This document provides details for a solicitation seeking proposals for an indefinite delivery indefinite quantity multiple award construction contract to provide construction services in Colorado, Montana, Utah, North Dakota, South Dakota, and Wyoming. The solicitation is for a total small business set-aside. The contract will have a one year base period and four one-year options periods and will be awarded to multiple awardees. Construction services will include new construction, renovations, repairs, alterations, and lease construction for federal buildings managed by the General Services Administration Public Buildings Service Region 8. Proposals are due by the date specified in the attached solicitation notice. The contract has an estimated value of $500 million over the five-year period.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
ANDERSON HALLAS
ARCHITECTS, PC
SHEET OF
PROPERTY OF THE UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS,
PLANS, OR SPECIFICATIONS TO UNAUTHORIZED USERS
IS PROHIBITED
Do Not Remove This Notice Properly Destroy Documents When No Longer Needed
GENERAL SERVICES ADMINISTRATION ~ DENVER FEDERAL CENTER ~ BUILDING 56
/8
/2
:0
:0
P
M
1 50
7/25/2019
BUILDING 56 - 2ND FLOOR NRCS CONSOLIDATION
G 010
100% CD ISSUE JULY 25, 2019
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
GENERAL NOTES
1. DO NOT SCALE DRAWINGS
2. ALL WORK TO BE PERFORMED TO APPLICABLE BUILDING CODES.
3. ALL DIMENSIONS ARE TO FACE OF STRUCTURE UNLESS OTHERWISE NOTED. ALL DIMENSIONS INDICATING
REQUIRED CLEARANCES ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIM OR HERSELF WITH THE CONTRACT
DOCUMENTS, VERIFYING FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. CONTRACTOR SHALL NOTIFY GOVERNMENT & ARCHITECT IN WRITING OF ANY DISCREPANCY WITHIN THE CONTRACT DOCUMENTS AND REQUEST
CLARIFICATION PRIOR TO PROCEEDING WITH CONSTRUCTION.
5. SHOULD THERE BE ANY QUESTIONS CONCERNING THE CONTRACT DOCUMENTS, EXISTING CONDITIONS, AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE GOVERNMENT & ARCHITECT PRIOR TO PROCEEDING WITH THE WORK, OR RELATED WORK IN QUESTION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIMSELF WITH THE PROJECT SCOPE OF WORK, SCHEDULE, AND DEADLINES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADVISING THE GOVERNMENT & ARCHITECT OF ALL ITEMS REQUIRING A LONG LEAD TIME UPON NOTICE TO PROCEED THAT WILL AFFECT THE SCHEDULE, AND SHALL SUBMIT ORDER CONFIRMATIONS AND DELIVERY DATES FOR THE ITEMS IN QUESTION TO THE
GOVERNMENT.
7. INSTALL ALL MANUFACTURED ITEMS, MATERIALS, AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDED SPECIFICATIONS, EXCEPT WHERE THE CONTRACT DOCUMENTS ARE MORE STRINGENT. ANY MISCELLANEOUS ITEMS OR MATERIALS NOT SPECIFICALLY NOTED, BUT REQUIRED FOR PROPER INSTALLATION SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. THE CONTRACTOR SHALL FURNISH TO THE GOVERNMENT ALL WARRANTIES AND GUARANTEES REQUIRED AT THE CONCLUSION OF THE PROJECT.
8. ALL CONTRACTOR OR SUPPLIER REQUESTS FOR SUBSTITUTIONS OF SPECIFIED ITEMS SHALL BE SUBMITTED IN WRITING TO THE GOVERNMENT & ARCHITECT WITHIN 14 DAYS OF NOTICE TO PROCEED, AND BE ACCOMPANIED WITH THE ALTERNATIVE PRODUCT INFORMATION. SUBSTITUTIONS WILL BE CONSIDERED ONLY IF IT DOES NOT
SACRIFICE QUALITY, APPEARANCE, DELIVERY TIME, OR FUNCTION.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL HOOK UPS / UTILITY CONNECTIONS, ETC. TO TEMPORARY TRAILERS.
A4.0
A8.0
ROOM
250 SF
A9.0
A5.0
N
FIRST FLOOR
100'-0"
5 1 6 75
KEY
NOTE
WALL
TYPE
WINDOW
TYPE/NUMBER
DOOR
NUMBER
ELEVATION MARK NORTH ARROW
DETAIL REFERENCE
BUILDING SECTION
EXTERIOR
ELEVATION
INTERIOR
ELEVATION
ROOM
TAG
SYMBOLS
PROJECT TEAM
Owner
General Services Administration, Region 8 DFC Building 41 Denver, CO 80225 303.236.0855 Ben Reko, Project Manager
720.412.2812 c benjamin.reko@gsa.gov
Architect
Anderson Hallas Architects, PC 715 14th St.
Golden, CO 80401 P: 303-278-4378 F: 303-278-0521 Principal in Charge: Dave Anderson Project Manager: Rebecca Silva email: rebeccasilva@andarch.com
Mechanical / Plumbing Engineer
360 Engineering 1600 Jackson Street, Suite 360 Golden, CO 80401 303.940.2050 Denise Dehle ddihle@360eng.com Travis Menard
720.619.1545 c tmenard@360eng.com
Electrical Engineer
AE Design 1900 Wazee Street #350 Denver, CO 80202 720.266.4755 Jon Brooks jbrooks@aedesign-inc.com Patrick Durham
303.444.1951 c pdurham@aedesign-inc.com
Parametrix, Inc.
J. R. Anzer, Cost Estimator 7186 South Highland Drive Salt Lake City, Utah 84121 Phone: 801-733-5900 Fax: 801-733-5500
Cost Estimator
Veritas Fire Engineer 12364 W. Alameda Pkwy Suite 135 Lakewood, CO 80228 Phone: 303.985.3300 Toll-Free: 1.866.985.2050 Fax: 303.985.5594 Kerry Madigan Kerry@veritasfire.com Bryan Echelberger Bryan@veritasfire.com
Protection Fire Engineer
G
LS
I A S M E
EP
EL
P
FA
FS
TC
TA
TE
SEC
GENERAL
LIFE SAFETY
INTERIORS
ARCHITECTURAL
STRUCTURAL
MECHANICAL/HVAC
ELECTRICAL
ELECTRICAL - POWER
ELECTRICAL - LIGHTING
PLUMBING
FIRE ALARM
FIRE SAFETY
TELECOMMUNCATIONS
AUDIO VISUAL
AUDIO VISUAL -
INFRASTRUCTURE
SECURTY
0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 9 00
GENERAL INFORMATION
FLOOR PLANS
ELEVATIONS - EXTERIOR
SECTIONS
ENLARGED DWGS
DETAILS
SCHEDULES
REFLECTED CEILING PLAN (RCP)
FINISH PLANS
ELEVATIONS - INTERIOR
DISIPLINE INDEX
CONTEXT INDEX
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:0
P
M
G 0 02 2 50
DCA/ RS
DAM / LB 07/25/2019
22X34
2ND FLOOR
INDEX & GENERAL INFORMATION
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
OD OUTSIDE DIAMETER
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PT PAINT
PTD PAINTED
PWD PLYWOOD
QT QUARRY TILE
RAD RADIUS
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFER TO or REFERENCE
REINF REINFORCED
RELOC RELOCATE(D)
REQ REQUIRED
REV REVISE, REVISED or REVISION
RM ROOM
RO ROUGH OPENING
RS ROUGH SAWN
(S) SEALANT
S SOUTH
SCHED SCHEDULE
SF SQUARE FEET
SHTG SHEATHING
SIM SIMILAR
SL SHEET LINOLEUM
SOG SLAB ON GRADE
SPEC SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STN STAIN
STRUC STRUCTURE or STRUCTURAL
(T) TEMPERED
T&G TONGUE AND GROOVE
T.O. TOP OF
TD THRESHOLD
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VIN VINYL
VTR VENT THROUGH ROOF
W WEST
W/ WITH
W/O WITHOUT
WD WOOD
WIN WINDOW
EXT EXTERIOR
FACP FIRE ALARM CONTROL PANEL
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH(ED)
FIXT FIXTURE
FLR FLOOR(ING)
FO FACE OF
FP FIRE PROTECTION
FRP FIBERGLASS REINFORCED PANEL(ING)
FT FEET
FTG FOOTING
FURR FURRING
GA GAUGE OR GYPSUM ASSOCIATION
GALV GLAVANIZED
GC GENERAL CONTRACTOR
GD GRADE
GL GLASS or GLAZING
GND GROUND
GWB GYPSUM WALLBOARD
HM HOLLOW METAL
HAZMAT HAZARDOUS MATERIAL
HDR HEADER
HDW HARDWARE
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATION and AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
INFO INFORMATION
INS INSULATION or INSULATED
INT INTERIOR
JT JOINT
LAV LAVATORY
LIN LINOLEUM
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL and
PLUMBING
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
<N> NEW
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
# POUND(S) or NUMBER
& AND
< ANGLE
@ AT
A/V AUDIO VISUAL
ABV ABOVE
ACM ASBESTOS CONTAINING MATERIAL
ACT ACCOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADD ADDENDUM
ADJ ADJACENT or ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATE(LY)
ARCH ARCHITECTURAL
ASPH ASPHALT
B.O. BOTTOM OF
BLDG BUILDING
BLKG BLOCKING
BR BACKER ROD
BTWN BETWEEN
CAB CABINET
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTBB CEMENTITIOUS TILE BACKER BOARD
CTR CENTER
DBL DOUBLE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DIAM DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
<E> EXISTING
E EAST
EA EACH
EG FOR EXAMPLE
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENGR ENGINEER
EQ EQUAL
EQP EQUIPMENT
ETR EXISTING TO REMAIN
INDEX
ABBREVIATIONS
SHEET SUB. SHEET Sheet Name
GENERAL
1 01 COVER SHEET
2 G 0 02 INDEX & GENERAL INFORMATION
3 G 0 03 CODE AND EGRESS INFORMATION
4 G 0 04 WALL TYPES CEILING TYPES
STATE VICINITY MAP CITY LOCATION MAP
N N
NTS NTS
CITY LOCATION
MAP PROJECT AREA:
DENVER FEDERAL CENTER
PROJECT AREA STREET MAP
N
NTS
K
IP
L
IN
G S
T R
E E
T
WEST 6TH AVE.
PROJECT AREA:
DENVER FEDERAL CENTER
BUILDING 56
6TH STEET
DENVER, COLORADO 80215
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
ARCHITECTURAL
5 A 4 01 ENLARGED DEMO FLOOR PLAN - PART 'A'
6 A 4 02 ENLARGED DEMO FLOOR PLAN - PART 'B'
7 A 4 03 ENLARGED NEW FLOOR PLAN - PART 'A'
8 A 4 04 ENLARGED NEW FLOOR PLAN - PART 'B'
9 A 5 01 CASEWORK DETAILS
10 A 6 01 DOOR AND WINDOW SCHEDULES
11 A 6 02 ROOM FINISH SCHEDULE AND DETAILS
12 A 7 01 ENLARGED DEMO REFLECTED CEILING PLAN - PART 'A'
13 A 7 02 ENLARGED DEMO REFLECTED CEILING PLANS - PART 'B'
14 A 7 03 ENLARGED NEW REFLECTED CEILING PLAN - PART 'A'
15 A 7 04 ENLARGED NEW REFLECTED CEILING PLAN - PART 'B'
16 A 9 01 INTERIOR ELEVATIONS - OPEN OFFICE
MECHANICAL
17 M 0 MECHANICAL COVER SHEET
18 MD 1 MECHANICAL DEMO PLAN PART A
19 M 1 MECHANICAL FLOOR PLAN PART A
20 M 2 MECHANICAL FLOOR PLAN PART B
PLUMBING
21 P 1 PLUMBING FLOOR PLAN
ELECTRICAL
22 E 0 01 ELECTRICAL COVER SHEET
23 E 0 00 ELECTRICAL COVER SHEET
24 ED 2 01 ELECTRICAL DEMO POWER PLAN-AREA A
25 ED 2 02 ELECTRICAL DEMO POWER PLAN-AREA B
26 ED 2 03 ELECTRICAL DEMO POWER PLAN-AREA C
27 ED 3 01 ELECTRICAL DEMO LIGHTING PLAN-AREA A
28 ED 3 02 ELECTRICAL DEMO LIGHTING PLAN-AREA B
29 ED 3 03 ELECTRICAL DEMO LIGHTING PLAN-AREA C
30 E 2 01 ELECTRICAL POWER PLAN-AREA A
31 E 2 02 ELECTRICAL POWER PLAN-AREA B
32 E 2 03 ELECTICAL POWER PLAN-AREA C
33 E 3 01 ELECTRICAL LIGHTING PLAN-AREA A
34 E 2 04 ELECTRICAL POWER PLAN- AREA D
35 E 3 02 ELECTRICAL LIGHTING PLAN-AREA B
36 E 3 03 ELECTRICAL LIGHTING PLAN-AREA C
37 E 6 00 ELECTRICAL ONE LINE DIAGRAM
38 E 7 00 ELECTRICAL SCHEDULES
39 E 7 10 ELECTRICAL PANEL SCHEDULES
40 E 7 20 ELECTRICAL PANEL SCHEDULES
FIRE PROTECTION
41 FP 1 01 FP NOTES AND DETAILS
42 FP 1 02 FIRE SPRINKLER DEMO PART-A
43 FP 1 03 FIRE SPRINKLER DEMO PART-B
44 FP 1 04 FIRE SPRINKLER PART-A
45 FP 1 05 FIRE SPRINKLER PART-B
46 FA 1 01 FA NOTES AND DETAILS
47 FAD 1 02 FIRE ALARM DEMO PART-A
48 FAD 1 03 FIRE ALARM DEMO PART-B
49 FA 1 04 FIRE ALARM PART-A
50 FA 1 05 FIRE ALARM PART-B
MARK DATE DESCRIPTION
ALTERNATES:
1. ACOUSTIC WALL PANELS PER SHEET A 9 01.
FIRE SAFETY/EGRESS LEGEND
- EGRESS DOOR W/ EXIT SIGNAGE
- EGRESS PATH
- ASSUMED (E) 2HR RATED PARTITION
- DIRECTION OF EGRESS TRAVEL
- FIRE EXTINGUISHER CABINET
- EXIT SIGNAGE
- EMERGENCY LIGHT
FEC
- AREA OF WORK
AREA OF WORK
~ PARTS 'A' & 'B'
18.1
C
D
E
F
G
H
I
13 14 15 16 17 1816.112.1
STORAGE & IT
WAITING /
RECEPTION
MEETING ROOM 1
MEETING ROOM 2
BREAK ROOM
CLOSET /
STORAGE
N.I.C.
DN
EXISTING MEN'S
RR (N.I.C.)
N.I.C.
EXISTING
WOMEN'S RR
(N.I.C.)
N.I.C.
EXISTING OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. HALL (N.I.C.)
N.I.C.
EXT. COMM /
ELEC. RM. (N.I.C.)
N.I.C.
MECHANICAL
ECS OFFICE
OPEN OFFICE
OPEN OFFICE
STATE CONSERV.
OFFICE
PROGRAMS
OFFICE
SNOW OFFICE
PHONE BOOTH
PHONE BOOTH
OPEN OFFICE
CLOSET
SOILS OFFICE
MGT & STRAT.
OFFICE
ENG. OFFICE
PHONE BOOTH
PHONE BOOTH
JEFFCO STG
MAX EXIT
ACCESS TRAVEL
DISTANCE: 96' - 0"
91'-5"
TRAVEL
DISTANCE
BUILDING CODE ANALYSIS
Code analysis is based on the 2015 International Building Code, and the 2015 International Existing Building Code. Refer to Mechanical, Plumbing, Electrical & Fire Protection sheets for additional information.
Date: 02.15.2019 Analysis By: RAS Project Number: 2017360 Project Name: NRCS Consolidation Address: Building 56 6th Street
Denver, CO 80255
SCOPE OF WORK:
This project is a tenant finish to a small portion of the 2nd floor of Building 56, located in the Federal Center. The scope includes minor wall reconfiguration, new interior finishes, a new break room, and minor reconfiguration of mechanical, electrical and fire protection systems.
No work to the building envelope is included.
PROJECT OCCUPANCY: B
CONSTRUCTION TYPE:
Type IIB, with a fully automatic NFPA 13 sprinkler system
PROJECT AREA: 9750sf
OCCUPANT LOAD:
Business(100sf/person): 8265sf = 83 Mechanical/ Support (300sf/person): 810sf = 3 Total Occupant Load: 86
BUILDING HEIGHT AND NUMBER OF STORIES: Unchanged
BUILDING AREA: Unchanged
FIRE PROTECTION:
Existing fire sprinkler system to be upgraded to comply with Section 903.
Portable fire extinguishers required per section 906, and located per GSA P100 in mechanical, electrical, IT and Break Rooms. Contractor to verify existing extinguishers are present, code compliant, and in working order. If not, replace.
Existing fire alarm system to be upgraded to comply with Section 907.
EGRESS:
Egress width: 32" + 64" provided. Required width = 32" min.
Two exits provided. - Required # = 2
Exit Access Travel Distance: 96' max. provided. 300' max. required.
Common Path of Egress Travel Distance: 58' max. provided. 100' max. provided.
PLUMBING FIXTURE COUNT: unchanged
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:1
P
M
G 0 03 3 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
CODE AND EGRESS INFORMATION
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
2nd FLOOR KEY PLAN
N
3/32" = 1'-0"
EGRESS - SECOND LEVEL FLOOR PLAN - PART 'A' AND 'B'
AREA OF WORK
AREA OF WORK
N
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
MATCH LINE
MARK DATE DESCRIPTION
18 GA. BOTTOM TRACK
~ ANCHOR WITH
POWER ACTUATED
FASTENERS AT 24" O.C.
RESILIENT BASE, RE:
ROOM FINISH SCHEDULE
FOR LOCATION
18 GA. METAL STUDS
AT 24" O.C.5/8" GYPSUM BOARD AT
EACH FACE OF STUD
18 GA. METAL TOP TRACK
~ ANCHOR TO EXISTING
CEILING TRACK, SET IN
BED OF SEALANT (AT
TRACK LOCATION ONLY)
MODIFY <E> CEILING TILE
TO ACCOMMODATE NEW
WALL, TILE SHALL LAY
LEVEL AND
UNINTERRUPTED
PROVIDE METAL L-BEAD,
TYP EACH SIDE OF WALL
<E> CEILING TILE
PROVIDE METAL STUD
DIAGONAL BRACING TO
STRUCTURE AT 48" O.C.,
ALTERNATE DIRECTION
PROVIDE ACOUSTIC
BATT INSULATION FROM
FLOOR TO CEILING
ABOVE BETWEEN
STUDS, FULL DEPTH OF
WALL
<E> SUPPORT
HANGERS TO REMAIN
SECTION
3-5/8" x 18 GA. METAL
STUDS AT 16" O.C. WITH
18GA. TOP AND BOTTOM
TRACK
5/8" GYPSUM BOARD AT
EACH FACE OF STUD
PLANPROVIDE ACOUSTIC BATT INSULATION
FROM FLOOR TO CEILING ABOVE
BETWEEN STUDS, FULL DEPTH OF
WALL
WALL
TYPE
WALL
TYPE
1.1 = SAME AS WALL TYPE WT1, WALL CONSTRUCTED WITH 6" 18GA.
METAL STUDS AT 16" O.C. WITH TOP AND BOTTOM TRACKS
UN-
RATED
UN-
RATED
WALL
TYPE
3.1 = SAME AS WALL TYPE WT1, WALL ~ NO ACOUSTIC BATT
INSULATION
UN-
RATED
INSTALL 12" MIN. ACOUSTIC
BATT INSULATION OVER
<N> AND <E> WALL
LOCATIONS TO A MINIMUM
OF 4-0" FROM WALL, EACH
SIDE.
WALL
TYPE
3.0
NOTE: CONTRACTOR TO
VERIFY (E) WALL ASSEMBLY
IN FIELD. NOTIFY ARCHITECT
IF DIFFERENT THAN DRAWN.
3-5/8" x 18 GA. METAL
STUDS AT 16" O.C. WITH
18GA. TOP AND BOTTOM
TRACK
2 LAYERS OF 5/8"
GYPSUM BOARD AT
EACH FACE OF STUD
PLAN
PROVIDE ACOUSTIC BATT INSULATION
FROM FLOOR TO CEILING ABOVE
BETWEEN STUDS, FULL DEPTH OF
WALL
18 GA. BOTTOM TRACK
~ ANCHOR WITH
POWER ACTUATED
FASTENERS AT 24" O.C.
RESILIENT BASE, RE:
ROOM FINISH SCHEDULE
FOR LOCATION
18 GA. METAL STUDS
AT 24" O.C.5/8" GYPSUM BOARD AT
EACH FACE OF STUD
18 GA. METAL TOP TRACK
~ ANCHOR TO CEILING
TRACK, SET IN BED OF
SEALANT (AT TRACK
LOCATION ONLY)
PROVIDE METAL L-BEAD,
TYP EACH SIDE OF WALL
<N> CEILING TILE
PROVIDE METAL STUD
DIAGONAL BRACING TO
STRUCTURE AT 48" O.C.,
ALTERNATE DIRECTION
PROVIDE ACOUSTIC
BATT INSULATION FROM
FLOOR TO CEILING
ABOVE BETWEEN
STUDS, FULL DEPTH OF
WALL
SUPPORT HANGERS
SECTION
INSTALL 12" MIN. ACOUSTIC
BATT INSULATION OVER
<N> AND <E> WALL
LOCATIONS TO A MINIMUM
OF 4-0" FROM WALL, EACH
SIDE.
(E) CMU WALL
(N) RESILIENT FURRING
CHANNELS
PLAN
(N) 5/8" GYPSUM BOARD
WALL
TYPE
2.0UN-
RATED
ASSUMED (E) 3 5/8"
FURRING & INSULATION
2 HR FIRE RATED
UL UL404B
SUSPENDED ACOUSTIC TILE (ACT) ~
MATCH EXISTING ADJACENT CEILING TILE
RE: CEILING PLAN AND ROOM FINISH SCHEDULE
FOR CEILING ELEVATIONS
SUSPENDED SUPPORT HANGERS ~
ATTACH TO STRUCTURE ABOVE AT
EACH INTERSECTIONS OF CROSS TEE'S
SUSPENDED CEILING
CROSS TEE'S ~ NEW TEE'S
TO MATCH ADJACENT <E>
TEE'S
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:1
P
M
G 0 04 4 50
DCA / RS
DAM / LB 04/15/2019
22X34
WALL TYPES CEILING TYPES
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
1 1/2" = 1'-0"
WALL TYPES
1 1/2" = 1'-0"
CEILING TYPE C1 - Typical ACT Ceiling
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
AREA OF
WORK ~ PART
'A'
18.1
G
H
I
J
13 14 15 16 17 1816.112.1
REMOVE <E> FLOORING
<E> FLOORING TO REMAIN
DF1 DF1
DF3
DF3
DF5
1197 1198
11401141
DF7
DF8
DF6
/2
/2
R.O
3' - 2" 15' - 3 5/8"
R.O
3' - 2" 5" 3' - 2" 5"
DF9
/8
STATE
CONSERVATIONIST
DEPUTY
2403 STATE
CONSERVATIONIST
RECEPTION AREA
2405A
HALL WAY
2405B
COMM/ ELEC.
N.I.C.
MEN'S TOILET
NO. 3
N.I.C.
WOMEN'S TOILET
NO. 3
N.I.C.
MAIL ROOM
OFFICE PAS
OFFICE
OPERATIONS
OFFICE
PROGRAMS
OFFICE ECS
OFFICE AREA
OFFICE ADMIN.
OFFICE ADMIN.
OFFICE ADMIN.
N.I.C.
OFFICE ADMIN.
N.I.C.
HALL WAY
N.I.C.
HALL WAY
N.I.C.
EXECUTIVE
LARGE MEETING
ROOM
MATCH LINE
WALL TO BE REMOVED IN ITS
ENTIRETY
DEMO LEGEND
DOOR TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
KEYNOTE TAGXX
XX DOOR TAG - DOOR TO BE
SALVAGED FOR REUSE
MATCH LINE
GENERAL AND SALVAGE NOTES:
1. CAREFULLY REMOVE ALL <E> INTERIOR DOOR LEAVES FOR REINSTALLATION (13 TOTAL DOORS).
2. COORDINATE REMOVAL AND REINSTALLATION OF MISC WALL MOUNTED ITEMS WITH OWNER
3. CONTRACTOR TO COORDINATE REMOVAL/REUSE OF (E) CUBICLES, FURNITURE, & CASEWORK WITH NRCS & GSA
4. REMOVE ALL FLOORING WITHIN AREA. SALVAGE <E> CARPET TO PATCH WHERE WALL REMOVED AT ADJACENT
SPACE TO SOUTH.
5. CAREFULLY REMOVE ALL <E> WINDOW COVERINGS. PROTECT & STORE FOR REINSTALLATION IN SAME LOCATION.
6. ALL <E> EXTERIOR WINDOWS TO REMAIN, PROTECT IN PLACE.
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:4
P
M
A 4 01 5 50
DCA / RS
DAM / LB 04/15/2019
22X34
2nd FLOOR
ENLARGED DEMO FLOOR PLAN - PART 'A'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
2nd FLOOR KEY PLAN
N
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1/8" = 1'-0"
DEMO - SECOND LEVEL FLOOR PLAN - PART 'A'
N
N
DEMO KEYNOTES
Key Value Keynote Text
DF1 REMOVE <E> INTERIOR WINDOW
DF3 <E> FINISHES TO REMAIN
DF5 COORDINATE RELOCATION OF IT EQUIPMENT WITH NRCS IT
STAFF, RE: ELEC.
DF6 REMOVE (E) GWB. THIS SIDE
DF7 REMOVE (E) PORTION OF (E) MASONRY WALL (E) BEAM TO
REMAIN
DF8 (E) SOFFIT TO REMAIN
DF9 (E) COLUMN TO REMAIN
0 8' 16'
C
D
E
F
G
15 16 16.1
DF3
DF3
AREA OF
WORK ~ PART
'B'
FILE/STORAGE
ROOM
PROGRAMS
CLOSET
OFFICE AREA
ECS PLOT AREA
& SUPPORT
SPACE
OFFICE AREA
EXISTING MECH.
EQUIP/FURN
STORAGE PAS
FILE STORAGE
LIBRARY
STAIR
N.I.C.
MATCH LINE
WALL TO BE REMOVED IN ITS
ENTIRETY
DEMO LEGEND
DOOR TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
KEYNOTE TAGXX
XX DOOR TAG - DOOR TO BE
SALVAGED FOR REUSE
MATCH LINE
GENERAL AND SALVAGE NOTES:
1. CAREFULLY REMOVE ALL <E> INTERIOR DOOR LEAVES FOR REINSTALLATION (13 TOTAL DOORS).
2. COORDINATE REMOVAL AND REINSTALLATION OF MISC WALL MOUNTED ITEMS WITH OWNER
3. CONTRACTOR TO COORDINATE REMOVAL/REUSE OF (E) CUBICLES, FURNITURE, & CASEWORK WITH NRCS & GSA
4. REMOVE ALL FLOORING WITHIN AREA. SALVAGE <E> CARPET TO PATCH WHERE WALL REMOVED AT ADJACENT
SPACE TO SOUTH.
5. CAREFULLY REMOVE ALL <E> WINDOW COVERINGS. PROTECT & STORE FOR REINSTALLATION IN SAME LOCATION.
6. ALL <E> EXTERIOR WINDOWS TO REMAIN, PROTECT IN PLACE.
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:4
P
M
A 4 02 6 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
ENLARGED DEMO FLOOR PLAN - PART 'B'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
N
1/8" = 1'-0"
DEMO - SECOND LEVEL FLOOR PLAN - PART 'B'
2nd FLOOR KEY PLAN
N
DEMO KEYNOTES
Key Value Keynote Text
DF3 <E> FINISHES TO REMAIN
R E
F
D W
GENERAL PLAN NOTES
1. REFER TO RCP, MECH, ELEC, AND PLUMBING FOR ADDITIONAL INFORMATION
2. REINSTALL <E> WINDOW COVERINGS IN SAME LOCATION. PROTECT IN PLACE.
TYP. ALL WINDOWS
3. ALL FURNISHINGS AND SYSTEMS FURNITURE BY OWNER CONSULTANT. SHOWN
FOR REFERENCE ONLY.
4. COORDINATE RELOCATION OF IT EQUIPMENT W/ NRCS STAFF. REFER TO
ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.
5. DIMENSIONS TO CL OF DOORS IN (N) WALLS
6. PREP SUB FLOOR FOR <N> FLOORING
18.1
G
H
I
J
13 14 15 16 17 1816.112.1
STORAGE & IT
WAITING /
RECEPTION
MEETING ROOM 1
MEETING ROOM 2
BREAK ROOM
CLOSET /
STORAGE
N.I.C.
DN
EXISTING MEN'S
RR (N.I.C.)
N.I.C.
EXISTING
WOMEN'S RR
(N.I.C.)
N.I.C.
EXISTING OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. HALL (N.I.C.)
N.I.C.
EXT. COMM /
ELEC. RM. (N.I.C.)
N.I.C.
STATE CONSERV.
OFFICE
B
2403A
3 3
3.13.1
SNOW OFFICE
PROGRAMS
OFFICE
JEFFCO STG
OPEN OFFICE
PHONE BOOTH
PHONE BOOTH
NF3
3.1
FIN. TO STUD
36' - 5 3/8" 8' - 1 5/8"
10' - 11 1/4"
H O
L D
/8
F
IN
T O
S T
U D
/4
/8
/8
/8
/8
F
IN
T O
S T
U D
/8
A L
IG
N
A L
IG
N
A L
IG
N
A L
IG
N
COPY/ FILE/
STORAGE
/4
CUBICLE PARTITIONS BY
GSA FURNITURE SUPPLIER
5 5/8" 11' - 1 3/4" 6' - 4 7/8"
ADA CABINET FOR
30" X 48" FRONT
APPROACH
A5 011
A L
IG
N
A4 03
A9 01 45
NF5
NF6
CL
2' - 0"
CL
2' - 0"
CL
2' - 0"
NF2
MATCH LINE
NF2
NF6NF6
6' - 7 5/8" 5' - 10" 2' - 3 5/8"
1' - 11 1/2"
AREA OF
WORK ~ PART
'A'
PHONE BOOTH
PHONE BOOTH
18" DEEP ABA COUNTER
ON BRACKETS, RE: A5 01
A5 01
Sim
A5 01
Sim
(N) WALL, RE: TAG FOR TYPE
PLAN LEGEND
KEYNOTE TAGXX
DOOR TAG
MATCH LINE
2.0 WALL TYPE TAG
XXX
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:5
P
M
A 4 03 7 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
ENLARGED NEW FLOOR PLAN - PART 'A'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017N
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1/8" = 1'-0"
NEW - SECOND LEVEL FLOOR PLAN - PART 'A'
2nd FLOOR KEY PLAN
N
NEW KEYNOTES
Key Value Keynote Text
NF2 PATCH END OF WALL MATCH (E) ADJACENT FINISH
NF4 INFILL (E) OPENING WHERE DOOR WAS REMOVED. MATCH
(E) ADJACENT WALL ASSEMBLY; ASSUMED WALL TYPE 3.
NF6 PATCH/REPAIR EXISTING FLOORING AND CEILING TO
MATCH (E) FINISH WHERE WALL IS REMOVED. USE
SALVAGED CARPET FROM DEMO.
0 8' 16'
1/4" = 1'-0"
ENLARGED PLAN - PHONE BOOTHS
ROOMS 2425 & 2427 SIMILAR
E
F
G
15 16 16.1
MECHANICAL
OPEN OFFICE
ECS OFFICE
OPEN OFFICE
DN
CLOSET
SOILS OFFICE
MGT & STRAT.
OFFICE
ENG. OFFICE
OPEN OFFICE
PHONE BOOTH
PHONE BOOTH
FIN TO STUD
11' - 3 1/2" 6' - 4 7/8"
/8
/8
/8
/2
FIN TO STUD
13' - 10 1/2"
/8
/8
F
IN
T O
S T
U D
/8
PLOTTER/ COPY
ECS &
ENGINEERING
STORAGE
/4
NF4
A4 03
Sim
HOLD
8' - 4"
HOLD
4' - 9 3/8"
A9 013 2
A9 01
A9 01 45
NF5
2' - 1"
2' - 1"
MATCH LINE
ALIGN
AREA OF
WORK ~ PART
'B'
GENERAL PLAN NOTES
1. REFER TO RCP, MECH, ELEC, AND PLUMBING FOR ADDITIONAL INFORMATION
2. REINSTALL <E> WINDOW COVERINGS IN SAME LOCATION. PROTECT IN PLACE.
TYP. ALL WINDOWS
3. ALL FURNISHINGS AND SYSTEMS FURNITURE BY OWNER CONSULTANT. SHOWN
FOR REFERENCE ONLY.
4. COORDINATE RELOCATION OF IT EQUIPMENT W/ NRCS STAFF. REFER TO
ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.
5. DIMENSIONS TO CL OF DOORS IN (N) WALLS
6. PREP SUB FLOOR FOR <N> FLOORING
(N) WALL, RE: TAG FOR TYPE
PLAN LEGEND
KEYNOTE TAGXX
DOOR TAG
MATCH LINE
2.0
WALL TYPE TAG
XXX
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:5
P
M
A 4 04 8 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
ENLARGED NEW FLOOR PLAN - PART 'B'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1/8" = 1'-0"
NEW - SECOND LEVEL FLOOR PLAN - PART 'B'
N
2nd FLOOR KEY PLAN
N
NEW KEYNOTES
Key Value Keynote Text
NF2 PATCH END OF WALL MATCH (E) ADJACENT FINISH
NF4 INFILL (E) OPENING WHERE DOOR WAS REMOVED. MATCH
(E) ADJACENT WALL ASSEMBLY; ASSUMED WALL TYPE 3.
NF6 PATCH/REPAIR EXISTING FLOORING AND CEILING TO
MATCH (E) FINISH WHERE WALL IS REMOVED. USE
SALVAGED CARPET FROM DEMO.
AREA OF
WORK ~ PART
'A'
SECOND LEVEL
114' - 6"
<E> WALL BUMP OUT TO REMAIN
18" DEEP PLASTIC
LAMINATE MICROWAVE
SHELVES TO MATCH
CABINETRY ON HIDDEN
COUNTERTOP BRACKETS
PLASTIC LAMINATE COUNTERTOP
W/ 4" INTEGRAL BACKSPLASH
36" CLEAR MIN.
WC24
2' - 0"
WC24
2' - 0"
WC36
3' - 0"
WC36
3' - 0"
WC18
1' - 6" 4' - 6"
PROVIDE 4" TOE KICK
W/ RUBBER BASE
REF.
BC24
2' - 0"
DW
2' - 0"
SB36 (ADA)
3' - 0"
BC36
3' - 0"
BC36
3' - 0"
BC36
3' - 0"
FILLER V.I.F.
5 1/8"
A5 01
A5 01
A5 01
A5 01
A5 01
A5 01
C L E
A R
(N) SINK,
RE: PLUMB
XX-XXX
= CASEWORK TYPE TAG
BC = BASE CABINET
SB = SINK BASE
TC = TALL CABINET
WC = WALL CABINET
DR = DRAWER
DO = DOOR
RF = REFRIGERATOR
DW = DISH WASHER
CASEWORK TYPE CASEWORK INDICATOR
= KEYED NOTE
GENERAL LEGEND:
GENERAL CASEWORK NOTES
1. PROVIDE PLAM FINISHED END PANELS AT ALL EXPOSED CABINET SURFACES
2. REFRIGERATOR, DW AND MICROWAVES PROVIDED BY NRCS. INSTALLED BY
CONTRACTOR
SECOND LEVEL
114' - 6"
HIDDEN COUNTER
BRACKETS, TYP AT EACH
STUD LOCATION AND
WITHIN 3" OF
COUNTERTOP ENDS
PLAM COUNTER
1/4" RADIUS EDGE
1' - 6"
A D
J A
C E
N T
C A
B 'S
M
A T
C H
H E
IG
H
T O
F
PLAM FLAT PANEL DOOR
RUBBER
BASE
BLOCKING
MELAMINE INTERIOR
FINISH (WHITE)
WIRE DOOR PULL
CABINET DOOR
1/4" RADIUS EDGE
/2
SINK, RE:
MECHANICAL
/2
4"
8"
KNEE SPACE OUTLINE11"
BLOCKING
INTEGRAL TOE KICK.
ATTACH TO DOOR WITH
CONT. METAL ANGLES.
PIPE SHIELDING
INSULATION ON ALL
PLUMBING LINES
BELOW SINK
WOOD FALSE DRAWER
PANEL
/2
M A
X
PLAM COUNTERTOP
/2
PLAM COUNTERTOP
W/ 4" INTEGRAL
BACKSPLASH
BLOCKING BY G.C.
CABINET BACK
BLOCKING BY G.C.
FINISHED FLOOR
LINE
DISHWASHER,
RE: SPEC
/2
/2
7/8"
2'-1 1/2" U.N.O.
PLAM COUNTERTOP
W/ 4" INTEGRAL
BACKSPLASH
CLOSURE PIECE AS
NECESSARY FOR
DISHWASHER
RUBBER BASE
PLAM FLAT PANEL
LOCKABLE DOOR
LOCKABLE DRAWER
PLAM COUNTERTOP
& BACKSPLASH W/
4" INTEGRAL
BACKSPLASH
2X BLOCKING
BLOCKING
BLOCKING
CABINET BACK
"4"
WIRE DRAWER
PULL.
ADJUSTABLE
MELAMINE SHELF
2'-1 1/2" U.N.O.
PREMANUFACTURED
PLAM BASE CABINET
WITH MELAMINE
INTERIOR
/4
/4
LOCK
RUBBER BASE
LOCKABLE DRAWER
PLAM COUNTERTOP
& BACKSPLASH
2X BLOCKING
BLOCKING
BLOCKING
CABINET BACK
WIRE DRAWER
PULL.
2'-1 1/2" U.N.O.
4"
LOCKABLE
DRAWER
LOCKABLE DRAWER
PREMANUFACTURED PLAM
BASE CABINET WITH
MELAMINE INTERIOR
4" INTEGRAL PLAM
BACKSPLASH
LOCK
WIRE DOOR PULL
(2) ADJUSTABLE SHELVES:
MELAMINE ON 3/4" SUBSTRATE
MELAMINE CABINET
BACK
LOCKABLE PLAM FLAT
PANEL CABINET DOOR
BLOCKING IN WALL
CABINET BLOCKING
1' - 0"
NOTE: MILLWORK PER CURRENT
EDITION OF AWI STANDARDS
CUSTOM GRADE
3/4" PLYWOOD PLAM
SHELF TO MATCH
CABINETRY
PLAM COUNTERTOP
4" INTEGRAL PLAM
BACKSPLASH
C L E
A R
HIDDEN COUNTER
BRACKET, TYP AT EACH
STUD AND W/ IN 3" OF
COUNTERTOP ENDS
1' - 6"
CHAMFER CORNER 6"
TO MEET WALL
CABINET
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:5
P
M
A 5 01 9 50
DAM / RS
DAM / LB 04/15/2019
22X34
CASEWORK DETAILS
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
2nd FLOOR KEY PLAN
N
1/2" = 1'-0"
Break Room 2405 Elevation- South
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1 1/2" = 1'-0"
SECTION @ PHONE BOOTH COUNTER
1 1/2" = 1'-0"
ADA SINK
1 1/2" = 1'-0"
BASE CABINET @ DISHWASHER
1 1/2" = 1'-0"
BASE CABINET W/ DRAWER
1 1/2" = 1'-0"
BASE CABINET - 3 DRAWERS
1 1/2" = 1'-0"
UPPER CABINET
1 1/2" = 1'-0"
WALL SHELVES
3' - 0"
DOOR: RE
SCHEDULE
2"3' - 0"2"1' - 0"2"
4' - 6"
2" 3' - 0" 2"
3' - 4"
DOOR, RE:
SCHEDULE
= DOOR APPROACH DIRECTION
24" MIN
M
IN
*48" MIN (1220) IF
CLOSER IS PROVIDED
(G) LATCH APPROACH,
PUSH SIDE
24" MIN
*54" MIN (1370) IF
CLOSER IS PROVIDED
(F) LATCH APPROACH,
PULL SIDE
M
IN
22" MIN
*IF BOTH CLOSER & LATCH
ARE PROVIDED
**48" MIN (1220) IF BOTH
CLOSER & LATCH
PROVIDED
(E) HINGE APPROACH,
PUSH SIDE
M
IN
12" MIN*
X
(C&D) HINGE APPROACH,
PULL SIDE
Y
22" MIN
(B) FRONT APPROACH,
PUSH SIDE
M
IN
12" MIN*
*IF BOTH CLOSER &
LATCH ARE PROVIDED
18" MIN
(A) HINGE APPROACH,
PULL SIDE
M
IN
X = 36" (915) MIN IF Y = 60"
(1525); X = 42" (1065) MIN
IF Y = 54" (1370)
WALL: SEE WALL TYPES
STEEL STUD
H.M. FRAME
PANEL AS
SCHEDULED
SECOND LAYER OF 5/8"
TYPE 'X' GWB EACH
SIDE TO ACHIEVE
REQUIRED RATING
WALL: SEE WALL TYPES
HEADER --
LIGHT GAGE
STEEL
H.M. FRAME
PANEL, AS
SCHEDULED
NEW OR EXISTING
SECOND LAYER OF 5/8"
TYPE 'X' GWB EACH
SIDE TO ACHIEVE
REQUIRED RATING
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:5
P
M
A 6 01 10 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
DOOR AND WINDOW SCHEDULES
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
DOOR SCHEDULE
NUMBER
ROOM
NUMBER
NEW
DOOR
SALVAGE /
RELOCATE
SALVAGED
DOOR #
DOOR
TYPE
FRAME
MATERIAL
FRAME
TYPE
LEAF
MATERIAL
SIZE FIRE
RATING
HARDWARE
SET COMMENTSTHICKNESS WIDTH HEIGHT
2403A 2403 Yes 1148 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2403B 2403 Yes No A Hollow Metal Steel 1 3/4" 3' - 0" 7' - 0" 1.5 hr 1 CLOSER- adjust door opener so door shall open with a force not to exceed 5 ft lbs
2405 2405 Yes No A Hollow Metal Steel 1 3/4" 3' - 0" 7' - 0" 1.5 hr 1 CLOSER- adjust door opener so door shall open with a force not to exceed 5 ft lbs
2406 2406 Yes No A Hollow Metal Steel 1 3/4" 3' - 0" 7' - 0" 1.5 hr 1 CLOSER- adjust door opener so door shall open with a force not to exceed 5 ft lbs
2408 2408 Yes 1140 EXIST. Hollow Metal (E) 1 3/4" 3' - 0" 7' - 0" 3
2409 2409 Yes No A Hollow Metal Solid Core Wood 1 3/4" 3' - 0" 7' - 0" 3
2411 2411 Yes 1139 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2413 2413 Yes 1151 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2414 2414 Yes 1141 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 2
2415 2415 Yes 1150 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2416 2416 Yes 1149 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 2
2418 2418 No Yes 1128 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2419 2419 Yes 2410 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2424 2424 Yes 1198 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2425 2425 Yes 1197 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 2
2426 2426 Yes 2419 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 4
2427 2427 Yes 2418 EXIST. Hollow Metal B (E) 1 3/4" 3' - 0" 7' - 0" 2
1/2" = 1'-0"
DOOR LEAF TYPE A
1/2" = 1'-0"
DOOR FRAME TYPE B
1/2" = 1'-0"
DOOR FRAME TYPE A 1/4" = 1'-0"
DOOR CLEARANCES
3" = 1'-0"
TYP. PARTITION DOOR JAMB
3" = 1'-0"
TYP. PARTITION DOOR HEAD
MARK DATE DESCRIPTION
NOTE: CONTRACTOR TO VERIFY DIMENSIONS OF EXISTING DOORS TO BE REUSED. PROMPTLY NOTIFY GOVERNMENT & ARCHITECT IF DIMENSIONS VARY FROM SHOWN ABOVE.
A
A
A
A
A
F .D
W
CPT = CARPET TILE
SL = SHEET LINOLEUM
<E> = EXISTING
RB = RUBBER BASE - ALL WALLS
ACT = ACOUSTIC CEILING TILE
PT = PAINT
- EGGSHELL COLOR SELECTED BY OWNER
- 20% OF ALL WALLS ARE ACCENT.
FINISH SCHEDULE LEGEND
GENERAL FINISH PLAN NOTES
1. REMOVE (E) FINISHES IN ALL LOCATIONS NOTED TO RECIEVE NEW FINISH.
2. IF HAZARDOUS MATERIALS ARE DISCOVERED DURING DEMOLITION, STOP WORK
AND NOTIFY GOVERNMENT.
3. ALLOW FOR TWO ACCENT PAINT COLORS (APPOX. 20% OF WALLS). COLOR TO BE
SELECTED BY OWNER.
4. PROVIDE STAINLESS STEEL ABA TRANSITION STRIPS AT ALL ADJACENT
DISSIMILAR FLOORING.
5. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF GYP BOARD WALLS.
6. PATCH AND REPAIR ALL FINISHES DAMAGED BY DEMOLITION OR INSTALLATION
OF EQUIPMENT. MATCH (E) ADJACENT FINISH.
7. PROVIDE SMOOTH AND FLUSH TRANSITION BETWEEN (N) AND (E) GWB.
18.1
C
D
E
F
G
H
I
J
13 14 15 16 17 1816.112.1
STORAGE & IT
WAITING /
RECEPTION
MEETING ROOM 1
MEETING ROOM 2
BREAK ROOM
CLOSET /
STORAGE
N.I.C.
DN
EXISTING MEN'S
RR (N.I.C.)
N.I.C.
EXISTING
WOMEN'S RR
(N.I.C.)
N.I.C.
EXISTING OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. HALL (N.I.C.)
N.I.C.
EXT. COMM /
ELEC. RM. (N.I.C.)
N.I.C.
STATE CONSERV.
OFFICE
SNOW OFFICE
PROGRAMS
OFFICE
JEFFCO STG
PHONE BOOTH
PHONE BOOTH
COPY/ FILE/
STORAGE
ECS OFFICE
ENG. OFFICE
ECS &
ENGINEERING
STORAGE
PLOTTER/ COPY
OPEN OFFICE
OPEN OFFICE
MECHANICAL
SOILS OFFICE
MGT & STRAT.
OFFICE
OPEN OFFICE
CLOSET
PHONE BOOTH
PHONE BOOTH
NF6
NF6NF6
NF2
NF4 NF4
LEGEND:
CARPET
SHEET LINOLEUM
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:5
P
M
A 6 02 11 50
DCA / RS
DAM / LB 10/06/2017
22X34
2ND FLOOR
ROOM FINISH SCHEDULE AND DETAILS
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
ROOM FINISH SCHEDULE
ROOM
NUMBER Area NAME
FLOOR
FINISH BASE
CEILING
FINISH
WALL
FINISH COMMENTS
2401 327 SF WAITING / RECEPTION CPT RB ACT PT
2402 79 SF COPY/ FILE/ STORAGE CPT RB ACT PT
2403 483 SF MEETING ROOM 1 CPT RB ACT PT
2405 321 SF MEETING ROOM 2 CPT RB ACT PT
2406 332 SF BREAK ROOM SL RB <E> ACT PT
2408 80 SF JEFFCO STG SL RB OPEN PT
2409 389 SF STORAGE & IT SL RB OPEN PT
2411 127 SF STATE CONSERV. OFFICE CPT RB ACT PT
2412 2891 SF OPEN OFFICE CPT RB ACT PT
2413 113 SF PROGRAMS OFFICE CPT RB ACT PT
2414 34 SF PHONE BOOTH CPT RB ACT PT
2415 113 SF SNOW OFFICE CPT RB ACT PT
2416 34 SF PHONE BOOTH CPT RB ACT PT
2417 18 SF CLOSET <E> <E> <E> ACT PT
2418 113 SF MGT & STRAT. OFFICE CPT RB ACT PT
2419 113 SF SOILS OFFICE CPT RB ACT PT
2420 291 SF MECHANICAL <E> <E> <E> PT
2421 1514 SF OPEN OFFICE CPT RB ACT PT
2422 106 SF PLOTTER/ COPY CPT RB ACT PT
2423 250 SF ECS & ENGINEERING STORAGE CPT RB ACT PT
2424 114 SF ENG. OFFICE CPT RB ACT PT
2425 30 SF PHONE BOOTH CPT RB ACT PT
2426 114 SF ECS OFFICE CPT RB ACT PT
2427 30 SF PHONE BOOTH CPT RB ACT PT
2428 824 SF OPEN OFFICE CPT RB ACT PT
1/16" = 1'-0"
NEW - SECOND LEVEL FINISH PLAN - OVERALL
MARK DATE DESCRIPTION
NEW KEYNOTES
Key Value Keynote Text
NF2 PATCH END OF WALL MATCH (E) ADJACENT FINISH
NF4 INFILL (E) OPENING WHERE DOOR WAS REMOVED. MATCH
(E) ADJACENT WALL ASSEMBLY; ASSUMED WALL TYPE 3.
NF6 PATCH/REPAIR EXISTING FLOORING AND CEILING TO
MATCH (E) FINISH WHERE WALL IS REMOVED. USE
SALVAGED CARPET FROM DEMO.
P
= SHADED AREA
INDICATED AREA OF
CEILING DEMOLITION
= 2x4 LIGHT FIXTURE TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
= MECHANICAL 2X2 RETURN AIR
FIXTURE TO BE REMOVED OR
RELOCATED, RE: MECHANICAL
DRAWINGS FOR ADDITIONAL
INFORMATION
= CEILING MOUNTED EXIT SIGN WITH
ALUMINATED DIRECTIONAL ARROWS TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
= 2x2 - ACOUSTIC
CEILING TILE (ACT) &
TRACK
TO REMAIN
= 2x4 - ACOUSTIC CEILING TILE
(ACT) SCORED TO LOOK LIKE
2X2 & TRACK TO BE REMOVED
= SEMI RESSED FIRE SPRINKLER (DOWN) TO BE
REMOVED OR RELOCATED,
RE: FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= CEILING MOUNTED FIRE STROBE AND
SPEAKER TO BE REMOVED OR RELOCATED, RE:
FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= CEILING MOUNTED SMOKE DETECTOR TO BE
REMOVED OR RELOCATED,
RE: FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= RESSED CANLIGHT FIXTURE TO BE REMOVED
OR RELOCATED
RE: ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION
= GYPSUM BOARD
CEILING TO REMAIN
CEILING LEGEND:
= MECHANICAL 2x2 AIR SUPPLY
FIXTURE TO BE REMOVED OR
RELOCATED, RE: MECHANICAL
DRAWINGS FOR ADDITIONAL
INFORMATION
= WALL MOUNTED EMERGENCY SIGN WITH
LUMINATED DIRECTIONAL ARROWS TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
G
H
I
J
13 14 15 16 17 1816.112.1
DC1
DC1
DC2
DC3
DC1
DC2
MATCH LINE
AREA OF
WORK ~ PART
'A'
EXECUTIVE
LARGE MEETING
ROOM
STATE
CONSERVATIONIST
DEPUTY
STATE
CONSERVATIONIST
RECEPTION AREA
2405A
HALL WAY
2405B
COMM/ ELEC.
N.I.C.
MEN'S TOILET
NO. 3
N.I.C.
WOMEN'S TOILET
NO. 3
N.I.C.
MAIL ROOM
OFFICE PAS
OFFICE
OPERATIONS
OFFICE
PROGRAMS
OFFICE ECS
OFFICE AREA
OFFICE ADMIN.
OFFICE ADMIN.
OFFICE ADMIN.
N.I.C.
OFFICE ADMIN.
N.I.C.
HALL WAY
N.I.C.
GENERAL DEMO CEILING NOTES
1. REFER TO MECH., ELEC., FIRE PROTECTION SHEETS FOR DEMO OR
RELOCATION OF FIXTURES.
2. <E> ANGLED GYP. SOFFIT TO REMAIN.
3. PATCH AND REPAIR ALL CEILING SURFACES THROUGHOUT AREA OF WORK
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:0
P
M
A 7 01 12 50
DCA / RS
DAM / LB 04/152019
22X34
2ND FLOOR
ENLARGED DEMO REFLECTED CEILING PLAN - PART 'A'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1/8" = 1'-0"
DEMO - SECOND LEVEL RCP - PART 'A'
N
2nd FLOOR KEY PLAN
N
DEMO RCP KEYNOTES
Key Value Keynote Text
DC1 (E) ANGLED GYP. SOFFIT TO REMAIN
DC2 (E) SOFFIT TO REMAIN
DC3 REMOVE PORTION OF (E) MASONRY WALL, (E) BEAM TO
REMAIN
MATCH LINE
= SHADED AREA
INDICATED AREA OF
CEILING DEMOLITION
= 2x4 LIGHT FIXTURE TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
= MECHANICAL 2X2 RETURN AIR
FIXTURE TO BE REMOVED OR
RELOCATED, RE: MECHANICAL
DRAWINGS FOR ADDITIONAL
INFORMATION
= CEILING MOUNTED EXIT SIGN WITH
ALUMINATED DIRECTIONAL ARROWS TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
= 2x2 - ACOUSTIC
CEILING TILE (ACT) &
TRACK
TO REMAIN
= 2x4 - ACOUSTIC CEILING TILE
(ACT) SCORED TO LOOK LIKE
2X2 & TRACK TO BE REMOVED
= SEMI RESSED FIRE SPRINKLER (DOWN) TO BE
REMOVED OR RELOCATED,
RE: FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= CEILING MOUNTED FIRE STROBE AND
SPEAKER TO BE REMOVED OR RELOCATED, RE:
FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= CEILING MOUNTED SMOKE DETECTOR TO BE
REMOVED OR RELOCATED,
RE: FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION
= RESSED CANLIGHT FIXTURE TO BE REMOVED
OR RELOCATED
RE: ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION
= GYPSUM BOARD
CEILING TO REMAIN
CEILING LEGEND:
= MECHANICAL 2x2 AIR SUPPLY
FIXTURE TO BE REMOVED OR
RELOCATED, RE: MECHANICAL
DRAWINGS FOR ADDITIONAL
INFORMATION
= WALL MOUNTED EMERGENCY SIGN WITH
LUMINATED DIRECTIONAL ARROWS TO BE
REMOVED OR RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
C
D
E
F
G
15 16 16.1
DC1
DC1
DC1
DC1
DC1
MATCH LINE
AREA OF
WORK ~ PART
'B'
FILE/STORAGE
ROOM
PROGRAMS
2410CLOSET
OFFICE AREA
ECS PLOT AREA
& SUPPORT
SPACE
OFFICE AREA
EXISTING MECH.
EQUIP/FURN
STORAGE PAS
FILE STORAGE
LIBRARY
STAIR
N.I.C.
GENERAL DEMO CEILING NOTES
1. REFER TO MECH., ELEC., FIRE PROTECTION SHEETS FOR DEMO OR
RELOCATION OF FIXTURES.
2. <E> ANGLED GYP. SOFFIT TO REMAIN.
3. PATCH AND REPAIR ALL CEILING SURFACES THROUGHOUT AREA OF WORK
715 FOURTEENTH STREET
GOLDEN, COLORADO 80401
(303) 278-4378
FAX (303) 278-0521
Principal: Dave Anderson
AIA, LEED AP
daveanderson@andarch.com
D R
A W
IN
G
DRAWING NO.
CHECKED BY
DRAWN BY
FLOOR NO.
FILE NAME
DRAWING TITLE
SUB. DATE
SUBMISSION
GSA PM
PROJECT NO.
PROJECT
DESCRIPTION
PROJECT
TITLE
FACILITY CODE
OTHER
BUILDING NOs
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
CONSTR. CON.
SUB A/E
PRIM A/E
CONS. WORK
CONS. CONTR.
A/E TASK NO.
A/E CON. NO.
P R
O
JE
C T
B U
IL
D
IN
G
C O
N T
R A
C T
O R
S G
R
AP
H
IC
S C
AL
E
R E
V
IS
IO
N
N O
T E
S K
E Y
P
LA
N C
E R
T
IF
IC
A
T
IO
N S
Ben Reko
Project Manager
D.F.C. BUILDING 41 ~ SUITE 246
DENVER, COLORADO ~ 80255
303.236.0855 Phone | 720.412.2812 Cell
benjamin.reko@gsa.gov
GENERAL SERVICES
ADMINISTRATION
SHEET OF
DISCIPLINE SHEET TYPE SEQUENCE
SHEET SIZE:
DATE DRAFTED:
ANDERSON HALLAS
ARCHITECTS, PC
PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy documents when no longer needed.8 /8
/2
:0
:0
P
M
A 7 02 13 50
DCA / RS
DAM / LB 04/15/2019
22X34
2ND FLOOR
ENLARGED DEMO REFLECTED CEILING PLANS - PART 'B'
07/25/2019
100 CD ISSUE
BEN REKO
EP-GS-P-08-16-JB-7053
BUILDING 56 - 2ND FLOOR NRCS
CONSOLIDATION
BUILDING 56 - NRCS
BUILDING 56
DENVER, COLORADO 80255
6TH STEET
BUILDING 56
ANDERSON HALLAS ARCHITECTS PC
GS-08P-13-JB-D-0032
EP-GS-P-08-16-JB-7053
GS-08P-JB-D-0017
100% CONSTRUCTION DOCUMENTS
BUILDING 56 - 2ND FLOOR
NRCS CONSOLIDATION
-- FOR CONSTRUCTION --
1/8" = 1'-0"
DEMO - SECOND LEVEL RCP - PART 'B'
N
2nd FLOOR KEY PLAN
N
DEMO RCP KEYNOTES
Key Value Keynote Text
DC1 (E) ANGLED GYP. SOFFIT TO REMAIN
DC2 (E) SOFFIT TO REMAIN
DC3 REMOVE PORTION OF (E) MASONRY WALL, (E) BEAM TO
REMAIN
G
H
I
J
13 14 15 16 17 1816.112.1
NC1
A7 03
NC5
NC4
NC7
NC7
NC7
NC7
AREA OF
WORK ~ PART
'A'
STORAGE & IT
WAITING /
RECEPTION
MEETING ROOM 1
BREAK ROOM
CLOSET /
STORAGE
N.I.C.
EXISTING MEN'S
RR (N.I.C.)
N.I.C.
EXISTING
WOMEN'S RR
(N.I.C.)
N.I.C.
EXISTING OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. OFFICE
(N.I.C.)
N.I.C.
EXT. HALL (N.I.C.)
N.I.C.
EXT. COMM /
ELEC. RM. (N.I.C.)
N.I.C.
STATE CONSERV.
OFFICE
JEFFCO STG
MEETING ROOM 2
COPY/ FILE/
STORAGE
OPEN OFFICE
PROGRAMS
OFFICE
SNOW OFFICE
PHONE BOOTH
PHONE BOOTH
GENERAL CEILING NOTES
1. REFER TO MECH., ELEC., FIRE PROTECTION SHEETS FOR
CEILING FIXTURE LOCATIONS AND ADDITIONAL
INFORMATION
2. REINSTALL <E> WINDOW COVERINGS IN SAME LOCATION.
PROTECT IN PLACE. TYP. ALL WINDOWS
= 2x4 LIGHT FIXTURE NEW OR
RELOCATED, RE:
ELECTRICAL DRAWINGS
FOR ADDITIONAL INFORMATION
= MECHANICAL 2X2 RETURN AIR
FIXTURE NEW OR RELOCATED, RE:
MECHANICAL DRAWINGS FOR
ADDITIONAL…