2-PLAN Beech St Pump Station Upgrades.pdf
PDF 10 MB Posted
- Solicitation number
- Not on record
- Issued by
- Delaware County, Pennsylvania
About this file
This file consists of electrical plan drawings and specifications for the Southern Delaware County Authority's Beech Street Pump Station Upgrades project located in Upper Chichester, Pennsylvania. The project involves upgrades to pump station electrical systems, including the installation of three new variable frequency drives (VFDs) to replace existing equipment, replacement of 200-ampere three-phase breakers with new 225-ampere three-phase breakers, installation of new wiring and conduit from the existing motor control center (MCC) to the VFDs, and termination of pump connections with junction boxes. The electrical work includes rigid metal conduit installation, liquid-tight flexible conduit connections to pump motors located approximately 30 feet below grade, and control wiring connections to a programmable logic controller (PLC). A mandatory pre-bid conference is scheduled for March 26, 2026, at 10:00 AM at the project site, with sealed bids due by 10:00 AM on Thursday, April 9, 2026, through the PennBid Program. Bids will be publicly opened and read aloud at the specified time.
The project requires a bid bond of ten percent of the total bid amount payable to the Southern Delaware County Authority, along with performance and payment bonds for 100 percent of the contract price and a one-year maintenance bond for 10 percent of the contract price. The successful bidder must pay a PennBid Program fee of one-third of one percent of the contract award value, with a minimum fee of $150.00 and maximum of $6,000.00. All work must comply with the National Electrical Code, 2021 International Building Code, applicable Pennsylvania Department of Environmental Protection standards, prevailing wage requirements, and various insurance, nondiscrimination, and equal opportunity provisions. The project is subject to all Authority, Township, and State standards, rules, and regulations, with the Southern Delaware County Authority retaining the right to accept or reject any and all bids as deemed in the Authority's best interest.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NLOCATION MAP
SCALE: 1"= 1000'
SITE
NOTES:
SOCK FABRIC SHALL MEET STANDARDS OF TABLE 4.1 OF THE PA DEP EROSION CONTROL
MANUAL. COMPOST SHALL MEET THE STANDARDS OF TABLE 4.2 OF THE PA DEP EROSION
CONTROL MANUAL.
COMPOST FILTER SOCK SHALL BE PLACED AT EXISTING LEVEL GRADE. BOTH ENDS OF THE
BARRIER SHALL BE EXTENDED AT LEAST 8 FEET UP SLOPE AT 45 DEGREES TO THE MAIN
BARRIER ALIGNMENT. MAXIMUM SLOPE LENGTH ABOVE ANY BARRIER SHALL NOT EXCEED
THAT SPECIFIED FOR THE SIZE OF THE SOCK AND THE SLOPE OF ITS TRIBUTARY AREA.
TRAFFIC SHALL NOT BE PERMITTED TO CROSS COMPOST FILTER SOCKS.
ACCUMULATED SEDIMENT SHALL BE REMOVED WHEN IT REACHES 1/2 THE ABOVE GROUND
HEIGHT OF THE BARRIER AND PROPERLY DISPOSED.
COMPOST FILTER SOCKS SHALL BE INSPECTED WEEKLY AND AFTER EACH RUNOFF EVENT.
DAMAGED SOCKS SHALL BE REPAIRED ACCORDING TO MANUFACTURER’S SPECIFICATIONS
OR REPLACED WITHIN 24 HOURS OF INSPECTION.
BIODEGRADABLE COMPOST FILTER SOCKS SHALL BE REPLACED AFTER 6 MONTHS;
PHOTODEGRADABLE SOCKS AFTER 1 YEAR. POLYPROPYLENE SOCKS SHALL BE REPLACED
ACCORDING TO MANUFACTURER’S RECOMMENDATIONS.
UPON STABILIZATION OF THE AREA TRIBUTARY TO THE SOCK, STAKES SHALL BE REMOVED.
THE SOCK MAY BE LEFT IN PLACE AND VEGETATED OR REMOVED. IN THE LATTER CASE, THE
MESH SHALL BE CUT OPEN AND THE MULCH SPREAD AS A SOIL SUPPLEMENT.
SECTION
PLAN VIEW
102FL
OW FLOW
M
IN
GENERAL SPECIFICATIONS
ABBREVIATIONS
1.
2.
NOTES:
STANDARD MOUNTING HEIGHTS
WALL-MOUNTED CLOCKS, PROGRAM BELLS, FIRE ALARM AUDIBLE AND
VISUAL DEVICES (OR AS SHOWN ON ARCHITECTURAL DETAILS)
EXIT SIGNS, BATTERY UNITS AND EMERGENCY REMOTE HEADS (OR 6"
BELOW FINISHED CEILING TO TOP OF FIXTURE)
WARNING AND SIGNALING FIXTURES/SIGNS.
TOP OF FLUSH AND SURFACE MOUNTED ELECTRICAL PANELBOARDS,
TELEPHONE CABINETS, OR FIRE ALARM CABINETS EXCLUDING
MULTI-FAMILY RESIDENTIAL DWELLING UNITS.
TOP OF BACK-MOUNTED WALL EXIT FIXTURES (NOT MOUNTED ABOVE
DOORS)
TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT SWITCHES,
MAGNETIC STARTERS, CONTACTORS.
WALL MOUNTED TELEPHONES AND PAY STATIONS, THERMOSTATS
(3'-6" AT HANDICAP LOCATIONS).
MULTI-FAMILY DWELLING UNITS: INSTALL ELECTRICAL PANELS SUCH
THAT HIGHEST BREAKER IS 46" AFF.
WALL MOUNTED ELECTRICAL LIGHT SWITCHES, MANUAL MOTOR
STARTERS, FIRE ALARM PULL STATIONS, AND WALL MOUNTED
WIREMOLD. OBTAIN MOUNTING HEIGHT APPROVAL FROM BUILDING
INSPECTOR PRIOR TO ROUGHING IN LIGHT SWITCHES.
ADA UNIT INTERCOM. CENTER OF "CALL" BUTTON.
ELECTRICAL RECEPTACLE WITHIN ELECTRICAL/MECHANICAL SPACES
AND ELEVATOR ROOMS.
ELECTRICAL RECEPTACLES, TELEPHONE OUTLETS, COMPUTER
OUTLETS UNLESS IN WIREMOLD, OR OTHERWISE NOTED.
BOTTOM OF EXIT SIGN ADJACENT TO DOOR (WHERE REQUIRED)
FINISHED FLOOR
0'-8"
1'-6"
2'-0"
3'-0"
3'-6"
3'-10"
4'-6"
6'-0"
6'-3"
6'-6"
CENTERED ABOVE DOOR OR
WINDOW OPENING
10'-0"
PER N.F.P.A. & A.D.A.
CODE REQUIREMENTS
MUNICIPALITY
USE AND OCC. CLASSIFICATION
APPLICABLE CODES
UPPER CHICHESTER, PA
B (BUSSINESS)
CODE SUMMARY
BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE
MECHANICAL CODE: 2021 INTERNATIONAL MECHANICAL CODE
PLUMBING CODE: 2021 INTERNATIONAL PLUMBING CODE
FUEL GAS CODE: 2021 INTERNATIONAL FUEL GAS CODE
ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (BY REFERENCE)
FIRE CODE: 2021 INTERNATIONAL FIRE CODE
ENERGY CODE: 2021 INTERNATIONAL ENERGY CONSERVATION CODE/ASHRAE 90.1-2019
MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY WALL
CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK OR
BRICK COURSING.
THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED
OTHERWISE ON THE DRAWINGS OR SPECIFICATIONS.
1. DRAWINGS AND SPECIFICATIONS FORM COMPLIMENTARY REQUIREMENTS; PROVIDE WORK SPECIFIED AND NOT SHOWN, AND WORK SHOWN BUT NOT SPECIFIED AS THOUGH EXPLICITLY REQUIRED BY BOTH. ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTENANCES, DEVICES AND MATERIALS OBVIOUSLY
NECESSARY FOR A SOUND, SECURE AND COMPLETE INSTALLATION
2. ANY CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, AND THE REQUIREMENTS OF THE BUILDING SHALL BE BID USING THE MOST STRINGENT REQUIREMENT, INCLUDING THE GREATER QUANTITY OF WORK AND THE GREATER MATERIAL COST
3. THE DRAWINGS AND SPECIFICATIONS INDICATE A PERFORMANCE SPECIFICATION FOR THE FIRE PROTECTION AND FIRE ALARM SYSTEMS. AWARDED CONTRACTORS ARE RESPONSIBLE FOR DETAILED DESIGN AND PREPARATION OF SIGNED AND SEALED ENGINEERING DOCUMENTS FOR REVIEW/APPROVAL FROM OWNERS INSURANCE CARRIER AND LOCAL AUTHORITY HAVING
JURISDICTION.
4. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. COORDINATE WITH ARCHITECTURAL
DRAWINGS AND OTHER TRADES.
5. ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ARCHITECT'S INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL
6. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS INSTALLED IN ACCORDANCE WITH THE ASSOCIATED MANUFACTURER'S INSTRUCTIONS. NOT EVERY COMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLY ASSOCIATED WITH THE PARTICULAR SYSTEM AND/OR REQUIRED BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE SYSTEM SHALL BE FULLY COMMISSIONED AND SIGNED OFF BY AN OFFICER
OF THE RESPECTIVE CONTRACTOR.
7. PRIOR TO COMMENCING WORK, COORDINATION DRAWINGS MUST BE PREPARED AND SUBMITTED FOR REVIEW AND APPROVAL TO THE ARCHITECT/ENGINEER. EACH TRADE (HVAC, PLUMBING, ELECTRIC, AND FIRE PROTECTION) IS RESPONSIBLE FOR DOCUMENTING THEIR WORK ON THE PLAN ORIGINALLY SUBMITTED AS THE SPRINKLER PIPE FABRICATION DRAWING. LOCATION AND ELEVATION OF THE RESPECTIVE DISCIPLINE'S WORK MUST BE SHOWN ON THE COORDINATION DRAWINGS. SHEETMETAL SHOP DRAWINGS SHALL INCLUDE ALL ELEMENTS OF THE EQUIPMENT, DUCTWORK, AIR DEVICES, AND REFLECTED CEILING PLAN
FOR COORDINATION OF CRITICAL DIMENSIONS OF ARCHITECTURAL/STRUCTURAL COMPONENTS.
8. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TO PERFORM WORK IN ACCORDANCE WITH ALL LEGAL
REQUIREMENTS AND WITH THE DESIGN DOCUMENTS.
9. PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT DATA FOR MATERIALS AND EQUIPMENT TO THE ARCHITECT FOR REVIEW AND APPROVAL. MATERIALS AND EQUIPMENT SHALL NOT BE INSTALLED BEFORE SHOP DRAWINGS ARE REVIEWED AND APPROVED. SCHEDULE AT LEAST TEN WORKING DAYS, EXCLUSIVE OF TRANSMITTAL TIME, FOR SUBMITTAL REVIEW SHALL BE ALLOWED.
10. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVED BY ASME AND AGA FOR
INTENDED SERVICE.
11. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK, AND FOR INITIATING, MAINTAINING AND SUPERVISING
ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.
12. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE, AND SHALL BE RESOLVED PRIOR
TO THE INSTALLATION OF THE WORK INVOLVED.
13. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THE STANDARDS, REGULATIONS, CODES, ORDINANCES, AND LAW OF LOCAL, STATE, AND FEDERAL GOVERNMENTS, AND OTHER AUTHORITIES THAT HAVE LAWFUL
JURISDICTION.
14. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALL OTHER TRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC, SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL ARCHITECTURE. OFFSETS IN PIPING AND OFFSETS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
15. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THE WORK OF THAT OR ANY OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE CONTRACTOR WHO SUBMITTED
THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.
16. EACH CONTRACTOR IS RESPONSIBLE FOR ITS CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OF ITS NEW WORK.
CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THE GREATEST EXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS OF
CUTTING AND PATCHING WORK.
17. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE AS SHORT AS POSSIBLE AND AT A TIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITH INTERRUPTIONS. INTERRUPTIONS SHALL BE
SCHEDULED WITH OWNER 48 HOURS IN ADVANCE.
18. CONTRACTOR SHALL COORDINATE ITS RESPECTIVE CEILING MOUNTED EQUIPMENT WITH OTHER TRADE CONTRACTORS PRIOR TO
INSTALLATION TO AVOID CONFLICTS.
19. ANY DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, GENERAL CONTRACTOR AND ENGINEER. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF THE DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT AND MATERIALS PER OWNERS REQUEST.
20. WORK SHALL BE EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT NEAT, RECTILINEAR APPEARANCE WHEN COMPLETED. MAINTAIN MAXIMUM HEAD ROOM AT ALL TIMES. DO NOT RUN PIPES, DUCTS, AND CONDUIT EXPOSED UNLESS SHOWN
AND NOTED TO BE EXPOSED ON DRAWINGS. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS, SO THAT COMPLETED INSTALLATION SHALL OPERATE SAFELY AND
EFFICIENTLY.
21. EACH RESPECTIVE CONTRACTOR SHALL FIRE STOP ALL NEW SLEEVES THROUGH CONCRETE FLOORS AND FIRE RATED WALLS OR PARTITIONS WITH UL RATED ASSEMBLIES WITH EQUAL FIRE RATING. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER
SECTIONS AND WITH FLASHING REQUIREMENTS.
22. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING REQUIREMENTS.
23. ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED OTHERWISE.
24. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITYFOR PERFORMANCE AND
MATERIALS.
25. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.
26. EACH RESPECTIVE CONTRACTOR SHALL PROVIDE PROPER ACCESS TO EQUIPMENT THAT REQUIRES INSPECTION, REPLACEMENT OR REPAIR. ACCESS PANELS SHALL BE A MINIMUM OF 12" X 12" OR AS NEEDED FOR APPROPRIATE ACCESS. TO BE SUPPLIED TO GENERAL CONTRACTOR FOR INSTALLATION. ACCESS PANELS IN RATED ASSEMBLIES SHALL BE ACUDOR FW-5050. ACCESS PANELS IN NON-RATED DRYWALL CEILINGS SHALL BE WIND-LOCK "STEALTH". ACCESS PANELS IN NON-RATED WALLS SHALL BE ADUDOR
UF-5000.
27. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL APPLICABLE EQUIPMENT WITH
THE ELECTRICAL CONTRACTOR.
28. ALL EQUIPMENT, PIPING, INSULATION, ETC., INSTALLED IN HVAC PLENUM SPACES SHALL MEET CODE REQUIREMENTS FOR SMOKE
AND COMBUSTIBILITY.
29. AS WORK PROGRESSES AND FOR DURATION OF CONTRACT, MAINTAIN COMPLETE SET OF PRINTS OF CONTRACT DRAWINGS AT JOB SITE AT ALL TIMES. RECORD WORK COMPLETED AND ALL CHANGES FROM ORIGINAL CONTRACT DRAWINGS CLEARLY AND ACCURATELY INCLUDING WORK INSTALLED AS A MODIFICATION OR ADDITION TO THE ORIGINAL DESIGN TURN OVER ALL OPERATING MANUALS, MAINTENANCE MANUALS, AND "AS BUILT" DRAWINGS TO OWNER AT CONCLUSION OF CONSTRUCTION.
30. DO NOT SUPPORT EQUIPMENT FROM SUSPENDED CEILINGS. SUPPORT ALL EQUIPMENT AND PIPING FROM BUILDING. STRUCTURE TO PROVIDE A VIBRATION FREE INSTALLATION. NOTIFY ARCHITECT AND STRUCTURAL ENGINEER OF ALL WEIGHTS AND METHODS
OF SUPPORT.
31. RUN PIPING/WIRING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.
32. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON PIPING/WIRING.
33. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS OR STATED IN THE SPECIFICATIONS SHALL NOT BE MISCONSTRUED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATE AND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS, REGARDLESS OF ANY SPECIFICATION REFERENCES TO OTHER CONTRACTORS.
34. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR ONE YEAR FROM THE DATE OF OWNER'S ACCEPTANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY, REPAIR OR REPLACE DEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTS WITHIN THIS PERIOD. OWNER'S SATISFACTION ANY DAMAGE REPLACEMENTS UNDER GUARANTEED AT NO ADDITIONAL COST TO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS UNDER LAW AND
THIS CONTRACT.
A
ABV.
A.F.F.
A.F.G.
A.H.U.
C/B
C.H.
CLG.
CONC.
COND.
CONT'R.
D.E.
DNLT.
DWG
E.B.H.
E.C.
E.F.
ELECT.
EM
E.P.O.
EUH
EWC
EWH
EXIST.
FACP
FATB
FSD
FU
GEN.
G.F.I.
GND.
HP
HTR.
HVAC
H.V.
AMPS
ABOVE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLER UNIT
CIRCUIT BREAKER
CABINET HEATER
CEILING
CONCRETE
CONDENSER
CONTRACTOR
DUAL ELEMENT (TIME DELAY)
DOWNLIGHT
DRAWING
ELECTRIC BASEBOARD HEATER
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELECTRIC
INDICATES LIGHT FIXTURE OR
DEVICE WIRED TO EMERGENCY
CIRCUIT
EMERGENCY POWER-OFF
PUSHBUTTON SWITCH
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WALL HEATER
EXISTING
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL BOX
FIRE SMOKE DAMPER
FUSE (OR FUSED)
GENERAL
GROUND FAULT INTERRUPT
GROUND
HORSE POWER
HEATER
HEATING, VENTILATING, AND AIR
CONDITIONING
HIGH VOLTAGE (PRIMARY)
IG
JB
KVA
KW
LTG.
L.V.
M.C.
MCB
MECH.
MLO
MOD
MT.
MTD.
MTG.
N.L.
P.C.
PLG
P.S.
R.T.U
SLD
SP/ST
S/S
SW
T/C
TYP.
UH
U.O.N.
V
VAV
WH
WP
XFMR.
(E)
(R)
(RL)
ISOLATED GROUND
JUNCTION BOX
KILOVOLT-AMPERE
KILOWATT
LIGHTING
LOW VOLTAGE
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MECHANICAL
MAIN LUGS ONLY
MOTOR OPERATED DOOR
MOUNT
MOUNTED
MOUNTING
NIGHT LIGHTING
PLUMBING CONTRACTOR
PLUMBING
PAY STATION
ROOF TOP UNIT
SINGLE LINE DIAGRAM
SINGLE POLE/SINGLE THROW
SAFETY SWITCH (DISCONNECT
SWITCH)
SWITCH
TIME CLOCK
TYPICAL
UNIT HEATER
UNLESS OTHERWISE NOTED
VOLTS
VARIABLE AIR VOLUME
WATER HEATER
WEATHERPROOF
TRANSFORMER
EXISTING TO REMAIN
REMOVE EXISTING
RELOCATED EXISTING
PRICING INSTRUCTIONS - BASE BID
1. BID PRICE SHALL INCLUDE AN ALLOWANCE FOR CONTROL CONNECTIONS FROM VFD'S TO PLC.
E.C. SHALL ALLOW FOR COORDINATION WITH OWNERSHIP TO FINALIZE THE FULL EXTENT OF
THIS SCOPE.
DRAWING NO. DRAWING TITLE
IS
SUE
BID IS
SUE
3/1
2/2
BEECH STREET - DRAWING INDEX
E0.0 ELECTRICAL COVER SHEET
E0.1 ELECTRICAL COVER SHEET
E1.0 ELECTRICAL DETAILS
E2.1 ELECTRICAL PUMP ROOM ROOM PLAN DEMO PLAN AND NEW WORK PLAN
E5.0 ELECTRICAL SINGLE LINE DIAGRAM 5561 Pennell Rd Media, PA 19063 P: 610.361.0700
6 10
NOTE: (#) DENOTES NUMBER OF SETS OF WIRES
AND CONDUITS
###W#
DENOTES NUMBER OF PHASE/LINE
& NEUTRAL CONDUCTORS WIRE
"X" DENOTES SEPARATELY DERIVED
SYSTEMS, GENERATORS AND
TRANSFORMER SECONDARIES
CONDUCTORS AMPERE VALUE
2 #12
2 #10
2 #8
2 #4
3/4"C
3/4"C
3/4"C
20W2
70W2
30W2
35W2
40W2
45W2
50W2
60W2
N O T E S
WIRE ID #OF WIRES CONDUIT
COPPER (CU) ALUMINUM (AL) REMARKS COPPER (CU) ALUMINUM (AL)
BRANCH & FEEDER CIRCUIT SCHEDULE
GROUND
1 #12 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #8 G.
3/4"C2 #8
2 #8
2 #8
2 #6
2 #10
2 #8
2 #8
2 #2
3/4"C
3/4"C
3/4"C
1"C
1 1/4"C
#OF WIRES CONDUITGROUND
1 #10 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #6 G.
3/4"C2 #8
2 #6
2 #6
2 #4
2 #2
3 #1/0
3 #2/0
3 #3/0
3-250 KCMIL
1 1/4"C
1 1/2"C
2"C
2"C
2 1/2"C
80W2
90W2
100W2
20W3
25W3
30W3
40W3
50W3
60W3
70W3
80W3
90W3
100W3
110W3
125W3
150W3
175W3
200W3
250W3
1 #8 G.
1 #8 G.
1 #8 G.
2 #4
2 #2
3 #12
3 #10
3 #10
3 #4
3 #2
3/4"C
3/4"C
3/4"C
1 1/4"C
1 1/4"C
1 #12 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #10 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #8 G.
3 #8
3 #6
3 #4
3 #2
1 #10 G.3 #8
3 #2 1 #6 G.
1 #6 G.3 #1
1 #6 G.
1 #6 G.
1 #4 G.
3-350 KCMIL 2 1/2"C300W3 1 #4 G.
3-600 KCMIL 3 1/2"C400W3 1 #3 G.
2 #2
3 #3/0
3 #4/0
3-250KCMIL
3-350 KCMIL
1 1/4"C
1 1/4"C
1 1/4"C
2"C
2"C
2"C
3 1/2"C
1 #6 G.
1 #6 G.
2 #2
2 #1
3/4"C
3/4"C
3/4"C
1 1/4"C
1 1/4"C
1 1/4"C
1 1/2"C
1"C
3 #1/0
3 #2/0
1 #4 G.
3-500 KCMIL
3"C
1 #2 G.
(2) 3-250 KCMIL (2) 1 #1 G.
3 #10
3 #10
3 #2
3 #2
1 #10 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #8 G.
1 #6 G.
1 #6 G.
1 #6 G.
1 #6 G.
3 #8
3 #8
3 #6
3 #4
3 #2
3 #1
4 #475W4
(2) 2 1/2"C
1 1/2"C
2 1/2"C
60W4 1 1/4"C4 #6
1 #6 G. 1 #4 G.
3 #4/0 2"C225W3 1 #4 G. 3-300 KCMIL 1 #2 G.
3-500 KCMIL 3"C350W3 (2) 3#4/01 #3 G. (2) 1 #1 G.
WIRE ID #OF WIRES CONDUITGROUND #OF WIRES CONDUITGROUND
(2) 2 1/2"C
100W4
125W4
150W4
175W4
200W4
225W4
250W4
300W4
350W4
400W4
450W4
4 #2
4 #1
4 #1/0
4-250KCMIL
4-500 KCMIL
2"C
2 1/2 "C
3"C
3 1/2"C
4"C
1 #8 G.
1 #6 G.
1 #6 G.
1 #6 G.
1 #4 G.
1 #4 G.
1 #4 G.
1 #3 G.
1 #3 G.
4 #2/0
4 #4/0
4-350 KCMIL
4-600 KCMIL
2"C1 #6 G.4 #3/0
(2) 4#4/0 (2) 1 #2 G.
2"C
3"C
3 1/2"C
(2) 2 1/2"C
(2) 3"C
3"C
(2) 1 #1/0 G.
4 #1
4 #2/0
(2) 4 #4/0
1 #4 G.
1 #4 G.
1 #4 G.
1 #4 G.
1 #2 G.
1 #2 G.
1 #2 G.
(2) 1 #1 G.
(2) 1 #1 G.
4 #3/0
4 #4/0
4-250KCMIL
(2) 4-250 KCMIL
(2) 4-350 KCMIL
(2) 4-600 KCMIL
(3) 4-400 KCMIL
(2) 2 1/2"C
(2) 3"C
(2) 4"C
(3) 3"C
500W4
600W4
800W4
1000W4
(2) 4-250 KCMIL
(2) 1 #2/0 G.
(3) 1 #4/0 G.
(3) 1 #3/0 G.
(2) 1 #1/0 G.
(3) 4-600 KCMIL (3) 4"C1200W4
(3) 4-400 KCMIL (3) 3"C1000UW4 (3) 4-600 KCMIL
(3) 4-600 KCMIL (3) 3 1/2"C1200UW4 (4) 4-500 KCMIL
(4) 4-600 KCMIL1600UW4 (5) 4-600 KCMIL
(5) 4-600 KCMIL2000UW4 (6) 6-600 KCMIL
(2) 4-600 KCMIL (2) 3 1/2"C800UW4 (3) 4-400 KCMIL (3) 3 1/2"C
3 1/2"C400UW4 -- (2) 4-250 KCMIL -- (2) 2 1/2"C4-600 KCMIL
(2) 4#4/0 (2) 2"C450UW4 (2) 4-300 KCMIL (2) 3"C
(2) 4-500 KCMIL750UW4 (3) 4-400 KCMIL (3) 3 1/2"C
(6) 4-600 KCMIL2500UW4 (7) 4-750 KCMIL
(2) 4-350 KCMIL600UW4 (2) 3"C (2) 4"C
3/4"C
3/4"C
1"C
1"C
1"C
1"C
1"C
1"C
3/4"C
3/4"C
3/4"C
3/4"C
3/4"C
3/4"C
1 #8 G.
1 #6 G.
3/4"C
1 1/4"C
2 1/2"C
1 1/4"C
1 #4 G.
1 #4 G.
1 #4 G.
3"C
1 #2 G.
(2) 2 1/2"C
1 #10 G.
1 #8 G.
1"C
2"C
1 1/4"C
1 1/4"C
1 1/2"C
4 #4
4 #2
1 #8 G.
1 #6 G.
1 #6 G.
2"C
2 1/2"C
2 1/2"C
"U" DENOTES UTILITY SERVICE DROP
CONDUCTORS WITHOUT GROUND
(2) 1 #2 G.
(2) 1 #1 G.
(2) 1 #1/0 G.
(3) 1 #2/0 G.
(3) 1 #3/0 G.
2 1/2 "C
3"C
(2) 3"C
(2) 3"C
(2) 3 1/2"C
(3) 3 1/2"C
(3) 4"C
(4) 3 1/2"C
4-500 KCMIL
4-350 KCMIL
4-300 KCMIL
(2) 4-300 KCMIL
(2) 4-350 KCMIL
(2) 4-500 KCMIL
(2) 4-400 KCMIL
(3) 4-600 KCMIL
(4) 4-500 KCMIL (4) 250 KCMIL
FOR CIRCUITS: 3-PHASE + NEUTRAL + GEC GROUND
4-250 KCMIL 2 1/2"C250XW4 1 #2 G. 3"C4-350 KCMIL 1 #1/0 G.
4-350 KCMIL 3"C300XW4 1 #2 G. 3 1/2"C4-500 KCMIL 1 #1/0 G.
4-500 KCMIL 3 1/2"C350XW4 1 #1/0 G. (2) 2 1/2"C(2) 4 #4/0 (2) 1 #3/0 G.
4-600 KCMIL 4"C400XW4 1 #1/0 G. (2) 3"C(2) 4-250 KCMIL (2) 1 #3/0 G.
(2) 4 #4/0 (2) 2 1/2"C450XW4 (2) 1 #1/0 G. (2) 3"C(2) 4-300 KCMIL (2) 1 #3/0 G.
(2) 4-350 KCMIL (2) 3"C600XW4 (2) 1 #2/0 G. (2) 3 1/2"C(2) 4-500 KCMIL (2) 1 #4/0 G.
(2) 4-500 KCMIL (2) 3 1/2"C750XW4 (2) 1 #3/0 G. (3) 3 1/2"C(3) 4-400 KCMIL (3) 250 KCMIL
(2) 4-600 KCMIL (2) 4"C800XW4 (2) 1 #3/0 G. (3) 3 1/2"C(3) 4-400 KCMIL (3) 250 KCMIL
FOR CIRCUITS: 3-PHASE + NEUTRAL
(2) 3"C
(2) 4-500 KCMIL
(4) 3 1/2"C
(5) 3 1/2"C
(6) 3 1/2"C
(3) 3 1/2"C
(4) 3 1/2"C
(5) 3 1/2"C
(6) 4"C
(7) 4"C
THIS CHART IS BASED UPON INSULATED
WIRE IN CONDUIT - NEC TABLE 310.15(b)
(16), EXCEPT FOR WIRE SIZES #8 CU AND
BELOW AS PER NEC 240.4(d).
60 DEG COLUMN #1 AND LESS
75 DEG COLUMN #1/0 AND GREATER
N E
L
TVSS
M
K
E
SURGE PROTECTION DEVICE
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
AUTOMATIC TRANSFER SWITCH
GROUND CONNECTION
KEY INTERLOCK SWITCH
ELECTRIC INTERLOCK SWITCH
LIGHTNING ARRESTOR
COMMUNICATION DEVICES
TYPICAL NOTATIONS
NOTES
LIGHTING SYMBOLS
A 2 a
A 2 a
A 2 a
A 2 a
X X
A
2 a
A
2 a
EM
A A 2 a
A
A 2 a
A 2 a
A
J
LIGHTING SWITCHES & CONTROLS
OS
SF
S3x
SDx
Sosx
Sx
S4x
TC-"#"
x
WAP
MS
WP
EC
J
PB
GENERAL POWER
U
P1-3
G
R
SINGLE LINE SYMBOLS
T
TV
AA/FA
LA
OD
SPD
SPD
U
DS
x
NOTES
1.
125V., 20A DUPLEX RECEPTACLE MOUNTED AT 18" AFF UNLESS
OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF OR 6"
ABOVE COUNTER OR BACKSPLASH. "U" INDICATES USB
RECEPTACLE WITH COMBINATION USB-A AND USB-C (LEVITON
T5633 OR EQUAL).
125V., 20A DUPLEX GFCI RECEPTACLE MOUNTED AT 18" AFF
UNLESS OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF
OR 6" ABOVE COUNTER OR BACKSPLASH. "WP" INDICATES
WEATHERPROOF ENCLOSURE . "U" INDICATES USB RECEPTACLE
WITH COMBINATION USB-A AND USB-C (LEVITON GUAC2 OR
EQUAL).
125V., 20A DOUBLE DUPLEX (QUAD) RECEPTACLE, MOUNTED AT
18" AFF UNLESS OTHERWISE NOTED.
125V., 20A DUPLEX RECEPTACLE WITH BOTTOM RECEPTACLE
CONNECTED TO WALL SWITCH, MOUNTED AT 18" AFF UNLESS
OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF OR 6"
ABOVE COUNTER.
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE, RATING AND
VOLTAGE AS NOTED.
CEILING MOUNTED 125V., 20A DUPLEX RECEPTACLE
CEILING MOUNTED 125V., 20A DOUBLE DUPLEX (QUAD)
RECEPTACLE.
RECESSED COMBINATION POWER/DATA FLOOR DEVICE, LEGRAND
EVOLUTION SERIES BOX OR EQUAL. REFER TO FLOOR PLAN FOR
CONFIGURATION.
RECESSED COMBINATION POWER/DATA FLOOR DEVICE.
LEGRAND EVOLUTION SERIES POKE-THRU DEVICE OR EQUAL.
PROVIDE FIRE RATED ASSEMBLY WHERE REQUIRED.
SURFACE MOUNTED WIRE RACEWAY, TYPE AND DEVICES AS
INDICATED ON PLANS. LEGRAND PLUGMOLD 2000 SERIES OR
EQUAL.
JUNCTION BOX, COORDINATE LOCATION, RATING AND SIZE WITH
END DEVICE. PROVIDE FIRE RATED ASSEMBLY WHERE REQUIRED.
COORDINATE JUNCTION BOX TYPE FOR FAN/ PENDANT RATING
WHERE REQUIRED.
PULL BOX. COORDINATE SIZE AS REQUIRED.
MOTOR RATED SWITCH, COORDINATE LOCATION, RATING, AND
SIZE WITH END DEVICE
DISCONNECT SWITCH, COORDINATE LOCATION, RATING AND SIZE
WITH END DEVICE. IF CONCEALED USE GENERAL DUTY, IF
EXPOSED USE HEAVY DUTY.
FUSED DISCONNECT SWITCH, COORDINATE LOCATION, RATING
AND SIZE WITH END DEVICE. IF CONCEALED USE GENERAL DUTY,
IF EXPOSED USE HEAVY DUTY.
COMBINATION MOTOR STARTER AND DISCONNECT; PROVIDED BY
MECHANICAL CONTRACTOR/PLUMBING CONTRACTOR; INSTALLED
BY ELECTRICAL CONTRACTOR
ELEVATOR CONTROL SWITCH (EC) - 'EC' SHALL BE EATON "ES"
SERIES OR EQUAL WITH THE FOLLOWING:
SHUNT TRIP INTERFACE WITH FIRE ALARM SYSTEM
PILOT LIGHT (PER NFPA 72 & ASME A17.1)
CONTROL POWER (PER NFPA 72 & ASME A17.1)
MONITORING (PER NFPA 72 & ASME A17.1)
AUXILIARY CONTACTS
PROVIDE SURGE PROTECTION (SPD)
OVERHEAD DOOR, COORDINATE POWER/CONTROL
REQUIREMENTS WITH VENDOR/OWNERSHIP.
SURGE PROTECTION DEVICE
HOME RUN TO PANEL, "P1" INDICATES PANEL NAME, "3" INDICATES
CIRCUIT BREAKER POSITION.
PANELBOARD, SURFACE MOUNTED.
PANELBOARD, FLUSH MOUNTED.
TRANSFORMER, SIZE, TYPE AND RATING AS INDICATED ON PLAN.
COPPER GROUND BAR, SIZE AS INDICATED ON PLAN.
COPPER GROUND CONDUCTOR, SIZE AS INDICATED ON PLAN.
PLAN NOTE CALLOUT
NEW CONNECTION TO EXISTING
TERMINATION OF DEMOLITION
LIGHT FIXTURE; "A" INDICATES TYPE, "2" INDICATES CIRCUIT
BREAKER POSITION; "a" INDICATES SWITCHING.
LIGHT FIXTURE CONNECTED TO EMERGENCY (EM) AND/OR NIGHT
LIGHT (NL) CIRCUIT; "A" INDICATES TYPE; "2" INDICATES CIRCUIT
BREAKER POSITION; "a" INDICATES SWITCHING.
PENDANT MOUNTED LIGHT FIXTURE; "A" INDICATES TYPE, "2"
INDICATES CIRCUIT BREAKER POSITION; "a" INDICATES SWITCHING.
RECESSED DOWNLIGHT; "A" INDICATES TYPE; "2" INDICATES CIRCUIT
BREAKER POSITION; "a" INDICATES SWITCHING.
RECESSED WALLWASHER DOWNLIGHT, "A" INDICATES TYPE; "2"
INDICATES CIRCUIT BREAKER POSITION; "a" INDICATES SWITCHING.
WALL MOUNTED LIGHT FIXTURE; "A" INDICATES TYPE, "2" INDICATES
CIRCUIT BREAKER POSITION; "a" INDICATES SWITCH CONTROL.
CEILING OR WALL MOUNTED LINEAR LED LIGHT FIXTURE; "A"
INDICATES TYPE; "2" INDICATES CIRCUIT BREAKER POSITION, "a"
INDICATES SWITCH CONTROL.
TAPE LIGHT OR WALL MOUNTED LED STRIP LIGHT FIXTURE; "A"
INDICATES TYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a"
INDICATES SWITCH CONTROL.
CEILING OR WALL MOUNTED TRACK LIGHT FIXTURE; "A" INDICATES
TYPE, "2" INDICATES CIRCUIT BREAKER POSITION, "a" INDICATES
SWITCHING.
POLE MOUNTED LIGHT FIXTURE. "A" INDICATES TYPE, "2" INDICATES
CIRCUIT BREAKER POSITION.
CEILING OR WALL MOUNTED SINGLE FACE EXIT SIGN, "X" INDICATES
TYPE; ARROWS AS INDICATED ON PLANS. CONNECT TO LOCAL
LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING UNLESS
OTHERWISE NOTED.
CEILING OR WALL MOUNTED DOUBLE FACE EXIT SIGN, "X" INDICATES
TYPE, ARROWS AS INDICATED ON PLANS. CONNECT TO LOCAL
LIGHTING BRANCH CIRCUIT AHEAD OF ALL SWITCHING UNLESS
OTHERWISE NOTED.
CEILING OR WALL MOUNTED EXIT SIGN WITH INTEGRAL EMERGENCY
LIGHT HEADS; "X" INDICATES TYPE, ARROWS AS INDICATED ON
PLANS. CONNECT TO LOCAL LIGHTING BRANCH CIRCUIT AHEAD OF
ALL SWITCHING UNLESS OTHERWISE NOTED.
WALL MOUNTED EMERGENCY BATTERY PACK WITH (2)-LIGHT HEADS;
"EM" INDICATES TYPE. CONNECT TO LOCAL LIGHTING BRANCH
CIRCUIT AHEAD OF ALL SWITCHING UNLESS OTHERWISE NOTED.
WALL OR CEILING MOUNTED SINGLE HEAD OR TWIN REMOTE
EMERGENCY LIGHT "EM" INDICATES TYPE. "WP" INDICATES
WEATHERPROOF.
CEILING MOUNTED PADDLE FAN, "A" INDICATES TYPE, "2" INDICATES
CIRCUIT BREAKER POSITION.
SWITCHES, COVERPLATES AND RECEPTACLES BASIS OF DESIGN:
COMMERCIAL - DEVICES SHALL BE WHITE WITH A METAL STAINLESS
STEEL COVERPLATE.
RESIDENTIAL-DEVICE COLOR BY ARCHITECT WITH A MATCHING
SCREWLESS COVERPLATE.
LOAD CENTERS, SWITCHBOARDS, PANELBOARDS, SWITCHGEAR,
METER CENTERS, TRANSFORMERS WHERE SHOWN ON PLANS ARE
ESTIMATED SIZES. COORDINATE NEC REQUIRED CLEARANCES WITH
FINAL SELECTION FROM MANUFACTURER. ELECTRICAL
CONTRACTOR RESPONSIBLE FOR SELECTING MANUFACTURER
THAT PROVIDES EQUIPMENT THAT FITS WITHIN THE SIZES SHOWN
ON PLANS OR SMALLER.
1. ALL SWITCHES SHALL BE MOUNTED AT 42" ABOVE FINISHED FLOOR,
UNLESS OTHERWISE NOTED.
2. SWITCHES SHALL BE RATED AT VOLTAGE OF FIXTURES OR LOAD
CONTROLLED.
3. DIMMER SWITCHES SHALL BE COMPATIBLE WITH LIGHTING FIXTURE
AND LAMP SOURCE BALLAST/DRIVER BEING CONTROLLED BY SWITCH.
4. WHERE MULTIPLE SWITCHES ARE SHOWN, GANG SWITCHES IN SINGLE
ENCLOSURE WITH SINGLE FACEPLATE.
TOGGLE SWITCH
CEILING FAN SPEED SWITCH, COORDINATE SWITCH
CONFIGURATION/TYPE WITH MANUFACTURER.
3-WAY TOGGLE SWITCH
4-WAY TOGGLE SWITCH
DIMMER SWITCH
WALL MOUNTED, DUAL TECHNOLOGY OCCUPANCY SENSOR.
CEILING MOUNTED DUAL, TECHNOLOGY OCCUPANCY SENSOR.
DAYLIGHT SENSOR
TIME CLOCK. SEE TC-"#" SCHEDULE.
"x" SWITCHED LIGHT, "x" INDICATES AREA OF SWITCH CONTROL
"WP" WEATHERPROOF ENCLOSURE WITH "NTRL" LISTED COVERPLATE FOR
WET LOCATION
"#" DESIGNATES TIME CLOCK NUMBER
COORDINATE MOUNTING HEIGHT OF COMMUNICATION DEVICES WITH
ARCHITECTURAL ELEVATIONS/OWNERSHIP
VOICE COMMUNICATION OUTLET
DATA COMMUNICATION OUTLET
VOICE & DATA COMMUNICATION OUTLET
COMBINATION COAX/DATA LOCATION (APARTMENT)
RECESSED CABLE TV BOX WITH DUPLEX RECEPTACLE
AND TELE/DATA ACCESSORIES
WIRELESS ACCESS POINT
PANELBOARD; SIZE, TYPE AND RATING AS NOTED
AA = PANEL DESIGNATION;
### = PANEL CAPACITY (AMPERAGE)
MLO = MAIN LUGS ONLY
MCB = MAIN CIRCUIT BREAKER
COORDINATE MFG./TYPE WITH LOCAL UTILITY
METER AND SOCKET. COORDINATE MFG./TYPE WITH LOCAL
UTILITY
TRANSIENT VOLTAGE SURGE SUPPRESSION SYSTEM
PANEL AA
MLO/MCB
MOTOR OR MOTORIZED EQUIPMENT. NUMBER INDICATES
HORSEPOWER (HP)
MOLDED CASE CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER MEDIUM VOLTAGE
FUSED SWITCH
FUSE
CONTACT
RELAY/CONTACTOR COIL
POWER TRANSFORMER, WITH VOLTAGES AS INDICATED
TRANSFORMER: ### - TRANSFORMER CAPACITY AT
AMBIENT
AIR
*** - TRANSFORMER CAPACITY AT FORCED AIR
AA - AMBIENT AIR
FA - FORCED AIR
Y CONFIGURATION TO GROUND DELTA
CONFIGURATION
5561 Pennell Rd Media, PA 19063 P: 610.361.0700
7 10
5561 Pennell Rd Media, PA 19063 P: 610.361.0700
EXAMPLE OF P-1 JUNCTION BOX INSTALLATION FOLLOW SIMILAR INSTALLATION FOR P-2 AND P-3.
E1.0
SCALE - NO SCALE
EXAMPLE OF P-1 JUNCTION BOX
E1.0
SCALE - NO SCALE
125 HP OWNER SUPPLIED VFD SUBMITTAL
E1.0
SCALE - NO SCALE
125 HP OWNER SUPPLIED VFD SUBMITTAL
E1.0
SCALE - NO SCALE
125 HP OWNER SUPPLIED VFD SUBMITTAL
E1.0
SCALE - NO SCALE
125 HP OWNER SUPPLIED VFD SUBMITTAL
8 10
EXIST
MCC
P
(N)
P
(N)VFD
P-3
(N)
VFD
P-2
(N)
VFD
P-1
(N)
1 P
(E)
PROVIDE NEW WIRING FROM MCC TO VFD,
AND FROM VFD TO P-1. FOLLOW SINGLE LINE
DIAGRAM FOR WIRING AND CONDUIT SIZING.
ALL CONDUIT TO BE RUN IN RIGID METAL
CONDUIT. TERMINATE PUMP CONNECTION
WITH JUNCTION BOX IN GROUND FOR
CONNECTION TO PUMP MOTOR WIRES
SHALL BE RAN IN FLEXIBLE LIQUID TIGHT
CONDUIT. PUMP MOTOR LOCATED
APPROXIMATELY 30' BELOW. INSTALLATION
SHALL MATCH JUNCTION BOX STYLE OF P-1
SEE DETAIL 1 ON DWG E1.0. EXISTING PUMP
TO REMAIN.
PROVIDE NEW WIRING FROM MCC TO VFD,
AND FROM VFD TO P-2, AND P-3
RESPECTIVELY. FOLLOW SINGLE LINE
DIAGRAM FOR WIRING AND CONDUIT SIZING.
ALL CONDUIT TO BE RUN IN RIGID METAL
CONDUIT. TERMINATE PUMP CONNECTION
WITH JUNCTION BOX IN GROUND FOR
CONNECTION TO PUMP MOTOR WIRES
SHALL BE RAN IN FLEXIBLE LIQUID TIGHT
CONDUIT. PUMP MOTOR LOCATED
APPROXIMATELY 30' BELOW. INSTALLATION
SHALL MATCH JUNCTION BOX STYLE OF P-1
SEE DETAIL 1 ON DWG E1.0.
INSTALL FLOOR MOUNTED VFD ON METAL
PEDESTAL ABOVE 100 YEAR STORM LEVEL.
METAL PEDESTAL SHALL BE CAPABLE OF
WITHSTANDING WEIGHT OF VFD AND ALLOW
FOR MOUNTING/BOLTING OF VFD DIRECTLY
TO PEDESTAL. PEDESTAL SHALL BE
APPROXIMATELY 30" ABOVE FINISHED
FLOOR. COORDINATE EXACT HEIGHT WITH
CIVIL ENGINEER PRIOR TO FABRICATION.
EXTEND CONTROL WIRING FORM LOCAL PLC
CONTROLLER TO NEW VFD LOCATION.
PROVIDE SPLICE BOXES AS NECESSARY.
CONNECT ALL CONTROL WIRING TO VFD FOB
FULL OPERATION OF VFD.
NEW WORK SHEET NOTES
(R) VFD P-3
(R)
VFD
P-2
(R)
VFD
P-1
EXIST
MCC
P
(R)
P
(R)
P
(E)
VFD
P-3
(R)
VFD
P-2
(R)
VFD
P-1
(R)
DEMOLISH VFD AND UNISTRUT ASSOCIATED
WITH VFD. COORDINATE PUMP INSTALLATION
WITH OTHER TRADES. LEAVE ALL
COMMUNICATION WIRE FOR FUTURE VFD.
PROVIDE SPLICE BOX FOR EXTENSION OF
CONTROL WIRE TO NEW VFD LOCATIONS AS
SHOWN ON NEW WORK DRAWINGS.
DEMOLITION WORK SHEET NOTES
1. ALL WORK SHALL BE COMPLETED IN
ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE AND THE LOCAL
AUTHORITY HAVING JURISDICTION.
2. COORDINATE OTHER TRADE
CONSTRUCTION WITH APPROPRIATE
TRADE.
3. CONFIRM ALL DEVICE MOUNTING HEIGHTS
AND EXISTING CONDITIONS PRIOR TO
INSTALLATION.
4. NEC 110.26 REQUIRED CLEARANCES SHALL
BE MAINTAINED FOR EXISTING AND NEW
ELECTRICAL EQUIPMENT INSTALLED
DURING CONSTRUCTION.
5. COORDINATE ALL VFD TO PLC SIGNAL AND
CONTROL WIRING INTERCONNECTION
REQUIREMENTS WITH OWNERSHIP PRIOR
TO CONSTRUCTION. PLC PROGRAMMING BY
OTHERS. CONTROL AND SIGNAL WIRING BY
E.C.
GENERAL NOTES
5561 Pennell Rd Media, PA 19063 P: 610.361.0700
E2.0
SCALE - 1/8" = 1'-0"
GROUND LEVEL FLOOR PLAN - NEW WORK
E2.0
SCALE - 1/8" = 1'-0"
GROUND LEVEL FLOOR PLAN - DEMOLITION
9 10
REPLACE 200A 3P
BREAKERS WITH NEW
225A 3P BREAKERS
(TYP FOR 3)
3 # 4/0 & 1 #4 GRD CU IN
2" RIGID STL CONDUIT
3 # 4/0 & 1 #4 GRD CU IN
2" LIQUID-TIGHT FLEXIBLE CONDUIT
3 # 4/0 & 1 #4 GRD CU IN
2" RIGID STL CONDUIT
1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE AND THE LOCAL AUTHORITY HAVING JURISDICTION.
2. COORDINATE OTHER TRADE CONSTRUCTION WITH APPROPRIATE TRADE.
3. CONFIRM ALL DEVICE MOUNTING HEIGHTS AND EXISTING CONDITIONS PRIOR
TO INSTALLATION.
4. NEC 110.26 REQUIRED CLEARANCES SHALL BE MAINTAINED FOR EXISTING
AND NEW ELECTRICAL EQUIPMENT INSTALLED DURING CONSTRUCTION.
5. COORDINATE ALL VFD TO PLC SIGNAL AND CONTROL WIRING
INTERCONNECTION REQUIREMENTS WITH OWNERSHIP PRIOR TO
CONSTRUCTION. PLC PROGRAMMING BY OTHERS. CONTROL AND SIGNAL
WIRING BY E.C.
6. PROVIDE BONDING & GROUNDING PER NEC.
GENERAL NOTES:
DEMOLISH PUMP EQUIPMENT FEEDER BREAKER.1
DEMO SHEET NOTES
NEW CIRCUIT BREAKER TO MATCH EXISTING MCC KAIC. BLANK OFF OPENINGS
IN EXISTING BUCKET DOOR AS REQUIRED. PROVIDE NEW DOOR HARDWARE TO
SWITCH CIRCUIT BREAKER IF REQUIRED. NEW CIRCUIT BREAKER TRIP CURVES
SHALL BE COORDINATED WITH DOWNSTREAM VFD BREAKER.
NEW VFD OWNER SUPPLIED AND INSTALLED BY E.C. SEE VFD SUBMITTAL ON
DWG E1.0 FOR MORE INFORMATION.
E.C. TO PROVIDE CONNECTION FROM ATS TO PLC TO INDICATE WHEN
GENERATOR IS RUNNING. COORDINATE SIGNALS REQUIRED WITH OWNERSHIP
PRIOR TO CONSTRUCTION. IN A POWER OUTAGE SITUATION ONLY ONE PUMP
TO RUN, OTHER PUMPS TO BE LOCKED OUT.
NEW WORK SHEET NOTES
2 2 2
5561 Pennell Rd Media, PA 19063 P: 610.361.0700
E5.0
SCALE - NO SCALE
ELECTRICAL SINGLE LINE - DEMOLITION
E5.0
SCALE - NO SCALE
ELECTRICAL SINGLE LINE - NEW WORK
10 10
| Sheets and Views |
| 82700-100-S-22A Site-TITLE |
| 82700-100-S-22A Site-M1 |
| Sheets and Views |
| 82700-100-S-22A BSPS Mech-M2 EXIST-DEMO |
| 82700-100-S-22A BSPS Mech-M3 PROPOSED PUMPS |
| 82700-100-S-22A BSPS Mech-M4 DETAILS |
| Sheets and Views |
| E0.0 n E0.1 COVER-E0.0 |
| E0.0 n E0.1 COVER-E0.1 |
| E1.0 DETAILS-E1.0 |
| E2.1 NEW-E2.1 |
| E5.0 single line-E5.0 |