This is a Scope of Work document for the North County Government Center Card-Access Repair & Replace project in Palm Beach County, Florida. The project requires comprehensive removal and replacement of the existing Sielox card access system with a new Lenel-based access control system. Key deliverables include removing all legacy Sielox components (desktop, monitors, card access panels, power supplies, and related hardware), replacing seven Assa Abloy wireless card readers with wired alternatives, installing new Lenel Access Panels with Intelligent Controllers, and upgrading door hardware and electronic locks throughout the facility. The scope specifies installation of new card readers at multiple locations, replacement of magnetic locks on exterior doors with crash bars equipped with Delay Egress Units (DEU), removal of interior magnetic locks from corridor-to-stairwell doors, installation of door position switches on stairwell roof doors, and provision of a desktop computer with Lenel Card Access Client at the security desk. Additionally, the project includes installation of ten panic buttons at various locations including victim services, elections, clerk safe, tax collector, and courtroom areas. All work must be completed according to PBC ESS Card Access Specification Section 28 1300 and in compliance with 2017 Florida Building Code and Fire Prevention Code requirements for delayed egress locking systems.
The document specifies that all Lenel programming and installation must be completed by an authorized Lenel dealer and installer, with programming conducted either on-site or at Palm Beach County's ESS facility in West Palm Beach. All card access cabling must be labeled at both ends with door location identification, and wiring must meet or exceed manufacturer specifications with plenum-rated cabling required where not installed in conduit. The delayed egress locking system must be configured to allow passage within 15 seconds of pressure applied to exit devices, with card reader operation providing immediate unlock capabilities and alarm notifications to the system GUI. The document does not include pricing information, contract term details, set-asides, incumbent information, or funding sources.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REVISED
2. SCOPE OF WORK Amended
a. Remove Sielox Card Access desktop, monitor, RS232 Black Box serial communicators and UPS from Security desk.
b. Remove all existing Sielox card access panels, power supplies, elevator and door relays, proximity card readers and all other components associated with the existing Sielox card access system. See Exhibit “1” for Card Reader locations.
c. Remove 7 Assa Abloy wireless card readers and replace with wired Card
Readers. Install DPS, REX and new door lock hardware on these doors.
d. Reference Exhibit “1” for existing Card Access Panels, doors, and rooms proposed for replacement of the exiting card access system.
e. Remove and replace all Card Reader, DPS and REX (PIR) and install new card readers, REX and DPS on new access doors. Refer to PBC ESS Card Access Specification SECTION 28 1300 - Access Control Revision (1/20/2022).
f. Replace Lock Hardware on door 1205 to be locked on both sides of the door.
g. Provide and install a card reader on the inside of door 1036. Install a HID SIGNO card reader. As depicted on Exhibit “1”. Refer to PBC ESS Card Access Specification SECTION 28 1300 - Access Control Revision (01/20/2022).
h. Complete installation on the existing door Von Duprin Crash Bar 99 Series with a DEU (Delay Egress Unit) Crash-bar on door 1036. Program DEU to alarm on card access monitor as soon is engaged. Tie DEU to fire alarm Relay. See specifications on Exhibit “3” for door DEU info hardware.
i. Remove all Magnetic Locks from exterior doors and replace crash bars with a
DEU crash bar. All exterior doors are fail secure. Provide submittals for the new
DEU.
j. Remove interior magnetic locks and card readers from corridor to stairwell doors 2036, 2034.
k. Remove REX push button and Install PIR on all card access doors locations.
l. Provide and install new Lenel Access Panels including all Lenel Intelligent Controllers. See Exhibit “1” for room locations.
m. Provide and install Lenel 2-reader boards inside newly installed Lenel panel.
Refer to PBC ESS Card Access Specification SECTION 28 1300 - Access Control Revision (01/20/2022).
n. Provide and install new Lenel Input and output pc boards to accommodate minimum of 176 inputs and minimum 76 outputs. See Exhibit “1” for all in/out locations
o. Provide and install 3 Door Position Switches with infrastructure on 3 Stairwell roof doors. Add doors to the Lenel alarm monitor and program doors to alarm at all times when opened.
p. Provide and install Securitron (UL) Regulated, Filtered Power Supply 1AMP
24VDC with a (UL) Listed Enclosure All Lenel boards shall be open architectural Mercury based boards.
q. Provide and install a desktop computer with Lenel Card Access Client and
OnGuard GUI on the Security desk in the main lobby.
r. Configure Lockdown procedure for Lockdown buttons located at security desk and PBSO station. Reference Exhibit “1” for Card Access Panels, doors, and rooms proposed for replacement of the exiting card access system.
s. Delay Egress Locking: Doors equipped with exit devices, delayed egress locking systems, and card readers shall allow passage in not more than 15 seconds after pressure is applied to the exit device. Application of pressure on the exit device shall also initiate an audible signal in the vicinity of the door.
t. Card readers shall be connected to the delayed egress locking system so that the door shall unlock immediately upon card being read and door open upon pressure being applied to the exit device. There shall be no audible signal with card reader operation. An alarm shall be sent to the GUI at all times when doors are opened.
u. Delay Egress Locking system shall be installed in strict conformance with the
2017 Florida Building Code Section 1010.1.9.7 and the 2017 Florida Fire Prevention Code section 101-7.2.1.6.1 as amended by Palm Beach County
v. All card access cabling shall be labeled on both ends of cables identifying door location.
w. All wiring shall meet or exceed manufacturers’ recommendations. Plenum rated required when not in conduit.
x. Lenel card access system programming and installation shall be completed by an authorized Lenel dealer and installer.
y. Lenel card access system programming shall be done on site or at Palm Beach
County’s ESS facility located at 2633 Vista Parkway WPB, FL 33411.
z. Provide and install ten (10) new panic buttons at the following locations; Room 1436 (Victim Services) one (1) at the front desk, Room 2401 (Supervisor of Elections) two (2) at the front counter, Room 1107 (Clerk Safe) one (1). Room 1102 (Tax Collector) four (4) at the desks. Two (2) panic button on Courtroom 2, also remove existing panic button in the wall. All panic buttons are supervised.
aa. Install card readers on doors: 1210 County Criminal & 1202 County Civil.