This file consists of electrical plan drawings and specifications for the Southern Delaware County Authority's Beech Street Pump Station Upgrades project located in Upper Chichester, Pennsylvania. The project involves upgrades to pump station electrical systems, including the installation of three new variable frequency drives (VFDs) to replace existing equipment, replacement of 200-ampere three-phase breakers with new 225-ampere three-phase breakers, installation of new wiring and conduit from the existing motor control center (MCC) to the VFDs, and termination of pump connections with junction boxes. The electrical work includes rigid metal conduit installation, liquid-tight flexible conduit connections to pump motors located approximately 30 feet below grade, and control wiring connections to a programmable logic controller (PLC). A mandatory pre-bid conference is scheduled for March 26, 2026, at 10:00 AM at the project site, with sealed bids due by 10:00 AM on Thursday, April 9, 2026, through the PennBid Program. Bids will be publicly opened and read aloud at the specified time.

The project requires a bid bond of ten percent of the total bid amount payable to the Southern Delaware County Authority, along with performance and payment bonds for 100 percent of the contract price and a one-year maintenance bond for 10 percent of the contract price. The successful bidder must pay a PennBid Program fee of one-third of one percent of the contract award value, with a minimum fee of $150.00 and maximum of $6,000.00. All work must comply with the National Electrical Code, 2021 International Building Code, applicable Pennsylvania Department of Environmental Protection standards, prevailing wage requirements, and various insurance, nondiscrimination, and equal opportunity provisions. The project is subject to all Authority, Township, and State standards, rules, and regulations, with the Southern Delaware County Authority retaining the right to accept or reject any and all bids as deemed in the Authority's best interest.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NLOCATION MAP

SCALE: 1"= 1000'

SITE

NOTES:

SOCK FABRIC SHALL MEET STANDARDS OF TABLE 4.1 OF THE PA DEP EROSION CONTROL

MANUAL. COMPOST SHALL MEET THE STANDARDS OF TABLE 4.2 OF THE PA DEP EROSION

CONTROL MANUAL.

COMPOST FILTER SOCK SHALL BE PLACED AT EXISTING LEVEL GRADE. BOTH ENDS OF THE

BARRIER SHALL BE EXTENDED AT LEAST 8 FEET UP SLOPE AT 45 DEGREES TO THE MAIN

BARRIER ALIGNMENT. MAXIMUM SLOPE LENGTH ABOVE ANY BARRIER SHALL NOT EXCEED

THAT SPECIFIED FOR THE SIZE OF THE SOCK AND THE SLOPE OF ITS TRIBUTARY AREA.

TRAFFIC SHALL NOT BE PERMITTED TO CROSS COMPOST FILTER SOCKS.

ACCUMULATED SEDIMENT SHALL BE REMOVED WHEN IT REACHES 1/2 THE ABOVE GROUND

HEIGHT OF THE BARRIER AND PROPERLY DISPOSED.

COMPOST FILTER SOCKS SHALL BE INSPECTED WEEKLY AND AFTER EACH RUNOFF EVENT.

DAMAGED SOCKS SHALL BE REPAIRED ACCORDING TO MANUFACTURER’S SPECIFICATIONS

OR REPLACED WITHIN 24 HOURS OF INSPECTION.

BIODEGRADABLE COMPOST FILTER SOCKS SHALL BE REPLACED AFTER 6 MONTHS;

PHOTODEGRADABLE SOCKS AFTER 1 YEAR. POLYPROPYLENE SOCKS SHALL BE REPLACED

ACCORDING TO MANUFACTURER’S RECOMMENDATIONS.

UPON STABILIZATION OF THE AREA TRIBUTARY TO THE SOCK, STAKES SHALL BE REMOVED.

THE SOCK MAY BE LEFT IN PLACE AND VEGETATED OR REMOVED. IN THE LATTER CASE, THE

MESH SHALL BE CUT OPEN AND THE MULCH SPREAD AS A SOIL SUPPLEMENT.

SECTION

PLAN VIEW

102FL

OW FLOW

M

IN

GENERAL SPECIFICATIONS

ABBREVIATIONS

1.

2.

NOTES:

STANDARD MOUNTING HEIGHTS

WALL-MOUNTED CLOCKS, PROGRAM BELLS, FIRE ALARM AUDIBLE AND

VISUAL DEVICES (OR AS SHOWN ON ARCHITECTURAL DETAILS)

EXIT SIGNS, BATTERY UNITS AND EMERGENCY REMOTE HEADS (OR 6"

BELOW FINISHED CEILING TO TOP OF FIXTURE)

WARNING AND SIGNALING FIXTURES/SIGNS.

TOP OF FLUSH AND SURFACE MOUNTED ELECTRICAL PANELBOARDS,

TELEPHONE CABINETS, OR FIRE ALARM CABINETS EXCLUDING

MULTI-FAMILY RESIDENTIAL DWELLING UNITS.

TOP OF BACK-MOUNTED WALL EXIT FIXTURES (NOT MOUNTED ABOVE

DOORS)

TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT SWITCHES,

MAGNETIC STARTERS, CONTACTORS.

WALL MOUNTED TELEPHONES AND PAY STATIONS, THERMOSTATS

(3'-6" AT HANDICAP LOCATIONS).

MULTI-FAMILY DWELLING UNITS: INSTALL ELECTRICAL PANELS SUCH

THAT HIGHEST BREAKER IS 46" AFF.

WALL MOUNTED ELECTRICAL LIGHT SWITCHES, MANUAL MOTOR

STARTERS, FIRE ALARM PULL STATIONS, AND WALL MOUNTED

WIREMOLD. OBTAIN MOUNTING HEIGHT APPROVAL FROM BUILDING

INSPECTOR PRIOR TO ROUGHING IN LIGHT SWITCHES.

ADA UNIT INTERCOM. CENTER OF "CALL" BUTTON.

ELECTRICAL RECEPTACLE WITHIN ELECTRICAL/MECHANICAL SPACES

AND ELEVATOR ROOMS.

ELECTRICAL RECEPTACLES, TELEPHONE OUTLETS, COMPUTER

OUTLETS UNLESS IN WIREMOLD, OR OTHERWISE NOTED.

BOTTOM OF EXIT SIGN ADJACENT TO DOOR (WHERE REQUIRED)

FINISHED FLOOR

0'-8"

1'-6"

2'-0"

3'-0"

3'-6"

3'-10"

4'-6"

6'-0"

6'-3"

6'-6"

CENTERED ABOVE DOOR OR

WINDOW OPENING

10'-0"

PER N.F.P.A. & A.D.A.

CODE REQUIREMENTS

MUNICIPALITY

USE AND OCC. CLASSIFICATION

APPLICABLE CODES

UPPER CHICHESTER, PA

B (BUSSINESS)

CODE SUMMARY

BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE

MECHANICAL CODE: 2021 INTERNATIONAL MECHANICAL CODE

PLUMBING CODE: 2021 INTERNATIONAL PLUMBING CODE

FUEL GAS CODE: 2021 INTERNATIONAL FUEL GAS CODE

ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (BY REFERENCE)

FIRE CODE: 2021 INTERNATIONAL FIRE CODE

ENERGY CODE: 2021 INTERNATIONAL ENERGY CONSERVATION CODE/ASHRAE 90.1-2019

MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY WALL

CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK OR

BRICK COURSING.

THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED

OTHERWISE ON THE DRAWINGS OR SPECIFICATIONS.

1. DRAWINGS AND SPECIFICATIONS FORM COMPLIMENTARY REQUIREMENTS; PROVIDE WORK SPECIFIED AND NOT SHOWN, AND WORK SHOWN BUT NOT SPECIFIED AS THOUGH EXPLICITLY REQUIRED BY BOTH. ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTENANCES, DEVICES AND MATERIALS OBVIOUSLY

NECESSARY FOR A SOUND, SECURE AND COMPLETE INSTALLATION

2. ANY CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, AND THE REQUIREMENTS OF THE BUILDING SHALL BE BID USING THE MOST STRINGENT REQUIREMENT, INCLUDING THE GREATER QUANTITY OF WORK AND THE GREATER MATERIAL COST

3. THE DRAWINGS AND SPECIFICATIONS INDICATE A PERFORMANCE SPECIFICATION FOR THE FIRE PROTECTION AND FIRE ALARM SYSTEMS. AWARDED CONTRACTORS ARE RESPONSIBLE FOR DETAILED DESIGN AND PREPARATION OF SIGNED AND SEALED ENGINEERING DOCUMENTS FOR REVIEW/APPROVAL FROM OWNERS INSURANCE CARRIER AND LOCAL AUTHORITY HAVING

JURISDICTION.

4. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. COORDINATE WITH ARCHITECTURAL

DRAWINGS AND OTHER TRADES.

5. ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ARCHITECT'S INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL

6. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS INSTALLED IN ACCORDANCE WITH THE ASSOCIATED MANUFACTURER'S INSTRUCTIONS. NOT EVERY COMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLY ASSOCIATED WITH THE PARTICULAR SYSTEM AND/OR REQUIRED BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE SYSTEM SHALL BE FULLY COMMISSIONED AND SIGNED OFF BY AN OFFICER

OF THE RESPECTIVE CONTRACTOR.

7. PRIOR TO COMMENCING WORK, COORDINATION DRAWINGS MUST BE PREPARED AND SUBMITTED FOR REVIEW AND APPROVAL TO THE ARCHITECT/ENGINEER. EACH TRADE (HVAC, PLUMBING, ELECTRIC, AND FIRE PROTECTION) IS RESPONSIBLE FOR DOCUMENTING THEIR WORK ON THE PLAN ORIGINALLY SUBMITTED AS THE SPRINKLER PIPE FABRICATION DRAWING. LOCATION AND ELEVATION OF THE RESPECTIVE DISCIPLINE'S WORK MUST BE SHOWN ON THE COORDINATION DRAWINGS. SHEETMETAL SHOP DRAWINGS SHALL INCLUDE ALL ELEMENTS OF THE EQUIPMENT, DUCTWORK, AIR DEVICES, AND REFLECTED CEILING PLAN

FOR COORDINATION OF CRITICAL DIMENSIONS OF ARCHITECTURAL/STRUCTURAL COMPONENTS.

8. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TO PERFORM WORK IN ACCORDANCE WITH ALL LEGAL

REQUIREMENTS AND WITH THE DESIGN DOCUMENTS.

9. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT DATA FOR MATERIALS AND EQUIPMENT TO THE ARCHITECT FOR REVIEW AND APPROVAL. MATERIALS AND EQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED AND APPROVED. SCHEDULE AT LEAST TEN WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, FOR SUBMITTAL REVIEW SHALL BE ALLOWED.

10. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVED BY ASME AND AGA FOR

INTENDED SERVICE.

11. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK, AND FOR INITIATING, MAINTAINING AND SUPERVISING

ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.

12. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE, AND SHALL BE RESOLVED PRIOR

TO THE INSTALLATION OF THE WORK INVOLVED.

13. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THE STANDARDS, REGULATIONS, CODES, ORDINANCES, AND LAW OF LOCAL, STATE, AND FEDERAL GOVERNMENTS, AND OTHER AUTHORITIES THAT HAVE LAWFUL

JURISDICTION.

14. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALL OTHER TRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC, SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL ARCHITECTURE. OFFSETS IN PIPING AND OFFSETS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

15. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THE WORK OF THAT OR ANY OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE CONTRACTOR WHO SUBMITTED

THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.

16. EACH CONTRACTOR IS RESPONSIBLE FOR ITS CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OF ITS NEW WORK.

CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THE GREATEST EXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OF

CUTTING AND PATCHING WORK.

17. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT A TIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITH INTERRUPTIONS. INTERRUPTIONS SHALL BE

SCHEDULED WITH OWNER 48 HOURS IN ADVANCE.

18. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT WITH OTHER TRADE CONTRACTORS PRIOR TO

INSTALLATION TO AVOID CONFLICTS.

19. ANY DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, GENERAL CONTRACTOR AND ENGINEER. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF THE DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT AND MATERIALS PER OWNERS REQUEST.

20. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT NEAT, RECTILINEAR APPEARANCE WHEN COMPLETED. MAINTAIN MAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES, DUCTS, AND CONDUIT EXPOSED UNLESS SHOWN

AND NOTED TO BE EXPOSED ON DRAWINGS. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS, SO THAT COMPLETED INSTALLATION SHALL OPERATE SAFELY AND

EFFICIENTLY.

21. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW SLEEVES THROUGH CONCRETE FLOORS AND FIRE RATED WALLS OR PARTITIONS WITH UL RATED ASSEMBLIES WITH EQUAL FIRE RATING. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER

SECTIONS AND WITH FLASHING REQUIREMENTS.

22. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.

23. ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED OTHERWISE.

24. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITYFOR PERFORMANCE AND

MATERIALS.

25. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.

26. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT THAT REQUIRES INSPECTION, REPLACEMENT OR REPAIR. ACCESS PANELS SHALL BE A MINIMUM OF 12" X 12" OR AS NEEDED FOR APPROPRIATE ACCESS. TO BE SUPPLIED TO GENERAL CONTRACTOR FOR INSTALLATION. ACCESS PANELS IN RATED ASSEMBLIES SHALL BE ACUDOR FW-5050. ACCESS PANELS IN NON-RATED DRYWALL CEILINGS SHALL BE WIND-LOCK "STEALTH". ACCESS PANELS IN NON-RATED WALLS SHALL BE ADUDOR

UF-5000.

27. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL APPLICABLE EQUIPMENT WITH

THE ELECTRICAL CONTRACTOR.

28. ALL EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET CODE REQUIREMENTS FOR SMOKE

AND COMBUSTIBILITY.

29. AS WORK PROGRESSES AND FOR DURATION OF CONTRACT, MAINTAIN COMPLETE SET OF PRINTS OF CONTRACT DRAWINGS AT JOB SITE AT ALL TIMES. RECORD WORK COMPLETED AND ALL CHANGES FROM ORIGINAL CONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORK INSTALLED AS A MODIFICATION OR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS, MAINTENANCE MANUALS, AND "AS BUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.

30. DO NOT SUPPORT EQUIPMENT FROM SUSPENDED CEILINGS. SUPPORT ALL EQUIPMENT AND PIPING FROM BUILDING. STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS

OF SUPPORT.

31. RUN PIPING/WIRING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.

32. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING/WIRING.

33. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS OR STATED IN THE SPECIFICATIONS SHALL NOT BE MISCONSTRUED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATE AND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS, REGARDLESS OF ANY SPECIFICATION REFERENCES TO OTHER CONTRACTORS.

34. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR ONE YEAR FROM THE DATE OF OWNER'S ACCEPTANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY, REPAIR OR REPLACE DEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTS WITHIN THIS PERIOD. OWNER'S SATISFACTION ANY DAMAGE REPLACEMENTS UNDER GUARANTEED AT NO ADDITIONAL COST TO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW AND

THIS CONTRACT.

A

ABV.

A.F.F.

A.F.G.

A.H.U.

C/B

C.H.

CLG.

CONC.

COND.

CONT'R.

D.E.

DNLT.

DWG

E.B.H.

E.C.

E.F.

ELECT.

EM

E.P.O.

EUH

EWC

EWH

EXIST.

FACP

FATB

FSD

FU

GEN.

G.F.I.

GND.

HP

HTR.

HVAC

H.V.

AMPS

ABOVE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLER UNIT

CIRCUIT BREAKER

CABINET HEATER

CEILING

CONCRETE

CONDENSER

CONTRACTOR

DUAL ELEMENT (TIME DELAY)

DOWNLIGHT

DRAWING

ELECTRIC BASEBOARD HEATER

ELECTRICAL CONTRACTOR

EXHAUST FAN

ELECTRIC

INDICATES LIGHT FIXTURE OR

DEVICE WIRED TO EMERGENCY

CIRCUIT

EMERGENCY POWER-OFF

PUSHBUTTON SWITCH

ELECTRIC UNIT HEATER

ELECTRIC WATER COOLER

ELECTRIC WALL HEATER

EXISTING

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL BOX

FIRE SMOKE DAMPER

FUSE (OR FUSED)

GENERAL

GROUND FAULT INTERRUPT

GROUND

HORSE POWER

HEATER

HEATING, VENTILATING, AND AIR

CONDITIONING

HIGH VOLTAGE (PRIMARY)

IG

JB

KVA

KW

LTG.

L.V.

M.C.

MCB

MECH.

MLO

MOD

MT.

MTD.

MTG.

N.L.

P.C.

PLG

P.S.

R.T.U

SLD

SP/ST

S/S

SW

T/C

TYP.

UH

U.O.N.

V

VAV

WH

WP

XFMR.

(E)

(R)

(RL)

ISOLATED GROUND

JUNCTION BOX

KILOVOLT-AMPERE

KILOWATT

LIGHTING

LOW VOLTAGE

MECHANICAL CONTRACTOR

MAIN CIRCUIT BREAKER

MECHANICAL

MAIN LUGS ONLY

MOTOR OPERATED DOOR

MOUNT

MOUNTED

MOUNTING

NIGHT LIGHTING

PLUMBING CONTRACTOR

PLUMBING

PAY STATION

ROOF TOP UNIT

SINGLE LINE DIAGRAM

SINGLE POLE/SINGLE THROW

SAFETY SWITCH (DISCONNECT

SWITCH)

SWITCH

TIME CLOCK

TYPICAL

UNIT HEATER

UNLESS OTHERWISE NOTED

VOLTS

VARIABLE AIR VOLUME

WATER HEATER

WEATHERPROOF

TRANSFORMER

EXISTING TO REMAIN

REMOVE EXISTING

RELOCATED EXISTING

PRICING INSTRUCTIONS - BASE BID

1. BID PRICE SHALL INCLUDE AN ALLOWANCE FOR CONTROL CONNECTIONS FROM VFD'S TO PLC.

E.C. SHALL ALLOW FOR COORDINATION WITH OWNERSHIP TO FINALIZE THE FULL EXTENT OF

THIS SCOPE.

DRAWING NO. DRAWING TITLE

IS

SUE

BID IS

SUE

3/1

2/2

BEECH STREET - DRAWING INDEX

E0.0 ELECTRICAL COVER SHEET

E0.1 ELECTRICAL COVER SHEET

E1.0 ELECTRICAL DETAILS

E2.1 ELECTRICAL PUMP ROOM ROOM PLAN DEMO PLAN AND NEW WORK PLAN

E5.0 ELECTRICAL SINGLE LINE DIAGRAM 5561 Pennell Rd Media, PA 19063 P: 610.361.0700

6 10

NOTE: (#) DENOTES NUMBER OF SETS OF WIRES

AND CONDUITS

###W#

DENOTES NUMBER OF PHASE/LINE

& NEUTRAL CONDUCTORS WIRE

"X" DENOTES SEPARATELY DERIVED

SYSTEMS, GENERATORS AND

TRANSFORMER SECONDARIES

CONDUCTORS AMPERE VALUE

2 #12

2 #10

2 #8

2 #4

3/4"C

3/4"C

3/4"C

20W2

70W2

30W2

35W2

40W2

45W2

50W2

60W2

N O T E S

WIRE ID #OF WIRES CONDUIT

COPPER (CU) ALUMINUM (AL) REMARKS COPPER (CU) ALUMINUM (AL)

BRANCH & FEEDER CIRCUIT SCHEDULE

GROUND

1 #12 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #8 G.

3/4"C2 #8

2 #8

2 #8

2 #6

2 #10

2 #8

2 #8

2 #2

3/4"C

3/4"C

3/4"C

1"C

1 1/4"C

#OF WIRES CONDUITGROUND

1 #10 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #6 G.

3/4"C2 #8

2 #6

2 #6

2 #4

2 #2

3 #1/0

3 #2/0

3 #3/0

3-250 KCMIL

1 1/4"C

1 1/2"C

2"C

2"C

2 1/2"C

80W2

90W2

100W2

20W3

25W3

30W3

40W3

50W3

60W3

70W3

80W3

90W3

100W3

110W3

125W3

150W3

175W3

200W3

250W3

1 #8 G.

1 #8 G.

1 #8 G.

2 #4

2 #2

3 #12

3 #10

3 #10

3 #4

3 #2

3/4"C

3/4"C

3/4"C

1 1/4"C

1 1/4"C

1 #12 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #10 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #8 G.

3 #8

3 #6

3 #4

3 #2

1 #10 G.3 #8

3 #2 1 #6 G.

1 #6 G.3 #1

1 #6 G.

1 #6 G.

1 #4 G.

3-350 KCMIL 2 1/2"C300W3 1 #4 G.

3-600 KCMIL 3 1/2"C400W3 1 #3 G.

2 #2

3 #3/0

3 #4/0

3-250KCMIL

3-350 KCMIL

1 1/4"C

1 1/4"C

1 1/4"C

2"C

2"C

2"C

3 1/2"C

1 #6 G.

1 #6 G.

2 #2

2 #1

3/4"C

3/4"C

3/4"C

1 1/4"C

1 1/4"C

1 1/4"C

1 1/2"C

1"C

3 #1/0

3 #2/0

1 #4 G.

3-500 KCMIL

3"C

1 #2 G.

(2) 3-250 KCMIL (2) 1 #1 G.

3 #10

3 #10

3 #2

3 #2

1 #10 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #8 G.

1 #6 G.

1 #6 G.

1 #6 G.

1 #6 G.

3 #8

3 #8

3 #6

3 #4

3 #2

3 #1

4 #475W4

(2) 2 1/2"C

1 1/2"C

2 1/2"C

60W4 1 1/4"C4 #6

1 #6 G. 1 #4 G.

3 #4/0 2"C225W3 1 #4 G. 3-300 KCMIL 1 #2 G.

3-500 KCMIL 3"C350W3 (2) 3#4/01 #3 G. (2) 1 #1 G.

WIRE ID #OF WIRES CONDUITGROUND #OF WIRES CONDUITGROUND

(2) 2 1/2"C

100W4

125W4

150W4

175W4

200W4

225W4

250W4

300W4

350W4

400W4

450W4

4 #2

4 #1

4 #1/0

4-250KCMIL

4-500 KCMIL

2"C

2 1/2 "C

3"C

3 1/2"C

4"C

1 #8 G.

1 #6 G.

1 #6 G.

1 #6 G.

1 #4 G.

1 #4 G.

1 #4 G.

1 #3 G.

1 #3 G.

4 #2/0

4 #4/0

4-350 KCMIL

4-600 KCMIL

2"C1 #6 G.4 #3/0

(2) 4#4/0 (2) 1 #2 G.

2"C

3"C

3 1/2"C

(2) 2 1/2"C

(2) 3"C

3"C

(2) 1 #1/0 G.

4 #1

4 #2/0

(2) 4 #4/0

1 #4 G.

1 #4 G.

1 #4 G.

1 #4 G.

1 #2 G.

1 #2 G.

1 #2 G.

(2) 1 #1 G.

(2) 1 #1 G.

4 #3/0

4 #4/0

4-250KCMIL

(2) 4-250 KCMIL

(2) 4-350 KCMIL

(2) 4-600 KCMIL

(3) 4-400 KCMIL

(2) 2 1/2"C

(2) 3"C

(2) 4"C

(3) 3"C

500W4

600W4

800W4

1000W4

(2) 4-250 KCMIL

(2) 1 #2/0 G.

(3) 1 #4/0 G.

(3) 1 #3/0 G.

(2) 1 #1/0 G.

(3) 4-600 KCMIL (3) 4"C1200W4

(3) 4-400 KCMIL (3) 3"C1000UW4 (3) 4-600 KCMIL

(3) 4-600 KCMIL (3) 3 1/2"C1200UW4 (4) 4-500 KCMIL

(4) 4-600 KCMIL1600UW4 (5) 4-600 KCMIL

(5) 4-600 KCMIL2000UW4 (6) 6-600 KCMIL

(2) 4-600 KCMIL (2) 3 1/2"C800UW4 (3) 4-400 KCMIL (3) 3 1/2"C

3 1/2"C400UW4 -- (2) 4-250 KCMIL -- (2) 2 1/2"C4-600 KCMIL

(2) 4#4/0 (2) 2"C450UW4 (2) 4-300 KCMIL (2) 3"C

(2) 4-500 KCMIL750UW4 (3) 4-400 KCMIL (3) 3 1/2"C

(6) 4-600 KCMIL2500UW4 (7) 4-750 KCMIL

(2) 4-350 KCMIL600UW4 (2) 3"C (2) 4"C

3/4"C

3/4"C

1"C

1"C

1"C

1"C

1"C

1"C

3/4"C

3/4"C

3/4"C

3/4"C

3/4"C

3/4"C

1 #8 G.

1 #6 G.

3/4"C

1 1/4"C

2 1/2"C

1 1/4"C

1 #4 G.

1 #4 G.

1 #4 G.

3"C

1 #2 G.

(2) 2 1/2"C

1 #10 G.

1 #8 G.

1"C

2"C

1 1/4"C

1 1/4"C

1 1/2"C

4 #4

4 #2

1 #8 G.

1 #6 G.

1 #6 G.

2"C

2 1/2"C

2 1/2"C

"U" DENOTES UTILITY SERVICE DROP

CONDUCTORS WITHOUT GROUND

(2) 1 #2 G.

(2) 1 #1 G.

(2) 1 #1/0 G.

(3) 1 #2/0 G.

(3) 1 #3/0 G.

2 1/2 "C

3"C

(2) 3"C

(2) 3"C

(2) 3 1/2"C

(3) 3 1/2"C

(3) 4"C

(4) 3 1/2"C

4-500 KCMIL

4-350 KCMIL

4-300 KCMIL

(2) 4-300 KCMIL

(2) 4-350 KCMIL

(2) 4-500 KCMIL

(2) 4-400 KCMIL

(3) 4-600 KCMIL

(4) 4-500 KCMIL (4) 250 KCMIL

FOR CIRCUITS: 3-PHASE + NEUTRAL + GEC GROUND

4-250 KCMIL 2 1/2"C250XW4 1 #2 G. 3"C4-350 KCMIL 1 #1/0 G.

4-350 KCMIL 3"C300XW4 1 #2 G. 3 1/2"C4-500 KCMIL 1 #1/0 G.

4-500 KCMIL 3 1/2"C350XW4 1 #1/0 G. (2) 2 1/2"C(2) 4 #4/0 (2) 1 #3/0 G.

4-600 KCMIL 4"C400XW4 1 #1/0 G. (2) 3"C(2) 4-250 KCMIL (2) 1 #3/0 G.

(2) 4 #4/0 (2) 2 1/2"C450XW4 (2) 1 #1/0 G. (2) 3"C(2) 4-300 KCMIL (2) 1 #3/0 G.

(2) 4-350 KCMIL (2) 3"C600XW4 (2) 1 #2/0 G. (2) 3 1/2"C(2) 4-500 KCMIL (2) 1 #4/0 G.

(2) 4-500 KCMIL (2) 3 1/2"C750XW4 (2) 1 #3/0 G. (3) 3 1/2"C(3) 4-400 KCMIL (3) 250 KCMIL

(2) 4-600 KCMIL (2) 4"C800XW4 (2) 1 #3/0 G. (3) 3 1/2"C(3) 4-400 KCMIL (3) 250 KCMIL

FOR CIRCUITS: 3-PHASE + NEUTRAL

(2) 3"C

(2) 4-500 KCMIL

(4) 3 1/2"C

(5) 3 1/2"C

(6) 3 1/2"C

(3) 3 1/2"C

(4) 3 1/2"C

(5) 3 1/2"C

(6) 4"C

(7) 4"C

THIS CHART IS BASED UPON INSULATED

WIRE IN CONDUIT - NEC TABLE 310.15(b)

(16), EXCEPT FOR WIRE SIZES #8 CU AND

BELOW AS PER NEC 240.4(d).

60 DEG COLUMN #1 AND LESS

75 DEG COLUMN #1/0 AND GREATER

N E

L

TVSS

M

K

E

SURGE PROTECTION DEVICE

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

AUTOMATIC TRANSFER SWITCH

GROUND CONNECTION

KEY INTERLOCK SWITCH

ELECTRIC INTERLOCK SWITCH

LIGHTNING ARRESTOR

COMMUNICATION DEVICES

TYPICAL NOTATIONS

NOTES

LIGHTING SYMBOLS

A 2 a

A 2 a

A 2 a

A 2 a

X X

A

2 a

A

2 a

EM

A A 2 a

A

A 2 a

A 2 a

A

J

LIGHTING SWITCHES & CONTROLS

OS

SF

S3x

SDx

Sosx

Sx

S4x

TC-"#"

x

WAP

MS

WP

EC

J

PB

GENERAL POWER

U

P1-3

G

R

SINGLE LINE SYMBOLS

T

TV

AA/FA

LA

OD

SPD

SPD

U

DS

x

NOTES

1.

125V., 20A DUPLEX RECEPTACLE MOUNTED AT 18" AFF UNLESS

OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF OR 6"

ABOVE COUNTER OR BACKSPLASH. "U" INDICATES USB

RECEPTACLE WITH COMBINATION USB-A AND USB-C (LEVITON

T5633 OR EQUAL).

125V., 20A DUPLEX GFCI RECEPTACLE MOUNTED AT 18" AFF

UNLESS OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF

OR 6" ABOVE COUNTER OR BACKSPLASH. "WP" INDICATES

WEATHERPROOF ENCLOSURE . "U" INDICATES USB RECEPTACLE

WITH COMBINATION USB-A AND USB-C (LEVITON GUAC2 OR

EQUAL).

125V., 20A DOUBLE DUPLEX (QUAD) RECEPTACLE, MOUNTED AT

18" AFF UNLESS OTHERWISE NOTED.

125V., 20A DUPLEX RECEPTACLE WITH BOTTOM RECEPTACLE

CONNECTED TO WALL SWITCH, MOUNTED AT 18" AFF UNLESS

OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF OR 6"

ABOVE COUNTER.

SPECIAL PURPOSE RECEPTACLE, NEMA TYPE, RATING AND

VOLTAGE AS NOTED.

CEILING MOUNTED 125V., 20A DUPLEX RECEPTACLE

CEILING MOUNTED 125V., 20A DOUBLE DUPLEX (QUAD)

RECEPTACLE.

RECESSED COMBINATION POWER/DATA FLOOR DEVICE, LEGRAND

EVOLUTION SERIES BOX OR EQUAL. REFER TO FLOOR PLAN FOR

CONFIGURATION.

RECESSED COMBINATION POWER/DATA FLOOR DEVICE.

LEGRAND EVOLUTION SERIES POKE-THRU DEVICE OR EQUAL.

PROVIDE FIRE RATED ASSEMBLY WHERE REQUIRED.

SURFACE MOUNTED WIRE RACEWAY, TYPE AND DEVICES AS

INDICATED ON PLANS. LEGRAND PLUGMOLD 2000 SERIES OR

EQUAL.

JUNCTION BOX, COORDINATE LOCATION, RATING AND SIZE WITH

END DEVICE. PROVIDE FIRE RATED ASSEMBLY WHERE REQUIRED.

COORDINATE JUNCTION BOX TYPE FOR FAN/ PENDANT RATING

WHERE REQUIRED.

PULL BOX. COORDINATE SIZE AS REQUIRED.

MOTOR RATED SWITCH, COORDINATE LOCATION, RATING, AND

SIZE WITH END DEVICE

DISCONNECT SWITCH, COORDINATE LOCATION, RATING AND SIZE

WITH END DEVICE. IF CONCEALED USE GENERAL DUTY, IF

EXPOSED USE HEAVY DUTY.

FUSED DISCONNECT SWITCH, COORDINATE LOCATION, RATING

AND SIZE WITH END DEVICE. IF CONCEALED USE GENERAL DUTY,

IF EXPOSED USE HEAVY DUTY.

COMBINATION MOTOR STARTER AND DISCONNECT; PROVIDED BY

MECHANICAL CONTRACTOR/PLUMBING CONTRACTOR; INSTALLED

BY ELECTRICAL CONTRACTOR

ELEVATOR CONTROL SWITCH (EC) - 'EC' SHALL BE EATON "ES"

SERIES OR EQUAL WITH THE FOLLOWING:

SHUNT TRIP INTERFACE WITH FIRE ALARM SYSTEM

PILOT LIGHT (PER NFPA 72 & ASME A17.1)

CONTROL POWER (PER NFPA 72 & ASME A17.1)

MONITORING (PER NFPA 72 & ASME A17.1)

AUXILIARY CONTACTS

PROVIDE SURGE PROTECTION (SPD)

OVERHEAD DOOR, COORDINATE POWER/CONTROL

REQUIREMENTS WITH VENDOR/OWNERSHIP.

SURGE PROTECTION DEVICE

HOME RUN TO PANEL, "P1" INDICATES PANEL NAME, "3" INDICATES

CIRCUIT BREAKER POSITION.

PANELBOARD, SURFACE MOUNTED.

PANELBOARD, FLUSH MOUNTED.

TRANSFORMER, SIZE, TYPE AND RATING AS INDICATED ON PLAN.

COPPER GROUND BAR, SIZE AS INDICATED ON PLAN.

COPPER GROUND CONDUCTOR, SIZE AS INDICATED ON PLAN.

PLAN NOTE CALLOUT

NEW CONNECTION TO EXISTING

TERMINATION OF DEMOLITION

LIGHT FIXTURE; "A" INDICATES TYPE, "2" INDICATES CIRCUIT

BREAKER POSITION; "a" INDICATES SWITCHING.

LIGHT FIXTURE CONNECTED TO EMERGENCY (EM) AND/OR NIGHT

LIGHT (NL) CIRCUIT; "A" INDICATES TYPE; "2" INDICATES CIRCUIT

BREAKER POSITION; "a" INDICATES SWITCHING.

PENDANT MOUNTED LIGHT FIXTURE; "A" INDICATES TYPE, "2"

INDICATES CIRCUIT BREAKER POSITION; "a" INDICATES SWITCHING.

RECESSED DOWNLIGHT; "A" INDICATES TYPE; "2" INDICATES CIRCUIT

BREAKER POSITION; "a" INDICATES SWITCHING.

RECESSED WALLWASHER DOWNLIGHT, "A" INDICATES TYPE; "2"

INDICATES CIRCUIT BREAKER POSITION; "a" INDICATES SWITCHING.

WALL MOUNTED LIGHT FIXTURE; "A" INDICATES TYPE, "2" INDICATES

CIRCUIT BREAKER POSITION; "a" INDICATES SWITCH CONTROL.

CEILING OR WALL MOUNTED LINEAR LED LIGHT FIXTURE; "A"

INDICATES TYPE; "2" INDICATES CIRCUIT BREAKER POSITION, "a"

INDICATES SWITCH CONTROL.

TAPE LIGHT OR WALL MOUNTED LED STRIP LIGHT FIXTURE; "A"

INDICATES TYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a"

INDICATES SWITCH CONTROL.

CEILING OR WALL MOUNTED TRACK LIGHT FIXTURE; "A" INDICATES

TYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a" INDICATES

SWITCHING.

POLE MOUNTED LIGHT FIXTURE. "A" INDICATES TYPE, "2" INDICATES

CIRCUIT BREAKER POSITION.

CEILING OR WALL MOUNTED SINGLE FACE EXIT SIGN, "X" INDICATES

TYPE; ARROWS AS INDICATED ON PLANS. CONNECT TO LOCAL

LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING UNLESS

OTHERWISE NOTED.

CEILING OR WALL MOUNTED DOUBLE FACE EXIT SIGN, "X" INDICATES

TYPE, ARROWS AS INDICATED ON PLANS. CONNECT TO LOCAL

LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING UNLESS

OTHERWISE NOTED.

CEILING OR WALL MOUNTED EXIT SIGN WITH INTEGRAL EMERGENCY

LIGHT HEADS; "X" INDICATES TYPE, ARROWS AS INDICATED ON

PLANS. CONNECT TO LOCAL LIGHTING BRANCH CIRCUIT AHEAD OF

ALL SWITCHING UNLESS OTHERWISE NOTED.

WALL MOUNTED EMERGENCY BATTERY PACK WITH (2)-LIGHT HEADS;

"EM" INDICATES TYPE. CONNECT TO LOCAL LIGHTING BRANCH

CIRCUIT AHEAD OF ALL SWITCHING UNLESS OTHERWISE NOTED.

WALL OR CEILING MOUNTED SINGLE HEAD OR TWIN REMOTE

EMERGENCY LIGHT "EM" INDICATES TYPE. "WP" INDICATES

WEATHERPROOF.

CEILING MOUNTED PADDLE FAN, "A" INDICATES TYPE, "2" INDICATES

CIRCUIT BREAKER POSITION.

SWITCHES, COVERPLATES AND RECEPTACLES BASIS OF DESIGN:

COMMERCIAL - DEVICES SHALL BE WHITE WITH A METAL STAINLESS

STEEL COVERPLATE.

RESIDENTIAL-DEVICE COLOR BY ARCHITECT WITH A MATCHING

SCREWLESS COVERPLATE.

LOAD CENTERS, SWITCHBOARDS, PANELBOARDS, SWITCHGEAR,

METER CENTERS, TRANSFORMERS WHERE SHOWN ON PLANS ARE

ESTIMATED SIZES. COORDINATE NEC REQUIRED CLEARANCES WITH

FINAL SELECTION FROM MANUFACTURER. ELECTRICAL

CONTRACTOR RESPONSIBLE FOR SELECTING MANUFACTURER

THAT PROVIDES EQUIPMENT THAT FITS WITHIN THE SIZES SHOWN

ON PLANS OR SMALLER.

1. ALL SWITCHES SHALL BE MOUNTED AT 42" ABOVE FINISHED FLOOR,

UNLESS OTHERWISE NOTED.

2. SWITCHES SHALL BE RATED AT VOLTAGE OF FIXTURES OR LOAD

CONTROLLED.

3. DIMMER SWITCHES SHALL BE COMPATIBLE WITH LIGHTING FIXTURE

AND LAMP SOURCE BALLAST/DRIVER BEING CONTROLLED BY SWITCH.

4. WHERE MULTIPLE SWITCHES ARE SHOWN, GANG SWITCHES IN SINGLE

ENCLOSURE WITH SINGLE FACEPLATE.

TOGGLE SWITCH

CEILING FAN SPEED SWITCH, COORDINATE SWITCH

CONFIGURATION/TYPE WITH MANUFACTURER.

3-WAY TOGGLE SWITCH

4-WAY TOGGLE SWITCH

DIMMER SWITCH

WALL MOUNTED, DUAL TECHNOLOGY OCCUPANCY SENSOR.

CEILING MOUNTED DUAL, TECHNOLOGY OCCUPANCY SENSOR.

DAYLIGHT SENSOR

TIME CLOCK. SEE TC-"#" SCHEDULE.

"x" SWITCHED LIGHT, "x" INDICATES AREA OF SWITCH CONTROL

"WP" WEATHERPROOF ENCLOSURE WITH "NTRL" LISTED COVERPLATE FOR

WET LOCATION

"#" DESIGNATES TIME CLOCK NUMBER

COORDINATE MOUNTING HEIGHT OF COMMUNICATION DEVICES WITH

ARCHITECTURAL ELEVATIONS/OWNERSHIP

VOICE COMMUNICATION OUTLET

DATA COMMUNICATION OUTLET

VOICE & DATA COMMUNICATION OUTLET

COMBINATION COAX/DATA LOCATION (APARTMENT)

RECESSED CABLE TV BOX WITH DUPLEX RECEPTACLE

AND TELE/DATA ACCESSORIES

WIRELESS ACCESS POINT

PANELBOARD; SIZE, TYPE AND RATING AS NOTED

AA = PANEL DESIGNATION;

### = PANEL CAPACITY (AMPERAGE)

MLO = MAIN LUGS ONLY

MCB = MAIN CIRCUIT BREAKER

COORDINATE MFG./TYPE WITH LOCAL UTILITY

METER AND SOCKET. COORDINATE MFG./TYPE WITH LOCAL

UTILITY

TRANSIENT VOLTAGE SURGE SUPPRESSION SYSTEM

PANEL AA

MLO/MCB

MOTOR OR MOTORIZED EQUIPMENT. NUMBER INDICATES

HORSEPOWER (HP)

MOLDED CASE CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER MEDIUM VOLTAGE

FUSED SWITCH

FUSE

CONTACT

RELAY/CONTACTOR COIL

POWER TRANSFORMER, WITH VOLTAGES AS INDICATED

TRANSFORMER: ### - TRANSFORMER CAPACITY AT

AMBIENT

AIR

*** - TRANSFORMER CAPACITY AT FORCED AIR

AA - AMBIENT AIR

FA - FORCED AIR

Y CONFIGURATION TO GROUND DELTA

CONFIGURATION

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

7 10

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

EXAMPLE OF P-1 JUNCTION BOX INSTALLATION FOLLOW SIMILAR INSTALLATION FOR P-2 AND P-3.

E1.0

SCALE - NO SCALE

EXAMPLE OF P-1 JUNCTION BOX

E1.0

SCALE - NO SCALE

125 HP OWNER SUPPLIED VFD SUBMITTAL

E1.0

SCALE - NO SCALE

125 HP OWNER SUPPLIED VFD SUBMITTAL

E1.0

SCALE - NO SCALE

125 HP OWNER SUPPLIED VFD SUBMITTAL

E1.0

SCALE - NO SCALE

125 HP OWNER SUPPLIED VFD SUBMITTAL

8 10

EXIST

MCC

P

(N)

P

(N)VFD

P-3

(N)

VFD

P-2

(N)

VFD

P-1

(N)

1 P

(E)

PROVIDE NEW WIRING FROM MCC TO VFD,

AND FROM VFD TO P-1. FOLLOW SINGLE LINE

DIAGRAM FOR WIRING AND CONDUIT SIZING.

ALL CONDUIT TO BE RUN IN RIGID METAL

CONDUIT. TERMINATE PUMP CONNECTION

WITH JUNCTION BOX IN GROUND FOR

CONNECTION TO PUMP MOTOR WIRES

SHALL BE RAN IN FLEXIBLE LIQUID TIGHT

CONDUIT. PUMP MOTOR LOCATED

APPROXIMATELY 30' BELOW. INSTALLATION

SHALL MATCH JUNCTION BOX STYLE OF P-1

SEE DETAIL 1 ON DWG E1.0. EXISTING PUMP

TO REMAIN.

PROVIDE NEW WIRING FROM MCC TO VFD,

AND FROM VFD TO P-2, AND P-3

RESPECTIVELY. FOLLOW SINGLE LINE

DIAGRAM FOR WIRING AND CONDUIT SIZING.

ALL CONDUIT TO BE RUN IN RIGID METAL

CONDUIT. TERMINATE PUMP CONNECTION

WITH JUNCTION BOX IN GROUND FOR

CONNECTION TO PUMP MOTOR WIRES

SHALL BE RAN IN FLEXIBLE LIQUID TIGHT

CONDUIT. PUMP MOTOR LOCATED

APPROXIMATELY 30' BELOW. INSTALLATION

SHALL MATCH JUNCTION BOX STYLE OF P-1

SEE DETAIL 1 ON DWG E1.0.

INSTALL FLOOR MOUNTED VFD ON METAL

PEDESTAL ABOVE 100 YEAR STORM LEVEL.

METAL PEDESTAL SHALL BE CAPABLE OF

WITHSTANDING WEIGHT OF VFD AND ALLOW

FOR MOUNTING/BOLTING OF VFD DIRECTLY

TO PEDESTAL. PEDESTAL SHALL BE

APPROXIMATELY 30" ABOVE FINISHED

FLOOR. COORDINATE EXACT HEIGHT WITH

CIVIL ENGINEER PRIOR TO FABRICATION.

EXTEND CONTROL WIRING FORM LOCAL PLC

CONTROLLER TO NEW VFD LOCATION.

PROVIDE SPLICE BOXES AS NECESSARY.

CONNECT ALL CONTROL WIRING TO VFD FOB

FULL OPERATION OF VFD.

NEW WORK SHEET NOTES

(R) VFD P-3

(R)

VFD

P-2

(R)

VFD

P-1

EXIST

MCC

P

(R)

P

(R)

P

(E)

VFD

P-3

(R)

VFD

P-2

(R)

VFD

P-1

(R)

DEMOLISH VFD AND UNISTRUT ASSOCIATED

WITH VFD. COORDINATE PUMP INSTALLATION

WITH OTHER TRADES. LEAVE ALL

COMMUNICATION WIRE FOR FUTURE VFD.

PROVIDE SPLICE BOX FOR EXTENSION OF

CONTROL WIRE TO NEW VFD LOCATIONS AS

SHOWN ON NEW WORK DRAWINGS.

DEMOLITION WORK SHEET NOTES

1. ALL WORK SHALL BE COMPLETED IN

ACCORDANCE WITH THE NATIONAL

ELECTRIC CODE AND THE LOCAL

AUTHORITY HAVING JURISDICTION.

2. COORDINATE OTHER TRADE

CONSTRUCTION WITH APPROPRIATE

TRADE.

3. CONFIRM ALL DEVICE MOUNTING HEIGHTS

AND EXISTING CONDITIONS PRIOR TO

INSTALLATION.

4. NEC 110.26 REQUIRED CLEARANCES SHALL

BE MAINTAINED FOR EXISTING AND NEW

ELECTRICAL EQUIPMENT INSTALLED

DURING CONSTRUCTION.

5. COORDINATE ALL VFD TO PLC SIGNAL AND

CONTROL WIRING INTERCONNECTION

REQUIREMENTS WITH OWNERSHIP PRIOR

TO CONSTRUCTION. PLC PROGRAMMING BY

OTHERS. CONTROL AND SIGNAL WIRING BY

E.C.

GENERAL NOTES

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

E2.0

SCALE - 1/8" = 1'-0"

GROUND LEVEL FLOOR PLAN - NEW WORK

E2.0

SCALE - 1/8" = 1'-0"

GROUND LEVEL FLOOR PLAN - DEMOLITION

9 10

REPLACE 200A 3P

BREAKERS WITH NEW

225A 3P BREAKERS

(TYP FOR 3)

3 # 4/0 & 1 #4 GRD CU IN

2" RIGID STL CONDUIT

3 # 4/0 & 1 #4 GRD CU IN

2" LIQUID-TIGHT FLEXIBLE CONDUIT

3 # 4/0 & 1 #4 GRD CU IN

2" RIGID STL CONDUIT

1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE NATIONAL

ELECTRIC CODE AND THE LOCAL AUTHORITY HAVING JURISDICTION.

2. COORDINATE OTHER TRADE CONSTRUCTION WITH APPROPRIATE TRADE.

3. CONFIRM ALL DEVICE MOUNTING HEIGHTS AND EXISTING CONDITIONS PRIOR

TO INSTALLATION.

4. NEC 110.26 REQUIRED CLEARANCES SHALL BE MAINTAINED FOR EXISTING

AND NEW ELECTRICAL EQUIPMENT INSTALLED DURING CONSTRUCTION.

5. COORDINATE ALL VFD TO PLC SIGNAL AND CONTROL WIRING

INTERCONNECTION REQUIREMENTS WITH OWNERSHIP PRIOR TO

CONSTRUCTION. PLC PROGRAMMING BY OTHERS. CONTROL AND SIGNAL

WIRING BY E.C.

6. PROVIDE BONDING & GROUNDING PER NEC.

GENERAL NOTES:

DEMOLISH PUMP EQUIPMENT FEEDER BREAKER.1

DEMO SHEET NOTES

NEW CIRCUIT BREAKER TO MATCH EXISTING MCC KAIC. BLANK OFF OPENINGS

IN EXISTING BUCKET DOOR AS REQUIRED. PROVIDE NEW DOOR HARDWARE TO

SWITCH CIRCUIT BREAKER IF REQUIRED. NEW CIRCUIT BREAKER TRIP CURVES

SHALL BE COORDINATED WITH DOWNSTREAM VFD BREAKER.

NEW VFD OWNER SUPPLIED AND INSTALLED BY E.C. SEE VFD SUBMITTAL ON

DWG E1.0 FOR MORE INFORMATION.

E.C. TO PROVIDE CONNECTION FROM ATS TO PLC TO INDICATE WHEN

GENERATOR IS RUNNING. COORDINATE SIGNALS REQUIRED WITH OWNERSHIP

PRIOR TO CONSTRUCTION. IN A POWER OUTAGE SITUATION ONLY ONE PUMP

TO RUN, OTHER PUMPS TO BE LOCKED OUT.

NEW WORK SHEET NOTES

2 2 2

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

E5.0

SCALE - NO SCALE

ELECTRICAL SINGLE LINE - DEMOLITION

E5.0

SCALE - NO SCALE

ELECTRICAL SINGLE LINE - NEW WORK

10 10

Sheets and Views
82700-100-S-22A Site-TITLE
82700-100-S-22A Site-M1
Sheets and Views
82700-100-S-22A BSPS Mech-M2 EXIST-DEMO
82700-100-S-22A BSPS Mech-M3 PROPOSED PUMPS
82700-100-S-22A BSPS Mech-M4 DETAILS
Sheets and Views
E0.0 n E0.1 COVER-E0.0
E0.0 n E0.1 COVER-E0.1
E1.0 DETAILS-E1.0
E2.1 NEW-E2.1
E5.0 single line-E5.0