2025_0604_STEA_335051_Drawings.pdf
PDF 2 MB Posted
- Attached to
- STEA: REHABILIITATE MECHANICAL SYSTEM
- Solicitation number
- 140P4525R0016
About this file
These are mechanical engineering design drawings for a mechanical system rehabilitation project at Steamtown National Historical Site in Scranton, Pennsylvania. The comprehensive set of 16 technical drawings details extensive mechanical upgrades across multiple buildings, including the History Museum and Locomotive Shop. Key scope elements include:
Mechanical system modifications involve demolishing and replacing existing infrastructure such as air handling units (AHUs), hot water and chilled water pumps, boilers, air separators, expansion tanks, and associated piping and electrical systems. The project includes two implementation options (Option 1 and Option 2) with specific requirements for equipment installation, gas line modifications, electrical panel revisions, and system reconnections. Proposed equipment includes new AHUs, pumps, chillers, and control systems, with careful attention to integration with existing infrastructure and preservation of the historical site's mechanical systems. The drawings provide detailed floor plans, flow diagrams, equipment schedules, and installation specifications for comprehensive mechanical system rehabilitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P4525R0016_Amd_0003.pdf | ||
| STEAMTOWN_SITE_PHOTOS_History_Museum_0003.docx | DOCX document | |
| STEAMTOWN_SITE_PHOTOS_Loco_Shop_0003.docx | DOCX document | |
| B08_140P4525R0016__ALL_Questions_0002.docx | DOCX document | |
| Sol_140P4525R0016_Amd_0002.pdf | ||
| South_Exhibit_Buildings_with_Mark-ups_0002.pdf | ||
| Sol_140P4525R0016_Amd_0001.pdf | ||
| B08_140P4525R0016__Questions_and_Answers_0001.docx | DOCX document | |
| Site_Visit_Sign_In_Sheet_STEA_Rehabilitate_Mechanical_System_0001.pdf | ||
| B08_REV_2_Price_Schedule.docx | DOCX document | |
| Sol_140P4525R0016.pdf | ||
| B03_PA20250091_03142025.pdf | ||
| 2024_0604_335051_STEA_Specification.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. REFER TO ALL DRAWINGS SPECIFICATION FOR GENERAL DESCRIPTION OF AREAS REQUIRING DEMOLITION.
2. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR ALL EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY
OF THE OWNER.
3. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.
4. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.
5. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION. KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM HARVARD FACILITIES.
PROVIDE TEMPORARY SERVICES AS REQUIRED.
6. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS
SHOWN.
7. THIS CONTRACTOR SHALL PROVIDE SHUT DOWN OF SERVICES (BOILERS, AHU, PUMPS, ETC.) AND TRACING OF ALL PIPING WITHIN BASE BID.
HVAC DEMOLITION SPECIFICATION
1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL MX.XX SERIES DRAWINGS.
2. DRAWINGS ARE DIAGRAMMATIC, DETERMINE EXACT LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.
3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.
4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND STEEL PLATFORMS REQUIRED FOR MECHANICAL
WORK.
6. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.
7. SHEETMETAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED WITHOUT PRIOR CONSENT FROM
ARCHITECT/ENGINEER.
8. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND LEAKAGE CLASSES.
9. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS
CLOSE AS POSSIBLE TO WALL AND UNDERSIDE OF BEAMS AND JOISTS.
10. INSTALL THERMOSTATS AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA.
11. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY.
12. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS) AND TRANSITIONS
AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.
13. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE DUCT TRANSITIONS TO FURNISHED
EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONS BEFORE FABRICATION.
14. ACCESS PANELS SHALL BE PROVIDED TO CLEAN COILS AND SERVICE DAMPERS, HEATERS, VALVES AND ALL CONCEALED MECHANICAL
EQUIPMENT.
15. SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. PROVIDE TO GC A LIST OF ALL WEIGHTS AND METHODS OF SUPPORT FOR COORDINATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
16. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM IN ACCORDANCE WITH DIVISION 28 SPECIFICATIONS. MOUNT THE DETECTORS IN DUCTWORK. SMOKE DETECTORS SHALL BE INSTALLED AND WIRED TO THE BAS SYSTEM AND FAN STARTERS FOR SHUTDOWN
IN ACCORDANCE WITH DIVISION 23 SPECIFICATIONS.
17. SMOKE DAMPERS SHALL BE UL555S LISTED.
18. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.
19. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE FOR LINER IF APPLICABLE.
20. ALL MATERIALS AND EQUIPMENT SHALL BE NEW,
21. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.
22. ALL CONDENSATE DRAIN LINES SHALL HAVE A BALL VALVE AND CAPPED.
23. PROVIDE FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH 2018 INTERNATIONAL MECHANICAL CODE. FOR DUCTS THAT PENETRATE FIRE WALLS, FLOORS AND PARTITIONS PROVIDE SLEEVES WHERE PENETRATIONS ARE NOT PERPENDICULAR TO SURFACE PENETRATED. ENCLOSE DAMPERS IN 10 GAUGE STEEL SLEEVE.
24. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND AIR HANDLING UNITS UNLESS INTERNALLY ISOLATED. ALL DUCTS TO
BE GROUNDED ACROSS FLEXIBLE CONNECTION WITH FLEXIBLE COPPER GROUNDING STRAPS.
25. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT BLACK.
26. INSULATE PIPING AND DUCTWORK AS SPECIFIED: PERFORM TESTS SPECIFIED BEFORE INSULATING.
27. PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING.
28. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.
29. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO TERMINAL EQUIPMENT AND RISERS.
30. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA. MITERED (SQUARE) ELBOWS WITH TURNING VANES MAY NOT BE SUBMITTED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT/ENGINEER.
31. ISOLATION VALVES IN PIPING SYSTEMS ARE NOT SHOWN ON PLANS (FOR CLARITY) BUT ARE REQUIRED AT ALL PIPE BRANCHES AND
CONNECTIONS TO EQUIPMENT REFER TO DETAIL SHEETS AND FLOW DIAGRAMS.
32. PITCH PIPING 1 INCH IN 20 FEET MINIMUM IN DIRECTION OF FLOW, TO ALLOW FOR DRAINING
33. MANUAL DAMPERS ARE NOT SHOWN ON THE DRAWINGS IN ORDER FOR DRAWING CLARITY. PROVIDE MANUAL ADJUSTABLE DAMPERS ON EACH LOW PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT TAKE OFF, AND AT EACH TAKE OFF TO REGISTERS, GRILLES AND DIFFUSERS.
34. PROVIDE CEILING ACCESS PANELS BELOW ALL EQUIPMENT LOCATED ABOVE CEILINGS. EXACT SIZE AND LOCATION SHALL BE COORDINATED IN
FIELD WITH ARCHITECT.
GENERAL NOTESHYDRONIC SYSTEM SPECIFIC ABBREVIATIONSGENERIC HVAC ABBREVIATIONS
AIR SYSTEM SPECIFIC ABBREVIATIONS
GE
FSD
FPI
FLTR
FD
FCU
AC
ACC
ACD
AF
AHU
ALD
ATD
AVS
F F&B
FB
FC
FA
AIR CONDITIONING
AIR COOLED CONDENSER UNIT
AIR FOIL
AIR HANDLING UNIT
AIR VOLUME TRAVERSE STATION
FAN
FACE AND BYPASS
FAN BOX
FORWARD CURVED
FREE AREA
FIRE DAMPER (W/ ACCESS DOOR)
COMBINATION FIRE/SMOKE
DAMPER
FINS PER INCH
FILTER
GENERAL EXHAUST
°F °C Ø
DEGREES FAHRENHEIT
DIAMETER
DEGREES CELSIUS
ACV
AD
ADJ
ADDL
AFF
AFG
ALT
ALUM
AP
ARCH
ATC
ATV
AVG
BAS
BBD
BDT
BF
BFF
BHP
BLDG
BLR
BOD
BOP
BOT
BSMT
BTU
BTUH
C
CA
CF
CL
CLG
CO
COL
COMP
CONC
CONN
CONTR
CORR
CUF
CUH
CYL
CRCU
D
DB
DC
DDC
DDCFP
DIA
DIM
DN
DWG
EA
EAT
EFF
ECUH
ELEC
ELEV
EMER
EMS
ENT
EQUIP
EUH
EXH
EXP
FAS
FOB
FOT
FTR
FCV
FFOP
FG
FLEX
FLR
FLRDR
FP
FPM
FT
FT/SEC
FURN
FVNR
G
GA
GAL
GALV
GC
GND
GPH
GPM
GRD
GWB
H
HCPD
HD
HP
HPG
HR
HZ
HX
WRT
WG
WF
WB
W/O W/ W
VTR
VFD
VERT
VEL
V
TYP
TOP
TOD
TEMP
TEL
TEFC
TAV
TA
SUP
SUCT
STL
STDBY
STD
SS
SQFT
SQ
SPECS
SOV
SCH
RPM
RM
R.H.
REQS
REQD
RET
REP
R
PVC
PSIG
PSID
PSIA
PRIM
PR
PRESS
POS
PLBG
PH
PD
PCF
P
OV
OFOI
OFCI
ODP
OD
OC
OB
NTS
NOM
NO.
NO
NIC
NC
NC
N/A
MU
MTD
MIN
MH
MFR
MEZZ
MECH
MCC
MCA
MBH
MAX
M
LVG
LF
LAB
LB
L
KVA
KW
INSUL
IN
ID
AVERAGE
ATMOSPHERIC VENT
AUTOMATIC TEMPERATURE CONTROL
ARCHITECT
ACCESS PANEL
ALUMINUM
ALTERNATE
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
ADDITIONAL
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BASEMENT
BOTTOM
BOTTOM OF PIPE
BOTTOM OF DUCT
BOILER
BUILDING
BRAKE HORSEPOWER
BELOW FINISHED FLOOR
BOILER FEED WATER
BLOWDOWN TANK
BOILER BLOW DOWN
BUILDING AUTOMATION SYSTEM
COLD ROOM CONDENSING UNIT
CYLINDER
CABINET UNIT HEATER
CUBIC FEET
CORRIDOR
CONTRACTOR
CONNECTION
CONCRETE
COMPRESSOR
COLUMN
CLEAN-OUT
CEILING
CENTERLINE
CEILING FAN
COMPRESSED AIR
CONVECTOR
DRAIN
DRAWING
DOWN
DIMENSION
DIAMETER
DIRECT DIGITAL CONTROL FIELD PANEL
DIRECT DIGITAL CONTROL
DRY COOLER
DRY BULB TEMPERATURE
EXPANSION
EXHAUST
ELECTRIC UNIT HEATER
EQUIPMENT
ENTERING
ENERGY MANAGEMENT SYSTEM
EMERGENCY
ELEVATION
ELECTRICAL
ELECTRIC CABINET UNIT HEATER
EFFICIENCY
ENTERING AIR TEMPERATURE
EACH
FULL VOLTAGE NON-REVERSING
FURNISHED
FEET PER SECOND
FEET
FEET PER MINUTE
FIRE PROTECTION
FLOOR DRAIN
FLOOR
FLEXIBLE
FIBERGLASS
FIREFIGHTERS OVERRIDE PANEL
FLOW CONTROL VALVE
FINNED TUBE RADIATION
FLAT ON TOP
FLAT ON BOTTOM
FIRE ALARM SYSTEM
GYPSUM WALL BOARD
GRADE (GROUND LEVEL)
GALLONS PER MINUTE
GALLONS PER HOUR
GROUND
GENERAL CONTRACTOR
GALVANIZED
GALLONS
GAUGE
GAS
HEAT EXCHANGER
HERTZ
HOUR
HIGH PRESSURE GAS
HORSEPOWER
HEAD
HANDICAPPED
HEIGHT
WITH RESPECT TO
WATER GAUGE
WIDE FLANGE
WET BULB TEMPERATURE
WITHOUT
WITH
WIDTH
VENT THROUGH ROOF
VARIABLE FREQUENCY DRIVE
VERTICAL
VELOCITY
VENT
TYPICAL
TOP OF PIPE
TOP OF DUCT
TEMPERATURE
TELEPHONE
TOTALLY ENCLOSED FAN COOLED
THERMOSTATIC AIR VENT
THROW-AWAY
SUPPLY
SUCTION
STEEL
STANDBY
STANDARD
STAINLESS STEEL
SQUARE FEET
SQUARE
SPECIFICATIONS
REVOLUTIONS PER MINUTE
ROOM
RELATIVE HUMIDITY
REQUIREMENTS
REQUIRED
RETURN
REPRESENTATIVE
REHEAT
SCHEDULE
SOLENOID OPERATED VALVE
POLYVINYL CHLORIDE
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH DIFFERENTIAL
POUNDS PER SQUARE INCH ABSOLUTE
PRIMARY
PRESSURE REFERENCE
PRESSURE
PROVIDED BY OTHER SECTION(S)
PLUMBING
PHASE
PRESSURE DROP
POUNDS PER CUBIC FOOT
PERIMETER HEAT
OUTLET VELOCITY
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
OPEN DRIP PROOF
OUTSIDE DIAMETER
ON CENTER
OCTAVE BAND
NOT TO SCALE
NOMINAL
NUMBER
NORMALLY OPEN
NOT IN CONTRACT
NOISE CRITERIA
NORMALLY CLOSED
NOT APPLICABLE
MAKEUP WATER
MOUNTED
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MECHANICAL
MOTOR CONTROL CENTER
MINIMUM CIRCUIT AMPS
THOUSAND BRITISH THERMAL UNITS PER HOUR
MAXIMUM
ONE THOUSAND
LEAVING
LINEAR FEET
LABORATORY
POUND
LENGTH
KILOVOLT AMPERE
KILOWATT
INSULATION
INCHES
INSIDE DIAMETER
BDD
BI
BC
BSD
BACKDRAFT DAMPER
BACKWARD INCLINED
BLOWER COIL
BIOSEAL DAMPER
CC
CD
CFM
CG
COOLING COIL
CUBIC FEET PER MINUTE
CEILING DIFFUSER
CEILING GRILLE
CREF CHILLER ROOM EXHAUST FAN
CU CONDENSING UNIT
DIFF
DWDI DOUBLE WIDTH DOUBLE INLET
DIFFUSER
DWSI
DX DIRECT EXPANSION
DOUBLE WIDTH SINGLE INLET
EF
EG
EHC
EHU
ERU
ER
ERHC
ESP
EXHAUST FAN
EXHAUST GRILLE
ELECTRICAL HEATING COIL
EXHAUST AIR HANDLING UNIT
ENERGY RECOVERY UNIT
EXHAUST REGISTER
ELECTRIC REHEAT COIL
EXTERNAL STATIC PRESSURE
WMS
VVR
VVE
VV
VD
WIRE MESH SCREEN
VARIABLE VOLUME RETURN AIR TERMINAL BOX
VARIABLE VOLUME EXHAUST AIR TERMINAL BOX
VARIABLE VOLUME SUPPLY AIR TERMINAL BOX
VOLUME DAMPER
UC UNDERCUT DOOR
TSP
TR
TG
TF
TOTAL STATIC PRESSURE
TRANSFER
TRANSFER GRILLE
TRANSFER FAN
TEF DEDICATED TOILET EXHAUST FAN
TE TOILET EXHAUST
SWSI
SWDI
SV
SR
SP
SM
SGD
SG
SFD
SF
SEF
SDET
SD
SCR
SATT
SA
SINGLE WIDTH SINGLE INLET
SINGLE WIDTH DOUBLE INLET
VARIABLE VOLUME SUPPLY AIR TERMINAL BOX
SUPPLY REGISTER
STATIC PRESSURE
SHEETMETAL
SLIDE GATE DAMPER
SUPPLY GRILLE
COMBINATION AUTOMATIC SMOKE/FIRE
DAMPER WITH ACCESS DOOR
SUPPLY FAN
SMOKE EXHAUST FAN
SMOKE DETECTOR
SMOKE DAMPER
SCREEN
SOUND ATTENUATOR
SUPPLY AIR
RV
RS
RR
RLF
RL
RHC
RG
RF
RD
RA
RETURN AIR VALVE/BOX
REFRIGERANT SUCTION
RETURN REGISTER
RELIEF
REFRIGERANT LIQUID
REHEAT COIL
RETURN GRILLE
RETURN FAN
REFRIGERANT DISCHARGE (HOT GAS)
RETURN AIR
PHC PREHEAT COIL
OED
OBD
OAI
OA
OPEN END DUCT
OPPOSED BLADE DAMPER
OUTSIDE AIR INTAKE
OUTSIDE AIR
LVDR
LUVR
LD
LAT
LOUVERED DOOR
LOUVER
LINEAR DIFFUSER
LEAVING AIR TEMPERATURE
IH INTAKE HOOD
HU
HV
HRU
HPU
HEPA
HC
HUMIDIFIER
HEATING & VENTILATING UNIT
HEAT RECOVERY UNIT
HEAT PUMP UNIT
HIGH EFFICIENCY PARTICULATE AIR FILTER
HEATING COIL
GWCE
GH
GLASS WASH CENTER EXHAUST
GRAVITY HOOD
GEF GENERAL EXHAUST FAN
AIR SEPARATOR
AUTOMATIC AIR VENTAAV
AS
CH
CHEM
CHW
CHWR
CHWS
DOV
ET
EWT
GR
GS
GHW
GHWR
GHWS GLYCOL HOT WATER SUPPLY
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER
GLYCOL SUPPLY
GLYCOL RETURN
ENTERING WATER TEMPERATURE
EXPANSION TANK
DRAIN OFF VALVE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER
CHEMICAL FEED
CHILLER
HB
HCR
HCS
HRC
HW
HOSE BIBB CONN W/CHAINED CAP
HOT WATER
HEAT RECOVERY COIL - GLYCOL
HOT OR COLD WATER SUPPLY (DUAL TEMP)
HOT OR COLD WATER RETURN (DUAL TEMP)
UV
TDH
S(XXX)
RHWR
RHWS
T(XXX)
RHW
RH
RHP
PCHWS
PCHWR
PROCHW
PHX
PC
P
OS&Y
UNIT VENTILATOR
TOTAL DYNAMIC HEAD
TERTIARY (SYSTEM DEPENDENT PREFIX)
SECONDARY (SYSTEM DEPENDENT PREFIX)
REHEAT HOT WATER RETURN
REHEAT HOT WATER SUPPLY
REHEAT HOT WATER
REHEAT
RADIANT HEATING PANEL
PROCESS CHILLED WATER SUPPLY
PROCESS CHILLED WATER RETURN
PROCESS CHILLED WATER
PLATE HEAT EXCHANGER
PUMPED CONDENSATE
PUMP
OUTSIDE STEM AND YOKE
NET POSITIVE SUCTION HEAD
MANUAL AIR VENTMAV
NPSH
LWT
HWUH
HWS
HWR
HWRHC
HWPHC
HWHC
HWCUH HOT WATER CABINET UNIT HEATER
HOT WATER HEATING COIL
HOT WATER PREHEAT COIL
HOT WATER REHEAT COIL
HOT WATER RETURN
HOT WATER SUPPLY
HOT WATER UNIT HEATER
LEAVING WATER TEMPERATURE
VV SUPPLY VAV BOX
ADJUSTABLE
ACCESS DOOR
AUTOMATIC CONTROL VALVE
UH UNIT HEATER
SCHW SECONDARY CHILLED WATER
AIR TERMINAL DEVICE
ACOUSTICAL LINED DUCTWORK
AUTOMATIC CONTROL DAMPER
HR
HZ
HX HEAT EXCHANGER
HERTZ
HOUR
MECHANICAL
LEGENDM0.01
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
DN
UP
W
CO
MAV
AAV
PT
E
FM
S
OR
OR
OR
R w
GATE VALVE
BALL VALVE
BALL VALVE WITH MEMORY STOP (BALANCING VALVE)
BALL VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN VALVES)
BUTTERFLY VALVE
BUTTERFLY VALVE WITH MEMORY STOP (BALANCING VALVE)
GLOBE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
STRAINER W/BALL VALVE, HOSE BIBB & CAP (GATE VALVE FOR STEAM)
SOLENOID VALVE
AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR
AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE, TWO POSITION ACTUATOR
AUTOMATIC FLOW CONTROL VALVE (PRESSURE INDEPENDENT)
COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE (CIRCUIT SETTER)
FLOW MEASURING DEVICE
FLOW SWITCH
SAFETY RELIEF VALVE
UNION OR FLANGE (AS INDICATED BY PIPE SIZE - SEE SPEC.)
BLIND FLANGE
END CAP
PRESSURE GAUGE WITH GAUGE CLOCK
PRESSURE/TEMPERATURE WELL
AUTOMATIC AIR VENT WITH ISOLATION VALVE
MANUAL AIR VENT
REDUCER (ECCENTRIC-FLAT ON BOTTOM OR FLAT ON TOP)
REDUCER (CONCENTRIC)
FLEXIBLE CONNECTION
EXPANSION JOINT
PIPE GUIDE
ANCHOR
RISE (SINGLE LINE - PLAN VIEW)
DROP (SINGLE LINE - PLAN VIEW)
VALVE IN VERTICAL
TOP TAKEOFF
BOTTOM TAKEOFF
PIPE BREAK (SINGLE LINE)
WATER METER DIAL TYPE
DIRT LEG
CLEAN-OUT FOR CONDENSATE DRAIN
RISE (DOUBLE LINE - PLAN VIEW)
DROP (DOUBLE LINE - PLAN VIEW)
PIPE BREAK (DOUBLE LINE)
DIRECTION OF FLOW IN PIPE
PITCH PIPE UP IN DIRECTION OF FLOW
PITCH PIPE DOWN IN DIRECTION OF FLOW
NEW WORK
SUPPLY LINES
RETURN LINES
PIPING LEGENDDUCTWORK
SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE
ROUND SUPPLY
DUCT UP
SUPPLY
DUCT UP
ROUND SUPPLY
DUCT DN
SUPPLY DUCT
DOWN
STANDARD RADIUS
ELBOW
( R = W )
SUPPLY/RETURN
EXHAUST
SPLIT TAKE-OFF
W/ BRANCH DAMPERS
SUPPLY
BULLHEAD SPLIT
SUPPLY
CEILING DUCT
GOOD FOR
RING DUCT
TAKEOFF TO
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
CEILING DUCT
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
OPEN END
DUCT W/VD &
1/2"x1/2" WMS
FLEXIBLE
DUCT
RISE/DROP
RISE/DROP
ROUND RETURN OR
EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT DOWN
ROUND RETURN OR
EXHAUST DUCT
DN
HORIZONTAL
OFFSET
SUPPLY/RETURN
/EXHAUST
RISE OR DROP
SUPPLY/RETURN/
EXHAUST
RING
DUCT
90° TAKE-OFF W/BRANCH TAKE-OFF
VOLUME DAMPER (VD IN LOW PRESSURE
SYSTEMS ONLY)
BULLHEAD CONVERGE
RETURN/EXHAUST
W/BRANCH TAKE-OFF
VOLUME DAMPER
SIDEWALL DUCT MTD
REGISTER/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
SUPPLY SIDEWALL
LINEAR DIFFUSER
(W/ 1" INTERNALLY
LINED SM PLENUM)
BRANCH CONN
W/VD FOR EVERY
4' OF LINEAR
SUPPLY CEILING
LINEAR DIFFUSER (W/
1" INTERNALLY LINED
SM PLENUM) BRANCH
CONN W/VD FOR
EVERY 4' OF LINEAR BOOT
BY LD
MFR
AVS AIR VOLUME TRAVERSE STATION
WITH ACCESS DOOR
ROOF EXHAUST FAN
SHOWN ON ROOF
ROOF EXHAUST FAN
SHOWN ON FLOOR PLAN
RETURN OR EXHAUST
AIR FLOW
SUPPLY AIR FLOW
STANDARD 4-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 3-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 2-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 1-WAY BLOW
SUPPLY DIFFUSER
ALTERNATE CFM LOCATION
DESIGN CFM
(200) A(200)
SYMBOL DESIGNATES ASSOCIATED
SYSTEM OR SERVICE (ie HWS)
REFER TO DRAWINGS ( ) FOR
CONTINUATION XXX
SMOKE DETECTOR
PRESSURE TRANSMITTER
HUMIDITY INDICATOR
TEMPERATURE INDICATOR
HUMIDITY SENSOR
TEMPERATURE SENSOR
HUMIDISTAT
THERMOSTATSECTION DESIGNATION SHEET NUMBER
DETAIL DESIGNATION SHEET NUMBER
REVISION NUMBER
DIFFUSER, GRILLE, REGISTER LETTER
DESIGNATOR
CALL OUT SYMBOLS
M.XX
M.XX
SDET
P
MI
TI
MS
TS
C CARBON DIOXIDE SENSOR
MATCHLINE
BDD BACKDRAFT DAMPER
FSD COMBINATION SMOKE/FIRE
DAMPER W/ACCESS DOOR
SGD SLIDE GATE DAMPER
VD MANUAL VOLUME DAMPER
(OBD IN DIFFUSER)
ACD AUTOMATIC CONTROL DAMPER
W/ACCESS DOOR
SD AUTOMATIC SMOKE DAMPER
W/ACCESS DOOR
FD FIRE DAMPER W/ ACCESS DOOR
X PIPE ANCHOR FOR EXPANSION LOOP
PIPE GUIDE FOR EXPANSION LOOP
EQUIPMENT TAG SYMBOLS & ABBREVIATIONS
RH
VFD
C
C
C
VARIABLE FREQUENCY DRIVE
UNIT HEATER
CABINET HEATER
COOLING COIL
REHEAT COIL
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
W/ MODULATING ACTUATOR
W/ MODULATING ACTUATOR
W/ TWO POSITION ACTUATOR
BACKDRAFT DAMPER
PARALLEL BLADE DAMPER
W/ TWO POSITION ACTUATOR
OPPOSED BLADE DAMPER
ROOF FAN
FLOW DIAGRAM AND CONTROL DIAGRAM EQUIP SYMBOLS
C
H
HEATING COIL
FILTER BANK
INLINE CENTRIFUGAL FAN
CENTRIFUGAL FAN
PUMP
UPBLAST CENTRIFUGAL FAN
TAG
NO
TAG
NO
EXPANSION TANK
AIR SEPARATOR
CHEMICAL FEED SYSTEM
AIR TERMINAL BOX WITH
REHEAT COIL
AIR TERMINAL BOX
AAV
NOTE: REFER TO SCHEDULES FOR EQUIPMENT SPECIFIC DATA
OCCUPIED MAX CFM
UNOCCUPIED CFM
TERMINAL BOXVAV/VAVE
XXX
XXX
OCCUPIED MAX GPM
TERMINAL BOXVAV/VAVE
XXX
PUSH BUTTONPB
RF SHIELDED ROOM
EQUIPMENT NOT
REQUIRING
ELECTRIC SERVICE
EQUIPMENT
REQUIRING
ELECTRIC SERVICE
MECHANICAL
LEGENDM0.02
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
AIR VALVE
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AHU
1 DUCTWORK DEMOLITION FLOOR PLAN
1/8" = 1'-0"
2 DUCTWORK NEW WORK FLOOR PLAN
1/8" = 1'-0"
SCOPE OF WORK
1. DISCONNECT AND REMOVE EXISTING AHU. DEMOLISH DUCTWORK INDICATED ON PLANS.
2. NEW AHU SHALL BE BROUGHT IN THROUGH AREAWAY. REMOVE LOUVER AND FLOOR GRATE.
STORE ITEMS TO BE RE-INSTALLED AFTER AHU INSTILLATION.
3. AHU SHALL BE BROUGHT IN BY MODULES AND CONSTRUCTED IN THE BASEMENT.
4. RE-CONNECT DUCTWORK AND PIPING TO AHU. PROVIDE DAMPERS, VALVES, TEMPERATURE, AND
PRESSURE GAUGES AS INDICATED ON DRAWINGS AND DETAILS.
5. INSPECT BOILER VENT PIPES. REPLACE ANY COMPONENTS THAT DO NOT MEET SPECIFICATIONS.
6. INSPECT AND CLEAN EXISTING DUCTWORK. REPLACE ANY DAMAGED OF RUSTED DUCTWORK.
REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL DUCTWORK.
7. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL
WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.
BASE DESIGN - AHU
44"x44" SA
44"x44" EXISTING
SUPPLY RISER
70"x40" SA90"x20" RA 48"x48" EXISTING
RETURN AIR RISER
90"x64" OA
(NEW)
AHU
(EXISTING)
B
B
VENT AND COMBUSTION AIR
UP THROUGH AREA WAY
(EXISTING) (EXISTING)
DUCTWORK FLOOR PLAN
BASEMENT LEVELM1.01
HISTORY MUSEUM
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACEC
02/07/25
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
1 PIPING DEMOLITION BASEMENT FLOOR PLAN
1/8" = 1'-0"
2 PIPING NEW WORK BASEMENT FLOOR PLAN
1/8" = 1'-0"
SCOPE OF WORK
1. INSPECT HOT WATER SYSTEM, INCLUDING BOILERS, PUMPS, VALVES, PIPING, GAS LINE,
COMBUSTION AIR, AND EXHAUST AIR. REPLACE ANY COMPONENTS THAT DO NOT MEET
SPECIFICATIONS.
2. DISCONNECT AND REMOVE HOT WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND
ASSOCIATED PIPING AND VALVES. REFER TO FLOW DIAGRAM.
3. DISCONNECT AND REMOVE AHU. DEMO PIPING CONNECTIONS
4. INSTALL BOILERS ON CONCRETE PAD.
5. INSTALL NEW HOT WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED PIPING
AND VALVES. REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.
6. RECONNECT HOT WATER AND CHILLED WATER COILS TO THE NEW AHU. REFER TO DETAIL FOR
PIPING CONFIGURATION AND ASSOCIATE VALVES/GAUGES.
7. INSTALL NEW FCUS. RECONNECT HOT WATER, CHILLED WATER, AND CONDENSATE PIPING. REFER
TO DETAIL FOR PIPING CONFIGURATION AND ASSOCIATE VALVES/GAUGES.
8. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING
OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.
9. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL
WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.
10. BOILERS ARE PROPANE. CONTINUE RENTING PROPANE TANKS. IF OPTION 1 IS APPROVED, THEN
BOILERS SHALL BE CONVERTED TO NATURAL GAS AND PROPANE SYSTEM SHALL BE REMOVED.
4" HWS/R
4" CHWS/R
TO UNDERGROUND
DISTRIBUTION
B
B
4" HWS/R
4" CHWS/R
TO UNDERGROUND
DISTRIBUTION
B
B
AHU
(NEW)
P
(NEW)
P
(NEW)
AS
(NEW)
ET
(NEW)
P
P
P
(EXISTING)
P
(EXISTING)
P
(NEW)
P
(NEW)
FCU
(EXISTING)
FCU
(NEW)
3 PIPING NEW WORK LEVEL 1FLOOR PLAN
1/8" = 1'-0"
FCU
(NEW)
PROPANE UP
TO TANKS
(EXISTING)(EXISTING)
PROPANE UP
TO TANKS
PIPING FLOOR PLAN
BASEMENT LEVELM1.02
HISTORY MUSEUM
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
BASE DESIGN - LOCO SHOP
PUMP ROOM
BOILER ROOM
GAS LINE SERVING
BOILERS. CONNECTS
TO MAIN ON LEVEL 1
EXISTING PIPING
HOT WATER
DISTRIBUTION TO
THE BUILDING
EXISTING PUMPS
EXISTING PUMP
EXISTING PUMPS
EXISTING AIR SEPARATOR
EXISTING EXPANSION TANK
HOT WATER
DISTRIBUTION TO
THE BUILDING
BOILER EXHAUST
B
B
B
B
(EXISTING)
TO DOMESTIC COLD
WATER CONNECTION
LOCKER ROOM
ET
(EXISTING)(EXISTING)
(EXISTING)
(EXISTING)
PUMP ROOM
GAS LINE SERVING
BOILERS. CONNECTS
TO MAIN ON LEVEL 1
HOT WATER
DISTRIBUTION TO
THE BUILDING
EXISTING PUMPS
HOT WATER
DISTRIBUTION TO
THE BUILDING
LOCKER ROOM
TO BOILER
ROOM
TO BOILER
ROOM
P
(NEW)
P
(NEW)
P
BOILER ROOM
BOILER EXHAUST
B
B
B
B
TO DOMESTIC COLD
WATER CONNECTION
PROVIDE EMERGENCY
SHUTOFF FOR BOILERS
TO PUMP
ROOM
TO PUMP
ROOM
ET
AS
(NEW)
EF
(NEW)
12" Ø
12"x8" OED
W/ WMS
" Ø
MOTORIZED DAMPER
(EXISTING)
(EXISTING) (EXISTING) (EXISTING) (EXISTING)
1 MECHANICAL DEMOLITION FLOOR PLAN
1/8" = 1'-0"
2 MECHANICAL NEW WORK FLOOR PLAN - PUMP ROOM
1/4" = 1'-0" 3 MECHANICAL NEW WORK FLOOR PLAN - BOILER ROOM
1/4" = 1'-0"
SCOPE OF WORK
1. INSPECT HOT WATER SYSTEM, INCLUDING BOILERS, PIPING, VALVES, PIPING, GAS LINE, COMBUSTION AIR, AND EXHAUST AIR. REPLACE ANY COMPONENTS THAT DO NOT MEET
SPECIFICATIONS.
2. DISCONNECT AND REMOVE HOT WATER PUMPS, AIR SEPARATOR, AND ASSOCIATED PIPING AND
VALVES. REFER TO FLOW DIAGRAM.
3. INSTALL BOILERS ON CONCRETE PAD.
4. INSTALL NEW HOT WATER PUMPS, AIR SEPARATOR, AND ASSOCIATED PIPING AND VALVES.
REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.
5. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING
OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.
6. PROVIDE UPDATE FIRE PROTECTION AND FIRE ALARM DEVICES.
7. INSTALL EXHAUST FAN AND DUCTWORK. RUN EXHAUST THROUGH EXISTING FUEL AND REMOVE
CAP.
8. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL
WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.
MECHANICAL FLOOR PLAN
BASEMENT LEVELM1.03
LOCOMOTIVE SHOP
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
B
SCALE:
BOILER/HOT WATER PIPING DEMOLITION
CONDENSATE
DRAIN PIPING
B
4" HWR
4" HWS
WATER
COLD
BACKFLOW
N.C.
MAKE-UP PRV
B
SCALE:
BOILER/HOT WATER PIPING DEMOLITION
CONDENSATE
DRAIN PIPING
B
P
4" HWR
4" HWS
WATER
COLD
BACKFLOW
N.C.
MAKE-UP PRV
ET
AAV
COMPRESSION TANK
DIAPHRAGM EXPANSION/
FLOOR MOUNTED
12"
SEE NOTE 1
FLOOR
RELIEF VALVE (TYP.)
TO 6" AFF
TO 6" AFF
AS
AAV (LARGE CAPACITY)
WITH HOSE BIBB
DRAIN OFF VALVE
ADJUST TO 0.5 TO 1 PSI
MAXIMUM PRESSURE DROP
ACROSS AIR SEPARATOR
REDUCE TO SIZE
OF AIR SEPARATOR
P
P
P
(EXISTING)
(EXISTING) (EXISTING)
(EXISTING)
PUMP
(EXISTING)
AIR SEPARATOR
(EXISTING)
EXPANSION TANK
(EXISTING)
PUMP
(EXISTING)
P
(EXISTING)
P
COUPON RACK
CHEMICAL FEED
T F
TEMPERATURE
SENSOR
FLOW
SENSOR
T F
T F
F
VFD
VFD
(EXISTING)
(EXISTING)
(EXISTING)
GENERAL NOTES
1. DEMO EXISTING PIPING AS INDICATED ON FLOW DIAGRAM #1 AND FLOOR PLANS.
2. PROVIDE NEW VALVES AND EQUIPMENT AS INDICATED ON FLOW DIAGRAM #2 AND FLOOR PLANS.
HOT WATER
FLOW DIAGRAMM2.01
HISTORY MUSEUM
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
B
SCALE: NTS
BOILER/HOT WATER PIPING NEW WORK
CONDENSATE
DRAIN PIPING
ET
AAV
12"
FLOOR
RELIEF VALVE (TYP.)
TO 6" AFF
TO 6" AFF
WATER
COLD
BACKFLOW
N.C.
MAKE-UP PRV
B
B
B
P
P
4" HWR
4" HWS
B
SCALE: NTS
BOILER/HOT WATER PIPING DEMOLITION
CONDENSATE
DRAIN PIPING
ET
AAV
12"
FLOOR
RELIEF VALVE (TYP.)
TO 6" AFF
TO 6" AFF
WATER
COLD
B
B
B
4" HWR
4" HWS
PUMP
(EXISTING)
FROM BUILDING
DISTRIBUTION
AS
AAV (LARGE CAPACITY)
WITH HOSE BIBB
DRAIN OFF VALVE
ADJUST TO 0.5 TO 1 PSI
MAXIMUM PRESSURE DROP
ACROSS AIR SEPARATOR
SEE NOTE 3 (TYP)
REDUCE TO SIZE
OF AIR SEPARATOR COUPON RACK
CHEMICAL FEED
END OF
MAIN
BYPASS
P
(EXISTING) (EXISTING) (EXISTING) (EXISTING)
(EXISTING)
(NEW)
(NEW)
(NEW)
TO BUILDING
DISTRIBUTION
BOILER MECHANICAL ROOM
T F
TEMPERATURE
SENSOR
FLOW
SENSOR
T F
T F
LOW FLOW BYPASS
PUMP MECHANICAL ROOM
BOILER MECHANICAL ROOM PUMP MECHANICAL ROOM
FROM BUILDING
DISTRIBUTION
TO BUILDING
DISTRIBUTION
PUMP
(EXISTING)
PUMP
(EXISTING)
AIR SEPARATOR
(EXISTING)
EXPANSION TANK
(EXISTING)
(EXISTING)
STRAINER AND
CONTROL VALVE
ARE PART OF THE
BOILER. (TYP)
F
VFD
VFD
(EXISTING)(EXISTING)(EXISTING)(EXISTING)
GENERAL NOTES
1. DEMO EXISTING PIPING AS INDICATED ON FLOW DIAGRAM #1 AND FLOOR PLANS.
2. PROVIDE NEW VALVES AND EQUIPMENTAS INDICATED ON FLOW DIAGRAM #2 AND FLOOR PLANS.
HOT WATER
FLOW DIAGRAMM2.02
LOCOMOTIVE SHOP
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
MANUFACTURER
AIR HANDLING UNIT SCHEDULE
UNIT
SUPPLY FAN
TOTAL
SUPPLY
(CFM)
TSP
(IN.WG.)
MOTOR DATA
RPM BHP HP
HOT WATER HEATING COIL
TOTAL
CAP.
(MBH)
FILTERS
FILTER (2")LOCATION
GPM
(BASE OF DESIGN)
RANGE TYPE
AHU-1
HOT WATER DATAOUTSIDE
AIR
(CFM) ROWS
OF
ECM2,92521,175 1.89 1550 4.6 851414 1340.2 4.02
PROVIDE SPLIT COILS1
FLOWRATE
FAN
QTY.
CFM
PER
5,294
FAN
ESP
(IN.WG.)
0.75
EA. EA.EA.
52.0
DAIKIN
SENSIBLETOTAL
CHILLED WATER COOLING COIL
FACECOOLING
(MBH)
COOLING
(MBH) VELOC.
(FPM)
791 588 411
EAT
DB(°F) WB(°F)
80.0 66.0
LAT
DB(°F) WB(°F)
54.6 53.7
(IN.WG)
P.D.
0.4640-100
FAN
DIA.
(IN.)
EFF %
30 8
MERV
NO.
2 ECM FANS
0.2
P.D. (IN.W.G.)
INIT. FINAL
1.0
MAX
ROWS
AIR DATA CHILLED WATER DATA
GPM (FT)(°F)(°F)
LWTEWT PD
154 45 55 15.3
ELECT. SERVICE
HZPHASEV
460 3 60
GLYCOL
AIR DATA
EAT
DB(°F)
LAT
DB(°F) (FT)
PD %
GLYCOL (FT)(°F)(°F)
LWTEWT PD
180 160
FLA
4.92
TO BUILDING
FACE
VELOC.
(FPM)
MAX
HISTORY MUSEUM
BASEMENT
CAPACITY
CONTROL
CFM VALUES LISTED ARE THE REQUIREMENTS FOR THE BUILDING AND DO NOT
INCLUDE WHEEL LEAKAFE OR PUMP REQUIREMENTS. MANUFACTURER SHALL SIZE
FANS AS REQUIRED TO PROVIDE SCHEDULED CFM VALUES TO THE BUILDING.
PROVIDED WITH DISCONNECT SWITCH
PROVIDE WITH VIBRATION ISOLATION CURB. REFER TO DETAIL AND PLANS FOR CURB HEIGHT REQUIREMENTS.
PUMP SCHEDULE
UNIT NO. SERVICE LOCATION
P-1 HW FOR HISTORY
MUSEUM
HW FOR HISTORY
MUSEUM
BASEMENT
HISTORY MUSEUM
BASEMENT
HISTORY MUSEUMP-2
2 PROVIDE VSD
PROVIDE DISCONNECT SWITCH
IMPELLERHEAD SHUT-OFFFLUID
TEMPTYPE
CASING
TYPE (FT.)GPM HEAD
(FT.) (IN.)
SIZE
MOTOR ELECT. SERVICEWORKING PUMP MANUFACTURER
BHPPRESS.
(PSIG) RPM PHASEHP VOLTS HZ
MODEL NUMBER
(AS STANDARD)
REMARKS
180°F 192 30 - 1729 1.94 480 3 60 BELL & GOSSET
E-1510
END
SUCTIONS
VFD
Y
180°F
350.8 7WATER
BELL & GOSSET
E-1510 21
192 30 480 3 60Y3WATEREND
SUCTIONS
AIR SEPARATOR SCHEDULE
GPM P.D.
FT. HD.
EXPANSION TANK SCHEDULE
TANK
ACCEPTANCE
VOLUME (GAL)
ET-1
UNIT
NO.
180 10 60 30
SYSTEM PRESSURE(PSIG)
AT TANK LOCATION
MIN
SYSTEM TEMP (°F)
MIN
SERVICE
MAX MAX
PRESSURE
RATING(PSI)
MAX OPER.
TANK AIR
CHARGE
(PSIG)
MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
BELL & GOSSETT
40 D-208
SERVICEUNIT
NO.
AS-1
MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
- ARMSTRONG VA-2192
CONNECTION
SIZE
IN
ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER.1
BUILT-IN STRAINER REQUIRED1
P-5 180°F 132 20 - 1200 0.88 480 3 60 BELL & GOSSET
e-80N1.023.5 7WATER 1
P-6 60°F 154 20 - 1612 1.07 480 3 60 BELL & GOSSET
e-80N1.523.5 5.625WATER 1
P-7
HW HISTORY
MUSUEM
AS-2 - ARMSTRONG VA-2192 2 1HW LOCOMOTIVE
SHOP
HW HISTORY
MUSUEM
HW FOR LOCOMOTIVE
SHOP
BASEMENT
LOCOMOTIVE SHOP
180°F 192 480 3 60 BELL & GOSSET
E-1510
END
SUCTIONS
YWATER 21
HW FOR LOCOMOTIVE
SHOP
BASEMENT
LOCOMOTIVE SHOP
180°F 192 480 3 60 BELL & GOSSET
E-1510
END
SUCTIONS
YWATER 21
HISTORY MUSEUM HW
FREEZE PROTECTION
BASEMENT
HISTORY MUSEUM
INLINE
HISTORY MUSEUM
FREEZE PROTECTION
BASEMENT
HISTORY MUSEUM
INLINE
FAN COIL UNIT SCHEDULE
UNIT NO.
FAN
CFM
(MAX)
E.S.P.
(IN.
WG)
W ELEC
V/Ø/Hz
FAN MOTOR COOLING COILS
TOTAL
MBH
SEN.
MBH
EAT
DB(°F)
EAT
WB(°F)
LAT
DB(°F)
LAT WB
(°F)
EWT
(°F)
LWT
(°F)
GPM
(MAX)
WPD
(FT.)
RUNOUT
PIPE SIZE
(IN)
MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
(IN. W.G.)
APD MBH GPM
HEATING COIL (HOT WATER)
WPD
(FT-WG)
EWT
(°F)
LWT
(°F) EAT (°F) LAT (°F)
RUNOUT
PIPE SIZE
(IN)GLYCOL
GLYCOL
1600 - 35 35 60 58 9.6 6 -45 5580
115/1/60 1-1/4
3/4 70715 - 14.3 12.8 60 58 3.5 6 6.4 4 20 85.1
1 2
1 2
JOHNSON CONTROLS
FNX-16
PROVIDE DISCONNECT SWITCH
45 55
FCU-1
FCU-2 1
30 0 180 160-
115/1/60
PROVIDE MERV-13 FILTER
P-8
REMARKS
Ø HZBHPRPM
MOTOR
HP(W) V
MODEL NUMBER
(AS STANDARD)
ELECTRIC SERVICEFAN FAN MANUFACTURER
FAN SCHEDULE
DRIVE VELOCITY
(FPM)
DIA.
(IN) TYPECFM
TYPE
FANSERVICE
(IN. W.G.)
E.S.P.
WHEEL OUTLET
LOCATION
NO.
UNIT
LOCOMOTIVE
SHOP 700EF-1 0.5 1 60115407-0.5 1047 0.11
PROVIDE EC MOTOR
STORAGE RM 1
GREENHECKCENTRIFUGAL SQ-120-VGDIRECTINLINE
UNIT SHALL BE BROUGHT INTO THE BUILDING IN MODULES AND CONSTRUCTED IN THE BASEMENT.6
REMARKS
1 2 3 4 5 6
3 PROVIDE MOTOR STARTER
- 1729 1.9450.8 7
60 - 1731 3.9277.7 8.5
60 - 1731 3.9277.7 8.5
JOHNSON CONTROLS
FSX-06
PROVIDE TEMPERTURE SENSOR AT AIR DISCHARGE AND LEAK DETECTION SENSOR IN DRAIN PAN. 3
7 PROVIDE CONTROL DAMPERS ARE OA, SA, AND RA INLETS.
7 PROVIDE SMOKE DETECTORS AT SA OUTLET AND RA INLET. CONNECT SENSORS TO BAD AND FIRE ALARM
SYSTEM. REFER TO CONTROL SEQUENCE FOR OPERATION.
MECHANICAL
SCHEDULESM3.01
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
PT PT
NOTES:
1. PROVIDE ABRASIVE SEPARATORS FOR MECHANICAL SEALS.
REDUCER AS
REQUIRED
4" HOUSE-
KEEPING
PAD (POS)
SPECIFIED
VIBRATION
ISOLATION
SYSTEM
(SEE SPEC)
FULL SIZE
SUCTION
DIFFUSER
W/STRAINER
COUPLING GUARD
INCREASER AS
REQUIRED
GLOBE TYPE
SILENT
CHECK VALVE
SPOOL PIECE
LUG BODY BUTTERFLY
VALVE WITH MEMORY
STOP FOR BALANCING
SPRING HANGERS FIRST 3
HANGERS OR 50' HORIZONTAL
HANGERS ADJUSTED FOR NO
LOAD ON PUMP FITTINGS
LUG BODY
BUTTERFLY
VALVE
(OPERATORS
AS SPECIFIED) 1/4" SS
TUBING
FLEX CONNECTOR WITH
THRUST RODS AS
REQUIRED (TYP)
STAINLESS STEEL BRAIDED
INLINE PUMP
DO NOT USE ANY SCREWS,
BECAUSE THEY INTERFERE
WITH DAMPER BLADE(S).
FOR HANGING DUCT:
TRAPEZE DUCT OR
STRAP HANGER AROUND
DUCT COMPLETELY.
PROVIDE EXTRA LENGTH
TO AVOID "PINCHING"
OF INSULATION AT
CORNERS.
BUTT ENDS
& SEAL
PROVIDE LOCKING
QUADRANT ARM
STANDOFF
PT
NC
3/4"
1 X 1 TEE WITH PLUGGED END
TYPICAL FOR 6
NOTES:
1. TYPICAL FOR, CHILLED WATER AND HOT WATER.
LOCATE IN MECH ROOM AS INSTRUCTED BY CHEMICAL
TREATMENT CONTRACTOR AND OWNER.
BALL VALVE
RETURN MAIN
SUPPLY MAIN
SHUNT FROM CHILLED OR
HOT WATER SUPPLY
RETURN
3/4"
5 GALLON FILTER
FEEDER TANK OR
OTHER SIZE AS
SPECIFIED ASME
RATED
TO CHILLED OR HOT
WATER RETURN
SHUT OFF/
BALANCING VALVE
WITH MEMORY STOP
SUPPLY
NOTE: USE TFE TAPE ON ALL THREADED
JOINTS.
HIGHEST POINT IN SYSTEM
4 PIPE DIAMETERS (WITH 18"MAX)
REDUCER
1/4" BRASS NIPPLE
1/4" GAGE COCK
1/4" TYPE "L" COPPER TUBE
NOTE: USE TFE TAPE ON ALL THREADED
JOINTS.
HIGHEST POINT IN SYSTEM
4 PIPE DIAMETERS (WITH 18"MAX)
REDUCER
1/4" BRASS NIPPLE
1/4" GAGE COCK
FLOAT-TYPE AIR VENT
1/4" TUBE TO SCHRAEDER ADAPTER
1/4" TYPE "L" COPPER TUBE
SCALE:
END SUCTION PUMP
SCALE:
SCALE:
COUPON RACK
TYPICAL DUCT INSULATION & SUPPORTS NEAR
VOLUME DAMPERS
DUCT PENETRATION OF FULL HEIGHT
PARTITIONS
NOTES:
1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE
THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.
2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.
3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.
1"
MAX. 60" SEE NOTE c
ANGLE IRON
THREADED
HANGER ROD
UNISTRUT OR
HANGER
STRAP
OVER 60"
GALV. HANGER
STEEL FRAME, ANGLE
1.25"X1.25"X0.125" ONLY AT
PENETRATIONS EXPOSED TO
VIEW IN NON-MECHANICAL OR
ELECTRICAL SPACES
SILICONE
ACOUSTICAL
AND AIRFLOW
SEALANT (TYP)
FRAMED
OPENING OR
SHEETMETAL
SLEEVE
SHEETMETAL
SLEEVE
MINERAL
FIBER
PACKING
SILICONE
ACOUSTICAL
AND
AIRFLOW
SEALANT
(TYP)NON-RATED
PARTITION
1/2" MAX
(TYP)
1/2" MAX
(TYP)
NON-RATED
PARTITIONNOTES:
1. AT FIRE RATED PARTITIONS WITHOUT FIRE DAMPER, REPLACE PACKING AND SILICONE SEALANT
WITH UL LISTED FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH UL LISTING.
2. FIRE STOP DUCT PENETRATIONS THRU RATED AND NON-RATED CORRIDOR WALLS ABOVE CEILINGS.
SCALE:
CHEMICAL FEED (FILTER FEEDER)
INLINE PUMP PIPING (EACH PUMP)
SCALE:
10 TYPICAL PIPE INSULATION &
VALVE HANDLE EXTENSION
SCALE:
7 AUTOMATIC AIR VENT ASSEMBLY
MANUAL AIR VENT ASSEMBLY
BUTT & SEAL
JOINTS
CAP INSULATION. LEAVE
NO EXPOSED INSULATION
ANYWHERE
PROVIDE VALVE
EXTENSION KIT
TO ALLOW PROPER
INSULATION COVERAGE
DIFF.
PRESSURE
SWITCH
SCALE:
DIFFERENTIAL PRESSURE SWITCH
SCALE:
DUCT HANGER SUPPORT
D et ai ls
MECHANICAL
DETAILSM4.01
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1/2"MNPTx1/2"T SS CONN. COMPRESSION TYPE
AutoCAD SHX Text 1/2"ODx0.035 316SS SMLS TUBE
AutoCAD SHX Text 1/2"Tx1/2"Tx1/2"T TEE SS COMPRESSION TYPE
AutoCAD SHX Text
1/2" 3 VALVE MANIFOLD SS
AutoCAD SHX Text
1/2" BALL VALVE SS, 2000#
AutoCAD SHX Text
1/2"MNPT PLUG SS
AutoCAD SHX Text
1/2" TUBE UNION SS COMPRESSION TYPE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ITEM
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
BILL OF MATERIALS
AutoCAD SHX Text
QTY
AutoCAD SHX Text
PROVIDED BY
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text
INSTALLER
AutoCAD SHX Text A/R
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A/R
AutoCAD SHX Text
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
1. SLOPE 1" PER FT DOWN TO INSTRUMENT
AutoCAD SHX Text
2. TUBING ROUTING SHALL AVOID HIGH TEMPERATURE SWIRLS. TUBING AND SUPPORTS SHALL INCLUDE PROVISIONS FOR THERMAL EXPANSION.
AutoCAD SHX Text
3. FOR STAND DETAIL SEE DWG. NO. FOR MOUNTING DETAIL SEE DWG. NO.
AutoCAD SHX Text
4. TUBING SHALL BE SUPPORTED EVERY 5'-0" WITH MILL GALVANIZED STRUT & STAINLESS STEEL TUBING CLAMPS.
AutoCAD SHX Text
5. IF UNABLE TO SUPPORT TUBING EVERY 5'-0", INSTRUMENT TUBE TRAY IS TO BE USED WITH THE APPROPRIATE TUBING CLAMPS.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
CONTRACTOR TO SUBMIT SKETCH OF PROPOSED INSTALLATION INCLUDING SIZES
OF MEMBERS, WELDS, & BOLTS TO STRUCTURAL ENGINEER FOR APPROVAL.
WELD ENTIRE LENGTH OF SUPPORT ANGLE WHERE SUPPORT ANGLE IS RUN
PARALLEL TO STRUCTURAL STEEL.
PIPES & LARGER
WELD (TYP)
NOTES:
SMALLER 1/2"
FOR 2" PIPES &
THICK FOR 2-1/2"
3/8" THICK PLATE
WELD (TYP)
(SEE NOTE 2)
TO STRUCTURAL STEEL
WELD SUPPORT ANGLE
2-1/2" & LARGER
INSULATION
PIPES 2" & SMALLER
2"x2"x1/4"> FOR
3"x3"x5/16"> FOR
TYPICAL FOR CHECK VALVES
AND BALANCING VALVES STRAINERS WITH BLOW-OFF.
TYPICAL FOR Y-BRANCH AND
TYPICAL FOR ALL VALVES
CASE
REMOVABLE
ENCLOSED IN
FIBERGLASS
BOARD.
CASE
REMOVABLE
CASE
REMOVABLE
NOTES:
1. INSULATION TO BE USED ON STEAM,
CONDENSATE RETURN, CHILLED WATER AND
CW MAKEUP PIPING. REFER TO INSULATION
SPEC FOR ADDITIONAL INSULATION FINISH ON
EXPOSED FITTINGS.
2. SEAL WATERTIGHT, ALL EXPOSED FIBERGLASS AND
WHERE TWO OR MORE PIECES OF INSULATION MEET.
INSULATION SHALL BE PER SPECIFICATION DENSITY
(EXCEPT AT HANGERS) AND THE SAME THICKNESS AS
THE ADJOINING PIPE INSULATION.
6" FROM LOUVER WITH TRAP
INTO PAPER IS GREATER THAN 5'-0"),
SHOWN OTHERWISE ON PLANS)
DUCT, 12" X 12" MIN (UNLESS
ACCESS DOOR HALF HEIGHT OF
"D"
DN
CAULK ALL AROUND
STORM-PROOF LOUVER
DRAIN AT 5'-0" CENTERS (IF DEPTH
NOTE: WHEN "D" IS OVER 24" PROVIDE 3/4"
& UP 12"
SOLDER BOTTOM JOINT
PITCH TO OUTSIDE
ALL AROUND
SEAL AND CAULK
SEE NOTE
UNUSED LOUVER AREA)
BOARD INSULATION (ALSO INSULATE
EXPOSED PARTS W/ 2" RIGID
LOUVER PLENUM INSULATE ALL
1/2" BIRDSCREEN
(POS)
PIPE ANCHOR DETAIL STRUCTURAL STEEL
SCALE: NTS
AHU COIL PIPING DETAILS
SCALE:
SCALE:
LOUVER CONNECTION
SCALE:
FAN COIL DETAIL
SCALE:
2-PIPE FAN COIL, 2-WAY CONTROL VALVE
4-PIPE FAN COIL, 2-WAY CONTROL VALVES
SCALE:
BLOW THROUGH UNIT CONDENSATE TRAP
SCALE:
7 PIPE HANGER SUPPORT
VALVE & STRAINER INSULATION DETAIL
115 - 240 65 - 115 40 - 65 21 - 40 14 - 21 0 -14
WATER
COIL
TO
ADD'L
COILS
REDUCE AS
NEEDED (TYP)
SEE NOTE 4
NOTE 8
RETURN
SUPPLY
2-1/2
1-1/2 1-1/4
FLOW (GPM)SIZE (IN)
COIL RUNOUT PIPING SIZING
CO
CO
CO
DOV
DOVAIR
FLOW
DRAIN
PAN(S)
PIPING
(COOLING
ONLY)
6" DIRT POCKET FULL
SIZE OF HEADER
SEE NOTE 6
(TYP)
SEE NOTE 7 (TYP)
DRAIN VALVES AT LOW POINTS OF ALL COIL
HEADERS SAME SIZE AS COIL-OUTLET SIZES BUT
NOT LESS THAN 3/8".
TRAP SEAL REFER TO DRAINPAN WATER SEAL
DETAIL (TYP)
NOTE 9
SEE
NOTE 5
NOTES :
1. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH.
2. LOCATE PIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO FACILITATE COIL REMOVAL. PROVIDE
REDUCERS AS REQUIRED.
3. PROVIDE SIMILAR PIPING ARRANGEMENTS ON EACH SIDE FOR TWO-SECTION-WIDE COIL ASSEMBLY.
4. TWO-WAY CONTROL VALVE SHOWN. SEE AUTOMATIC-TEMPERATURE-CONTROL DIAGRAM AND
SPECIFICATIONS FOR ACTUAL JOB REQUIREMENTS. FOR 3-WAY VALVE PROVIDE ADDITIONAL THERMOMETER
AND ISOLATION VALVE W/MEMORY STOP IN BYPASS LEG.
5. FOR SUPPLY AND RETURN PIPES 2" AND SMALLER, USE BALL VALVES WITH UNIONS FOR ISOLATION.
6. FOR SUPPLY AND RETURN PIPES LARGER THAN 2" USE BUTTERFLY VALVES WITH FLANGES FOR ISOLATION.
7. REFER TO SPECIFICATIONS FOR DRAIN PAN REQUIREMENTS.
8. PROVIDE PROPER RANGE PRESSURE GAUGE OF FULL SCALE = 150% OF MAX PRESSURE OF PUMP.
9. REFER TO FREEZE PROTECTION PUMP DETAIL FOR ADDITIONAL REQUIREMENTS.
INDEPENDENT
DRAIN LINES
EXTEND TO
NEAREST
DRAIN (TYP)
ADJUSTABLE HANGER
WITH ROLLER
LOCKING NUT
SUPPORT NUT INSULATION
PIPE
PIPE COVERING
PROTECTION
16 GA SADDLE
GALVANIZED
INSULATION
SHIELD 12"LONG.
NOTES:
1. SEE SPECIFICATION FOR HANGER SIZES.
2. PIPE 8" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS.
3. FOR CHW SERVICE OVER 3" REPLACE SADDLE WITH 12" LONG 14 GA SHIELD WITH RIGID
INSULATION BETWEEN PIPE AND SHIELD.
MIN.9 lb/cft
DENSITY RIGID
INSULATION AT
SHIELD
CLEVIS HANGER
(FOR 1/2" UP TO
HEAVY DUTY
& INCL. 3" PIPE)
(FOR 4" TO 6" PIPE)
(c)
(b)
OUTLET.
(a)
(a)
(c)
(b)
DRAIN MUST BE LOWER THAN PAN
COILS AND MAXIMUM AIR FLOW).
DISCHARGE STATIC PRESSURE IN
THIS DIMENSION IN INCHES MUST BE
GREATER THAN THE MAXIMUM FAN
INCHES WC (WITH DIRTY FILTERS,
CLEANOUT (TYP.)
DRAIN PAN
NOTES: 1. ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP.
2. PITCH DRAIN FOR PROPER RUNOFF.
3. MANUALLY PRIME FILL TRAP BEFORE START-UP TO FORM
INITIAL DRAIN SEAL.
4. SUPPORT LENGTHY DRAIN LINES TO PREVENT SAG AND
CONDENSATE OVERFLOW.
1" WATER SEAL.
PITCH
PITCH
DRAIN PIPE
TO MATCH DRAIN
OUTLET SIZE.
COIL
COIL
SUPPLY RETURN
AND VALVES SHALL BE OVER EXTENDED DRAIN PAN.
WITHIN THE FAN COIL ENCLOSURE. UNINSULATED PIPE
ALL VALVES AND FITTINGS SHOWN ABOVE MUST FIT
NOTE:
PIPE COOLING COIL
TO DRAIN
DRAIN PAN
MAV
MAV
SUPPLYRETURN
NOTE:
PIPE DRAIN PAN TO DRAIN
COIL
RETURN SUPPLY
MAV
FILTER REMOVAL)
CEILING SERVICES WITH
COORDINATION OF OTHER
NECESSARY TO ALLOW
SIDE OR BOTTOM PULL IF
FILTER (MODIFY FRAME FOR
VALVES, ETC.
CONTROL VALVE, STRAINERS,
COMPONENTS INCLUDING
NOTE: INSULATE ALL PIPING
LINING
ACOUSTICAL
SEE SPECS
FLEX CONN
VIBRATION ISOLATION
SUPPORT FROM STRUCTURE
REFER TO WATER COIL
DETAIL FOR PIPING AND
DRAIN REQUIREMENTS
DUCTED
RETURN AIR
FLEX CONNECTION
(TYP)
h = DUCT HEIGHT w = DUCT WIDTH h w
NO. OF VANES
EQUIVALENT DIAMETER = (w+h)/2
WITHIN 2 EQUIV. DIA.:
WHEN 2 ELBOWS ARE
NO. OF VANES
DEPICTED HERE:
EXAMPLE AT LEFT IS
O U
TS
ID
E R
AD
IU
S
IN
IN
C
H
ES
IN
SI
D E
R
AD
IU
S
O F
EL
BO
W
IN
IN
C
H
ES
N O
. 1 O
F
N O
. 2 O
F
N O
. 3 O
F
N O
. 2 O
F
N O
. 1 O
F
N O
. 1 O
F
NUMBER OF SPLITTERS
OF 3 VANES.
NO. 2 VANE OF A TOTAL
"NO. 2 OF 3" =
OF 3 VANES.
NO. 1 VANE OF A TOTAL
"NO. 1 OF 3" =
TERMINOLOGY:
= INSIDE RADIUS
= CENTERLINE RADIUS
R r rR r/w = 0.5 IS A SQUARE THROAT ELBOW!
FOR 1 ELBOW:
r/w >= 1.50
1.5 > r/w >= 0.70
0.7 > r/w >= 0.60
0.6 > r/w >= 0.55
HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".
NOTE:
r/w RATIO:
RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS
R=20" R=2" R=4-1/4" R=9-1/4"
SHORT RADIUS ELBOW SPLITTER VANE
QUANTITY AND SPACING
SCALE: NTS
1. ALL VALVES AND FITTINGS SHOWN ABOVE MUST FIT WITHIN
THE FAN COIL ENCLOSURE.
2. UNINSULATED PIPE AND VALVES SHALL BE OVER EXTENDED
DRAIN PAN.
3. PROVIDE LEAK DETECTION SENSOR AT DRAIN PAN.
MECHANICAL
DETAILSM4.02
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text
MAV
AutoCAD SHX Text
MAV
AutoCAD SHX Text
MAV
AutoCAD SHX Text
MAV
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
GAS DOWN TO
UNDERGROUND
DISTRIBUTION
(EXISTING)
GAS METER
(EXISTING)
2 PSI GAS
REGULATOR
SERVING
BOILERS AND
WATER
HEATER.
(EXISTING)
2" GAS LINE
(EXISTING)
GAS LINE DOWN TO
BASEMENT
(EXISTING)
2" GAS LINE
(NEW)
HISTORY MUSEUM
LOCOMOTIVE SHOP
RUN GAS LINE THROUGH
EXTERIOR WALL. RUN LINE TO
HISTORY MUSEUM THROUGH
EXISTING TRENCH THAT
CONTAINS THE HOT WATER LINE.
2" GAS
LINE
(NEW)
ENTER HISTORY
MUSEUM THROUGH
AREAWAY. PROVIDE
GAS METER
CONNECT TO EXISTING BOILERS.
USE EXISTING PROPANE/NATURAL
GAS CONVERSION KITS TO CONVERT
BOILERS TO NATURAL GAS.
EXISTING TRENCH
OPTION 1
MECHANICAL SITE PLANM5.01
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text 1/16"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 15'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
2 PIPING NEW WORK BASEMENT FLOOR PLAN
1/8" = 1'-0"
SCOPE OF WORK
1. DEMOLISH CHILLED WATER WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED
PIPING AND VALVES. REFER TO FLOOR PLAN.
2. DISCONNECT UNDERGROUND CHW BRANCH PIPING FROM THE MAIN DISTRIBUTION LINE AT THE
VALVES. PRESSURE TEST EXISTING CHW PIPES ENTERING THE BUILDING.
3. INSTALL NEW CHILLED WATER PUMPS, AIR SEPARATOR, EXPANSION TANK, AND ASSOCIATED
PIPING AND VALVES. REFER TO FLOW DIAGRAM. RECONNECT TO EXISTING DISTRIBUTION.
4. INSTALL AIR COOLED CHILLER AT GRADE ON CONCRETE PAD. REFER TO FLOW DIAGRAM AND
DETAILS. CONNECT CHW PIPING TO EXISTING BRANCH PIPES IN THE VAULT NEXT TO THE
BUILDING.
5. INSPECT AND CLEAN EXISTING PIPING AND VALVES. REPLACE ANY DAMAGES OR RUSTED PIPING
OR VALVES. REPLACE ANY DAMAGED OR RIPPED INSULATION. LABEL ALL PIPING.
6. REMOVE, RETAIN, AND RE-INSTALL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) CONTROL
WIRING AND BACNET COMMUNICATION INTERFACE MATERIALS FOR COMMUNICATION.
1 PIPING DEMOLITION BASEMENT FLOOR PLAN
1/8" = 1'-0"
4" HWS/R
4" CHWS/R
TO UNDERGROUND
DISTRIBUTION
P
(EXISTING)
P
(EXISTING)
4" HWS/R
4" CHWS/R
TO UNDERGROUND
DISTRIBUTION
P
(NEW)
P
(NEW)
CH
(NEW)
AS
(NEW)
ET
(NEW)
OPTION 2
PIPING FLOOR PLAN
BASEMENT LEVELM6.01
HISTORY MUSEUM
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 8'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
COUPON RACK
CHEMICAL FEED
CH
P
P
SUPPORT WITH
SPECIFIED VIBRATION
ISOLATION (TYP)
AAV
PT
PT
FLEXIBLE DOUBLE SPHERE COUPLING
FLANGED CONNECTION
T
DOV W/HB
AIR-COOLED WATER CHILLER SCHEDULE
UNIT
NO. SERVICE LOCATION
MINIMUM
CAPACITY
(TONS) GPM
CHILLED WATER
EWT
(°F)
LWT
(°F)
MAX
P.D.
(FT)
REFRIG
TYPE QTY
COMPRESSOR
TYPE MAX
AMBIENT °F
MIN QTY HP
EA
CONDENSER FAN
RPM
ELECTRIC SERVICE
MCA V HZ
MANUFACTURER
REMARKS
CH-1 HISTORY BUILDING ON GRADE 70 160 55 45 5 R-410A 6 SCROLL 95 0 4 2 1160 169 460 3 60 YORK
YLAA 0070SE
Ø (AS STANDARD)%
GLYCOL
MODULES
PROVIDE DISCONNECT SWITCH AND STARTER.1
VFD FANS2
EXTERIOR INTERIOR
PUMP SCHEDULE
UNIT NO. SERVICE LOCATION
P-9 CHW FOR HISTORY
MUSEUM
CHW FOR HISTORY
MUSEUM
BASEMENT
HISTORY MUSEUM
BASEMENT
HISTORY MUSEUMP-10
2 PROVIDE VFD
PROVIDE DISCONNECT SWITCH
IMPELLERHEAD SHUT-OFFFLUID
TEMPTYPE
CASING
TYPE (FT.)GPM HEAD
(FT.) (IN.)
SIZE
MOTOR ELECT. SERVICEWORKING PUMP MANUFACTURER
BHPPRESS.
(PSIG) RPM PHASEHP VOLTS HZ
MODEL NUMBER
(AS STANDARD)
REMARKS
45°F 160 35 - 1563 1.82 480 3 60 BELL & GOSSET
E-1510
END
SUCTIONS
VFD
Y
45°F
350.0 7WATER
BELL & GOSSET
E-1510 21
160 35 480 3 60Y3WATEREND
SUCTIONS
4" CHWR
4" CHWS
SCALE:
AIR-COOLED WATER CHILLER PIPNG
AS
ET
AAV
COMPRESSION TANK
DIAPHRAGM EXPANSION/
FLOOR MOUNTED
12"
FLOOR
RELIEF VALVE (TYP.)
TO 6" AFF
TO 6" AFF
AIR SEPARATOR
AAV (LARGE CAPACITY)
WATER
COLD
PREVENTER
BACKFLOW
WITH HOSE BIBB
DRAIN OFF VALVE
N.C.
ADJUST TO 0.5 TO 1 PSI
MAXIMUM PRESSURE DROP
ACROSS AIR SEPARATOR
MAKE-UP PRV
SEE NOTE 3 (TYP)
REDUCE TO SIZE
OF AIR SEPARATOR
3/4"
12'' THICK CONCRETE PAD
#4'S @ 16'' O.C. EW
SIZE PAD TO 6'' GREATER THAN
CHILLER FOOTPRINT; ALL SIDES.
CHAMFER EDGES
COMPACTED GRANULAR BASE, 6''
AIR SEPARATOR SCHEDULE
GPM P.D.
FT. HD.
EXPANSION TANK SCHEDULE
TANK
ACCEPTANCE
VOLUME (GAL)
ET-3
UNIT
NO.
180 10 60 30
SYSTEM PRESSURE(PSIG)
AT TANK LOCATION
MIN
SYSTEM TEMP (°F)
MIN
SERVICE
MAX MAX
PRESSURE
RATING(PSI)
MAX OPER.
TANK AIR
CHARGE
(PSIG)
MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
BELL & GOSSETT
40 D-208
SERVICEUNIT
NO.
AS-1
MANUFACTURER
MODEL NUMBER
(AS STANDARD)
REMARKS
- ARMSTRONG VA-2160
CONNECTION
SIZE
IN
ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER.1
BUILT-IN STRAINER REQUIRED1
HW HISTORY
MUSUEMCHW HISTORY
MUSUEM
- 1563 1.8250.0 7
T F
TEMPERATURE
SENSOR
FLOW
SENSOR
T F
LOW FLOW BYPASS
END OF
MAIN
BYPASS
P
FROM BUILDING
DISTRIBUTION
TO BUILDING
DISTRIBUTION
F
VFD
VFD
T F
CHILLER PAD1
SCALE: NTS
6" 1'-0"
SUPPORT PIPING WITH
VIBRATION ISOLATION (TYP)
PROVIDE HEAT TRACE ON
ALL EXTERIOR PIPES
OPTION 2
CHILLED WATER
FLOW DIAGRAMM6.02
HISTORY MUSEUM
STEAMTOWN NATIONAL HISTORICAL SITE
335051
ELS
ELS
HACE
02/07/25
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
MAIN DISTRIBUTION PANEL, PANEL MDP:
277/480V, 3Ø, 4W, 600A MCB
CT'S
RELAYS
30 KVA TRANSFORMER:
480V TO 208Y/120 VOLTS
PANEL DP: 277/480V, 3Ø, 300A
ATS
PANEL DPE: 277V480 3Ø, 225A
NEW
CHILLER
480V, 3Ø, 169MCA
NEW AHU
480V, 16.8FLA
D
MDP
v v
P10
ELECTRICAL REVISIONS
P9P2P1 P6
P55
D
FCU-1
D
MDP
MDP
V
V
MDP
3-#3/0 & 1-#6G - 2"EMT.
7 65
P4P3
MDP MDP
AREAWAY
PANEL LP1: 120/208V, 3Ø, 225A
PANEL LPA: 277/480V, 3Ø, 100A
MDP MDP
MAIN DISTRIBUTION PANEL, PANEL MDP:
277/480V, 3Ø, 4W, 600A MCB
CT'S
RELAYS
30 KVA TRANSFORMER:
480V TO 208Y/120 VOLTS
PANEL DP: 277/480V, 3Ø, 300A
ATS
PANEL DPE: 277V480 3Ø, 225A
P10
D
MDP
ELECTRICAL REMOVALS
SCALE A
P9P2P1
D
FCU-1
MDP
AREAWAY
PANEL LP1: 120/208V, 3Ø, 225A
PANEL LPA: 277/480V, 3Ø, 100A
D SAFETY DISCONNECT SWITCH MOUNTED ON
THE WALL OR ASSOCIATED EQUIPMENT.
COMBINATION SAFETY SWITCH AND MOTOR
STARTER MOUNTED ON THE WALL.
DISCONNECT SWITCH AND VARIABLE
FREQUENCY DRIVE. VFD TO BE FURNISHED
BY THE HVAC CONTRACTOR AND MOUNTED
AND WIRED BY THE ELECTRICAL
CONTRACTOR.
EXISTING WIRING TO BE REMOVED.
EXISTING WIRING TO REMAIN.
NEW WIRING AND CONDUIT.
LEGEND
V
1. REMOVE TWO, EXISTING FEEDERS TO EXISTING HW PUMPS BACK
TO PANEL MDP.
2. REMOVE TWO, EXISTING FEEDERS TO EXISTING CW PUMPS BACK
TO PANEL MDP.
3. DISCONNECT, AND RETAIN, FEEDER TO EXISTING FCU-1. FCU-1 TO
BE REPLACED BY ANOTHER CONTRACTOR.
4. REMOVE EXISTING FEEDER TO EXISTING AHU-1 BACK TO PANEL
MDP.
5. FURNISH AND INSTALL TWO NEW DISCONNECT SWITCHES FOR
NEW HW PUMPS P1 & P2. MOUNT DISCONNECT SWITCHES AND
VFDS (SEE NOTE G1) ON THE WALL AND PROVIDE TWO NEW
FEEDERS FROM EXISTING 20A, 3P BREAKERS IN PANEL MDP FOR
NEW 480V, 3Ø, 3HP PUMPS.
6. FURNISH AND INSTALL TWO NEW DISCONNECT SWITCHES FOR
NEW CW PUMPS P9 & P10. MOUNT DISCONNECT SWITCHES AND
VFDS (SEE NOTE G1) ON THE WALL AND PROVIDE TWO NEW
FEEDERS FROM EXISTING 20A, 3P BREAKERS IN PANEL MDP FOR
NEW 480V, 3Ø, 3HP PUMPS.
7. CONNECT EXISTING FEEDER TO NEW 480V, 3Ø, 914W FCU-1.
8. FURNISH AND INSTALL NEW FEEDER TO NEW 480V, 3Ø, 4.92FLA
AHU-1.
9. FURNISH AND INSTALL TWO, NEW NEW FEEDERS TO TWO, NEW
HW FREEZE PROTECTION PUMPS, P5 (1HP) & P6 (1.5HP).
10. REMOVE EXISTING 125A, 3P CIRCUIT BREAKER AND FURNISH AND
INSTALL A NEW 200A, 3P CIRCUIT BREAKER FOR NEW CHILLER
CH-1. PROVIDE NEW TYPEWRITTEN PANEL SCHEDULE
REFLECTING NEW PUMPS IDENTIFICATION AND CHILLER.
11. EXISTING FCU-2 TO BE REPLACE WITH NEW FCU-2 RATED 120V,
1Ø, 142W BY ANOTHER CONTRACTOR .
12. DISCONNECT FEEDER FROM EXISTING FCU-2 AND RE-CONNECT
TO NEW FCU-2 AFTER SET-IN-PLACE BY OTHERS.
SHEET NOTES: #
1. DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO
SHOW GENERAL SYSTEM CONFIGURATION AND
PERFORMANCE. NOT ALL NECESSARY DEVICES AND
COMPONENTS ARE SHOWN. PROVIDE ALL DEVICES AND
COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM.
2. CONTRACT DRAWINGS AND SPECIFICATIONS ARE
COMPLEMENTARY AND MUST BE USED IN CONJUNCTION
TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.
CONTRACTOR SHALL COORDINATE ALL DRAWINGS AND
SPECIFICATIONS PRIOR TO COMMENCING WORK.
QUESTIONS REGARDING DESIGN INTENT OR SYSTEM
OPERATION SHALL BE PROMPTLY BROUGHT TO
ATTENTION OF THE COR.
3. THE TERM "REMOVE" MEANS DISCONNECT AND REMOVE
THE DEVICE, FEEDER, ETC, INCLUDING ALL ACCESSORIES
AND APPURTENANCES.
4. THE TERM “PROVIDE” MEANS FURNISH AND INSTALL,
COMPLETE AND READY FOR USE.
5. THE TERM “CONTRACT DOCUMENTS” MEANS THE
SPECIFICATIONS, DRAWINGS, ADDENDUMS, SKETCHES
AND OTHER DOCUMENTATION THAT DEFINE THE WORK.
6. ANY CONFLICTS BETWEEN SPECIFICATIONS AND
DRAWINGS SHALL BE PROMPTLY BROUGHT TO COR’S
ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH
ANY WORK EXCEPT AT THEIR OWN RISK, UNTIL
CLARIFICATIONS OF CONFLICTS ARE ISSUED TO THE
CONTRACTORS BY THE COR.