
4"
4" 4"
PLUMBING AND PIPING SYMBOLS
KEYNOTE CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL PLUMBING SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE
REDUCING 45
DEGREE TEE
45 DEGREE TEE
* NOTE *
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
LP PROPANE GAS
TYPE (SEE SCHEDULE)
Room
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
4000 SF
6" RD-1
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
PD PRESSURE DROP
PIV POST INDICATOR VALVE
ABBREVIATIONS
4" FD-1FLOOR DRAIN
4" FS-2FLOOR SINK
4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13
HUB DRAIN
DRAIN TAGS
"P" - INDICATES PRIMER
CONNECTION
FIXTURE UNITS
COMBINATION
DRAINS
ROOF AREA SERVED
BY DRAIN
2" DOM. WM
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
WATER CLOSET -
WALL HUNG - ADA WC-5
UR-2
1 WFU
LAV-1A
LAV-1A
4" WCO
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
4" WCO
TYPE (SEE SCHEDULE)
WC-5A
PIPING SYMBOLSGENERAL PLUMBING NOTES
1. ALL PLUMBING AND PRACTICE TO BE IN ACCORDANCE WITH
CURRENT UNIFORM PLUMBING CODE.
2. COMPLETE INSTALLATION OF PLUMBING SYSTEM TO
CONFORM TO STATE BUILDING, MECHANICAL ENERGY, FIRE,
AND HEALTH CODES, AND REGULATIONS ADOPTED BY LOCAL
JURISDICTIONS.
3. PLUMBING SYSTEMS AS SHOWN ARE SCHEMATIC IN NATURE
AND ITEMS NOT SPECIFICALLY CALLED FOR OR SHOWN, BUT
REQUIRED FOR INSTALLATION FOR THE COMPLETE MECH.
SHALL BE PROVIDED, AND ARE REQUIRED AS PART OF THE
CONTRACT. MANUFACTURER'S RECOMMENDATIONS AND
INDUSTRY STANDARDS SHALL APPLY.
4. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
PLUMBING SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED, AND AS REQUIRED BY CODE.
5. CONTRACTOR RESPONSIBILITY TO VERIFY QUANTITIES.
6. MAINTAIN A MINIMUM OF 6'-6" OF GROUND COVER OVER ALL
UNDERGROUND WATER MAINS AND A MINIMUM OF 3'0" OF
GROUND COVER OVER ALL UNDERGROUND SEWERS AND
DRAINS.
7. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.
8. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
9. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END
DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW
POINTS.
10. SUBCONTRACTOR SHALL COORDINATE WITH GENERAL AND
VERIFY ALL ROUTING AND SUPPORT SYSTEMS & INCLUDE IN HIS
BID ALL NECESSARY TO PROVIDE THE OWNER WITH A
COMPLETE SYSTEM.
11. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES
INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
12. ALL "OR EQUAL" FIXTURES AND ACCESSORIES TO BE APPROVED
BY ARCHITECT OR ENGINEER.
13. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL FIXTURES SHALL
BE WHITE.
14. IT IS UNLAWFUL TO CONCEAL CRACKS, HOLES, OR OTHER
IMPERFECTIONS IN MATERIALS BY WELDING, BRAZING, OR
SOLDERING OR BY USING THEREIN OR THEREON ANY PAINT,
WAX, TAR, OR OTHER LEAK-SEALING OR REPAIR AGENT.
15. BURRED ENDS OF ALL PIPE AND TUBING SHALL BE REAMED TO
THE FULL BORE OF THE PIPE.
16. PLUMBING SYSTEMS SHALL BE INSTALLED IN A MANNER
CONFORMING TO THE PLUMBING CODE AND THE
MANUFACTURER'S RECOMMENDATIONS. IN INSTANCES
WHERE THE CODE AND THE MANUFACTURER'S INSTRUCTIONS
CONFLICT, THE MORE STRINGENT PROVISIONS SHALL PREVAIL.
17. ALL VALVES, PIPES, AND FITTINGS SHALL BE INSTALLED IN
CORRECT RELATIONSHIP TO THE DIRECTION OF FLOW.
18. NO PIPING SHALL BE DIRECTLY EMBEDDED IN CONCRETE OR
MASONRY. NO STRUCTURAL MEMBER SHALL BE SERIOUSLY
WEAKENED OR IMPAIRED BY CUTTING, NOTCHING OR
OTHERWISE.
19. PIPING SUBJECT TO UNDUE CORROSION, EROSION, OR
MECHANICAL DAMAGE SHALL BE PROTECTED IN AN APPROVED
MANNER.
20. NO WATER, SOIL, OR WASTE PIPE SHALL BE INSTALLED OR
PERMITTED OUTSIDE A BUILDING OR IN AN EXTERIOR WALL
UNLESS, WHERE NECESSARY, ADEQUATE PROVISION IS MADE
TO PROTECT SUCH PIPE FROM FREEZING.
21. ALL PIPE PENETRATING FLOOR/CEILING ASSEMBLIES AND FIRE-
RESISTANCE RATED WALLS OR PARTITIONS SHALL BE
PROTECTED WITH THE REQUIREMENTS OF THE BUILDING
CODE.
22. SLEEVES SHALL BE PROVIDED TO PROTECT ALL PIPING
THROUGH CONCRETE OR MASONRY EXTERIOR OR BEARING
WALLS, AND SHALL BE SIZED SO THERE IS A MINIMUM 1/2"
CLEARANCE AROUND THE PIPE AND/OR INSULATION.
23. PIPING THROUGH CONCRETE OR MASONRY WALLS SHALL NOT
BE SUBJECT TO ANY LOAD FROM BUILDING CONSTRUCTION.
24. ALL PIPING SHALL BE SUPPORTED IN SUCH A MANNER AS TO
MAINTAIN ITS ALIGNMENT, AND PREVENT SAGGING.
25. ALL PIPING SHALL BE HUNG AND/OR SUPPORTED TO
ELIMINATE NOISE AND VIBRATION WITH APPROPRIATE
HANGERS AND SUPPORTS. SEE DETAILS FOR REQUIREMENTS.
26. PIPING IN THE GROUND SHALL BE LAID ON A FIRM BED FOR ITS
ENTIRE LENGTH. WHERE SUPPORT IS OTHERWISE PROVIDED, IT
SHALL BE ACCEPTABLE TO THE ADMINISTRATIVE AUTHORITY.
27. HANGERS AND ANCHORS SHALL BE OF SUFFICIENT STRENGTH
TO SUPPORT THE WEIGHT OF THE PIPE AND ITS CONTENTS.
PIPING SHALL BE ISOLATED FROM INCOMPATIBLE MATERIALS.
28. THREADS ON IRON PIPE SIZE (IPS) PIPE AND FITTINGS SHALL BE
STANDARD TAPER PIPE THREADS. THREADS ON TUBING SHALL
BE APPROVED TYPES. THREADS ON PLASTIC PIPE SHALL BE
FACTORY CUT OR MOLDED. THREADED PLASTIC PIPE SHALL BE
SCHEDULE 80 MINIMUM WALL THICKNESS. TUBING THREADS
SHALL CONFORM TO FINE TUBING THREAD STANDARDS. WHEN
A PIPE JOINT MATERIAL IS USED, IT SHALL BE APPLIED ONLY ON
MALE THREADS AND SUCH MATERIALS SHALL BE APPROVED
TYPES, INSOLUBLE IN WATER, AND NONTOXIC. CLEANOUT
PLUGS AND CAPS SHALL BE LUBRICATED WITH…
This is the start of the file's text. The full file is on GovTribe.