2025-01-27_9508_Oak_Grove_MS_Chiller_Repl-ELEC-Permit_Set-S&S.pdf
PDF 1 MB Posted
- Attached to
- Chiller Replacement State and local contract opportunity
- Solicitation number
- 25-CR-037
- Issued by
- Pinellas County, Florida
About this file
The document is an electrical engineering set of design drawings for the Oak Grove Middle School Chiller Replacement project for Pinellas County Schools in Clearwater, Florida. The project involves a comprehensive electrical system upgrade, focusing on replacing chillers and associated electrical infrastructure in Building 7. The drawings, dated January 27, 2025, include detailed electrical plans, symbol legends, demolition plans, power distribution diagrams, one-line electrical diagrams, and panel schedules. The electrical design covers modifications to existing electrical systems, including relocating starters, installing new feeder conductors, and connecting new mechanical equipment.
The electrical design encompasses multiple electrical panels and systems, including switchboards (DP), panelboards (HM and LM), and electrical connections for chillers (CH-1, CH-2), condensing units, and various mechanical equipment. The project involves replacing existing electrical components while maintaining the current electrical infrastructure's overall configuration. The design ensures compliance with electrical codes, includes detailed mounting height specifications, and provides comprehensive notes on installation requirements, conductor sizing, and equipment labeling. The electrical system upgrades are part of a broader chiller replacement initiative, with careful consideration given to existing electrical loads, circuit configurations, and mechanical system integration.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Chiller_Replacement_Addendum_1_Revision.pdf | ||
| Record_Submittal_11.22.24_-_PCSB_-_Oak_Grove_Chillers.pdf | ||
| 2025-02-17_9508_Pre-bid_meeting_sign-in_sheet.pdf | ||
| 2025-01-27_9508_Oak_Grove_MS_FULL_SET_SPECS_Mech_+_Elec-S&S.pdf | ||
| 2025-01-27_9508_Oak_Grove_MS_Chiller_Repl-MECH-Permit_Set_S&S.pdf | ||
| Bid_Protest_Procedure.pdf | ||
| Insurance_Specifications_for_Contractors.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
###X
J
P T
EQUIPMENT PROVIDED BY OTHER DIVISIONS REQUIRING ELECTRICAL CONNECTION(S). COORDINATE EQUIPMENT LOCATION, CONNECTION POINT(S), AND OTHER REQUIREMENTS WITH RESPECTIVE DIVISION'S DRAWINGS, SPECIFICATIONS, AND SHOP DRAWINGS. REFER TO EQUIPMENT CONNECTION SCHEDULES FOR ADDITIONAL REQUIREMENTS. EXAMPLES OF EQUIPMENT REQUIRING ELECTRICAL CONNECTION(S) AS
FOLLOWS:
"XXXX-##" INDICATES MECHANICAL / PLUMBING / FIRE PROTECTION EQUIPMENT
DESIGNATIONS, MATCHING LABELS USED IN THOSE DIVISIONS' CONSTRUCTION
DOCUMENTS.
"FS-##" INDICATES FOOD SERVICE EQUIPMENT, MATCHING ITEM NUMBER (##) AS SHOWN
ON FOOD SERVICE CONSTRUCTION DOCUMENTS.
"ELEV-##" INDICATES ELEVATOR, MATCHING DESIGNATION AS SHOWN ON ARCHITECTURAL
CONSTRUCTION DOCUMENTS.
XXXX-##
POWER & EQUIPMENT SYMBOL LEGEND
SYMBOL DESCRIPTION
HALF TONE LINES DENOTES BACKGROUND OR EXISTING TO REMAIN (E).
THIN SOLID LINES
DENOTES DEVICES, EQUIPMENT, ETC. EXISTING TO REMAIN (E).
HEAVY SOLID LINES
DENOTES NEW (N) OR RELOCATED (R) DEVICES, EQUIPMENT, ETC.
DASHED LINES DENOTES DEVICES, EQUIPMENT, ETC. TO BE DISCONNECTED AND REMOVED (D&R).
HEAVY PHANTOM LINES
DENOTES NEW (N) OR RELOCATED (R) CONDUIT, EQUIPMENT, ETC.UNDERGROUND
OR BELOW GRADE.
BRANCH CKT TURNING UP. BRANCH CKT TURNING DOWN. BRANCH CKT TURNING UP AND DOWN.
UE
UT
UNDERGROUND, UNDER FLOOR/SLAB DUCTBANK, DIRECT BURIED CABLE, CONDUIT/CONDUCTOR:
UT = TELECOM; UE = ELECTRICAL
GH
N #AWG
HOME RUN. HASH MARKS INDICATE CONDUCTOR QUANTITY. HASH MARKS DEFINED AS SHOWN.
"#" INDICATES SIZE OF CONDUCTORS OTHER THAN 12-AWG. ALL UNMARKED HOMERUNS SHALL CONTAIN (2)
#12 AWG & (1) #12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
ZZZ / #,#,#
480Y/277 VOLT, 3-PHASE, 4-WIRE ELECTRICAL DISTRIBUTION TYPE PANELBOARD.
WP
#,WP
WP
WP
WP
WPAS
AF
AS
AT
AS
AF
AS
208Y/120 VOLT, 3-PHASE, 4-WIRE ELECTRICAL DISTRIBUTION TYPE PANELBOARD.
480Y/277 VOLT, 3-PHASE, 4-WIRE, SURFACE MOUNTED ELECTRICAL PANELBOARD.
BRANCH CIRCUITING. "ZZZ" INDICATES PANEL DESIGNATION. "#,#,#," INDICATES CIRCUIT NUMBER(S).
208Y/120 VOLT, 3-PHASE, 4-WIRE, SURFACE MOUNTED ELECTRICAL PANELBOARD.
DRY-TYPE DISTRIBUTION TRANSFORMER.
NON-FUSED DISCONNECT SWITCH. "AS" INDICATES SWITCH SIZE.
"WP" INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
FUSED DISCONNECT SWITCH. "AF" INDICATES FUSE SIZE. "AS" INDICATES SWITCH SIZE.
"WP" INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
FUSED CIRCUIT BREAKER SWITCH. "AT" INDICATES CIRCUIT BREAKER TRIP RATING.
"AF" INDICATES FRAME SIZE. "WP" INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
MAGNETIC MOTOR STARTER MOUNTED IN A NEMA ENCLOSURE. "#" INDICATES STARTER SIZE. "WP"
INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
COMBINATION STARTER & FUSED DISCONNECT SWITCH. "#" INDICATES STARTER SIZE.
"AF" INDICATES FUSE SIZE, "AS" INDICATES SWITCH SIZE.
"WP" INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
COMBINATION VFD STARTER AND DISCONNECT SWITCH.
"WP" INDICATES WEATHERPROOF (NEMA 3R) ENCLOSURE.
FEEDER DESIGNATION. REFER TO
FEEDER SCHEDULE(S) FOR FEEDER
SIZE.
ONE-LINE DIAGRAM SYMBOL LEGEND
SYMBOL DESCRIPTION
DENOTES NEW (N) OR RELOCATED
(R) BUSSING, FEEDER, ETC.HEAVY SOLID LINES
AUTOMATIC TRANSFER SWITCH.
NUMBER OF POLES AND AMPERAGE
RATING AS NOTED OR SCHEDULED.
SYMBOL DESCRIPTION
DRY TYPE TRANSFORMER. kVA, PHASE, PRIMARY AND SECONDARY
RATING AS NOTED OR SCHEDULED.
PANELBOARD. DESIGNATION AS
NOTED. SEE PANELBOARD
SCHEDULES FOR ADDITIONAL
INFORMATION.
MOLDED CASE CIRCUIT BREAKER.
FRAME AND TRIP SIZES AS NOTED.
MOLDED CASE CIRCUIT BREAKER
WITH SHUNT TRIP OPERATOR.
FRAME AND TRIP SIZES AS NOTED.
LOW VOLTAGE FUSED DISCONNECT
SWITCH. FUSE AND DISCONNECT
SWITCH SIZES AS NOTED.
LOW VOLTAGE DISCONNECT SWITCH.
DISCONNECT SWITCH SIZE AS
NOTED.
LOW VOLTAGE FUSE. SIZE AS NOTED.
COMBINATION STARTER AND
MOTOR CIRCUIT PROTECTOR.
STARTER AND MOTOR CIRCUIT
PROTECTOR SIZES AS NOTED.
COMBINATION STARTER AND
FUSED DISCONNECT SWITCH.
STARTER, FUSE, AND SWITCH
SIZES AS NOTED.
SPECIALTY EQUIPMENT/DEVICES. "XX"
STANDS FOR THE FOLLOWING:
SPD SURGE PROTECTIVE
DEVICE.
GFP GROUND FAULT
PROTECTION.
C CONTACTOR.
M METERING.
EPO EMERGENCY POWER OFF
PUSHBUTTON.
VFD VARIABLE FREQUENCY
DRIVE PROVIDED BY
DIVISION 23.
EC ELEVATOR CONTROLLER
PROVIDED BY DIVISON 14.
THREE PHASE GENERATOR. SIZE
AS NOTED OR SCHEDULED.
THREE PHASE MOTOR.
HORSEPOWER AS NOTED OR
SCHEDULED. 'XX' INDICATES
MOTOR DESIGNATION.XX
SPACE IN CIRCUIT BREAKER OR
FUSED SWITCH DISTRIBUTION
PANELBOARD. FRAME SIZE AS
NOTED.
DELTA TO WYE CONNECTED
WIRING
CONTROL POWER
TRANSFORMER (CPT) OR
POTENTIAL TRANSFORMER (PT).
CURRENT TRANSFORMER. SIZE
AS REQUIRED.
NEUTRAL BUS TO GROUND BUS
BONDING.
MEDIUM VOLTAGE FUSED
DISCONNECT SWITCH. FUSE
SIZE AS NOTED.
MEDIUM VOLTAGE FUSE. SIZE AS
NOTED.
LOW VOLTAGE BOLTED
PRESSURE FUSED SWITCH. FUSE
AND DISCONNECT SWITCH SIZES
AS NOTED.
HAND/OFF/AUTO SWITCH.
FUSE
FUSE
G
TRIP
FRAME
STARTER
FUSE
SWITCH
MCP
STARTER
M
SPACE
G
NN
FUSE
ST
TRIP
FRAME
SWITCH
FUSE
SWITCH
NAME
SWITCH
XX
SWITCH
FUSE
SWITCH
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING TYPE, NEMA 5-20R, MOUNTED 18"A.F.F. UNLESS OTHERWISE NOTED. "+XX" INDICATES MOUNTING HEIGHT OTHER THAN 18". "ZZ / ##"
INDICATES BRANCH CIRCUITING.
ZZ/##
+XX"
OUTLET SYMBOL LEGEND
SYMBOL DESCRIPTION
ZZ/##
+XX"
ZZ/##
+XX"
ZZ/##
+XX"
SPECIAL PURPOSE RECEPTACLE. REFER TO ABOVE FOR MOUNTING HEIGHT AND CIRCUITING
INFORMATION. "X" INDICATES THE FOLLOWING:
A XX VOLT, X POLE, X WIRE, XX AMP (NEMA X-XXR)
COORDINATE EXACT NEMA CONFIGURATION WITH EQUIPMENT PRIOR TO ROUGH-IN.
SINGLE RECEPTACLE, 20 AMPERE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING TYPE, NEMA 5-20R, MOUNTED 18"A.F.F. UNLESS OTHERWISE NOTED. REFER TO ABOVE FOR MOUNTING HEIGHT AND CIRCUITING
INFORMATION.
DOUBLE DUPLEX (QUAD) RECEPTACLE, 20 AMPERE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING TYPE, NEMA 5-20R, MOUNTED 18"A.F.F. UNLESS OTHERWISE NOTED. REFER TO ABOVE FOR MOUNTING HEIGHT AND
CIRCUITING INFORMATION.
ZZ/##
ZZ/##
X
FLOOR MOUNTED RECEPTACLE, 20 AMPERE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING TYPE, NEMA 5-20R.
REFER TO ABOVE FOR CIRCUITING INFORMATION. "X" INDICATES THE FOLLOWING:
A1 SINGLE GANG WITH SINGLE DUPLEX. SEE DETAIL FOR ADDITIONAL INFORMATION.
A2 2-GANG WITH DOUBLE DUPLEX. SEE DETAIL FOR ADDITIONAL INFORMATION.
CEILING MOUNTED DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING TYPE, NEMA
5-20R. REFER TO ABOVE FOR CIRCUITING INFORMATION.
ZZ/##
X
FLOOR BOX OR POKE-THROUGH POWER AND TELECOM DEVICE. REFER TO ABOVE FOR CIRCUITING
INFORMATION. "X" INDICATES THE FOLLOWING:
B 2-GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE AND SINGLE GANG FOR
TELECOM. SEE DETAIL FOR ADDITIONAL INFORMATION.
C 3-GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE AND 2-GANGS FOR TELECOM.
SEE DETAIL FOR ADDITIONAL INFORMATION.
D 6-GANG FLOOR BOX WITH TWO DUPLEX RECEPTACLES AND 4-GANGS FOR TELECOM
AND/OR AUDIO-VISUAL. SEE DETAIL FOR ADDITIONAL INFORMATION.
E FIRE RATED POKE-THROUGH. SEE DETAIL FOR ADDITIONAL INFORMATION.
DEVICE MOUNTED 8" ABOVE COUNTER. REFER TO ABOVE FOR TYPE AND CIRCUITING INFORMATION.
DEVICE ON EMERGENCY POWER. REFER TO ABOVE FOR TYPE AND CIRCUITING INFORMATION.
JOB SPECIFIC OPTION. REFER TO ABOVE FOR TYPE AND CIRCUITING INFORMATION.
RECEPTACLES WITH ADDITIONAL SUBSCRIPT DESIGNATES TYPE OR SPECIFIC REQUIREMENTS AS
FOLLOWS:
G GROUND FAULT CIRCUIT INTERRUPTER TYPE.
AC DEVICE MOUNTED 8" ABOVE COUNTER.
AV DEVICE MOUNTED ADJACENT TO TELECOMMUNICATION DEVICE.
EWC ELECTRIC WATER COOLER (GFCI TYPE, COORDINATE WITH WATER COOLER).
E CIRCUITED TO EMERGENCY POWER.
IG ISOLATED GROUND.
TR TAMPER RESISTANT TYPE.
WP WEATHERPROOF "WHILE-IN-USE" (HUBBELL #WP26E) COVER.
JUNCTION BOX (SIZED AS REQUIRED PER N.E.C. ARTICLE 314).
FRACTIONAL HORSEPOWER MOTOR STARTER - 120 VOLT, 20 AMP, 1 POLE, PILOT LIGHT, UNLESS
OTHERWISE NOTED.
m
X
ZZ/##
X
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
E-001
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
ELECTRICAL
SYMBOL
LEGEND
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
ABBREVIATIONS
GENERAL
AC
AFF
AFG
AL
ATS
CB
CKT
CP
CR
CT
CU
EG
ELEV
EM
GAP
GEC
GEN
GFCI
GFP
GND
IG
IPP
LCP
LS
LTG
MCB
MCC
MDP
MEGB
MLO
MTGB
MTS
(N.I.C.)
NL
OS
PNL
REC
SB
SE
SW
SWBD
UC
UG
UPS
VFD
VP
VT
WIU
WP
ABOVE COUNTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ALUMINUM
AUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER
CIRCUIT
CONTROL PANEL
CRITICAL BRANCH
CURRENT TRANSFORMER
COPPER
EQUIPMENT GROUND
ELEVATOR
EMERGENCY
GENERATOR ANNUNCIATOR
PANEL
GROUNDING ELECTRODE
CONDUCTOR
GENERATOR
GROUND FAULT CIRCUIT
INTERRUPTER
GROUND FAULT PROTECTION
GROUND
ISOLATED GROUND
ISOLATED PPOWER PANEL
LIGHTING CONTROL PANEL
LIFE SAFETY
LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MAIN ELECTRIC GROUND BUS
MAIN LUG ONLY
MAIN TECHNOLOGY GROUND BUS
MANUAL TRANSFER SWITCH
NOT IN CONTRACT
NIGHT LIGHT
OCCUPANCY SENSOR
PANEL
RECEPTACLE
OPTIONAL STAND-BY
SERVICE ENTRANCE
SWITCH
SWITCHBOARD
UNDER COUNTER
UNDERGROUND
UNINTERRUPTIBLE POWER
SUPPLY
VARIABLE FREQUENCY DRIVE
VANDAL PROOF
VOLTAGE TRANSFORMER
WHILE IN USE
WEATHERPROOF
RACEWAY TYPES
AC
C
EMT
MC
PVC
RGS
ARMORED CABLE
CONDUIT
ELECTRIC METALIC TUBING
METAL CLAD
POLYVINYL CHLORIDE
RIGID GALVANIZED STEEL
MECHANICAL EQUIPMENT
AC
ACC
AHU
B
BAS
CH
CU
CUH
DDC
EF
EUH
EWC
EWH
F
FCU
FPVAV
HP
MAU
P
RTU
SAHU
UH
UST
VAV
AIR CONDITIONING UNIT
AIR COOLED CHILLER
AIR HANDLING UNIT
BOILER
BUILDING AUTOMATION
SYSTEM
CHILLER
CONDENSING UNIT
CABINET UNIT HEATER
DIGITAL DIRECT CONTROL
EXHAUST FAN
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FURNACE
FAN COIL UNIT
FAN-POWERED VARIABLE AIR
VOLUME
HEAT PUMP
MAKE-UP AIR UNIT
PUMP
ROOFTOP UNIT
SPLIT SYSTEM AIR HANDLING
UNIT
UNIT HEATER
UNDERGROUND STORAGE
TANK
VARIABLE AIR VOLUME
SCOPE OF WORK
(D&R)
(E)
(NIC)
(R)
(R&R)
(REP)
EC
GC
MC
TC
DISCONNECT AND REMOVE
EXISTING (TO REMAIN)
NOT IN CONTRACT
RELOCATED
REMOVE AND RELOCATE
REPLACE
ELECTRICAL CONTRACTOR
GENERAL CONTRACTOR
MECHANICAL CONTRACTOR
TECHNOLOGY CONTRACTOR
PANEL KEY
BLANK: NORMAL
E: EMERGENCY
S: OPTIONAL STAND-BY
LS: LIFE SAFETY
CR: CRITICAL BRANCH
EQ: EQUIPMENT BRANCH
LP: 480Y/277V
RP: 208Y/120V
B,1,2... FLOOR / LEVEL
A,B,C... BUILDING SECTOR / WING
1,2,3... SEQUENTIAL
LP 1 A 1
ELECTRICAL SHEET LIST
Sheet Number Sheet Name
E-001 ELECTRICAL SYMBOL LEGEND
E-002 ELECTRICAL GENERAL NOTES
E-201 SITE ELECTRICAL PLAN
ED-202 BUILDING 7 POWER DEMOLITION PLAN
E-202 BUILDING 7 POWER PLAN
E-511 POWER DETAILS AND DIAGRAMS
E-601 ELECTRICAL ONE LINE DIAGRAM
E-711 ELECTRICAL PANEL SCHEDULES
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
Robert Chrachol, PE
2/28/2025
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
E-002
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
ELECTRICAL
GENERAL
NOTES
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
1. ANY AND ALL "BUILDING STANDARDS" AND/OR "BUILDING" SPECIFICATIONS" SHALL BE
CONSIDERED AN INTEGRAL PART OF THESE DOCUMENTS AND THE CONTRACTOR SHALL BE
RESPONSIBLE TO OBTAIN A COPY OF THESE DOCUMENTS AND COMPLY WITH ALL
REQUIREMENTS AND STANDARDS CONTAINED WITHIN.
2. REFER TO THE FOLLOWING: SYMBOL LEGEND(S) AND NOTES: DWG's E-001 & E-002;
ELECTRICAL SPECIFICATIONS: DWG's E-003 & E-004; ELECTRICAL DETAILS: DWG. SERIES E-500's; ELECTRICAL ONE LINE DIAGRAM(S): DWG. SERIES E-600's; AND ELECTRICAL SCHEDULES: DWG. SERIES E-700's FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
3. ELECTRICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC, ARE INTENDED TO CONVEY THE
SCOPE OF WORK, AND INDICATE GENERAL ARRANGEMENT OF LIGHTING FIXTURES,
DEVICES, CONTROLS, ELECTRICAL FIXTURES, MOTORS, PANELBOARDS, EQUIPMENT, ETC.
THE LOCATIONS OF ALL ITEMS SHOWN ON ELECTRICAL DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT EXPLICITLY FIXED BY DIMENSIONS ARE APPROXIMATE. THE
EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE
DETERMINED AT THE PROJECT. ALL LOCATIONS OF WORK EXPOSED TO VIEW ARE SUBJECT
TO APPROVAL OF THE ARCHITECT PRIOR TO ROUGH-INS.
4. THE ELECTRICAL CONTRACTOR SHALL LAYOUT ALL EQUIPMENT ROOMS TO MAKE SURE THE
EQUIPMENT, AS PURCHASED, FITS IN THE ROOM OR SPACE SHOWN. EXACT LOCATION OF
ALL EQUIPMENT SHALL BE VERIFIED IN THE FIELD AND ROUTING OF CONDUITS SHALL SUITE
FIELD CONDITIONS.
5. THE CONTRACTOR SHALL VISIT THE SITE OF THE WORK TO FAMILIARIZE HIMSELF WITH THE
EXISTING CONDITIONS AND HIS PROPOSAL SHALL INCLUDE ALL CONTINGENCIES
NECESSARY FOR THE COMPLETION OF HIS WORK REGARDING SUCH EXISTING CONDITIONS.
THE ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING CONDITIONS TO INSURE THAT ALL
NEW WORK WILL FIT INTO THE EXISTING STRUCTURE AND CONDITIONS IN THE MANNER
INTENDED AND AS SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE
ARCHITECT/OWNERS REPRESENTATIVE PRIOR TO ANY ROUGH-INS, FABRICATIONS, OR
PERFORMING ANY WORK IN THE AREA INVOLVING DIFFERENCES. NOTIFICATION SHALL BE IN
THE FORM OF A DRAWING OR SKETCH INDICATING FIELD MEASUREMENTS AND NOTES
RELATED TO THE AREA.
6. ANY DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE PROMPTLY
BROUGHT TO THE ATTENTION OF THE ENGINEER FOR CLARIFICATION DURING THE BIDDING
PERIOD. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE TO THE CONTRACTOR BY
REASON OF HIS FAILURE TO HAVE BROUGHT SAID DISCREPANCIES TO THE ATTENTION OF
THE ENGINEER DURING THE BIDDING PERIOD OR OF ANY ERROR ON THE CONTRACTOR'S
PART.
7. THERE SHALL BE NO SUBSTITUTIONS UNLESS THE CONTRACTOR HAS OBTAINED WRITTEN
APPROVAL FROM THE OWNER AFTER HAVING SUBMITTED AN ALTERNATIVE PROPOSAL
COMPLETE WITH A DESCRIPTION OF DEVIATION FROM THE SPECIFICATIONS AND A
STATEMENT OF BENEFITS TO BE DERIVED SHOULD SUCH A PROPOSED SUBSTITUTE BE
ACCEPTED.
8. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT, PROFESSIONAL AND WORKMANLIKE
MANNER, RECTILINEAR TO FINISHES AND BUILDING STRUCTURE.
9. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL
CODE, OSHA REQUIREMENTS, AND LOCAL REQUIREMENTS, ALL AS INTERPRETED BY THOSE
HAVING JURISDICTION.
10. REFER TO ARCHITECTURAL ELEVATIONS TO DERIVE EXACT LOCATIONS OF ALL
RECEPTACLES, OUTLETS/JACKS, SWITCHES, WALL AND PENDANT/CABLE MOUNTED
LUMINAIRES, ETC. LUMINAIRES AND CEILING MOUNTED EQUIPMENT SHALL BE
COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS.
11. BEFORE DOING ANY WORK WHICH MIGHT ENTAIL A FULL OR PARTIAL SHUTDOWN, THE
ELECTRICAL CONTRACTOR SHALL INFORM THE OWNER SO THAT A SCHEDULED SHUTDOWN
ARRANGEMENT CAN BE MADE, TAKING EVERY PRECAUTION THAT THE ELECTRICAL SYSTEM
IS OPERATING SATISFACTORILY.
12. THE ELECTRICAL CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES THAT ARE
REQUIRED BY THE APPLICABLE LOCAL AND STATE LAWS.
13. CONDUIT HOME RUNS SHOWN ON THE DRAWING WITH MORE THAN THREE (3) CURRENT
CARRYING CONDUCTORS ARE SHOWN DIAGRAMMATICALLY. THIS CONTRACTOR SHALL NOT
INSTALL MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS IN A RACEWAY UNLESS
NATIONAL ELECTRIC CODE (N.E.C), ARTICLE 310.15 DERATING FACTORS ARE APPLIED.
14. THE ELECTRICAL CONTRACTOR SHALL REFER TO THE ELECTRICAL SPECIFICATIONS FOR
ACCEPTABLE CONDUIT TYPES/LOCATIONS. ALL CONDUIT SIZES ON THE DRAWINGS ARE
BASED ON THE LATEST EDITION OF THE N.E.C. CONDUIT FILL TABLES FOR ELECTRICAL
METALLIC TUBING (E.M.T). CONDUIT SIZES SHALL BE REVISED TO THE SIZE REQUIRED,
RELATIVE TO THE ACTUAL CONDUIT TYPE TO BE INSTALLED.
15. ALL COMPONENTS SHOWN ON THE RISER/ONE-LINE DIAGRAMS, BUT NOT ON THE PLAN OR
VICE VERSA, SHALL BE INCLUDED AS IF SHOWN ON BOTH.
16. IT IS NOT INTENDED THAT THE PLANS INDICATE ALL OBSTRUCTIONS, NECESSARY BENDS, OFFSETS, AND PULL BOXES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
INSTALL HIS WORK TO CONFORM TO N.E.C. REQUIREMENTS, THE STRUCTURE, MAINTAIN
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. REFER TO THE
ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AS REQUIRED.
17. IT IS NOT INTENDED THAT THE PLANS INDICATE ALL CONDUIT ROUTES, PULL BOXES,
JUNCTION BOXES, ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING ACTUAL
CONDUIT ROUTING, QUANTITY AND LOCATION OF PULL BOXES WITHIN ACCESSIBLE
LOCATIONS.
18. PROVIDE SCREW-COVER PULL BOXES IN CONDUIT RUNS AS REQUIRED TO LIMIT THE
NUMBER OF BENDS TO NO MORE THAN FOUR (4) 90° OR 360° TOTAL. SIZE PULL BOXES IN
ACCORDANCE WITH NEC, ARTICLE 314.28. DOCUMENT ON RECORD DRAWINGS, SIZE AND
LOCATION OF PULL BOXES USED IN FEEDER CONDUIT RUNS.
19. WHERE MULTIPLE DEVICES OF THE SAME TYPE/STYLE ARE SHOWN NEXT TO EACH OTHER,
GANG INTO A SINGLE COVER PLATE.
20. ALL RACEWAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH
APPROPRIATE EXPANSION FITTINGS.
21. IDENTIFY WITH LEGIBLE AND DURABLE MARKING, EACH DISCONNECTING MEANS INDICATING
ITS PURPOSE.
22. ALL RECEPTACLES, SWITCHES AND DEVICES SHALL HAVE PANEL AND CIRCUIT NUMBER
IDENTIFY WITH LEGIBLE AND DURABLE MARKING ON COVER PLATE. OWNER WILL INDICATE IF
MARKINGS ARE ON THE FRONT OR BACK OF COVER.
23. ALL LABOR AND MATERIAL FURNISHED BY THE CONTRACTOR AS PART OF THIS CONTRACT
SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE BY THE
OWNER. ANY DEFECTS WHICH APPEAR WITHIN THE GUARANTEE PERIOD SHALL BE
PROMPTLY REPAIRED OR REPLACED AT THE OWNER'S DISCRETION, WITHOUT ADDITIONAL
COST TO THE OWNER.
24. ALL EQUIPMENT GROUNDS SHALL BE TERMINATED WITH COMPRESSION FITTINGS AND
STAINLESS STEEL BOLTS OR IN PANEL GROUND BAR.
25. BEFORE DRILLING ANY HOLES IN WALLS OR FLOORS THE AREA MUST BE CHECKED FOR
EXISTING EMBEDDED CONDUITS AND WIRE. IF ANY EXISTING CONDUITS OR WIRING ARE
DAMAGED BY THIS CONTRACTOR IT IS THIS CONTRACTORS RESPONSIBILITY TO MAKE ALL
REPAIRS TO CONDUITS, WIRE, FLOORS AND BUILDING FINISHES IN KIND AT NO COST TO
OWNER.
26. PROVIDE UL LISTED FIRE STOP ASSEMBLY AT ALL NEW AND EXISTING PENETRATIONS IN
FIRE RATED STRUCTURES.
27. ALL 120 VOLT, SINGLE PHASE 15 AND 20 AMPERE RECEPTACLE OUTLETS USED BY THE
WORKMEN SHALL BE PROTECTED BY A "GROUND FAULT INTERRUPTER".
GENERAL ELECTRICAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE TO BE USED AS A GUIDELINE ONLY
FOR THE SCOPE OF DEMOLITION WORK. THE CONTRACTOR SHALL VISIT THE PROJECT SITE
DURING THE BID PHASE TO VERIFY THE EXACT CONDITIONS AND SCOPE OF WORK
REQUIRED FOR A COMPLETE AND INCLUSIVE DEMOLITION PACKAGE.
2. THE CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO
COMPARE THEM WITH THE CONTRACT DOCUMENTS AND TO HAVE SATISFIED HIMSELF AS TO
THE CONDITIONS OF THE PREMISES, THE SITE, ANY OBSTRUCTIONS, THE ACTUAL LEVELS,
ACCESS PANELS, AND ALL OTHER EXISTING CONDITIONS. THE CONTRACTOR SHALL VERIFY
ALL DIMENSIONS IN THE FIELD, SHALL CHECK LOCATION OF AND CONNECTION TO EXISTING
FACILITIES, AND SHALL ASSUME ALL RESPONSIBILITY FOR SAME.
3. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO LOCATE ALL EXISTING
UTILITIES IN WORK AREA PRIOR TO INITIATION OF DEMOLITION ACTIVITIES. BEGINNING OF
DEMOLITION SHALL SIGNIFY CONTRACTORS ACCEPTANCE OF EXISTING CONDITIONS AND
THE COST OF REWORKING ANY EXISTING SYSTEMS DUE TO CONFLICTS WITH EXISTING
CONDITIONS SHALL BE PAID BY CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR ALL
REQUIRED DEMOLITION WHETHER SHOWN ON THE PLANS OR NOT.
4. THE CONTRACTOR SHALL COORDINATE WITH THE TENANT AND/OR BUILDING MANAGEMENT
ALL INTERRUPTION OF ELECTRICAL SERVICES WITHIN THE TENANT SPACE AND/OR
BUILDING.
5. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL, MECHANICAL HVAC,
AND PLUMBING DEMOLITION DRAWINGS FOR ALL EQUIPMENT BEING DEMOLISHED, AND
SHALL DISCONNECT AND REMOVE COMPLETE THE ELECTRICAL SERVICES TO ALL
EQUIPMENT AND WIRING DEVICES. DEMOLITION DRAWINGS OF ALL DISCIPLINES MUST BE
CHECKED AND ALL ASSOCIATED ELECTRICAL DEVICES OF EQUIPMENT REMOVED BY
OTHERS MUST BE REMOVED.
6. ALL EXISTING LUMINAIRES AND ASSOCIATED CONTROLS, ELECTRICAL EQUIPMENT, WIRING
DEVICES, FIRE ALARM DEVICES, ETC. NOT INDICATED ON THIS PLAN SHALL BE EXISTING TO
REMAIN, UNLESS SPECIFICALLY NOTED OTHERWISE.
7. FOR ALL RENOVATION/REMOLDING WORK, INCLUDING ALL AREAS OF NO OR MINIMAL WORK,
EXISTING ELECTRICAL SERVICES SHALL BE MAINTAINED TO LUMINAIRES, EQUIPMENT,
WIRING DEVICES, ETC. (POWER, LIGHTING, ETC.), THAT ARE REQUIRED TO BE MAINTAINED.
THE CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN THESE SERVICES, EQUIPMENT,
WIRING DEVICES THAT ARE EXISTING TO REMAIN, WHETHER OR NOT INDICATED ON THE
PLANS.
8. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL EQUIPMENT, WIRING DEVICES,
TELECOM DEVICES, BLANK COVER PLATES, ETC. LOCATED IN WALLS/PARTITIONS LABELED
AS "TO BE REMOVED". REMOVE ALL EXISTING BRANCH CIRCUITING (CONDUCTORS AND
CONDUIT) BACK TO LAST ACTIVE DEVICE (OR SOURCE IF NO ACTIVE DEVICES REMAIN).
9. ALL ELECTRICAL LUMINAIRES, EQUIPMENT, WIRING DEVICES, TELECOMMUNICATIONS
VOICE/DATA CABLING, ETC. SHALL BE REMOVED COMPLETE, BACK TO SOURCE,
(PANELBOARD, TERMINAL BOARDS, ETC.), INCLUDING ALL BRANCH CIRCUITING,
(CONDUCTORS AND CONDUIT), FEEDERS, SUPPORTS, JUNCTION BOXES, PULL BOXES, ETC.
10. PROVIDE AND MAINTAIN TEMPORARY ELECTRICAL SERVICES, SUCH AS LIGHTING AND
POWER IN ALL AREAS OF DEMOLITION AND SURROUNDING AREAS NOT IN DEMOLITION FOR
THE DURATION OF THE PROJECT. COORDINATE ALL TEMPORARY ELECTRICAL SERVICES
WITH OWNER'S SITE REPRESENTATIVE AND/OR LOCAL ELECTRIC UTILITY.
11. EQUIPMENT AND WIRING DEVICES INDICATED AS (R&R) - EXISTING TO BE RELOCATED, SHALL
BE STORED FOR RE-USE AS INDICATED (R) - NEW LOCATION OF EXISTING RELOCATED
DEVICE, ON NEW PLAN DRAWINGS. DEVICES SHALL BE CLEANED, LUMINAIRES RE-LAMPED
PER SPECIFICATIONS, AND BALLAST REPLACED WHERE FOUND TO BE INOPERABLE.
12. EXISTING FIRE ALARM DEVICES THAT ARE LABELED (E) - EXISTING TO REMAIN, SHALL BE
PROTECTED FROM CONSTRUCTION DAMAGE AND DIRT. THE FIRE ALARM SYSTEM SHALL BE
KEPT OPERABLE DURING CONSTRUCTION.
13. ANY CIRCUITS FEEDING THROUGH EQUIPMENT OR DEVICES THAT ARE BEING DEMOLISHED,
REWORKED, OR RELOCATED, AND FEEDING OTHER EQUIPMENT/DEVICES THAT REMAIN ARE
TO BE MAINTAINED.
14. ALL CUTTING AND PATCHING OF WALLS, CEILINGS, OR FLOORS THAT ARE DISTURBED BY
DEMOLITION SHALL BE RETURNED TO THEIR ORIGINAL CONDITION. REFER TO THE
ARCHITECTURAL DOCUMENTS FOR EXACT SPECIFICATION REQUIREMENTS. PATCH FLOOR
TO ORIGINAL CONSTRUCTION SPECIFICATIONS AND U.L. FIRE RATING LISTINGS FOR ALL
FLOOR MOUNTED DEVICES SUCH AS FLOOR BOXES, (FIRE RATED) POKE-THROUGHS, ETC.
WHICH HAVE BEEN REMOVED.
15. ALL EQUIPMENT AND/OR DEVICES THAT ARE REMOVED AND NOT RE-USED SHALL BE
TURNED OVER TO THE TENANT AND/OR BUILDING MANAGEMENT OR DISPOSED OF PER
THEIR DIRECTION. MATERIAL OF NO SALVAGEABLE VALUE INCLUDING CONDUIT, WIRE AND
TRASH RESULTING FROM THE DEMOLITION WORK SHALL BE REMOVED BY THE ELECTRICAL
CONTRACTOR PROMPTLY FROM THE JOB SITE AND PROPERLY DISPOSED OF IN A LEGAL
MANNER. NO BURNING SHALL BE PERMITTED ON THE SITE.
16. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO CONDUCT ALL
DEMOLITION IN ACCORDANCE WITH OSHA, EPA, AND ALL OTHER APPLICABLE CODES AND
REGULATIONS FOR TYPE OF WORK.
17. ANY AND ALL ABANDONED CONDUIT AND/OR WIRING FOUND DURING DEMOLITION SHALL BE
REMOVED BY THE ELECTRICAL CONTRACTOR AT NO ADDITIONAL EXPENSE.
18. REMOVE ALL ELECTRICAL EQUIPMENT, DEVICES, BOXES, CONDUIT AND WIRE IN THE AREA
OF NEW CONSTRUCTION UNLESS OTHERWISE NOTED. CONDUIT, WIRE AND ELECTRIC
DEVICES WHICH MAY PASS THRU THE AREA OF NEW CONSTRUCTION AND/OR MAY BE
AFFECTED BY DEMOLITION SHALL REMAIN OR, IF REQUIRED, SHALL BE RE-WORKED TO KEEP
THOSE ITEMS OPERATIONAL.
19. AREAS AND SERVICES ADJACENT TO DEMOLITION AREAS SHALL BE PROTECTED FROM THE
DEMOLITION PROCESS. PROTECTIVE MEASURES SHALL BE THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR FOR ALL ELECTRICAL WORK AND SHALL BE MAINTAINED
CONTINUOUSLY UNTIL DEMOLITION IS COMPLETED.
20. ALL DEMOLITION AND MATERIAL REMOVAL OPERATIONS SHALL BE CAREFULLY AND SAFELY
CARRIED OUT. ELECTRICAL CONTRACTOR SHALL BE TOTALLY RESPONSIBLE FOR HIS SAFE
PRACTICES AND OPERATIONS.
21. PROTECTIVE MEASURES SHALL BE TAKEN DURING DEMOLITION TO KEEP THE INTERIOR OF
THE REMAINING BUILDING WEATHERTIGHT. ANY OPENINGS IN THE BUILDING SHELL
RESULTING FROM THE DEMOLITION PROCESS SHALL BE PROMPTLY SEALED.
22. ANY ITEM INTENDED TO BE REMOVED BUT NOT SHOWN SHALL BE VERIFIED AND REMOVED
BY THE ELECTRICAL CONTRACTOR AT NO ADDITIONAL COST.
23. ALL EXISTING CONDUITS PENETRATING FLOORS OR WALLS NOT REQUIRED TO BE REMOVED
AND ALL NEW CONDUITS SHALL BE SEALED WITH FIRESTOPPING SEALANT.
24. SHIFT AND REROUTE (IF REQUIRED) ANY EXISTING CONDUIT WHICH MAY INTERFERE WITH
NEW CONSTRUCTION. ALL DEVICES REMAINING MUST BE LEFT IN A CLEAN AND OPERATING
CONDITION.
25. ALL BELOW SLAB CONDUIT BEING ABANDONED SHALL BE CUT FLUSH WITH FLOOR AFTER
CONDUCTOR REMOVAL AND GROUTED FLUSH WITH FINISHED FLOOR.
26. ALL DEMOLITION WORK SHALL BE PERFORMED IN AN ORDERLY FASHION WITHOUT ANY
DAMAGE TO EXISTING STRUCTURE AND SYSTEMS.
27. THE EC SHALL FURNISH AND INSTALL ADDITIONAL CONDUIT AND WIRE AS REQUIRED AND
EXTEND EXISTING CIRCUITING TO FIXTURES AND DEVICES WHICH REMAIN BUT WHICH MAY
BE AFFECTED BY EXISTING FIXTURES AND DEVICES BEING REMOVED AND/OR RELOCATED.
FULL EXTENT OF WORK REQUIRED SHALL BE FIELD VERIFIED.
GENERAL ELECTRICAL DEMOLITION NOTES:
(E) DENOTES EXISTING DEVICE/EQUIPMENT TO BE MAINTAINED.
(D&R) DENOTES EXISTING DEVICE/EQUIPMENT TO BE REMOVED IN ITS ENTIRETY
INCLUDING JUNCTION BOXES, CONDUITS AND CIRCUITRY, ETC. COMPLETE
BACK TO SOURCE OR NEXT ACTIVE DEVICE BEING MAINTAINED ON CIRCUIT.
(R&R) DENOTES EXISTING DEVICE/EQUIPMENT TO BE REMOVED AND RELOCATED IN
ITS ENTIRETY. MAINTAIN ALL BRANCH CIRCUIT WIRING, CONDUIT, ETC. AS
REQUIRED FOR RELOCATION TO NEW LOCATION (R) INDICATED ON "NEW
WORK" DRAWINGS.
(R) DENOTES NEW LOCATION OF REMOVED AND RELOCATED (R&R)
DEVICE/EQUIPMENT. DEVICE SHALL BE CLEANED PRIOR TO REINSTALLATION.
EXTEND/REWORK ALL BRANCH CIRCUITING TO NEW LOCATION AS REQUIRED
FOR PROPER OPERATION. NEW BRANCH CIRCUITING SHALL MATCH EXISTING
IN SIZE, TYPE, AND/OR MATERIAL.
(N) DENOTES NEW DEVICE/EQUIPMENT TO BE PROVIDED IN ITS ENTIRETY,
INCLUDING ALL FEEDER/BRANCH CIRCUIT WIRING, CONDUIT, ETC. AS
REQUIRED FOR COMPLETE AND OPERATIONAL INSTALLATION.
DEMOLITION / NEW WORK ANNOTATION LEGEND:
WHERE THE FOLLOWING WORDS / PHRASES ARE INDICATED ON THE ELECTRICAL DOCUMENTS,
THEY SHALL HAVE THE FOLLOWING MEANING:
• FURNISH - TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH EVERY
NECESSARY APPURTENANCE AND SUPPORT.
• INSTALL - TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY
OPERATION NECESSARY FOR PROPER INSTALLATION PER CODES AND MANUFACTURERS
REQUIREMENTS, TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE
PROPER LOCATION IN THE PROJECT.
• PROVIDE - FURNISH AND INSTALL.
• BY OTHERS / BY OTHER DIVISION / BY DIVISION ## CONTRACTOR - EQUIPMENT, DEVICE, ETC.
PROVIDED UNDER THE SCOPE OF THIS CONTRACT AND IS SHOWN ON DRAWINGS OTHER
THAN ELECTRICAL.
• NOT IN CONTRACT / N.I.C. - EQUIPMENT, DEVICE, ETC. NOT PROVIDED UNDER THE SCOPE OF
THIS CONTRACT, INCLUDING BUT NOT LIMITED TO A PREVIOUS OR CONCURRENT PHASE OF
WORK.
ELECTRICAL DEFINITIONS:
1. GROUNDING INSTALLATION SHALL COMPLY WITH OSHA AND THE NATIONAL ELECTRICAL
CODE, EXCEPT WHERE LOCAL CODE PREVAILS.
2. GROUNDING TO BE SUFFICIENT TO PROVIDE AN EFFECTIVE GROUND PATH BETWEEN THE
EQUIPMENT AND THE GROUND, OF NOT MORE THAN 5 OHMS FOR THE FOLLOWING:
A. NEUTRAL OF 120/208V AND 277/480V LIGHTING SYSTEMS
B. DATA/TELEPHONE SYSTEMS.
C. SMALL TRANSFORMER HOUSINGS (LOW VOLTAGE).
D. MOTOR FRAMES.
E. STEEL FABRICATED ELECTRICAL EQUIPMENT RACK ASSEMBLIES.
F. AT TWO POINTS FOR THE FOLLOWING EQUIPMENT:
a. ALL TRANSFORMERS
b. MAIN SWITCH GEAR
c. GENERATOR
G. STRUCTURAL STEEL COLUMN OF BUILDING.
H. FUEL DISPENSING EQUIPMENT AND TANKS.
3. COMPONENTS WHICH ARE INTRINSIC TO THE ELECTRICAL CONTROL AND/OR EQUIPMENT
PANEL SHALL BE CONSIDERED GROUNDED WHEN THE ENCLOSURE IS GROUNDED.
4. MINIMUM OF #12 COPPER GROUND WIRE TO BE RUN THROUGH ALL LIGHTING/POWER AND
SYSTEM DISTRIBUTION CONDUITS.
5. ALL SURFACES TO BE GROUNDED SHALL BE THOROUGHLY CLEANED TO BARE METAL
BEFORE ATTACHING GROUND CONNECTIONS.
6. WHEN STUBBING-UP GROUND WIRES AT BUILDING COLUMNS, MOTOR, FRAMES, ETC. STUB-
UP 3'-0" PIGTAIL MINIMUM ABOVE FINISHED GRADE UNLESS OTHERWISE NOTED. PROVIDE
MINIMUM OF 15'-0" PIGTAILS TO MISCELLANEOUS EQUIPMENT FROM BUILDING COLUMNS.
7. ALL GROUND CONNECTIONS SHALL BE EXOTHERMIC-WELD UNLESS OTHERWISE NOTED.
8. ALL EQUIPMENT GROUNDS SHALL BE TERMINATED WITH COMPRESSION FITTINGS AND
STAINLESS STEEL BOLTS OR IN PANEL GROUND BAR.
GENERAL GROUNDING NOTES:
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
PROJECT AREA. REFER TO
DRAWINGS ED-202 AND E-202.
SCHOOL
PARKING LOT
PARKING LOT
BUS LOOP
TRACK
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
E-201
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
SITE
ELECTRICAL
PLAN
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
SCALE: 1" = 50'-0"
SITE POWER PLAN
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
J
J
J
J
J
J
J
BOILER
07-102
MECHANICAL
07-101
GRAVEL
COURTYARD
(R&R) PCHP-1
PCHP-1
PCHP-2
SCHP-1
HM/2,4,6
HM/7,9,11
HM/1,3,5
(E) DP
(E) TLM
(E) HM
(E) LM
(E) PCHP-2
(E) PCHP-3
(E) SCHP-3(E) SCHP-1
(E) SCHP-2
LM/5
LM/7
DP/4
LM/1
LM/3
DP/3
G,WP
(E)
LM/10G,WP
(E)
LM/10
LM/10LM/10
(E)(E)
G,WPG,WP
(E) GENERATOR
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
ED-202
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
BUILDING 7
POWER
DEMOLITION
PLAN
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
1. FOR ANY WIRES THAT REMAIN IN JUNCTION BOXES, LABEL THE SOURCE AND CAP
WIRES.
2. IN AREAS OF DEMOLITION WHERE EXISTING BRANCH CIRCUITS ARE TO BE RE-
USED FOR NEW WORK, CAP ALL DISCONNECTED ELECTRICAL CIRCUITRY IN
JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS, WITHIN EXISTING WALLS, ETC.
AND MAINTAIN FOR EXTENSION.
3. REFER TO NEW WORK DRAWINGS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.
GENERAL DEMOLITION NOTES:
SHEET KEY NOTES:#
1. EXISTING MECHANICAL EQUIPMENT TO BE DISCONNECTED AND REPLACED.
MAINTAIN EXISTING BRANCH CIRCUIT WIRING TO BE RE-USED UNDER NEW
WORK.
2. EXISTING STARTER FOR PCHP-1 TO BE RELOCATED. INTERCEPT AND EXTEND
CONDUCTORS TO NEW LOCATION SHOWN ON SHEET E-202.
3. EXISTING CHILLERS TO BE DISCONNECTED AND REPLACED. DISCONNECT AND
REMOVE EXISTING BRANCH CIRCUIT WIRING BACK TO SOURCE. EXISTING
CONDUIT TO REMAIN AND BE RE-USED UNDER NEW WORK.
SCALE: 1/4" = 1'-0"
BUILDING 7 POWER DEMO PLAN
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
J
J
J
J
J
J
J
J
BOILER
07-102
MECHANICAL
07-101
GRAVEL
COURTYARD
PCHP-1
(E) DP
(E) TLM
(E) HM
HM/1,3,5
PCHP-2
HM/7,9,11
SCHP-1
HM/2,4,6
LM/1
LM/3
LM/5
LM/7
(E) LM
(R) PCHP-1
(E) PCHP-2
(E) PCHP-3
(E) SCHP-3
(E) SCHP-2
(E) SCHP-1
DP/3
CH
CH
DP/4
CU-1
LM/22,24
30AS/30AF
AC-1
m6
G,WP
LM/10
G,WP
(E)
LM/10
(E)
G,WP LM/10
G,WP
(E)
LM/10
(E)
G,WP LM/10
(E) GENERATOR
C P
WP
WP
C P
WP
WP
CU
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
E-202
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
BUILDING 7
POWER PLAN
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
1. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS,
OWNER FURNISHED EQUIPMENT, ETC. THAT REQUIRE ELECTRICAL CONNECTIONS
ARE SHOWN ON THEIR RESPECTIVE DISCIPLINE DRAWINGS. COORDINATE EXACT
LOCATIONS WITH RESPECTIVE CONTRACTORS AND/OR VENDORS PRIOR TO ANY
ROUGH-INS.
2. REVIEW AND COORDINATE WITH ALL TRADES' CONTRACT DOCUMENTS AND
CONTRACTORS TO DETERMINE SPECIFIC MOUNTING LOCATIONS FOR EQUIPMENT
WITH ELECTRICAL CONNECTIONS. COORDINATE EXACT MOUNTING LOCATIONS
WITH THE SPECIFIC TRADE.
3. MINIMUM CONDUCTOR SIZE FOR 277 VOLT BRANCH CIRCUITING SHALL BE #
12AWG. FOR 277 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 125 LINEAR
FEET A MINIMUM CONDUCTOR SIZE OF #10AWG SHALL BE PROVIDED FROM FIRST
JUNCTION BOX TO BRANCH CIRCUIT PANELBOARD. ASSOCIATED EQUIPMENT
GROUNDING CONDUCTOR SHALL ALSO BE INCREASED PER N.E.C. ARTICLE
250.122(B) REQUIREMENTS.
4. MINIMUM CONDUCTOR SIZE FOR 120 VOLT BRANCH CIRCUITS SHALL BE #12AWG.
FOR 120 VOLT BRANCH CIRCUITS WITH HOMERUNS OVER 75 LINEAR FEET, A
MINIMUM WIRE SIZE OF #10AWG SHALL BE PROVIDED FROM FIRST JUNCTION BOX
TO BRANCH CIRCUIT PANELBOARD. FOR 120 VOLT BRANCH CIRCUITS WITH
HOMERUN OVER 150 LINEAR FEET, A MINIMUM WIRE SIZE OF #8AWG SHALL BE
PROVIDED FROM FIRST JUNCTION BOX TO BRANCH CIRCUIT PANELBOARD.
ASSOCIATED EQUIPMENT GROUNDING CONDUCTOR SHALL ALSO BE INCREASED
PER N.E.C. ARTICLE 250.122(B) REQUIREMENTS.
5. AT A MINIMUM ALL BRANCH CIRCUITS SHALL CONTAIN 2#12AWG, #12 EG, 3/4"
CONDUIT UNLESS OTHERWISE INDICATED.
6. ALL BRANCH CIRCUITS SHALL BE RUN WITH AN INDIVIDUAL NEUTRAL WIRE.
BRANCH CIRCUITS SHALL NOT SHARE NEUTRAL WIRES.
7. RECEPTACLE BRANCH CIRCUITS MAY SHARE EQUIPMENT GROUND CONDUCTORS.
ALL SHARED EQUIPMENT GROUND CONDUCTORS SHALL BE #10 AWG MINIMUM.
8. ALL CONDUCTORS SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT
NUMBER(S) IN ALL CABINETS, JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES,
SPLICE OR TERMINATION POINTS, ETC.
9. A NEW TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL
PANELS INSTALLED OR MODIFIED UNDER THIS CONTRACT. NEW DIRECTORY
CARDS SHALL BE LOCATED ON THE INSIDE DOOR OF ASSOCIATED PANELS.
10. REFER TO ALL EQUIPMENT AND PANEL SCHEDULES FOR ADDITIONAL
INFORMATION.
POWER SHEET GENERAL NOTES:
SHEET KEY NOTES:#
1. CONNECT EXISTING BRANCH CIRCUIT WIRING TO NEW MECHANICAL
EQUIPMENT.
2. RELOCATE EXISTING STARTER FOR PCHP-1. MAINTAIN SERVICE CLEARENCE
REQUIREMENTS AS PER NEC.
3. PROVIDE NEW FEEDER CONDUCTORS TO SERVE CHILLER. EXISTING CONDUIT
SHALL BE RE-USED AND EXTENDED TO NEW EQUIPMENT. PROVIDE NEW
BRANCH CIRCUIT WIRING TO 120V ACCESSORY EQUIPMENT DEVICES, WIRE
EACH CIRCUIT WITH 2#12 & 1#12 EG IN EXISTING CONDUIT.
4. NOT USED.
5. CONNECTION TO CU-1. WIRE WITH 2#10 CU & 1#10 EG CU IN 3/4"C. PROVIDE
NEMA 4X STAINLESS STEEL FUSED DISCONNECT SWITCH.
6. CONNECT AC-1 TO ASSOCIATED CONDENSING UNIT CU-1. WIRE WITH 2#10 CU &
1#10 EG CU IN 3/4"C. COORDINATE CONTROL WIRING (THERMOSTAT WIRING,
ETC.) WITH MECHANICAL CONTRACTOR.
7. CONTRACTOR SHALL FIELD VERIFY CIRCUIT SERVING CHILLER YARD
RECEPTACLES. INTERCEPT AND EXTEND THIS CIRCUIT TO NEW GFCI,
WEATHER PROOF RECEPTACLE SERVING CU-1.
SCALE: 1/4" = 1'-0"
BUILDING 7 POWER PLAN
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
NOTES:
1. ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TO THE CENTERLINE OF DEVICES EXCEPT FIRE
ALARM A/V DEVICES.
2. NO WIRING DEVICES OR OUTLET BOXES SHALL BE MOUNTED BACK TO BACK.
3. ALL MOUNTING HEIGHTS SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON THIS DETAIL UNLESS NOTED
OTHERWISE.
4. FOR ALL ELEVATIONS (WHERE APPLICABLE), CASEWORK DETAILS, FIRE WALLS, SMOKE WALLS, LOCATION OF COUNTERTOP RECEPTACLES, LIGHTING FIXTURE SWITCHES, TELEPHONE OUTLETS, EQUIPMENT ROUGH-INS, HEADWALLS, ETC., SEE ARCHITECTURAL DRAWINGS. WHERE NO ARCHITECTURAL ELEVATIONS OR DETAILS OCCUR, CONTRACTOR SHALL USE MEANS AND METHODS AS WELL AS HIS/HER FIELD KNOWLEDGE TO SPOT
DEVICES IN BEST LOCATIONS FOR THE PROJECT.
5. ALL MOUNTING HEIGHTS SHALL COMPLY WITH ADA REQUIREMENTS:
A. GENERAL DEVICES: 15" MINIMUM, 48" MAXIMUM.
B. ABOVE COUNTER DEVICES: 44" MAXIMUM.
C. FIRE ALARM SIGNAL, SPEAKER, AND/OR LIGHT DEVICES: 80" MINIMUM, 96" MAXIMUM.
FIRE ALARM SIGNAL, SPEAKER,
OR LIGHT.
FIRE ALARM PULL STATION.
WALL TELEPHONES.
LIGHTING CONTROLS.
VOLUME CONTROLS.
DEVICES ABOVE
COUNTERTOP AND/OR
BACKSPLASH.
RECEPTACLES IN MECH/ELEC
SPACES AND ADJACENT TO
LAVATORIES.
RECEPTACLES BEHIND
DOMESTIC WASHERS
AND DRYERS.
GENERAL PURPOSE
RECEPTACLES.
DATA/VOICE OUTLETS.
RECEPTACLES FOR
DISHWASHERS AND
GARBAGE DISPOSALS.
DISCONNECT
SWITCHES
PANELBOARD
FINISHED FLOOR
(M A
X
IM
U M
EQUIPMENT
NAMEPLATE.
A S
R E
Q U
IR
E
D '-0
M
IN
RGS CONDUIT.
X" RGS ELBOW.
2'-0" RADIUS.
.010" THICK PIPE WRAPPING
PLASTIC TAPE WITH A
50% OVERLAY.X" PVC-SCHED-40 CONDUIT
FLOOR SLAB, PAD, OR GRADE
/2
(M
IN
IM
U
M
5" (MINIMUM)
NAME LOAD NAME: 1/2" LETTERING.
FEEDER: 4#2, #8 EG - 1 1/2"C.
TRIP / FUSE RATING: 100 AMPS
FEEDER SIZE: 1/8" LETTERING.
OCPD SIZE: 1/8" LETTERING.
NOTES:
1. REFER TO EQUIPMENT NAMEPLATE DETAIL
NOTES AND ELECTRICAL SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
/2
(M
IN
IM
U
M
5" (MINIMUM)
NORMAL SYSTEM SYSTEM DESCRIPTION: 1/8" LETTERING.
NAME EQUIPMENT NAME: 1/2" LETTERING.
VOLTAGE: 480Y/277V, 3Ø, 4W
FED FROM: "EQUIPMENT NAME" IN ROOM "####"
FEEDER: 4#2, #8 EG - 1 1/2"C.
STARTER SIZE: 3
SYSTEM VOLTAGE: 1/8" LETTERING.
EQUIPMENT "FED FROM": 1/8" LETTERING.
FEEDER SIZE: 1/8" LETTERING.
STARTER SIZE (WHERE APPLICABLE): 1/8" LETTERING.
NOTES:
1. REFER TO EQUIPMENT NAMEPLATE DETAIL
NOTES AND ELECTRICAL SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
FUSING / TRIP RATING: 100 AMPS OCPD SIZE (WHERE APPLICABLE): 1/8" LETTERING.
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:1
A
M
E-511
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
POWER
DETAILS AND
DIAGRAMS
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
1. DETAIL #1 SHALL BE UTILIZED FOR THE FOLLOWING EQUIPMENT:
A. SWITCHGEAR MAIN AND FEEDER BREAKERS.
B. SWITCHBOARD MAIN AND FEEDER BREAKERS.
C. DISTRIBUTION PANELBOARD MAIN AND FEEDER BREAKERS.
2. DETAIL #2 SHALL BE UTILIZED FOR THE FOLLOWING EQUIPMENT:
A. NON-FUSED DISCONNECT SWITCHES.
B. FUSIBLE DISCONNECT SWITCHES.
C. MOTOR STARTERS.
D. COMBINATION MOTOR STARTERS.
E. VARIABLE FREQUENCY DRIVES (VFD's).
3. REFER TO OWNER'S STANDARDS FOR VARIATIONS TO REQUIRED NAMEPLATE
INFORMATION AND FORMATTING.
4. TEXT INCLUDED IN BOLDED ITALICIZED TEXT INDICATES INFORMATION SPECIFIC
TO EACH PIECE OF EQUIPMENT.
5. NAMEPLATES SHALL BE ENGRAVED ACRYLIC OR MELAMINE WITH BEVELED EDGES.
6. FURNISH NAMEPLATE WITH SELF-ADHESIVE BACK OR PROVIDE TWO (2) STAINLESS
STEEL SCREWS TO SECURE NAMEPLATE:
A. SCREWS SHALL MAINTAIN 1/2" DISTANCE FROM LETTERING.
B. SCREWS SHALL NOT DEGRADE THE NEMA RATING OF THE EQUIPMENT
ENCLOSURE.
7. WHERE EQUIPMENT LISTED ABOVE IS FURNISHED OR PROVIDED BY OTHER
DIVISIONS AND CONNECTED OR INSTALLED BY THE ELECTRICAL CONTRACTOR,
THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE EQUIPMENT NAMEPLATE.
NAMEPLATE SHALL NOT COVER ANY FACTORY INSTALLED LABELING OR OTHER
EQUIPMENT INFORMATION / IDENTIFICATION.
8. NAMEPLATE BACKGROUND AND LETTER COLORING SHALL BE AS FOLLOWS:
A. NORMAL SYSTEMS: BLACK LETTERS ON A WHITE BACKGROUND.
B. ARTICLE 700 SYSTEMS (EMERGENCY, LIFE SAFETY, CRITICAL BRANCH, ETC.):
WHITE LETTERS ON A RED BACKGROUND.
C. ARTICLE 701 SYSTEMS (LEGALLY REQUIRED STAND-BY): WHITE LETTERS ON A
RED BACKGROUND.
D. ARTICLE 702 SYSTEMS (OPTIONAL STAND-BY): BLACK LETTERS ON YELLOW
BACKGROUND.
ELECTRICAL EQUIPMENT NAMEPLATE DETAIL NOTES:
SCALE: NONE
TYPICAL MOUNTING HEIGHTS
DETAIL
SCALE: NONE
TYPICAL CONDUIT TRANSITION PVC
TO RGS DETAIL
SCALE: NONE
TYPICAL FEEDER OCPD
NAMEPLATE DETAIL
SCALE: NONE
TYPICAL DISCONNECT NAMEPLATE
DETAIL
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
EXISTING DISTRIBUTION PANELBOARD 'DP'
1600 AMPS MLO 277/480V 3PH, 4W
400A 500A
PANEL 'HM'
400 MLO
500A
T-LM 30kVA
125A
PANEL 'LM'
100 MCB
SPACE
(200AF)
SPACE
(100AF)
SPD
INTEGRAL
CONTROL
PANEL
M
CH-1
INTEGRAL
CONTROL
PANEL
M
CH-2
SPD
60AT450A
TO CH-3 TO ATS
(E) 2 SETS OF 4 #
3/0 & 1#3EG IN 2"C.
2 SETS OF
3 -250 KCMIL
& 1#2EG IN
2 1/2"C.
#3/0
GEC
480V
208Y/ 120V
(E) 4 #3 & 1#8EG IN 1 1/4"C.
(E) 3 #8 & 1#
10EG IN 3/4"C.
2 SETS OF
3 -250 KCMIL
& 1#2EG IN
2 1/2"C.
1600A
GFCI
MV
480Y/ 277V
TO UTILITY
(E) 4 SETS OF
4-600KCMIL IN 4"C.
(E) 4 SETS OF
4-600KCMIL & 1#4/0EG
IN 4"C.
CH-1 AND CH-2 REPLACED UNDER THIS PROJECT.
CHILLERS FURNISHED BY MECHANICAL CONTRACTOR.
PANEL AFFECTED UNDER
THIS PROJECT.
PANEL AFFECTED UNDER
THIS PROJECT.
1 1
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:2
A
M
E-601
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
ELECTRICAL
ONE LINE
DIAGRAM
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE LINE VOLTAGE WIRING BETWEEN
CONTROL PANELS AND/OR VFD's AND THEIR CORRESPONDING MOTORS. CONTROL PANELS AND/OR VFD's AND MOTORS ARE PROVIDED BY MECHANICAL HVAC CONTRACTOR. COORDINATE EXACT LOCATION OF ALL CONTROL PANELS, VFD's
AND MOTORS AND THEIR REQUIREMENTS WITH MECHANICAL HVAC AND/OR
CONTROLS CONTRACTOR PRIOR TO ROUGH-IN.
ELECTRICAL ONE LINE SHEET GENERAL NOTES:
SCALE: NONE
PARTIAL ONE LINE DIAGRAM
SHEET KEY NOTES:#
1. PROVIDE AND INSTALL TWO (2) NEW 500AT/600AF BREAKERS. NEW BREAKERS
SHALL BE SQUARE D, L FRAME, FIT EXISTING EQUIPMENT, AND BE RATED FOR
42kAIC.
TAG ISSUED DATE
100% Construction Documents
2025.01.
No. 93581
STATE
OF
R
O
BE
RT
CHRACHO
L
L I C E N S E
F L O R I D
A
P R O F
E
SSIONAL EN
G
IN
E E R
Robert Chrachol, PE
93581
This item has been electronically signed and sealed by using a Digital Signature and date.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER OF RECORD:
LICENSE NUMBER:
EXPIRATION DATE:
1111 Superior Avenue, Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
54321
A
B
C
D
OSBORN PROJ NO
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
CLIENT PROJ NO
CHECKED BY
DRAWN BY
A u to d e s k D o c s
/P in e ll a s C o u n ty
O a k G ro v e M
S C h il le r R e p la c e m e n t/ J .0
-O a k G ro v e M
S C h il le r R e p l- E
L E
C -R
.r v t
/2
/2
:2
:2
A
M
E-711
OEC
OEC
PINELLAS
COUNTY
SCHOOLS
OAK GROVE
MIDDLE
SCHOOL
CHILLER
REPLACEMENT
ELECTRICAL
PANEL
SCHEDULES
J20241923.000
CLEARWATER, FL
Enter Name here
Enter Number here
Enter Date here
Enter Name here, P.E.
PANELBOARD SCHEDULE NOTES:
1. BRANCH CIRCUIT BREAKER(S) FEEDING FIRE ALARM AND/OR EMERGENCY
COMMUNICATIONS SYSTEMS SHALL BE IDENTIFIED AS REQUIRED BY THE LATEST
ADOPTED EDITION OF NFPA 72 ARTICLES 10.6.5.2.2 AND 10.6.5.2.3.
2. PROVIDE HACR RATED BREAKERS FOR ALL MECHANICAL EQUIPMENT.
3. PER N.E.C. ARTICLE 408.4(A) A NEW TYPED PANELBOARD DIRECTORY CARD SHALL
BE PROVIDED FOR ANY AND ALL PANELBOARDS PROVIDED/MODIFIED UNDER THIS
CONTRACT. NEW DIRECTORY CARDS SHALL BE LOCATED ON THE INSIDE DOOR
OF ASSOCIATED PANELS.
4. AT THE CONCLUSION OF WORK, ALL EXISTING CIRCUIT BREAKERS THAT ARE NOT
IN USE SHALL BE LABELED AS SPARE IN THE UPDATED TYPE WRITTEN
PANELBOARD DIRECTORY AND SHALL BE IN THE "OFF" POSITION.
5. NUMBERS IN "NOTES" COLUMN CORRESPOND TO NOTES LISTED AT THE BOTTOM
OF THE PANEL SCHEDULE.
6. ADDITIONAL REQUIREMENTS AT THE BOTTOM OF THE PANEL SCHEDULE APPLY TO
THE ENTIRE PANEL.
7. PANELBOARD SCHEDULES FOR EXISTING PANELBOARDS ARE BASED ON VISUAL
OBSERVATIONS IN THE FIELD. CONTRACTOR SHALL VERIFY ALL CIRCUITS
REQUIRED TO BE RE-WORKED AND/OR MODIFIED UNDER THIS CONTRACT.
A. NEW LOADS ARE IDENTIFIED BY BOLD FACE TYPE WITHIN THE "DESCRIPTION"
COLUMN.
B. EXISTING LOADS ARE IDENTIFIED BY NORMAL TYPE WITHIN THE "DESCRIPTION"
COLUMN.
C. FOR BOLD FACE TYPE WITHIN THE "TRIP" AND "POLE" COLUMNS, PROVIDE
NEW CIRCUIT BREAKER AS INDICATED. ALL NEW CIRCUIT BREAKERS SHALL
MATCH EXISTING CIRCUIT BREAKERS IN TYPE AND kAIC RATING.
D. FOR NORMAL TYPE WITHIN THE "TRIP" AND "POLE" COLUMNS, CIRCUIT
BREAKER IS EXISTING TO REMAIN.
EXISTING SQUARE D, MODEL QED-2 SWITCHBOARD.
Notes:
Total Est. Demand Current: 1057 A
MISC. 228071 VA 100.00% 228071 VA Total Conn. Current: 1057 A
RECEPTACLE 1380 VA 100.00% 1380 VA Total Est. Demand: 878428 VA
LIGHTING 2360 VA 100.00% 2360 VA Total Conn. Load: 878428 VA
HVAC 646620 VA 100.00% 646620 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 1057 A
Total Conn. Load: 878428 VA
8 SPD 3 60 A 60 A 0 VA
7 (SPACE - 200AF) 3 -- -- --
6 (SPACE - 100AF) 3 -- -- --
5 ATS EM 3 125 A 125 A 28600 VA
4 CH-2 3 600 A 500 A 249760 VA
3 CH-1 3 600 A 500 A 249760 VA
2 PANEL HM 3 400 A 400 A 203254 VA
1 CH-3 3 450 A 450 A 147087 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: PER SPECIFICATIONS MCB Rating: 2000 A
Mounting: SURFACE Wires: 4 Mains Rating: 2000 A
Supply From: Phases: 3 Mains Type: MLO
Location: MECHANICAL 07-101 Volts: 480Y/277V A.I.C. Rating: 42 KAIC
Switchboard: DP (EXISTING PANEL)
1. REDUNDANT EXISTING PUMP HWP-2 FOR HWP-1 (LOAD TAKEN AT 0%, ONLY 1 PUMP
OPE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .