2-Patterson Hall Fiber Art Studio Relocation Drawings.pdf

PDF 20 MB Posted

Attached to
Mihalik-Thompson Stadium DHW Replacement Project
Solicitation number
Not on record
Issued by
Butler County, Pennsylvania

About this file

Patterson Hall Fiber Art Studio Relocation - Construction Documents Summary

This is a comprehensive set of construction documents for the Patterson Hall Fiber Art Studio Relocation project at Slippery Rock University in Pennsylvania, prepared by R3A Architecture and Barton Associates, Inc. The project involves the conversion of an existing crime lab (Room 017) into a fiber arts studio with associated storage space (Room 017B) and mechanical facilities (Room 028), totaling approximately 3,263 square feet. The scope encompasses architectural, mechanical, electrical, and plumbing work including demolition of existing conditions, installation of new interior finishes (epoxy flooring, wall paint, plastic laminate casework), lighting fixture replacement, plumbing fixture relocation and installation, HVAC duct and piping modifications, and various equipment installations. The construction documents include detailed plans for ground floor layouts, reflected ceiling plans, wall and finish specifications, flooring finish plans, equipment schedules, plumbing systems, mechanical systems, and electrical systems. A pre-bid conference with site visit is scheduled for May 27, 2026, at 11:00 AM at the Maintenance Center Conference Room, with electronic bids due no later than 11:00 AM EST on June 18, 2026, through PennBid. The project is expected to be completed by August 15, 2026, with liquidated damages assessed at $250 per calendar day of delay.

The project will be executed through separate prime contracts with the General Contractor serving as the lead contractor, with estimated cost ranges of $120,000-$130,000 for general construction, $50,000-$60,000 for plumbing, and $30,000-$40,000 for electrical work. All contractors must comply with the Pennsylvania Prevailing Wage Act and provide performance and payment bonds at 100% of the awarded contract price, as well as meet requirements under the Public Works Employment Verification Act and Investment Activities in Iran restrictions. The project is funded through the State System of Higher Education and must adhere to the 2018 International Building Code and related standards. Bid evaluation will be based on the lowest combination of base bid and alternates that can be awarded within budgeted funds, with the university retaining the right to accept or reject any bids. Multiple construction alternates are included in the documents, covering lighting replacement, countertop materials, epoxy flooring extent, under-cabinet lighting, and stainless steel sink installations, allowing the university flexibility in scope and cost management within available funding.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT

LOCATION

EC-1

(LIGHTING REPLACEMENT)

LIST OF ALTERNATES

ALTERNATE NO. ADD / DEDUCT BUILDING LOCATION DESCRIPTION DRAWING REFERENCE

ADD FIBER ARTS STUDIO CEILINGS

A-110

BASE BID:

ALTERNATE:

ALL EXISTING SURFACE MOUNTED LINEAR FIXTURES WITHIN THE WORK AREA ARE TO

REMAIN.

DEMOLISH EXISTING SURFACE MOUNTED LINEAR FIXTURE. UTILIZE EXISTING JUNCTION

BOXES AND REPLACE EXISTING SURFACE MOUNTED LINEAR FIXTURE WITH FIXTURE

IDENTIFIED IN ELECTRICAL DRAWINGS.

GC-1

(COUNTERTOPS) ADD FIBER ARTS STUDIO WET AREA A-110

BASE BID:

ALTERNATE:

PROVIDE PLASTIC LAMINATE COUNTERTOPS

PROVIDE SOLID SURFACE COUNTERTOPS.

GC-2

(EPOXY FLOORING) ADD FIBER ARTS STUDIO FLOOR FINISHES AF101

BASE BID:

ALTERNATE:

PROVIDE EPOXY SYSTEM SPECIFIED ON FINISH PLANS IN LOCATION INDICATED FOR THE

WET AREA ONLY SEE DETAIL 1/AF102

PROVIDE EPOXY SYSTEM THROUGHOUT WORK AREAS AS INDICATED ON FINISH PLANS

SEE DETAIL 2/AF102

EC-1

(UNDER-CABINET LIGHTING) ADD FIBER ARTS STUDIO WET AREA A-401

BASE BID:

ALTERNATE:

EXISTING UPPER CABINETS TO REMAIN AS IS.

EXISTING UPPER CABINETS TO RECEIVE UNDER-CABINET LIGHTING AND VALANCE.

VALANCE TO MATCH EXISTING UPPER CABINETS PLASTIC LAMINATE.

PC-1

(STAINLESS STEEL SINKS) ADD FIBER ARTS STUDIO WET AREA A101

BASE BID:

ALTERNATE:

PROVIDE ADDITIONAL SANITARY, HOT WATER / COLD WATER CONNECTIONS FOR (2)

ADDITIONAL DROP-IN TYPE SINKS ALONG WITH ADDITIONAL COUNTERS AND SINK BASES.

COORDINATE WITH PLUMBING DRAWINGS.

PROVIDE SANITARY, HOT & COLD WATER CONNECTIONS FOR (2) STAINLESS STEEL SINKS

TO BE RELOCATED FROM THE PREVIOUS SPACE BY THE OWNER AND INSTALLED BY THE

CONTRACTOR AS SHOWN ON THE PLUMBING DRAWINGS.

FIELD HOUSE ROAD

FIELD HOUSE ROAD

05/15/2026

SLIPPERY ROCK UNIVERSITY

PATTERSON HALL FIBER ART STUDIO RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA 16057

CONSTRUCTION DOCUMENTS

NTS

1 LOCATION MAP

OWNER: SLIPPERY ROCK UNIVERSITY

1 MORROW WAY, SLIPPERY ROCK, PA 16057

CONTACT: JUAN PEREZ

PHONE: (724)738-2964

EMAIL: JUAN.PEREZ@SRU.EDU

ARCHITECT: R3A ARCHITECTURE

48 S 14TH ST

PITTSBURGH, PA 15203

PHONE: 412-431-2480

CONTACT: NAOMI WILLIAMS

PHONE: (412)431-2480 EXT. 111

EMAIL: NW@R3A.COM

MECHANICAL, ELECTRICAL,

PLUMBING ENGINEER:

BARTON ASSOCIATES, INC.

CONTACT: JOHN SUNDY

PHONE: (412)421-0145

EMAIL: JMS@BA-INC.COM

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

G-001 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

COVER SHEET

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

SHEET LIST

NUMBER NAME

GENERAL

G-001 COVER SHEET

G-101 CODE REVIEW & LIFE SAFETY PLAN

G-102 CODE REVIEW

ARCHITECTURAL

A-001 ABBREVIATIONS, SYMBOLS AND STANDARD MOUNTING HEIGHTS

AD101 GROUND FLOOR AND REFLECTED CEILING DEMOLITION PLAN

A-101 GROUND FLOOR PLAN AND REFLECTED CEILING PLAN

A-401 ENLARGED PLANS AND ELEVATIONS

AF101 GROUND FLOOR WALL AND SURFACE FINISH PLAN

AF102 GROUND FLOOR FLOORING FINISH PLAN

AQ101 EQUIPMENT PLANS

PLUMBING

P-000 SYMBOLS & GENERAL NOTES - PLUMBING

PD-101 GROUND FLOOR PLAN - DEMOLITION - PLUMBING

P-101 GROUND FLOOR PLAN - DOMESTIC WATER

P-201 GROUND FLOOR PLAN - SANITARY & VENT

MECHANICAL

H-000 SYMBOLS & GENERAL NOTES - HVAC

HD-101 GROUND FLOOR PLAN - DEMOLITION - HVAC - DUCTWORK

HD-201 GROUND FLOOR PLAN - DEMOLITION - HVAC - PIPING

H-101 GROUND FLOOR PLAN - DUCTWORK

H-201 GROUND FLOOR PLAN - PIPING

H-601 SCHEDULES AND DETAILS

ELECTRICAL

E-000 SYMBOLS & GENERAL NOTES - ELECTRICAL

ED-101 GROUND FLOOR PLAN - DEMOLITION - ELECTRICAL

E-101 GROUND FLOOR PLAN - LIGHTING

E-201 GROUND FLOOR PLAN - POWER & SYSTEMS

E-601 SCHEDULES

1" = 100'-0"2 SITE PLAN

UP

R

AM

P

D N

UP

UP

DN

UP

pm dw

UP

UP

UP

UP

DN

UP

DN

RAMP DN

RAMP DN

1 HOUR FIRE RATED STAIR SEPARATION

1 HOUR FIRE RATED SEPARATION

NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

CONTRACTOR TO MARK FIRE RATED WALLS, BARRIERS & PARTITIONS

WITH THEIR FIRE RATING TYPE. INDICATED ON DRAWINGS PROVIDE

ADHERED STICKERS WITH RED LETTER SIGNAGE OR STENCILING 5'

BELOW THE BOTTOM OF DECK OR 6" ABOVE THE FINISHED CEILING

REPEAT IDENTIFICATION EVERY 30 FEET THE ENTIRE LENGTH OF THE

WALL. AND AT EACH BEND. SIGN TO READS "(X) HOUR FIRE (BARRIER,

WALL OR PARTITION)- PROTECT OPENINGS" TEXT TO MATCH CODE

REFERENCE SHEET. LETTERS TO BE 1 INCH HIGH: PROVIDE 6 INCH HIGH

SIGN FABRICATED FROM OPAQUE NON-REFLECTIVE VINYL FILM, .0035

INCH NOMINAL THICKNESS, WITH PRESSURE-SENSITIVE ADHESIVE

BACKING SUITABLE FOR INTERIOR APPLICATIONS.

WALKS, HALLS, CORRIDORS, AISLES, AND OTHER SPACES PART OF AN

ACCESSIBLE ROUTE ARE TO COMPLY WITH CHAPTER 4 OF ANSI-117.1.

PROVIDE EMERGENCY LIGHTING IN COMPLIANCE WITH NFPA 70.

EMERGENCY LIGHTING IS SHOWN ON ELECTRICAL (E-SERIES) DRAWINGS.

PROVIDE FIRE ALARM SYSTEM IN COMPLIANCE WITH NFPA 70. FIRE

ALARM SYSTEMS DESIGN REQUIREMENTS ARE SHOWN ON ELECTRICAL

(E-SERIES) DRAWINGS. FIRE ALARM SYSTEM IS A DEFERRED SUBMITTAL

TO BE PROVIDED BY SUCCESSFUL BIDDING CONTRACTOR.

PROVIDE FIRE SUPPRESSION (SPRINKLER) SYSTEM IN COMPLIANCE WITH

AUTHORITY HAVING JURISDICTION STANDARDS AND NFPA 13. FIRE

SUPPRESSION SYSTEMS DESIGN REQUIREMENTS ARE SHOWN ON FIRE

PROTECTION (FP-SERIES) DRAWINGS. FIRE SUPPRESSION IS A

DEFERRED SUBMITTAL TO BE PROVIDED BY SUCCESSFUL BIDDING

CONTRACTOR.

TACTILE EXIT SIGNS ARE REQUIRED IN ADDITION TO THE ILLUMINATED

SIGNS AND TO BE PROVIDED PER ELECTRICAL DRAWINGS. COORDINATE

OWNERS INSTALLATION AND OCCUPANCY INSPECTIONS.

PERMANENT SIGNAGE TO BE INSTALLED ON WALL ADJACENT TO THE

LATCH SIDE OF DOOR MOUNTING LOCATION MUST ALLOW PERSON TO

APPROACH WITHOUT ENCOUNTERING PROTRUDING OBJECTS WITHIN

THE SWING PATH OF THE DOOR. SIGNS MOUNTED TO GLASS TO ACHIEVE

THIS WILL RECEIVE BACKING PANEL. SEE SIGNAGE SHEETS.

DOORS IN RATED WALLS ARE REQUIRED TO BE FIRE RATED TO MATCH

WALL RATING OR ALLOWED REDUCTION IN RATING AND INSTALLED WITH

CLOSERS AND LATCHES.

UL DESIGN NUMBERS ARE INTENDED TO SHOW COMPLIANCE OF BASIS

OF DESIGN, PRODUCTS OR MATERIALS INDICATED AND TESTED BY

UNDERWRITER'S LABORATORY, AND ARE NOT INTENDED TO SPECIFY A

PROPRIETARY PRODUCT. MATERIALS NOT INCLUDED IN SELECTED UL

ASSEMBLY DESIGNATIONS BUT PROVEN BY THE CONTRACTOR TO HAVE

EQUAL OR BETTER FIRE RATED UL TESTED ASSEMBLIES WILL BE

CONSIDERED, BUT MUST BE APPROVED.

PROVIDE EMERGENCY EGRESS LIGHTING AS PER CODE.

PROVIDE FIRESTOPPING AND SEALANT FOR PENETRATIONS IN FIRE-

RESISTANCE-RATED WALLS AND FLOORS.

HANDICAPPED PARKING

ACCESSIBLE CLEAR FLOOR SPACE

EGRESS PATH

LEGEND

ACCESSIBLE PATH

DIRECTION OF TRAVEL PATH

EGRESS CAPACITY

EXIT ACCESS TRAVEL DISTANCE

1 1 1 1

1 1

EP EP EP EP

AP AP AP AP

000 PEOPLE

00 INCHES

1835 SF

FIBER ARTS STUDIO

441 SF

017B

FIBER ARTS

STORAGE

988 SF

MECHANICAL

180 People 36 Inches

180 People 36 Inches

180 People 54 Inches

180 People 36 Inches

180 People 36 Inches150 People

30 Inches

ARTS STUDIO LAB (HATCHED)

CLASSROOM VOCATIONAL OCCUPANCY

1,781 SF / 50 NSF = 36 OCCUPANTS

OFFICES (HATCHED)

BUSINESS AREAS

2,931 SF / 150 NSF = 20 OCCUPANTS

MECHANICAL AREAS (HATCHED)

MECHANICAL AREAS

998 SF / 300 GSF = 4 OCCUPANTS

MECHANICAL AREAS (HATCHED)

MECHANICAL AREAS

2,708 SF / 300 GSF = 10 OCCUPANTS

180 People 36 Inches

120 People 36 Inches

180 People 36 Inches

120 People 36 Inches

180 People 36 Inches

180 People 36 Inches

140 People 42 Inches

180 People 36 Inches

160 People 48 Inches

300 People 60 Inches

EXIT ACCESS

TRAVEL

DISTANCE:

54'-10"

MECHANICAL AREAS (HATCHED)

MECHANICAL AREAS

145 SF / 300 GSF = 1 OCCUPANTS

EXIT ACCESS TRAVEL

DISTANCE: 58'-9"

EXIT ACCESS TRAVEL DISTANCE: 33'-4"

EX

IT

A

CC

ES

S

TR

AV

EL

DI

ST

AN

CE

: 4 0'-

3"

EXIT ACCESS TRAVEL DISTANCE: 78'-6"

EXIT ACCESS TRAVEL DISTANCE: 65'-0"

EXIT ACCESS TRAVEL DISTANCE: 80'-10"

ARTS STUDIO LAB (HATCHED)

STORAGE OCCUPANCY

437 SF / 300 NSF = 2 OCCUPANTS

140 People 42 Inches

ACCESSIBLE RESTROOMS

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

G-101 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

CODE REVIEW &

LIFE SAFETY

PLAN

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

CODE ROOM SCHEDULE

RM # NAME AREA OCCUPANT TYPE / LOAD FACTOR

OCCUPANT

COUNT

017 FIBER ARTS STUDIO 1835 SF 50 35.60

017A MECHANICAL 0 SF 300 0.49

017B FIBER ARTS STORAGE 441 SF 300 1.46

028 MECHANICAL 988 SF 300 3.30

3263 SF

1/8" = 1'-0"2 GROUND FLOOR LIFE SAFETY PLAN

3/32" = 1'-0"1 FIRST FLOOR LIFE SAFETY PLAN

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

G-102 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

CODE REVIEW

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

STANDARD MOUNTING HEIGHTS-GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

THE REFERENCED HEIGHTS, DETAILS AND NOTES ON THIS SHEET ARE

"TYPICAL," AND ARE ITEMS LISTED SPECIFICALLY SHOWN ELSEWHERE IN

THIS SET OF CONSTRUCTION DOCUMENTS. THESE DETAILS ARE NOT

NECESSARILY SPECIFICALLY REFERENCED CONDITIONS AND ARE FOR

GENERAL INFORMATION.

THESE DIAGRAMS ILLUSTRATES THE SPECIFIC REQUIREMENTS OF

ACCESSIBILITY STANDARDS, TITLE 24 & ADA REQUIREMENTS AND IS

INTENDED ONLY AS AN AID FOR BUILDING DESIGN AND CONSTRUCTION.

MOUNTING HEIGHTS SHOWN ARE FROM ABOVE FINISH FLOOR. TO THE

HIGHEST OPERABLE PART WHICH IS ESSENTIAL TO BASIC OPERATION OF

THE DEVICE SHOWN. (CRITICAL FOR ADA COMPLIANCE)

CLEAR AREA DIMENSIONS SHOWN ARE FACE OF FINISH TO FACE OF

FINISH. (CRITICAL FOR ADA COMPLIANCE)

PROVIDE MILDEW RESISTANT SEALANT AROUND RECESSED RESTROOM

EQUIPMENT

PROVIDE 16 GA. BACKING OR WOOD BLOCKING AT LAVATORY TOPS,

GRAB BARS, TOILET/ BATH AND LAUNDRY ACCESSORIES; SECURE

PROVIDED BLOCKING TO AT LEAST 3 STUDS BUT NOT LESS THAN

INDICATED WIDTH. PROVIDE BLOCKING WHETHER LAVATORY TOPS,

GRAB BARS OR ACCESSORIES, ARE PROVIDED OR INSTALLED BY

CONTRACTOR, OWNER OR THIRD PARTY.

TOILET PAPER DISPENSERS INSTALLED AT 7" MIN. TO 9" MAX IN FRONT OF

WATER CLOSET

BOTTOM OF MIRROR TO BE INSTALLED 38" ABOVE FLOOR OR MINIMUM

OF 40" TO BOTTOM OF VIEWING SURFACE

CONTROLS AND OPERATING MECHANISMS TO BE OPERABLE WITH ONE

HAND AND NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF

THE WRIST. 5 LBF (22.2 N) FORCE REQUIRED TO ACTIVATE CONTROLS,

FAUCETS LEVER-OPERATED, PUSH-TYPE AND ELECTRONICALLY

CONTROLLED MECHANISMS. SELF-CLOSING VALVES TO REMAIN OPEN

FOR AT LEAST 10 SECONDS

DIMENSIONS SHOWN ARE TO CENTERLINE OF CONTROLS OR THE

ACTION REQUIRED TO OPERATE THE INDICATED ITEM. DIMENSIONS TO

CONTROLS ARE TO TOP OF BUTTON, LEVER, OR KNOB. VERTICAL

DIMENSIONS ARE THE TOP OF GRAB BARS AND HORIZONTAL ARE TO THE

CENTER LINE.

UNLESS OTHERWISE NOTED, TOILET ACCESSORIES ARE HORIZONTALLY

DIMENSIONED TO CENTERLINE OF FIXTURE. WHERE TOILET IS

INDICATED TO BE "WALL HUNG OR FLOOR MTD" REFER TO PLUMBING

DRAWINGS FOR EXACT FIXTURE.

GENERAL CONTRACTOR SHALL COORDINATE TOILET FIXTURE

LOCATIONS WITH PLUMBING CONTRACTOR WITH RESPECT TO FLUSH

VALVE HEIGHT AND HORIZONTAL LOCATION VS. GRAB BAR LOCATIONS.

GRAB BAR HEIGHT AND TOP OF TOILET SEAT HEIGHT IS BASED ON

ADAAG AND CANNOT BE CHANGED.

TV MONITOR

WALL MOUNT

RECESSED

MEDIA BOX

MONITOR

CONFIRM SIZE

CARD READER

OR AUTOMATIC

DOOR OPENER

" O

C

VI

F

W / O

W

NE

R' S

EQ

UI

PM

EN

T

M

IN

. F

RO

M B

OT

TO

M

OF

T

EX

T

M

AX

. F

RO

M T

OP

O

F

TE

XT

PAPER TOWEL

DISPENSER

HI

GH

ER

T

HA

N

" 4" MAX

6'- 8"

M

IN

WALL

OUTLET

THERMOSTAT

SWITCH

1'- 3"

M

IN

4'-

0" M

AX

3'- 0"

M

IN

MISCELLANEOUS

DEVICES

5"

SIGN

MOUNTING

4'- 0"

FIRE EXTINGUISHER

CABINET

" M

AX

CLEARANCES

CANE RANGE WHEELCHAIR REACH RANGES

"-5

1"

9"

8"8"

HE

AD

C

LE

AR

AN

CE

3'- 6"

5'- 0"

" A

FF

" A

FF

MOP BASIN &

HOLDER

3'-

SEE PLAN

4'- 0"

2'- 6"

M

IN

6'- 6"

MARKER

BOARD

BULLETIN

BOARD

TACK

BOARD

SE

E

PL

AN

SEE PLANSEE PLAN

6'-

6" SE

E

PL

AN

4'- 0"

4'- 0"

CANE

RANGE

EYE LEVEL

HANDLE

ARMREST LAP

SEAT

TOE

CL

" : Inch; Ditto (which means same as above) # : Number. or Pound

ABV: Above AC: Acoustical Panel Ceiling System

ACI: American Concrete Institute

ACR: Acrylic ACT: Acoustic Ceiling Tile ADA: Americans with Disabilities Act ADAAG: Americans with Disabilities Act Architectural Guidelines ADDL: Additional ADH: Adhesive ADJ: Adjacent AFF: Above Finished Floor

AIA: American Institute of Architects AIEE: American Institute of Electrical Engineers

AISC: American Institute of Steel Construction AL: Aluminum ALT: Alternate

AP: Access Panel, Acoustic Panel APPROX: Approximate APT: Apartment ARCH: Architectural

ASB: Asbestos ASCE: American Society of Civil Engineers ASME: American Society of Mechanical Engineers

ASPH: Asphalt ASSOC: Association ASTM: American Society for Testing and Materials

ATTEN: Attenuation ATM: Automatic Teller Machine AUTO: Automatic AVG: Average AW: Acid Waste AWG: American Wire Gauge AWS: American Welding Society

BH: Bulkhead BL: Building Line, Borrowed Lite BLDG: Building BLKG: Blocking BN: Bullnose BP: Base Plate BPL: Bearing Plate BRG: Bearing BRK: Brick BRKR: Breaker

BTUH: British Thermal Units per Hour BTM; Bottom BVL: Bevelled

C/C: Center to Center

CAB: Cabinet

CAIS: Caisson CAP: Capacity CB: Catch Basin

CCTV: Closed Circuit TV

CFM: Cubic Feet per Minute CFS: Cubic Feet per Second CG: Corner Guard CH: Coat Hook CHAM: Chamfer

CHAN: Channel

CIP: Cast-in-Place CIR: Circular CJ: Control Joint CL: Centerline, Closet CLG: Ceiling CLKG: Caulking

CMU: Concrete Masonry Unit CND: Conduit COAX: Coaxial CO: Cased Opening COL: Column COMB: Combination COMP: Compressed CONC: Concrete CONSTR: Construction CONT: Continuous CORR: Corridor CPL: Cement Plaster CPP: Cement Plaster Painted CPR: Copper CPT: Carpet, Carpet Tile, Broadloom Carpet, Area Rug

CS: Cast Stone CSG: Casing CSMT: Casement CT: Ceramic Tile CU: Cubic

CF: Cubic Feet, Contractor Furnish

CY: Cubic Yard

CW: Clockwise

CYL: Cylinder

DA: Double Acting DB: Decibel DBL: Double DEG: Degree

DEG.C: Degree Celcius DEG.F: Degree Farenheit

DIFF: Diffuser DIM: Dimension, Dimmer DIV: Division DL: Dead Load DN: Down DR: Drain

DTL: Detail DW: Distilled Water, Dishwasher DWG: Drawing

DS: Downspout

EA: Each EB: Expansion Bolt EC: Electrical Contractor EIFS: Exterior Insulation and Finish System EJ: Expansion Joint EL: Elevation ELEC: Electrical

EM: Emergency

ENCL: Enclosure

ENG: Engineer ENT: Entrance EPDM: Ethylene Propylene Diene Monomer

EQ: Equal EQUIP: Equipment ESC: Escalator EST: Estimate EWC: Electric Water Cooler EWH: Electric Water Heater

EXG: Existing EXP: Expansion

F: Fuse FA: Fire Alarm FAB: Fabricate FACP: Fire Alarm Control Panel FB: Floor Box FD: Floor drain FDN: Foundation

FE: Fire Extinguisher, Finished End FEC: Fire Extinguisher Cabinet FF: Finished Floor FF&E: Fixtures, Furnishings & Equipment

FHC: Fire Hose Cabinet FHR: Fire Hose Rack FHS: Fire Hose Station FIN: Finished FIXT: Fixture FL: Floor Line FLEX: Flexible FLR: Floor

FLUOR: Fluorescent FM: Fire Main FO: Finished Opening FOC: Face of Concrete FOF: Face of Finish FOS: Face of Studs

GA: Gauge GALV: Galvanized GC: General Contractor GCMU: Glazed Concrete Masonry Unit GFCI: Ground Fault Circuit Interrupter GFI: Ground Fault Interrupter GFRC: Glass Fiber Reinforced Concrete

GL BLK: Glass Block

GND: Ground GOVT: Government GPH: Gallons Per Hour GPM: Gallons Per Minute GR: Grade, Grille, Grout GRAN: Granular, Granite GRND: Ground

GVL: Gravel GWB: Gypsum Wall Board GYP: Gypsum

HB: Hose Bib HC: HVAC Contractor

HW: Hardware

HID: High Intensity Discharge HL: Hydrant Line HM: Hollow Metal HORIZ: Horizontal HPS: High Pressure Sodium, High Pressure Steam HR: Hour, Hand Rail HVAC: Heating, Ventilating & Air Conditioning

HWY: Highway

HYD: Hydraulic

ID: Inside Diameter, Interior Designer

IN: Inch INCL: Incline, Include INFO: Information

INSUL: Insulation INV: Invert

JAN: Janitor JB: Junction Box JC: Janitor's Closet JT: Joint

KIT: Kitchen KO: Knockout KP: Kickplate

KW: Kilowatt KWH: Kilowatt Hour

LAB: Laboratory, Labor LAD: Ladder LAM: Laminate, Laminated LAT: Lateral LAV: Lavatory

LB: Pound (weight), Lag Bolt LCD: Liquid Crystal Diode

MAINT: Maintenance MARB: Marble MAS: Masonry

MAT: Material, Walk Off Mat

MAX: Maximum

MECH: Mechanical

MTL: Metal

MEZZ: Mezzanine MFR: Manufacture, Manufacturer MH: Manhole

MIN: Minimum MISC: Miscellaneous

MO: Masonry Opening

MP: Metal Acoustal Panel MTD: Mounted

NAT: Natural NEC: National Electrical Code NIC: Not In Contract NO: Number, Normally Open

NOM: Nominal NRC: Noise Reduction Coefficient NTS: Not To Scale

OC: On Center OD: Outside Diameter

OFF: Office OH: Overhead OHD: Overhead Door

OPP: Opposite OPPH: Opposite Hand OR: Outside Radius

OZ: Ounce

PLAM: Plastic Laminate

PA: Public Address PAR: Parallel PB: Pull Box, Push Button, Panic Bar PC: Plumbing Contractor, Privacy Curtain, Powder Coated PCF: Pounds per cubic foot

PD: Pump Discharge, Plaza Drain

PE: Professional Engineer PED: Pedestal, Pedestrian PERF: Perforate, Performance PERIM: Perimeter PERP: Perpendicular

PJF: Preformed Joint Filler PKG: Parking PKWY: Parkway PL: Plate, Plan, Property Line

PLAS: Plaster, Plastic PLF: Pounds Per Lineal Foot PLWD: Plywood

PNL: Panel POL: Polish, Polished

POR: Porcelain PR: Pair PREFAB: Prefabricated PSF: Pounds per square foot

PSI: Pounds per square inch PT: Paint, Point PTC: Post-Tensioned Concrete PTD: Painted

PVC: Polyvinyl Chloride PVMT: Pavement PWR: Power

QUAL: Quality

QT: Quarry Tile, Quart QTR: Quarter QTY: Quantity

RA: Return Air, Registered Architect RAD: Radius, Radiator RB: Rubber, Resilient Base RCP: Reflected Ceiling Plan, Reinforced Concrete Pipe

RD: Roof Drain, Round, Receptacle Distribution Panel REBAR: Reinforcing Bar REF: Refer, Reference, Refrigerator

REG: Register, Regular REINF: Reinforcement, or Reinforce REQD: Required REV: Revise, Revision RH: Right Hand, Reheat, Relative Humidity

RHR: Right Hand Reverse, Reheater RM: Room RO: Rough Opening

ROW: Right of Way

RPM: Revolutions Per Minute

RR: Railroad

RWC: Rain Water Conductor RWL: Rain Water Leader

S: South, Sealant, Supply, Sink SAN: Sanitary SC: Solid Core, Short Circuit, Self Closing, Sill Cock SCHED: Schedule SCUP: Scupper

SCWD: Solid Core Wood

SE: Structural Engineer

SF: Square Foot

SFGL: Safety Glass SHWR: Shower

SIM: Similar

SLOT: Slotted

SP: Soil Pipe, Standpipe, Soundproof, Single Pole

SPK: Speaker

SST: Stainless Steel SSG: Structural Silicone Glazing

ST: Straight, Storm Water

STC: Sound Transmission Class STD: Standard STK: Stack STL: Steel STOR: Storage STRUCT: Structural

SUPP: Supplementary, Supplement SUSP: Suspended, Suspend

SY: Square Yard

T&G: Tongue & Groove

TAN: Tangent

TEL: Telephone

TEMP: Temporary, Tempered, Temperature

THK: Thick, Thickness THRM: Thermal

TSTAT: Thermostat

TB: Tackboard

TLT: Toilet

TRAV: Travertine

TRD: Tread TS: Time Switch

TV: Television TW: Top of Wall,Tempered Water

TYP: Typical

UH: Unit Heater UL: Underwriters' Laboratories UNEXC: Unexcavated UNO: Unless Noted Otherwise

VEST: Vestibule

VIF: Verify In the Field VP: Vapor Proof, Vent Pipe VR: Vapor Retarder, Vacuum Return, Vertical Riser VRM: Vermiculite VS: Vent Stack

W/: With

W/O: Without

WB: Wood Base WC: Watercloset, Wall Covering WD: Wood WDSS: Wood, Stained & Sealed WDW: Window

WH: Water Heater, Wall Hung, Wall Hydrant

WP: Waterproof, Working Point, Working Pressure, Weatherproof, Wall Protection WPR: Waterproofing WR: Water Resistant, Water Repellant

YD: Yard YR: Year

CLR: Clear CM: Centimeter

CR: Card Reader, Crash Rail

CAC: Ceiling Attenuation Class

ANOD: Anodized

FG: Fire Rated Glass

ENS: Entrance Mat System

ELEV: Elevator

EPX: Epoxy

GL: Glass GF: Glass Film

HCW: Hollow Core Wood

WF: Wood Flooring

INHM: Insulated Hollow Metal

IG: Insulated Glass

PET: Polyethylene Terephthalate Felt

MON: Monitor

MM: Milimeter

MW: Microwave, Millwork

MC: Metal Faced Mineral Core

MLD: Moulding

MB: Marker Board, Media Box

MA: Millwork Accessory

MDF: Medium Density Fiberboard, Main Distribution Frame

MIC: Microphone

QZ: Quartz

RTF: Resiliant Tile Flooring RSF: Resiliant Sheet Flooring RS: Roller Shade

SI: Spray Insulation

SD: Smoke Detector SDT: Static Dissipative Tile

SEC: Security

SLD: Sealed

WRC: Waste Receptacle

WELL: Well Building Standard

WT: Window Treatment

VEN: Wood Veneer

WMC: Wood Veneer Mineral Core

VENT: Vent Pipe

UF: Unfinished

UC: Undercut

TZ: Terrazzo (poured), Terrazzo Tile TR: Transition, Transition Strip, Trim

TG: Tempered Glass

TP: Toilet Partition

TA: Toilet Accessory

TB: Tile Base

STN: Stain, Stone

SS: Solid Surface SR: Sheet Rubber

SV: Sheet Vinyl

BRZ: Bronze BSMT: Basement BTU: British Thermal Units

DEMO: Demolition DEPT: Department DET: Detail DF: Drinking Fountain DH: Double Hung DIAG: Diagonal

FP: Fireproof, Fire Protection

FT: Feet FTG: Footing FURN: Furnish, Furnish, Furniture FUT: Future

FRP: Fiberglass Reinforced Panel FS: Filler Strip

LH: Left Hand LG: Laminated Glass

LED: Light Emitting Diode

LEED: Leadership in Energy & Environmental Design

LHR: Left Hand Reverse LIB: Library

LKR: Locker LL: Live Load

LPS: Low Pressure Sodium, Low Pressure Steam LS: Limestone, Loud Speaker

LIN: Linoleum Sheet, Tile, or Poured

LT: Light Fixture

VCT: Vinyl Composition Tile

VERT: Vertical

EXH: Exhaust

OF: Owner Furnish

OI: Owner Install

CI: Contractor Install

OVF: Owner's Vendor Finish OVI: Owner's Vendor Install

LCVF: Lab Casework Vendor Furnish LCVI: Lab Casework Vendor Install

CWW: Counterclockwise

EXR: Existing to Remain

FLT:Felt

GT: Glass Tile

LVT: Luxury Vinyl Tile

U/C: Undercabinet, Undercounter

AHJ: Authority Having Jurisdiction

A

E

RH

S

H

FEC

F

0'-0

0'-0"

EXTERIOR ELEVATION INDICATOR

INTERIOR ELEVATION INDICATOR

SHEET NUMBER

DETAIL OR ENLARGED PLAN NUMBER

DETAIL OR ENLARGED PLAN INDICATOR

AREA OF DETAIL OR ENLARGED PLAN

A-400

A-400

SHEET NUMBER

ELEVATION NUMBER

ELEVATION NUMBER

ELEVATION NUMBER

A-200

A-300

A-300

SHEET NUMBER

ELEVATION NUMBER

INDICATES SURFACE ELEVATED

BUILDING SECTION INDICATOR

WALL SECTION INDICATOR

SHEET NUMBER

SECTION NUMBER

INDICATES DIRECTION OF WALL

SECTION VIEW

SHEET NUMBER

SECTION NUMBER

INDICATES DIRECTION OF WALL

SECTION VIEW

100-1

DOOR NUMBER

NOTE: REFER TO DOOR SCHEDULE

FOR ADDITIONAL INFORMATION.

ROOM NUMBER

DOOR INDICATOR

CONTROL POINT NUMBER

CONTROL POINT SYMBOL INDICATOR

CP-#

T1100

LOBBY

ROOM NUMBER

ROOM FINISH TYPE. SEE SCHEDULE OF

FINISHES FOR DESCRIPTION

ROOM NAME INDICATOR

ROOM NAME

REFERENCE NOTE

SYMBOL INDICATOR

NOTE NUMBER.

REFER TO REFERENCED NOTES.

00.00

EXISTING DOOR

NEW DOOR SMOKE DETECTOR

HEAT DETECTOR

EMERGENCY BATTERY UNIT

REMOTE HEAD

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

EXIT SIGN

FIRE ALARM (MANUAL PULL TYPE)

FIRE EQUIPMENT LEGEND

NEW FINISHED ELEVATION

GRADE ELEVATION INDICATOR

EXISTING ELEVATION

FINISHED FLOOR ELEVATION

GRADE ELEVATION INDICATOR

A-500

SHEET NUMBER

DETAIL NUMBER

INDICATES DIRECTION OF DETAIL VIEW

DETAIL INDICATOR

0'-0"

FINISHED ELEVATION

CEILING ELEVATION INDICATOR

0'-0"

GWB FINISHED MATERIAL

V

INDICATES ITEM SCHEDULED AND

SPECIFIED IN PROJECT MANUAL

TOILET ACCESSORY INDICATOR

EXISTING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

NOTE: REFER TO WALL TYPE INDICATOR FOR SPECIFIC WALL TYPE

NEW WALL

WALL TYPE INDICATOR

WALL TYPE. REFER TO WALL TYPE

LEGEND FOR ADDITIONAL

INFORMATION.

ABC

WINDOW NUMBER

NOTE: REFER TO WINDOW SCHEDULE

FOR ADDITIONAL INFORMATION.

WINDOW INDICATOR

A

COLUMN LINE INDICATOR

SIGNAGE INDICATOR

NOTE: REFER TO SPECIFICATION FOR

ADDITIONAL INFORMATION.

SIGNAGE INDICATOR

A-300

EXISTING DOOR TO BE REMOVED

COLUMN GRID LINE

COLUMN GRID NUMBER OR LETTER

NOTE: HATCH PATTERNS SHOWN ON DRAWINGS ARE FOR GRAPHICAL

REPRESENTATION ONLY AND SHOULD NOT BE INTERPRETED AS LITERAL

OR EXACT DEPICTIONS OF MATERIALS, DIMENSIONS, OR CONSTRUCTION

METHODS.

NOTE: REFER TO FINISH LEGEND ON SHEET AF001 FOR ADDITIONAL INFO.

FINISH MATERIAL EXTENTS LEADER

WALL BASE FINISH TAG

WALL FINISH TAG

FINISH MATERIAL INDICATORS

PT-1

B-1

AREA NOT IN ARCHITECTURAL SCOPE

THE SCOPE OF WORK AREA INDICATED ON THE DRAWINGS IS FOR GENERAL

COORDINATION PURPOSES ONLY AND IS NOT TO LIMIT THE PROJECT SCOPE

DIRECTLY - THE CONTRACTOR IS TO COORDINATE THE OVERALL PROJECT

SCOPE AS INDICATED ON THE DRAWINGS. DIRECT SCOPE OUTLINED AND

DIRECTED VIA DRAWING, NOTES, OR DETAILS ELSEWHERE WITHIN

DOCUMENTS SUPERCEDES WHETHER OR NOT INDICATED WITHIN THE

SCOPE OF WORK AREA. THE CONTRACTOR IS TO COORDINATE TEMPORARY

PARTITIONS AND PROTECTIVE MEASURES REQUIRED TO PROTECT EXISTING

CONDITIONS AND PROVIDE A SAFE WORK AREA FOR BUILDING OCCUPANTS

PER THE SCOPE OF WORK INDICATED IN THESE DOCUMENTS.

LIMIT OF ARCHITECTURAL WORK LINE

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

A-001 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

ABBREVIATIONS,

SYMBOLS AND

STANDARD

MOUNTING

HEIGHTS

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

1/4" = 1'-0"

STANDARD MOUNTING HEIGHTS

ABBREVIATIONS SYMBOL LEGEND

R

AM

P

D N

UP

UP

DN

UP

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

THE CONSTRUCTION DOCUMENTS ARE BASED ON THE EXISTING

DRAWINGS PRODUCED BY ORIGINAL CONSTRUCTION DOCUMENTS BY

ALTENHOF AND BROWN FROM FEBRUARY 1957, AND RENOVATION

DOCUMENTS BY FOREMAN ARCHITECT AND ENGINEERS IN 2011; AND A

FIELD SURVEY OF EXISTING CONDITIONS. CONTRACTORS SHALL VERIFY

EXISTING CONDITIONS AND ANY DISCREPANCIES SHALL BE BROUGHT TO

THE ATTENTION OF OWNER'S REPRESENTATIVE AND THE ARCHITECT.

HAZARDOUS MATERIALS ARE NOT ANTICIPATED. NOTIFY OWNER &

ARCHITECT OF ANY ASBESTOS MATERIALS THAT ARE UNCOVERED

DURING DEMOLITION

PROPERLY DISPOSED OF ANY MERCURY CONTAINING FLUORESCENT

LIGHT TUBES AND BULBS, PCB BALLASTS AND EXIT SIGNS.

OWNER TO PROVIDE ASBESTOS ABATEMENT PRIOR TO BIDDING.

ASBESTOS ABATEMENT TO BE COMPLETED BY OWNER. GENERAL

CONTRACTOR TO COORDINATE REMOVAL WITH OWNER AND DEMOLITION

WORK TO MAINTAIN WEATHER TIGHT BUILDING.

CONDUCT WORK UNDER THE ASSUMPTION THAT SURFACE COATINGS

CONTAIN LEAD.

OWNER HAS THE RIGHT OF FIRST OF REFUSAL FOR ALL SALVAGEABLE

MATERIALS.

REMOVE FLOOR FINISHES AND ADHESIVES. SUBFLOOR TO BE SHOT

BLASTED GROUND, SCARIFIED, AND/OR ETCHED AS REQUIRED TO

REMOVE ADHESIVES AND TO ACHIEVE SUITABLE SURFACE ACCEPTABLE

TO GUARANTEE FLOOR FINISH WARRANTY. PROVIDE MINIMUM OF 1/2"

SELF LEVELING COMPOUND AT TILE OR SHEET GOOD PREPARED FOR

NEW FLOOR FINISH.

REMOVE EXPOSED PIPING OR FIXTURES THAT ARE NOT IN OPERATION

OR PROPOSED TO BE ABANDONED THAT WILL INTERFERE W/ NEW WORK

OR BE EXPOSED AFTER NEW WORK IS COMPLETED.

CAP AND RENDER SAFE ALL ELECTRICAL WIRING FROM EXISTING TO BE

DEMOLISHED ELECTRICAL OUTLETS AND EQUIPMENT. SEE E-SERIES

DRAWINGS.

FIRE ALARM AND ELECTRICAL PANELS LOCATED IN WALLS INDICATED TO

BE REMOVED SHALL REMAIN ACTIVE UNTIL THEY ARE REPLACED OR

RELOCATED, REFER TO ELECTRICAL DRAWINGS FOR NEW LOCATIONS.

PROVIDE TEMPORARY BARRICADES AND OTHER TEMPORARY FACILITIES

TO PROTECT THE PUBLIC, STORED MATERIALS AND INSTALLED

MATERIALS.

REQUIRED TEMPORARY PARTITIONS ARE TO BE CONSTRUCTED FROM

FLOOR TO CEILING TO ENSURE ACCESS AND DUST CONTROL.

TEMPORARY PARTITIONS AND BARRIERS ARE TO MEET APPLICABLE

CODES AND ORDINANCES.

VERTICAL PENETRATIONS TO BE PATCHED AS SPECIFIED PER SECTION

078413. REFER TO SECTION 017329 CUTTING AND PATCHING.

IF THE BUILDING WILL BE OCCUPIED DURING DEMOLITION AND

CONSTRUCTION, THE CONTRACTORS SHALL COORDINATE ANY

REQUIRED UTILITY SHUT DOWNS WITH THE OWNER. CONTRACTORS TO

PROVIDE TEMPORARY BARRICADES, PER APPROVAL OF BUILDING

OWNER, TO PROTECT THE USERS AND EXISTING MATERIALS TO REMAIN.

MEANS OF EGRESS ARE REQUIRED TO BE MAINTAINED THROUGHOUT

DEMOLITION AND CONSTRUCTION.

GENERAL DEMOLITION NOTES

DEMOLITION LEGEND

EXISTING DOOR AND FRAME TO REMAIN

EXISTING DOOR AND FRAME TO BE DEMOLISHED

EXISTING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

DEMOLITION PLAN LEGEND

EXISTING CEILING TO REMAIN

EXISTING CEILING TO BE DEMOLISHED

EXG-# X'-X"

EXG-# X'-X"

DEMOLITION REFLECTED CEILING PLAN LEGEND

02.02

02.01

02.01 02.04

02.04

02.04

02.05

02.03

MECHANICAL PIPING SHOWN FOR CLARITY AND

COORDINATION PURPOSES. CONTRACTOR TO VERIFY

ROUTING AND PIPE RUNS IN THE FIELD AND COORDINATE

CEILING WORK INCLUDING DEMOLITION AND NEW WORK

WITH MECHANICAL PLANS AND NOTIFY ARCHITECT AND

OWNER OF DISCREPANCIES.

EXG-3 8'-2"

EXG-4 9'-0"

EXG-1 8'-2" 017

CRIME LAB

017A

CRIME LAB

MECHANICAL ROOM

MECHANICAL ROOM

017A

CRIME LAB

CRIME LAB

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

AD101

26030

05/15/2026

CONSTRUCTION

DOCUMENTS

GROUND

FLOOR AND

REFLECTED

CEILING

DEMOLITION

PLAN

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

REFERENCED DEMOLITION NOTES

MARK DESCRIPTION

02.01 DEMOLISH INTERIOR DOOR

02.02 DEMOLISH DOOR

02.03 DEMOLISH EXISTING CEILING - CLEAN EXPOSED DECK ABOVE FOR NEW

FINISH AND PAINT TO MATCH EXISTING EXPOSED DECK.

02.04 REMOVE FLOOR FINISH AND PREP SUBSTRATE FOR NEW FINISH

02.05 DEMOLISH RAILING AND GRIND SMOOTH WITH FLOOR.

1/8" = 1'-0"2 GROUND FLOOR REFLECTED CEILING DEMO PLAN

1/8" = 1'-0"1 GROUND FLOOR DEMO PLAN

R

AM

P

D N

UP

UP

DN

UP

UP

UP

R

AM

P

D N

UP

UP

1.

2.

3.

4.

5.

6.

7.

8.

9.

CONTRACTOR TO VERIFY DIMENSIONS, QUANTITIES AND CONDITIONS IN

FIELD AT JOB SITE AND NOTIFY ARCHITECT & ENGINEER OF

DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS PRIOR TO

COMMENCING WORK.

INTERIOR DIMENSION ARE FROM FACE OF FINISH MATERIAL TO FACE OF

FINISH MATERIAL, UNLESS NOTED OTHERWISE. DIMENSIONS CONNECT

COLUMN LINES, FACE OF FINISH MATERIAL. REFER TO WALL TYPES FOR

THICKNESS OF WALLS.

THE SCOPE OF WORK AREA INDICATED ON THE DRAWINGS IS FOR

GENERAL COORDINATION PURPOSES ONLY AND IS NOT TO LIMIT THE

PROJECT SCOPE DIRECTLY - THE CONTRACTOR IS TO COORDINATE THE

OVERALL PROJECT SCOPE AS INDICATED ON THE DRAWINGS. DIRECT

SCOPE OUTLINED AND DIRECTED VIA DRAWING, NOTES, OR DETAILS

ELSEWHERE WITHIN DOCUMENTS SUPERSEDES WHETHER OR NOT

INDICATED WITHIN THE SCOPE OF WORK AREA.

THE CONTRACTOR IS TO COORDINATE TEMPORARY PARTITIONS AND

PROTECTIVE MEASURES REQUIRED TO PROTECT EXISTING CONDITIONS

AND PROVIDE A SAFE WORK AREA FOR BUILDING OCCUPANTS PER THE

SCOPE OF WORK INDICATED IN THESE DOCUMENTS.

THE CONSTRUCTION DOCUMENTS ARE BASED ON THE EXISTING

DRAWINGS PRODUCED BY ORIGINAL CONSTRUCTION DOCUMENTS BY

ALTENHOF AND BROWN FROM FEBRUARY 1957, AND RENOVATION

DOCUMENTS BY FOREMAN ARCHITECT AND ENGINEERS IN 2011; AND

AFIELD SURVEY OF EXISTING CONDITIONS. CONTRACTORS SHALL VERIFY

EXISTING CONDITIONS AND ANY DISCREPANCIES SHALL BE BROUGHT TO

THE ATTENTION OF OWNER'S REPRESENTATIVE AND THE ARCHITECT.

REFER TO LIFE SAFETY PLANS FOR LOCATION AND EXTENT OF FIRE

RATED ASSEMBLIES AND ADDITIONAL LIFE SAFETY INFORMATION.

GC TO PROVIDE ACCESS PANEL LOCATION DOCUMENTATION AND

COORDINATE ALL CEILING ACCESS AROUND FIXTURES, FURNISHINGS,

AND EQUIPMENT REQUIRED FOR MEP & FP SCOPE OF WORK. GC TO

SUBMIT LOCATIONS AND TYPES FOR ARCHITECT APPROVAL.

THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND

SPECIFICATIONS OF ALL OTHER TRADES. ALL ITEMS REQUIRING POWER

INDICATED ON THE ARCHITECTURAL DRAWINGS SET (INCLUDING BUT NOT

LIMITED TO CORE DRILLS, FLOOR BOXES, DOOR ACCESS CONTROLS, AND

POWER LOCATIONS FOR MONITORS) SHALL BE CONSIDERED A PART OF

THE ELECTRICAL CONTRACTOR’S WORK. NOTIFY ARCHITECT IF

DISCREPANCIES OCCUR BEFORE PERFORMING CORE DRILL WORK.

PATCH ALL UNPROTECTED PENETRATIONS IN THE MECHANICAL ROOMS

IN WALLS, CEILINGS, AND FLOORS WITH APPROPRIATELY RATED

SEALANTS AND ASSEMBLIES. THE GENERAL CONTRACTOR IS

RESPONSIBLE FOR SURVEYING THE PROJECT AREA FOR UNPROTECTED

PENETRATIONS.

GENERAL CONSTRUCTION NOTES

FIBER ARTS STUDIO

017B

FIBER ARTS

STORAGE

MECHANICAL

- 1

/2

1'-6" 18'-0"

HIF

A-401

KBD

IBH

IBH

'-1 0"

VIF

3'-4" 26'-1" VIF

09.01

09.01

09.02 09.02

05.01

AL

IG

N

09.05 09.05 09.05

22.02

23.01

09.06

8"

A-401

HIF

26.02

9487 SF

22.01

23.0123.01IKJ

IKJ

HIF

35/8" METAL STUDS @ 16" OC

5/8" WATER-RESISTANT GWB, EXTEND

TIGHT TO DECK

35/8" METAL STUD WITH GWB WATER-RESISTANT

BASE

PLAN

HEAD

UNDERSIDE OF STRUCTURE ABOVE

WALL BASE & FLOOR FINISH

AS SCHEDULED

FINISHED SLAB

SCALE: 11/2" = 1'-0"

KAE

6" METAL STUD WITH GWB

6" METAL STUDS @ 16" O.C.

5/8" GWB, EXTEND TIGHT TO

CEILING

BASE

PLAN

HEAD

UNDERSIDE OF CEILING ABOVE

WALL BASE & FLOOR FINISH

AS SCHEDULED

FINISHED SLAB6 5/8"

SCALE: 11/2" = 1'-0"

IBH

35/8" METAL STUDS @ 16" OC

5/8" TYPE 'X' GWB BOTH SIDES,

EXTEND TIGHT TO DECK, INSULATE

VOID, SEALANT AT JUNCTIONS.

SOUND ATTENUATING BATT

INSULATION

35/8" METAL STUD WITH GWB (UL #U432 - 1 HOUR)

BASE

PLAN

HEAD

UNDERSIDE OF STRUCTURE ABOVE

WALL BASE & FLOOR FINISH

AS SCHEDULED

FIRE RATED SEALANT BOTH SIDES

4 7/8" FINISHED SLAB

FIRE RATED SEALANT BOTH SIDES

SCALE: 11/2" = 1'-0"

IKJ

35/8" METAL STUDS @ 16" OC

5/8" GWB, TWO LAYERS, EXTEND

TIGHT TO CEILING, INSULATE VOID,

SEALANT AT JUNCTIONS.

SOUND ATTENUATING BATT

INSULATION

35/8" METAL STUD GWB AND RESILIENT CHANNEL

ACOUSTICAL PARTITION

BASE

PLAN

HEAD

UNDERSIDE OF CEILING ABOVE

WALL BASE & FLOOR FINISH

AS SCHEDULED

ACOUSTIC SEALANT BOTH SIDES

FINISHED SLAB

ACOUSTIC SEALANT BOTH SIDES

SCALE: 11/2" = 1'-0"

SOUND ISOLATION CLIPS AND

HAT CHANNELS @ 16" OC

VERTICALLY ATTACHED TO

EVERY OTHER STUD

5/8" TYPE GWB, EXTEND

7 1/8"

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

SPECIFIC MATERIAL UNITS DEPICTED ON DETAILS & SECTIONS INTENDED

FOR GRAPHIC ILLUSTRATION ONLY AND DO NOT NECESSARILY INDICATE

MATERIAL SPACING, INSTALLATION METHODS, OR OTHER MEANS &

METHODS; UNLESS SPECIFICALLY DIMENSIONED AND NOTED

OTHERWISE.

FIRE RATED PARTITIONS EXTEND STUDS AND BOTH SIDES OF WALL

BOARD TO DECK UNLESS NOTED OTHERWISE. FIRE SAFE JOINTS AND

PENETRATIONS AT FIRE RATED PARTITIONS.

UL NUMBERS LISTED APPLY ONLY TO THE TESTED MANUFACTURERS'

PRODUCT OR SYSTEM. EQUAL MANUFACTURERS' WITH EQUIVALENT

PRODUCT OR UL ASSEMBLY INFORMATION MUST BE APPROVED BY

ARCHITECT.

WHERE 3 5/8", 4" OR 6" DEEP STUD WALLS ARE INDICATED, FOLLOW

MANUFACTURER'S RECOMMENDATIONS AND TEST RESULTS FOR HEIGHT

LIMITS. DESIGN DEPTHS ARE APPROXIMATED FROM GENERIC SPAN

TABLES.

UNLESS OTHERWISE NOTED EXTEND WALL STUDS AND SINGLE SIDE OF

WALL GYPSUM WALL BOARD TO DECK

EXTEND INSULATION FULL HEIGHT OF PARTITION STUDS. WHERE SOUND

ATTENUATION BATTS ARE INDICATED IN PARTITIONS, INSTALL ACOUSTIC

SEALANT AT BOTH SIDES OF PARTITION BOARDING , ALONG THE TOP AND

BOTTOM, AND AT INTERSECTING PARTITIONS.

STOP WALL BOARD ON PARTITION STUDS 1/2" FROM SUBFLOOR, TYPICAL.

PROVIDE WATER RESISTANT GYPSUM BOARD ON WET WALLS, UNLESS

PORCELAIN OR CREAM TILE IS USED OR OTHERWISE NOTED.

PROVIDE CEMENT BACKER BOARD WHERE WALLS ARE INDICATED OR

SCHEDULED TO RECEIVE PORCELAIN OR CERAMIC TILE, UNLESS NOTED

OTHERWISE. INSTALL FOR THE EXTENT INDICATED OR SCHEDULE FOR

STOP CEMENT BOARD AT EDGE OF TILE FINISH.

REFER TO A-100 & A-400 SERIES FOR WALL LOCATIONS.

PROVIDE ACOUSTIC SEALANT AT TOP & BOTTOM OF PARTITION ON NOISE

GENERATING SIDE, AS REQUIRED BY STC RATING.

REFER TO SHEET SERIES AF101 FOR FINISHES. PROVIDE FINISHES PER

FINISH TYPES AND FINISH SCHEDULE, UNLESS NOTED OTHERWISE.

PROVIDE PRIME COAT ON GYPSUM .WALL BOARD REGARDLESS OF FINAL

FINISHES OR IF NOT SCHEDULED TO RECEIVE FINAL FINISH.

PROVIDE MINIMUM OF LEVEL 4 FINISH ON GYPSUM WALL BOARD

REGARDLESS OF FINAL FINISHES OR IF NOT SCHEDULED TO RECEIVE

FINAL FINISH. UNLESS NOTED OR SPECIFIED OTHERWISE.

GENERAL WALL TYPE NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

CONTRACTOR TO VERIFY DIMENSIONS, QUANTITIES AND CONDITIONS IN

FIELD AT JOB SITE AND NOTIFY ARCHITECT & ENGINEER OF

DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS PRIOR TO

BEFORE COMMENCING WORK.

INTERIOR DIMENSION ARE FROM FACE OF FINISH MATERIAL TO FACE OF

FINISH MATERIAL, UNLESS NOTED OTHERWISE. DIMENSIONS CONNECT

COLUMN LINES, FACE OF FINISH MATERIAL. REFER TO WALL TYPES FOR

THICKNESS OF WALLS.

DIMENSION ARE FROM FACE OF FINISH MATERIAL TO FACE OF FINISH

MATERIAL, UNLESS NOTED OTHERWISE.

REFER TO AF SERIES FOR FINISH MATERIAL TYPES AND SCHEDULE FOR

ADDITIONAL INFORMATION OF LOCATIONS AND TYPES OF FINISH

MATERIALS.

UNLESS OTHERWISE NOTED, CENTER IN ROOMS WITH EQUAL SPACING

AND/OR EDGE ALIGN CEILING GRID, CEILING MOUNTED LUMINAIRES,

DIFFUSERS, EQUIPMENT BY OTHERS IN CEILING TILES, AS INDICATED

GRAPHICALLY FOR COORDINATION.

REFLECTED CEILING PLAN INDICATES THE PREFERRED LOCATION OF

HVAC DIFFUSERS AND RETURN AIR GRILLES, GENERIC SPACING OF

SPRINKLER HEADS AND PLACEMENT OF ADDITIONAL MECHANICAL

EQUIPMENT. COORDINATE PLACEMENT OF HVAC, PLUMBING AND

SPRINKLER SYSTEMS WITH TRADE DRAWINGS. RESOLVE CONFLICT IN

LAYOUT WITH DESIGN PROFESSIONALS BEFORE INSTALLATION.

QUANTITIES OF CEILING FIXTURES, DIFFUSERS, RETURN AIR GRILLES,

AND ALL OTHER EQUIPMENT INDICATED ON THE REFLECTED CEILING

PLANS TO BE COORDINATED WITH MEP AND FIRE PROTECTION

DRAWINGS. REFLECTED CEILING PLAN INDICATES RELATIVE SIZES AND

LOCATIONS.

COORDINATE AND PROVIDE CEILING ACCESS PANEL TYPES AND

LOCATIONS REQUIRED WITH THE CEILING LAYOUT, CEILING TYPES AND

MEP & FIRE PROTECTION DRAWINGS AND SPECIFICATIONS.

REFER TO BOTH ARCHITECTURAL REFLECTED CEILING PLAN DRAWINGS

AND ELECTRICAL DRAWINGS FOR ALL CEILING MOUNTED ELECTRICAL

DEVICES.

SEE MECHANICAL DRAWINGS FOR DIFFUSERS DESCRIPTION AND CEILING

MOUNTED MECHANICAL DEVICES.

SEE PLUMBING DRAWINGS FOR SPRINKLER LOCATIONS, RISER

INFORMATION, AND OTHER WORK BY PLUMBING CONTRACTOR.

CENTER LIGHT FIXTURES IN ROOM WITH EQUAL SPACING UNLESS

OTHERWISE NOTED.

FACE OF BULKHEADS ARE TO ALIGN WITH FACE OF ADJACENT WALLS TO

WHICH BULKHEADS ARE PARALLEL , UNLESS NOTED OTHERWISE OR

DIMENSIONED.

WHERE EXIT SIGNS OCCUR OVER A DOOR OR PAIR OF DOORS, CENTER

SIGN ON DOOR OPENING UNLESS OTHERWISE NOTED.

GENERAL REFLECTED CEILING PLAN NOTES

RCP LEGEND

CEILING MOUNTED EXIT SIGN, DOUBLE FACE, WITH ARROWS

CEILING MOUNTED EXIT SIGN, SINGLE FACE, WITH ARROW

XXX 9'-0" CEILING TAG: TYPE / HEIGHT

CEILING FINISH TAGPT-1

TH1 SURFACE MOUNTED TRACK HEAD

EXISTING LIGHT FIXTURE

TH1TH1TH1TH1TH1TH1TH1TH1TH1TH1TH1TH1

EXG-1 8'-2"

+/- 2'-4" 5'-0"

EQ

+/- 4'-0" 5'-0" 5'-0"

TYP.

5'-0"

EQ

+/- 4'-0"

EQ

+/- 4'-0" 5'-0" 5'-0"

TYP.

5'-0"

EQ

+/- 4'-0"14'-0"

TYP.

5'-0"

EQ

+/- 4'-0"

+/- 23'-0"+/- 23'-0"+/- 23'-0"

FIBER ARTS STUDIO

017B

FIBER ARTS

STORAGE

MECHANICAL

EXST EXST

EXST EXST EXST EXST EXST

EXSTEXSTEXSTEXSTEXSTEXSTEXST

EXST

EXSTEXST

09.03

EXST

EX-1 EX-3

EX-2

07.01

07.01

07.01

PT-2

EXG-1 8'-2"

MECHANICAL PIPING SHOWN FOR CLARITY AND

COORDINATION PURPOSES. CONTRACTOR TO VERIFY

ROUTING AND PIPE RUNS IN THE FIELD AND COORDINATE

CEILING WORK INCLUDING DEMOLITION AND NEW WORK

WITH MECHANICAL PLANS AND NOTIFY ARCHITECT AND

OWNER OF DISCREPANCIES.

09.0409.04

6'-3" Here

09.07

06.01

EXST

EXST

EXST

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

A-101 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

GROUND

FLOOR PLAN

AND

REFLECTED

CEILING PLAN

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

REFERENCED CONSTRUCTION NOTES

MARK DESCRIPTION

05.01 NEW WALL MOUNTED HANDRAIL, RETURN TO WALL AT ENDS - SEE

DETAIL 8/A-401

06.01 PROVIDE BLOCKING FOR CEILING-MOUNTED PROJECTION SCREEN TO

BE PROVIDED BY OWNER.

07.01 SEAL PENETRATION AT NEW PARTITON TO MATCH EXISTING WALL

RATING

09.01 ALIGN FINISH FACE OF WALL WITH FACE OF RAMP

09.02 ALIGN FINISH FACE OF WALL WITH FINISH FACE OF EXISTING COLUMN

09.03 CEILING HUNG DRYING RACK RELOCATED FROM PREVIOUS SPACE

PROVIDED BY OWNER INSTALLED BY CONTRACTOR.

09.04 PROVIDE HANGER ROD AND SUPPORT FOR S-HOOK FROM DECK, SEE

DETAIL 10/A-401

09.05 PROVIDE HOOKS FOR IRONING BOARDS AND IRONS.

09.06 COMMERCIAL KITCHEN STAINLESS STEEL WALL SHELF FOR POT AND

PAN STORAGE WITH RAIL AND HOOKS.

09.07 3-WIRE HANGING RACK PROVIDED BY OWNER AND INSTALLED BY

CONTRACTOR; CONFIRM FINAL LOCATION WITH OWNER.

22.01 ALTERNATE P-1: COUNTERTOP AND BASE AT SINKS. PROVIDE

ROUGH-INS FOR FUTURE SINKS TO BE PROVIDED BY OWNER -

COORDINATE WITH PLUMBING DRAWINGS.

22.02 FLOOR DRAIN, COORDINATE WITH PLUMBING DRAWINGS

23.01 EXISTING RADIATOR TO REMAIN, COORDINATE FRAMING WITH

RADIATOR

26.01 RELOCATED RACEWAY; COORDINATE OUTLET QUANTITY AND

PLACEMENT WITH ELECTRICAL PLAN

26.02 LOCATION OF LAPTOP CONNECTION FOR PROJECTOR, PROVIDE

PATHWAY AND HOOKUP TO PROJECTOR AND OUTLET IN THIS AREA AT

COUNTER HEIGHT. COORDINATE WITH ELECTRICAL DRAWINGS.

1 1/2" = 1'-0"

WALL TYPES

1/8" = 1'-0"1 GROUND FLOOR PLAN

1/8" = 1'-0"2 GROUND FLOOR REFLECTED CEILING PLAN

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER MODEL/STYLE

BOTTOM OF

FIXTURE HEIGHT SIZE FINISH

COLOR

TEMPERATURE CRI MOUNTING REMARKS

EX-1 - EXISTING EXIT SIGN. DOUBLE FACE, RIGHT ARROWS - - - - - -

EX-2 - NEW EXIT SIGN. SINGLE FACE, LEFT ARROW - - - - - - NEW EXIT SIGN

EX-3 - EXISTING RELOCATED SIGN. SINGLE FACE, RIGHT ARROW.

COORDINATE WITH ELECTRICAL DRAWINGS.

- - - - - CEILING RELOCATE OUT OF PROJECTOR THROW ADJACENT TO DOOR.

EXST - EXISTING LINEAR LIGHT - - - - - SURFACE COORDINATE WITH ELECTRICAL DRAWINGS TO PROVIDE

PRICING FOR ALTERNATE E-1.

TH1 ILLUMNI LUMENTURE/T50-35H-1100-22-B-J-S12-SN - - TBD 4000K 90 SURFACE

CEILING TYPE SCHEDULE

TYPE DESCRIPTION MANUFACTURER STYLE COLOR/FINISH SIZE REMARKS CONTACT

LBC RED

LIST FREE

LBC RED LIST

COMPLIANT

EXG-1 EXISTING PLASTER CEILING - - - - EXISTING CEILING TO REMAIN

EXG-3 EXISTING GYPSUM WALLBOARD

CEILING

- - - - EXISTING CEILING TO BE DEMOLISHED, PATCH AND PAINT EXPOSED STRUCTURE TO

MATCH ADJACENT CEILINGS. - SEE DEMOLITION PLANS

EXG-4 EXISTING PLASTER CEILING - - - - EXISTING CEILING TO REMAIN

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

CONTRACTOR TO VERIFY DIMENSIONS, QUANTITIES AND CONDITIONS IN

FIELD AT JOB SITE AND NOTIFY ARCHITECT & ENGINEER OF

DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS PRIOR TO

BEFORE COMMENCING WORK.

INTERIOR DIMENSIONS ARE FROM FACE OF FINISH MATERIAL TO FACE OF

FINISH MATERIAL, UNLESS NOTED OTHERWISE. DIMENSIONS CONNECT

COLUMN LINES, FACE OF FINISH MATERIAL. REFER TO WALL TYPES FOR

THICKNESS OF WALLS.

COORDINATE EQUIPMENT AND DEVICE MOUNTING HEIGHTS TO BE ABOVE

FINISHED FLOOR (AFF) CONDITION REQUIRED BY CODE.

PROVIDE 16 GA. MINIMUM METAL STRAPPING AS IN-WALL BLOCKING TO

SUPPORT CABINETRY, FINISH CARPENTRY AND ANCILLARY COMPONENTS

(INCLUDING BUT NOT LIMITED TO WALL PANELS, MILLWORK, CUSTOM

CASEWORK, GRAPHIC PANELS, BANNERS, ETC.) SHOWN OR INDICATED AS

RIGIDLY ATTACHED TO WALLS OR OTHER STRUCTURAL COMPONENTS.

TYPES OF BLOCKING SOWN IN DETAILS ARE INTENDED FOR GRAPHICAL

ILLUSTRATION ONLY AND FULL SCOPE OF WORK MAY NOT BE INDICATED

FOR EACH TYPE OF REQUIRED BLOCKING.

PROVIDE BLOCKING IN WALL FOR WALL EQUIPMENT, TYPICAL.

REFER TO SPECIFICATION MANUAL SECTIONS 064023 FOR A COMPLETE

ENUMERATION OF PERFORMANCE AND FABRICATION GUIDELINES.

ACCESS PANEL REQUIRED FOR MEP & FP SCOPE OF WORK MAY NOT BE

INDICATED ON THE PLANS COORDINATE AND PROVIDE CEILING ACCESS

PANEL (AP) TYPES AND LOCATIONS REQUIRED WITH THE CEILING

LAYOUT, CEILING TYPES AND MEP & FIRE PROTECTION DRAWINGS AND

SPECIFICATIONS.

PROVIDE “CORNER CABINET” EXTENSION AT INSIDE CORNERS. FILL IN

CORNER DEAD SPACE – MODIFY AUGMENT SHELF SUPPORTS AS

REQUIRED.

PROVIDE ADJUSTABLE SHELVES (UNLESS NOTED OTHERWISE)

SUPPORTED ON NICKEL (SPOON-TYPE) SHELF PINS. RECEIVING HOLES TO

BE SPACED 2” OC

NOT IN CONTRACT (NIC) EQUIPMENT/APPLIANCES SHOWN WITH DOTTED

LINES, AND INDICATED FOR COORDINATION AND REFERENCE ONLY.

VERIFY LOCATIONS IN FIELD WITH OWNER.

CLAD EXPOSED EXTERIOR SURFACES WITH PLASTIC LAMINATE (COLOR

AS NOTED). CLAD EXPOSED INTERIOR SURFACES WITH WHITE MELAMINE.

CLAD HIDDEN OR CONCEALED FACES WITH PLASTIC LAMINATE BACKER.

CLAD DOORS AND ADJUSTABLE SHELVES WITH SAME PLASTIC LAMINATE

AS THE CASE (UNLESS NOTED OTHERWISE).

GENERAL ENLARGED PLAN & INTERIOR ELEVATION NOTES

EQ-9 EQ-9EQ-9

EQ-1EQ-1

EQ-4

TY

P.

1'- 8"

A .F

.F

TY

P.

1'- 8"

A .F

.F

EQ-5

EQ-10 EQ-10EQ-10 EQ-10

A-401

A-401

2'-9" 3'-0" 3'-2" 2'-9" 2'-9" 3'-6"

17'-11"

EQ-3 EQ-3EQ-9 EQ-9

EQ-10

TY

P.

1'- 8"

A .F

.F

09.06

26.0126.01 26.01

EQ-18

A-401

26.01

EQ-13 EQ-13

A-401

Sim

EXISTING MECHANICAL

TY

P.

2'- 9"

1'- 3"

EQ-19

4'- 0"

EQ-19EQ-19

TRASH CAN TO BE PROVIDED BY OWNER

EQ-20

EQ-20

22.01

A-401

EQ-11

EQ-7

EQ-6

A-401

2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 12'-6"

2'-6"2'-6"2'-6"2'-6"2'-6"

12'-6"

A-401

BASE PER SCHEDULE, RB-1

PLAM-1

DOOR PULL TYP. MA-1

WHITE MELAMINE TYP.

SOFT CLOSED CONCEALED EUROPEAN

HINGES TYP.

EUROPEAN SOFT CLOSE HINGES TYP.

EXISTING OPEN SHELVING

4" 2'-

PLAM-2

2'-1"

1'-9" 3"

2'-0"

1/

2"

2'-

1/ 2"

4"

1'-

1/ 4"

2'-

3/ 4"

PLAM-2 BACKSPLASH

VALANCE TO BE ADDED TO EXISTING OPEN

SHELVING. PLASTIC LAMINATE TO MATCH

EXISTING.

UNDERCABINET LED STRIP LIGHT

7'- 0"

EPOXY INTEGRAL WALL BASE. WB-1

1" RADIUS COVE

EPOXY FLOORING, EPX-1

EXISTING CONCRETE FLOOR

6" STONHARD OVERLAYMENT

1. CLAD EXPOSED EXTERIOR SURFACES WITH PLASTIC LAMINATE (COLOR

AS NOTED). CLAD EXPOSED INTERIOR SURFACES WITH WHITE MELAMINE.

CLAD HIDDEN OR CONCEALED FACES WITH PLASTIC LAMINATE BACKER.

CLAD DOORS AND ADJUSTABLE SHELVES WITH SAME PLASTIC LAMINATE

AS THE CASE (UNLESS NOTED OTHERWISE).

GENERAL MILLWORK NOTES

BASE PER SCHEDULE, RB-1

PLAM-1

DOOR PULL TYP. MA-1

EUROPEAN SOFT CLOSE HINGES TYP.

PLAM-2

RELOCATED SINK AND FAUCET, EQ-3

WHITE MELAMINE TYP.

PLAM-2 BACKSPLASH

2'-1"

4" 2'-

1'-9" 3"

2'-0"

1/

2"

2'-

1/ 2"

4" BASE PER SCHEDULE, RB-1

PLAM-1

DOOR PULL TYP. MA-1

EUROPEAN SOFT CLOSE HINGES TYP.

PLAM-2

RELOCATED 2 BURNER COOKTOP, EQ-2

WHITE MELAMINE TYP.

PLAM-2 BACKSPLASH

1'-9" 3"

2'-0"

1/

2"

2'-

1/ 2"

4"

4" 2'-

2'-1"

MIN

1 1/2"

1/

2"

1 1/2" DIAMETER HANDRAIL

HANDRAIL BRACKET

PROVIDE BLOCKING AND

SUITABLE FASTENERS FOR

SUBSTRATE.

WALL

1'-0"

1" PER 12" MAXIMUM RAMP SLOPE

MATCH SLOPE OF RAMP 1'-0"

1 1/2" DIAMETER WALL

MOUNTED HANDRAIL

3'-

0" WALL BRACKETS,

COORDINATE PER

DELEGATED DESIGN

END CAP, TYPICALRETURN TOP END

OF HANDRAIL TO

WALL.

EXISTING DECK TO REMAIN

HANGER ROD FASTENED THROUGH

PLASTER TO METAL DECK

EXISTING PLASTER CEILING TO

REMAIN, PATCH AND PAINT TO MATCH

ADJACENT FINISHES.

STAINLESS STEEL S HOOK

LOCATE HOOK 7'-2" A.F.F.

ALLTHREAD ROD FASTENED THROUGH

PLASTER CEILING INTO SUBSTRATE ABOVE.

THREADED COUPLING WITH EYELET

EQ-12

BASE PER SCHEDULE, RB-1

ADJUSTABLE HEIGHT SHELVES

EXISTING OPEN SHELVING

1'-9" 3" 2'-0"

1/

2" 2'-

1/

2" 4"

2'-

3/ 4"

1'-

1/ 4"

4" 2'-

2'-1"

PLAM-2

PLAM-2 BACKSPLASH

VALANCE TO BE ADDED TO EXISTING OPEN

SHELVING. PLASTIC LAMINTE TO MATCH

EXISTING.

UNDERCABINET LED STRIP LIGHT

PLAM - 1 COVERED BASE CABINET;

COVER EXPOSED BASE CABINET

SURFACES WITH PLASTIC

LAMINATE TYP.

7'- 0"

BASE PER SCHEDULE, RB-1

PLAM-1

DOOR PULL TYP. MA-1

EUROPEAN SOFT CLOSE HINGES

TYP.

PLAM-2

WHITE MELAMINE TYP.

PLAM-2 BACKSPLASH

1'-9" 3"

2'-0"

1/

2"

2'-

1/ 2"

4"

4" 2'-

2'-1"

SOFT CLOSED CONCEALED

EUROPEAN HINGES TYP.

4'-

1/ 4"

HANDRAIL, SEE TYPICAL DETAIL

SOLID SURFACE CAP

3/4" PLYWOOD SUBSTRATE

ALIGN FACE OF

STUD WITH FACE

OF CONCRETE

WALL.

48 SOUTH 14TH STREET

PITTSBURGH, PA 15203

PHONE: 412-431-2480

WWW.R3A.COM

COPYRIGHT R3A

THIS DRAWING IS INTENDED TO BE USED ONLY FOR THE PROJECT AND OWNER

INDICATED IN THIS TITLE BLOCK. USE OF THIS DRAWING FOR ANY OTHER PROJECT, BY

ANY OTHER OWNER THAN THE ONE LISTED ABOVE, IS EXPRESSLY PROHIBITED WITHOUT

PRIOR WRITTEN APPROVAL FROM RENAISSANCE 3 ARCHITECTS

CONSULTANT:

R3A PROJECT #

ISSUED:

c

REVISIONS

A-401 26030

05/15/2026

CONSTRUCTION

DOCUMENTS

ENLARGED

PLANS AND

ELEVATIONS

SLIPPERY ROCK

UNIVERSITY

PATTERSON

HALL FIBER ART

STUDIO

RELOCATION

105 FIELD HOUSE RD

SLIPPERY ROCK, PA

16057

1/4" = 1'-0"1 INTERIOR ELEVATION - FIBER ARTS STUDIO - SOUTH

1/4" = 1'-0"2 INTERIOR ELEVATION - FIBER ARTS STUDIO - NORTH

1 1/2" = 1'-0"8 SECTION - CASEWORK

3" = 1'-0"12 EPOXY INTEGRAL WALL BASE

1 1/2" = 1'-0"4 SECTION - CASEWORK

1 1/2" = 1'-0"5 SECTION - CASEWORK

3" = 1'-0"11 TYPICAL WALL MOUNTED RAILING DETAILS

1/2" = 1'-0"10 TYPICAL WALL MOUNTED HANDRAIL AT RAMP

3" = 1'-0"9 CEILING-MOUNTED S-HOOK DETAIL

1/4" = 1'-0"3 INTERIOR ELEVATION - FIBER ARTS STUDIO - EAST

1 1/2" = 1'-0"7 SECTION - CASEWORK

1 1/2" = 1'-0"6 SECTION - CASEWORK

1 1/2" = 1'-0"13 HALF-HEIGHT WALL SECTION

REFERENCED CONSTRUCTION NOTES

MARK DESCRIPTION

05.01 NEW WALL MOUNTED HANDRAIL, RETURN TO WALL AT ENDS - SEE

DETAIL 8/A-401

06.01 PROVIDE BLOCKING FOR CEILING-MOUNTED PROJECTION SCREEN TO

BE PROVIDED BY OWNER.

07.01 SEAL PENETRATION AT NEW PARTITON TO MATCH EXISTING WALL

RATING

09.01 ALIGN FINISH FACE OF WALL WITH FACE OF RAMP

09.02 ALIGN FINISH FACE OF WALL WITH FINISH FACE OF EXISTING COLUMN

09.03 CEILING HUNG DRYING RACK RELOCATED FROM PREVIOUS SPACE

PROVIDED BY OWNER INSTALLED BY CONTRACTOR.

09.04 PROVIDE HANGER ROD AND SUPPORT FOR S-HOOK FROM DECK, SEE

DETAIL 10/A-401

09.05 PROVIDE HOOKS FOR IRONING BOARDS AND IRONS.

09.06 COMMERCIAL KITCHEN STAINLESS STEEL WALL SHELF FOR POT AND

PAN STORAGE WITH RAIL AND HOOKS.

09.07 3-WIRE HANGING RACK PROVIDED BY OWNER AND INSTALLED BY

CONTRACTOR; CONFIRM FINAL LOCATION WITH OWNER.

22.01 ALTERNATE P-1: COUNTERTOP AND BASE AT SINKS. PROVIDE

ROUGH-INS FOR FUTURE SINKS TO BE PROVIDED BY OWNER -

COORDINATE WITH PLUMBING DRAWINGS.

22.02 FLOOR DRAIN, COORDINATE WITH PLUMBING DRAWINGS

23.01 EXISTING RADIATOR TO REMAIN, COORDINATE FRAMING WITH

RADIATOR

26.01 RELOCATED RACEWAY; COORDINATE OUTLET QUANTITY AND

PLACEMENT WITH ELECTRICAL PLAN

26.02 LOCATION OF LAPTOP CONNECTION FOR PROJECTOR, PROVIDE

PATHWAY AND HOOKUP TO PROJECTOR AND OUTLET IN THIS AREA AT

COUNTER HEIGHT. COORDINATE WITH ELECTRICAL DRAWINGS.

R

AM

P

D N

UP

UP

DN

UP

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

REFER TO REFLECTED CEILING PLAN AND PROJECT MANUAL FOR CEILING

MATERIAL AND FINISH INFORMATION.

RESILIENT BASE (VINYL OR RUBBER) PROVIDE COVE PROFILE AT

EXPOSED CONCRETE (UNLESS OTHERWISE NOTED).

PROVIDE FLOOR TRANSITION STRIPS BETWEEN DISSIMILAR FLOOR FINISH

MATERIALS EXCEPT AT DOORS THAT HAVE SILL PLATES OR THRESHOLDS.

PROVIDE A SMOOTH TRANSITION, TRIP HAZARD IS A REASON FOR

REJECTION OF WORK.

VERTICAL TRANSITIONS BETWEEN DIFFERING WALL FINISHES ARE TO BE

MADE AT INSIDE CORNERS (UNLESS NOTED OTHERWISE).

DRYWALL SOFFITS TO BE PAINTED [PT-2] UNLESS NOTED OTHERWISE ON

CEILING PLANS.

COORDINATE FINISHED FLOOR ELEVATIONS WITH RECESSES OR FLUSH

MOUNTED FLOOR MOUNTED COMPONENTS (RECEPTACLES, ACCESS

PANELS, ETC.) ENSURE INTEGRATED AND FLUSH MOUNTING.

COMPLETELY REMOVE EXISTING FLOOR FINISHES AND ADHESIVES.

EXISTING SUBFLOOR TO BE GROUND, SCARIFIED, ETCHED BEAD, SHOT

OR SAND BLASTING AS NECESSARY TO REMOVE OLD FINISHES AND

ADHESIVES AND TO ACHIEVE SUITABLE SURFACE TO RECEIVE SPECIFIED

FINISH.

EXTEND FLOORING UNDER BENCHES & CASEWORK TO WALLS. PROVIDE

RUBBER BASE AT CASEWORK AND FIXED EQUIPMENT TOE KICKS.

PATCH AND PREPARE WALLS AS REQUIRED TO COMPLETE WORK AND

PROVIDE ONE COAT PRIMER AND TWO COATS OF PAINT TO EXPOSED

WALL AND CEILING SURFACES FROM CORNER TO CORNER (UNLESS

OTHERWISE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .