200686-000-ELEC-Bid Questions Response.pdf
PDF 476 KB Posted
- Solicitation number
- 36C25522R00240001
About this file
This document package includes construction drawings and specifications for an electrical system renovation project. The project scope involves relocating a medical ward for patient privacy at VA Medical Center facility number 589A4 located at 800 Hospital Drive in Columbia, Missouri. Drawing sheets provide demolition plans, lighting plans, power plans, systems plans, and details. Specifications address lighting fixtures, switches, receptacles, communications outlets, low voltage systems, and special power requirements. The solicitation number is 36C25522R00240001 and relates to project number 589A4-21-100. Construction work must comply with NEC and NFPA codes.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ONE-LINE
LSIG = LONG TIME, SHORT TIME,
INSTANTANEOUS, GROUND FAULT
GFI = GROUND FAULT
DISCONNECT SWITCH (SEE EQUIP
CONN SCHED)
CIRCUIT BREAKER
OVERLOADS
FUSE
INDICATOR LIGHT(G=GREEN, R=RED)
CIRCUIT BREAKER ACCESSORIES:
CONTACTS (N.O., N.C.)
K = KIRK KEY INTERLOCK
(CIRCUIT NUMBER / SWITCH SIZE
/ FUSE SIZE / # OF POLES) (# OF
POLES IF OTHER THAN 3)
FUSIBLE SWITCH
ST = SHUNT TRIP
DRAWOUT CONTACTS
G
A
A
A A
AT
AFA
PANEL
M M
VFD AT
RV
SPD
LSIG
GFI
ST
K
'1'
HP KW
N
ATS
E
'1'
(VOLTAGE / SWITCH SIZE / FUSE
SIZE / # OF POLES - NOTED IF
EQUIPMENT NOT SCHEDULED)
STARTER (SEE EQUIP CONN SCHED)
(VOLTAGE / STARTER SIZE /
# OF POLES - NOTED IF
EQUIPMENT NOT SCHEDULED)
GROUND CONNECTION
LIGHTNING ARRESTOR
FEEDER DESIGNATION
SURGE PROTECTIVE DEVICE
(CIRCUIT NUMBER / SWITCH
SIZE / FUSE SIZE / # OF POLES
/ STARTER SIZE) (# OF POLES
IF OTHER THAN 3)
STARTER WITH FUSIBLE SWITCH
2P
2P
(CIRCUIT NUMBER / TRIP SIZE / #
OF POLES) (FRAME SIZE / TRIP
SIZE) (# OF POLES IF OTHER
THAN 3)
CIRCUIT BREAKER (MOLDED CASE
NON-ADJUSTABLE TRIP /
ADJUSTABLE TRIP)
2P 2P
3Ø TRANSFORMER (DELTA PRIMARY
/ WYE SECONDARY)
1Ø TRANSFORMER
METER (UTILITY / PANEL MOUNTED)
EQUIPMENT (SINGLE MOTOR / MULTI-
MOTOR OR OTHER TYPE AS NOTED)
VARIABLE FREQUENCY DRIVE
(HP SIZE IF NOT SCHEDULED)
PANELBOARD
(BUILT-IN SPD)
SPD
TRANSFER SWITCH (ATS =
AUTOMATIC, MTS = MANUAL)
MOTOR STARTER [SINGLE SPEED
ACROSS-THE-LINE (UON)]
(AMP SIZE / VOLTAGE / POLES
/ AIC RATING / NEMA RATING)
(NEMA RATING IF OTHER
THAN NEMA-1)
(NEMA SIZE /
RV AT= REDUCED VOLTAGE /
AUTO-TRANSFORMER /
SS = SOLID STATE)
N1. THE CONTRACTOR SHALL PROVIDE OUTLET BOXES AND
1"C. TO ABOVE NEAREST ACCESSIBLE CEILING FOR ALL
NURSE CALL DEVICE LOCATIONS. ALL NURSE CALL
DEVICE LOCATIONS SHALL BE COORDINATED WITH THE
FINAL DRAWINGS FROM THE NURSE CALL SYSTEM
SUPPLIER. COORDINATE ALL REQUIREMENTS WITH THE
NURSE CALL SYSTEM SUPPLIER. MOUNTING HEIGHT FOR
EMERGENCY BATH STATIONS SHALL BE PER AIA
GUIDELINES.
NURSE CALL
H1. DO NOT ROUTE BRANCH CIRCUITS OR FEEDERS
ABOVE OR BELOW IMAGING ROOMS BECAUSE OF
POSSIBLE ELECTROMAGNETIC INTERFERENCE.
H2. BOND PANELBOARDS SERVING THE SAME PATIENT
CARE VICINITY WITH #6 AWG MINIMUM COPPER
CONDUCTOR PER NEC ARTICLE 517. THIS INCLUDES
NORMAL AND ESSENTIAL PANELBOARDS AND
ESSENTIAL PANELBOARDS FED FROM DIFFERENT
TRANSFER SWITCHES.
H3. THE GROUNDING SYSTEM IN PATIENT CARE AREAS
SHALL BE TESTED BY VOLTAGE AND IMPEDANCE
MEASUREMENTS PER NFPA 99 REQUIREMENTS.
H4. MEDICAL GAS ALARM CABLING SHALL BE PROVIDED
AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
VERIFY ALL REQUIREMENTS WITH THE MEDICAL GAS
SUPPLIER. ALL MEDICAL GAS CABLING SHALL BE IN
CONDUIT.
H5.
H6.
REFER TO THE SPECIFICATIONS FOR REQUIREMENTS
ON COLOR CODING BOXES AND/OR CONDUIT
ACCORDING TO THE SPECIFIC BRANCH OF THE
ESSENTIAL ELECTRICAL SYSTEM.
H7.
REFER TO THE SPECIFICATIONS FOR REQUIREMENTS
ON COLOR CODING OF NAMEPLATES ACCORDING TO
THE SPECIFIC BRANCH OF THE ESSENTIAL ELECTRICAL
SYSTEM.
THIS IS A LIFE SAFETY BUILDING WHICH MEANS IT
SHALL REMAIN REASONABLY OPERATIONAL IN THE
CASE OF A SEISMIC EVENT. REFER TO THE
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS ON
EQUIPMENT BRACING.
H8.
H9.
H10.
ALL PATIENT CARE AREAS (PATIENT ROOMS AND
SUPPORT SPACES) SHALL HAVE TWO GROUND
PATHS PER N.E.C. ARTICLE 517.
THE LIFE SAFETY BRANCH AND THE CRITICAL BRANCH
OF THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE KEPT
ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND
EQUIPMENT AND SHALL NOT ENTER THE SAME
RACEWAY, BOXES, OR CABINETS WITH EACH OTHER OR
OTHER WIRING PER N.E.C. ARTICLE 517.
HEALTHCARE
HOSPITAL GRADE RECEPTACLES SHALL ONLY BE
PROVIDED IN OPERATING ROOMS AND IN CATEGORY 1
AND CATEGORY 2 PATIENT CARE AREAS AS DEFINED
BY NEC ARTICLE 517 AND NFPA 99.
T1. EACH DATA, TELEPHONE, VIDEO, OR OTHER SYSTEMS
OUTLET REQUIRES 1"C. WITH PULL ROPE STUBBED 6"
ABOVE NEAREST ACCESSIBLE CEILING UNLESS
OTHERWISE NOTED ON PLANS. CONDUITS STUBBED
UP ABOVE CEILINGS SHALL BE TURNED OUT 90
DEGREES. PROVIDE INSULATED BUSHINGS ON ALL
CONDUITS. LABEL CONDUIT TO IDENTIFY ITS
INTENDED USE (I.E. TELEPHONE, DATA, ETC.).
COMMUNICATION / DATA
T2. RUN CABLES CONTINUOUS FROM JACK TO
ASSOCIATED SYSTEM PATCH PANEL IN CONDUIT,
CABLE TRAY, OR J-HOOKS PER THE PLANS AND
SPECIFICATIONS. NUMBER BESIDE CABLE
SYMBOL INDICATES QUANTITY OF CABLES
REQUIRED PER HOME RUN.
T3. PROVIDE QUANTITY AND TYPE OF JACKS PER THE
DRAWINGS, SPECIFICATIONS AND DETAILS. PROVIDE
JACK AND CABLE LABELING PER THE SPECIFICATIONS.
1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE
(NEC) & THE AMERICANS WITH DISABILITIES ACT (ADA).
2. REFER TO RELATED ARCHITECTURAL, MECHANICAL,
STRUCTURAL, AND CIVIL DRAWINGS FOR RELATED
INFORMATION.
3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE
DRAWINGS.
4. E.C. SHALL REFER TO MECHANICAL DRAWINGS AND
SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED
WITH WIRING AND CONNECTION OF INTERLOCKING AND
CONTROLS OF MECHANICAL UNITS AND THERMOSTAT
LOCATIONS.
5. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO
MINIMIZE CUTTING OF BRICK OR BLOCK.
6. ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS
OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON
THE JOB PRIOR TO ROUGH-IN.
7. CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND
WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS
REQUIRED.
8. WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON
THE PLANS, THE LARGER CONDUCTOR SIZE SHALL BE
USED THROUGHOUT THE LENGTH OF THE CIRCUIT,
INCLUDING NEUTRAL AND GROUND.
9. "CT" INDICATED ADJACENT TO DEVICE INDICATES DEVICE
MOUNTED ABOVE BACKSPLASH OF COUNTER TOP.
VERIFY EXACT HEIGHT WITH ARCHITECTURAL PLANS AND
ELEVATIONS.
10. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME
RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE
CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY
BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE
CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE
MARKED OR LABELED TO INDICATE WHICH CIRCUIT THEY
ARE ASSOCIATED WITH. SEE SPECIFICATION SECTION
"LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND
CABLES" FOR ADDITIONAL INFORMATION.
12. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE
WITH PANEL DESIGNATION AND CIRCUIT NUMBER
USING CLEAR THERMAL TRANSFER (ELECTRONIC
DYMO) LABELS WITH 1/8" HIGH BLACK LETTERS (OR
CONTRASTING COLOR IF COVERPLATES ARE BLACK OR
BROWN). LABELS SHALL BE SUITABLE FOR
INDOOR/OUTDOOR USE. LABEL THE BACK OF EACH
LIGHT SWITCH COVERPLATE WITH PANEL DESIGNATION
AND CIRCUIT NUMBER USING A FINE BLACK
PERMANENT MARKER.
11. JUNCTION BOX OR RECEPTACLE FOR DRINKING FOUNTAINS
SHALL BE LOCATED BEHIND THE EQUIPMENT SKIRT UNLESS
OTHERWISE NOTED. COORDINATE CONNECTION TYPE AND
LOCATION WITH EQUIPMENT PROVIDED.
13. PROVIDE 18" LONG (MIN.) CONDUIT SLEEVES THRU ALL
WALLS WHERE CABLES ARE INDICATED OR REQUIRED TO
PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS.
SIZE CONDUIT FOR CABLES INSTALLED. AT CABLE TRAYS,
PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH OF
CABLE TRAY. MAXIMUMS SHALL BE:
1"C. = 10 CABLES
2 1/2"C. = 20 CABLES
3"C. = 30 CABLES
4"C. = 50 CABLES
14. LOCATE CABLE TRAYS 6" ABOVE CEILING. OFFSET TRAY
UP AND OVER LIGHT FIXTURES AND DUCTWORK (FIELD
VERIFY AND PROVIDE AS REQUIRED). IF PHYSICALLY
IMPOSSIBLE TO RUN CABLE TRAY UP AND OVER, THEN
PROVIDE CABLE SUPPORT HOOKS FROM STRUCTURE
ABOVE, SIZED AND RATED FOR INSTALLED CABLES PLUS
25% SPARE.
15. PROVIDE DIMMER PER THE SPECIFICATIONS.
COORDINATE DIMMER TYPE AND WIRING WITH
ASSOCIATED LIGHT FIXTURE DIMMING REQUIREMENTS (I.E.
3-WIRE, O-10V, ELECTRONIC OR MAGNETIC LOW VOLTAGE,
ETC.) OR WITH LIGHTING CONTROL SYSTEM PROPRIETARY
REQUIREMENTS (I.E. LUTRON, nLIGHT, DALI, ETC.) AS
NECESSARY. 3-WIRE DIMMERS SHALL BE PROVIDED WITH
A DEDICATED NEUTRAL FOR EACH CONTROL ZONE. 0-10V
DIMMERS SHALL BE PROVIDED WITH DIM/ON/OFF
CONTROL. COORDINATE PHASE CONTROL OF LED
DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.)
WITH LIGHT FIXTURE MANUFACTURER'S
RECOMMENDATIONS. LOW VOLTAGE CONTROL WIRING IS
NOT SHOWN ON PLANS FOR CLARITY, BUT SHALL BE
PROVIDED AS REQUIRED.
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
PEN WEIGHT LEGEND
LIGHT FIXTURE TO BE REMOVED
EXISTING LIGHT FIXTURE TO REMAIN
NEW LIGHT FIXTURE
DUPLEX GROUNDED REC TO BE REMOVED
EXISTING DUPLEX GROUNDED REC TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
SOLID LINES ARE NEW TO BE INSTALLED
NEW DUPLEX GROUNDED RECEPTACLE
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN HALFTONE
SOLID LINES ARE EXISTING TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
DASHED LINES ARE EXISTING TO BE REMOVED
LIGHT FIXTURE TO BE RELOCATED
DUPLEX GROUNDED REC TO BE RELOCATED
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT
DASHED LINES ARE EXISTING TO BE RELOCATED
SECURITY
WALL M
E
W
W
K KEY PAD
SECURITY BEAM DETECTOR
GLASS BREAK SENSOR
CARD READER
MAGNETIC LOCK
ELECTRIC DOOR STRIKE
DOOR POSITION SWITCH
DOOR LOCK & POSITION SWITCHDOOR RELEASE BUTTON
CCTV CAMERA - FIXED
CCTV CAMERA - FIXED
CCTV CAMERA - PAN/TILT/ZOOM
DURESS
CCTV CAMERA - PAN/TILT/ZOOM
SEC ROOM MOTION DETECTOR
SEC ROOM MOTION DETECTOR
WALL
CEILING
CEILING
REQUEST TO EXIT DEVICE (MOTION)ED
WALL/CLG
SEC CORRIDOR MOTION DETECTOR
CEILING
B
CR
RE REQUEST TO EXIT DEVICE (PSHBTN) WALL WAVE OPENER SWITCH 46"AFF
CONDUIT AND WIRING
PHASE CONDUCTORS/
NEUTRAL CONDUCTOR (#12 UON)
EMERGENCY CIRCUIT
CONDUIT RUN PARTIAL CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CDT RUN 2#12 & 1#12 GRD.- 1/2"C.
OR CDT RUN AS NOTED ON PLAN
CDT RUN 2#12 & 1#12 GRD.- 3/4"C.
OR CDT RUN AS NOTED ON PLAN
CLG/WALL
MASTER/SLAVE FIXTURE WHIP
CONDUIT HOME RUN, 2 CIRCUITS.
4#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 3 CIRCUITS.
6#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#10 & 1#10 GRD.
#10
GROUND CONDUCTOR (#12 UON)
CONDUIT HOME RUN, 2 CIRCUITS
SWITCH LEGS (#12 UON)
CEILING
CLG/WALL
CLG/WALL
EARTH/
FLOOR
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
LOW VOLTAGE WIRING CLG/WALL
MISC. EQUIPMENT CONNECTION
CONDUIT SEAL OFF
AUDIO-VISUAL
CEILINGCEILING MOUNTED SPEAKER
CLOCK/SPEAKER (SYSTEM CLOCK)
WALL MOUNTED SPEAKER
DIGITAL CLOCK WITH TIMER
WALL
PA/SOUND SYSTEM W/RACK/SHELF'PACP' FLOOR/WALL
WALL
SYSTEM CLOCK
(A=ANALOG, D=DIGITAL)
WALL
WALL
VOLUME CONTROL
BELL
MICROPHONE OUTLET
WALL
46"AFF
BOTTOM 80"
V
SA
WALL'NCCP' NC CONTROL PANEL
NC STATION: 3-GANG J-BOX
NC STAFF ASSIST STATION
WITHOUT AUDIO
NC DUTY STATION
CEILINGNC ZONE LIGHT
S 46" AFF
NC STAFF STATION W/ AUDIO
NC AUXILIARY JACK
NC BED INTERFACE UNIT 46" AFF
NC MASTER STATION DESKTOP
CLG/WALLNC VISUAL SIGNAL
NC CODE BLUE STATION 46" AFF
NC EMERGENCY BATH STATION
46" AFF
46" AFF
46" AFF
46" AFF
46" AFF
NURSE CALL
NC PATIENT STATION P
N
E
X
A
B
BI
NC
NC NURSE LOCATING LIGHTIR CEILING
1-VOICE OUTLET & JACK (GEN
NOTES T1 & T3)
1-VOICE/1-DATA OUTLET &
JACKS (GEN NOTES T1 & T3)
1-DATA OUTLET & JACK (GEN
NOTES T1 & T3)
18"AFF
CABLE TV OR VIDEO OUTLET &
CONNECTOR (GEN NOTES T1 & T3)
1-VOICE/2-DATA OUTLETS &
JACKS (GEN NOTES T1 & T3)
2-VOICE/2-DATA OUTLETS & JACKS
(GEN NOTES T1 & T3)
1-VOICE/3-DATA OUTLETS &
JACKS (GEN NOTES T1 & T3)
4-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
2-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
3-DATA OUTLETS & JACKS (GEN
NOTES T1 & T3)
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF 18"AFF
18"AFF
18"AFF
COMMUNICATION / DATA
VIDEO COAX CABLE HOME RUN
FIBER OPTIC CABLE HOME RUN
(MULTI MODE)
FIBER OPTIC CABLE HOME RUN
(SINGLE MODE)
DATA UTP CABLE HOME RUN
VOICE UTP CABLE HOME RUN GEN NOTE T2
GEN NOTE T2
GEN NOTE T2
GEN NOTE T2 GEN NOTE T2
### XX
### = TERMINATION ROOM
XX = CABLE CONFIGURATION
SEE HOR.
CABLE
SCHEDULE
POWER
DUPLEX GROUNDED RECEPTACLE
FUSTAT BUSS #SSY
SPECIAL DEVICE (AS NOTED)
JUNCTION BOX - 1-GANG
DOUBLE DUPLEX GROUNDED REC
GROUND FAULT DUPLEX REC
DUPLEX GROUNDED RECEPTACLE
SINGLE GROUNDED RECEPTACLE
DUPLEX GRD REC BOTTOM SWITCHD
GRD FAULT DOUBLE DUPLEX REC
18" AFF
A
ELECTRICAL DISTRIBUTION EQUIP
EQUIPMENT - SEE EQUIPMENT
CONNECTION SCHEDULE
x-x x-x
CONDUIT SLEEVE (GEN NOTE 13)
CABLE TRAY (GEN NOTE 14)
FEEDER DESIGNATION
M MANUAL STARTER
CIRCUIT BREAKER
DISCONNECT SWITCH
M MOTOR
PLUGMOLD SURFACE RACEWAY
S
18" AFF
18" AFF
CEILING
18" AFF
18" AFF
18" AFF
FLOOR/WALL
72" TO TOP
WALL
JUNCTION BOX - 2-GANG
PLUG LOAD SENSOR CEILING
HANDICAP DOOR PUSHBUTTON 36" AFF
RELAY
PUSHBUTTON (1-BUTTON, 2-BUTTON)
BOX MOUNTED TRANSFORMER
46" AFF
CONTACTOR
METER
STARTER OR ATS (AS NOTED)
COMBINATION STARTER/DISC
BUSDUCT PLUG
THERMOSTAT/TEMP SENSOR 46" AFF
SPECIAL OUTLET (SEE
SCHEDULE OR AS NOTED)
BRANCH CIRCUIT PANEL AND
PANEL DESIGNATION
AA
TS
H
P
R
TAMPER-PROOF DUPLEX REC 18" AFF
TAMPER-PROOF GFCI DUPLEX REC 18" AFF
T
C
1J
J
F
1D
2M
SWITCHES (KEYED, PILOT, TIMER)
INDICATES SWITCHING SCHEME
EMERGENCY BATTERY LIGHT FIXT
LIGHT FIXTURE & FIXTURE LETTER
46" AFF
A
A
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
STRIP LIGHT FIXTURE & FIXT LETTERA
A
A
A
1 RELAY OCCUPANCY SENSOR SW
2 RELAY OCCUPANCY SENSOR SW
OCCUPANCY SENSOR
1 RELAY OCCUPANCY SENSOR/
DIMMER SWITCH (GEN NOTE 15)
M
D DIMMER SWITCH (GEN NOTE 15)
ON/OFF SWITCH
S
DS DAYLIGHT SENSOR
CLG/WALL
46" AFF
46" AFFSSS
SSS
S a, b, c
CLG SURF/
RECESSED
CEILING
WALL
CEIL/WALL
WALL
CEIL/WALL
46" AFF
46" AFF
46" AFF
46" AFF
2 3 4
K P T
LIGHTING, SWITCHES AND SENSORS
SWITCHES (1-POLE, 2-POLE,
3-WAY, 4-WAY)
EXIT SIGN (SHADING DENOTES
EXIT FACE SIDE)
FIXTURE WITH SHADED LAMP(S)
ON EMERGENCY POWER
WALLCOMB EXIT SIGN/EM BATTERY LIGHT
LP LIGHTING CONTROL POWER PACK
EP UL-924 LISTED POWER PACK
46" AFF
ON/OFF/0-10V DIMMING SWITCH
S
46" AFF
DUAL TECH ON/OFF SENSOR
S
46" AFF
16-SCENE WALL CONTROLLER
S
46" AFF
DUAL TECH ON/OFF/0-10V DIM SW
S
46" AFF
LOW VOLTAGE SWITCH
S
A
A
A
A A
LIGHT FIXTURE & FIXTURE LETTERA POLEA
AV AV SYSTEM/LIGHTING INTERFACE
A
A CLG SURF/
RECESSED
A
CLG SURF/
RECESSED
A A
A
A
LIGHTING TRACK, TRACK FIXTURES,
& FIXTURE LETTERS CEILING
A AA
A A T
CEILING
PC PHOTOCELL
NIGHT LIGHT - WIRE AHEAD OF
ABBREVIATIONS
NL
EM
WP
CT
UON
ON EMERGENCY POWER
WEATHERPROOF
COUNTERTOP (SEE GEN. NOTE 9)
UNLESS OTHERWISE NOTED
ABOVE FINISHED FLOORAFF
AFG ABOVE FINISHED GRADE
WALLW
CONTROLS
DRINKING FOUNTAIN -
SEE GENERAL NOTE 11
DF
GAP GENERATOR ANNUNCIATOR PANEL
GENERAL NOTES
SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING
OMAHA | LINCOLN | COLORADO SPRINGS | SIDNEY
FARRIS ENGINEERING
farris-usa.com
FE#:202054
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e ig h th in c o fo t o q u a rt e r i n t th re h s t o a lf t th a rt rs t o t o d h t th h t
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
Department of Veterans Affairs
1 BID QUESTION RESPONSE 02/23/22
E-001
ELECTRICAL GENERAL NOTES AND
SYMBOLS
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
ELECTRICAL SHEET INDEX
SHEET NO. SHEET TITLE
ED121 ELECTRICAL DEMOLITION PLAN - 2ND FLOOR - AREA A
ED131 ELECTRICAL DEMOLITION PLAN - 3RD FLOOR - AREA A
ED132 ELECTRICAL DEMOLITION PLAN - 3RD FLOOR - AREA B
EL131 ELECTRICAL LIGHTING PLAN - 3RD FLOOR - AREA A
EL132 ELECTRICAL LIGHTING PLAN - 3RD FLOOR - AREA B
EL141 ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A
EL141.2 ELECTRICAL LIGHTING PLAN - 4TH FLOOR - AREA A - BID ITEM #2 (DEDUCT)
EL431 ELECTRICAL ENLARGED LIGHTING PLANS
EL432 ELECTRICAL ENLARGED LIGHTING PLANS
EL501 ELECTRICAL LIGHTING DETAILS AND SCHEDULES
EP101 ELECTRICAL POWER PLAN - BASEMENT
EP131 ELECTRICAL POWER PLAN - 3RD FLOOR - AREA A
EP132 ELECTRICAL POWER PLAN - 3RD FLOOR - AREA B
EP141 ELECTRICAL POWER PLAN - ROOF
EP431 ELECTRICAL ENLARGED POWER PLANS
EP432 ELECTRICAL ENLARGED POWER PLANS
EP501 ELECTRICAL POWER DETAILS
EP601 ELECTRICAL PARTIAL ONE-LINE DIAGRAM
EP602 ELECTRICAL POWER SCHEDULES
EP603 ELECTRICAL POWER SCHEDULES
EY131 ELECTRICAL SYSTEMS PLAN - 3RD FLOOR - AREA A
EY132 ELECTRICAL SYSTEMS PLAN - 3RD FLOOR - AREA B
EY431 ELECTRICAL ENLARGED SYSTEMS PLANS
EY432 ELECTRICAL ENLARGED SYSTEMS PLANS
E-001 ELECTRICAL GENERAL NOTES AND SYMBOLS
EY501 ELECTRICAL SYSTEMS DETAILS AND SCHEDULES
SPECIAL OUTLETS
MARK DESCRIPTION
BB BED BUG HEATER OUTLET. PROVIDE 50A, 250V, 2P, 3W GROUNDED RECEPTACLE (NEMA
6-50R) WITH MATCHING STAINLESS STEEL COVEPRLATE FOR BED BUG HEATER
CONNECTION. MOUNT UNDER COUNTER UNLESS OTHERWISE NOTED.
DSK CHARTING DESK. PROVIDE (2) 20A, 120V DUPLEX RECEPTACLES, (2) DATA OUTLETS, AND
4-SQUARE JUNCTION BOX WITH 2-GANG MUD RING AND COVERPLATE WITH BRUSHED
OPENING MOUNTED INSIDE CHARTING DESK CASEWORK. PROVIDE 1" CONDUIT TO ABOVE
ACCESSIBLE CEILING WITH PULL CORD. COORDINATE ROUGH-IN REQUIREMENTS WITH
CASEWORK SUPPLIER.
HW HEADWALL CONNECTION. PROVIDE 120V CRITICAL AND 120V NORMAL POWER CIRCUIT TO
SEPARATE JUNCTION BOXES ABOVE CEILING FOR HEADWALL CONNECTION. HEADWALL TO
BE PROVIDED WITH HOSPITAL GRADE RECEPTACLES. PROVIDE TWO-GANG BOX ABOVE
CEILING FOR PHONE/DATA CABLING. PHONE AND DATA 8P8C JACKS AND TERMINATIONS BY
CONTRACTOR. HEADWALL TO BE PROVIDED WITH PROVISIONS FOR NURSE CALL PATIENT
STATION AND CODE BLUE DEVICES. NURSE CALL DEVICES BY CONTRACTOR. HEADWALL TO
BE PROVIDED WITH ROUGH-IN FOR LOW VOLTAGE LIGHTING CONTROL SWITCH AND
ROUGH-IN FOR DIMMER SWITCH. LIGHTING CONTROL DEVICES BY CONTRACTOR. DEVICE
PROVIDED BY VA, INSTALLED BY CONTRACTOR. REFERENCE ARCHITECTURAL HEADWALL
ELEVATIONS AND DETAILS.
PD DOOR POWER SUPPLY. PROVIDE CONNECTION TO DOOR POWER SUPPLY AND OPERATOR
AS REQUIRED. INTERFACE POWER/CONTROLS WITH FIRE ALARM CONTROL PANEL AS
REQUIRED. VERIFY INSTALLATION REQUIREMENTS FOR PUSH BUTTONS AND/OR MOTION
SENSORS AND PROVIDE ROUGH-IN AND INTERCONNECTING CABLING AS REQUIRED FOR A
COMPLETE AND OPERATIONAL SYSTEM. REFERENCE DOOR HARDWARE SPECIFICATIONS
FOR ALL ELECTRIFIED DOOR COMPONENTS.
PL PATIENT LIFT CONNECTION. PROVIDE DUPLEX RECEPTACLE IN LOCKABLE ENCLOSURE
ABOVE CEILING. SIZE LOCKABLE ENCLOSURE AS REQUIRED BY PATIENT LIFT EQUIPMENT.
VERIFY LOCATION WITH PATIENT LIFT CONNECTIONS.
PTV PATIENT TV/FLAT PANEL LOCATION: PROVIDE FSR#PWB-250 RECESSED WALL BOX. PROVIDE
(1) 20A 125V DUPLEX GROUNDED RECEPTACLE, (1) DATA OUTLET, AND (1) CATV OUTLET.
COORDINATE NURSE CALL INTERFACE REQUIREMENTS WITH NURSE CALL VENDOR.
PROVIDE MATCHING COVERPLATE AND ALL ASSOCIATED MOUNTING HARDWARE.
COORDINATE MOUNTING LOCATION SUCH THAT WALL BOX IS COMPLETELY HIDDEN BEHIND
FLAT PANEL DISPLAY AND DOES NOT INTERFERE WITH WALL-MOUNT BRACKET. REFERENCE
DETAIL 6/EY501 FOR ADDITIONAL REQUIREMENTS.
TM TELEMETRY MONITOR LOCATION: PROVIDE PROVIDE DUPLEX RECEPTACLE AND 4-SQUARE
BOX WITH 2-GANG MUDRING. ROUTE 1-1/2" CONDUIT FROM 4-SQUARE BOX TO NEAREST
WALL TO ABOVE ACCESSIBLE CEILING. PROVIDE COVERPLATE WITH BRUSHED OPENING.
VERIFY MOUNTING AND LOCATION WITH COR.
TV TV/FLAT PANEL LOCATION: PROVIDE FSR#PWB-250 RECESSED WALL BOX. PROVIDE (1) 20A
125V DUPLEX GROUNDED RECEPTACLE, (1) DATA OUTLET, AND (1) CATV OUTLET. PROVIDE
MATCHING COVERPLATE AND ALL ASSOCIATED MOUNTING HARDWARE. COORDINATE
MOUNTING LOCATION SUCH THAT WALL BOX IS COMPLETELY HIDDEN BEHIND FLAT PANEL
DISPLAY AND DOES NOT INTERFERE WITH WALL-MOUNT BRACKET. REFERENCE DETAIL
6/EY501 FOR ADDITIONAL REQUIREMENTS.
USB DUAL USB CHARGING RECEPTACLE AND 20A, 125V DUPLEX RECEPTACLE. PROVIDE LEVITON
#T5832 RECEPTACLE OR APPROVED EQUAL. MOUNT AT 30" AFF UNLESS OTHERWISE NOTED.
USBH HOSPITAL GRADE USB OUTLET. 20A DUPLEX RECEPTACLE WITH DUAL USB CHARGING
RECEPTACLE. PROVIDE HUBBELL #USBB8300AC5 TAMPER-PROOF, HOSPITAL GRADE
RECEPTACLE OR APPROVED EQUAL. MOUNT AT 26" AFF UNLESS OTHERWISE NOTED.
WA1 CLINICAL WIRELESS ACCESS POINT. PROVIDE GREEN CAT-6A CABLE DROP WITH 10 FEET
EXCESS CABLE COILED ABOVE CEILING. TERMINATE TO 8P8C CONNECTOR. WIRELESS
ACCESS DEVICE PROVIDED AND INSTALLED BY VA. COORDINATE EXACT LOCATION WITH
COR.
WA2 GUEST WIRELESS ACCESS POINT. PROVIDE PINK CAT-6A CABLE DROP WITH 10 FEET
EXCESS CABLE COILED ABOVE CEILING. TERMINATE TO 8P8C CONNECTOR. WIRELESS
ACCESS DEVICE PROVIDED AND INSTALLED BY VA. COORDINATE EXACT LOCATION WITH
COR.
# Revision Date
1 BID QUESTION RESPONSE 02/23/22
02/24/2022
FLOOR
FLAT PANEL
DISPLAY AND MOUNT
BY OTHERS
SPECIAL OUTLET
1-1/4" CONDUIT WITH PULL CORD
STUB OUT INTO ACCESSIBLE LOCATION
AND INSTALL INSULATED BUSHINGS
TV
CEILING
6"
ACP
IFP
CEILING.
CR
120V.
4 5 6
INSTALL LABEL TO
INDICATE PANEL NAME
AND CIRCUIT.
BMS
QUANTITY AND TYPE OF CABLE
PER SYSTEM MANUFACTURER.
ACCESS CONTROL
INTERFACE PANEL.
24VDC. POWER
SUPPLY FURNISHED
WITH HARDWARE.
POWER
SUPPLY
CONNECT DOOR TO EXISTING LENNEL
ACCESS CONTROL SYSTEM. PROVIDE
EXPANSION CARDS AS REQUIRED FOR
QUANTITY OF DOORS TO BE CONNECTED
TO EXISTING SYSTEM.
RUN CABLE IN
DOOR JAMB.
VERIFY DOOR TYPE WITH ARCHITECTURAL DOOR HARDWARE SCHEDULE.
ELECTRIC STRIKE
CARD READERS. QUANTITIES
AND LOCATIONS PER PLANS.
4'-0" 4'-0"
CEILING
PROVIDE MOUNTING AND FINISHING PLATES
AND ACCESSORIES AS REQUIRED FOR A FULLY
SEALED AND FIRE RATED SYSTEM.
CORRIDOR SIDE ROOM SIDE
ROUTE CABLES IN CABLE
TRAY AS SHOWN ON PLANS
FIRE RATED THRU-WALL PATHWAY EQUAL TO LEGRAND EZ-PATH
SERIES 44. PROVIDE MODULE SIZE AS REQURED FOR NUMBER
OF CABLES. INSTALL PER MANUFACTURER RECOMMENDATION.
TYPICAL J-HOOK
SUPPORTS TO BE
USED WITH-IN
INDIVIDUAL ROOMS.
6" MIN.
SEE J-HOOK
DETAIL
BOND CABLE TRAY TO EACH CONDUIT SLEEVE
VIA #6 BARE COPPER AWG GROUND WIRE.
BASKET CABLE TRAY
RIGID CENTER HANGER.
THREADED ROD COUPLING
NOTE:
CABLE TRAY SHALL BE SUPPORTED
AT MAX. OF 5'-0" ON CENTER.
DO NOT RUN SUPPORTS THROUGH
EXISTING CABLE TRAYS, SUPPORTS
OR EQUIPMENT.
1/2" ALL-THREAD
ROD (TYPICAL)
HEADLESS PLAIN STEEL
HANGER SCREW, 3/8"-16
NUT SIZE, 6" LENGTH.
DRILL 9/16"∅ HOLE IN
SUPPORTING MEMBER
6" MIN.
TYPICAL SUPPENSION OF
CABLE TRAY FROM
STRUCTURE
ABOVE.
CORRIDOR SIDECORRIDOR SIDE
CEILING
4'-0"4'-0"
FIRE RATED THRU-WALL PATHWAY EQUAL TO LEGRAND EZ-PATH
SERIES 44. PROVIDE MODULE SIZE AS REQURED FOR NUMBER OF
CABLES. INSTALL PER MANUFACTURER RECOMMENDATION.
CABLE
TRAY
CABLE TRAY
BOND CABLE TRAY TO EACH CONDUIT SLEEVE
ON EACH SIDE OF PENETRATION VIA #6 BARE
COPPER AWG GROUND WIRE. (TYPICAL)
PROVIDE MOUNTING AND FINISHING PLATES
AND ACCESSORIES AS REQUIRED FOR A FULLY
SEALED AND FIRE RATED SYSTEM.
RJ-45 CONNECTOR FOR
CAT 6A VOICE WIRING
7 853 4 61 2
21 643 5 87 7 853 4 61 2
CONNECTOR FOR CAT. 6
LAN WIRING (TYPICAL OF 2).
CONNECTOR COLOR AS
DIRECTED BY USER
SPECIFICATIONS
EACH VOICE AND DATA PORT SHALL BE PROVIDED WITH A
PORT LABEL LOCATED ABOVE THE PORT. SEE DETAIL xxx
FOR LABELING. (TYPICAL OF 4 PORTS)
VOICE #1
DATA #1
FUTURE
DATA #2
BLANK INSERT PLATE
1" EMT
CEILING
NON-METALLIC
BUSHING
WALL
FLOOR
4 11/16"SQ. x 2 1/8"DEEP
OUTLET BOX WITH SIMPLEX
MUD RING
OMAHA | LINCOLN | COLORADO SPRINGS | SIDNEY
FARRIS ENGINEERING
farris-usa.com
FE#:202054
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
303 S. TOPEKA
WICHITA, KANSAS 67202
316.262.2691
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o t o a rt e r i n t th h t o t th a rt rs t o t o d h t th h t
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
Dwg.
Drawing Number
Building Number
Project Number
Office of Construction and Facilities Management
Department of Veterans Affairs
1 BID QUESTION RESPONSE 02/23/22
EY501
ELECTRICAL SYSTEMS DETAILS AND
SCHEDULES
RELOCATE MEDICAL WARD
FOR PATIENT PRIVACY
800 HOSPITAL DRIVE COLUMBIA, MO 65201
07-26-2021
589A4-21-100
FINAL CONSTRUCTION DOCUMENTS
N0 SCALE
ACCESS CONTROL DETAIL
N0 SCALE
TYPICAL THRU-WALL CONDUIT SLEEVE
N0 SCALE
BASKET CABLE TRAY SUPPORT
N0 SCALE
CABLE TRAY WALL PENETRATION
N0 SCALE
TYPICAL DATACOM OUTLET DETAIL (QUAD)
N0 SCALE
DATACOM OUTLET DETAIL
HORIZONTAL CABLE SCHEDULE
CABLE
CONFIG.
PHONE DATA TELEMETRY
REF. NOTECABLE JACK
COLOR
CABLE JACK
COLOR
CABLE JACK
COLORQTY TYPE COLOR QTY TYPE COLOR QTY TYPE COLOR
A 0 1 CAT-6A BLUE BLUE 0
C 1 CAT-6A WHITE WHITE 1 CAT-6A BLUE BLUE 0
D 1 CAT-6A WHITE WHITE 2 CAT-6A BLUE BLUE 0
F 0 2 CAT-6A BLUE BLUE 0
H 0 3 CAT-6A BLUE BLUE 0
J 1 CAT-6A WHITE WHITE 1 CAT-6A BLUE BLUE 1 CAT-6A ORANGE ORANGE SPECIAL OUTLET 'HW'
K 0 2 CAT-6A BLUE BLUE 0 SPECIAL OUTLET 'DSK'
L 0 1 CAT-6A TAN TAN 0 SPECIAL OUTLET 'PTV'
M 0 1 CAT-6A GREEN GREEN 0 SPECIAL OUTLET 'WA1'
N 0 1 CAT-6A PINK PINK 0 SPECIAL OUTLET 'WA2'
O 0 1 CAT-6A TAN TAN 0 SPECIAL OUTLET 'TV'
P 0 1 CAT-6A BLUE BLUE 1 CAT-6A ORANGE ORANGE SPECIAL OUTLET 'TM'
Q 1 CAT-6A PURPLE PURPLE SECURITY CAMERA
R 1 CAT-6A BLUE BLUE SPEAKER
N0 SCALE
SPECIAL OUTLET 'TV' & 'PTV'
1 1 1 1
# Revision Date
1 BID QUESTION RESPONSE 02/23/22
02/24/2022
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOLS |
| EY501 - ELECTRICAL SYSTEMS DETAILS AND SCHEDULES |
File details come from the government source that posted it. Updated .