2025_0604_STEA_335051_Drawings.pdf

PDF 2 MB Posted

Attached to
STEA: REHABILIITATE MECHANICAL SYSTEM
Solicitation number
140P4525R0016
Issued by

About this file

These are mechanical engineering design drawings for a mechanical system rehabilitation project at Steamtown National Historical Site in Scranton, Pennsylvania. The comprehensive set of 16 technical drawings details extensive mechanical upgrades across multiple buildings, including the History Museum and Locomotive Shop. Key scope elements include:

Mechanical system modifications involve demolishing and replacing existing infrastructure such as air handling units (AHUs), hot water and chilled water pumps, boilers, air separators, expansion tanks, and associated piping and electrical systems. The project includes two implementation options (Option 1 and Option 2) with specific requirements for equipment installation, gas line modifications, electrical panel revisions, and system reconnections. Proposed equipment includes new AHUs, pumps, chillers, and control systems, with careful attention to integration with existing infrastructure and preservation of the historical site's mechanical systems. The drawings provide detailed floor plans, flow diagrams, equipment schedules, and installation specifications for comprehensive mechanical system rehabilitation.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. REFER TO ALL DRAWINGS SPECIFICATION FOR GENERAL DESCRIPTION OF AREAS REQUIRING DEMOLITION.

2. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR ALL EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY

OF THE OWNER.

3. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.

4. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.

5. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM HARVARD FACILITIES.

PROVIDE TEMPORARY SERVICES AS REQUIRED.

6. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS

SHOWN.

7. THIS CONTRACTOR SHALL PROVIDE SHUT DOWN OF SERVICES (BOILERS, AHU, PUMPS, ETC.) AND TRACING OF ALL PIPING WITHIN BASE BID.

HVAC DEMOLITION SPECIFICATION

1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL MX.XX SERIES DRAWINGS.

2. DRAWINGS ARE DIAGRAMMATIC, DETERMINE EXACT LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.

3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.

4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

5. PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND STEEL PLATFORMS REQUIRED FOR MECHANICAL

WORK.

6. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.

7. SHEETMETAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED WITHOUT PRIOR CONSENT FROM

ARCHITECT/ENGINEER.

8. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND LEAKAGE CLASSES.

9. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS

CLOSE AS POSSIBLE TO WALL AND UNDERSIDE OF BEAMS AND JOISTS.

10. INSTALL THERMOSTATS AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA.

11. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY.

12. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS) AND TRANSITIONS

AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.

13. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE DUCT TRANSITIONS TO FURNISHED

EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONS BEFORE FABRICATION.

14. ACCESS PANELS SHALL BE PROVIDED TO CLEAN COILS AND SERVICE DAMPERS, HEATERS, VALVES AND ALL CONCEALED MECHANICAL

EQUIPMENT.

15. SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. PROVIDE TO GC A LIST OF ALL WEIGHTS AND METHODS OF SUPPORT FOR COORDINATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

16. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM IN ACCORDANCE WITH DIVISION 28 SPECIFICATIONS. MOUNT THE DETECTORS IN DUCTWORK. SMOKE DETECTORS SHALL BE INSTALLED AND WIRED TO THE BAS SYSTEM AND FAN STARTERS FOR SHUTDOWN

IN ACCORDANCE WITH DIVISION 23 SPECIFICATIONS.

17. SMOKE DAMPERS SHALL BE UL555S LISTED.

18. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.

19. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE FOR LINER IF APPLICABLE.

20. ALL MATERIALS AND EQUIPMENT SHALL BE NEW,

21. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.

22. ALL CONDENSATE DRAIN LINES SHALL HAVE A BALL VALVE AND CAPPED.

23. PROVIDE FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH 2018 INTERNATIONAL MECHANICAL CODE. FOR DUCTS THAT PENETRATE FIRE WALLS, FLOORS AND PARTITIONS PROVIDE SLEEVES WHERE PENETRATIONS ARE NOT PERPENDICULAR TO SURFACE PENETRATED. ENCLOSE DAMPERS IN 10 GAUGE STEEL SLEEVE.

24. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND AIR HANDLING UNITS UNLESS INTERNALLY ISOLATED. ALL DUCTS TO

BE GROUNDED ACROSS FLEXIBLE CONNECTION WITH FLEXIBLE COPPER GROUNDING STRAPS.

25. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT BLACK.

26. INSULATE PIPING AND DUCTWORK AS SPECIFIED: PERFORM TESTS SPECIFIED BEFORE INSULATING.

27. PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING.

28. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.

29. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO TERMINAL EQUIPMENT AND RISERS.

30. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA. MITERED (SQUARE) ELBOWS WITH TURNING VANES MAY NOT BE SUBMITTED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT/ENGINEER.

31. ISOLATION VALVES IN PIPING SYSTEMS ARE NOT SHOWN ON PLANS (FOR CLARITY) BUT ARE REQUIRED AT ALL PIPE BRANCHES AND

CONNECTIONS TO EQUIPMENT REFER TO DETAIL SHEETS AND FLOW DIAGRAMS.

32. PITCH PIPING 1 INCH IN 20 FEET MINIMUM IN DIRECTION OF FLOW, TO ALLOW FOR DRAINING

33. MANUAL DAMPERS ARE NOT SHOWN ON THE DRAWINGS IN ORDER FOR DRAWING CLARITY. PROVIDE MANUAL ADJUSTABLE DAMPERS ON EACH LOW PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT TAKE OFF, AND AT EACH TAKE OFF TO REGISTERS, GRILLES AND DIFFUSERS.

34. PROVIDE CEILING ACCESS PANELS BELOW ALL EQUIPMENT LOCATED ABOVE CEILINGS. EXACT SIZE AND LOCATION SHALL BE COORDINATED IN

FIELD WITH ARCHITECT.

GENERAL NOTESHYDRONIC SYSTEM SPECIFIC ABBREVIATIONSGENERIC HVAC ABBREVIATIONS

AIR SYSTEM SPECIFIC ABBREVIATIONS

GE

FSD

FPI

FLTR

FD

FCU

AC

ACC

ACD

AF

AHU

ALD

ATD

AVS

F F&B

FB

FC

FA

AIR CONDITIONING

AIR COOLED CONDENSER UNIT

AIR FOIL

AIR HANDLING UNIT

AIR VOLUME TRAVERSE STATION

FAN

FACE AND BYPASS

FAN BOX

FORWARD CURVED

FREE AREA

FIRE DAMPER (W/ ACCESS DOOR)

COMBINATION FIRE/SMOKE

DAMPER

FINS PER INCH

FILTER

GENERAL EXHAUST

°F °C Ø

DEGREES FAHRENHEIT

DIAMETER

DEGREES CELSIUS

ACV

AD

ADJ

ADDL

AFF

AFG

ALT

ALUM

AP

ARCH

ATC

ATV

AVG

BAS

BBD

BDT

BF

BFF

BHP

BLDG

BLR

BOD

BOP

BOT

BSMT

BTU

BTUH

C

CA

CF

CL

CLG

CO

COL

COMP

CONC

CONN

CONTR

CORR

CUF

CUH

CYL

CRCU

D

DB

DC

DDC

DDCFP

DIA

DIM

DN

DWG

EA

EAT

EFF

ECUH

ELEC

ELEV

EMER

EMS

ENT

EQUIP

EUH

EXH

EXP

FAS

FOB

FOT

FTR

FCV

FFOP

FG

FLEX

FLR

FLRDR

FP

FPM

FT

FT/SEC

FURN

FVNR

G

GA

GAL

GALV

GC

GND

GPH

GPM

GRD

GWB

H

HCPD

HD

HP

HPG

HR

HZ

HX

WRT

WG

WF

WB

W/O W/ W

VTR

VFD

VERT

VEL

V

TYP

TOP

TOD

TEMP

TEL

TEFC

TAV

TA

SUP

SUCT

STL

STDBY

STD

SS

SQFT

SQ

SPECS

SOV

SCH

RPM

RM

R.H.

REQS

REQD

RET

REP

R

PVC

PSIG

PSID

PSIA

PRIM

PR

PRESS

POS

PLBG

PH

PD

PCF

P

OV

OFOI

OFCI

ODP

OD

OC

OB

NTS

NOM

NO.

NO

NIC

NC

NC

N/A

MU

MTD

MIN

MH

MFR

MEZZ

MECH

MCC

MCA

MBH

MAX

M

LVG

LF

LAB

LB

L

KVA

KW

INSUL

IN

ID

AVERAGE

ATMOSPHERIC VENT

AUTOMATIC TEMPERATURE CONTROL

ARCHITECT

ACCESS PANEL

ALUMINUM

ALTERNATE

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

ADDITIONAL

BRITISH THERMAL UNIT PER HOUR

BRITISH THERMAL UNIT

BASEMENT

BOTTOM

BOTTOM OF PIPE

BOTTOM OF DUCT

BOILER

BUILDING

BRAKE HORSEPOWER

BELOW FINISHED FLOOR

BOILER FEED WATER

BLOWDOWN TANK

BOILER BLOW DOWN

BUILDING AUTOMATION SYSTEM

COLD ROOM CONDENSING UNIT

CYLINDER

CABINET UNIT HEATER

CUBIC FEET

CORRIDOR

CONTRACTOR

CONNECTION

CONCRETE

COMPRESSOR

COLUMN

CLEAN-OUT

CEILING

CENTERLINE

CEILING FAN

COMPRESSED AIR

CONVECTOR

DRAIN

DRAWING

DOWN

DIMENSION

DIAMETER

DIRECT DIGITAL CONTROL FIELD PANEL

DIRECT DIGITAL CONTROL

DRY COOLER

DRY BULB TEMPERATURE

EXPANSION

EXHAUST

ELECTRIC UNIT HEATER

EQUIPMENT

ENTERING

ENERGY MANAGEMENT SYSTEM

EMERGENCY

ELEVATION

ELECTRICAL

ELECTRIC CABINET UNIT HEATER

EFFICIENCY

ENTERING AIR TEMPERATURE

EACH

FULL VOLTAGE NON-REVERSING

FURNISHED

FEET PER SECOND

FEET

FEET PER MINUTE

FIRE PROTECTION

FLOOR DRAIN

FLOOR

FLEXIBLE

FIBERGLASS

FIREFIGHTERS OVERRIDE PANEL

FLOW CONTROL VALVE

FINNED TUBE RADIATION

FLAT ON TOP

FLAT ON BOTTOM

FIRE ALARM SYSTEM

GYPSUM WALL BOARD

GRADE (GROUND LEVEL)

GALLONS PER MINUTE

GALLONS PER HOUR

GROUND

GENERAL CONTRACTOR

GALVANIZED

GALLONS

GAUGE

GAS

HEAT EXCHANGER

HERTZ

HOUR

HIGH PRESSURE GAS

HORSEPOWER

HEAD

HANDICAPPED

HEIGHT

WITH RESPECT TO

WATER GAUGE

WIDE FLANGE

WET BULB TEMPERATURE

WITHOUT

WITH

WIDTH

VENT THROUGH ROOF

VARIABLE FREQUENCY DRIVE

VERTICAL

VELOCITY

VENT

TYPICAL

TOP OF PIPE

TOP OF DUCT

TEMPERATURE

TELEPHONE

TOTALLY ENCLOSED FAN COOLED

THERMOSTATIC AIR VENT

THROW-AWAY

SUPPLY

SUCTION

STEEL

STANDBY

STANDARD

STAINLESS STEEL

SQUARE FEET

SQUARE

SPECIFICATIONS

REVOLUTIONS PER MINUTE

ROOM

RELATIVE HUMIDITY

REQUIREMENTS

REQUIRED

RETURN

REPRESENTATIVE

REHEAT

SCHEDULE

SOLENOID OPERATED VALVE

POLYVINYL CHLORIDE

POUNDS PER SQUARE INCH GAUGE

POUNDS PER SQUARE INCH DIFFERENTIAL

POUNDS PER SQUARE INCH ABSOLUTE

PRIMARY

PRESSURE REFERENCE

PRESSURE

PROVIDED BY OTHER SECTION(S)

PLUMBING

PHASE

PRESSURE DROP

POUNDS PER CUBIC FOOT

PERIMETER HEAT

OUTLET VELOCITY

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

OPEN DRIP PROOF

OUTSIDE DIAMETER

ON CENTER

OCTAVE BAND

NOT TO SCALE

NOMINAL

NUMBER

NORMALLY OPEN

NOT IN CONTRACT

NOISE CRITERIA

NORMALLY CLOSED

NOT APPLICABLE

MAKEUP WATER

MOUNTED

MINIMUM

MANHOLE

MANUFACTURER

MEZZANINE

MECHANICAL

MOTOR CONTROL CENTER

MINIMUM CIRCUIT AMPS

THOUSAND BRITISH THERMAL UNITS PER HOUR

MAXIMUM

ONE THOUSAND

LEAVING

LINEAR FEET

LABORATORY

POUND

LENGTH

KILOVOLT AMPERE

KILOWATT

INSULATION

INCHES

INSIDE DIAMETER

BDD

BI

BC

BSD

BACKDRAFT DAMPER

BACKWARD INCLINED

BLOWER COIL

BIOSEAL DAMPER

CC

CD

CFM

CG

COOLING COIL

CUBIC FEET PER MINUTE

CEILING DIFFUSER

CEILING GRILLE

CREF CHILLER ROOM EXHAUST FAN

CU CONDENSING UNIT

DIFF

DWDI DOUBLE WIDTH DOUBLE INLET

DIFFUSER

DWSI

DX DIRECT EXPANSION

DOUBLE WIDTH SINGLE INLET

EF

EG

EHC

EHU

ERU

ER

ERHC

ESP

EXHAUST FAN

EXHAUST GRILLE

ELECTRICAL HEATING COIL

EXHAUST AIR HANDLING UNIT

ENERGY RECOVERY UNIT

EXHAUST REGISTER

ELECTRIC REHEAT COIL

EXTERNAL STATIC PRESSURE

WMS

VVR

VVE

VV

VD

WIRE MESH SCREEN

VARIABLE VOLUME RETURN AIR TERMINAL BOX

VARIABLE VOLUME EXHAUST AIR TERMINAL BOX

VARIABLE VOLUME SUPPLY AIR TERMINAL BOX

VOLUME DAMPER

UC UNDERCUT DOOR

TSP

TR

TG

TF

TOTAL STATIC PRESSURE

TRANSFER

TRANSFER GRILLE

TRANSFER FAN

TEF DEDICATED TOILET EXHAUST FAN

TE TOILET EXHAUST

SWSI

SWDI

SV

SR

SP

SM

SGD

SG

SFD

SF

SEF

SDET

SD

SCR

SATT

SA

SINGLE WIDTH SINGLE INLET

SINGLE WIDTH DOUBLE INLET

VARIABLE VOLUME SUPPLY AIR TERMINAL BOX

SUPPLY REGISTER

STATIC PRESSURE

SHEETMETAL

SLIDE GATE DAMPER

SUPPLY GRILLE

COMBINATION AUTOMATIC SMOKE/FIRE

DAMPER WITH ACCESS DOOR

SUPPLY FAN

SMOKE EXHAUST FAN

SMOKE DETECTOR

SMOKE DAMPER

SCREEN

SOUND ATTENUATOR

SUPPLY AIR

RV

RS

RR

RLF

RL

RHC

RG

RF

RD

RA

RETURN AIR VALVE/BOX

REFRIGERANT SUCTION

RETURN REGISTER

RELIEF

REFRIGERANT LIQUID

REHEAT COIL

RETURN GRILLE

RETURN FAN

REFRIGERANT DISCHARGE (HOT GAS)

RETURN AIR

PHC PREHEAT COIL

OED

OBD

OAI

OA

OPEN END DUCT

OPPOSED BLADE DAMPER

OUTSIDE AIR INTAKE

OUTSIDE AIR

LVDR

LUVR

LD

LAT

LOUVERED DOOR

LOUVER

LINEAR DIFFUSER

LEAVING AIR TEMPERATURE

IH INTAKE HOOD

HU

HV

HRU

HPU

HEPA

HC

HUMIDIFIER

HEATING & VENTILATING UNIT

HEAT RECOVERY UNIT

HEAT PUMP UNIT

HIGH EFFICIENCY PARTICULATE AIR FILTER

HEATING COIL

GWCE

GH

GLASS WASH CENTER EXHAUST

GRAVITY HOOD

GEF GENERAL EXHAUST FAN

AIR SEPARATOR

AUTOMATIC AIR VENTAAV

AS

CH

CHEM

CHW

CHWR

CHWS

DOV

ET

EWT

GR

GS

GHW

GHWR

GHWS GLYCOL HOT WATER SUPPLY

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER

GLYCOL SUPPLY

GLYCOL RETURN

ENTERING WATER TEMPERATURE

EXPANSION TANK

DRAIN OFF VALVE

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER

CHEMICAL FEED

CHILLER

HB

HCR

HCS

HRC

HW

HOSE BIBB CONN W/CHAINED CAP

HOT WATER

HEAT RECOVERY COIL - GLYCOL

HOT OR COLD WATER SUPPLY (DUAL TEMP)

HOT OR COLD WATER RETURN (DUAL TEMP)

UV

TDH

S(XXX)

RHWR

RHWS

T(XXX)

RHW

RH

RHP

PCHWS

PCHWR

PROCHW

PHX

PC

P

OS&Y

UNIT VENTILATOR

TOTAL DYNAMIC HEAD

TERTIARY (SYSTEM DEPENDENT PREFIX)

SECONDARY (SYSTEM DEPENDENT PREFIX)

REHEAT HOT WATER RETURN

REHEAT HOT WATER SUPPLY

REHEAT HOT WATER

REHEAT

RADIANT HEATING PANEL

PROCESS CHILLED WATER SUPPLY

PROCESS CHILLED WATER RETURN

PROCESS CHILLED WATER

PLATE HEAT EXCHANGER

PUMPED CONDENSATE

PUMP

OUTSIDE STEM AND YOKE

NET POSITIVE SUCTION HEAD

MANUAL AIR VENTMAV

NPSH

LWT

HWUH

HWS

HWR

HWRHC

HWPHC

HWHC

HWCUH HOT WATER CABINET UNIT HEATER

HOT WATER HEATING COIL

HOT WATER PREHEAT COIL

HOT WATER REHEAT COIL

HOT WATER RETURN

HOT WATER SUPPLY

HOT WATER UNIT HEATER

LEAVING WATER TEMPERATURE

VV SUPPLY VAV BOX

ADJUSTABLE

ACCESS DOOR

AUTOMATIC CONTROL VALVE

UH UNIT HEATER

SCHW SECONDARY CHILLED WATER

AIR TERMINAL DEVICE

ACOUSTICAL LINED DUCTWORK

AUTOMATIC CONTROL DAMPER

HR

HZ

HX HEAT EXCHANGER

HERTZ

HOUR

MECHANICAL

LEGENDM0.01

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

DN

UP

W

CO

MAV

AAV

PT

E

FM

S

OR

OR

OR

R w

GATE VALVE

BALL VALVE

BALL VALVE WITH MEMORY STOP (BALANCING VALVE)

BALL VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN VALVES)

BUTTERFLY VALVE

BUTTERFLY VALVE WITH MEMORY STOP (BALANCING VALVE)

GLOBE VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

STRAINER W/BALL VALVE, HOSE BIBB & CAP (GATE VALVE FOR STEAM)

SOLENOID VALVE

AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR

AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR

AUTOMATIC FLOW CONTROL VALVE (PRESSURE INDEPENDENT)

COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE (CIRCUIT SETTER)

FLOW MEASURING DEVICE

FLOW SWITCH

SAFETY RELIEF VALVE

UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)

BLIND FLANGE

END CAP

PRESSURE GAUGE WITH GAUGE CLOCK

PRESSURE/TEMPERATURE WELL

AUTOMATIC AIR VENT WITH ISOLATION VALVE

MANUAL AIR VENT

REDUCER (ECCENTRIC-FLAT ON BOTTOM OR FLAT ON TOP)

REDUCER (CONCENTRIC)

FLEXIBLE CONNECTION

EXPANSION JOINT

PIPE GUIDE

ANCHOR

RISE (SINGLE LINE - PLAN VIEW)

DROP (SINGLE LINE - PLAN VIEW)

VALVE IN VERTICAL

TOP TAKEOFF

BOTTOM TAKEOFF

PIPE BREAK (SINGLE LINE)

WATER METER DIAL TYPE

DIRT LEG

CLEAN-OUT FOR CONDENSATE DRAIN

RISE (DOUBLE LINE - PLAN VIEW)

DROP (DOUBLE LINE - PLAN VIEW)

PIPE BREAK (DOUBLE LINE)

DIRECTION OF FLOW IN PIPE

PITCH PIPE UP IN DIRECTION OF FLOW

PITCH PIPE DOWN IN DIRECTION OF FLOW

NEW WORK

SUPPLY LINES

RETURN LINES

PIPING LEGENDDUCTWORK

SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE

ROUND SUPPLY

DUCT UP

SUPPLY

DUCT UP

ROUND SUPPLY

DUCT DN

SUPPLY DUCT

DOWN

STANDARD RADIUS

ELBOW

( R = W )

SUPPLY/RETURN

EXHAUST

SPLIT TAKE-OFF

W/ BRANCH DAMPERS

SUPPLY

BULLHEAD SPLIT

SUPPLY

CEILING DUCT

GOOD FOR

RING DUCT

TAKEOFF TO

MTD DIFF/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

CEILING DUCT

MTD DIFF/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

OPEN END

DUCT W/VD &

1/2"x1/2" WMS

FLEXIBLE

DUCT

RISE/DROP

RISE/DROP

ROUND RETURN OR

EXHAUST

DUCT UP

RETURN/EXHAUST

DUCT UP

RETURN/EXHAUST

DUCT DOWN

ROUND RETURN OR

EXHAUST DUCT

DN

HORIZONTAL

OFFSET

SUPPLY/RETURN

/EXHAUST

RISE OR DROP

SUPPLY/RETURN/

EXHAUST

RING

DUCT

90° TAKE-OFF W/BRANCH TAKE-OFF

VOLUME DAMPER (VD IN LOW PRESSURE

SYSTEMS ONLY)

BULLHEAD CONVERGE

RETURN/EXHAUST

W/BRANCH TAKE-OFF

VOLUME DAMPER

SIDEWALL DUCT MTD

REGISTER/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

SUPPLY SIDEWALL

LINEAR DIFFUSER

(W/ 1" INTERNALLY

LINED SM PLENUM)

BRANCH CONN

W/VD FOR EVERY

4' OF LINEAR

SUPPLY CEILING

LINEAR DIFFUSER (W/

1" INTERNALLY LINED

SM PLENUM) BRANCH

CONN W/VD FOR

EVERY 4' OF LINEAR BOOT

BY LD

MFR

AVS AIR VOLUME TRAVERSE STATION

WITH ACCESS DOOR

ROOF EXHAUST FAN

SHOWN ON ROOF

ROOF EXHAUST FAN

SHOWN ON FLOOR PLAN

RETURN OR EXHAUST

AIR FLOW

SUPPLY AIR FLOW

STANDARD 4-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 3-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 2-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 1-WAY BLOW

SUPPLY DIFFUSER

ALTERNATE CFM LOCATION

DESIGN CFM

(200) A(200)

SYMBOL DESIGNATES ASSOCIATED

SYSTEM OR SERVICE (ie HWS)

REFER TO DRAWINGS ( ) FOR

CONTINUATION XXX

SMOKE DETECTOR

PRESSURE TRANSMITTER

HUMIDITY INDICATOR

TEMPERATURE INDICATOR

HUMIDITY SENSOR

TEMPERATURE SENSOR

HUMIDISTAT

THERMOSTATSECTION DESIGNATION SHEET NUMBER

DETAIL DESIGNATION SHEET NUMBER

REVISION NUMBER

DIFFUSER, GRILLE, REGISTER LETTER

DESIGNATOR

CALL OUT SYMBOLS

M.XX

M.XX

SDET

P

MI

TI

MS

TS

C CARBON DIOXIDE SENSOR

MATCHLINE

BDD BACKDRAFT DAMPER

FSD COMBINATION SMOKE/FIRE

DAMPER W/ACCESS DOOR

SGD SLIDE GATE DAMPER

VD MANUAL VOLUME DAMPER

(OBD IN DIFFUSER)

ACD AUTOMATIC CONTROL DAMPER

W/ACCESS DOOR

SD AUTOMATIC SMOKE DAMPER

W/ACCESS DOOR

FD FIRE DAMPER W/ ACCESS DOOR

X PIPE ANCHOR FOR EXPANSION LOOP

PIPE GUIDE FOR EXPANSION LOOP

EQUIPMENT TAG SYMBOLS & ABBREVIATIONS

RH

VFD

C

C

C

VARIABLE FREQUENCY DRIVE

UNIT HEATER

CABINET HEATER

COOLING COIL

REHEAT COIL

OPPOSED BLADE DAMPER

PARALLEL BLADE DAMPER

W/ MODULATING ACTUATOR

W/ MODULATING ACTUATOR

W/ TWO POSITION ACTUATOR

BACKDRAFT DAMPER

PARALLEL BLADE DAMPER

W/ TWO POSITION ACTUATOR

OPPOSED BLADE DAMPER

ROOF FAN

FLOW DIAGRAM AND CONTROL DIAGRAM EQUIP SYMBOLS

C

H

HEATING COIL

FILTER BANK

INLINE CENTRIFUGAL FAN

CENTRIFUGAL FAN

PUMP

UPBLAST CENTRIFUGAL FAN

TAG

NO

TAG

NO

EXPANSION TANK

AIR SEPARATOR

CHEMICAL FEED SYSTEM

AIR TERMINAL BOX WITH

REHEAT COIL

AIR TERMINAL BOX

AAV

NOTE: REFER TO SCHEDULES FOR EQUIPMENT SPECIFIC DATA

OCCUPIED MAX CFM

UNOCCUPIED CFM

TERMINAL BOXVAV/VAVE

XXX

XXX

OCCUPIED MAX GPM

TERMINAL BOXVAV/VAVE

XXX

PUSH BUTTONPB

RF SHIELDED ROOM

EQUIPMENT NOT

REQUIRING

ELECTRIC SERVICE

EQUIPMENT

REQUIRING

ELECTRIC SERVICE

MECHANICAL

LEGENDM0.02

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

AIR VALVE

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AHU

1 DUCTWORK DEMOLITION FLOOR PLAN

1/8" = 1'-0"

2 DUCTWORK NEW WORK FLOOR PLAN

1/8" = 1'-0"

SCOPE OF WORK

1. DISCONNECT AND REMOVE EXISTING AHU. DEMOLISH DUCTWORK INDICATED ON PLANS.

2. NEW AHU SHALL BE BROUGHT IN THROUGH AREAWAY. REMOVE LOUVER AND FLOOR GRATE.

STORE ITEMS TO BE RE-INSTALLED AFTER AHU INSTILLATION.

3. AHU SHALL BE BROUGHT IN BY MODULES AND CONSTRUCTED IN THE BASEMENT.

4. RE-CONNECT DUCTWORK AND PIPING TO AHU. PROVIDE DAMPERS, VALVES, TEMPERATURE, AND

PRESSURE GAUGES AS INDICATED ON DRAWINGS AND DETAILS.

5. INSPECT BOILER VENT PIPES. REPLACE ANY COMPONENTS THAT DO NOT MEET SPECIFICATIONS.

6. INSPECT AND CLEAN EXISTING DUCTWORK. REPLACE ANY DAMAGED OF RUSTED DUCTWORK.

REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL DUCTWORK.

7. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL

WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.

BASE DESIGN - AHU

44"x44" SA

44"x44" EXISTING

SUPPLY RISER

70"x40" SA90"x20" RA 48"x48" EXISTING

RETURN AIR RISER

90"x64" OA

(NEW)

AHU

(EXISTING)

B

B

VENT AND COMBUSTION AIR

UP THROUGH AREA WAY

(EXISTING) (EXISTING)

DUCTWORK FLOOR PLAN

BASEMENT LEVELM1.01

HISTORY MUSEUM

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACEC

02/07/25

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

1 PIPING DEMOLITION BASEMENT FLOOR PLAN

1/8" = 1'-0"

2 PIPING NEW WORK BASEMENT FLOOR PLAN

1/8" = 1'-0"

SCOPE OF WORK

1. INSPECT HOT WATER SYSTEM, INCLUDING BOILERS, PUMPS, VALVES, PIPING, GAS LINE,

COMBUSTION AIR, AND EXHAUST AIR. REPLACE ANY COMPONENTS THAT DO NOT MEET

SPECIFICATIONS.

2. DISCONNECT AND REMOVE HOT WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND

ASSOCIATED PIPING AND VALVES. REFER TO FLOW DIAGRAM.

3. DISCONNECT AND REMOVE AHU. DEMO PIPING CONNECTIONS

4. INSTALL BOILERS ON CONCRETE PAD.

5. INSTALL NEW HOT WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED PIPING

AND VALVES. REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.

6. RECONNECT HOT WATER AND CHILLED WATER COILS TO THE NEW AHU. REFER TO DETAIL FOR

PIPING CONFIGURATION AND ASSOCIATE VALVES/GAUGES.

7. INSTALL NEW FCUS. RECONNECT HOT WATER, CHILLED WATER, AND CONDENSATE PIPING. REFER

TO DETAIL FOR PIPING CONFIGURATION AND ASSOCIATE VALVES/GAUGES.

8. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING

OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.

9. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL

WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.

10. BOILERS ARE PROPANE. CONTINUE RENTING PROPANE TANKS. IF OPTION 1 IS APPROVED, THEN

BOILERS SHALL BE CONVERTED TO NATURAL GAS AND PROPANE SYSTEM SHALL BE REMOVED.

4" HWS/R

4" CHWS/R

TO UNDERGROUND

DISTRIBUTION

B

B

4" HWS/R

4" CHWS/R

TO UNDERGROUND

DISTRIBUTION

B

B

AHU

(NEW)

P

(NEW)

P

(NEW)

AS

(NEW)

ET

(NEW)

P

P

P

(EXISTING)

P

(EXISTING)

P

(NEW)

P

(NEW)

FCU

(EXISTING)

FCU

(NEW)

3 PIPING NEW WORK LEVEL 1FLOOR PLAN

1/8" = 1'-0"

FCU

(NEW)

PROPANE UP

TO TANKS

(EXISTING)(EXISTING)

PROPANE UP

TO TANKS

PIPING FLOOR PLAN

BASEMENT LEVELM1.02

HISTORY MUSEUM

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

BASE DESIGN - LOCO SHOP

PUMP ROOM

BOILER ROOM

GAS LINE SERVING

BOILERS. CONNECTS

TO MAIN ON LEVEL 1

EXISTING PIPING

HOT WATER

DISTRIBUTION TO

THE BUILDING

EXISTING PUMPS

EXISTING PUMP

EXISTING PUMPS

EXISTING AIR SEPARATOR

EXISTING EXPANSION TANK

HOT WATER

DISTRIBUTION TO

THE BUILDING

BOILER EXHAUST

B

B

B

B

(EXISTING)

TO DOMESTIC COLD

WATER CONNECTION

LOCKER ROOM

ET

(EXISTING)(EXISTING)

(EXISTING)

(EXISTING)

PUMP ROOM

GAS LINE SERVING

BOILERS. CONNECTS

TO MAIN ON LEVEL 1

HOT WATER

DISTRIBUTION TO

THE BUILDING

EXISTING PUMPS

HOT WATER

DISTRIBUTION TO

THE BUILDING

LOCKER ROOM

TO BOILER

ROOM

TO BOILER

ROOM

P

(NEW)

P

(NEW)

P

BOILER ROOM

BOILER EXHAUST

B

B

B

B

TO DOMESTIC COLD

WATER CONNECTION

PROVIDE EMERGENCY

SHUTOFF FOR BOILERS

TO PUMP

ROOM

TO PUMP

ROOM

ET

AS

(NEW)

EF

(NEW)

12" Ø

12"x8" OED

W/ WMS

" Ø

MOTORIZED DAMPER

(EXISTING)

(EXISTING) (EXISTING) (EXISTING) (EXISTING)

1 MECHANICAL DEMOLITION FLOOR PLAN

1/8" = 1'-0"

2 MECHANICAL NEW WORK FLOOR PLAN - PUMP ROOM

1/4" = 1'-0" 3 MECHANICAL NEW WORK FLOOR PLAN - BOILER ROOM

1/4" = 1'-0"

SCOPE OF WORK

1. INSPECT HOT WATER SYSTEM, INCLUDING BOILERS, PIPING, VALVES, PIPING, GAS LINE, COMBUSTION AIR, AND EXHAUST AIR. REPLACE ANY COMPONENTS THAT DO NOT MEET

SPECIFICATIONS.

2. DISCONNECT AND REMOVE HOT WATER PUMPS, AIR SEPARATOR, AND ASSOCIATED PIPING AND

VALVES. REFER TO FLOW DIAGRAM.

3. INSTALL BOILERS ON CONCRETE PAD.

4. INSTALL NEW HOT WATER PUMPS, AIR SEPARATOR, AND ASSOCIATED PIPING AND VALVES.

REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.

5. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING

OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.

6. PROVIDE UPDATE FIRE PROTECTION AND FIRE ALARM DEVICES.

7. INSTALL EXHAUST FAN AND DUCTWORK. RUN EXHAUST THROUGH EXISTING FUEL AND REMOVE

CAP.

8. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL

WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.

MECHANICAL FLOOR PLAN

BASEMENT LEVELM1.03

LOCOMOTIVE SHOP

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

B

SCALE:

BOILER/HOT WATER PIPING DEMOLITION

CONDENSATE

DRAIN PIPING

B

4" HWR

4" HWS

WATER

COLD

BACKFLOW

N.C.

MAKE-UP PRV

B

SCALE:

BOILER/HOT WATER PIPING DEMOLITION

CONDENSATE

DRAIN PIPING

B

P

4" HWR

4" HWS

WATER

COLD

BACKFLOW

N.C.

MAKE-UP PRV

ET

AAV

COMPRESSION TANK

DIAPHRAGM EXPANSION/

FLOOR MOUNTED

12"

SEE NOTE 1

FLOOR

RELIEF VALVE (TYP.)

TO 6" AFF

TO 6" AFF

AS

AAV (LARGE CAPACITY)

WITH HOSE BIBB

DRAIN OFF VALVE

ADJUST TO 0.5 TO 1 PSI

MAXIMUM PRESSURE DROP

ACROSS AIR SEPARATOR

REDUCE TO SIZE

OF AIR SEPARATOR

P

P

P

(EXISTING)

(EXISTING) (EXISTING)

(EXISTING)

PUMP

(EXISTING)

AIR SEPARATOR

(EXISTING)

EXPANSION TANK

(EXISTING)

PUMP

(EXISTING)

P

(EXISTING)

P

COUPON RACK

CHEMICAL FEED

T F

TEMPERATURE

SENSOR

FLOW

SENSOR

T F

T F

F

VFD

VFD

(EXISTING)

(EXISTING)

(EXISTING)

GENERAL NOTES

1. DEMO EXISTING PIPING AS INDICATED ON FLOW DIAGRAM #1 AND FLOOR PLANS.

2. PROVIDE NEW VALVES AND EQUIPMENT AS INDICATED ON FLOW DIAGRAM #2 AND FLOOR PLANS.

HOT WATER

FLOW DIAGRAMM2.01

HISTORY MUSEUM

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

B

SCALE: NTS

BOILER/HOT WATER PIPING NEW WORK

CONDENSATE

DRAIN PIPING

ET

AAV

12"

FLOOR

RELIEF VALVE (TYP.)

TO 6" AFF

TO 6" AFF

WATER

COLD

BACKFLOW

N.C.

MAKE-UP PRV

B

B

B

P

P

4" HWR

4" HWS

B

SCALE: NTS

BOILER/HOT WATER PIPING DEMOLITION

CONDENSATE

DRAIN PIPING

ET

AAV

12"

FLOOR

RELIEF VALVE (TYP.)

TO 6" AFF

TO 6" AFF

WATER

COLD

B

B

B

4" HWR

4" HWS

PUMP

(EXISTING)

FROM BUILDING

DISTRIBUTION

AS

AAV (LARGE CAPACITY)

WITH HOSE BIBB

DRAIN OFF VALVE

ADJUST TO 0.5 TO 1 PSI

MAXIMUM PRESSURE DROP

ACROSS AIR SEPARATOR

SEE NOTE 3 (TYP)

REDUCE TO SIZE

OF AIR SEPARATOR COUPON RACK

CHEMICAL FEED

END OF

MAIN

BYPASS

P

(EXISTING) (EXISTING) (EXISTING) (EXISTING)

(EXISTING)

(NEW)

(NEW)

(NEW)

TO BUILDING

DISTRIBUTION

BOILER MECHANICAL ROOM

T F

TEMPERATURE

SENSOR

FLOW

SENSOR

T F

T F

LOW FLOW BYPASS

PUMP MECHANICAL ROOM

BOILER MECHANICAL ROOM PUMP MECHANICAL ROOM

FROM BUILDING

DISTRIBUTION

TO BUILDING

DISTRIBUTION

PUMP

(EXISTING)

PUMP

(EXISTING)

AIR SEPARATOR

(EXISTING)

EXPANSION TANK

(EXISTING)

(EXISTING)

STRAINER AND

CONTROL VALVE

ARE PART OF THE

BOILER. (TYP)

F

VFD

VFD

(EXISTING)(EXISTING)(EXISTING)(EXISTING)

GENERAL NOTES

1. DEMO EXISTING PIPING AS INDICATED ON FLOW DIAGRAM #1 AND FLOOR PLANS.

2. PROVIDE NEW VALVES AND EQUIPMENTAS INDICATED ON FLOW DIAGRAM #2 AND FLOOR PLANS.

HOT WATER

FLOW DIAGRAMM2.02

LOCOMOTIVE SHOP

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

MANUFACTURER

AIR HANDLING UNIT SCHEDULE

UNIT

SUPPLY FAN

TOTAL

SUPPLY

(CFM)

TSP

(IN.WG.)

MOTOR DATA

RPM BHP HP

HOT WATER HEATING COIL

TOTAL

CAP.

(MBH)

FILTERS

FILTER (2")LOCATION

GPM

(BASE OF DESIGN)

RANGE TYPE

AHU-1

HOT WATER DATAOUTSIDE

AIR

(CFM) ROWS

OF

ECM2,92521,175 1.89 1550 4.6 851414 1340.2 4.02

PROVIDE SPLIT COILS1

FLOWRATE

FAN

QTY.

CFM

PER

5,294

FAN

ESP

(IN.WG.)

0.75

EA. EA.EA.

52.0

DAIKIN

SENSIBLETOTAL

CHILLED WATER COOLING COIL

FACECOOLING

(MBH)

COOLING

(MBH) VELOC.

(FPM)

791 588 411

EAT

DB(°F) WB(°F)

80.0 66.0

LAT

DB(°F) WB(°F)

54.6 53.7

(IN.WG)

P.D.

0.4640-100

FAN

DIA.

(IN.)

EFF %

30 8

MERV

NO.

2 ECM FANS

0.2

P.D. (IN.W.G.)

INIT. FINAL

1.0

MAX

ROWS

AIR DATA CHILLED WATER DATA

GPM (FT)(°F)(°F)

LWTEWT PD

154 45 55 15.3

ELECT. SERVICE

HZPHASEV

460 3 60

GLYCOL

AIR DATA

EAT

DB(°F)

LAT

DB(°F) (FT)

PD %

GLYCOL (FT)(°F)(°F)

LWTEWT PD

180 160

FLA

4.92

TO BUILDING

FACE

VELOC.

(FPM)

MAX

HISTORY MUSEUM

BASEMENT

CAPACITY

CONTROL

CFM VALUES LISTED ARE THE REQUIREMENTS FOR THE BUILDING AND DO NOT

INCLUDE WHEEL LEAKAFE OR PUMP REQUIREMENTS. MANUFACTURER SHALL SIZE

FANS AS REQUIRED TO PROVIDE SCHEDULED CFM VALUES TO THE BUILDING.

PROVIDED WITH DISCONNECT SWITCH

PROVIDE WITH VIBRATION ISOLATION CURB. REFER TO DETAIL AND PLANS FOR CURB HEIGHT REQUIREMENTS.

PUMP SCHEDULE

UNIT NO. SERVICE LOCATION

P-1 HW FOR HISTORY

MUSEUM

HW FOR HISTORY

MUSEUM

BASEMENT

HISTORY MUSEUM

BASEMENT

HISTORY MUSEUMP-2

2 PROVIDE VSD

PROVIDE DISCONNECT SWITCH

IMPELLERHEAD SHUT-OFFFLUID

TEMPTYPE

CASING

TYPE (FT.)GPM HEAD

(FT.) (IN.)

SIZE

MOTOR ELECT. SERVICEWORKING PUMP MANUFACTURER

BHPPRESS.

(PSIG) RPM PHASEHP VOLTS HZ

MODEL NUMBER

(AS STANDARD)

REMARKS

180°F 192 30 - 1729 1.94 480 3 60 BELL & GOSSET

E-1510

END

SUCTIONS

VFD

Y

180°F

350.8 7WATER

BELL & GOSSET

E-1510 21

192 30 480 3 60Y3WATEREND

SUCTIONS

AIR SEPARATOR SCHEDULE

GPM P.D.

FT. HD.

EXPANSION TANK SCHEDULE

TANK

ACCEPTANCE

VOLUME (GAL)

ET-1

UNIT

NO.

180 10 60 30

SYSTEM PRESSURE(PSIG)

AT TANK LOCATION

MIN

SYSTEM TEMP (°F)

MIN

SERVICE

MAX MAX

PRESSURE

RATING(PSI)

MAX OPER.

TANK AIR

CHARGE

(PSIG)

MANUFACTURER

MODEL NUMBER

(AS STANDARD)

REMARKS

BELL & GOSSETT

40 D-208

SERVICEUNIT

NO.

AS-1

MANUFACTURER

MODEL NUMBER

(AS STANDARD)

REMARKS

- ARMSTRONG VA-2192

CONNECTION

SIZE

IN

ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER.1

BUILT-IN STRAINER REQUIRED1

P-5 180°F 132 20 - 1200 0.88 480 3 60 BELL & GOSSET

e-80N1.023.5 7WATER 1

P-6 60°F 154 20 - 1612 1.07 480 3 60 BELL & GOSSET

e-80N1.523.5 5.625WATER 1

P-7

HW HISTORY

MUSUEM

AS-2 - ARMSTRONG VA-2192 2 1HW LOCOMOTIVE

SHOP

HW HISTORY

MUSUEM

HW FOR LOCOMOTIVE

SHOP

BASEMENT

LOCOMOTIVE SHOP

180°F 192 480 3 60 BELL & GOSSET

E-1510

END

SUCTIONS

YWATER 21

HW FOR LOCOMOTIVE

SHOP

BASEMENT

LOCOMOTIVE SHOP

180°F 192 480 3 60 BELL & GOSSET

E-1510

END

SUCTIONS

YWATER 21

HISTORY MUSEUM HW

FREEZE PROTECTION

BASEMENT

HISTORY MUSEUM

INLINE

HISTORY MUSEUM

FREEZE PROTECTION

BASEMENT

HISTORY MUSEUM

INLINE

FAN COIL UNIT SCHEDULE

UNIT NO.

FAN

CFM

(MAX)

E.S.P.

(IN.

WG)

W ELEC

V/Ø/Hz

FAN MOTOR COOLING COILS

TOTAL

MBH

SEN.

MBH

EAT

DB(°F)

EAT

WB(°F)

LAT

DB(°F)

LAT WB

(°F)

EWT

(°F)

LWT

(°F)

GPM

(MAX)

WPD

(FT.)

RUNOUT

PIPE SIZE

(IN)

MANUFACTURER

MODEL NUMBER

(AS STANDARD)

REMARKS

(IN. W.G.)

APD MBH GPM

HEATING COIL (HOT WATER)

WPD

(FT-WG)

EWT

(°F)

LWT

(°F) EAT (°F) LAT (°F)

RUNOUT

PIPE SIZE

(IN)GLYCOL

GLYCOL

1600 - 35 35 60 58 9.6 6 -45 5580

115/1/60 1-1/4

3/4 70715 - 14.3 12.8 60 58 3.5 6 6.4 4 20 85.1

1 2

1 2

JOHNSON CONTROLS

FNX-16

PROVIDE DISCONNECT SWITCH

45 55

FCU-1

FCU-2 1

30 0 180 160-

115/1/60

PROVIDE MERV-13 FILTER

P-8

REMARKS

Ø HZBHPRPM

MOTOR

HP(W) V

MODEL NUMBER

(AS STANDARD)

ELECTRIC SERVICEFAN FAN MANUFACTURER

FAN SCHEDULE

DRIVE VELOCITY

(FPM)

DIA.

(IN) TYPECFM

TYPE

FANSERVICE

(IN. W.G.)

E.S.P.

WHEEL OUTLET

LOCATION

NO.

UNIT

LOCOMOTIVE

SHOP 700EF-1 0.5 1 60115407-0.5 1047 0.11

PROVIDE EC MOTOR

STORAGE RM 1

GREENHECKCENTRIFUGAL SQ-120-VGDIRECTINLINE

UNIT SHALL BE BROUGHT INTO THE BUILDING IN MODULES AND CONSTRUCTED IN THE BASEMENT.6

REMARKS

1 2 3 4 5 6

3 PROVIDE MOTOR STARTER

- 1729 1.9450.8 7

60 - 1731 3.9277.7 8.5

60 - 1731 3.9277.7 8.5

JOHNSON CONTROLS

FSX-06

PROVIDE TEMPERTURE SENSOR AT AIR DISCHARGE AND LEAK DETECTION SENSOR IN DRAIN PAN. 3

7 PROVIDE CONTROL DAMPERS ARE OA, SA, AND RA INLETS.

7 PROVIDE SMOKE DETECTORS AT SA OUTLET AND RA INLET. CONNECT SENSORS TO BAD AND FIRE ALARM

SYSTEM. REFER TO CONTROL SEQUENCE FOR OPERATION.

MECHANICAL

SCHEDULESM3.01

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

PT PT

NOTES:

1. PROVIDE ABRASIVE SEPARATORS FOR MECHANICAL SEALS.

REDUCER AS

REQUIRED

4" HOUSE-

KEEPING

PAD (POS)

SPECIFIED

VIBRATION

ISOLATION

SYSTEM

(SEE SPEC)

FULL SIZE

SUCTION

DIFFUSER

W/STRAINER

COUPLING GUARD

INCREASER AS

REQUIRED

GLOBE TYPE

SILENT

CHECK VALVE

SPOOL PIECE

LUG BODY BUTTERFLY

VALVE WITH MEMORY

STOP FOR BALANCING

SPRING HANGERS FIRST 3

HANGERS OR 50' HORIZONTAL

HANGERS ADJUSTED FOR NO

LOAD ON PUMP FITTINGS

LUG BODY

BUTTERFLY

VALVE

(OPERATORS

AS SPECIFIED) 1/4" SS

TUBING

FLEX CONNECTOR WITH

THRUST RODS AS

REQUIRED (TYP)

STAINLESS STEEL BRAIDED

INLINE PUMP

DO NOT USE ANY SCREWS,

BECAUSE THEY INTERFERE

WITH DAMPER BLADE(S).

FOR HANGING DUCT:

TRAPEZE DUCT OR

STRAP HANGER AROUND

DUCT COMPLETELY.

PROVIDE EXTRA LENGTH

TO AVOID "PINCHING"

OF INSULATION AT

CORNERS.

BUTT ENDS

& SEAL

PROVIDE LOCKING

QUADRANT ARM

STANDOFF

PT

NC

3/4"

1 X 1 TEE WITH PLUGGED END

TYPICAL FOR 6

NOTES:

1. TYPICAL FOR, CHILLED WATER AND HOT WATER.

LOCATE IN MECH ROOM AS INSTRUCTED BY CHEMICAL

TREATMENT CONTRACTOR AND OWNER.

BALL VALVE

RETURN MAIN

SUPPLY MAIN

SHUNT FROM CHILLED OR

HOT WATER SUPPLY

RETURN

3/4"

5 GALLON FILTER

FEEDER TANK OR

OTHER SIZE AS

SPECIFIED ASME

RATED

TO CHILLED OR HOT

WATER RETURN

SHUT OFF/

BALANCING VALVE

WITH MEMORY STOP

SUPPLY

NOTE: USE TFE TAPE ON ALL THREADED

JOINTS.

HIGHEST POINT IN SYSTEM

4 PIPE DIAMETERS (WITH 18"MAX)

REDUCER

1/4" BRASS NIPPLE

1/4" GAGE COCK

1/4" TYPE "L" COPPER TUBE

NOTE: USE TFE TAPE ON ALL THREADED

JOINTS.

HIGHEST POINT IN SYSTEM

4 PIPE DIAMETERS (WITH 18"MAX)

REDUCER

1/4" BRASS NIPPLE

1/4" GAGE COCK

FLOAT-TYPE AIR VENT

1/4" TUBE TO SCHRAEDER ADAPTER

1/4" TYPE "L" COPPER TUBE

SCALE:

END SUCTION PUMP

SCALE:

SCALE:

COUPON RACK

TYPICAL DUCT INSULATION & SUPPORTS NEAR

VOLUME DAMPERS

DUCT PENETRATION OF FULL HEIGHT

PARTITIONS

NOTES:

1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE

THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.

2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.

3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.

1"

MAX. 60" SEE NOTE c

ANGLE IRON

THREADED

HANGER ROD

UNISTRUT OR

HANGER

STRAP

OVER 60"

GALV. HANGER

STEEL FRAME, ANGLE

1.25"X1.25"X0.125" ONLY AT

PENETRATIONS EXPOSED TO

VIEW IN NON-MECHANICAL OR

ELECTRICAL SPACES

SILICONE

ACOUSTICAL

AND AIRFLOW

SEALANT (TYP)

FRAMED

OPENING OR

SHEETMETAL

SLEEVE

SHEETMETAL

SLEEVE

MINERAL

FIBER

PACKING

SILICONE

ACOUSTICAL

AND

AIRFLOW

SEALANT

(TYP)NON-RATED

PARTITION

1/2" MAX

(TYP)

1/2" MAX

(TYP)

NON-RATED

PARTITIONNOTES:

1. AT FIRE RATED PARTITIONS WITHOUT FIRE DAMPER, REPLACE PACKING AND SILICONE SEALANT

WITH UL LISTED FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH UL LISTING.

2. FIRE STOP DUCT PENETRATIONS THRU RATED AND NON-RATED CORRIDOR WALLS ABOVE CEILINGS.

SCALE:

CHEMICAL FEED (FILTER FEEDER)

INLINE PUMP PIPING (EACH PUMP)

SCALE:

10 TYPICAL PIPE INSULATION &

VALVE HANDLE EXTENSION

SCALE:

7 AUTOMATIC AIR VENT ASSEMBLY

MANUAL AIR VENT ASSEMBLY

BUTT & SEAL

JOINTS

CAP INSULATION. LEAVE

NO EXPOSED INSULATION

ANYWHERE

PROVIDE VALVE

EXTENSION KIT

TO ALLOW PROPER

INSULATION COVERAGE

DIFF.

PRESSURE

SWITCH

SCALE:

DIFFERENTIAL PRESSURE SWITCH

SCALE:

DUCT HANGER SUPPORT

D et ai ls

MECHANICAL

DETAILSM4.01

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"MNPTx1/2"T SS CONN. COMPRESSION TYPE

AutoCAD SHX Text 1/2"ODx0.035 316SS SMLS TUBE

AutoCAD SHX Text 1/2"Tx1/2"Tx1/2"T TEE SS COMPRESSION TYPE

AutoCAD SHX Text

1/2" 3 VALVE MANIFOLD SS

AutoCAD SHX Text

1/2" BALL VALVE SS, 2000#

AutoCAD SHX Text

1/2"MNPT PLUG SS

AutoCAD SHX Text

1/2" TUBE UNION SS COMPRESSION TYPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ITEM

AutoCAD SHX Text

MATERIAL

AutoCAD SHX Text

BILL OF MATERIALS

AutoCAD SHX Text

QTY

AutoCAD SHX Text

PROVIDED BY

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text

INSTALLER

AutoCAD SHX Text A/R

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A/R

AutoCAD SHX Text

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text

1. SLOPE 1" PER FT DOWN TO INSTRUMENT

AutoCAD SHX Text

2. TUBING ROUTING SHALL AVOID HIGH TEMPERATURE SWIRLS. TUBING AND SUPPORTS SHALL INCLUDE PROVISIONS FOR THERMAL EXPANSION.

AutoCAD SHX Text

3. FOR STAND DETAIL SEE DWG. NO. FOR MOUNTING DETAIL SEE DWG. NO.

AutoCAD SHX Text

4. TUBING SHALL BE SUPPORTED EVERY 5'-0" WITH MILL GALVANIZED STRUT & STAINLESS STEEL TUBING CLAMPS.

AutoCAD SHX Text

5. IF UNABLE TO SUPPORT TUBING EVERY 5'-0", INSTRUMENT TUBE TRAY IS TO BE USED WITH THE APPROPRIATE TUBING CLAMPS.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

CONTRACTOR TO SUBMIT SKETCH OF PROPOSED INSTALLATION INCLUDING SIZES

OF MEMBERS, WELDS, & BOLTS TO STRUCTURAL ENGINEER FOR APPROVAL.

WELD ENTIRE LENGTH OF SUPPORT ANGLE WHERE SUPPORT ANGLE IS RUN

PARALLEL TO STRUCTURAL STEEL.

PIPES & LARGER

WELD (TYP)

NOTES:

SMALLER 1/2"

FOR 2" PIPES &

THICK FOR 2-1/2"

3/8" THICK PLATE

WELD (TYP)

(SEE NOTE 2)

TO STRUCTURAL STEEL

WELD SUPPORT ANGLE

2-1/2" & LARGER

INSULATION

PIPES 2" & SMALLER

2"x2"x1/4"> FOR

3"x3"x5/16"> FOR

TYPICAL FOR CHECK VALVES

AND BALANCING VALVES STRAINERS WITH BLOW-OFF.

TYPICAL FOR Y-BRANCH AND

TYPICAL FOR ALL VALVES

CASE

REMOVABLE

ENCLOSED IN

FIBERGLASS

BOARD.

CASE

REMOVABLE

CASE

REMOVABLE

NOTES:

1. INSULATION TO BE USED ON STEAM,

CONDENSATE RETURN, CHILLED WATER AND

CW MAKEUP PIPING. REFER TO INSULATION

SPEC FOR ADDITIONAL INSULATION FINISH ON

EXPOSED FITTINGS.

2. SEAL WATERTIGHT, ALL EXPOSED FIBERGLASS AND

WHERE TWO OR MORE PIECES OF INSULATION MEET.

INSULATION SHALL BE PER SPECIFICATION DENSITY

(EXCEPT AT HANGERS) AND THE SAME THICKNESS AS

THE ADJOINING PIPE INSULATION.

6" FROM LOUVER WITH TRAP

INTO PAPER IS GREATER THAN 5'-0"),

SHOWN OTHERWISE ON PLANS)

DUCT, 12" X 12" MIN (UNLESS

ACCESS DOOR HALF HEIGHT OF

"D"

DN

CAULK ALL AROUND

STORM-PROOF LOUVER

DRAIN AT 5'-0" CENTERS (IF DEPTH

NOTE: WHEN "D" IS OVER 24" PROVIDE 3/4"

& UP 12"

SOLDER BOTTOM JOINT

PITCH TO OUTSIDE

ALL AROUND

SEAL AND CAULK

SEE NOTE

UNUSED LOUVER AREA)

BOARD INSULATION (ALSO INSULATE

EXPOSED PARTS W/ 2" RIGID

LOUVER PLENUM INSULATE ALL

1/2" BIRDSCREEN

(POS)

PIPE ANCHOR DETAIL STRUCTURAL STEEL

SCALE: NTS

AHU COIL PIPING DETAILS

SCALE:

SCALE:

LOUVER CONNECTION

SCALE:

FAN COIL DETAIL

SCALE:

2-PIPE FAN COIL, 2-WAY CONTROL VALVE

4-PIPE FAN COIL, 2-WAY CONTROL VALVES

SCALE:

BLOW THROUGH UNIT CONDENSATE TRAP

SCALE:

7 PIPE HANGER SUPPORT

VALVE & STRAINER INSULATION DETAIL

115 - 240 65 - 115 40 - 65 21 - 40 14 - 21 0 -14

WATER

COIL

TO

ADD'L

COILS

REDUCE AS

NEEDED (TYP)

SEE NOTE 4

NOTE 8

RETURN

SUPPLY

2-1/2

1-1/2 1-1/4

FLOW (GPM)SIZE (IN)

COIL RUNOUT PIPING SIZING

CO

CO

CO

DOV

DOVAIR

FLOW

DRAIN

PAN(S)

PIPING

(COOLING

ONLY)

6" DIRT POCKET FULL

SIZE OF HEADER

SEE NOTE 6

(TYP)

SEE NOTE 7 (TYP)

DRAIN VALVES AT LOW POINTS OF ALL COIL

HEADERS SAME SIZE AS COIL-OUTLET SIZES BUT

NOT LESS THAN 3/8".

TRAP SEAL REFER TO DRAINPAN WATER SEAL

DETAIL (TYP)

NOTE 9

SEE

NOTE 5

NOTES :

1. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.

2. LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO FACILITATE COIL REMOVAL. PROVIDE

REDUCERS AS REQUIRED.

3. PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR TWO-SECTION-WIDE COIL ASSEMBLY.

4. TWO-WAY CONTROL VALVE SHOWN. SEE AUTOMATIC-TEMPERATURE-CONTROL DIAGRAM AND

SPECIFICATIONS FOR ACTUAL JOB REQUIREMENTS. FOR 3-WAY VALVE PROVIDE ADDITIONAL THERMOMETER

AND ISOLATION VALVE W/MEMORY STOP IN BYPASS LEG.

5. FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH UNIONS FOR ISOLATION.

6. FOR SUPPLY AND RETURN PIPES LARGER THAN 2" USE BUTTERFLY VALVES WITH FLANGES FOR ISOLATION.

7. REFER TO SPECIFICATIONS FOR DRAIN PAN REQUIREMENTS.

8. PROVIDE PROPER RANGE PRESSURE GAUGE OF FULL SCALE = 150% OF MAX PRESSURE OF PUMP.

9. REFER TO FREEZE PROTECTION PUMP DETAIL FOR ADDITIONAL REQUIREMENTS.

INDEPENDENT

DRAIN LINES

EXTEND TO

NEAREST

DRAIN (TYP)

ADJUSTABLE HANGER

WITH ROLLER

LOCKING NUT

SUPPORT NUT INSULATION

PIPE

PIPE COVERING

PROTECTION

16 GA SADDLE

GALVANIZED

INSULATION

SHIELD 12"LONG.

NOTES:

1. SEE SPECIFICATION FOR HANGER SIZES.

2. PIPE 8" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS.

3. FOR CHW SERVICE OVER 3" REPLACE SADDLE WITH 12" LONG 14 GA SHIELD WITH RIGID

INSULATION BETWEEN PIPE AND SHIELD.

MIN.9 lb/cft

DENSITY RIGID

INSULATION AT

SHIELD

CLEVIS HANGER

(FOR 1/2" UP TO

HEAVY DUTY

& INCL. 3" PIPE)

(FOR 4" TO 6" PIPE)

(c)

(b)

OUTLET.

(a)

(a)

(c)

(b)

DRAIN MUST BE LOWER THAN PAN

COILS AND MAXIMUM AIR FLOW).

DISCHARGE STATIC PRESSURE IN

THIS DIMENSION IN INCHES MUST BE

GREATER THAN THE MAXIMUM FAN

INCHES WC (WITH DIRTY FILTERS,

CLEANOUT (TYP.)

DRAIN PAN

NOTES: 1. ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP.

2. PITCH DRAIN FOR PROPER RUNOFF.

3. MANUALLY PRIME FILL TRAP BEFORE START-UP TO FORM

INITIAL DRAIN SEAL.

4. SUPPORT LENGTHY DRAIN LINES TO PREVENT SAG AND

CONDENSATE OVERFLOW.

1" WATER SEAL.

PITCH

PITCH

DRAIN PIPE

TO MATCH DRAIN

OUTLET SIZE.

COIL

COIL

SUPPLY RETURN

AND VALVES SHALL BE OVER EXTENDED DRAIN PAN.

WITHIN THE FAN COIL ENCLOSURE. UNINSULATED PIPE

ALL VALVES AND FITTINGS SHOWN ABOVE MUST FIT

NOTE:

PIPE COOLING COIL

TO DRAIN

DRAIN PAN

MAV

MAV

SUPPLYRETURN

NOTE:

PIPE DRAIN PAN TO DRAIN

COIL

RETURN SUPPLY

MAV

FILTER REMOVAL)

CEILING SERVICES WITH

COORDINATION OF OTHER

NECESSARY TO ALLOW

SIDE OR BOTTOM PULL IF

FILTER (MODIFY FRAME FOR

VALVES, ETC.

CONTROL VALVE, STRAINERS,

COMPONENTS INCLUDING

NOTE: INSULATE ALL PIPING

LINING

ACOUSTICAL

SEE SPECS

FLEX CONN

VIBRATION ISOLATION

SUPPORT FROM STRUCTURE

REFER TO WATER COIL

DETAIL FOR PIPING AND

DRAIN REQUIREMENTS

DUCTED

RETURN AIR

FLEX CONNECTION

(TYP)

h = DUCT HEIGHT w = DUCT WIDTH h w

NO. OF VANES

EQUIVALENT DIAMETER = (w+h)/2

WITHIN 2 EQUIV. DIA.:

WHEN 2 ELBOWS ARE

NO. OF VANES

DEPICTED HERE:

EXAMPLE AT LEFT IS

O U

TS

ID

E R

AD

IU

S

IN

IN

C

H

ES

IN

SI

D E

R

AD

IU

S

O F

EL

BO

W

IN

IN

C

H

ES

N O

. 1 O

F

N O

. 2 O

F

N O

. 3 O

F

N O

. 2 O

F

N O

. 1 O

F

N O

. 1 O

F

NUMBER OF SPLITTERS

OF 3 VANES.

NO. 2 VANE OF A TOTAL

"NO. 2 OF 3" =

OF 3 VANES.

NO. 1 VANE OF A TOTAL

"NO. 1 OF 3" =

TERMINOLOGY:

= INSIDE RADIUS

= CENTERLINE RADIUS

R r rR r/w = 0.5 IS A SQUARE THROAT ELBOW!

FOR 1 ELBOW:

r/w >= 1.50

1.5 > r/w >= 0.70

0.7 > r/w >= 0.60

0.6 > r/w >= 0.55

HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".

NOTE:

r/w RATIO:

RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS

R=20" R=2" R=4-1/4" R=9-1/4"

SHORT RADIUS ELBOW SPLITTER VANE

QUANTITY AND SPACING

SCALE: NTS

1. ALL VALVES AND FITTINGS SHOWN ABOVE MUST FIT WITHIN

THE FAN COIL ENCLOSURE.

2. UNINSULATED PIPE AND VALVES SHALL BE OVER EXTENDED

DRAIN PAN.

3. PROVIDE LEAK DETECTION SENSOR AT DRAIN PAN.

MECHANICAL

DETAILSM4.02

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text

MAV

AutoCAD SHX Text

MAV

AutoCAD SHX Text

MAV

AutoCAD SHX Text

MAV

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

GAS DOWN TO

UNDERGROUND

DISTRIBUTION

(EXISTING)

GAS METER

(EXISTING)

2 PSI GAS

REGULATOR

SERVING

BOILERS AND

WATER

HEATER.

(EXISTING)

2" GAS LINE

(EXISTING)

GAS LINE DOWN TO

BASEMENT

(EXISTING)

2" GAS LINE

(NEW)

HISTORY MUSEUM

LOCOMOTIVE SHOP

RUN GAS LINE THROUGH

EXTERIOR WALL. RUN LINE TO

HISTORY MUSEUM THROUGH

EXISTING TRENCH THAT

CONTAINS THE HOT WATER LINE.

2" GAS

LINE

(NEW)

ENTER HISTORY

MUSEUM THROUGH

AREAWAY. PROVIDE

GAS METER

CONNECT TO EXISTING BOILERS.

USE EXISTING PROPANE/NATURAL

GAS CONVERSION KITS TO CONVERT

BOILERS TO NATURAL GAS.

EXISTING TRENCH

OPTION 1

MECHANICAL SITE PLANM5.01

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text 1/16"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 15'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

2 PIPING NEW WORK BASEMENT FLOOR PLAN

1/8" = 1'-0"

SCOPE OF WORK

1. DEMOLISH CHILLED WATER WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED

PIPING AND VALVES. REFER TO FLOOR PLAN.

2. DISCONNECT UNDERGROUND CHW BRANCH PIPING FROM THE MAIN DISTRIBUTION LINE AT THE

VALVES. PRESSURE TEST EXISTING CHW PIPES ENTERING THE BUILDING.

3. INSTALL NEW CHILLED WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED

PIPING AND VALVES. REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.

4. INSTALL AIR COOLED CHILLER AT GRADE ON CONCRETE PAD. REFER TO FLOW DIAGRAM AND

DETAILS. CONNECT CHW PIPING TO EXISTING BRANCH PIPES IN THE VAULT NEXT TO THE

BUILDING.

5. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING

OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.

6. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL

WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.

1 PIPING DEMOLITION BASEMENT FLOOR PLAN

1/8" = 1'-0"

4" HWS/R

4" CHWS/R

TO UNDERGROUND

DISTRIBUTION

P

(EXISTING)

P

(EXISTING)

4" HWS/R

4" CHWS/R

TO UNDERGROUND

DISTRIBUTION

P

(NEW)

P

(NEW)

CH

(NEW)

AS

(NEW)

ET

(NEW)

OPTION 2

PIPING FLOOR PLAN

BASEMENT LEVELM6.01

HISTORY MUSEUM

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

COUPON RACK

CHEMICAL FEED

CH

P

P

SUPPORT WITH

SPECIFIED VIBRATION

ISOLATION (TYP)

AAV

PT

PT

FLEXIBLE DOUBLE SPHERE COUPLING

FLANGED CONNECTION

T

DOV W/HB

AIR-COOLED WATER CHILLER SCHEDULE

UNIT

NO. SERVICE LOCATION

MINIMUM

CAPACITY

(TONS) GPM

CHILLED WATER

EWT

(°F)

LWT

(°F)

MAX

P.D.

(FT)

REFRIG

TYPE QTY

COMPRESSOR

TYPE MAX

AMBIENT °F

MIN QTY HP

EA

CONDENSER FAN

RPM

ELECTRIC SERVICE

MCA V HZ

MANUFACTURER

REMARKS

CH-1 HISTORY BUILDING ON GRADE 70 160 55 45 5 R-410A 6 SCROLL 95 0 4 2 1160 169 460 3 60 YORK

YLAA 0070SE

Ø (AS STANDARD)%

GLYCOL

MODULES

PROVIDE DISCONNECT SWITCH AND STARTER.1

VFD FANS2

EXTERIOR INTERIOR

PUMP SCHEDULE

UNIT NO. SERVICE LOCATION

P-9 CHW FOR HISTORY

MUSEUM

CHW FOR HISTORY

MUSEUM

BASEMENT

HISTORY MUSEUM

BASEMENT

HISTORY MUSEUMP-10

2 PROVIDE VFD

PROVIDE DISCONNECT SWITCH

IMPELLERHEAD SHUT-OFFFLUID

TEMPTYPE

CASING

TYPE (FT.)GPM HEAD

(FT.) (IN.)

SIZE

MOTOR ELECT. SERVICEWORKING PUMP MANUFACTURER

BHPPRESS.

(PSIG) RPM PHASEHP VOLTS HZ

MODEL NUMBER

(AS STANDARD)

REMARKS

45°F 160 35 - 1563 1.82 480 3 60 BELL & GOSSET

E-1510

END

SUCTIONS

VFD

Y

45°F

350.0 7WATER

BELL & GOSSET

E-1510 21

160 35 480 3 60Y3WATEREND

SUCTIONS

4" CHWR

4" CHWS

SCALE:

AIR-COOLED WATER CHILLER PIPNG

AS

ET

AAV

COMPRESSION TANK

DIAPHRAGM EXPANSION/

FLOOR MOUNTED

12"

FLOOR

RELIEF VALVE (TYP.)

TO 6" AFF

TO 6" AFF

AIR SEPARATOR

AAV (LARGE CAPACITY)

WATER

COLD

PREVENTER

BACKFLOW

WITH HOSE BIBB

DRAIN OFF VALVE

N.C.

ADJUST TO 0.5 TO 1 PSI

MAXIMUM PRESSURE DROP

ACROSS AIR SEPARATOR

MAKE-UP PRV

SEE NOTE 3 (TYP)

REDUCE TO SIZE

OF AIR SEPARATOR

3/4"

12'' THICK CONCRETE PAD

#4'S @ 16'' O.C. EW

SIZE PAD TO 6'' GREATER THAN

CHILLER FOOTPRINT; ALL SIDES.

CHAMFER EDGES

COMPACTED GRANULAR BASE, 6''

AIR SEPARATOR SCHEDULE

GPM P.D.

FT. HD.

EXPANSION TANK SCHEDULE

TANK

ACCEPTANCE

VOLUME (GAL)

ET-3

UNIT

NO.

180 10 60 30

SYSTEM PRESSURE(PSIG)

AT TANK LOCATION

MIN

SYSTEM TEMP (°F)

MIN

SERVICE

MAX MAX

PRESSURE

RATING(PSI)

MAX OPER.

TANK AIR

CHARGE

(PSIG)

MANUFACTURER

MODEL NUMBER

(AS STANDARD)

REMARKS

BELL & GOSSETT

40 D-208

SERVICEUNIT

NO.

AS-1

MANUFACTURER

MODEL NUMBER

(AS STANDARD)

REMARKS

- ARMSTRONG VA-2160

CONNECTION

SIZE

IN

ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER.1

BUILT-IN STRAINER REQUIRED1

HW HISTORY

MUSUEMCHW HISTORY

MUSUEM

- 1563 1.8250.0 7

T F

TEMPERATURE

SENSOR

FLOW

SENSOR

T F

LOW FLOW BYPASS

END OF

MAIN

BYPASS

P

FROM BUILDING

DISTRIBUTION

TO BUILDING

DISTRIBUTION

F

VFD

VFD

T F

CHILLER PAD1

SCALE: NTS

6" 1'-0"

SUPPORT PIPING WITH

VIBRATION ISOLATION (TYP)

PROVIDE HEAT TRACE ON

ALL EXTERIOR PIPES

OPTION 2

CHILLED WATER

FLOW DIAGRAMM6.02

HISTORY MUSEUM

STEAMTOWN NATIONAL HISTORICAL SITE

335051

ELS

ELS

HACE

02/07/25

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

MAIN DISTRIBUTION PANEL, PANEL MDP:

277/480V, 3Ø, 4W, 600A MCB

CT'S

RELAYS

30 KVA TRANSFORMER:

480V TO 208Y/120 VOLTS

PANEL DP: 277/480V, 3Ø, 300A

ATS

PANEL DPE: 277V480 3Ø, 225A

NEW

CHILLER

480V, 3Ø, 169MCA

NEW AHU

480V, 16.8FLA

D

MDP

v v

P10

ELECTRICAL REVISIONS

P9P2P1 P6

P55

D

FCU-1

D

MDP

MDP

V

V

MDP

3-#3/0 & 1-#6G - 2"EMT.

7 65

P4P3

MDP MDP

AREAWAY

PANEL LP1: 120/208V, 3Ø, 225A

PANEL LPA: 277/480V, 3Ø, 100A

MDP MDP

MAIN DISTRIBUTION PANEL, PANEL MDP:

277/480V, 3Ø, 4W, 600A MCB

CT'S

RELAYS

30 KVA TRANSFORMER:

480V TO 208Y/120 VOLTS

PANEL DP: 277/480V, 3Ø, 300A

ATS

PANEL DPE: 277V480 3Ø, 225A

P10

D

MDP

ELECTRICAL REMOVALS

SCALE A

P9P2P1

D

FCU-1

MDP

AREAWAY

PANEL LP1: 120/208V, 3Ø, 225A

PANEL LPA: 277/480V, 3Ø, 100A

D SAFETY DISCONNECT SWITCH MOUNTED ON

THE WALL OR ASSOCIATED EQUIPMENT.

COMBINATION SAFETY SWITCH AND MOTOR

STARTER MOUNTED ON THE WALL.

DISCONNECT SWITCH AND VARIABLE

FREQUENCY DRIVE. VFD TO BE FURNISHED

BY THE HVAC CONTRACTOR AND MOUNTED

AND WIRED BY THE ELECTRICAL

CONTRACTOR.

EXISTING WIRING TO BE REMOVED.

EXISTING WIRING TO REMAIN.

NEW WIRING AND CONDUIT.

LEGEND

V

1. REMOVE TWO, EXISTING FEEDERS TO EXISTING HW PUMPS BACK

TO PANEL MDP.

2. REMOVE TWO, EXISTING FEEDERS TO EXISTING CW PUMPS BACK

TO PANEL MDP.

3. DISCONNECT, AND RETAIN, FEEDER TO EXISTING FCU-1. FCU-1 TO

BE REPLACED BY ANOTHER CONTRACTOR.

4. REMOVE EXISTING FEEDER TO EXISTING AHU-1 BACK TO PANEL

MDP.

5. FURNISH AND INSTALL TWO NEW DISCONNECT SWITCHES FOR

NEW HW PUMPS P1 & P2. MOUNT DISCONNECT SWITCHES AND

VFDS (SEE NOTE G1) ON THE WALL AND PROVIDE TWO NEW

FEEDERS FROM EXISTING 20A, 3P BREAKERS IN PANEL MDP FOR

NEW 480V, 3Ø, 3HP PUMPS.

6. FURNISH AND INSTALL TWO NEW DISCONNECT SWITCHES FOR

NEW CW PUMPS P9 & P10. MOUNT DISCONNECT SWITCHES AND

VFDS (SEE NOTE G1) ON THE WALL AND PROVIDE TWO NEW

FEEDERS FROM EXISTING 20A, 3P BREAKERS IN PANEL MDP FOR

NEW 480V, 3Ø, 3HP PUMPS.

7. CONNECT EXISTING FEEDER TO NEW 480V, 3Ø, 914W FCU-1.

8. FURNISH AND INSTALL NEW FEEDER TO NEW 480V, 3Ø, 4.92FLA

AHU-1.

9. FURNISH AND INSTALL TWO, NEW NEW FEEDERS TO TWO, NEW

HW FREEZE PROTECTION PUMPS, P5 (1HP) & P6 (1.5HP).

10. REMOVE EXISTING 125A, 3P CIRCUIT BREAKER AND FURNISH AND

INSTALL A NEW 200A, 3P CIRCUIT BREAKER FOR NEW CHILLER

CH-1. PROVIDE NEW TYPEWRITTEN PANEL SCHEDULE

REFLECTING NEW PUMPS IDENTIFICATION AND CHILLER.

11. EXISTING FCU-2 TO BE REPLACE WITH NEW FCU-2 RATED 120V,

1Ø, 142W BY ANOTHER CONTRACTOR .

12. DISCONNECT FEEDER FROM EXISTING FCU-2 AND RE-CONNECT

TO NEW FCU-2 AFTER SET-IN-PLACE BY OTHERS.

SHEET NOTES: #

1. DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO

SHOW GENERAL SYSTEM CONFIGURATION AND

PERFORMANCE. NOT ALL NECESSARY DEVICES AND

COMPONENTS ARE SHOWN. PROVIDE ALL DEVICES AND

COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM.

2. CONTRACT DRAWINGS AND SPECIFICATIONS ARE

COMPLEMENTARY AND MUST BE USED IN CONJUNCTION

TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.

CONTRACTOR SHALL COORDINATE ALL DRAWINGS AND

SPECIFICATIONS PRIOR TO COMMENCING WORK.

QUESTIONS REGARDING DESIGN INTENT OR SYSTEM

OPERATION SHALL BE PROMPTLY BROUGHT TO

ATTENTION OF THE COR.

3. THE TERM "REMOVE" MEANS DISCONNECT AND REMOVE

THE DEVICE, FEEDER, ETC, INCLUDING ALL ACCESSORIES

AND APPURTENANCES.

4. THE TERM “PROVIDE” MEANS FURNISH AND INSTALL,

COMPLETE AND READY FOR USE.

5. THE TERM “CONTRACT DOCUMENTS” MEANS THE

SPECIFICATIONS, DRAWINGS, ADDENDUMS, SKETCHES

AND OTHER DOCUMENTATION THAT DEFINE THE WORK.

6. ANY CONFLICTS BETWEEN SPECIFICATIONS AND

DRAWINGS SHALL BE PROMPTLY BROUGHT TO COR’S

ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH

ANY WORK EXCEPT AT THEIR OWN RISK, UNTIL

CLARIFICATIONS OF CONFLICTS ARE ISSUED TO THE

CONTRACTORS BY THE COR.

7. PROVIDE…