2023-12-19 West Bastion Dwgs 360-B1360-010.pdf
PDF 4 MB Posted
- Solicitation number
- 53196
- Issued by
- Hampton City, Virginia
About this file
This document is related to a state and local contract opportunity for the West Bastion Visitor Experience Enhancement Project issued by the Fort Monroe Authority (FMA) in Virginia. The project involves the selective removal of non-historic and non-character defining masonry infill at two communication arches within the West Bastion tunnel and replacing it with a clear glazing system to improve visitor interpretation of the space. Additionally, the project includes the removal and reinstallation of historic brick pavers within the Casemate Museum and the passageway, the installation of new linear up-lighting, and the removal of existing lighting and power circuitry. The work must comply with the Fort Monroe Historic Preservation Manual, the Secretary of the Interior's Standards for the Treatment of Historic Properties, and all applicable state and local codes. Qualified contractors will be invited to submit a sealed bid on the project by separate invitation for bid. Building 20 is a contributing element to the Fort Monroe National Historic Landmark District and the National Register of Historic Places.
The project is located within the City of Hampton, Virginia. Funding requirements and sources are not specified in the document. No information is provided regarding set asides, incumbents, or the current contract environment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| dgs-30-168_08-20_co-16 (2).docx | DOCX document | |
| SCC Registration Info Form.docx | DOCX document | |
| 2023-12-19 West Bastion Project Manual.pdf | ||
| dgs-30-172_04-15_co-16-crosswalk-of-firm-and-key-personnel-experience (1).xlsx | XLSX spreadsheet | |
| RFx ID 53196.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. BUILDING 20 IS A CONTRIBUTING ELEMENT TO THE FORT MONROE NHL AND NRHP DISTRICTS. ALL WORK MUST BE DONE
IN ACCORDANCE WITH THE FORT MONROE HISTORIC PRESERVATION MANUAL AND DESIGN STANDARDS. THE WORK
SHALL ALSO COMPLY WITH THE SECRETARY OF THE INTERIOR’S STANDARDS FOR THE TREATMENT OF HISTORIC
PROPERTIES. ANY DEVIATIONS IN THE WORK FROM THESE CONTRACT DOCUMENTS MUST BE APPROVED BY THE
ARCHITECT AND THE FORT MONROE HISTORIC PRESERVATION OFFICER (FMHPO) PRIOR TO COMMENCING WITH THE
WORK IN QUESTION.
2. THESE DOCUMENTS REPRESENT THE CONDITIONS OF THE SITE AT THE TIME OF THEIR PREPARATION AND ARE BASED
ON FIELD OBSERVATIONS AND HISTORICAL DOCUMENTS PROVIDED BY THE FMHPO. THE FMA HAS MAINTAINED THESE
CONDITIONS TO THE GREATEST EXTENT POSSIBLE. ANY DISCREPANCY IN THE DOCUMENTS AND THE FIELD
CONDITIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT.
3. PRIOR TO COMMENCING WITH THE WORK, THE CONTRACTOR SHALL PHOTOGRAPHICALLY DOCUMENT THE EXISTING
CONDITIONS.
4. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO FABRICATION OF COMPONENTS TO BE INCLUDED
IN THE WORK. DIMENSIONS PROVIDED ON THE CONTRACT DOCUMENTS ARE TO FACE OF MASONRY, HOWEVER, DUE TO
THE ROUGH FACE OF THE STONE MASONRY, THE DIMENSIONS ON THE CONTRACT DOCUMENTS MAY VARY SLIGHTLY.
5. THE LOCATION OF EXISTING UTILITIES PASSING THROUGH THE POSTERN GATE HAVE BEEN IDENTIFIED ON THE
DRAWINGS FROM A UTILITY SURVEY PROVIDED BY THE FMA AND MAY NOT ACCURATELY REPRESENT THE ACTUAL FIELD
CONDITIONS. THE CONTRACTOR SHALL REVIEW OWNER DOCUMENTS AND HAS THE RESPONSIBILITY TO VERIFY
LOCATIONS AND DEPTHS IN THE FIELD, AND TO COORDINATE NEW WORK WITH THE EXISTING UTILITIES.
6. TEMPORARY PROTECTION SHALL BE PROVIDED FOR THE TWO ARCHED OPENINGS TO THE CASEMATE MUSEUM.
TEMPORARY PROTECTION SHALL BE WEATHERPROOF AND PROVIDE A SECURE BARRIER TO PROTECT THE MUSEUM
AND ITS CONTENTS. CONSTRUCTION OF TEMPORARY PROTECTION SHALL BE SUCH THAT ITS ERECTION AND REMOVAL
DOES NOT DAMAGE THE HISTORIC BUILDING MATERIALS.
7. ANY DISRUPTION TO THE CASEMATE MUSEUM’S OPERATIONS SHALL BE COORDINATED WITH THE FMA AND MUSEUM
STAFF. AMPLE NOTICE OF THE DISRUPTION SHALL BE PROVIDED TO ALLOW THE MUSEUM TO ACCOMMODATE THE
WORK.
8. THE POSTERN GATE IS A PUBLIC PASSAGE AND TO THE GREATEST EXTENT POSSIBLE, EFFORTS SHALL BE MADE TO
RETAIN THE PASSAGEWAY AND SAFE PASSAGE OF THE PUBLIC DURING THE WORK. CLOSURE OF THE POSTERN GATE
FOR FINITE PERIODS OF TIME SHALL BE PERMITTED BUT MUST BE COORDINATED WELL IN ADVANCE WITH THE FMA.
9. A SECURE STORAGE LOCATION SHALL BE PROVIDED BY THE FMA WITHIN REASONABLE (WALKING) DISTANCE TO THE
SITE. HISTORIC MATERIALS THAT ARE REMOVED AND INTENDED TO BE REINSTALLED IN THE FINISHED WORK (E.G. THE
HISTORIC BRICK PAVERS) SHALL NOT BE REMOVED FROM THE SITE, BUT STORED IN A SECURE LOCATION. MATERIALS, WHETHER NEWLY PROVIDED OR EXISTING TO BE REMOVED, SHALL NOT BE STORED OR ALLOWED TO ACCUMULATE ON
THE SITE OR WITHIN THE POSTERN GATE PASSAGE.
10. ALL WORK SHALL CONFORM TO STATE AND LOCAL CODES, ORDINANCES AND REQUIREMENTS.
11. SEAL ALL PENETRATIONS THROUGH WALLS AND CEILINGS WITH APPROVED MATERIALS AS INDICATED.
PROJECT DESCRIPTION
THE INTENT OF THIS PROJECT IS TO SELECTIVELY REMOVE NON-HISTORIC AND NON-CHARACTER DEFINING PORTLAND
BASED MASONRY INFILL AT THE LOCATION OF TWO COMMUNICATION ARCHES BETWEEN WB1 AND WB9 WITHIN THE WEST
BASTION TUNNEL AND REPLACE THE NON- HISTORIC MASONRY WITH A CLEAR GLAZING SYSTEM TO ASSIST IN
INTERPRETING THE SPACE AS WOULD HAVE BEEN THE ORIGINAL INTENT. REMOVAL OF INAPPROPRIATE INSTITUTIONAL
CEILING LIGHTING AND ASSOCIATED CONDUIT FROM THE HISTORIC VIEWSHED AND PROVIDE FOR SUFFICIENT LIGHTING
FOR THE WEST BASTION TUNNEL IS ALSO INCLUDED. NEW LINEAR UP LIGHTING ADJACENT TO THE WALLS WITH NEW
CIRCUITRY SHALL BE PROVIDED HAVING THE CONDUIT CONCEALED BELOW THE NEW BRICK PAVERS. ALL EXTANT NON-
HISTORIC AND INAPPROPRIATE PAVERS WITHIN WB8 AND WB9 SHALL BE REMOVED THROUGHOUT THE PASSAGE. THE
PREVIOUSLY EXCAVATED PASSAGE WILL BE EXCAVATED TO A DEPTH TO PROVIDE FOR A NEW SETTING BED TO RE-LAY
APPROPRIATELY SIZED PAVERS IN A HERRINGBONE PATTERN WITHIN WB9 AND WB8 MATCHING THAT OF THE ORIGINAL.
THE WORK IS GENERALLY LIMITED TO THE POSTERN GATE TUNNEL. A LIMITED AMOUNT OF RESETTING BRICK PAVERS
WITHIN WB1, AN UNDERGROUND CONNECTION FOR ELECTRICITY FROM THE POSTERN GATE TO THE CASEMATE MUSEUM’S
SECURITY ROOM (WB3A), AND LIMITED WORK WITHIN THE SECURITY ROOM IS INCLUDED.
APPLICABLE CODES AND STANDARDS
VIRGINIA UNIFORM STATEWIDE BUILDING CODE, CONSISTING OF--
2018 VIRGINIA EXISTING BUILDING CODE
2018 VIRGINIA ENERGY CONSERVATION CODE
2022, REV 1 COMMONWEALTH OF OF VIRGINIA CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL, DATED
FEBRUARY 14, 2023
FORT MONROE HISTORIC PRESERVATION MANUAL & DESIGN STANDARDS AND REFERENCED DUCUMENTS THEREIN
USE GROUPS
ASSEMBLY GROUP A-3 MUSEUM
CONSTRUCTION TYPE
TYPE III-B (STONE MASONRY)
FIRE SUPPRESSION SYSTEM
NONE EXISTING, NONE PROPOSED
EXISTING BUILDING NOTES
1. BUILDING 20 IS A CONTRIBUTING ELEMENT TO THE FORT MONROE NATIONAL HISTORIC LANDMARK (NHL) AND
NATIONAL REGISTRY OF HISTORIC PLACES (NRHP) DISTRICTS.
2. THIS PROJECT IS A LEVEL 2 ALTERATION THAT ADDS TWO (2) NEW WINDOWS, REPAIRS EXTERIOR LIGHTING, AND
REPAIRS FLOOR FINISHES (PAVERS)
3. NO ALTERATIONS OR REPAIRS AFFECT THE EXISTING LEVEL OF FIRE PROTECTION OR MEANS OF EGRESS
4. NEW WINDOWS SHALL COMPLY WITH THE ENERGY CONSERVATION CODE (SEE BELOW)
5. NO NEW HABITABLE AND OCCUPIABLE SPACES ARE CREATED BY THIS PROJECT
6. NO ALTERATIONS TO MECHANICAL VENTILATION SYSTEMS ARE IN THE SCOPE OF THIS PROJECT
7. NO WORK TO STRUCTURAL ELEMENTS OR SYSTEMS ARE IN THE SCOPE OF THIS PROJECT
8. NO WORK TO ROOFS ARE IN THE SCOPE OF THIS PROJECT
ENERGY CONSERVATION NOTES
1. NEW WINDOWS SHALL COMPLY WITH MAXIUMUM U-FACTOR FOR FIXED FENESTRATIONS IN CLIMATE ZONE 4 OF 0.38
2. NEW WINDOWS WILL BE INSTALLED INSIDE A TUNNEL THAT IS INTEGRAL TO THE STONE FORT, LOCATED AT LEAST 20'
FROM THE TUNNEL OPENING. THEREFORE, THE ADJUSTED SOLAR HEAT GAIN COEFFICIENT MAXIMUM SHALL BE 0.58
STATE BUILDING CONSTRUCITON IN FLOODPLAIN
BUILDING 20 LIES WITHIN SPECIAL FLOOD HAZARD AREA (SFHA) ZONE X, HAVING AN ADJACENT FLOODWAY ZONE AE8.
BULDING 20 IS A CONTRIBUTING "HISTORIC STRUCTURE" AS DEFINED WITHIN THE NATIONAL FLOOD INSURANCE PROGRAM
(NFIP) AND THE 2018 VIRGINIA EXISTING BUILDING CODE (VEBC) AND, AS SUCH, THE WORK PROPOSED DOES NOT
CONSTITUTE A SUBSTANTIAL IMPROVEMENT. THE FORT MONROE HISTORIC PRESERVATION OFFICER (FMHPO), IN THEIR
APPICATOIN OF STIPULATION IV.B THROUGH IV.D OF THE BASE REALIGNMENT AND CLOSURE (BRAC) PROGRAMMATIC
AGREEMENT (PA), HAS MADE THE DETERMINATION AND THE VIRGINIA STATE HISTORIC PRESERVATION OFFICER (SHPO)
HAS CONCURRED THAT THE PROPOSED REPAIR OR REHABILITATON WILL NOT PRECLUDE THE STRUCTURE'S CONTINUED
DESIGNATION AS A HISTORIC BUILDING AFTER THE WORK IS COMPLETE.
GROUND DISTURBANCE
THE CONTRACTOR SHAL SUBMIT A PROJECT SCREENING FORM (PSF)AND GROUND DISTURBANCE PERMIT (GDP) TO THE
FORT MONROE AUTHORITY (FMA) VIA EMAIL TO: PROJECTREVIEW@FORTMONROE.ORG. THE CONTRACTOR IS REQUIRED
TO PROVIDE ALL REQUESTED AND NECESSARY INFORMATON AS INDICATEED ON THE PSF AND GDP.
THE CONTRACTOR SHALL NOTIFY "MISS UTILITY" AT 1-800-552-7001 OR 811 A MINIMUM OF 72 HOURS IN ADVANCE OF ANY
EXCAVATION AND PROVIDE THE TICKET NUMBER(S) TO THE FMA PRIOR TO EXCAVATION. ANY DAMAGE TO EXISTING
UTILITIES WILL BE REPAIRED BY THE UTILITY OWNER AT THE CONTRACTOR'S EXPENSE. THE CONTRATOR SHALL TAKE ALL
NECESSARY PRECAUTIONS TO PROTECT EXISTING UTILITIES.
POSTERN
GATE
CASEMATE
MUSEUM
SECURITY
MOAT SIDE
BR
ID
GE
PUB
LIC
PED
EST
RIA
N
WA
Y
PUBLIC PEDESTRIAN WAY
BUILDING 20 AND WEST
BASTION PROJECT SITE,
REFER TO SITE MAP
PARADE SIDE
WB3 WB2 WB1 WB9 WB8
WB3A
LOCATION MAP SITE MAP
FORT MONROE
HAMPTON ROADS BRIDGE TUNNEL
HAMPTON,
VIRGINIA
NORFOLK,
VIRGINIA
HWY 64
HWY 64
FORT MONROE/
PHOEBUS EXIT 268
PROJECT SITE
BUILDING 20 AND
WEST BASTION
INNER
FORT
VEHICLE ENTRANCE TO
INNER FORT, MAX
VEHICLE HEIGHT 12'-3",
WIDTH 10'-0", 20 TONS
BUILDING 21 AND
SOUTH BASTION
HANBURY
COPYRIGHT © 2021
DRAWN BY:
CHECKED BY:
PROJECT NO:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51
21 43 5
C
B
D
C
B
D
AA
C O N S U
LT
A N T
W E S T B A S T
IO
N
V
IS
IT
O R
E X P E R
IE
N C
H A N C E M E
T
P
O J E C T
B
E R
N A
R D
R O
A D
F O
R T
M O
N R
O E
V
A
P R
O J E
C T
C O
D E
-B
-0
ISSUED FOR BID12/01/2023N/A
REVISED12/19/2023N/A
12/19/2023
20027.02
ARC
GLR
COVER SHEET, PROJECT
DATA AND DRAWING
INDEX
G001
GENERAL NOTES
INDEX OF DRAWINGS
SHEET
NUMBER SHEET NAME
G001 COVER SHEET, PROJECT DATA AND DRAWING
INDEX
A101 FLOOR PLAN - DEMOLITION AND NEW WORK
A102 ARCHITECTURAL LIGHTING PLAN
A401 ENLARGED PLANS
WEST BASTION VISITOR EXPERIENCE
ENHANCEMENT PROJECT
FORT MONROE
FORT MONROE, VIRGINIA
OWNER
FORT MONROE AUTHORITY
20 INGALLS ROAD
FORT MONROE, VA 23651
ARCHITECT
HANBURY
120 ATLANTIC STREET
NORFOLK, VA 23510
(757) 321.9600
MECHANICAL, ELECTRICAL,
AND PLUMBING ENGINEER
VANSANT & GUSLER
CONSULTING ENGINEERS
6330 NEWTOWN ROAD
SUITE 400
NORFOLK, VA 23502
(757) 461.6757
PROJECT INFORMATION
PHOTOGRAPH KEY PLAN
PHOTO 1 PHOTO 2
PHOTO 3 PHOTO 4
PHOTO 5 PHOTO 6
PHOTO 7 PHOTO 8 PHOTO 9
WB1 PARADE SIDE WB1 MOAT SIDE
WB9 MOAT SIDEWB9 PARADE SIDE
ENTRY TO WB9 WB9 PARADE SIDE
WB8 LOOKING INTO WB9 WB8 AT TUNNEL ENTRY WB8 CEILING
PHASE: ISSUED FOR BID
DATE: DECEMBER 1, 2023
A401
B1
3300.02
3300.03
3300.04
SECURITY
CASEMATE
MUSEUM
POSTERN
GATE
2600.16
0420.03
LIMIT OF
PAVER WORK
EDGE OF INVERTED BRICK
ARCH BELOW PAVERS
0472.010420.01
EXISTING STONE
WALL, TYPICAL
MOAT
MOAT
EXISTING BRIDGE
3300.01
2600.09 TYPICAL
2600.15
2600.07
2600.07
0851.01
0851.01
LIMIT OF PAVER WORK
LIMIT OF
PAVER WORK
SEE SHEET A102 FOR
ELECTRICAL WORK
WB3 WB2 WB1 WB9
WB8
WB3A
MOAT SIDE
PARADE SIDE
3300.02
3300.03
3300.01
3300.04
3300.05
0241.01
0241.03
0241.06
SECURITY
CASEMATE
MUSEUM
POSTERN
GATE
0241.02
0241.02
0241.04
0241.04
0241.11
0241.07
0241.08
0241.09
TIME CLOCK
T C
0241.11
0241.05
0241.05
LIMIT OF DEMOLITION WORK
INDICATED BY DASH LINES
EXISTING BRICK SIDEWALK
0241.10
0420.06
0401.02
0401.02
3300.07
3300.06
0241.12
0241.13
WB3 WB2 WB1
WB9
WB8
WB3A
MOAT SIDE
PARADE SIDE
+/- 16' - 1 1/4" +/- 5' - 0" +/- 16' - 1" +/- 15' - 5 5/8"
4' /2
/4
/2
4' /4
+/- 53' - 4 7/8"
+/- 5' - 0"
+/- 18' - 5 1/8"
2'
3' - 2"
+/- 207 SF
COMBINED
REPAIR AREAS
1324 SF
+/- TUNNEL
PAVER AREA
NOTE: SEE GENERAL NOTE 4,
SHEET G001, REGARDING ALL
EXISTING DIMENSIONS
HANBURY
COPYRIGHT © 2021
DRAWN BY:
CHECKED BY:
PROJECT NO:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51
21 43 5
C
B
D
C
B
D
P R
IN
T E D
AA
C O N S U
LT
A N T
W E
S T
B A
S T
IT
P E
R
IE
N
H A
N C
E M
E
O J
E C
T
B
E R
N A
R D
R O
A D
F O
R T
M O
N R
O E
V
A
P R
O J E
C T
C O
D E
-B
-0
ISSUED FOR BID12/01/2023N/A
REVISED12/19/2023N/A
12/19/2023
/1 9/ :2 1:
P M
20027.02
ARC
GLR
FLOOR PLAN -
DEMOLITION AND NEW
WORK
A101
1/8" = 1'-0"C1
FLOOR PLAN
1/8" = 1'-0"A1
DEMOLITION PLAN
WORK NOTES
NUMBER DESCRIPTION
0241.01 REMOVE BRICK BORDER AND FIELD PAVERS TO EXPOSE EXISTING UNDERGROUND
CONDUIT (SEE NOTE 0241.06), ENLARGE TRENCH TO ADD A SECOND CONDUIT, SEE SHEET
A102
0241.02 REMOVE CEILING MOUNTED LIGHTING FIXTURES AND WALL MOUNTED CONVENIENCE
OUTLETS AND ASSOCIATED CONDUIT, STRAPS, FASTENERS AND ANCHORS
0241.03 REMOVE CONDUIT ASSOCIATED WITH POSTERN GATE LIGHTING AND OUTLETS WITHIN
SECURITY ROOM, INCLUDING THROUGH WALL PENETRATION, PREPARE PENETRATION FOR
NEW CONDUIT
0241.04 REMOVE NON-HISTORIC MASONRY WALL INFILL (2 WYTHES THICK), USE HAND TOOLS IN THE
AREA OF ELECTRICAL CONDUIT LOCATION INDICATED
0241.05 REMOVE PAVERS, SUBSTRATE AND FILL AS NEEDED TO EXPOSE THE ENTIRETY OF THE
BRICK INFILL TO BE REMOVED AND THE INTRADOS OF THE INVERTED ARCH, USE HAND
TOOLS, SEE "WINDOW OPENINGS" UNDER SPECIFICATION SECTION 024119 - SELECTIVE
DEMOLITION
0241.06 REMOVE UNDERGROUND CONDUIT FROM THE THRU-WALL PENETRATION TO THE POSTERN
GATE ENTRANCE
0241.07 PANELBOARD MPH, EXISTING TO REMAIN
0241.08 DISCONNECT SWITCH, EXISTING TO REMAIN
0241.09 REMOVE TIME CLOCK WITH ASSOCIATED CONDUIT AND BRANCH CIRCUITING BACK TO
ELECTRICAL PANELBOARD MPH
0241.10 DO NOT DISTURB BRICK PAVERS OR CANNON RAIL IN THIS AREA, IF PAVERS AND BASE
MUST BE REMOVED TO COMPLETE THE WORK, NOTIFY THE ARCHITECT PRIOR TO REMOVAL
0241.11 REMOVE BRICK PAVERS THROUGHOUT PASSAGE, SEE "PAVERS" UNDER SPECIFICATION
SECTION 024119 - SELECTIVE DEMOLITION
0241.12 REMOVE DAMAGED SECTION OF BRICK PAVERS IN AREA INDICATED AND PREPARE FOR
REPAIR
0241.13 EXISTING CONCRETE THRESHOLD, TO REMAIN
0401.02 EXISTING STONE THRESHOLD, TO REMAIN
0420.01 RE-LAID PAVERS, HERRING BONE PATTERN
0420.03 RE-SET PAVERS AND BORDER, SEE SHEET A102 FOR ADDITIONAL ELECTRICAL INFORMATION
0420.06 EXISTING ROWLOCK PAVERS, TO REMAIN
0472.01 CAST STONE PAVERS, MATCH SIZE AND SHAPE OF ORIGINAL IN WB1, SAME THICKNESS AS
BRICK PAVERS, MIRROR LAYOUT ON CENTERLINE OF CASEMATE
0851.01 ARCH GLASS WINDOW, SEE SHEET A401
2600.09 NEW RECESSED, FLOOR MOUNTED LIGHT FIXTURE, PROVIDE GROUND MOUNTING SLEEVES, END CAPS, CABLES AND CONNECTORS AS REQUIRED TO FACILITATE A COMPLETE
INSTALLATION, TYPICAL FOR TYPE A AND B FIXTURES
2600.15 HANDHOLE, SEE DETAIL SHEET A102
2600.16 PROVIDE UNDERGROUND CONDUIT FOR LIGHTING AND POWER, SEE SHEET A102
3300.01 EXISTING MANHOLE, TO REMAIN
3300.02 APPROXIMATE LOCATION OF NATURAL GAS LINE
3300.03 APPROXIMATE LOCATION OF SANITARY SEWER LINE
3300.04 APPROXIMATE LOCATION OF COPPER LINE
3300.05 APPROXIMATE LOCATION OF ABANDONED SANITARY SEWER LINE
3300.06 EXISTING ELECTRICAL MANHOLE AND VAULT BELOW PAVERS, APPROXIMATE SIZE SHOWN, TO REMAIN
3300.07 APPROXIMATE LOCATION OF ELECTRICAL CONDUIT, +/-18" FROM FINISH FLOOR TO INVERT
OF CONDUIT, COORDINATE WITH FMA AND FACILITY MANAGEMENT (VEOLIA) AND MISS
UTILITY FOR PRECISE LOCATION
EXISTING CONDITIONS
024119 – SELECTIVE DEMOLITION
WINDOW OPENINGS: REMOVE BRICK PAVERS TO THE EXTENT NECESSARY ON BOTH SIDES OF THE
BRICK INFILL TO EXPOSE THE ENTIRE INFILL WALL AND TOP SURFACE OF THE INVERTED ARCH.
SALVAGE AND STORE PAVERS IN A SECURE LOCATION FOR RE-INSTALLATION KEEPING THE INTERIOR
PAVERS AND THE EXTERIOR PAVERS SEPARATE SO AS TO REINSTALL IN THEIR EXISTING LOCATIONS.
REMOVE THE BRICK MASONRY INFILL AND CLEAN RESIDUAL MORTAR FROM EXTANT SURFACES. SEE
GENERAL NOTES, SHEET, G-01 FOR TEMPORARY PROTECTION.
PAVERS: REMOVE PAVERS THROUGHOUT THE ENTIRE PASSAGEWAY AND STORE IN A SECURE
LOCATION UNTIL READY FOR RE-INSTALLATION. PAVERS ARE SUBJECT TO SELECTION FOR SIZE AND
COLOR. REFER TO UNIT PAVING BELOW.
REMOVE AND EXCAVATE THE EXISTING SETTING BED(S) TO A DEPTH TO ACCOMMODATE THE NEW SUB-
BASE, SETTING BED AND PAVERS REINSTALLED WITH THE STRETCHER FACE EXPOSED
(APPROXIMATELY 12” OF DEPTH.) UPON COMPLETION OF THE EXCAVATION, NOTIFY THE ARCHITECT
AND REVIEW THE EXISTING CONDITIONS WITH THE ARCHITECT AND THE FORT MONROE HISTORIC
PRESERVATION OFFICER TO DETERMINE IF ADDITIONAL EXCAVATION, OR OTHER TREATMENTS TO THE
SUBSTRATE WILL BE NECESSARY. AT A MINIMUM, COMPACTION OF THIS BASE SHALL BE INCLUDED IN
THE WORK. SEE GENERAL NOTES, SHEET G-01 FOR UNDERGROUND UTILITIES.
MASONRY
042000 – BRICK MASONRY
MATERIALS: BUILDING BRICK, ASTM C 62, GRADE MW, PROVIDE SOLID UNITS FOR TOP COURSE.
MORTAR: TYPE M. REINFORCEMENT: TRUSS TYPE GALVANIZED HORIZONTAL REINFORCEMENT
INSTALLATION: INSTALL OVER A BOND BREAK (30# ASPHALT FELT PAPER) AT THE CENTER LINE OF THE
INVERTED ARCH. CUT BRICK TO MATCH THE CURVATURE OF THE ARCH AND TO PROVIDE A SOUND
SEAT ONTO THE ARCH. LAY REINFORCEMENT IN EVERY OTHER BED JOINT. LAY UNITS WITH
COMPLETELY FILLED BED AND HEAD JOINTS. STRIKE MORTAR JOINT FLUSH WITH FACE OF MASONRY
METALS
055000 – METAL FABRICATIONS
MATERIALS: STEEL PLATE AND TUBES: ASTM A276, TYPE 304 STAINLESS STEEL, UNPOLISHED;
ALUMINUM: PREFINISHED BRAKE-METAL 0.063 INCH THICK, BLACK ANODIZED. FASTENERS FOR
STAINLESS STEEL: TYPE 304 STAINLESS STEEL. PRIMER FOR STAINLESS STEEL: GALVANIZED METAL
ETCHING PRIMER.
FABRICATION/INSTALLATION: STAINLESS STEEL FRAMES SHALL BE FABRICATED TO CONFORM TO THE
ARCHED OPENINGS ALLOWING A MINIMUM CLEARANCE BETWEEN THE STEEL AND THE STONE/BRICK
MASONRY. JOINTS SHALL BE WELDED AND GROUND SMOOTH. HOLES FOR FASTENERS SHALL BE FIELD
LOCATED SO THE ANCHOR BOLTS ARE INSERTED INTO THE MORTAR JOINTS OF THE STONE, NOT INTO
THE STONE ITSELF. THE UNEXPOSED FACE OF THE STEEL PLATE SHALL BE PRIMED. ALL OTHER
SURFACES SHALL REMAIN UNCOATED. ALUMINUM BRAKE METAL WTIH A FLUOROPOLYMER COATING
SHALL BE BENT AND INSTALLED BETWEEN THE LIGHT FIXTURES AND THE STONE WALL MAINTAINING A
STRAIGHT EDGE ON THE HORIZONTAL LEG THAT ABUTS THE WIDEST PORTION OF THE STONE. SUBMIT
SHOP DRAWINGS FOR APPROVAL.
THERMAL AND MOISTURE PROTECTION
072500 – WEATHER BARRIERS/BOND BREAK
MATERIALS: SELF-ADHEREING RUBBERIZED ASPHALT SHEET MEMBRANE SUCH AS BLUESKIN® BY
HENRY COMPANY; 30# ASPHALT FELT
INSTALLATION: APPLY RUBBERIZED ASPHALT SHEET TO THE NON-VISIBLE SIDE OF THE STAINLESS-
STEEL FRAME. TRIM EDGES SO THE MEMBRANE IS NOT VISIBLE. LAY 30# ASPHALT FELT ON TOP OF THE
INVERTED ARCH TO PROVIDE A BOND BREAK BETWEEN NEW AND EXISTING MASONY
079200 – JOINT SEALANTS
MATERIALS: CLEAR SILICONE SEALANT FOR BUTT-GLAZED GLASS; COLORFAST, SILICONIZED ACRYLIC
LATEX WITH SANDED TEXTURE FOR JOINT BETWEEN STEEL AND MASONRY, COLOR TO MATCH FRENCH
GRAY BY HYDROMENT OR CHARCOAL BY MAPEI, OR AN EQUAL PRODUCT TO MATCH
INSTALLATION: INSTALL SILICONE SEALANT BETWEEN PANES OF GLASS AND MAINTAIN A FLUSH FINISH
TO THE GLASS. INSTALL ACRYLIC LATEX BETWEEN THE STAINLESS-STEEL FRAME AND STONE/BRICK
MASONRY MAINTAINING A 1/8” – ¼” CONSISTENT DEPTH FROM THE EDGE OF THE FRAME, TOOL TO A
CONCAVE PROFILE.
OPENINGS
084126 – ALL GLASS STOREFRONTS
MANUFACTURER: VIRGINIA GLASS PRODUCTS CORPORATION; GLASS: CLEAR, 1/2" TEMPERED AND
LAMINATED, MAXIMUM U-FACTOR 0.38, MAXIMUM SHGC 0.58; ALUMINUM EXTRUSIONS: ALLOY AND
TEMPER OF NOT LESS THAT THE STRENGTH AND DURABILITY OF 6063-T5; ALUMINUM FINISH: MILL
FINISH. FASTENERS AND ANCHORS: CONCEALED WHERE PRACTICAL, WHERE EXPOSED, HEADS OF
FASTENERS SHALL BE FINISHED TO MATCH ADJACENT METAL. SUBMIT SHOP DRAWINGS FOR
APPROVAL.
FINISHES
099124 – EXTERIOR PAINTING
MATERIALS: WHITE WASH: ECOLOGIC LIMEWASH PLATINUM
INSTALLATION: POWER-WASH SURFACES CURRENTLY WHITE-WASHED AFTER THE EXISITING PAVERS
HAVE BEEN REMOVED. ALLOW TO DRY THOROUGHLY BEFORE REAPPLYING NEW COAT. APPLY TO
WALLS ONLY. COORDINATE PREP AND PAINTING WITH THE INSTALLATION OF UNIT PAVING SO AS TO
NOT PAINT AFTER THE PAVERS HAVE BEEN INSTALLED.
EXTERIOR IMPROVEMENTS
321400 – UNIT PAVING
MATERIALS:
BRICK: EXISTING BRICK SALVAGED FROM THE PASSAGEWAY AND SUPPLEMENTED WITH NEW SOLID
BRICK OF THE SAME SIZE, TEXTURE AND COLOR RANGE. SELECT SALVAGED PAVERS FOR RE-USE
ONLY IF THEY MATCH THE ORIGINAL SIZE INDICATED AND ORIGINAL COLOR RANGE. AN ORIGINAL BRICK
COMPARISON AREA IS LOCATED ON THE MOAT SIDE CASEMATES OF THE SOUTH BASTION, WITHIN
BUILDING 21. THIS IS NOT A PUBLIC AREA, COORINATE WITH OWNER FOR ACCESS. ALL REMAINING
PAVERS NOT USED FOR THIS PROJECT SHALL BE RETAINED BY THE FMA.
SUBMIT SAMPLES OF NEW BRICK FOR APPROVAL.
INSTALL HERRING BONE IN DIRECTION INDICATED ON PLAN.
CAST STONE: UNITS SHALL COMPLY WITH ASTM C1364 AND BE MANUFACTURED USING THE VIBRANT
DRY TAMP OR WET-CAST METHOD. CAST STONE PAVERS SHALL BE 4” THICK (+/- TO MATCH THE DEPTH
OF THE BRICK) AND OF SIZE AND SHAPE TO MATCH THE EXISTING ORIGINAL TRAVERSING RING PIECES.
EXPOSED SURFACE SHALL BE SMOOTH; COLOR SHALL BE SELECTED FROM THE MANUFACTURERS FULL
RANGE. CUT AND LAY BRICK PAVERS TIGHT TO THE SHAPE OF THE CAST STONE.
JOINT SAND: MASON’S SAND; SAND SETTING BED: CONCRETE SAND PER ASTM C33
STONE SUBBASE: QUARRY PROCESSED DENSE GRADE AGGREGATE (3/4” OR LESS CRUSHED STONE
AND STONE DUST AKA CRUSHER RUN)
INSTALLATION IN THE POSTERN GATE PASSAGEWAY: INSTALL STONE SUB-BASE IN TWO LIFTS TO A
TOTAL THICKNESS OF 6 INCHES, COMPACT EACH LIFT TO 95%. INSTALL SAND BED 1 TO 1 ½” THICK, SCREED LEVEL. BLEND EXISTING AND NEW BRICK, INSTALL BRICK IN HERRINGBONE PATTERN WITH
STRETCHER FACE EXPOSED (AS IN THE CASEMATE MUSEUM) SPREAD JOINT SAND OVER THE PAVERS
AND SWEEP INTO THE JOINTS, COMPACT THE PAVERS AND APPLY MORE SAND, REPEAT UNTIL THE
JOINTS ARE FILLED.
REINSTALLATION IN THE CASEMATE MUSEUM: INFILL EXCAVATION AND BRING THE SAND BED UP TO
THE LEVEL OF THE BED UNDER PAVERS THAT REMAIN. HAND TAMP TO COMPACT. REINSTALL THE
PAVERS THAT WERE REMOVED AND SWEEP MASONS SAND INTO THE JOINTS. COMPACTION OF THE
PAVERS WILL NOT BE NECESSARY.
SPECIFICATIONS
FIRST FLOOR
0"
5"
1/8" THICK STEEL LANDSCAPE
EDGING WITH 12" STAKES, MINIMUM
3 STAKES PER PIECE OF EDGING
LIGHT FIXTURE IN GROUND SLEEVE
BRICK PAVERS
SAND BED
6" DEEP MINIMUM CRUSHED
STONE AND CONCRETE
SAND, COMPACTED
FLUSHCUT PAVER FILL
16 GAGE BLACK BREAK METAL,
COLOR BLACK, REFER TO
SPECIFICATIONS FOR METAL
FABRICATIONS
3 1/8"
FROM STONE WALL
3 1/2" TO 4" AVERAGE
ENSURE DRAIN HOLES IN
GROUND SLEEVE ARE
UNOBSTRUCTED
NOTE: LIGHT FIXTURE MUST
ALIGN WITH THE FULL
LENGTH OF STONE WALL
EXISTING STONE WALL
A
A
A
A A
A A
A
A
A
A
A B
B
B
B
SECURITY
2600.01
2600.04
2600.03
2600.02
2600.05
0420.02
POSTERN
GATE
CASEMATE
MUSEUM
3"
2600.06
6"
2600.09
2600.12
2600.10
2600.11 B1
A102
LC 2600.13
2600.13
2600.13
2600.13
2600.14
2600.15
H H
2600.13
WP
WP
3"
DURING CONSTRUCTION, FMA MUSEUM STAFF WILL
TEMPORARILY CLOSE WB1 TO VISITORS AND MOVE THE
EXIT DOOR TO WB2, THE REMAINDER OF THE MUSEUM
WILL STAY OPEN TO THE PUBLIC
WB3 WB2 WB1 WB9
WB8
WB3A
2600.07
2600.07
IN GRADE LUMINAIRE
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT, 2 #12
AND 1 #12 GROUND IN 3/4" CONDUIT, CONDUIT LARGER
THAN 3/4" AND WIRE LARGER THAN #12 SHALL BE AS
INDICATED
HOME RUN TO PANELBOARD, PANELBOARD AND CIRCUIT
DESIGNATIONS ARE AS INDICATED
FLOOR FLUSH MOUNT 2-GANG RECEPTACLE, GROUND
FAULT INTERRUPTING TYPE, 20A 120V
ELECTRICAL PANELBOARD, 120/208V, 3ø, 4W, UON
TIME CLOCK
LIGHTING CONTROLLER
HAND HOLE, SEE DETAIL FOR INFORMATION
WP
TC
LC
HH
6" M
IN
CRUSHED ROCK
BRICK PAVER ON SAND
BOX AND COVER
HANDHOLE SIZING
10" X 15" X 18" DEEP
STAINLESS STEEL HEX
BOLT AND WASHER
PULL SLOT
LA
BE
L
SKID RESISTANT
SURFACE
NOTES:
1. HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A
HEAVY WEAVE FIBERGLASS REINFORCING WITH COMPRESSIVE
STRENGTH OF NO LESS THAN 10,000 PSI
2. COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS
THAN 15,000 LBS OVER A 10" X 10" AREA
3. COVER AND BOX TO BE EITHER MANUFACTURER'S STANDARD BRICK
COLOR OR A PAINTABLE SURFACE
4. PROVIDE STAINLESS STEEL BOLTS AND INSERTS
5. PROVIDE WITH (2) 2 1/2" MOUSEHOLES
6. PROVIDE LABEL "LIGHTING" FOR HANDHOLE COVER
1. THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS IS TO DESCRIBE THE INSTALLATION OF A COMPLETE, FULLY ADJUSTED, AND OPERATIONAL SYSTEM. ANYTHING NOT EXPRESSLY SET
FORTH BUT WHICH IS REASONABLY IMPLIED AND/OR NECESSARY FOR PROPER AND COMPLETE PERFORMANCE OF THE WORK SHALL BE INCLUDED.
2. REFER TO SHEET A101, FLOOR PLAN - DEMOLITION AND NEW WORK, FOR DEMOLITION OF EXISTING LIGHT FIXTURES, ELECTRICAL CONDUIT, WIRING, AND DEVICES.
3. COORDINATE ELECTRICAL WORK WITH THE MUSEUM EXITS SO-AS TO NOT BLOCK OR IMPEDE AN ACTIVE EGRESS DOOR OUT OF THE MUSEUM.
4. WHERE THE DRAWINGS DO NOT ADDRESS INSTALLATION METHODOLOGY, THE CONTRACTOR SHALL BE BOUND TO PERFORM IN STRICT COMPLIANCE WITH THE MANUFACTURER'S
SPECIFICATIONS AND INDUSTRY STANDARDS.
5. THE DRAWINGS ARE DIAGRAMMATIC ONLY. MAKE FIELD ADJUSTMENTS TO ACCOMMODATE ACTUAL FIELD CONDITIONS.
6. COORDINATE ALL WORK WITH THE GENERAL CONTRACTOR AND OTHER TRADES INVOLVED IN THE CONSTRUCTION PROJECT. CAREFULLY LAY OUT ALL WORK IN ADVANCE TO COORDINATE
ARCHITECTURAL AND ELECTRICAL FEATURES OF CONSTRUCTION.
7. PROVIDE ALL SUPERVISION, LABOR, MATERIAL, EQUIPMENT, MACHINERY, AND ANY AND ALL OTHER ITEMS NECESSARY TO COMPLETE THE SYSTEM.
8. ACCOMPLISH ALL WORK UNDER THIS SECTION IN STRICT ACCORDANCE WITH LOCAL, AND STATE BUILDING CODES INCLUDING BUT NOT LIMITED TO NFPA 70, VUSBC, AND FACILITY STANDARDS.
9. RECEPTACLES SHALL COMPLY WITH UL STANDARD 498, "ELECTRICAL ATTACHMENT PLUGS AND RECEPTACLES," COMMERCIAL GRADE 20A RATED EXCEPT AS OTHERWISE INDICATED.
10. PROVIDE ALL LUMINAIRES SHOWN ON THE LUMINAIRE SCHEDULE, COMPLETE WITH ALL MOUNTING ACCESSORIES. SUPPORT LUMINAIRES AS INDICATED.
11. RUN ALL WIRING IN CONDUIT, 3/4" IS THE MINIMUM INDOOR CONDUIT SIZE. USE NONMETALLIC CONDUIT BELOW GRADE, PROVIDE RIGID CONDUIT TO TURN UP AT EXTERIOR WALLS OR EQUIPMENT.
USE ELECTRICAL METALLIC TUBING, TYPE AC, OR MC CABLE FOR BRANCH CIRCUITS WHERE ALLOWED BY NEC AND NOT SUBJECT TO PHYSICAL DAMAGE, MOISTURE OR DAMPNESS FOR INDOOR
CONDUIT. USE NEMA TYPE 1 FOR INDOOR BOXES AND ENCLOSURES, EXCEPT IN DAMP OR WET LOCATIONS USE NEMA TYPE 3R. USE NEMA TYPE 3R FOR OUTDOOR ENCLOSURES AND BOXES.
TIGHTEN CONNECTIONS AND TERMINALS, INCLUDING SCREWS AND BOLTS, ACCORDING TO EQUIPMENT MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES FOR EQUIPMENT
CONNECTORS. WHERE MANUFACTURER'S TORQUING REQUIREMENTS ARE NOT INDICATED, TIGHTEN CONNECTORS AND TERMINALS ACCORDING TO TIGHTENING TORQUES SPECIFIED IN UL
STANDARD 486A. CONDUITS EXPOSED TO DIFFERENT TEMPERATURES SHALL BE SEALED AS REQUIRED BY NEC ARTICLE 300.7(A). RIGID CONDUIT FITTINGS SHALL BE THREADED, EXCEPT WHERE
RIGID CHANGES TO EMT ABOVE GRADE, FITTINGS MAY BE THREADLESS TYPE. USE GALVANIZED STEEL CONCRETE-TIGHT, SET SCREW TYPE ELECTRICAL METALLIC TUBING FITTINGS.
12. RUN UNDERGROUND CONDUIT(S) UNDER BRICK PAVERS 12” BELOW GRADE AND 18” BELOW GRADE WHERE NOT BELOW PAVERS IN ACCORDANCE WITH NEC TABLE 300.5
13. ALL FEEDERS AND BRANCH CIRCUIT CONDUCTORS TO BE COPPER IN MATERIAL AND ONE OF THE FOLLOWING INSULATION TYPES THW, THHW, THWN, XHHW, OR XHHW-2 WITH A MINIMAL
TEMPERATURE RATING OF 75 DEG. C. SOLID CONDUCTORS FOR NO. 10 AWG AND SMALLER, STRANDED CONDUCTORS FOR NO. 8 AWG AND LARGER
14. CONDUCTORS COLOR CODED AS FOLLOWS:
A. PHASE: 208/120 VOLTS
B. A: BLACK
C. B: RED
D. C: BLUE
E. NEUTRAL: WHITE
F. GROUND: GREEN
15. PROVIDE A GREEN INSULATED COPPER GROUND WIRE, SIZED PER NEC, IN ALL NON-METALLIC CONDUIT, ELECTRIC METALLIC TUBING, FLEXIBLE CONDUIT USED FOR FEEDERS AND AS OTHERWISE
NOTED ON THE DRAWINGS.
16. MARK ALL DEVICES AS TO WHICH PANELBOARD AND CIRCUIT THEY ARE CONNECTED.
17. LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS WITHIN.
18. MAKE ALL NECESSARY TESTS TO ENSURE THAT THE ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS AND FROM SHORTED AND/OR OPEN CIRCUITS. VOLTAGE, CURRENT, AND
ROTATION TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN OPERATION. ALL LOADS MUST BE BALANCED ACROSS PHASES. CHECK TO SEE THAT ALL LIGHTS WORK AND ARE
CONTROLLED BY SWITCHES INDICATED ON DRAWINGS OR BREAKERS SO INDICATED ON PANELBOARD SCHEDULE.
19. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
20. PROVIDE GROUNDING FOR SERVICE, ALL CONDUITS, MOTOR FRAMES, METAL CASINGS, RECEPTACLES, SYSTEM NEUTRAL, ETC. AND AS REQUIRED BY NEC AS MINIMUM. RESISTANCE TO GROUND
SHALL NOT EXCEED 25 OHMS.
21. OPERATION AND MAINTENANCE MANUALS: PROVIDE OPERATION AND MAINTENANCE MANUALS TO OWNER FOR MATERIALS PROVIDED UNDER THIS CONTRACT: SYSTEMS AND EQUIPMENT
OPERATION MANUALS, SYSTEMS AND EQUIPMENT MAINTENANCE MANUALS, AND PRODUCT MAINTENANCE MANUALS.
22. CONDUIT SUPPORTS SHALL BE APPROVED WALL BRACKETS, STRAP HANGER OR PIPE STRAPS SECURED TO HOLLOW MASONRY WITH TOGGLE BOLTS; TO METAL SURFACES WITH MACHINE
SCREWS; AND TO WOOD WITH WOOD SCREWS. ANY FORM OF TIE WIRE IS UNACCEPTABLE.
HANBURY
COPYRIGHT © 2021
DRAWN BY:
CHECKED BY:
PROJECT NO:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51
21 43 5
C
B
D
C
B
D
P R
IN
T E D
AA
C O N S U
LT
A N T
W E
S T
B A
S T
IT
P E
R
IE
N
H A
N C
E M
E
O J
E C
T
B
E R
N A
R D
R O
A D
F O
R T
M O
N R
O E
V
A
P R
O J E
C T
C O
D E
-B
-0
ISSUED FOR BID12/01/2023N/A
REVISED12/19/2023N/A
12/19/2023
/1 9/ :2 1:
P M
20027.02
ARC
GLR
ARCHITECTURAL
LIGHTING PLAN
A102
6" = 1'-0"B1
LIGHT FIXTURE DETAIL
1/8" = 1'-0"C1
LIGHTING AND ELECTRICAL FLOOR PLAN
WORK NOTES
NUMBER DESCRIPTION
0420.02 RE-LAID PAVERS, SAILOR AND RUNNING BOND PATTERN
2600.01 NEW UNDERGROUND 1" CONDUIT, RUN (3) 3 PAIR #22AWG DMX CABLING IN CONDUIT FROM LIGHTING
CONTROLLER TO HANDHOLE
2600.02 EXISTING ELECTRICAL PANELS MOUNTED TO UNISTRUT SYSTEM, TO REMAIN
2600.03 PROVIDE 3 DMX CONTROL CABLES WITHIN 1" CONDUIT FOR LIGHT FIXTURES AND CONNECT TO
LIGHTING CONTROLLER
2600.04 ROUTE CONDUIT THROUGH MASONRY WALL WHERE PREVIOUSLY DEMO'D CONDUIT WAS LOCATED
2600.05 NEW LIGHTING CONTROLLER, MOUNT TO EXISTING UNISTRUT SYSTEM
2600.06 NEW UNDERGROUND 3/4" CONDUIT, SEE GENERAL NOTES
2600.09 NEW RECESSED, FLOOR MOUNTED LIGHT FIXTURE, PROVIDE GROUND MOUNTING SLEEVES, END CAPS, CABLES AND CONNECTORS AS REQUIRED TO FACILITATE A COMPLETE INSTALLATION, TYPICAL
FOR TYPE A AND B FIXTURES
2600.10 PROVIDE PVC CONDUIT FOR ALL BELOW GRADE RUNS, TRANSITION TO EMT WHERE CONDUIT TURNS VERTICALLY OUT OF BRICK PAVERS, PAINT EXPOSED EMT ON THE EXTERIOR TO MATCH BRICK COLOR, COLOR TO BE APPROVED BY THE ARCHITECT
2600.11 ROUTE CONDUIT TIGHT TO WALL AND CONNECT TO EXISTING PANEL OR LIGHTING CONTROLLER
2600.12 PROVIDE WIRING FOR TWO (2) QUAD CONVENIENCE OUTLETS AND CONNECT TO EXISTING ELECTRICAL
PANEL
2600.13 3/4" CONDUIT WITH 3 PAIR 22AWG DMX CABLE, TYPICAL FOR ENTIRE LENGTH OF CIRCUIT
2600.14 RUN HOME RUN CIRCUIT UNDERGROUND BACK TO PANELBOARD MPH, CONNECT TO AVAILABLE 20A-1P
SPARE CIRCUIT BREAKER
2600.15 HANDHOLE, SEE DETAIL SHEET A102
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER MODEL MODEL NUMBER COMMENTS
A ACDC LIGHTING BLADE LRI BL LRI L12 5000-RGBW-M-ABK-0-67-DMX 4' NOMINAL LENGTH
B ACDC LIGHTING BLADE LRI BL LRI L09 3800-RGBW-M-ABK-0-67-DMX 3' NOMINAL LENGTH
ELECTRICAL LEGEND
B2
ELECTRICAL HANDHOLE (NONTRAFFIC)
ELECTRICAL GENERAL NOTES
A401A1
Q
E Q
E Q
E Q
1/ 2"
E Q
E Q
1/ 2"
ALIGN CENTERS
E Q
E Q
E Q
E Q
1/ 2"
E Q
E Q
E Q
E Q
1/ 4"
1/ 4"
1/ 4"
0472.01
0420.01
0401.01
3300.01
B1
A102
C4
A401
B4
A401
A401
A4
@ HEAD
@ SILL
0420.05
0420.05
0420.06
0401.020401.02
1/ 4"
FMA STAFF TO SHIFT GUN
CARRIAGE TO PROPER LEFT
TO FACILITATE THE WORK,
COORDINATE WITH FMA
3300.01
0420.01
WB1 WB9
WB8
0401.03
0472.01
0401.03
0401.02
0472.01
0420.07
0472.01
0472.01
- R 6.
FI
EL
D V E R
IF
Y
FIELD VERIFY
+/- R 5.6
A3
A401
FIELD VERIFY
+/- 1' - 1"
FIELD
VER
IFY
+/- 4'
- 2 3 /4"
JOINT, TYPICAL
FIELD VERIFY
+/- 3' - 1"
FIE
LD
V E R
IFY
+/- 1' - 1"
FIRST FLOOR
0"
B1
A102
BRICK ARCH
STONE WALL
12" THICK MASONRY INFILL
TOP OF BRICK PAVERS
INVERTED BRICK ARCH
(BELOW GRADE / FLOOR LINE)
C4
A401
B4
A401
A4
A401
1' - 6" +/-
5'
BRICK VAULT
1/2" TEMPERED GLASS
IN ALUMINUM FRAME
GLAZING BUTT JOINT
EQ 5' - 0" EQ EQ 5' - 0" EQ
5'
9' 0" R
9' R
2600.08
+/- 9' - 8" FIELD VERIFY+/- 9' - 0 3/4" FIELD VERIFY
FIRST FLOOR
0"
1/8" RADIUS EASED TOP EDGECAST STONE
RE-LAYED BRICK
1" LEVELING SAND
SWEEP SAND INTO JOINTS
CRUSHED STONE BASE
5" X 1/4" BENT S.S. PLATE
EXTERIORINTERIOR
BRICK ARCH
3/8" THREADED DIA. X 1-3/4"
LONG ZINC PLATED LAG SHIELD
EXPANSION ANCHOR
HORSE SHOE SHIMS
BITUTHENE WATER
PROOF MEMBRANE
SEALANT
1 1/4" 2 3/4" 1 1/4"
3"
2 PART HEAD WITH CLADDING
CLADDING
1/2" TEMPERED GLASS
1/ 2"
3/ 8"
1/2"
BENT PLATE (BEYOND)
FIRST FLOOR
0"
1/2" TEMPERED GLASS
EXTERIORINTERIOR
5" X 1/4" S.S. PLATE
1"H X 1-1/4"W GLAZING CHANNEL
4"
1/ 2"
6"
WASHED CONCRETE SAND
(BEDDING SAND) BASE
CRUSHED BRICK BASE, INSTALL IN 2 LIFTS
12" THICK BRICK INFILL, SOLID
BRICK, FLEMISH BOND PATTERN
STRIKE JOINTS FLUSH
INVERTED BRICK ARCH (EXISTING)
30# ASPHALT FELT BOND BREAK
3'-0" WIDE
2" X 5" S.S. STEEL TUBE, WELDED TO PLATE
RELAID BRICK PAVER OR STONE
BLUESKIN SA RUBBERIZED ASPHALT
SELF-ADHESIVE MEMBRANE
BENT PLATE (BEYOND)
EXISTING ELECTRICAL CONDUIT,
BEYOND, PROVIDE SLEEVE IF NONE
PRESENT
CONTINUOUS SEALANT, BOTH SIDES
STONE JAMB
SEALANT
HORSESHOE SHIMS
1-1/2" X 3-1/2"
38" THREAD DIA. ZINC PLATED
LAG SHIELD EXPANSION
ANCHORS X 1-3/4" LENGTH
5/ 8"
LOCATE MASONRY ANCHORS @
HORIZONTAL MORTAR JOINTS, MIN.
8/JAMB
5" X 1/4" S.S. PLATE
1/ 2"
1/2" TEMPERED GLASS
CLEAR SILICON @
GLAZING JOINT
1/8"
CLEAR SILICON SEALANT
1" X 1-1/4" GLASS CHANNEL
STRETCHER FACE
SHINER FACE
NOTE: APPROXIMATE SIZE OF EXISTING
PAVERS TO BE MATCHED ARE:
• 2 1/4" TO 2 3/8" HEIGHT (STRETCHER FACE)
• 4" DEPTH (SHINER FACE)
• 8" TO 8 1/2" LENGTH
HANBURY
COPYRIGHT © 2021
DRAWN BY:
CHECKED BY:
PROJECT NO:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51
21 43 5
C
B
D
C
B
D
P R
IN
T E D
AA
C O N S U
LT
A N T
W E
S T
B A
S T
IT
P E
R
IE
N
H A
N C
E M
E
O J
E C
T
B
E R
N A
R D
R O
A D
F O
R T
M O
N R
O E
V
A
P R
O J E
C T
C O
D E
-B
-0
ISSUED FOR BID12/01/2023N/A
REVISED12/19/2023N/A
12/19/2023
/1 9/ :2 1:
P M
20027.02
ARC/AMB
GLR
ENLARGED PLANS
A401
1/4" = 1'-0"B1
ENLARGED FLOOR PLAN
1/4" = 1'-0"A1
INTERIOR ELEVATION / SECTION - EAST
3" = 1'-0"A3
PAVER SECTION DETAIL
WORK NOTES
NUMBER DESCRIPTION
0401.01 EXISTING STONE WALL
0401.02 EXISTING STONE THRESHOLD, TO REMAIN
0401.03 POWER WASH ALL WHITE-WASHED SURFACES IN WEST BASTION 8 AND 9, APPLY
NEW WHITE WASH, SEE SPECIFICATIONS
0420.01 RE-LAID PAVERS, HERRING BONE PATTERN
0420.05 RE-LAID PAVERS, HERRING BONE PATTERN, TO REPAIR AREA DISTURBED BY
INSTALLATION OF GLASS
0420.06 EXISTING ROWLOCK PAVERS, TO REMAIN
0420.07 SINGLE ROWLOCK TO TRANSITION BETWEEN HERRING BONE ORIENTATION
0472.01 CAST STONE PAVERS, MATCH SIZE AND SHAPE OF ORIGINAL IN WB1, SAME
THICKNESS AS BRICK PAVERS, MIRROR LAYOUT ON CENTERLINE OF CASEMATE
2600.08 EXISTING ELECTRICAL CONDUIT, PROVIDE A NEW SLEEVE IF NONE EXISTING, NO
WEIGHT SHALL BEAR ON THE CONDUIT
3300.01 EXISTING MANHOLE, TO REMAIN
4' 8' 12'0'
4' 8' 12'0'
3" = 1'-0"C4
ARCH WINDOW HEAD DETAIL
0' 1'4" 8"
3" = 1'-0"B4
ARCH WINDOW SILL DETAIL
0' 1'4" 8"
0' 1'4" 8" 3" = 1'-0"A4
ARCH WINDOW JAMB & GLAZING BUTT JOINT DETAIL
0' 1'4" 8"
B3
HERRINGBONE PAVING PATTERN
NOT TO SCALE
| Sheets |
| A101 - FLOOR PLAN - DEMOLITION AND NEW WORK |
| A102 - ARCHITECTURAL LIGHTING PLAN |
| A401 - ENLARGED PLANS |
| G001 - COVER SHEET, PROJECT DATA AND DRAWING INDEX |
File details come from the government source that posted it. Updated .