The documents detail the HVAC upgrades for the Blennerhassett Mansion, a project for the West Virginia Division of Natural Resources. The comprehensive set of construction documents includes mechanical, electrical, plumbing, and demolition plans for a multi-floor renovation of the historic building. The project involves replacing existing heating and cooling systems with new heat pumps, furnaces, indoor and outdoor units, electric duct heaters, and associated electrical infrastructure across the basement, first floor, second floor, and attic levels.
The technical specifications outline the replacement of five heat pumps (HP-1 through HP-5) from Carrier, with corresponding furnaces and indoor units, along with two mini-split systems. The electrical plans show modifications to existing electrical panels, installation of new receptacles, and routing of power for the new HVAC equipment. The project requires detailed coordination of mechanical systems, electrical connections, and precise installation procedures, with specific attention to mounting, routing of linesets, and maintaining the architectural integrity of the historic mansion. The documents are prepared by Miller Engineering, Inc., with offices in Pennsylvania and West Virginia, and are designed to provide a comprehensive upgrade to the building's climate control systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PENNSYLVANIA OFFICE
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PHONE: (724) 966 - 5655
WEST VIRGINIA OFFICE
54 WEST RUN RD
MORGANTOWN, WV 26508
PHONE: (304) 291 - 2234
BLENNERHASSETT MANSION HVAC UPGRADES
MEI PROJECT #
DWG TITLE
GENERAL
G000 COVER PAGE
G100 OVERALL FLOOR PLANS
PLUMBING
P000 PLUMBING ABBREVIATIONS
P101 PLUMBING PLAN
MECHANICAL
M000 MECHANICAL ABBREVIATIONS
M001 DEMO MECHANICAL PLAN
M002 DEMO MECHANICAL PLAN
M003 DEMO MECHANICAL PLAN
M101 MECHANICAL PLAN
M102 MECHANICAL PLAN
M103 MECHANICAL PLAN
M104 MECHANICAL PLAN
M201 MECHANICAL SECTIONS
M401 ENLARGED MECHANICAL PLAN
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
ELECTRICAL
E000 ELECTRICAL ABBREVIATIONS
E001 DEMO BASEMENT ELECTRICAL FLOOR PLAN
E002 DEMO ELECTRICAL FLOOR PLAN
E003 DEMO ELECTRICAL FLOOR PLAN
E101 ELECTRICAL POWER PLAN
E102 ELECTRICAL POWER PLAN
E103 ELECTRICAL POWER PLAN
E601 ELECTRICAL SCHEDULE & DETAILS
PA OFFICE:
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
G100
OVERALL FLOOR
PLANS
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
3/16" = 1'-0"
BASEMENT 3/16" = 1'-0"
FIRST FLOOR
3/16" = 1'-0"
ATTIC
3/16" = 1'-0"
SECOND FLOOR
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS
SPECIFIED, AND REQUIRED BY CODE.
2. RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE
UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL
BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY
GRAVITY.
3. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO
UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.
PIPING IS TO BE "TOP DOWN".
4. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,
TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING
ACCESS ARE ACCESSIBLE.
5. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
6. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END
DRAINS VALVES AT THE BOTTOM OF ALL RISERS AND LOW
POINTS.
7. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE
OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS
(GREATER THAN 100 FEET) TO PERMIT DISASSEMBLY FOR
ALTERATIONS AND REPAIRS.
8. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY
OPERATION.
9. PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT w/
ACCESSIBLE STOPS.
10. PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE
SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTIONS, NEAR
THE BASE OF STACKS, EVERY 50'-0" IN HORIZONTAL RUN AND
ELSEWHERE AS INDICATED.
11. ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 4
INCHES AND SMALLER AND SHALL BE 4 INCHES FOR PIPE SIZES
LARGER THAN 4 INCHES.
12. ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS
IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE
OF VALVE IS REMOVED.
13. ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
14. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS
CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL
BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS
INDICATED ON THE DRAWINGS.
15. WASTE PIPING TO BE P40 PVC (BURIED OR CONCEALED), OR
CAST IRON NO-HUB (EXPOSED). VENT SANITARY PIPING AS
NECESSARY PER I.P.C. 2018. VENT THROUGH THE ROOF SUCH
THAT THE OUTSIDE AIR INTAKE IS MIN. OF 10'-0" FROM VENT.
16. FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,
FIXTURE PLACEMENT, ROUTING, ETC. IS THE RESPONSIBILITY OF
THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING. VERIFY ALL FIELD CONDITIONS AND
MEASUREMENTS PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER TRADES. COORDINATE ALL MOUNTED DEVICES w/ ALL
OTHER TRADES PRIOR TO INSTALLATION. FIRESTOP ALL
PENETRATIONS OF FIRE WALL (SEE ARCH. PLANS) AND FLOORS.
17. ALL WORK TO MEET REQUIREMENTS OF CURRENT
INTERVENTIONAL PLUMBING CODE, INTERNATIONAL
MECHANICAL CODE, STATE AND LOCAL CODES AND
REQUIREMENTS AND INTERNATIONAL FUEL GAS CODE.
PLUMBING NOTES
L
--------------------A------------------------------------------------------------------------------------
AAV AUTOMATIC AIR VENT
ABV ABOVE
AD ACCESS DOOR
ADA AMERICANS WITH DISABLITIES ACT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AP ACCESS PANEL
APPROX APPROXIMATELY
ASSOC ASSOCIATED
ASSY ASSEMBLY
ATC AUTOMATIC TEMPERATURE CONTROL
AUTO AUTOMATIC
AUX AUXILIARY
AV AIR VENT
AVG AVERAGE
AWT AVERAGE WATER TEMPERATURE
---------------B----------------------------------------------------------------------------------------
BB BASEBOARD
BC BALANCING COCK
BD BLOW DOWN
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BHP BRAKE HORESPOWER
BLDG BUILDING
BLR BOILER
BLW BELOW
BO BLOW OFF
BTM BOTTOM
BOP BOTTOM OF PIPE
BTUH BRITISH THERMAL UNIT PER HOUR
BV BALL VALVE
---------------C---------------------------------------------------------------------------------------
CA COMPRESSED AIR
CAP CAPACITY
CCW COUNTER CLOCKWISE
CDL CONDENSATE DRAIN LINE
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CHKV CHECK VALVE
CHWR CHILLED & HOT WATER RETURN
CHWS CHILLED & HOT WATER SUPPLY
CHWS&R CHILLED & HOT WATER SUPPLY AND RETURN
CIRC CIRCULATING
CI CAST IRON
CIRC CIRCULATING
CKT CIRCUIT
CLG CEILING
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
C/O CLEAN OUT
COL COLUMN
COMB COMBINATION
COMP COMPRESSOR
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CONST CONSTRUCTION
COP COEFFICIENT OF PERFORMANCE
CORR CORRIDOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
Cv COEFFICIENT, VALVE FLOW
CW COLD WATER/CLOCKWISE
CWFT CONDENSER WATER FROM TOWER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CWS&R CHILLED WATER SUPPLY AND RETURN
CWTT CONDENSER WATER TO TOWER
---------------D----------------------------------------------------------------------
D DEEP
Db DRY BULB TEMPERATURE(ºF)
DCO DOUBLE CLEAN OUT
DEMO DEMOLISH
DEPT DEPARTMENT
DIA DIAMETER
DIAG DIAGRAM
DISCH DISCHARGE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DN DOWN
DP DIFFERENTIAL PRESSURE
DPT DEW POINT TEMPERATURE(ºF)
DR DRAIN
DWG DRAWING
DWH DOMESTIC WATER HEATER
DX DIRECT EXPANSION
----------------E----------------------------------------------------------------------
EA EACH
EC ELECTRICAL CONTRACTOR
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
ENCL ENCLOSURE
ENT ENTERING
EP END PANEL/EXPLOSION PROOF
EQUIP EQUIPMENT
ER ECCENTRIC REDUCER(BOTTOMS FLAT)
ESP EXTERNAL STATIC PRESSURE
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATUR(ºF)
----------------F----------------------------------------------------------------------
ºF FAHRENHEIT
FA FREE AREA
FB FREE BLOW
F&T FLOAT AND THERMOSTATIC TRAP
FC FLEXIBLE CONNECTION
FCD FLOW CONTROL DEVICE
FCO FLOOR CLEAN OUT
FCU FAN COIL UNIT
FD FIRE DAMPER/FLOOR DRAIN
FDN FOUNDATION
FF FOULING FACTOR
FIN FINISHED
FLA FULL LOAD AMPS
FLG FLANGE
FLR FLOOR
FNL FUNNEL
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOS&R FUEL OIL SUPPLY AND RETURN
FOV FUEL OIL VENT
FPB FAN POWERED BOX
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FIN-TUBE/FEET
FTG FITTING
FURN FURNISH
FV FACE VELOCITY
FW FEED WATER
----------------G----------------------------------------------------------------------
G GAS
GALV GALVANIZED
GA GAUGE, GAGE
GC GENERAL CONTRACTOR
GCWR GLYCOL CHILLED WATER RETURN
GCWS GLYCOL CHILLED WATER SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GLV GLOBE VALVE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRAV GRAVITY
GRV GRAVITY ROOF VENTILATOR
GV GATE VALVE
----------------H----------------------------------------------------------------------
H HEIGHT
HB HOSE BIBB
HC HEATING CONTRACTOR;
HANICAPPED
HD HEAD/HUB DRAIN
HG MERCURY
HGR HANGER
HP HORSEPOWER/HEAT PUMP
HORIZ HORIZONTAL
HPD HIGH PRESSURE DRIP
HPR HIGH PRESSURE RETURN
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HUH HORIZONTAL UNIT HEATER
HV HIGH VELOCITY
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HW HOT WATER
HWBG HOT WATER BELOW GRADE
HWOH HOT WATER OVER HEAD
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HWS&R HOT WATER SUPPLY AND
RETURN
----------------I----------------------------------------------------------------------
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCHES
INV INVERT
IN-WG INCHES-WATER GAGE
INSUL INSULATION
IPS IRON PIPE SIZE
IVS ISOLATION VALVE STATION
IW INDIRECT WASTE
----------------J----------------------------------------------------------------------
JT JOINT
----------------K ---------------------------------------------------------------------
KS KITCHEN SINK
----------------L----------------------------------------------------------------------
L LENGTH
LAV LAVATORY
LBS POUNDS
LBS/HR POUNDS PER HOUR
LF LINEAR FEET
LP LOW PRESSURE
LPD LOW PRESSURE DRIP
LPR LOW PRESSURE RETURN
LPG LOW PETROLEUM GAS
LPS LOW PRESSURE STEAM
LV LOW VELOCITY
LVG LEAVING
LWCO LOW WATER CUTOFF
LWT LEAVING WATER
TEMPERATURE(ºF)
----------------M----------------------------------------------------------------------
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSAND BTUH
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFG MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MPD MEDIUM PRESSURE DRIP
MPR MEDIUM PRESSURE RETURN
MPS MEDIUM PRESSURE STEAM
MS MINI-SPLIT SYSTEM
MTD MOUNTED
MTG MOUNTING
MTL METAL
MTR MOTOR
MWT MEAN WATER TEMPERATURE(ºF)
----------------N----------------------------------------------------------------------
N NORTH
N/A NOT APPLICABLE
NC NORMALLY CLOSED; NOISE CRITERIA
NEG NEGATIVE
NIC NOT IN CONTRACT
NM NONMETALLIC
NMAG NONMAGNETIC
NO NORMALLY OPEN
No NUMBER
NOM NOMINAL
NORM NORMAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
NWL NORMAL WATER LEVEL
----------------O----------------------------------------------------------------------
OA OVERALL; OUTSIDE AIR
OC ON CENTER
OCC OCCUPANCY
OCPD OVERCURRENT PROTECTION DEVICE
OD OUTSIDE DIAMETER; OUTSIDE DIMENSION
ODS OXYGEN DEPRIVATION SENSOR
OF/CI OWNER FURNISHED / CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED / OWNER INSTALLED
OFD OVER FLOW DRAIN
OH OVERHEAD
OPER OPERATED
OPP OPPOSITE
OPT OPTIONAL; OPTIMUM
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSV OIL SAFETY VALVE
OUT OUTLET
OVC OVERCURRENT
OVF OVERFLOW
OZ OUNCE
----------------P----------------------------------------------------------------------
P PUMP
PC PLUMBING CONTRACTOR
PD PRESSURE DROP/PUMP
PE PNEUMATIC - ELECTRIC
PG PRESSURE DROP/PUMP DISCHARGE
PH PHASE
PLBG PLUMBING
PNL PANEL
PR PANEL RADIATOR
PRESS PRESSURE
PRV POWER ROOF VENTILATOR/PRESSURE REDUCING
VALVE
PS PIPE SUPPORT
PSI POUND PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAGE
PT PRESSURE/TEMPERATURE TAP
PTAC PACKAGED TERMINAL AIR CONDITIONER
PVC POLYVINYL CHLORIDE
----------------Q----------------------------------------------------------------------
QTY QUANTITY
----------------R----------------------------------------------------------------------
RA RELIEF/RETURN AIR
RAD RADIATOR
RAF RETURN AIR FIXTURES
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED/RECEIVED
REFRIG REFRIGERANT
REG REGISTER
REINF REINFORCED
REQD REQUIRED
RET RETURN
REV REVISION
RF RETURN/RELIEF FAN
RH REHEAT COIL
RHG REFRIGERANT HOT
RL REFRIGERANT LIQUID
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RV RELIEF VALVE
RWC RAIN WATER CONDUCTOR
----------------S----------------------------------------------------------------------
SA SUPPLY AIR
SCH SCHEDULE
SDPR SMOKE DAMPER
SENS SENSIBLE
SEP SEPARATOR
SF SUPPLY FAN
SHT SHEET
SK SINK
SP STATIC PRESSURE (INCHES OF WATER)
SPEC SPECIFICATION
SPGR SPECIFIC GRAVITY
SQ SQUARE
SQFT SQUARE FOOT
SS STAINLESS STEEL UNIT
STAT STATIC
STD STANDARD
STL STEEL
STR STRAINER
SUP SUPPLY
SV SAFETY VALVE
SW SWITCH
----------------T----------------------------------------------------------------------
TA THROW AWAY
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TDV TRIPLE DUTY VALVE
TEMP TEMPERATURE
TH THERMOMETER
THK THICK
TK TANK
TMV THRTMOSTATIC MIXING VALVE
TOT TOTAL
TP TRAP PRIMER/TRAP PRIMER SUPPLY
TRANS TRANSITION
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
----------------U----------------------------------------------------------------------
UC UNDERCUT
UF UNDER FLOOR
UG UNDERGROUND
UH UNIT HEATER
UR URINAL
----------------V----------------------------------------------------------------------
V VOLTAGE/VALVE/VENT
VAC VACUUM
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VFS VENTURI FLOW STATION
VOL VOLUME
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THROUGH ROOF
----------------W----------------------------------------------------------------------
W WIDTH
W/ WITH
W/O WITHOUT
WA WATER HAMMER ARRESTER
Wb WET BULB TEMPERATURE(ºF)
WC WATER COLUMN/WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAUGE
WH WALL HEATER
WL WATER LEVEL
WP WEATHERPROOF
WT WEIGHT
----------------Y----------------------------------------------------------------------
YCO YARD CLEANOUT
----------------Z----------------------------------------------------------------------
Z ZONE
ZCV ZONE CONTROL VALVE
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
P000
PLUMBING
ABBREVIATIONS
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
PLUMBING ABBREVIATIONS
PLUMBING PIPING SYSTEM LEGEND
ABBREVIATION SYSTEM TYPE
SAN SANITARY
N O
D
E S
C R
IP
T
IO
N
D A
T E
F-3
F-4
IDU-2
IDU-1F-2
F-1
4"ø SAN
INSTALL 115V LITTLE GIANT VCMA-15 SERIES CONDENSATE PUMP(TYP-ALL)
2" ø
SAN
2" ø
SAN
2" ø
SAN
3/8" plastic tubing (TYP)
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
PLUMBING SYSTEMS AS INDICATED ON THE DRAWING, AS
SPECIFIED, AND REQUIRED BY CODE.
2. RUN ALL SOIL WASTE AND VENT PIPING WITH 2% MIN. GRADE
UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL
BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY
GRAVITY.
3. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO
UNDERSIDE OF SLAB w/ SPACE FOR INSULATION IF REQUIRED.
PIPING IS TO BE "TOP DOWN".
4. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,
TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING
ACCESS ARE ACCESSIBLE.
5. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
6. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END
DRAINS VALVES AT THE BOTTOM OF ALL RISERS AND LOW
POINTS.
7. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE
OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS
(GREATER THAN 100 FEET) TO PERMIT DISASSEMBLY FOR
ALTERATIONS AND REPAIRS.
8. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY
OPERATION.
9. PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT w/
ACCESSIBLE STOPS.
10. PROVIDE CLEANOUTS IN SANITARY AND STORM DRAINAGE
SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTIONS, NEAR
THE BASE OF STACKS, EVERY 50'-0" IN HORIZONTAL RUN AND
ELSEWHERE AS INDICATED.
11. ALL CLEANOUTS SHALL BE FULL SIZE OF PIPE FOR PIPE SIZES 4
INCHES AND SMALLER AND SHALL BE 4 INCHES FOR PIPE SIZES
LARGER THAN 4 INCHES.
12. ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE REMAINS
IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE
OF VALVE IS REMOVED.
13. ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
14. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS
CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL
BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS
INDICATED ON THE DRAWINGS.
15. WASTE PIPING TO BE P40 PVC (BURIED OR CONCEALED), OR
CAST IRON NO-HUB (EXPOSED). VENT SANITARY PIPING AS
NECESSARY PER I.P.C. 2018. VENT THROUGH THE ROOF SUCH
THAT THE OUTSIDE AIR INTAKE IS MIN. OF 10'-0" FROM VENT.
16. FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,
FIXTURE PLACEMENT, ROUTING, ETC. IS THE RESPONSIBILITY OF
THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING. VERIFY ALL FIELD CONDITIONS AND
MEASUREMENTS PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER TRADES. COORDINATE ALL MOUNTED DEVICES w/ ALL
OTHER TRADES PRIOR TO INSTALLATION. FIRESTOP ALL
PENETRATIONS OF FIRE WALL (SEE ARCH. PLANS) AND FLOORS.
17. ALL WORK TO MEET REQUIREMENTS OF CURRENT
INTERVENTIONAL PLUMBING CODE, INTERNATIONAL
MECHANICAL CODE, STATE AND LOCAL CODES AND
REQUIREMENTS AND INTERNATIONAL FUEL GAS CODE.
PLUMBING NOTES
1. INSTALL 2" REDUCING 45 DEG TEE. INSTALL 2" TRAP &
ROUTE 3/8"' TUBING FOR CONDENSATE DRAINS TO 2"
TRAP.
SHEET NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
P101
PLUMBING PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
3/8" = 1'-0"
BASEMENT SANITARY PLAN
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
--------------------SYMBOLS------------------------------------------------------------------------
# NUMBER
& AND
º DEGREES
ºF DEGREES FAHRENHEIT
--------------------A------------------------------------------------------------------------------------
AAV AUTOMATIC AIR VENT
ABV ABOVE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATELY
AUX AUXILIARY
AVG AVERAGE
---------------B----------------------------------------------------------------------------------------
BFV BUTTERFLY VALVE
BH BASEBOARD HEATER
BHP BRAKE HORESPOWER
BLR BOILER
BTUH BRITISH THERMAL UNIT PER HOUR
BV BALL VALVE
---------------C---------------------------------------------------------------------------------------
CA COMPRESSED AIR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CHKV CHECK VALVE
CIRC CIRCULATING
CI CAST IRON
CKT CIRCUIT
CMU CONCRETE MASONARY UNIT
C/O CLEAN OUT
CON CONDENSATE
CONT CONTINUATION
CT COOLING TOWER
CU CONDENSING UNIT
---------------D----------------------------------------------------------------------
DIA DIAMETER
DWG DRAWING
DWH DOMESTIC WATER HEATER
----------------E----------------------------------------------------------------------
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE(ºF)
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EXH EXHAUST
EXIST EXISTING
EWT ENTERING WATER TEMPERATUR(ºF)
----------------F----------------------------------------------------------------------
ºF FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER/FLOOR DRAIN
FLA FULL LOAD AMPS
FLR FLOOR
FO FLAT OVAL
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET
----------------G----------------------------------------------------------------------
GAS NATURAL GAS
GALV GALVANIZED
GA GAUGE
GC GENERAL CONTRACTOR
GLV GLOBE VALVE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GATE VALVE
----------------H----------------------------------------------------------------------
HCWL HYDRONIC CHILLED WATER LOOP
HCWR HYDRONIC CHILLED WATER RETURN
HCWS HYDRONIC CHILLED WATER SUPPLY
HHWL HYDRONIC HOT WATER LOOP
HHWR HYDRONIC HOT WATER RETURN
HHWS HYDRONIC HOT WATER SUPPLY
HORIZ HORIZONTAL
HP HORSEPOWER/HEAT PUMP
HR HOUR
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HZ HERTZ
----------------I----------------------------------------------------------------------
ID INSIDE DIAMETER
IN INCHES
INV INVERT
----------------J----------------------------------------------------------------------
JB JUNCTION BOX
----------------K----------------------------------------------------------------------
KW KILOWATT
KWH KILOWATT HOUR
----------------L----------------------------------------------------------------------
LAT LEAVING AIR TEMPERATURE(ºF)
LBS POUNDS
LBS/HR POUNDS PER HOUR
LF LINEAR FEET
LP LIQUID PROPANE
LV LOUVER
LVG LEAVING
LWT LEAVING WATER TEMPERATURE(ºF)
----------------M----------------------------------------------------------------------
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIUM
MBH THOUSAND BTUH
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MS MINI-SPLIT SYSTEM
----------------N----------------------------------------------------------------------
N/A NOT APPLICABLE
NC NORMALLY CLOSED; NOISE CRITERIA
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
----------------O----------------------------------------------------------------------
OA OUTSIDE AIR
OC ON CENTER
OCC OCCUPANCY
OD OUTSIDE DIAMETER
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSV OIL SAFETY VALVE
OZ OUNCE
----------------P----------------------------------------------------------------------
P PUMP
PC PLUMBING CONTRACTOR
PNL PANEL
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAGE
PTAC PACKAGED TERMINAL AIR CONDITIONER
----------------Q----------------------------------------------------------------------
QTY QUANTITY
----------------R----------------------------------------------------------------------
RA RETURN AIR
RAD RADIATOR
RCP RADIANT CEILING PANEL
REFRIG REFRIGERANT
REQD REQUIRED
REV REVISION
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RV RELIEF VALVE
----------------S----------------------------------------------------------------------
SA SUPPLY AIR
SCH SCHEDULE
SD SMOKE DAMPER
SENS SENSIBLE
SP STATIC PRESSURE (INCHES OF WATER)
SPEC SPECIFICATION
SQ SQUARE
SQFT SQUARE FOOT
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
----------------T----------------------------------------------------------------------
T THERMOSTATE
TA TRANSFER AIR
TCV TEMPERATURE CONTROL VALVE
TDV TRIPLE DUTY VALVE
TEMP TEMPERATURE
TOT TOTAL
TRANS TRANSITION
TSTAT THERMOSTAT
TV TURNING VANES
TYP TYPICAL
----------------U----------------------------------------------------------------------
UH UNIT HEATER
UV UNIT VENTILATOR
----------------V----------------------------------------------------------------------
VOLTS VOLTAGE
VA VOLT AMPERES
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VOLTS VOLTAGE
VRF VARIABLE REFRIGERANT FLOW
VVT VARIABLE VOLUME AND TEMPERATURE
----------------W----------------------------------------------------------------------
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WT WEIGHT
----------------Z----------------------------------------------------------------------
Z ZONE
ZCV ZONE CONTROL VALVE
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M000
MECHANICAL
ABBREVIATIONS
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
MECHANICAL ABBREVIATIONS
ANNOTATION STYLE DUCTWORK SHAPE
24" x 12" RECTANGULAR
24" ø ROUND
24" / 12" FLAT OVAL
DUCTWORK SHAPE LEGEND
DUCT SYSTEM LEGEND
ABBREVIATION SYSTEM NAME
OA OUTDOOR AIR
RA RETURN AIR
SA SUPPLY AIR
TA TRANSFER AIR
N O
D
E S
C R
IP
T
IO
N
D A
AHU-4
AHU-3
A H
U -2
DEMO CONNECTING DUCT
FOR RECONNECTION
DEMO CONNECTING DUCT
FOR RECONNECTION
DEMO CONNECTING DUCT
FOR RECONNECTION
AHU-1
DEMO CONNECTING DUCT
FOR RECONNECTION
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M001
DEMO MECHANICAL
PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
3/8" = 1'-0"
BASEMENT MECHANICAL DEMO PLAN
DEMO HEAT PUMP, REFRIGERANT PIPING, AND PAD. MAKE SMOOTH WITH EXISTING CONCRETE.
DEMO HEAT PUMP, REFRIGERANT PIPING, AND PAD. MAKE SMOOTH WITH EXISTING CONCRETE.
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M002
DEMO MECHANICAL
PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
1/4" = 1'-0"
FIRST FLOOR MECHANICAL DEMO PLAN
AHU-5
DEMO CONNECTING DUCT
FOR RECONNECTION.
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M003
DEMO MECHANICAL
PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
3/8" = 1'-0"
ATTIC MECHANICAL DEMO PLAN
M201
11"x16" SA
11"x19" SA
M201
16"x12" RA
M201
F-1
F-2
F-3
F-4
IDU-1
IDU-2
M201
DIG AND POUR 6"
HOUSEKEEPING PAD. PAD TO
EXTEND BEYOND FOOTPRINT
OF FURNACE/COLD AIR BOOT
FITTING 6" ON EACH SIDE. TOP
OF PAD TO BE FLUSH W/
HIGHEST ADJACENT GRADE.
SET CONDENSATE PUMP ON
PAD. (TYPICAL FURNACE 1-4)
INSTALL (7) 3" PVC SLEEVES, EXTEND TO MECHANICAL COURTYARD. EXCAVATE AS NECESSARY.
16"x16" RA
"x
S A
"x
R A
"x
R A
"x
S A
RE-USE EXISTING CHASE TO
ROUTE LINESETS TO F-5 IN ATTIC.
FROM ODU-1
FROM HP-2
FROM HP-4
FROM ODU-2
FROM HP-1
FROM HP-3
FROM HP-5
LINESETS SHOWN ARE DIAGRAMMATIC IN NATURE.
CONTRACTOR TO FIELD VERIFY ROUTING & CONFIRM
DISTANCES FOR LINESET SIZING PRIOR TO
INSTALLING.
EDH-2
EDH-4
EDH-3
EDH-1
CONTINUED ON M102
1. PLACE FURNACE F-1 ON 24"X26" SHEET METAL BOXED
FURNACE KIT WITH A 20"X20" RETURN COLD AIR BOOT
DUCT FITTING TO CONNECT TO THE SHEET METAL
BOXED FURNACE KIT. INCLUDE PLENUM SUPPLY KIT
FITTING TO CONNECT TO EXISTING 24"X18" S.A.
DUCTWORK.
2. PLACE FURNACE F-2 ON 22"X24" SHEET METAL BOXED
FURNACE KIT WITH A 20"X20" RETURN COLD AIR BOOT
DUCT FITTING TO CONNECT TO THE SHEET METAL
BOXED FURNACE KIT. INCLUDE PLENUM SUPPLY KIT
FITTING TO CONNECT TO EXISTING 22"X15" S.A,
DUCTWORK.
3. PLACE FURNACE F-3 ON 24"X24" SHEET METAL BOXED
FURNACE KIT WITH A 16"X12" RETURN COLD AIR BOOT
DUCT FITTING TO CONNECT TO THE SHEET METAL
BOXED FURNACE KIT.
4. PLACE FURNACE F-4 ON 24"X24" SHEET METAL BOXED
FURNACE KIT WITH A 16"X16" RETURN COLD AIR BOOT
DUCT FITTING TO CONNECT TO THE SHEET METAL
BOXED FURNACE KIT.
SHEET NOTES
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M101
MECHANICAL PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
3/8" = 1'-0"
BASEMENT MECHANICAL PLAN
DUCT SYSTEM LEGEND
ABBREVIATION SYSTEM NAME
OA OUTDOOR AIR
RA RETURN AIR
SA SUPPLY AIR
TA TRANSFER AIR
M401
HP-1
HP-3
HP-5HP-4
HP-2
ODU-1
ODU-2
RACK LINESETS ON VERTICAL UNISTRUT ALONG WALL.
T
T
THERMOSTAT TO CONTROL F-2/HP-2 INSTALLED IN SAME
LOCATION AS EXISTING. VERIFY FINAL LOCATION IN FIELD.
THERMOSTAT TO CONTROL F-1/HP-1 INSTALLED IN SAME
LOCATION AS EXISTING. VERIFY FINAL LOCATION IN FIELD.
RACK LINESETS ON
VERTICAL UNISTRUT
ALONG WALL.
FOR OUTDOOR UNITS, MOUNT
ALL TO 16" GROUND STANDS
(TYP).
CONTINUED ON M101
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
4. CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
5. ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
6. CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
7. PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
8. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
9. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
11. COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
12. LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
14. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
15. ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
17. SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
18. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
19. PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
20. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M102
MECHANICAL PLAN
14 AUG 24
TRT
TWT
24008
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
BLENNERHASSETT
MANSION HVAC
UPGRADES
N O
D
E S
C R
IP
T
IO
N
D A
T E
1/4" = 1'-0"
FIRST FLOOR MECHANICAL PLAN
DUCT SYSTEM LEGEND
ABBREVIATION SYSTEM NAME
OA OUTDOOR AIR
RA RETURN AIR
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
2. SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
3. ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE…