2022 Annual FLS Testing Report LaneActivityCenter.pdf
PDF 222 KB Posted
- Solicitation number
- S-44300-00005148
- Issued by
- Union County, Oregon
About this file
This document is an NFPA 72 fire alarm inspection report for the Oregon Health Authority (OHA) Pendleton System 3 LAC building located at 2585 Westgate in Pendleton, Oregon. The report was completed on September 20, 2022 by Siemens Industry, Inc. and covers the inspection and testing of the fire alarm control panel, notification appliances, and initiating devices in the building. The report indicates that all components were found to be functioning properly during the inspection.
The related state and local contract opportunity is an RFP issued by the Oregon State Hospital to contract with an experienced and qualified contractor to perform fire protection system maintenance upgrades for three buildings located at 2585 Westgate in Pendleton, Oregon. The project will involve replacement of detection devices and system equipment based on a like-for-like swap of existing components to bring the current fire protection system up to code. The jurisdiction for this contract is Umatilla County, Oregon.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2022 Annual FLS Testing Report Cottage 2475.pdf | ||
| CP-30 Troubleshooting guide.pdf | ||
| CP-30 data sheet.pdf | ||
| G - Responsibility Inquiry.doc | DOC document | |
| C2022842_RFP_CommunityLenderLoanLossReserveAccountProgram.docx | DOCX document | |
| B - Disclosure Exemption Affidavit.doc | DOC document | |
| C- Proposer Info and Cert Sheet.pdf | ||
| E - Price Proposal.docx | DOCX document | |
| H - Background Check Form~1.pdf | ||
| A - Sample Contract~2.pdf | ||
| Bill of Materials - estimate.pdf | ||
| Drawing Lane Activity Center.pdf | ||
| Drawing Photo Cottage 2495.pdf | ||
| F - COBID outreach.doc | DOC document | |
| 2022 Annual FLS Testing Report Cottage 2495.pdf | ||
| D - Reference Check form.doc | DOC document | |
| Drawing Photo Cottage 2475.pdf | ||
| Intent to Award Notice.pdf | ||
| RFP S-44300-00005148~4.pdf |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 7
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: OHA PENDLETON SYSTEM 3 LAC Panel Name: 01 - OHA PENDLETON SYSTEM 3 LAC Building
Inspection/Test Start Date/Time: 20 Sep 2022 0700 Inspection/Test Completion Date/Time: 20 Sep 2022 1500
Contract Info: OR1P-FIS-OSH Pendleton (2600114256) Notification Number: 5102303440
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: Oregon Health Authority 2585 Westgate (4433-97801-00014)
Address: LAC 2585 Westgate Pendleton Or. 97801
Description of property:
Name of property representative: OREGON HEALTH AUTHORITY (30581098), None
Address: 2585 WESTGATE, PENDLETON, OR 97801
Phone: None Fax: None E-mail: None
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 9755 SW Barnes Rd, Suite 205, Portland, OR 97225
Phone: 503 207 1900 Fax: 503 207 1901 E-mail: NA
Monitoring organization: Moon Security
Address: NA
Phone: 541 276-0295 Fax: NA E-mail: NA
Account number: 2575 Phone line 1: NA Phone line 2: NA
Means of transmission: Parallel Phone
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software: NA
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: OHA PENDLETON SYSTEM 3 LAC Panel Name: 01 - OHA PENDLETON SYSTEM 3 LAC Building
Panel Location and Address: Fire Panel Room, LAC 2575 Westgate, Pendleton Or. 97801
Manufacturer: Siemens Model number: System 3
4.2 Software and Firmware
Firmware revision number: NA
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 120v Amps: 20a Location: Fire Panel Room
Overcurrent protection type: Breaker Amps: 20a
Disconnecting means location: House Panel
4.3.2 Secondary Power
Type: Storage Battery Location: Fire Panel Room
Battery type (if applicable): Sealed Lead Acid Manufactured Date:
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 5
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 7
4.4 Notification Appliance Power Extender Panels
4.4.1 Primary Power
ID Location Input Volts
Panel Amps
Over-current Type
Over-current Amps
Primary Supply Location Disconnect Location
01:Bldg LAC FACP Room 120v Breaker House Panel
4.4.2 Secondary Power
ID Location Battery Type
Manufactured Date
Voltage Rating
Amp Rating
Standby Hours
Alarm Minutes
01:Bldg LAC FACP Room SLA Sep 1 2021 12v 8ah 24 5
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: Moon Security 541-276-0295 Time: 0700
Building management Contact: NA Time: NA
Building occupants Contact: Aaron Williams 541-310-0103 Time: 0700
Authority having jurisdiction (AHJ) Contact: NA Time: NA
Other, if required Contact: NA Time: NA
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional Test Comments
Control unit Functional None
Disconnect switches Functional None
Fuses Functional None
Ground-fault monitoring Functional None
Interface Equipment Functional None
Lamps/LEDs/LCDs Functional None
Local annunciator Functional None
Primary Power Functional None
Remote annunciators Functional N/A
Remote power panels Functional N/A
Supervision Functional None
Trouble signals Functional None
6.2 Secondary Power
Description Visual Inspection or Functional Test Comments
Battery condition Functional None
Charger test Functional None
Discharge test Functional None
Load voltage Functional None
Remote panel batteries Functional N/A
6.3 Notification Appliance Power Extender Panels Secondary Power
ID Location Battery Voltage
Battery Amps
Test Method
Pass/ Fail
01:Bldg LAC FACP Room Functional Pass
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 7
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
6.7 Supervising Station Monitoring
Description Received Time / Elapsed
Time Pass/Fail Comments
Alarm signal Yes NA / NA Pass None
Alarm restoration Yes NA / NA Pass None
Trouble signal Yes NA / NA Pass None
Trouble restoration Yes NA / NA Pass None
Supervisory signal Yes NA / NA Pass None
Supervisory restoration Yes NA / NA Pass None
6.8 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal NA NA
Alarm restoration NA NA
Trouble signal NA NA
Trouble restoration NA NA
Supervisory signal NA NA
Supervisory restoration NA NA
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: Moon Security 541 276-0295 Time: 1500
Building management Contact: NA Time: NA
Building occupants Contact: Aaron Williams 541-310-0103 Time: 1500
Authority having jurisdiction (AHJ) Contact: NA Time: NA
Other, if required Contact: NA Time: NA
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 20 Sep 2022 Time: 1500
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed: Jason Carpenter Nicet 141882 Date: 09/20/2022
Printed name: Jason Carpenter Title: Technician License No.: Nicet# 141882
Organization: SIEMENS Phone: 503 207 1900
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service, Programming
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed: Printed name: Aaron Williams 541-310-0103 Date:
Organization: OREGON HEALTH AUTHORITY (30581098) Phone: None
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 7 owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.
Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
Sensitivity test performed on all smoke detectors. 9/29/2020 Pass.
12.2 Comments
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 7
NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: Oregon Health Authority 2585 Westgate (4433-97801-00014)
Address: LAC 2585 Westgate Pendleton Or. 97801
2. NOTIFICATION APPLIANCE TEST RESULTS
2.1 Notification Appliances Equipment Summary by Type
Total Qty
ALL
Functionally Tested Qty
ALL
Functionally Tested %
100%
Visually Tested
Qty
Visually Tested %
Failed Qty
Failed %
0%
Device or System Type
Horn / Strobes
2.2 Notification Appliances Testing Results by Type
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 7
INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: Oregon Health Authority 2585 Westgate (4433-97801-00014)
Address: LAC 2585 Westgate Pendleton Or. 97801
2. INITIATING DEVICE TEST RESULTS
2.1 Initiating Devices Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
1 1 100% 0 0% 0 0% Control Valve Switches
50 50 100% 0 0% 0 0% System Smoke Detectors (P)
1 1 100% 0 0% 0 0% Waterflow Devices
2.2 Initiating Devices Testing Results by Type
Control Valve Switches
Row Date Dev.# Location Visual/ Functional
Pass/
1 12/30/22 01-104-021 TAMPER SWITCH LAC C WING Functional Pass
System Smoke Detectors (P)
Functional
Pass/ Fail
1 12/30/22 01-102-001 FACP ROOM HEAT LAC A WING Functional Pass
2 12/30/22 01-102-002 LOBBY SMOKE LAC A WING Functional Pass
3 12/30/22 01-102-003 LOBBY PULL STATION LAC A WING Functional Pass
4 12/30/22 01-102-004 GROUP ROOM #1 SMOKE LAC A WING Functional Pass
5 12/30/22 01-102-005 GROUP ROOM #1 PULL STATION LAC A WING Functional Pass
6 12/30/22 01-102-006 LOBBY SMOKE LAC A WING Functional Pass
7 12/30/22 01-102-007 LOBBY SMOKE LAC A WING Functional Pass
8 12/30/22 01-102-008 OXYGEN ROOM HEAT LAC A WING Functional Pass
9 12/30/22 01-102-009 EAST STORAGE ROOM HEAT LAC A WING Functional Pass
10 12/30/22 01-102-010 EAST EXIT PULL STATION LAC A WING Functional Pass
11 12/30/22 01-102-011 EAST HALL SMOKE LAC A WING Functional Pass
12 12/30/22 01-102-012 ADMIN OFFICE SMOKE LAC A WING Functional Pass
13 12/30/22 01-102-013 GROUP ROOM #2 SMOKE LAC A WING Functional Pass
14 12/30/22 01-102-014 GROUP ROOM #2 HEAT LAC A WING Functional Pass
15 12/30/22 01-103-001 HALLWAY SMOKE LAC B WING Functional Pass
16 12/30/22 01-103-002 EAST EXIT SMOKE LAC B WING Functional Pass
17 12/30/22 01-103-003 EAST EXIT PULL STATION LAC B WING Functional Pass
18 12/30/22 01-103-004 GYM SMOKE LAC B WING Functional Pass
19 12/30/22 01-103-005 ELECTRICAL ROOM HEAT LAC B WING Functional Pass
20 12/30/22 01-103-006 HALLWAY SMOKE LAC B WING Functional Pass
21 12/30/22 01-103-007 HALLWAY SMOKE LAC B WING Functional Pass
22 12/30/22 01-103-008 HALLWAY SMOKE LAC B WING Functional Pass
23 12/30/22 01-103-009 EASTSIDE ROOM SMOKE LAC B WING Functional Pass
24 12/30/22 01-103-010 SOUTHSIDE ROOM SMOKE LAC B WING Functional Pass
25 12/30/22 01-103-011 SOUTHSIDE ROOM SMOKE LAC B WING Functional Pass
26 12/30/22 01-103-012 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
27 12/30/22 01-103-013 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
28 12/30/22 01-103-014 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
29 12/30/22 01-103-015 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
30 12/30/22 01-103-016 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 7
System Smoke Detectors (P)
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
31 12/30/22 01-103-017 WESTSIDE ROOM SMOKE LAC B WING Functional Pass
32 12/30/22 01-103-022 EASTSIDE ROOM SMOKE LAC B WING Functional Pass
33 12/30/22 01-104-001 NORTH ENTRANCE SMOKE LAC C WING Functional Pass
34 12/30/22 01-104-002 NORTH ENTRANCE PULL LAC C WING Functional Pass
35 12/30/22 01-104-003 NORTH OFFICE SMOKE LAC C WING Functional Pass
36 12/30/22 01-104-004 HALLWAY BY WING DOORS SMOKE LAC C WING Functional Pass
37 12/30/22 01-104-005 OFFICE LEFT OF N. EXIT SMOKE LAC C WING Functional Pass
38 12/30/22 01-104-006 FILE STORAGE SMOKE LAC C WING Functional Pass
39 12/30/22 01-104-007 STORAGE ROOM HEAT LAC C WING Functional Pass
40 12/30/22 01-104-008 BREAK ROOM SMOKE LAC C WING Functional Pass
41 12/30/22 01-104-009 BREAK ROOM SMOKE LAC C WING Functional Pass
42 12/30/22 01-104-010 N.W. OFFICE SMOKE LAC C WING Functional Pass
43 12/30/22 01-104-011 HALLWAY SMOKE LAC C WING Functional Pass
44 12/30/22 01-104-012 REDS OFFICE SMOKE LAC C WING Functional Pass
45 12/30/22 01-104-013 CONF. ROOM WEST SMOKE LAC C WING Functional Pass
46 12/30/22 01-104-015 N.W. EXIT PULL STATION LAC C WING Functional Pass
47 12/30/22 01-104-016 N.W. EXIT SMOKE LAC C WING Functional Pass
48 12/30/22 01-104-017 N.W. STORAGE SMOKE LAC C WING Functional Pass
49 12/30/22 01-104-018 N.W. EXIT PULL STATION DAS AREA LAC C WING Functional Pass
50 12/30/22 01-104-019 HALLWAY SMOKE DAS AREA LAC C WING Functional Pass
Waterflow Devices
Functional
Pass/
1 12/30/22 01-104-020 WATERFLOW LAC C WING Functional Pass
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
File details come from the government source that posted it. Updated .