2025-01-27_9508_Oak_Grove_MS_Chiller_Repl-MECH-Permit_Set_S&S.pdf
PDF 4 MB Posted
- Attached to
- Chiller Replacement State and local contract opportunity
- Solicitation number
- 25-CR-037
- Issued by
- Pinellas County, Florida
About this file
The documents are mechanical engineering design drawings for the Oak Grove Middle School Chiller Replacement project for Pinellas County Schools in Clearwater, Florida. The project involves replacing existing HVAC equipment, specifically two air-cooled chillers (CH-1 and CH-2), multiple pumps (SCHP-1, PCHP-1, PCHP-2), and an additional mini-split system (AC-1/CU-1). The drawings are dated January 27, 2025, and include detailed mechanical plans, demolition plans, site layouts, piping diagrams, equipment schedules, and control system schematics. The project scope includes removing existing equipment, extending concrete equipment pads, installing new chillers and pumps with associated piping and controls, and ensuring compatibility with the existing mechanical systems.
The technical specifications indicate the new equipment will be from manufacturers like Trane and Mitsubishi, with specific model numbers and performance characteristics detailed in the schedules. The chillers will use R-454B refrigerant, have a nominal capacity of 230 tons, and include features such as low ambient cooling, architectural louvered panels, and BACnet communication interfaces. Electrical requirements include 460V/3-phase power, with specific notes on short circuit current ratings, disconnect switches, and power connections. The project appears to be funded through Pinellas County Schools and is designed to upgrade and improve the HVAC infrastructure at Oak Grove Middle School, with a focus on energy efficiency, system reliability, and maintaining existing operational sequences.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Chiller_Replacement_Addendum_1_Revision.pdf | ||
| Record_Submittal_11.22.24_-_PCSB_-_Oak_Grove_Chillers.pdf | ||
| 2025-02-17_9508_Pre-bid_meeting_sign-in_sheet.pdf | ||
| 2025-01-27_9508_Oak_Grove_MS_FULL_SET_SPECS_Mech_+_Elec-S&S.pdf | ||
| 2025-01-27_9508_Oak_Grove_MS_Chiller_Repl-ELEC-Permit_Set-S&S.pdf | ||
| Bid_Protest_Procedure.pdf | ||
| Insurance_Specifications_for_Contractors.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
G-000
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
PROJECT
COVER SHEET
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
Mechanical Sheet List
Sheet Number Sheet Name
G-000 PROJECT COVER SHEET
M-001 MECHANICAL SYMBOL LEGEND AND NOTES
M-101 SITE MECHANICAL PLAN
MD -102 BUILDING 7 MECHANICAL DEMOLITION PLAN
M-102 BUILDING 7 MECHANICAL PLAN
M-501 MECHANICAL DETAILS
M-601 MECHANICAL CONTROLS
M-701 MECHANICAL SCHEDULES
OAK GROVE MIDDLE SCHOOL -
PINELLAS COUNTY SCHOOLS
1370 S BELCHER RD, CLEARWATER, FL 33764
VICINITY MAP
BOARD MEMBERS:
LAURA HINE - CHAIRPERSON - DISTRICT #1
CAPRICE EDMOND - VICE CHAIRPERSON - DISTRICT #7
KATIE BLAXBERG - DISTRICT #5
LISA N. CANE - DISTRICT #2
EILEEN M. LONG - DISTRICT #4
STEPHANIE MEYER - DISTRICT #6
DAWN M. PETERS - DISTRICT #3
SUPERINTENDANT OF SCHOOLS: KEVIN K. HENDRICK
PERMIT AND BID DOCUMENTS FOR:
OAK GROVE MIDDLE SCHOOL CHILLER REPLACEMENT
PINELLAS COUNTY SCHOOLS PROJECT NUMBER 9508
100% CONSTRUCTION DOCUMENTS
TAG ISSUED DATE
100% Construction Documents
2025.01.27
T S
P
HVAC DUCTWORK LEGEND
CERTAIN ITEMS IN THE LEGEND BELOW MAY NOT APPLY TO THIS PROJECT.
DARK PIPING INDICATES NEW PIPING AND LIGHT INDICATES EXISTING.
RETURN DUCT
EXHAUST AIR DUCT
4-WAY CEILING DIFFUSER
EXISTING TO REMAIN
SUPPLY AIR DUCT OR OUTSIDE AIR DUCT
DUCT TRANSITION
BALANCED DAMPER
FIRE DAMPER
MOTORIZED DAMPER
DUCT SENSOR
DIFFERENTIAL PRESSURE SWITCH
DUCT SMOKE DETECTOR
STATIC PRESSURE SENSOR
MANUAL TIMER ON/OFF SWITCH
TEMPERATURE SENSOR
THERMOSTAT
ROOM TEMPERATURE SENSOR (ADJUSTABLE)
"XXX" = VAV BOX SERVED
ROOM TEMPERATURE & CO2 SENSOR (ADJ)
"XXX" = VAV BOX SERVED
ROOM TEMP. & HUMIDITY SENSOR (ADJ) "XXX"
= VAV BOX SERVED
ROOM TEMP, CO2, & HUMIDITY SENSOR (ADJ)
"XXX" = VAV BOX SERVED
ROOM NON-ADJUSTABLE TEMPERATURE
SENSOR "XXX" = VAV BOX SERVED
EXISTING TO BE REMOVED
NEW
CONNECT TO EXISTING
LIMIT OF DEMOLITION
RECTANGULAR DUCT BREAK
AIRFLOW
DP
C02 SENSOR
T1
XXX
T2
XXX
T3
XXX
T4
XXX
T5
XXX
S
CO2
SW
M
FD
SMOKE DAMPER
SD
FSD FIRE/SMOKE DAMPER
DD
S
APPLICABLE MECHANICAL CODES - COMMERCIAL
1. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY OR MAY
NOT APPLY TO THIS PROJECT.
2. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH
STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS.
WHEN THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE
PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER.
NFPA-13 (2019)
INSTALLATION OF SPRINKLER SYSTEMS
NFPA-54 (2021)
NATIONAL FUEL GAS CODE
NFPA-70 (2020)
NATIONAL ELECTRICAL CODE
NFPA-72 (2019)
NATIONAL FIRE ALARM CODE
NFPA-90A (2021)
INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS
NFPA-90B (2021)
INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS
NFPA-91 (2020)
EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND
NON-COMBUSTIBLE PARTICULATE SOLIDS
NFPA-96 (2021)
VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING
OPERATIONS.
THE FLORIDA SPECIFIC EDITION OF NFPA 101. THE LIFE SAFETY CODE (2021
EDITION) [69A-3.012(1) FAC] [69A-53.004 FAC]
NFPA-110 (2019) EMERGENCY AND STANDBY POWER SYSTEMS
NFPA-780 (2020) LIGHTNING PROTECTION CODE
FLORIDA BUILDING CODE, BUILDING 8TH EDITION (2023)
FLORIDA BUILDING CODE, MECHANICAL 8TH EDITION (2023)
FLORIDA BUILDING CODE, PLUMBING 8TH EDITION (2023)
FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRICANE
ZONES 8TH EDITION (2023)
FLORIDA BUILDING CODE, FUEL GAS 8TH EDITION (2023)
FLORIDA FIRE PREVENTION CODE 8TH EDITION (2023)
FLORIDA ACCESSIBILITY CODE (2023)
FLORIDA ENERGY CONSERVATION CODE 8TH EDITION (2023)
STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60.
WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE
"BUILDING" AND "MECHANICAL" OR "PLUMBING" CODES, IT WILL BE
ASSUMED THAT THE BUILDING CODE TAKES PRECEDENCE.
ASHRAE/ANSI-62.1 (2019)
VENTILATION AND ACCEPTABLE INDOOR AIR QUALITY
SMACNA/ANSI (2020)
HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE - 4TH EDITION
UL-1995 (2015)
HEATING AND COOLING EQUIPMENT - WITH REVISIONS THROUGH AUGUST 2022
ARI 550/590
ARI 370
ASHRAE 15
SAFETY CODE FOR MECHANICAL REFRIGERATION
ASHRAE 90.1
ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS
ASME SEC 8
BOILER AND PRESSURE VESSEL CODE
NEMA MG 1
MOTORS AND GENERATORS
UL 465
CENTRAL COOLING AIR CONDITIONERS
MECHANICAL SYSTEMS SUMMARY TABLE
OAK GROVE MIDDLE SCHOOL CHILLER REPLACEMENT
PINELLAS COUNTY SCHOOLS
1370 S. BELCHER ROAD CLEARWATER, FL 33764-3771
APPROX: 3630 SF
CHILLER REPLACEMENT
PROJECT NAME:
PROJECT OWNER:
PROJECT ADDRESS:
PROJECT SIZE:
DESIGN CRITERIA
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-001
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
MECHANICAL
SYMBOL
LEGEND AND
NOTES
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
1. REFRIGERANT LINES SHOWN ARE DIAGRAMMATIC AND FOR SUGGESTED ROUTING
ONLY. THE MECHANICAL CONTRACTOR SHALL PROVIDE REFRIGERANT LINE SIZES,
FINAL LAYOUT, AND REQUIRED ACCESSORIES (SUCH AS SIGHT GLASS, EXPANSION
VALVES, FILTER-DRIER, LIQUID LINE TRAPS, SUCTION ACCUMULATOR, ETC.) IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
2. FOR NATURAL GAS PIPING, SEE PLUMBING DRAWINGS.
3. FOR EXACT LOCATION OF DIFFUSERS AND GRILLES, SEE ARCHITECTURAL
REFLECTED CEILING PLANS.
4. FOR ROOF PENETRATION DETAILS SEE ARCHITECTURAL AND STRUCTURAL DWGS.
5. FLEX DUCTWORK TO DIFFUSERS SHALL MATCH NECK SIZE OF DIFFUSER WHERE
INDICATED.
6. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE
DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY STATE AND LOCAL CODES.
7. INSTALL ALL NEW WORK IN ACCORDANCE WITH MANUFACTURERS'
RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND
REGULATIONS.
8. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE BEST
APPROXIMATES ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST
CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE
CONDITIONS AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING
INSTALLED. DO NOT SCALE DRAWINGS.
9. COORDINATE CONSTRUCTION OF ALL HVAC WORK WITH ARCHITECTURAL,
STRUCTURAL, PLUMBING, CIVIL, ELECTRICAL, TECHNOLOGY, ETC., SHOWN ON OTHER
CONTRACT DOCUMENT DRAWINGS.
10. ALL HVAC WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO
OWNER.
11. MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES AND SUSPENDED
EQUIPMENT THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.
12. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED,
THE PRODUCT OF ONE MANUFACTURER SHALL BE USED.
13. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION SHALL BE
FURNISHED AND INSTALLED BY THE HVAC CONTRACTOR.
14. COORDINATE ACCESS PANEL LOCATIONS FOR INSTALLATION IN WALLS AND
CEILINGS, WHERE REQUIRED, TO SERVICE VALVES, FIRE DAMPERS, VAV BOXES, AND
OTHER CONCEALED HVAC EQUIPMENT.
15. ALL EQUIPMENT, PIPING, ETC. SHALL BE SUPPORTED AS REQUIRED TO PROVIDE A
VIBRATION FREE INSTALLATION.
16. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS
AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE
CONNECTIONS SHALL BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR
AS INDICATED ON THE DRAWINGS.
17. ALL PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL BE
COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR
JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. SEE STRUCTURAL
NOTES AND SPECIFICATIONS FOR REQUIRED PRODUCTS AND INSTALLATION OF
HANGARS AND SUPPORTS. HVAC EQUIPMENT AND PIPING SHALL NOT BE SUPPORTED
FROM METAL DECK.
18. CONTRACTOR TO INFORM THE STRUCTURAL ENGINEER IN WRITING OF ANY
SUSPENDED LOAD IN EXCESS OF 400 POUNDS.
19. PROVIDE SHUTOFF VALVES IN ALL HEATING WATER PIPING SYSTEM BRANCHES
BETWEEN FLOOR LEVELS AND AT BRANCHES SERVING THREE OR MORE PIECES OF
EQUIPMENT IN ADDITION TO ANY AREAS SHOWN ON PLANS.
20. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND
OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
21. WATER AND DRAIN PIPING SHALL NOT BE RUN THROUGH OR ABOVE ELECTRICAL
SWITCH GEAR OR ROOMS, TECHNOLOGY ROOMS, OR TELEPHONE ROOMS.
22. IF THERE IS ANY DEVIATION BETWEEN THE SPECIFICATIONS AND DRAWINGS THE
CONTRACTOR SHALL ADHERE TO THE MORE STRINGENT CONDITION.
23. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED
AND LOCATED BY THE CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL BE
4 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4 INCHES ON
EACH SIDE. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE
CONTRACTOR. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
COORDINATE SIZE AND LOCATION OF CONCRETE HOUSEKEEPING PADS.
24. EXHAUST ONLY ROOMS SUCH AS JANITORS CLOSETS, ELECTRICAL CLOSETS, AND
STORAGE ROOMS SHALL HAVE DOOR UNDERCUTS OF 5/8" FOR MAKEUP AIR
INDICATED WITH FLOW ARROW ON PLANS. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
GENERAL MECHANICAL NOTES:
HVAC ABBREVIATIONS
CERTAIN ABBREVIATIONS LISTED BELOW MAY NOT APPLY TO THIS PROJECT.
Key Name Abbreviation Description
AC ALTERNATING CURRENT
ACB ACTIVE CHILLED BEAM
ACC AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROLLED DAMPERD DAMPER
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHRI AIR-CONDITIONING, HEATING, AND REFRIGERATION
INSTITUE
AHU AIR HANDLING UNIT
AMCA AIR MOVEMENT AND CONTROL ASSOCIATION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ASJ ALL SERVICE JACKET
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
BAS BUILDING AUTOMATION SYSTEM
BD BACK-DRAFT DAMPER
BFF BELOW FINISHED FLOOR
BFG BELOW FINSHED GRADE
BHP BRAKE HORSE POWER
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
C CELSIUS
CD CEILING DIFFUSER
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CH CHILLER (WATER-COOLED)
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CM CENTIMETERS
CO CARBON MONOXIDE
COND CONDENSATE
CONN CONNECTION
CT COOLING TOWER
CUH CABINET UNIT HEATER
CWP CONDESNER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
D&R DISCONNECT & REMOVE
DB DRY BULD
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG, ° DEGREE
DIA, Ø DIAMETER
DIM DIMENSION
DN DOWN
DP DIFFERENTIAL PRESSURE
DWG(S) DRWAING(S)
DWH DOMESTIC WATER HEATER
E EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRCIAL CONTRARACTOR
EF EXHAUST FAN
EPDM ETHYLENE PROPYLENE DIENE MONOMER
ER EXHAUST REGISTER
ERU ENERGY RECOVER UNIT HEATER
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
F FAREINHEIT
F&T FLOAT & THERMOSTATIC
FCU FAN COIL UNIT
FD FIRE DAMPER
FDA U.S. FOOD AND DRUG ADMINISTRATION
FF FINSHED FLOOR
FG FINISHED GRADE
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FPB FAN POWERED BOX
FPM FEET PER MINUTE
FT, ' FLASH TANK
FTR FIN TUBE RADIATION
FVAV FAN POWERED VAV
G GAS
GA GAUGE
GAL GALLON
GALV GALVANIZED
GPH FALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIB (CONNECTION)
HP HORSE POWER
HPS HIGH PRESSURE STEAM
HUM HUMIDIFER
HVAC HEATING VENTILATION AND AIR CONDITIONING
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
HVAC ABBREVIATIONS
CERTAIN ABBREVIATIONS LISTED BELOW MAY NOT APPLY TO THIS PROJECT.
Key Name Abbreviation Description
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN, " INCHES
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LD LINEAR DIFFUSER
LPS LOW PRESSURE STEAM
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MAKE-UP AIR UNIT
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
MC MECHANICAL CONTRACTOR
MERV MINIMUM EFFICIENCY REPORTING VALUE
MIN MINIMUM
MM MILLIMETERS
MPH MILES PER HOUR
N NEW WORK
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPENED
NPS NOMINAL PIPE SIZE
NPT NATIONAL PIPE THREAD
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
ODP OPEN DRIP PROOF
OS&Y OUTSIDE SCREW AND YOKE
OSHA OCCUPATIONAL SAFTEY AND HEALTH ADMINISTRATION
PCB PASSIVE CHILLED BEAM
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PDF PORTABLE DOCUMENT FORMAT
PRV PRESSURE REDUCTIN VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINLY CHLORIDE
R RELOCATED
R&R REMOVE AND RELOCATE
RA RETURN AIR
REQ'D REQUIRED
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RM ROOM
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTD RESISTANCE TEMPERATURE DETECTOR
RTU ROOF TOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SEN SENSIBLE
SF SUPPLY FAN
SFD COMBINATION SMOKE AND FIRE DAMPER
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS
NATIONAL ASSOCIATION
SP STATIC PRESSURE
SQ SQAURE
SQ FT SQUARE FEET
SR SUPPLY REGISTER
STD STANDARD
STM STEAM
T THERMOSTAT
TCP/IP TRANSMISSION CONTROL PROTOCOL/INTERNET
PROTOCOL
TD TRANSFER AIR DUCT
TEAO TOTALLY ENCLOSED AIR OVER
TEFC TOTALLY ENCLOSED FAN COOLED
TEMP TEMPERATURE
TG TRANSFER GRILLE
TOD TOP OF DUCT
TON 12,000 BTU (COOLING CAPACITY)
TYP TYPICAL
UC UNDER CONUNTER
UH UNIT HEATER
UL UNDERWRITERS LABRATORIES
V VOLTS
VA VOLT AMPS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
VVT VARIABLE VOLUME AND TEMPERATURE
WB WET BULB
WC WATER COLUMN
WFS WATER FLOW SWITCH
WG WATER GAUGE
WPD WATER PRESSURE DROP
Mechanical Sheet List
Sheet Number Sheet Name
G-000 PROJECT COVER SHEET
M-001 MECHANICAL SYMBOL LEGEND AND NOTES
M-101 SITE MECHANICAL PLAN
MD -102 BUILDING 7 MECHANICAL DEMOLITION PLAN
M-102 BUILDING 7 MECHANICAL PLAN
M-501 MECHANICAL DETAILS
M-601 MECHANICAL CONTROLS
M-701 MECHANICAL SCHEDULES
TAG ISSUED DATE
100% Construction
M-102
SCHOOL
MECHANICAL
BUILDING/CHILLER YARD -
SCOPE OF WORK
PARKING LOT
PARKING LOT
BUS LOOP
TRACK
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-101
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
SITE
MECHANICAL
PLAN
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
1. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL EXTENT
OF THE WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION AND PROPER INSTALLATION OF ALL MECHANICAL SYSTEMS.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY OFFSETS AND FITTINGS
WHICH MAY BE REQUIRED DUE TO SPACE CONSTRAINTS OR OTHER
CONDITIONS.
2. THE CONTRACTOR SHALL PROVIDE MISCELLANEOUS SUPPORTING STEEL,
ETC. FOR THE PROPER INSTALLATION OF ALL MECHANICAL SYSTEMS.
3. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL, AND ROOF
PENETRATIONS, ETC. WITH THE GENERAL CONTRACTOR.
4. THE CONTRACTOR SHALL VERIFY ALL CLEARANCES PRIOR TO THE
FABRICATION OF ANY WORK.
5. PIPING OR ANY OTHER MECHANICAL SYSTEM COMPONENT SHALL NOT BE
LOCATED OVER THE TOP OF ANY ELECTRICAL PANELS OR EQUIPMENT.
GENERAL SHEET NOTES
N
SCALE: 1" = 40'-0"
SITE HVAC PLAN
TAG ISSUED DATE
100% Construction
(E)6" CHWR
(E)6" CHWS
(E)6" CHWR
(E)6" CHWS
PCHP
PCHP
SCHP
STARTER:
PCHP-1
CH
CH
(E)6" CHWS
(E)6" CHWR
(E)6" CHWR
(E)10" CHWS
(E)8" CHWS
GENERATOR
(E)
BOILER
07-102
MECHANICAL
07-101
GRAVEL
COURTYARD
(E)SCHP
(E)
VFD
SCHP-3
(E)
VFD
SCHP-2(E)
VFD
SCHP-1
(E)
AS-1
(E)
ET-1
(E)
CH-3
(E)6" CHWS
(E)10" CHWS
(E)6" CHWR
(E)SCHP
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
MD -102
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
BUILDING 7
MECHANICAL
DEMOLITION
PLAN
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
1. IN EVERY INSTANCE OF DEMOLITION AND/OR REMODELING, THE MECHANICAL
CONTRACTOR SHALL PROVIDE A COMPLETE SCOPE OF WORK AS NONE
OTHER SHALL BE ACCEPTED.
2. THE DRAWINGS ARE TO BE USED ONLY AS A GUIDELINE FOR
DEMOLITION. THE MECHANICAL CONTRACTOR MUST VISIT THE SITE PRIOR TO
BIDDING TO VERIFY ALL WORK REQUIRED FOR A COMPLETE SCOPE OF WORK
AND INCLUDE THE COST OF SUCH WORK IN THEIR BID.
3. THE MECHANICAL CONTRACTOR SHALL MAINTAIN EXISTING SERVICES TO AND
IN THE EXISTING AREA AS REQUIRED.
4. IF NECESSARY, THE MECHANICAL CONTRACTOR SHALL PROVIDE TEMPORARY
SERVICES IN THE EXISTING AREAS.
5. IN ADDITION TO ALL OTHER DEMOLITION REQUIREMENTS, ANY MECHANICAL
EQUIPMENT AND/OR DEVICES SHOWN AS BEING REMOVED SHALL BE
REMOVED COMPLETE INCLUDING SUPPORTING STEEL AND TEMPERATURE
CONTROLS. ALL EXISTING RECESSED CONTROLS REMOVED SHALL BE
REPLACED WITH STAINLESS STEEL COVER PLATE.
6. ALL WALLS, CEILINGS, FLOORS, ETC., BEING DISTURBED BY THE WORK SHALL
BE RETURNED TO FINISHED CONDITIONS TO MATCH EXISTING BY THE
MECHANICAL CONTRACTOR AND THEY SHALL DO THEIR OWN CUTTING AND
PATCHING AS NECESSARY UNDER THEIR CONTRACT.
7. EXISTING EQUIPMENT AND MATERIALS SHALL BE TURNED OVER TO THE
OWNER FOR FIRST RIGHT OF REFUSAL. IF NOT REQUIRED BY THE OWNER,
THE CONTRACTOR SHALL REMOVE SAID EQUIPMENT AND MATERIALS FROM
THE PREMISES AND DISPOSE OF IN A LEGAL MANNER.
8. MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR AND OWNER'S REPRESENTATIVE REGARDING TESTING AND
ABATEMENT OF ANY HAZARDOUS MATERIAL PRIOR TO STARTING ANY
DEMOLITION WORK.
GENERAL DEMOLITION NOTES
SHEET KEY NOTES:#
1. REMOVE EXISTING CHILLER AND DEMOLISH ASSOCIATED PIPING AND
APPURTENANCES BACK TO DISCONNECT POINT. DO NOT DEMOLISH CHILLER,
TURN OVER TO OWNER FOR REPURPOSING. EXISTING CONCRETE PAD SHALL
REMAIN. CONTRACTOR SHALL CAP ALL PIPING UNTIL NEW CONNECTIONS ARE
MADE TO THE NEW CHILLER. REFER TO SHEET M-102 FOR NEW WORK.
2. PCHP-2, SCHP-1 - DEMOLISH AND REMOVE EXISTING PUMP AND MOTOR.
DISCONNECT ASSOCIATED PIPING AS REQUIRED TO MAKE NEW
CONNECTIONS IN SIMILAR LOCATION. CONTRACTOR TO CAP ALL PIPING
SERVICES UNTIL NEW CONNECTIONS ARE MADE TO THE NEW PUMPS. REFER
TO SHEET M-102 FOR NEW WORK.
3. PCHP-1 - DEMOLISH AND REMOVE EXISTING PUMP. REMOVE MOTOR AND
TURN OVER TO OWNER FOR BACKUP. DISCONNECT ASSOCIATED PIPING AS
REQUIRED TO MAKE NEW CONNECTIONS IN SIMILAR LOCATION. CONTRACTOR
TO CAP ALL PIPING SERVICES UNTIL NEW CONNECTIONS ARE MADE TO THE
NEW PUMPS. REFER TO SHEET M-102 FOR NEW WORK.
4. FOR MECHANICAL CONTRACTOR REFERENCE ONLY - COORDINATE WITH
ELECTRICAL CONTRACTOR AS REQUIRED: EXISTING STARTER PCHP-1
CONTROL PANEL TO BE RELOCATED. REFER TO SHEET M-102 FOR NEW
LOCATION.
5. FIELD VERIFY EXISTING CONCRETE MOUNTING PAD INTEGRITY FOR REUSE IN
NEW WORK PLAN TO ACCOMMODATE NEW MOTOR AND PUMP ASSEMBLY -
EXTEND/MODIFY PAD AS REQUIRED.
N SCALE: 1/4" = 1'-0"
BUILDING 7 HVAC DEMO PLAN
TAG ISSUED DATE
100% Construction
6" CHWS
6" CHWR
6" CHWR
6" CHWS
SCHP
PCHP
PCHP
AC
CU
STARTER: PCHP-1
(E)8" CHWS
6" CHWR
10" CHWS
6" CHWR
6" CHWR
6" CHWR
10" CHWS
CH
CH
GENERATOR
(E)
M-101
BELOW GRADE
PIPING, TYPICAL
6" CHWR6" CHWS
BOILER
07-102
MECHANICAL
07-101
GRAVEL
COURTYARD
AC-1
(E)
VFD
SCHP-1
(E)
VFD
SCHP-2
(E)
VFD
SCHP-3
(E)
AS-1
(E)
ET-1
(E)
CH-3
6" CHWR
6" CHWS
T
3 4
5/8" RS
5/8" CD
3/8" RL
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-102
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
BUILDING 7
MECHANICAL
PLAN
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
1. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL EXTENT
OF THE WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION AND PROPER INSTALLATION OF ALL MECHANICAL SYSTEMS.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY OFFSETS AND FITTINGS
WHICH MAY BE REQUIRED DUE TO SPACE CONSTRAINTS OR OTHER
CONDITIONS.
2. THE CONTRACTOR SHALL PROVIDE MISCELLANEOUS SUPPORTING STEEL,
ETC. FOR THE PROPER INSTALLATION OF ALL MECHANICAL SYSTEMS.
3. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL, AND ROOF
PENETRATIONS, ETC. WITH THE GENERAL CONTRACTOR.
4. THE CONTRACTOR SHALL VERIFY ALL CLEARANCES PRIOR TO THE
FABRICATION OF ANY WORK.
5. PIPING OR ANY OTHER MECHANICAL SYSTEM COMPONENT SHALL NOT BE
LOCATED OVER THE TOP OF ANY ELECTRICAL PANELS OR EQUIPMENT.
GENERAL SHEET NOTES
SHEET KEY NOTES:#
1. PROVIDE NEW AIR COOLED CHILLER ON EXISTING CONCRETE PAD. EXTEND
EXISTING CONCRETE PAD AS REQUIRED TO INSTALL NEW LONGER
UNIT.INSTALL UNIT PER MANUFACTURER RECOMMENDATIONS. PROVIDE
NEOPRENE PAD FOR VIBRATION ISOLATION.
A. EXISTING CHILLER PAD IS 25'-6" LONG. NEW CHILLER IS 27'-8" LONG. 3'-2"
EXTENSION OF PAD IS REQUIRED FOR PAD TO EXTEND 6" ON ALL SIDES
OF UNIT (EXISTING WIDTH OF PAD IS ADEQUATE FOR NEW CHILLER
DIMENSION) - CONTRACTOR SHALL FIELD VERIFY DIMENSIONS OF
EXISTING PAD AND COORDINATE CHILLER PAD EXTENSION WITH
MANUFACTURER AS REQUIRED TO INSTALL UNIT.
2. EXTEND 6" INSULATED CHILLED WATER SUPPLY/RETURN PIPING TO
INLET/OUTLET CONNECTION POINTS AT UNIT FROM THE LIMIT OF
DEMOLITION. COORDINATE ROUTING AS REQUIRED TO AVOID ENCROACHING
INTO ANY ACCESS AREAS FOR CHIILER. REFER TO EQUIPMENT SCHEDULE
FOR MANUFACTURER PROVIDED ACCESSORIES, REPLACE ALL PREVIOUSLY
DEMOLISHED PIPING APPURTENANCES IN KIND.
3. FIELD VERIFY EXISTING CONCRETE MOUNTING PAD INTEGRITY TO
ACCOMMODATE NEW MOTOR AND PUMP ASSEMBLY - EXTEND/MODIFY PAD
AS REQUIRED.
4. PROVIDE NEW PUMP AND MOTOR ASSEMBLY IN SAME LOCATION AS
PREVIOUSLY DEMOLISHED. MODIFY/EXTEND EXISTING PIPING AND
ASSOCIATED ACCESSORIES AS REQUIRED TO CONNECT TO NEW PUMP
INLET/OUTLETS. INSTALL AND MAINTAIN REQUIRED CLEARANCES PER NEC
AND MANUFACTURER RECOMMENDATIONS. REFER TO SCHEDULES AND
DETAILS FOR MORE INFORMATION.
5. PROVIDE MANUFACTURER REQUIRED CLEARANCES WHEREVER INDICATED.
6. EXISTING VFD TO BE REUSED FOR REPLACEMENT PUMP/MOTOR
ASSEMBLIES. INFORM EOR OF ANY DISCREPANCIES.
7. FOR MECHANICAL CONTRACTOR REFERENCE ONLY - COORDINATE WITH
ELECTRICAL CONTRACTOR AS REQUIRED: EXISTING RELOCATED STARTER
PCHP-1 CONTROL PANEL.
8. PROVIDE AIR COOLED CONDENSING UNIT MOUNTED ON WALL BRACKETS.
INSTALL AND MAINTAIN REQUIRED CLEARANCES PER NEC, RATED WIND
LOADS, AND MANUFACTURERS RECOMMENDATIONS. REFER TO SCHEDULES
AND DETAILS FOR MORE INFORMATION.
9. PROVIDE REFRIGERANT LINESET PIPING IN THE MOST DIRECT ROUTE
BETWEEN INDOOR AND OUTDOOR UNIT AND TIGHT TO DECK. REFER TO
MANUFACTURER INSTRUCTIONS FOR INSTALLATION AND ROUTING
REQUIREMENTS.
10. ROUTE 1"⌀ CONDENSATE PIPING TO EXTERIOR AND DISCHARGE TO
SPLASHBLOCK ON GRADE. COORDINATE EXACT LOCATION IN FIELD.
11. UNIT MOUNTED CONTROL PANEL. PROVIDE MANUFACTURER AND NEC
REQUIRED CLEARANCES. COORDINATE WITH MANUFACTURER FOR
ADEQUATE NEMA RATING FOR OUTDOOR INSTALLATION.
N SCALE: 1/4" = 1'-0"
BUILDING 7 HVAC PLAN
TAG ISSUED DATE
100% Construction
FINISHED FLOOR
FLEXIBLE COUPLING WITH GAURD
MOTOR
BASE PLATE
FINISHED FLOOREXISTING CONCRETE PAD
SUPPORT
NEW FLEXIBLE
CONNECTION
NEW SUCTION DIFFUSER
NO STRAINER SHALL BE PROVIDED
NEW PRESSURE GAUGE WITH PETCOCK (TYP.)
NEW SILENT CHECK VALVE
NEW BALANCING VALVE
NEW BUTTERFLY
VALVE
FROM SYSTEM (EXISTING)
TO SYSTEM (EXISTING)
PUMP MOTOR
NEW WYE
STRAINER
TRAPEZE HANGER DETAIL
PIPE HANGER DETAIL
HIGH COMPRESSION
STRENGTH INSULATION
AT EA. HANGER
EXTENDING 2" BEYOND
SHT. MTL. SHIELD
HANGER ROD
INSULATION
SHT. MTL. SHIELD
PIPE
INSULATION
(TYP.)
UNISTRUT
CHANNEL
SHT. MTL. SHIELD
CHANNEL
CLAMP
INSULATION
PIPE
HIGH COMPRESSION
STRENGTH INSULATION
AT EA. HANGER
EXTENDING 2" BEYOND
SHT. MTL. SHIELD, TYP.
HANGER ROD
(TYP.)
CAST-IN-PLACE - FIRE RATED SILICONE SEALER
CORED HOLES - SILICONE SEALER
EXTERIOR WALLS - ABOVE GRADE: SILICONE SEALER
EXTERIOR WALLS - BELOW GRADE: MODULAR LINK SEAL
SEAL ANNULAR
SPACE WITH FIRE
RATED SILICONE FOAM
SEAL SPACE BETWEEN
SLEEVE AND WALL
1" ANNULAR SPACE BETWEEN
PIPE AND SLEEVE
SLEEVE- GALVANIZED PIPE FOR
MASONRY WALL, 20 GA
GALVANIZED SHEET METAL FOR
OTHERS
TERMINATE INSULATION
ADJACENT TO SLEEVE
INTERIOR WALL.
WALL MOUNTED AIR
HANDLING UNIT. MOUNT
UNIT PER MANUFACTURER'S
RECOMMENDATIONS.
CONDENSATE DRAIN. PROVIDE 208V
CONDENSATE PUMP. COORDINATE
ROUTING WITH PLUMBING
CONTRACTOR.
FOR REFRIGERANT LINE SETS,
SUCTION LINE TO BE INSULATED.
EXISTING
EQUIP PAD 1'-1"
EQUIP PAD
EXTENSION
ROUGHEN SLAB SURFACE
#4 BENT BAR @ 12" O.C. USE
EPOXY ADHESIVE SYSTEM TO
ANCHOR BAR INTO SLAB
3/4" CHAMFER
ALL ROUND
ALLOW FOR 1" NON-SHRINK
GROUT IF REQUIRED
SEE PLAN
T/SLAB EL
NOTES:
1. ALL CONCRETE SHALL HAVE A MIN. COMPRESSIONSTRENGTH OF 4000 PSI AT 28 DAYS.
2. ALL CONCRETE & REINFORCING STEEL SHALL BE FURNISHED, FABRICATED AND INSTALLED IN ACCORDANCE WITH THE ACI STANDARD BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-83)
3. COORDINATE SIZE, QUANTITY AND LOCATION OF EQUIPMENT BOLTS AND PAD WITH EQUIPMENT SUPPLIER'S CERTIFIED DRAWINGS. USE EPOXY ADHESIVE SYSTEM TO ANCHOR THREADED RODS INTO SLABS.
#5 DOWEL X 1'-4" LONG
12" O.C. KEEP DOWELS
LEVEL AND PARALLEL TO
ONE ANOTHER
T/2 T
T/ OF EQUIP PAD
TO MATCH EX
RECTORSEAL HURRICANE RATED
CONDENSER WALL BRACKET,
MIAMI-DADE NOA# 21-1012.03.
ANCHORAGE TO WALL SHALL BE A
DELEGATED DESIGN AND SHALL BE
A PERMIT REVISION SUBMITTED BY
THE CONTRACTOR. CONDENSING
UNIT SHALL BE MOUNTED 3'-0"
ABOVE GRADE/FLOOR.
CONTRACTOR TO COORDINATE
AND CONFIRM WITH OWNER PRIOR
TO ROUGH-IN.
26 3/16"
1/ 4"
1 1/8" 2' - 0" 1 1/8"
INSTALL (4) TAPCO
EACH SIDE OF RAIL
W A
L L
NOTES:
1. 1/4' SS (302/304/316) ASTM CLASS A BOLT, LOCK
WASHERS & NUT AT EA. CONNECTION (AND A/C UNiï TO
BRACKET)
2. ATTACH TO CONCRETE W/ (8) 1/4"x2" TAPCONS.
3. CONSTRUCT BRACKET FROM 2"X2"X1/4" ALUMINUM
ANGLE. 1/4' FILLET WELD JOINTS
FS
6" HIGH CONCRETE HOUSEKEEPING PAD
SUPPORT CHILLER WITH I-
BEAMS PERPENDICULAR TO
CHILLER PER
MANUFACTURER'S
RECOMMENDATIONS. PROVIDE
NEOPRENE PADS ON TOP OF
CONCRETE SLAB AND
BETWEEN I-BEAM AND
CHILLER.
NOTE:
PROVIDE OIL COOLER PIPING AS DIRECTED BY CHILLER MANUFACTUER
PRESSURE GAGE WITH
NEEDLE VALVE
NEEDLE VALVE
MANUAL AIR VENT
P-T TEST PORT
FLOW SWITCH
ANGLE GATE VALVE W/ HOSE BIB
THERMOMETER
CHILLED WATER SUPPLY
& RETURN
BUTTERFLY VALVE
BALANCING/SHUTOFF VALVEWYE STRAINER ON INLET
0.5(X) (X) 1(X) (X) 0.5(X)
PIPING ON RUBBER PIPE SADDLE
WITH SADDLE CLAMP BOLTED TO
STEEL PLATE
1/4"
ANGLE BRACKET
1/4"x 2"x
STEEL PLATE
X = PIPE⌀
(TYP)
(TYP)
SCHEDULE 40 STEEL PIPE. PIPE
DIAMETER EQUAL TO 0.5x LARGEST PIPE
DIAMETER ON PLATE
3/8" EXPANSION ANCHOR IN CONCRETE
BASE MIN. 2" EMBEDMENT
SCHEDULE 40 STEEL PIPE FLANGE
ANCHORED TO CONCRETE BASE, REFER
TO ARCHITECTURAL/STRUCTURAL
DETAILS FOR BASE PAD.
M
IN
IM
U
M
'-8
A F
G
PIPE (SIZE VARIES)
RUBBER SADDLE PAD BETWEEN PIPE
AND SADDLE
VERTICAL SUPPORT PIPE HEIGHT VARIES
MINIMUM 1/2 DIAMETER OF CARRIED PIPE
1/2" SLEEVE ANCHOR EQUAL TO
REDHEAD GYNABOLT. MINIMUM
INSTALLATION DEPTH OF 2"
1/8" RED RUBBER PAD BETWEEN FLAT
AND SLAB. MINIMUM 1/8" OVERHANG ALL
SIDES
CONCRETE SLAB OR PAD
SADDLE PLATE
FILLET WELD FLUSH AND
PLUMB
3/8" NUT AND MASHER
(EPOXY COATED)
8"x 8"x 1/2" STEEL PLATE
(EPOXY COATED)
NOTES:
1. PIPE SUPPORTS, PLATES, AND HARDWARE SHALL BE EPOXY COATED TO PREVENT RUST. SUPPORTING PIPE SIZE SHALL
NOT BE LESS THAN HALF OF THE DIAMETER OF THE CARRIER.
2. VERTICAL PIPE SUPPORT SHALL BE FOR LOAD-BEARING PIPING IN THE CHILLER ROOM AND TOWER YARD.
3. MOUNTING PLATE SHALL MATCH PIPE IN MATERIAL AND STRENGTH.
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-501
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
MECHANICAL
DETAILS
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
SCALE: NONE
END SUCTION PUMP + MOTOR ASSEMBLY REPLACEMENT DETAIL
SCALE: NONE
PIPE HANGER DETAIL
SCALE: NONE
PIPE WALL SLEEVE
SCALE: NONE
DX DUCTLESS AC SYSTEM
SCALE: NONE
EQUIPMENT PAD EXTENSION
SCALE: NONE
CONDENSING UNIT WALL MOUNTING
SCALE: NONE
TYPICAL AIR COOLED CHILLER PIPING DIAGRAM
SCALE: NONE
TYPICAL PIPE STAND DETAIL (MULTIPLE PIPES)
SCALE: NONE
TYPICAL PIPE STAND
TAG ISSUED DATE
100% Construction using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-601
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
MECHANICAL
CONTROLS
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
DO
SS
AI
PF
AI
PF
T T
45°F 55°FTC DO
SS
AO
WR
AI
PF
CT
AI
PF
FS
DO
SS
AI
PF
AI
PF
T T
45°F 55°FTC DO
SS
AO
WR
AI
PF
CT
AI
PF
FS
CH-1 NEW CHILLER
PCHP-2 NEW MOTOR NEW PUMP
PCHP-1 NEW MOTOR NEW PUMP AI
PF
T
AI
PF
T
DO
SS
AO
WR
AI
PF
CT
AI
PF
DO
SS
AO
WR
AI
PF
CT
AI
PF
DO
SS
AO
WR
AI
PF
(E)
VFD
CT
AI
PF
AI
PF
T
QUICK
FILL
SCHP-1
NEW MOTOR
NEW PUMP
(E) FLOW
TRANSMITTER
FT
AI
PF
PC
DP
AI
PF
PC
AI
PF
T
AO
VM
TO/FROM (E) PCHP-3 AND (E)
CH-3 (EXISTING HEAT
RECOVERY CHILLER)
(E) SHOT
FEEDER
TO AHU'S
FROM AHU'S
COUPON
STATION
FT
AI
PF
(E) AIR
SEPARATOR
MECHANICAL FLOW DIAGRAM - CHILLER
(CHILLER/PUMP REPLACEMENT)
GENERAL CONTROL NOTES
ALL CONTROL POINTS ARE EXISTING AND/OR TO BE MATCHED WHERE
PREVIOUSLY DEMOLISHED. NO NEW CONTROL POINTS SHALL BE ADDED IN THIS
SCOPE OF WORK. THIS FLOW DIAGRAM IS REFERENCED FROM INITIAL CHILLER
DESIGN PROJECT, INFORM EOR OF ANY DISCREPANCIES.
1. CONTRACTOR SHALL MATCH SEQUENCE OF OPERATION OF EXISTING
CHILLER PLANT FOR ALL EQUIPMENT BEING REPLACED INCLUDING CHILLERS
AND PUMPS.
2. ALL CONTROL POINTS FROM EXISTING EQUIPMENT BEING REPLACED SHALL
BE CARRIED OVER FOR NEW EQUIPMENT.
3. CONTRACTOR SHALL REFURBISH OR REPLACE AS REQUIRED ANY CONTROL
OR MONITORING DEVICES AS REQUIRED.
RELOCATED STARTER FOR PCHP-1
CH-2 NEW CHILLER
SCHP-2 (E)
PUMP
SCHP-3 (E)
PUMP
(E)
VFD
(E)
VFD
CONTROL POINT ABBREVIATIONS
AI
AO
DI
DO
SS
FF
WR
VM
T P
DP
SP
TS
HS
PF
TD
ANALOG INPUT
ANALOG OUTPUT
DIGITAL INPUT
DIGITAL OUTPUT
START/STOP SIGNAL
FLOW FEEDBACK/STATUS SIGNAL
CHILLED WATER RESET 4-20 mA SIGNAL
PID VALV MODULATION
TEMPERATURE SENSOR/TRANSMITTER
PRESSURE SENSOR/TRANSMITTER
DIFFERENTIAL PRESSURE SWITCH
SETPOINT
THERMOSTAT
HUMIDISTAT
PROPORTIONAL, LINEARIZED FEEDBACK 4-20 mA SIGNAL
TIME DELAY
REPLACE APPURTENANCES
AND CONTROLS WHEREVER
DEMOLISHED, TYPICAL
REPLACE APPURTENANCES
AND CONTROLS WHEREVER
DEMOLISHED, TYPICAL REPLACE APPURTENANCES
AND CONTROLS WHEREVER
DEMOLISHED, TYPICAL
(E) BLADDER
TYPE
EXPANSION
TANK
FROM MAKEUP
WATER SYSTEM
TAG ISSUED DATE
100% Construction using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- M
E C
H -R
.r v t
/2
/2
:1 :2
P
M
M-701
AN
HPC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
MECHANICAL
SCHEDULES
J20241923.000
CLEARWATER, FL
ERIC J. REICHLING
92682
02.28.2027
ERIC J. REICHLING, P.E.
H, PACKAGED CHILLER UNIT AND CONTROLS SHALL BE RATED FOR 42kAIC
G. PROVIDE WITH HIGH SHORT CIRCUIT CURRENT RATING (SCCR) 65K MIN. AMPS.
F. PROVIDE 125 VAC, 20 AMP DUPLEX CONVENIENCE RECEPTACLE MOUNTED TO UNIT READY FOR FIELD WIRING WITH A COVER UL LISTED FOR WET AND DAMP LOCATIONS WHEN IN USE.
E. COORDINATE SIZE OF CONDUCTOR TERMINATION LUGS WITH CONDUCTOR SIZES SHOWN ON ELECTRICAL DRAWINGS.
D. PROVIDE SINGLE POINT POWER CONNECTION.
C. PROVIDE FACTORY MOUNTED INTEGRAL DISCONNECT SWITCH INSTALLED ON SERVICE SIDE OF UNIT
B. EQUIPMENT SIZED FOR 95 °F AMBIENT TEMPERATURE.
SUPERIOR UNIT SOUND PACKAGE, FACTORY R-454B REFRIGERANT CHARGE, STANDARD COOLING, GROOVED PIPE, FLOW SWITCH SET POINT 60, STANDARD 0.75 INCH INSULATION,LOW AMBIENT COOLING, COMPLETECOAT MICROCHANNEL CONDENSER FINS, EC CONDENSER FAN MOTORS, ACROSS-THE-LINE COMPRESSOR STARTER, CIRCUIT BREAKER, DEFAULT SHORT CIRCUIT RATING, UNDER/OVER VOLTAGE PROTECTION, BACNET INTERFACE (MS/TP) REMOTE
COMMUNICATION OPTION, ARCHITECTURAL LOUVERED PANELS, ELASTOMERIC ISOLATORS
A. THE FOLLOWING OPTIONS ARE PROVIDED FOR THE CHILLER:
NOTES:
MODEL NUMBERS AND NOMINAL TONS LISTED SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER, MODEL NUMBERS, OR NOMINAL TONS ONLY. REVIEW THE COMPLETE DESCRIPTION, NOTES AND SPECIFICATIONS TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE MANUFACTURERS LISTED ARE THE BASIS FOR THE DESIGN.
CH-2 TRANE ACSA2302EUA 230 R-454B 512.75 55 45 14.07 12 15.7 10.298 16.903 460/3 466 500 FACTORY 10701 A-H
CH-1 TRANE ACSA2302EUA 230 R-454B 512.75 55 45 14.07 12 15.7 10.298 16.903 460/3 466 500 FACTORY 10701 A-H
(GPM) ( °F) ( °F) (FT) FANS EACH (KW) V/PH MCA MOCP TYPE (LBS) NOTES
MARK MANUFACTURER MODEL REFRIGERANT FLOW EWT LWT MAX P.D. NUMBER OF FAN POWER DISC WEIGHT
NOMINAL
TONS
EVAPORATOR DATA CONDENSER DATA
EER IPLV
ELECTRICAL OPERATING
AIR-COOLED CHILLER SCHEDULE - OWNER SUPPLIED (FOR REFERENCE ONLY)
E. CONTRACTOR SHALL MAKE PROVISION FOR REMOVAL OF PUMP IMPELLER TO BE SENT BACK TO MANUFACTURER FOR SHAVING AND REINSTALL IN PUMP
D. CONTRACTOR SHALL FIELD VERIFY CONNECTION SIZES AND MATCH EXISTING PUMP SUCTION AND DISCHARGE DIAMETERS - INFORM EOR OF ANY DISCREPANCIES
C. PROVIDE INVERTER DUTY MOTOR. VARIABLLE FREQUENCY DRIVE INSTALLATION TO BE COORDINATED WITH CONTROLS CONTRACTOR AND ELECTRICAL CONTRACTOR.
B. INSTALL NEOPRENE PADS UNDER EQUIPMENT FOR VIBRATION CONTROL
A. BASIS OF DESIGN LISTED. REFER TO SPECIFICATIONS FOR APPROVED EQUIVALENT MANUFACTURERS.
NOTES:
MODEL NUMBERS LISTED SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER OR MODEL NUMBERS ONLY. REVIEW THE COMPLETE DESCRIPTION, NOTES AND SPECIFICATIONS TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE MANUFACTURERS LISTED ARE THE BASIS FOR THE DESIGN.
SCHP-1 TACO FL4013D-4P-PM BASE MOUNTED END SUCTION - TEFC 5x4 286T CHILLED WATER 830 104 45 175 81% 30.17 30 1760 480/3 A-E
PHCP-2 TACO FL4009D-4P-PM BASE MOUNTED END SUCTION - TEFC 5x4 254T CHILLED WATER 527 54.2 55 175 80% 10.4 15 1760 480/3 A-E
PCHP-1 TACO FL4009D-4P-PM BASE MOUNTED END SUCTION - TEFC 5x4 254T CHILLED WATER 527 54.2 55 175 80% 10.4 15 1760 480/3 A-E
(GPM) (FT) ( °F)
SIZE SERVICE FLOW HEAD TEMP
NOL BHP MOTOR HP RPM
MARK MANUFACTURER MODEL TYPE
MOTOR
FRAME
FLUID DATA
WORKING
PRESSURE (PSI)
PUMP
EFFICIENCY
MOTOR DATA
V/PH/HZ NOTES
PUMP SCHEDULE
TAG ISSUED DATE
100% Construction Documents
2025.01.27
G. INSTALL CONDENSING UNIT ON OUTDOOR WALL BRACKET. REFER TO DETAIL ON M-501
F. THE INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.
E. PROVIDE WITH INTEGRAL CONDENSATE PUMP.
D. PROVIDE WITH WALL MOUNTED THERMOSTAT BY UNIT MANUFACTURER.
C. EQUIPMENT CAPACITY SCHEDULED IS MINIMUM CAPACITY THAT MUST BE PROVIDED AT AMBIENT TEMPERATURE INDICATED.
B. CONTRACTOR SHALL VERIFY WITH EQUIPMENT SUPPLIER EXACT QUANTITY AND SIZE OF REFRIGERANT PIPING. INSTALL PER MANUFACTURERS RECOMMENDATIONS.
A. DISCONNECT SWITCH PROVIDED BY DIVISION 26 CONTRACTOR FOR EVAPORATOR SECTION AND CONDENSING SECTION.
NOTES:
MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND MODEL NUMBERS ONLY. REVIEW THE COMPLETE DESCRIPTION, NOTES AND SPECIFICATIONS TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE
MANUFACTURERS LISTED ARE THE BASIS FOR THE DESIGN.
AC-1 / CU-1 MECHANICAL ROOM MITSUBISHI R-410A PKA-A36KA8 920 36 40 208 / 1 1.00 0.57 46.00 PUZ-A36NKA7 25.0 31.0 208 / 1 95 19.4 211 A-G
(MBH) (MBH) (LBS) ( °F) (LBS)
MODEL CFM
TOTAL COOLING HEATING
V/PH MCA FLA
WEIGHT
MODEL MCA MOCP V/PH
AMB
SEER2
WEIGHTMARK SERVICE MANUFACTURER REFRIGERANT TYPE
EVAPORATOR SECTION CONDENSING SECTION
NOTES
MINI-SPLIT SCHEDULE
| Sheets |
| G-000 - PROJECT COVER SHEET |
| M-001 - MECHANICAL SYMBOL LEGEND AND NOTES |
| M-101 - SITE MECHANICAL PLAN |
| M-102 - BUILDING 7 MECHANICAL PLAN |
| M-501 - MECHANICAL DETAILS |
| M-601 - MECHANICAL CONTROLS |
| M-701 - MECHANICAL SCHEDULES |
| MD -102 - BUILDING 7 MECHANICAL DEMOLITION PLAN |
| 2025-01-27T13:36:17-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:25-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:31-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:37-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:41-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:44-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:47-0500 | |
| Eric J Reichling |
| 2025-01-27T13:36:51-0500 | |
| Eric J Reichling |
File details come from the government source that posted it. Updated .