2021-08-27_FPBB142001-B-3_Plans.pdf
PDF 23 MB Posted
- Attached to
- Ft Drum Construct Operations Space and Mobile Ground Control Station Shelter Federal contract opportunity
- Solicitation number
- W50S8N23B0001
About this file
This document outlines a federal construction contract solicitation. The solicitation seeks bids for Project #FPBB142001 to construct an operations space and mobile ground control station shelter at Wheeler Sacks Army Airfield at Fort Drum, New York. The construction contract value is estimated between $500,000 and $1,000,000. This is a 100% total small business set-aside with a NAICS code of 236210 and $45 million average annual revenue size standard. Bids are due by the date specified in the solicitation, which will be posted at https://sam.gov along with any notices and amendments. Award will be made to the responsible bidder submitting the most advantageous bid based on price and price-related factors only. Funds are not presently available but are expected to be appropriated by September 30, 2023; no award will be made without available funds. This project is on the New York Army National Guard's priority list to award if funds become available within the awardable price range.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FPBB142001 Bid Abstract.pdf | ||
| W50S8N23B0001 Questions and Answers Updated 10 Aug.pdf | ||
| Site Visit Attendee List.pdf | ||
| W50S8N23B0001 Questions and Answers Updated 2 Aug.pdf | ||
| W50S8N23B00010005.pdf | ||
| W50S8N23B00010004.pdf | ||
| W50S8N23B0001 Questions and Answers.pdf | ||
| W50S8N23B00010003.pdf | ||
| W50S8N23B00010002.pdf | ||
| W50S8N23B00010001.pdf | ||
| 2021-08-27_FPBB142001-B-3_Specs_Clean.pdf | ||
| W50S8N23B0001 FPBB142001.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fort Drum Military Reservation
Contract No. W9133L-15-D-0004
C o n t r a c t D r a w i n g s F o r
Fort Drum, New York June 2021
Client Logo
FPBB142001
Construct Operations Space/MGCS Shelter
NEW YORK AIR NATIONAL GUARD
B-2 SUBMITTAL
PROJECT LOCATION MAP
PROJECT VICINITY MAP
PROJECT SITE
PROJECT SITE
Task Order No. W50S8N20F0014 HDR Project No. 10256943
B-3 SUBMITTAL
August 2021
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
N/A
G-001
SHEET INDEX
FPBB142001
I N D E X O F D R A W I N G S
GENERAL
G-000 COVER SHEET
G-001 SHEET INDEX
G-002 LEGEND & GENERAL NOTES
DEMOLITION
X-101 DEMOLITION PLAN & ELEVATION
X-102 EXISTING SITE UTILITY DEMOLITION PLAN
CIVIL
C-101 SITE ACCESS, STAGING & HAUL ROUTE
C-102 EXISTING CONDITIONS
C-103 SITE PLAN AND SEDIMENT & EROSION CONTROL PLAN
C-501 SITE AND SE&SC DETAILS
STRUCTURAL
S-100 STRUCTURAL NOTES
S-101 FOUNDATION PLAN
S-501 TYPICAL CONCRETE DETAILS
S-502 FOUNDATION DETAILS
ARCHITECTURAL
A-101 FLOOR PLAN
A-102 REFLECTED CEILING PLAN
A-104 ROOF PLAN
A-201 EXTERIOR ELEVATIONS
A-301 PROPOSED BUILDING SECTIONS
A-302 PROPOSED BUILDING SECTIONS
A-501 WALL SECTIONS AND DETAILS
A-502 PLAN DETAILS
A-503 PLAN DETAILS
A-701 PARTITION, DOOR AND FINISH SCHEDULES
MECHANICAL
M-101 MECHANICAL FLOOR PLAN
M-201 MECHANICAL SECTIONS
M-301 MECHANICAL SCHEDULES
M-401 MECHANICAL DETAILS
FIRE PROTECTION
F-100 FIRE PROTECTION NOTES & LEGEND
F-101 FIRE PROTECTION & FIRE ALARM FLOOR PLAN
ELECTRICAL
E-001 ELECTRICAL NOTES & LEGEND
E-101 POWER PLAN
E-102 LIGHTING PLAN
E-501 ELECTRICAL DETAILS
TELECOMMUNICATIONS
ET-101 TELECOMMUNICATIONS PLAN
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1" = 30'
G-002
LEGEND & GENERAL NOTES
FPBB142001
EXISTING SANITARY SEWER SERVICE LINE
EXISTING SANITARY SEWER MAIN
EXISTING UNDERGROUND ELECTRIC
EXISTING UNDERGROUND COMMUNICATION LINE
EXISTING PROPANE GAS LINE
EXISTING FIRE DEPARTMENT CONNECTION LINE
EXISTING GAS LINE
EXISTING STORM DRAINAGE LINE
EXISTING WATER SERVICE
EXISTING SANITARY MANHOLE
EXISTING MONITORING WELL
EXISTING ELECTRICAL VAULT
EXISTING WATER VALVE
EXISTING HYDRANT
EXISTING TRANSFORMER
EXISTING COMMUNICATION MANHOLE
EXISTING COMMUNICATION VAULT
EXISTING STORMWATER MANHOLE
EXISITNG BOLLARD
PROPOSED SANITARY SEWER SERVICE LINE
PROPOSED SANITARY SEWER CLEANOUT
PROPOSED SILT FENCE
PROPOSED SIDEWALK
SS
SF SF SF
GENERAL NOTES:
CIVIL NOTES:
1. IF PAVEMENT REMOVAL IS REQUIRED TO CONSTRUCT BUILDING ADDITION,
REMOVAL SHALL BE PERFORMED BY SAW CUT. EXTEND REMOVAL LINES TO
INCLUDE ANY ADJOINING BROKEN OR DETERIORATING PAVEMENT.
2. ALL DEMOLITION RUBBLE, DEBRIS, AND EXCESS SOILS SHALL BE PROMPTLY
REMOVED FROM THE SITE. STOCKPILED MATERIALS SHALL BE PLACED IN
APPROVED LOCATIONS WITHOUT INTERFERING WITH OTHER CONTRACTOR
WORK, OR WITH EXISTING DRAINAGE.
3. ALL SHORING AND TEMPORARY BRACING IS THE CONTRACTOR'S
RESPONSIBILITY.
4. THE VEHICLE ACCESS INTO THE EXISTING HANGER (10' x 16') WAS
ANTICIPATED BY THE ORIGINAL HANGER CONSTRUCTION. CONTRACTOR TO
VERIFY LOCATION. CONTRACTOR TO VERIFY THAT THE EXISTING HANGER
EXTERIOR WALL IS FRAMED AND STABLE PRIOR TO REMOVALS.
5. STRIP AND STOCKPILE SUFFICIENT EXISTING ORGANIC TOPSOILS FOR
RESPREADING AS REQUIRED ON DISTURBED AND REGRADED AREAS TO BE
ESTABLISHED AS LAWN AND FOR REPAIR OF EXISTING LAWNS ASSOCIATED
WITH STOCKPILE/LAYDOWN AREA.
6. ALL FILL/BACKFILL OF EXCAVATIONS AND VOIDS RESULTING FROM
REMOVALS AND RELATED WORK UNDER PROPOSED OR REPLACEMENT
PAVING AREAS SHALL ONLY BE COARSE AGGREGATE FILL OR SUBBASE
MATERIAL THOROUGHLY COMPACTED IN ACCORDANCE WITH THE TECHNICAL
SPECIFICATIONS OR SITE GEOTECH REPORT.
7. PROTECT ALL FACILITIES AND IMPROVEMENTS ON AND ADJOINING THE
PROPERTY WITH ARE NOT SPECIFICALLY IDENTIFIED FOR REMOVAL. VERIFY
LOCATIONS AND DEPTHS OF ALL SUBSURFACE UTILITIES TO REMAIN PRIOR
TO ANY ADJACENT REMOVAL AND EXCAVATION WORK.
8. ALL EXISTING FEATURES SHALL REMAIN UNLESS OTHERWISE NOTED. IF THE
CONTRACTOR DAMAGES ANY OF THE EXISTING ON-SITE FACILITIES TO
REMAIN, WHETHER SHOWN ON THE PLANS OR NOT, THE CONTRACTOR SHALL
REPAIR AND/OR REPLACE SUCH ITEMS AT HIS OWN EXPENSE AND ASSUME
ALL RESPONSIBILITY FOR SUCH DAMAGE WITHOUT ANY ADDITIONAL COST TO
THE OWNER. REPLACEMENT MATERIAL SHALL BE SAME QUALITY AND
QUANTITY AS ORIGINAL.
9. ALL NON-PAVED AREAS ARE TO BE LAWN UNLESS OTHERWISE NOTED.
10. CONTRACTOR SHALL BLEND NEW WORK SMOOTHLY AND EVENLY WITH
ADJACENT EXISTING LINES AND GRADES.
11. THIS ADDITION DOES NOT HAVE ANY PROPOSED RESTROOMS OR SINKS. AS
SUCH, THERE IS NO ANTICIPATED EXTERIOR UTILITY WORK FOR WATER OR
SANITARY SEWER. WATER FOR FIRE PROTECTION WILL BE PROVIDED
THROUGH CONNECTIONS FROM THE ADJACENT MECHANICAL ROOM.
ELECTRICAL AND TELECOMMUNICATIONS CONNECTIONS WILL BE MADE
THROUGH CONNECTIONS FROM THE ADJACENT ELECTRICAL ROOM. REFER
TO THE MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL PLANS.
12. EXTERIOR ELECTRICAL WORK IS ANTICIPATED TO RELOCATE THE EXISTING
COMMUNICATION PEDESTAL INSIDE THE PROPOSED MGCS SHELTER. REFER
TO THE ELECTRICAL PLANS FOR MORE INFORMATION.
13. EISA 438 IS NOT APPLICABLE TO THIS PROJECT SINCE THE PROPOSED
BUILDING FOOTPRINT DOES NOT EXCEED 5,000 SQUARE FEET. THE ORIGINAL
DESIGN OF THE MQ-9 LRE & HANGAR INCLUDED THE PROPOSED ADDITION AS
AN OPTION THAT WAS NOT EXECUTED, BUT ACCOUNTED FOR THE
IMPERVIOUS AREA OF THE ADDITION IN THE STORMWATER MANAGEMENT
DESIGN AT THE TIME.
14. PRIOR TO THE START OF CONSTRUCTION, THE CONTRACTOR SHALL OBTAIN
ALL REQUIRED EXCAVATION PERMITS, AS REFERENCED IN THE FORT DRUM
PUBLIC WORKS EXCAVATION PERMIT POLICY.
15. THE CONTRACTOR SHALL ADHERE TO THE FORT DRUM PUBLIC WORKS
AS-BUILT REQUIREMENTS WITH UTILITY STANDARDS.
ARCHITECTURAL NOTES:
1. THE ADDITION'S EXTERIOR METAL BUILDING ENVELOPE, INCLUDING
FENESTRATION AND TRIM SHALL MATCH THE COLOR, STYLE AND PATTERN
OF EXISTING ADJACENT CONSTRUCTION. CONTRACTOR SHALL FIELD VERIFY
PRIOR TO BID.
2. THE ADDITION'S METAL ROOFING AND SNOW GUARDS SHALL MATCH THE
EXISTING ADJACENT UTILITY ROOMS IN HEIGHT, SLOPE, PATTERN, COLOR
AND FINISH. CONTRACTOR SHALL FIELD VERIFY PRIOR TO BID.
3. THE CONTRACTOR SHALL ASSURE THAT THE FOLLOWING BUILDING
COMPONENTS ARE PROVIDED AND COORDINATED BY THE METAL BUILDING
FABRICATOR:
A. A CONTINUOUS AIR BARRIER IN COMPLIANCE WITH THESE
SPECIFICATIONS.
B. BUILDING FENESTRATION FEATURES COMPLIANT WITH THESE
SPECIFICATIONS (DOORS AND WINDOWS).
C. A PREFABRICATED ROOF PANEL SYSTEM PROVIDING A CONTINUOUS
THERMAL BARRIER.
D. COORDINATE PRIMARY STEEL FRAMING WITH GIRTS AND SUB-GIRTS AS
NEEDED TO ASSURE THAT THE ROOF LINES LINE UP AND ALL ROOFING
COMPONENTS ARE ANCHORED TO THE STRUCTURE.
E. A PREFABRICATED WALL PANEL SYSTEM TO PROVIDE A CONTINUOUS
THERMAL BARRIER.
F. WALL TO WALL, ROOF TO ROOF, AND ROOF TO WALL EXPANSION
JOINTS.
SHOULD THE CONTRACTOR DETERMINE TO ADDRESS ANY OF THE ABOVE
DIRECTLY, PROVISION AND COORDINATION OF THESE ITEMS WILL FALL ON
THE CONTRACTOR AND SHALL BE AT NO ADDITIONAL COST TO THE
GOVERNMENT.
4. ALL SIGNAGE SHALL COMPLY WITH THE FT DRUM SUPPLEMENT 420-1 SIGN
REGULATION.
A. ALL ROOMS SHALL BE PROVIDED WITH A ROOM NUMBER SIGN IN
COMPLIANCE WITH FD SUPL. 420.1. COORDINATE ROOM NUMBERS
WITH FT. DRUM PUBLIC WORKS.
B. ALL ROOMS SHALL BE PROVIDED WITH A ROOM IDENTIFICATION SIGN
IN COMPLIANCE WITH FD SUPL. 420-1
C. INTERIOR SIGNAGE SHALL BE IN COMPLIANCE WITH UFC 3-120-01
(THE FD STANDARD DESCRIBES THE SIZE AND MATERIAL FOR THE
ROOM NUMBER AND ROOM IDENTIFICATION SIGNS)
D. EXTERIOR SAFETY SIGNS SHALL COMPLY WITH AR 385-30, SAFETY
COLOR MARKINGS AND SIGNS
FIRE PROTECTION NOTES:
1. A 1 HOUR FIRE SEPARATION SHALL BE MAINTAINED BETWEEN THE EXISTING
HANGER AND THE NEW ADDITION. THE COILING VEHICLE ACCESS DOOR
SHALL BE A 45 MINUTE FIRE SHUTTER PROVIDED WITH A FUSIBLE LINK. THE
PERSONNEL DOOR SHALL BE FIRE PROOF SELF CLOSING WITH A 45 MINUTE
RATING.
ABBREVIATIONS:
A, AMP AMPERE
ACI AMERICAN CONCRETE INSTITUTE
AFF ABOVE FINISHED FLOOR
AIC AMPS INTERRUPTING CAPACITY
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
AWG AMERICAN WIRE GAGE
CFM CUBIC FEET PER MINUTE
CKT CIRCUIT
DOD DEPARTMENT OF DEFENSE
EF EXHAUST FAN
FC FOOT-CANDLES
FDECU FIELD DEPLOYABLE ENVIRONMENTAL CONTROL UNITS
FTU FLIGHT TRAINING UNIT
GC GENERAL CONTRACTOR
GND GROUND
GPM GALLONS PER MINUTE
GWB GYPSUM WALL BOARD
HDPE HIGH-DENSITY POLYETHYLENE
HVAC HEATING, VENTILATING, AND AIR CONDITIONG
KSI KILOPOUND PER SQUARE INCH
KVA KILOVOLT AMPERES
KW KILOWATT
LED LIGHT-EMITTING DIODE
LRE LAUNCH AND RECOVERY ELEMENT
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LTG, LTS LIGHTING
MEP MECHANICAL, ELECTRICAL, AND PLUMBING
MGCS MOBILE GROUND CONTROL STATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OCP OVER CURRENT PROTECTION
PSF POUND PER SQUARE FOOT
PSI POUND PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED STEEL
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS'
NATIONAL ASSOCIATION
TOS TOP OF SLAB
UFC UNIFIED FACILITIES CRITERIA
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VA VOLT AMPERE
VIF VERIFY IN FIELD
SUPR. ROOM
FIRE
HANGAR
REMOVE EXIST. DOOR
AND DOOR FRAME,
PATCH WALLS AS REQUIRED
SAW CUT EXIST. METAL
PANEL TO PROVIDE
14'-0" W x 10'-0" OPENING
REMOVE PART OF SIDEWALK,
SEE CIVIL DRAWINGS
15'-1"
11"
11"
7"
7"
8'-6"2'-0" 1'-5"
3'-4"
OPENING
2'-5" 14'-0"
OPENING
SUPR. ROOM
FIRE
HJ GK
'-0
15'-0"
1' -5
8'-7" 11"11" 2'-0" 4'-5" 1'-5"
'-5
40'-3"
1'-0"
REMOVE EXISTING
METAL WALL PANEL,
TYP.
EXISTING METAL
PANEL FACADE
REMOVE EXIST. DOOR,
DOOR FRAME AND
METAL WALL PANEL
HJ GK
ISSUE1
ISSUE2
ISSUE3
ISSUE4
ISSUE5
ISSUE6
ISSUE7
ISSUE8
ISSUE9
X-101
DEMOLITION PLAN AND ELEVATION
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 DEMOLITION FLOOR PLAN
SCALE: 1/4" = 1'-0"
NORTH
0 4' 8'2'
NOTE:
* REMOVE METAL WALL PANEL.
1 DEMOLITION - SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
0 4' 8'2'
PROPOSED AREA OF
CONSTRUCTION
LIMITS
1" = 30'
X-102
EXISTING SITE UTILITY DEMOLITION PLAN
FPBB142001
1 EXISTING SITE UTILITY DEMOLITION PLAN
SCALE: 1" = 30'
NORTH
GENERAL NOTES:
1. PROPOSED AREA OF CONSTRUCTION LIMITS CONSISTS
PRIMARILY OF GRASS COVER. SOME DEMOLITION OF THE
EXISTING HANGAR WILL BE NECESSARY TO COMPLETE
CONSTRUCTION. REFER TO SHEET X-101 FOR THE EXISTING
HANGAR DEMOLITION PLAN & ELEVATION.
2. UTILITY, SURFACE, AND TOPOGRAPHIC SURVEY HAVE NOT
BEEN PERFORMED IN CONJUNCTION WITH THIS DESIGN. THE
UTILITY AND TOPOGRAPHIC DATA SHOWN ON THIS SHEET HAVE
BEEN RE-USED FROM PREVIOUS PLANS:
A. TOPOGRAPHY, SUB-SURFACE UTILITIES, AND ABOVE
GROUND FEATURES ARE TAKEN FROM THE "OVERALL SITE
GRADING, DRAINAGE, AND SWPPP PLAN & BLOWUP DETAIL"
SHEET C-102 FROM THE MQ-9 FLIGHT TRAINING UNIT HANGER
PROJECT #FPBB129050 (FY14), SHEET DATED 07-07-14.
B. TOPOGRAPHY SHOWN IS A COMBINATION OF SURVEYED
TOPOGRAPHY AND PROPOSED CONTOURS TAKEN FROM THE
AFOREMENTIONED SHEET C-102. THE SURVEYED
TOPOGRAPHY PORTION WAS PERFORMED BY BEARDSLEY
DESIGN ASSOCIATES, L.S., P.C. THERESA BOONVILLE ROME,
NY DATED 4/29/2010. ADDITIONAL SURVEY AND
TOPOGRAPHIC INFORMATION PROVIDED BY LAFAVE, WHITE &
MCGIVERN, L.S., DATED 6/5/2014.
3. BASED ON NOTE #1, EXISTING CONDITIONS UTILITY DATA
SHOWN ON THIS SHEET MAY BE INCOMPLETE OR INCORRECT.
OWNER AND A/E DO NOT CONFIRM THE COMPLETENESS OR
ACCURACY OF THE INFORMATION SHOWN. CONTRACTOR SHALL
PERFORM TOPOGRAPHIC AND UTILITY SURVEY PRIOR TO THE
START OF CONSTRUCTION TO VERIFY LOCATIONS, ELEVATIONS
AND INVERTS OF ALL EXISTING FEATURES, ABOVE AND BELOW
GROUND. CONTRACTOR SHALL NOTIFY THE COR IN THE EVENT
THAT SUBSEQUENT SURVEY REVEALS ANY CONFLICTS.
KEY NOTES:
REMOVE EXISTING SIDEWALK - APPROX. 180 SF1
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
SAW CUT AND REMOVE EXISTING ASPHALT PAVEMENT
FOR BUILDING ADDITION AND CONCRETE RAMP -
APPROX. 430 SF
RELOCATE EXISTING FIBER OPTIC CABINET INSIDE THE
NEW MGCS SHELTER. SEE SHEET ET-101 FOR NEW
LOCATION. THE FIBER OPTIC CABINET WILL BE
MOUNTED TO THE INTERIOR WALL.
EXTEND EXISTING UNDERGROUND CONDUITS AND
CONDUIT STUB UPS TO THE INTERIOR WALL OF THE
MGCS SHELTER FOR FUTURE USE.
GENERAL NOTES:
1. The underground utilities and features shown hereon have been located from above ground visible features and other available records and therefore their location should be considered approximate only. Other underground utilities and features may exist, either in service or abandoned, that are not indicated on this survey. Dig Safely New York (UFPO) should be contacted prior to performing any excavation activities.
2. The underground domestic water and natural gas utilities are plotted from information provided by Barber Corporation.
3. This as-built sketch was assembled by Aubertine and Currier, PLLC as requested by R.J. Ortlied Construction Co. Aubertine and Currier, PLLC did not perform any field location or verification for this as-built sketch.
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1" = 30'
C-101
SITE ACCESS, STAGING & HAUL ROUTE
FPBB142001
1 SITE ACCESS, STAGING & HAUL ROUTE
SCALE: 1" = 30'
NORTH
KEY NOTES:
MAIN ENTRANCE TO
CONSTRUCTION SITE
2 CONSTRUCTION LIMITS = 2,600 SF
3 TEMPORARY STAGING/LAYDOWN
AREA = 2,300 SF
4 CONTRACTOR ACCESS/
HAUL ROUTE
5 PROPOSED BUILDING LOCATION
GENERAL NOTES:
1. UTILITY, SURFACE, AND TOPOGRAPHIC SURVEY
HAVE NOT BEEN PERFORMED IN CONJUNCTION
WITH THIS DESIGN. THE UTILITY AND TOPOGRAPHIC
DATA SHOWN ON THIS SHEET HAVE BEEN RE-USED
FROM PREVIOUS PLANS:
A. TOPOGRAPHY, SUB-SURFACE UTILITIES, AND
ABOVE GROUND FEATURES ARE TAKEN FROM
THE "OVERALL SITE GRADING, DRAINAGE, AND
SWPPP PLAN & BLOWUP DETAIL" SHEET C-102
FROM THE MQ-9 FLIGHT TRAINING UNIT HANGER
PROJECT #FPBB129050 (FY14), SHEET DATED
07-07-14.
2. BASED ON NOTE #1, EXISTING CONDITIONS
UTILITY DATA SHOWN ON THIS SHEET MAY BE
INCOMPLETE OR INCORRECT. OWNER AND A/E DO
NOT CONFIRM THE COMPLETENESS OR ACCURACY
OF THE INFORMATION SHOWN. CONTRACTOR
SHALL PERFORM TOPOGRAPHIC AND UTILITY
SURVEY PRIOR TO THE START OF CONSTRUCTION
TO VERIFY LOCATIONS, ELEVATIONS AND INVERTS
OF ALL EXISTING FEATURES, ABOVE AND BELOW
GROUND. CONTRACTOR TO NOTIFY COR IN THE
EVENT THAT SUBSEQUENT SURVEY REVEALS
ADDITIONAL UTILITY CONFLICTS.
1" = 30'
C-102
EXISTING CONDITIONS
FPBB142001
1 EXISTING CONDITIONS
SCALE: 1" = 30'
NORTH
GENERAL NOTES:
1. UTILITY, SURFACE, AND TOPOGRAPHIC SURVEY
HAVE NOT BEEN PERFORMED IN CONJUNCTION
WITH THIS DESIGN. THE UTILITY AND TOPOGRAPHIC
DATA SHOWN ON THIS SHEET HAVE BEEN RE-USED
FROM PREVIOUS PLANS:
A. TOPOGRAPHY, SUB-SURFACE UTILITIES, AND
ABOVE GROUND FEATURES ARE TAKEN FROM
THE "OVERALL SITE GRADING, DRAINAGE, AND
SWPPP PLAN & BLOWUP DETAIL" SHEET C-102
FROM THE MQ-9 FLIGHT TRAINING UNIT HANGER
PROJECT #FPBB129050 (FY14), SHEET DATED
07-07-14.
B. TOPOGRAPHY SHOWN IS A COMBINATION OF
SURVEYED TOPOGRAPHY AND PROPOSED
CONTOURS TAKEN FROM THE AFOREMENTIONED
SHEET C-102. THE SURVEYED TOPOGRAPHY
PORTION WAS PERFORMED BY BEARDSLEY
DESIGN ASSOCIATES, L.S., P.C. THERESA
BOONVILLE ROME, NY DATED 4/29/2010.
ADDITIONAL SURVEY AND TOPOGRAPHIC
INFORMATION PROVIDED BY LAFAVE, WHITE &
MCGIVERN, L.S., DATED 6/5/2014.
2. BASED ON NOTE #1, EXISTING CONDITIONS
UTILITY DATA SHOWN ON THIS SHEET MAY BE
INCOMPLETE OR INCORRECT. OWNER AND A/E DO
NOT CONFIRM THE COMPLETENESS OR ACCURACY
OF THE INFORMATION SHOWN. CONTRACTOR
SHALL PERFORM TOPOGRAPHIC AND UTILITY
SURVEY PRIOR TO THE START OF CONSTRUCTION
TO VERIFY LOCATIONS, ELEVATIONS AND INVERTS
OF ALL EXISTING FEATURES, ABOVE AND BELOW
GROUND. CONTRACTOR TO NOTIFY COR IN THE
EVENT THAT SUBSEQUENT SURVEY REVEALS
ADDITIONAL UTILITY CONFLICTS.
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
TEMPORARY
STOCKPILE &
LAYDOWN AREA
SF SF SF SF SF SF SF SF SF SF
SF
SF
SF
SF
SF
SFSFSFSFSFSFSFSFSFSF
SF
SF
SF
SF
TEMPORARY
STOCKPILE
STABILIZED
CONSTRUCTION
ENTRANCE
FPBB142001
MGCS
SHELTER
FFE 698.8
MAINTAIN 30' MIN. WIDE
TRAVEL LANE BETWEEN
SHELTER AND EXISTING
SOUTHERN EDGE OF
ASHPALT PAVEMENT
EXTEND EXISTING
SIDEWALK TO MATCH
SOUTHERN EDGE OF
SHELTER - 40 SF
15' LONG TRANSITION
RAMP TO MATCH EXISTING
ASPHALT PAVEMENT
ELEVATION - 240 SF
PROPOSED
BOLLARD (TYP.)
1" = 20'
C-103
SEDIMENT & EROSION CONTROL PLAN
SITE PLAN AND
FPBB142001
NORTH
GENERAL NOTES:
1. UTILITY, SURFACE, AND TOPOGRAPHIC SURVEY HAVE NOT
BEEN PERFORMED IN CONJUNCTION WITH THIS DESIGN. THE
UTILITY AND TOPOGRAPHIC DATA SHOWN ON THIS SHEET HAVE
BEEN RE-USED FROM PREVIOUS PLANS:
A. TOPOGRAPHY, SUB-SURFACE UTILITIES, AND ABOVE
GROUND FEATURES ARE TAKEN FROM THE "OVERALL SITE
GRADING, DRAINAGE, AND SWPPP PLAN & BLOWUP DETAIL"
SHEET C-102 FROM THE MQ-9 FLIGHT TRAINING UNIT HANGER
PROJECT #FPBB129050 (FY14), SHEET DATED 07-07-14.
B. TOPOGRAPHY SHOWN IS A COMBINATION OF SURVEYED
TOPOGRAPHY AND PROPOSED CONTOURS TAKEN FROM THE
AFOREMENTIONED SHEET C-102. THE SURVEYED
TOPOGRAPHY PORTION WAS PERFORMED BY BEARDSLEY
DESIGN ASSOCIATES, L.S., P.C. THERESA BOONVILLE ROME,
NY DATED 4/29/2010. ADDITIONAL SURVEY AND
TOPOGRAPHIC INFORMATION PROVIDED BY LAFAVE, WHITE &
MCGIVERN, L.S., DATED 6/5/2014.
2. BASED ON NOTE #1, EXISTING CONDITIONS UTILITY DATA
SHOWN ON THIS SHEET MAY BE INCOMPLETE OR INCORRECT.
OWNER AND A/E DO NOT CONFIRM THE COMPLETENESS OR
ACCURACY OF THE INFORMATION SHOWN. CONTRACTOR SHALL
PERFORM TOPOGRAPHIC AND UTILITY SURVEY PRIOR TO THE
START OF CONSTRUCTION TO VERIFY LOCATIONS, ELEVATIONS
AND INVERTS OF ALL EXISTING FEATURES, ABOVE AND BELOW
GROUND. CONTRACTOR TO NOTIFY COR IN THE EVENT THAT
SUBSEQUENT SURVEY REVEALS ADDITIONAL UTILITY
CONFLICTS.
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
SEE DETAIL
C-501
SITE AND SE&SC DETAILS
FPBB142001
SILT FENCE DETAIL
NOT TO SCALE8
STABILIZED CONSTRUCTION
ENTRANCE DETAIL
NOT TO SCALE9
SIDEWALK DETAIL
NOT TO SCALE6
ASPHALT & SIDEWALK JOINT DETAIL
NOT TO SCALE7
ASPHALT PAVEMENT EDGE DETAIL
NOT TO SCALE3
ASPHALT PAVEMENT DETAIL
NOT TO SCALE4
NOTES:
1. ALL DEPTHS OF PAVEMENT AND STONE ARE AFTER COMPACTION.
2. PROVIDE TACK COAT BETWEEN ASPHALT PAVEMENT LIFTS AND ALONG
INTERFACE BETWEEN ASPHALT PAVEMENT AND STRUCTURES.
NOTES:
1. PROVIDE 14" WIDE CONTROL JOINTS TOOLED OR SAWN, 1-1/2" DEPTH AT
SPACING EQUAL TO WIDTH OF SIDEWALK.
2. PROVIDE 12" WIDE EXPANSION JOINTS, FILLER AS SPECIFIED - RECESS AT 14"
FILL WITH SEALANT. EXPANSION JOINT SPACING NOT TO EXCEED 30'0" IN ANY
DIRECTION AND AT CONTACT WITH WALLS, DOORS, OR OTHER VERTICAL
SURFACES.
3. PROVIDE STIFF BROOM FINISH PERPENDICULAR TO DIRECTION OF TRAFFIC
PIPE BEDDING DETAIL
NOT TO SCALE5
NOTES:
1. FOR EXCAVATION AND BEDDING MATERIAL, REFER TO EARTHWORK
SPECIFICATION.
PIPE UTILITY TRENCH DETAIL
NOT TO SCALE1
NOTES:
1. TRENCH DEPTHS, WIDTHS, SHEETING, SHORING, BRACING AND CUTBACK
SLOPES TO BE DETERMINED BY THE CONTRACTOR AND SHALL COMPLY WITH OSHA,
NEW YORK STATE DEPARTMENT OF LABOR, NEW YORK STATE INDUSTRIAL CODE
AND ALL OTHER APPLICABLE SAFETY STANDARDS.
2. PROVIDE TRACER WIRE 1'-0" ABOVE OUTSIDE DIAMETER OF UTILITY AND
DETECTABLE WARNING TAPE 1'-6" BELOW FINISHED GRADE.
3. PROVIDE TRACER WIRE TEST BOX EVERY 500 FEET EITHER FLUSH OR POLE
MOUNTED.
TYPICAL EXTERIOR CLEANOUT DETAIL
NOT TO SCALE2
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
SYMBOL
CONSTRUCTION SPECIFICATIONS
SILT FENCE
U.S. DEPARTMENT OF AGRICULTURE
NATURAL RESOURCES CONSERVATION SERVICE
NEW YORK STATE DEPARTMENT OF ENVIRONMENTAL CONSERVATION
NEW YORK STATE SOIL & WATER CONSERVATION COMMITTEE
WOVEN WIRE FENCE
(MIN. 14 1/2 GAUGE
W/ MAX. 6" MESH
SPACING)
36" MIN. LENGTH FENCE
POSTS DRIVEN MIN. 16"
INTO GROUND.
HEIGHT OF FILTER
= 16" MIN.
8" MIN.
FLO
W
10' MAX. C. TO C.
5. MAINTENANCE SHALL BE PERFORMED AS NEEDED AND MATERIAL REMOVED WHEN
4. PREFABRICATED UNITS SHALL BE GEOFAB, ENVIROFENCE, OR APPROVED EQUIVALENT.
FENCE WITH TIES SPACED EVERY 24" AT TOP AND MID SECTION.
FENCE SHALL BE WOVEN WIRE, 12 1/2 GAUGE, 6" MAXIMUM MESH OPENING.
2. FILTER CLOTH TO BE TO BE FASTENED SECURELY TO WOVEN WIRE
3. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN EACH OTHER THEY SHALL BE OVER-
LAPPED BY SIX INCHES AND FOLDED. FILTER CLOTH SHALL BE EITHER FILTER X,
OR STAPLES. POSTS SHALL BE STEEL EITHER "T" OR "U" TYPE OR HARDWOOD.
1. WOVEN WIRE FENCE TO BE FASTENED SECURELY TO FENCE POSTS WITH WIRE TIES
"BULGES" DEVELOP IN THE SILT FENCE.
MIRAFI 100X, STABILINKA T140N, OR APPROVED EQUIVALENT.
UNDISTURBED GROUND
EMBED FILTER CLOTH
A MIN. OF 6" IN GROUND.
4"
16"MIN.
WOVEN WIRE FENCE (MIN. 14 1/2
GAUGE W/ MAX. 6" MESH SPACING)
WITH FILTER CLOTH
36" MIN. FENCE POST
FLOW
COMPACTED SOIL
20"MIN.
PERSPECTIVE VIEW
SECTION VIEW
SYMBOL
CONSTRUCTION SPECIFICATIONS
STABILIZED
CONSTRUCTION
ENTRANCE
U.S. DEPARTMENT OF AGRICULTURE
NATURAL RESOURCES CONSERVATION SERVICE
NEW YORK STATE DEPARTMENT OF ENVIRONMENTAL CONSERVATION
NEW YORK STATE SOIL & WATER CONSERVATION COMMITTEE
9. PERIODIC INSPECTION AND NEEDED MAINTENANCE SHALL BE PROVIDED AFTER EACH
STONE AND WHICH DRAINS INTO AN APPROVED SEDIMENT TRAPPING DEVICE.
8. WHEN WASHING IS REQUIRED, IT SHALL BE DONE ON A AREA STABILIZED WITH
MUST BE REMOVED IMMEDIATELY.
SEDIMENT SPILLED, DROPPED, WASHED OR TRACTED ONTO PUBLIC RIGHTS-OF-WAY
PREVENT TRACKING OR FLOWING OF SEDIMENT ONTO PUBLIC RIGHTS-OF-WAY, ALL
7. MAINTENANCE - THE ENTRANCE SHALL BE MAINTAINED IN A CONDITION WHICH WILL
IMPRACTICAL, A MOUNTABLE BERM WITH 5:1 SLOPES WILL BE PERMITTED.
STRUCTION ENTRANCES SHALL BE PIPED ACROSS THE ENTRANCE. IF PIPING IS
6. SURFACE WATER - ALL SURFACE WATER FLOWING OR DIVERTED TOWARD CON-
5. FILTER CLOTH - WILL BE PLACED OVER THE ENTIRE AREA PRIOR TO PLACING
POINTS WHERE INGRESS OR EGRESS OCCURS. TWENTY-FOUR (24) FOOT IF SINGLE
4. WIDTH - TWELVE (12) FOOT MINIMUM, BUT NOT LESS THAN THE FULL WIDTH AT
2. LENGTH - NOT LESS THAN 50 FEET (EXCEPT ON A SINGLE RESIDENCE LOT WHERE
1. STONE SIZE - USE 2" STONE, OR RECLAIMED OR RECYCLED CONCRETE EQUIVALENT.
A 30 FOOT MINIMUM LENGTH WOULD APPLY).
3. THICKNESS - NOT LESS THAN SIX (6) INCHES.
ENTRANCE TO SITE.
RAIN.
OF STONE.
3' 5:1
PLAN VIEW
PROFILE
EXISTING
GROUND
FILTER
CLOTH
EXISTING
PAVEMENT
MOUNTABLE BERM
(OPTIONAL)
EXISTING
PAVEMENT
10'MIN.
10'MIN.
12'MIN.
50'MIN.
6"MIN.
EXISTING
GROUND
50'MIN.
12'MIN.
08/27/21
L K1 G F
6'-11"33'-2"
MGCS SHELTER
5' -0
"16'-0"
6' -1
0"
'-0
9'
-6
10'-7" 10'-2" 10'-7"
H
J
J.1
7.1
5.1
6.1
EXTERIOR WALLS:
PRE-ENGINEERED
INSULATED METAL
CONSTRUCTION, TYP.
PR
IM
AR
Y
ST
EE
L
FR
AM
IN
G
PR
IM
AR
Y
ST
EE
L
FR
AM
IN
G
30'-4"
BOLLARDS
SEE CIVIL
'-7
'-7
ROOF OUTLINE ABOVE
MGCS
115A
115C-OH
115D-OH
C1
A
EXISTING SITE
EQUIPMENT
TO REMAIN
CA115B
14'-0"
C1
2' -1
0"
3' -9
'-2
7'-8"
K 2'-4"6'-2"
3'-4" 3'-4"
7'-8"
'-8
3' -4
HANGAR
A
A 1' -6
L1
6'-0"
CLEAR MINIMUM
C1
C1
A-101
FLOOR PLAN
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
NORTH1
A-301
0 4' 8'2'
A-301
AR-201
AR-201
A-201
A-502
A-502
SIM
A-502
A-502
KEY NOTES:
1/2 INCH WIDE WALL TO WALL EXPANSION JOINT BY METAL BUILDING
FABRICATOR SIMILAR TO SMACNA ARCHITECTURAL SHEET METAL
MANUAL (7TH EDITION) FIGURE 5-7. PROVIDE SHOP DRAWING.
PARTITION SCHEDULE:
TYPE A - SHAFT WALL PARTITION USING A 6 INCH C-H STUD, A 1 INCH
SHAFT LINER, AND 5/8 INCH FIRE RATED GWB. THE PARTITION SHALL
EXTEND TO THE UNDERSIDE OF THE METAL DECK.
TYPE B - GWB PARTITION: 3-1/2 INCH METAL STUDS WITH 5/8 INCH GWB
B1: FULL HEIGHT WITH ABUSE RESISTANT GWB TO A HEIGHT OF 10 FT
TYPE C - GWB FURRING AT EXTERIOR WALL:
C1 : FULL HEIGHT: 5/8 INCH GWB SECURED TO 3-5/8 INCH METAL
STUDS NESTED BETWEEN THE GIRTS EXTENDING FULL HEIGHT
OF SHELTER. ABUSE RESISTANT GWB TO A HEIGHT OF 10 FT AFF.
C2 : TERMINATION ABOVE CEILING: NOT USED
TYPE D - GWB FURRING AT MASONRY WALL: NOT USED
TYPE E - LATRINE WALLS: NOT USED
PROVIDE 1/2 INCH SOFT JOINT, PREFORMED COMPRESSIBLE
CONTROL JOINT WITH COMPATIBLE SEALANT. EMSEAL OR EQUAL.
PROVIDE INTERIOR WALL VENT, 6 INCH SQUARE WITH GRILLE
AT 8 FT. AFF.
1/2 INCH WIDE FLOOR TO FLOOR EXPANSION JOINT, REFER TO
SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE 5-8B.
PROVIDE SHOP DRAWING
ANTENNA WALL PENETRATION, 4 INCH DIAMETER AT 5'-0" AFF. REFER
TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE 8-5.
OVERHEAD COILING DOOR TO BE SUPPLIED BY METAL BUILDING
FABRICATOR. PROVIDE FRAMING AND JAMB CLOSURES. PROVIDE
SHOP DRAWING.
PROVIDE FENESTRATION (DOORS AND WINDOWS) IN EXTERIOR
WALLS THROUGH METAL BUILDING FABRICATOR. PROVIDE SHOP
DRAWINGS.
EXTENDED METAL ROOF OVER ALLEY BY METAL BUILDING
FABRICATOR.
TUBULAR STEEL COLUMN BY METAL BUILDING FABRICATOR, SEE
STRUCTURAL.
A-502
A-502
FIRE
ROOM
ELEC.
ROOM
MECH.
ROOM
COMM.
L K1 G F
H
J
J.1
7.1
5.1
6.1
K HANGAR
L1
MGCS SHELTER
A-102
REFLECTED CEILING PLAN
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"
NORTH
A-301
0 4' 8'2'
A-302
A-201
A-201
A-201
7'-8" 8'-0" 8'-0" 7'-8"
9' -2
'-0
8' -7
/8
'-0
KEY NOTES:
EXTEND PURLINS THROUGH EXTERIOR WALL TO SUPPORT ROOF
EXTENSION, FLASH PENETRATION IN ACCORDANCE WITH SMACNA
ARCHITECTURAL SHEET METAL MANUAL FIGURE 8-7.
EXTENDED METAL ROOF OVER ALLEY BY METAL BUILDING
FABRICATOR.
EXPOSED PAINTED STEEL ROOF BEAM.
HUNG GWB CEILING AT 10 FT AFF.
5/8 INCH GWB CEILING ON 1-1/2 INCH FURRING CHANNELS.
TYP. FOR
THE ENTIRE
EAST WALL
K
J
F
'-3
40'-0"
SL
O
PE
:1
VI
F
GH
5' -2
5.1
6.1
7.1
J.1
EXISTING SNOW GUARD
PRE-ENGINEERED
STANDING SEAM
METAL ROOF TO
MATCH EXISTING
ADJACENT IN SLOPE
AND FINISH
EXISTING ROOF
SL
O
PE
:1
VI
F
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
A-104
ROOF PLAN
FPBB142001
2 ROOF PLAN
SCALE: 1/4" = 1'-0"
NORTH
0 4' 8'2'
A-201
A-201
A-302
A-301
A-301
KEY NOTES:
ROOF TO ROOF EXPANSION JOINT BY METAL BUILDING FABRICATOR.
REFER TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE
5-5. PROVIDE SHOP DRAWING.
PROVIDE CONTINUOUS SNOW GUARD TO MATCH EXISTING ADJACENT
PRODUCT IN SIZE, STYLE, LOCATION AND FINISH. SNOW GUARD SHALL
BE BY METAL BUILDING FABRICATOR. SNOW GUARDS SHALL BE
MECHANICALLY SECURED. PROVIDE SHOP DRAWING.
UNIT HEATER VENT AND FLASHING BY METAL BUILDING FABRICATOR.
REFER TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURES
8-1 AND 8-2. PROVIDE SHOP DRAWING.
METAL BUILDING FABRICATOR TO PROVIDE METAL GUTTER BOX TO
MATCH FASCIA. SIZE GUTTER IN ACCORDANCE WITH SMACNA
ARCHITECTURAL SHEET METAL MANUAL CHAPTER ONE. SECURE
AND FLASH IN ACCORDANCE WITH SMACNA DETAIL 1-19A.
5 PROVIDE DOWNSPOUTS SIZED AND INSTALLED IN ACCORDANCE
WITH SMACNA FIGURE 1-31, PLAIN ROUND.
K HJ.1
'-0
"13 '-1
0"
PRE-ENGINEERED METAL
ROOF TO MATCH
EXISTING ADJACENT IN
SLOPE AND FINISH
5' -0
ANTENNA WALL
PENETRATION COVER, TYP.
115B-OH
12"
2"
PRE-ENGINEERED
METAL SIDING TO
MATCH EXISTING ADJACENT
5.1 6.1 7.1
'-1
0"
PRE-ENGINEERED METAL ROOF TO
MATCH EXISTING ADJACENT IN
HEIGHT, SLOPE AND FINISH
5' -0
ANTENNA WALL
PENETRATION COVER, TYP.
1' -0
6'
-0
5' -6
'-0
12"
2"
PRE ENGINEERED
METAL SIDING TO
MATCH EXISTING
ADJACENT
5.16.17.1
'-1
0"
PRE-ENGINEERED
METAL ROOF TO
MATCH EXISTING
ADJACENT IN
HEIGHT, SLOPE AND
FINISH
EXISTING EGRESS
DOOR
A-201
EXTERIOR ELEVATIONS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
0 4' 8'2'
2 WEST ELEVATION
SCALE: 1/4" = 1'-0"
0 4' 8'2'
3 EAST ELEVATION
SCALE: 1/4" = 1'-0"
0 4' 8'2'
A-3011
A-302
A-302
KEY NOTES:
1/2 INCH WIDE WALL TO WALL EXPANSION JOINT BY METAL BUILDING FABRICATOR SIMILAR TO SMACNA ARCHITECTURAL SHEET METAL MANUAL (7TH ADDITION) FIGURE
5-7. PROVIDE SHOP DRAWING.1
OVERHEAD COILING DOOR TO BE SUPPLIED BY METAL BUILDING FABRICATOR. PROVIDE FRAMING AND JAMB CLOSURES. PROVIDE SHOP DRAWING.
ANTENNA MOUNTING CONDUIT
METAL SOFFIT BY METAL BUILDING FABRICATOR AT 14 FT AFF. CONCEAL BEAMS AND PURLINS WITHIN METAL SOFFIT. PROVIDE SHOP DRAWING.
EXTEND PURLINS THROUGH EXTERIOR WALL TO SUPPORT ROOF EXTENSION, FLASH PENETRATION IN ACCORDANCE WITH SMACNA ARCHITECTURAL SHEET METAL
MANUAL FIGURE 8-7.
ROOF TO ROOF EXPANSION JOINT BY METAL BUILDING FABRICATOR. REFER TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE 5-5. PROVIDE SHOP DRAWING.
PROVIDE CONTINUOUS SNOW GUARD TO MATCH EXISTING ADJACENT PRODUCT IN SIZE, STYLE, LOCATION AND FINISH. SNOW GUARD SHALL BE BY METAL BUILDING FABRICATOR.
SNOW GUARDS SHALL BE MECHANICALLY SECURED. PROVIDE SHOP DRAWING.
ROOF TO WALL EXPANSION JOINT BY METAL BUILDING MANUFACTURER, REFER TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE 5-6 SIMILAR.
(VIF)
TYP. FOR THIS
ELEVATION
(VIF)
6'-0" MIN.
4 9
4 9
9 METAL BUILDING FABRICATOR TO PROVIDE METAL GUTTER BOX TO MATCH FASCIA. SIZE GUTTER IN ACCORDANCE WITH SMACNA ARCHITECTURAL SHEET METAL MANUAL
CHAPTER ONE. SECURE AND FLASH IN ACCORDANCE WITH SMACNA DETAIL 1-19A.
10 PROVIDE DOWNSPOUTS SIZED AND INSTALLED IN ACCORDANCE WITH SMACNA FIGURE 1-31, PLAIN ROUND.
ANTENNAE -
BY OWNER
GALVANIZED RIGID
CONDUIT SECURED
TO BUILDING, TYP.
DETAIL 6/A502
ANTENNAE
CABLE
ANTENNAE
CABLE
DETAIL 6/A502
GALVANIZED RIGID
CONDUIT SECURED
TO BUILDING, TYP.
ANTENNAE - BY
OWNER
Tectonic Copyright 2007
EXISTING
MQ-9 LRE
AND HANGAR
12"
2"
T.O. FIRST FLOOR
EL. 698'-10"
T.O. STEEL (EXISTING)
EL. 739'-4"
ALIGN W/ EXIST. STRUCTURE BEYOND
EL. 722'-2" VIF
T.O. NEW EXTERIOR WALL
EL. 712'-9" +/-
'-3
1 2"
'-0
METAL STANDING
SEAM ROOF ALIGN
WITH EXISTING
EXISTING METAL
PANEL FACADE
'-0
1 2"
FOUNDATION WALL
AND FOOTING, TYP.
SLAB ON GRADE
OUTLINE OF MGCS
'-0
FACE OF EXISTING
BUILDING BEYOND
MGCS SHELTER
5.16.17.1
'-2
CONTRACTOR TO VERIFY
EXISTING FRAMING AND
SUPPORT OF EXISTING
EXTERIOR WALL PRIOR
TO REMOVALS
T.O. EXISTING EXTERIOR WALL
EL. 713'-7" VIF
'-9
A-301
PROPOSED BUILDING SECTIONS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 BUILDING SECTION 1
SCALE: 1/4" = 1'-0"
0 4' 8'2'
A-302
A-501
A-501
KEY NOTES:
2 COLUMN ENCASED IN GWB
HUNG GWB CEILING AT 10 FT AFF.
ABUSE RESISTANT GWB
'-0
J.1 K
PRE-ENGINEERED
METAL PANEL FACADE
1" RIGID INSULATION
GIRT BY METAL BDLG.
MANUFACTURER'S
DESIGN TO MEET NYS
WIND LOADING
STEEL
COLUMN
BEYOND
FACE OF
EXISTING
BUILDING
ALIGN NEW ROOF
WITH EXISTING
ROOF HEIGHT
STANDING SEAM METAL
ROOF
RIGID INSULATION
2 LAYERS
12" FIBERGLASS BATT
INSULATION, FACED
BETWEEN PURLINS
5/8" GYPSUM WALLBOARD
ON 1-1/2" FURRING
CHANNELS
H
REFER TO STRUCTURAL
FOR FOUNDATION DEPTH
9" FIBERGLASS BATT
INSULATION, R-30 MIN.
5/8" IMPACT- RESISTANT
GYPSUM WALLBOARD TO
A HEIGHT OF 10' AFF ON
3-5/8 INCH METAL STUDS
NESTED BETWEEN GIRTS
AND NORMAL GWB
EXTENDING TO CEILING
TWO (2) LAYERS 1-1/2"
RIGID INSULATION
A-302
PROPOSED BUILDING SECTIONS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 BUILDING SECTION 2
SCALE: 1/4" = 1'-0"
0 4' 8'2'
A-301
A-501
KEY NOTES:
EXPOSED PAINTED STEEL ROOF BEAM.
ROOF TO ROOF EXPANSION JOINT BY METAL BUILDING FABRICATOR.
REFER TO SMACNA ARCHITECTURAL SHEET METAL MANUAL FIGURE
5-5. PROVIDE SHOP DRAWING.
6'-0" MIN. VIF
3 REFER TO A-502 AND A-503 FOR BUILDING OVERHANG
Tectonic Copyright 2007
A-501
WALL SECTIONS AND DETAILS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
A-503
A-503
A-701
T.O. FLOOR
EL. 698'-10"
B.O. EXIST. STRUCTURE
EL. 722'-2" VIF
T.O. STRUCTURE
EL. 712'-2"
A-301
SCALE:: 1/2"=1'-0"
WALL SECTION 0 42
SCALE IN FEET
'-4
'-0
'-0
A-503
STANDING SEAM
METAL ROOF, TYP.
STANDING SEAM
METAL ROOF, TYP.
5/8" GYPSUM WALLBOARD
ON 1-1/2" FURRING CHANNELS
STANDING SEAM
METAL ROOF, TYP.
BATT INSULATION
2 LAYERS RIGID
INSULATION
7.1
5.1
J.1
T.O. NEW EXTERIOR WALL
ALIGN WITH EXIST. ADJACENT BUILDING
A-301
SCALE:: 1/2"=1'-0"
WALL SECTION 0 42
SCALE IN FEET A-302
SCALE:: 1/2"=1'-0"
WALL SECTION 0 42
SCALE IN FEET
A-503
A-302
SCALE:: 1/2"=1'-0"
WALL SECTION 0 42
SCALE IN FEET
A-503
A-503
J.1
HANGAR
MGCS SHELTER
ACCESSWAY
HANGAR
SHELTER
MGCS STREET
SHELTER
MGCS
SHELTER
MGCSSTREET
SHELTER
MGCS
LINE OF RAMP,
SEE CIVIL DWGS.
1 HOUR FIRE RATED
CONSTRUCTION
5/8" IMPACT- RESISTANT GYPSUM WALLBOARD
TO A HEIGHT OF 10' AFF ON 3-5/8 INCH METAL
STUDS NESTED BETWEEN GIRTS AND NORMAL
GWB EXTENDING TO CEILING
A-502
PLAN DETAILS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
A-101
SCALE:: 1"=1'-0"
PLAN DETAIL 2'1'0
SCALE IN FEETA-101
SCALE:: 1"=1'-0"
PLAN DETAIL 2'1'0
SCALE IN FEET
K
K
6.1
5.1
A-101
SCALE:: 1"=1'-0"
PLAN DETAIL 2'1'0
SCALE IN FEET
A-101
SCALE:: 1"=1'-0"
PLAN DETAIL 2'1'0
SCALE IN FEET
J J.1
5.15.1
EXISTING WALL
PERLIN
FIBERGLASS BATT
INSULATION MIN. R-30
MGCS SHELTER
HANGAR
SHAFT AREA
5/8" GWB OVER
6" C-H METAL STUD
1 HOUR FIRE RATED
CONSTRUCTION
1" LINER PANEL
1" RIGID INSULATION
5/8" GWB OVER
3-5/8" METAL STUD
STEEL COLUMN AND
METAL WALL PANEL (BY PRE-
ENGINEERED METAL
BLDG. MANUFACTURER)
K
7.1
A-101
SCALE:: 1"=1'-0"
PLAN DETAIL 2'1'0
SCALE IN FEET
FIRE STOPPING BY
METAL BUILDING
FABRICATOR
1 HOUR FIRE RATED
CONSTRUCTION
EXISTING HANGAR WALL
NEW BOX STUDS AND GWB
FINISH AT BUILDING OPENING
EXISTING HANGAR WALL
NEW BOX STUDS AND GWB
FINISH AT BUILDING OPENING
HORIZONTAL GIRTS BY METAL
BUILDING FABRICATOR
HORIZONTAL GIRTS
BY METAL BUILDING
FABRICATOR
9"
HORIZONTAL GIRTS BY METAL
BUILDING FABRICATOR
1 HOUR FIRE RATED
CONSTRUCTION
SIMILAR
KEY NOTES:
1/2 INCH WIDE WALL TO WALL
EXPANSION JOINT BY METAL BUILDING
FABRICATOR SIMILAR TO SMACNA
ARCHITECTURAL SHEET METAL
MANUAL (7TH EDITION) FIGURE 5-7.
PROVIDE SHOP DRAWING.
PROVIDE 1/2 INCH SOFT JOINT, PREFORMED
COMPRESSIBLE CONTROL JOINT WITH
COMPATIBLE SEALANT. EMSEAL OR EQUAL.
COLUMN ENCASED IN GWB
A-201
SCALE:: 1"=1'-0"
ANTENNAE MOUNT DETAIL 2'1'0
SCALE IN FEET
4" X 3 8" OUTRIGGER
4" X 6" CLIP ANGLE
PROVIDE CONNECTION TO TWO
HORIZONTAL GIRTS AT MINIMUM OF
6'-0" APART VERTICALLY
RIGID INSULATION
METAL BUILDING PANEL
1'-2" VIF
PROVIDE 2" CLEARANCE
PAST FASCIA/ROOF
RIGID CONDUIT
SEE ELEVATIONS FOR
LOCATION AND LENGTH
THROUGH BOLT
ANTENNA CABLE
CONTRACTOR TO PROVIDE
METAL CLOSURE TO MATCH
BUILDING FINISH
3 HOLE CABLE ENTRY BOOT
BY COMMSCOPE OAE
CONTRACTOR TO PROVIDE
METAL CLOSURE TO MATCH
BUILDING FINISH
TRIM ON ALL FOUR SIDES SET IN SEALANT
4" FEED THROUGH ENTRY PANEL,
5 12" X 5 12" CX101-157 BY COMMSCOPE OAE
NOTE:
BATT INSULATION, METAL STUDS NOT SHOWN FOR CLARITY
A-201
3'-4"
PIPE CLAMP
5'-0" ABOVE FLOOR
2'-0"
A-503
PLAN DETAILS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET
7.1
5.1
A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET
STANDING SEAM
METAL ROOF, TYP.
5/8" GWB OVER
6" C-H METAL STUD
STEEL COLUMN AND
BEAM BEYOND (BY PRE-
ENGINEERED METAL
BLDG. MANUFACTURER)
2 LAYERS 2" RIGID
INSULATION, MIN. R-20
FASTENED TO B-DECK
EXISTING BUILDING
EXTERIOR WALL
EXISTING BUILDING
EXTERIOR WALL
VAPOR BARRIER
B-DECK
FIBERGLASS BATT
INSULATION MIN. R-38
PERLIN
5/8" GWB ON 1-1/2"
FURRING CHANNELS
A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET
5.1
A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET
STANDING SEAM
METAL ROOF, TYP.
2 LAYERS 2" RIGID
INSULATION, MIN. R-20
FASTENED TO B-DECK
VAPOR BARRIER
B-DECK
PERLIN
JAMB TRIM
K
A-501
SCALE: 1"=1'-0"
SECTION DETAIL 4'2'0
SCALE IN FEET
METAL WALL PANEL BY
PRE-ENGINEERED METAL
BUILDING MANUFACTURER
1" RIGID INSULATION
FIBERGLASS BATT
NSULATION MIN. R-38
2 LAYERS 2" RIGID
INSULATION, MIN. R-20
FASTENED TO B-DECK
VAPOR BARRIER
B-DECK
GIRT
METAL FLASHING
WEATHERHEAD FASTENER
@ 12" O.C. TAPE SEALANT
CONTINUOUS SEALANT TAPE
WITH POP RIVIT AT 12" O.C.
MFR. STANDARD
RAKE FLASHING
CONTINUOUS CLEAT SET IN
SEALANT
5/8" GWB OVER
6" C-H METAL STUD
STEEL COLUMN AND BEAM,
SEE STRUC. DWGS.
EXPANSION JOINT COVER
(2) #14 HEX HEAD FASTENING
AT EACH GABLE HELTER
STANDING SEAM
METAL ROOF, TYP.
1/2 INCH EXPANSION JOINT
EXPANSION JOINT
EXISTING STANDING
SEAM ROOF
CONCRETE SLAB,
SEE STRUCTURAL DWGS.
1" LINER PANEL
2 LAYERS 1-1/2"
RIGID INSULATION
METAL WALL PANEL BY
PRE-ENGINEERED METAL
BUILDING MANUFACTURER
1" RIGID INSULATION
METAL FLASHING
NESTED 3-5/8 INCH STUDS AND
RUNNER WITH ABUSE RESISTANT GWB
9 INCHES FIBERGLASS
BATT INSULATION MIN. R-30
STANDING SEAM
METAL ROOF, TYP.
COMPACTED GRAVEL
T.O. FLOOR
EL. 100'-0"
CONCRETE FOUNDATION,
SEE STRUCTURAL DWGS.
CONCRETE FOOTING,
SEE STRUCTURAL DWGS.
CONCRETE FOUNDATION,
SEE STRUCTURAL DWGS.
CONCRETE FOOTING,
SEE STRUCTURAL DWGS.
GRADE
4" RESILIENT BASE
4" RESILIENT BASE
EXISTING
WALL
1" LINER PANEL
STEEL COLUMN AND BEAM,
SEE STRUC. DWGS.
HANGAR
K
HANGAR
EXISTING BUILDING
FOUNDATION WALL
AND FOOTING
METAL ROOF TO MATCH EXISTING
ADJACENT CONSTRUCTION,
SECURE TO STRUCTURE, TYP.
2 LAYERS 2" RIGID
INSULATION, MIN. R-20
FASTENED TO B-DECK
VAPOR BARRIER
FIBERGLASS BATT
INSULATION MIN. R-38
SEALANT
SOFFIT PANEL
P. T. WOOD BLOCKING
EAVE STRUT
GABLE EAVE
FLASHING
STEEL COLUMN AND
BEAM BEYOND (BY PRE-
ENGINEERED METAL
BLDG. MANUFACTURER)
1/2 INCH EXPANSION JOINT
SHELTER
MGCS
SHELTER
MGCS SHELTER
MGCS
SHELTER
MGCS
SHELTER
MGCS
REFER TO STRUCTURAL
DRAWINGS
CONTINUOUS
AIR BARRIER
CONTINUOUS
AIR BARRIER
CONTINUOUS
AIR BARRIER
PREFORMED
COMPRESSIBLE
CONTROL JOINT WITH
COMPATIBLE SEALANT
CONTINUOUS
AIR BARRIER
GIRT
CONTINUOUS AIR BARRIER
2'-0" OF RIGID INSULATION
AROUND PERIMETER, TYP.
10" MAX
1' -2
1'-2"
3' -0
" A .F
.F
A-701
PARTITION, DOOR AND FINISH SCHEDULES
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
7' -0
3'-0"
1"
1"
3'-4"
DOOR SCHEDULE
DOOR
NO.
RM.
NO.
ROOM NAME INT./
EXT.
DOOR FRAME FIRE
RATING
HDWR.
SET
(d)
REMARKS
DOOR
TYPE DOOR MAT.
DOOR
FINISH
DOOR
WIDTH
DOOR
HEIGHT THICK.
OPENING
NOMINAL SIZE
FRAME
TYPE
FRAME
MAT.
FRAME
FINISH
GLASS
TYPE
DETAILS
WIDTH HEIGHT JAMB HEAD SADDLE
115B 115 MGCS SHELTER INT A HM PT-1 3'-0" 7'-0" 1 3/4" 3'-4" 7'-2" SF HM PT-1 - 4 3 - 45 MIN HW
(d) REFER TO SPECIFICATION
SECTION 08 71 00.
115C-OH 115 MGCS SHELTER EXT B GALV STL PT-1 16'-0" 10'-0" 3/4" 14'-0" 10'-0" SF STL PT-1 - 8 9 - 0 HR N/A
115D-OH 115 MGCS SHELTER INT C GALV STL PT-1 14'-0" 10'-0" 3/4" 16'-0" 10'-0" SF STL PT-1 - 7 10 - 45 MIN N/A
115A 115 MGCS SHELTER EXT A HM PT-1 3'-0" 7'-0" 1 3/4" 3'-4" 7'-2" SF HM PT-1 - 6 5 - 0 HR HW
FRAME TYPE DOOR TYPE
SEE SCHEDULE
SE
E
SC
H
ED
U
LE
1 A B C
LOUVER
L1
2/3'1/3'0
SCALE IN FEET
A701
7' -2
A701
A7012
A701
A701
A7017'
-2
A-701
SCALE: 3"=1'-0"
JAMB DETAIL 2/3'1/3'0
SCALE IN FEET A-701
SCALE: 3"=1'-0"
JAMB DETAIL
2/3'1/3'0
SCALE IN FEET
A-701
SCALE: 3"=1'-0"
HEAD DETAIL
A-701
SCALE: 3"=1'-0"
HEAD DETAIL
1'-0"
A-701
SCALE: 3"=1'-0"
LOUVER SECTION DETAIL 2/3'1/3'0
SCALE IN FEET
A701
A-701
SCALE: 3"=1'-0"
JAMB DETAIL 2/3'1/3'0
SCALE IN FEET
METAL FLASHING
AND STILL TRIM
CEILING AT 10" AFF
TOP OF FRAME AT 7'-2" AFF
METAL PANEL
1' -0
/- 2"
DOOR
4-1/2" +/-
6" FRAME
INSULATE JAMB
2"
A-701
SCALE: 1/2"=1'-0"
HEAD COILING DOOR, INTERIOR CONDITION 4'2'0
SCALE IN FEET
EXTERIOR
1-
/1
6" DOOR
6" FRAME
2" 2"
2"
2/3'1/3'0
SCALE IN FEET
TRIM
METAL FLASHING
A-701
SCALE: 3"=1'-0"
JAMB DETAIL 2/3'1/3'0
SCALE IN FEET
A-701
SCALE: 3"=1'-0"
HEAD DETAIL 2/3'1/3'0
SCALE IN FEET
BUTYL TAPE
ABUSE RESISTANT GWB
SEALANT
1" RIGID INSULATION
OVERHEAD DOOR
METAL PANEL
'C' CHANNEL
FRAME
HEADER TRIM
BATT INSULATION
GIRT SUPPORT FOR COIL
OF DOOR
BATT
INSULATION
1" RIGID INSULATION
METAL BLDG. MFG. TO PROVIDE
ADDITIONAL BOX BEAM GIRT TO
STABILIZE DOOR HEAD. WELD
'C' TO GIRT
METAL PANEL
'C' CHANNEL FRAME
BUTYL TAPE
HEADER TRIM
FIRE
ROOM
ELEC.
ROOM
MECH.
ROOM
COMM.
L K1 G F
MGCS SHELTER
H
J
J.1
7.1
5.1
6.1
115A
115C-OH
115D-OH
115B
K HANGAR
L1
LV-1
12x12
140 CFM
UH-1
UH-2
EF-1
T
THERMOSTAT TO
UH-1 AND UH-2
MGCS
DUCTED FIELD
DEPLOYABLE
UNIT FOR MGCS (BY
OTHERS)
SUPPLY AND
RETURN AIR DUCT
BY OTHERS
DUCTED FIELD
DEPLOYABLE
UNIT FOR MGCS (BY
OTHERS)
M-101
MECHANICAL FLOOR PLAN
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
NORTH
0 4' 8'2'
GENERAL NOTES:
1. MGCS WILL BE PROVIDED WITH DEDICATED FIELD
DEPLOYABLE ENVIRONMENTAL CONTROL UNITS (FDECU) IN
ORDER TO MAINTAIN THE HEATING AND COOLING SETPOINTS
WITHIN THE UNIT.
SEQUENCE OF OPERATIONS:
EXHAUST FAN (EF-1)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME
SCHEDULE IN THE FOLLOWING MODES:
· ENERGIZED MODE:
THE MOTORIZED DAMPER SHALL OPEN.
FAN:
THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN,
UNLESS SHUTDOWN ON SAFETIES.
UNIT HEATERS (UH-1, UH-2)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME
SCHEDULE IN THE FOLLOWING MODES:
· HEATING MODE:
THE UNIT SHALL MAINTAIN A 50°F (ADJ.) HEATING SETPOINT.
FAN:
THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN,
UNLESS SHUTDOWN ON SAFETIES.
Mechanical 8/27/2021
J.1 K
T.O. FIRST FLOOR
EL. 100'-0"
T.O. NEW EXTERIOR WALL
EL. 113'-0"
ALIGN W/ EXIST. STRUCTURE BEYOND
EL. 123'-4"
H
DUCTED FIELD
DEPLOYABLE
UNIT FOR MGCS (BY
OTHERS)
MGCS SHELTER
UH-2
EF-1
M-201
MECHANICAL SECTIONS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
1 SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
0 4' 8'2'
M-301
MECHANICAL SCHEDULES
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
EXTERIOR WALL
EXTERIOR LOUVER
DAMPER
PROTECTION
SCREEN
WALL OPENING SHALL BE
FURNISHED AND INSTALLED
WITH A STAINLESS STEEL
INSECT SCREEN ON THE
INTERIOR OF THE LOUVER
LOW LEAK
MOTORIZED
DAMPER
INTAKE LOUVER DETAIL
SCALE: NOT TO SCALE
EXHAUST FAN
SECURE DUCT TO CURB
10 GA. SCREWS AT 12" CC
(MINIMUM 2 PER SIDE)
INSULATED CURB
WALL
MOTORIZED BACKDRAFT
DAMPER (SECURE DAMPER TO
CURB IF FAN IS NOT DUCTED)
10 GA. SCREWS AT 12" CC
(MINIMUM 2 PER SIDE).
SECURE DUCT TO WALL
CONSTRUCTION OR
CURB (AIR TIGHT)
WALL MOUNTED EXHAUST FAN DETAIL
SCALE: NOT TO SCALE
HANGING SUPPORT
GAS FIRED UNIT HEATER DETAIL
SCALE: NOT TO SCALE
UNIT HEATER
TYPE B GAS VENT
UNION
CAP
BALL VALVE
GAS CONTROL VALVE
M-401
MECHANICAL DETAILS
FPBB142001
B
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2" FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
ISSUE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1" 2"
FILENAME
SCALE
SHEET
DATE
C
D
A
1 3 4 5 6 7 8
FPBB142001 CONSTRUCT OPERATIONS SPACE /
MGCS SHELTER
FORT DRUM MILITARY RESERVATION, NY
ANTHONY BROZIER
10256943
CIVIL
STRUCTURAL
ARCHITECTURAL
ELECTRICAL
MEP
FIRE PROTECTION
CYBERSECURITY
B-3 SUBMISSION27 AUG 20213
B-2 SUBMISSION8 JUN 20212
B-1 SUBMISSION20 APR 20211
A. BROZIER
J. JAECKEL
A. STANISCIA
I. DENHOLM
D. SPENCER
E. SHOWALTER
J. MONFORTON
NOT TO SCALE
F-100
FIRE PROTECTION NOTES & LEGEND
FPBB142001
FIRE ALARM GENERAL NOTESFIRE PROTECTION/SUPPRESSION GENERAL NOTES
1. PROVIDE CODE COMPLIANT COMBINE FIRE ALARM AND MASS
NOTIFICATION SYSTEM IN THE HANGAR ADDITION. INSTALL FIRE
ALARM / MASS NOTIFICATION EQUIPMENT AS NEEDED TO CONNECT
TO EXISTING SYSTEMS. PROVIDE MANUAL PULL STATIONS AT ALL
EXITS. PROVIDE OCCUPANT NOTIFICATION COMPLYING WITH NFPA
72. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH
APPLICABLE EDITIONS OF NFPA 70, NFPA 72, NFPA 101, UFC 3-600-01
AND UFC 4-021-01. CERTIFICATE OF FINAL INSPECTION SHALL BE
PROVIDED BY THE CONTRACTOR AT COMPLETION OF PROJECT
AND PRESENTED TO THE CONTRACTING OFFICER.
2. FURNISH AND INSTALL ALL COMPONENTS TO COMPLETE A
FUNCTIONAL SYSTEM IN THE NEW ADDITION AS INDICATED ON
CONTRACT DOCUMENTS AND AS EVIDENTLY INTENDED.
DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE
GENERAL ARRANGEMENTS OF SYSTEMS AND SCOPE OF WORK.
CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT AND WIRING
AS REQUIRED ACCOMPLISHING THE FUNCTIONS INTENDED.
3. COORDINATE WORK WITH THE WORK OF OTHER TRADES.
RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN.
FAILURE TO COORDINATE WORK WITH OTHER TRADES SHALL NOT
BE CAUSE FOR ADDITIONAL COMPENSATION AND MAY RESULT IN
REJECTION OF CONTRACTOR'S WORK.
4. THE QUANTITY AND PLACEMENT OF VISUAL NOTIFICATION DEVICES
IS DEPENDENT UPON CANDELA RATING. DEVICE PLACEMENT
SHOULD BE BASED UPON NFPA 72 CHAPTER 18.5.5.4.
5. FIRE ALARM / MASS NOTIFICATION CONTROL UNIT SHALL TRANSMIT
SIGNALS AS CURRENTLY PROGRAMMED.
6. MATERIALS SHALL BE NEW AND SUITABLE FOR THE APPLICATION
INTENDED. MATERIALS SHALL BEAR LABELS OR MARKINGS
INDICATING THIRD PARTY TESTING LABORATORY LISTINGS
ACCEPTABLE TO AUTHORITY HAVING JURISDICTION.
7. CABLES SHOULD BE INSTALLED IN METAL RACEWAYS. METALLIC
RACEWAYS, CONDUIT, BACK BOXES, AND JUNCTION BOXES SHALL
BE PAINTED RED.
8. RACEWAY SHALL BE CONCEALED IN FINISHED SPACES. RACEWAY
SHALL BE RUN PERPENDICULAR OR PARALLEL TO THE BUILDING'S
STRUCTURAL COMPONENTS. JUNCTION BOXES INSTALLATION
SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES.
9. CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX,
OUTLET BOX, CABINET, ETC., WITH VINYL SELF-ADHESIVE TAGS
INDICATING PANEL AND CIRCUIT NUMBER AND OTHER
APPROPRIATE INFORMATION.