2-Issued for Bid 250908 U46 SEHS Pool 2024.121.pdf
PDF 6 MB Posted
- Attached to
- SOUTH ELGIN HIGH SCHOOL POOL RENOVATION, NO. 282
- Solicitation number
- 386- 25/26
- Issued by
- Cook County, Illinois
About this file
This is a set of architectural and engineering design drawings for the South Elgin High School Pool Renovation project, commissioned by School District U-46 and located at 760 E Main St., South Elgin, Illinois. The project involves comprehensive renovations to the existing high school swimming pool facility, including replacing starting blocks, installing new aluminum plank seating, updating water coolers with bottle filler functionality, and making various electrical, plumbing, and structural modifications. The architectural plans, dated September 8th, 2025, include detailed floor plans, demolition plans, reflected ceiling plans, and electrical and plumbing layouts, with work focused on modernizing and improving the pool area while maintaining the existing structural integrity.
The renovation scope includes specific upgrades such as replacing floor drains, removing and reinstalling handrails, updating flooring with quartz and epoxy systems, and relocating electrical and plumbing fixtures. The project involves careful coordination across multiple trades, with explicit instructions to protect existing building elements and minimize disruption to the school's operations. Specific technical details include installing new starting blocks provided by the owner, replacing aluminum seating with red plank seating, and updating electrical and plumbing systems to current code standards. The design emphasizes maintaining existing structural elements while introducing modern amenities and improving the overall functionality of the pool area.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3-Zoom Credentials Bid Opening.docx (42).pdf | ||
| 1-Issued for Bid 250908 Spec U46 SEHS Pool 2024.121 (1).pdf | ||
| 4-Legal Ad Template BID.docx | DOCX document | |
| 5-SEHS Pool Renovation No. 282 ITB .docx.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
8' MB
DM
4' TB
AED
FE
FEC
FEC/FB
LICENSED ARCHITECT'S CERTIFICATION OF PLANS AND
SPECIFICATIONS FOR NEW CONSTRUCTION
I hereby certify that these plans and specifications, dated SEPTEMBER 8TH, 2025, for SOUTH ELGIN HIGH SCHOOL POOL
RENOVATIONS, located at 760 E MAIN ST., SOUTH ELGIN, for SCHOOL DISTRICT U-46, were prepared under my supervision using the 23 ILLINOIS ADMINISTRATIVE CODE 180 and the 2015 INTERNATIONAL BUILDING CODE and to the best of my knowledge, comply with the Health/ Life Safety Code as prepared by the State Board of Education.
Architect's Firm:
Architect's Name:
License Number:
License Expiration:
Signature:
DLA Architects, Ltd.
CARRIE MATLOCK
001018535
NOV. 30, 2026
1. VERIFY ALL EXISTING CONDITIONS RELATED TO CONSTRUCTION COMPARED TO THE INFORMATION PROVIDED IN THE CONSTRUCTION DOCUMENTS. IF DISCREPANCIES OR CONFLICTS BETWEEN THE TWO ARE DISCOVERED, NOTIFY THE ARCHITECT FOR CLARIFICATION PRIOR TO SUBMITTING A BID AND/ OR
PERFORMING WORK.
2. COMPLY WITH ALL APPLICABLE STATE AND LOCAL CODES.
3. COORDINATE ALL TRADES PRIOR TO PERFORMING WORK INCLUDING BUT NOT LIMITED TO MECHANICAL, PLUMBING, ELECTRICAL, AND STRUCTURAL.
4. OTHER WORK MAY BE PERFORMED UNDER A SEPARATE CONTRACT. COORDINATE WITH ALL OTHER CONTRACTED TRADES SO AS TO NOT INTERFERE WITH
THEIR WORK.
5. STORE MATERIALS IN A MANNER NOT TO OVERSTRESS, OVERLOAD, OR OTHERWISE PUT AN INAPPROPRIATE LOAD ON ANY STRUCTURE DURING
CONSTRUCTION.
6. SCHEDULE AND COORDINATE ALL SHUT-DOWNS OF EXISTING UTILITIES WITH THE OWNER PRIOR TO SHUT DOWN. PREPARE ALL NECESSARY WORK PRIOR TO
SHUT-DOWNS. IF AT ALL POSSIBLE, COMBINE UTILITY SHUT-DOWNS TO MINIMIZE THE IMPACT OF THE OWNER'S OPERATION OF EXISTING FACILITIES. SEE
SPECIFICATIONS FOR ANY FURTHER DETAILS.
7. LOCATE ALL MATERIALS, EQUIPMENT, TRUCKS, DUMPSTERS, AND CONSTRUCTION FACILITIES IN AREAS APPROVED BY OWNER. SPECIAL CARE SHALL BE TAKEN TO PREVENT DAMAGE TO EXISTING BUILDING STRUCTURE, LANDSCAPING, AND PAVED AREAS. PROVIDE WOOD PLANK PROTECTION BELOW ALL DUMPSTERS AND OTHER HEAVY EQUIPMENT. ALL DAMAGED ITEMS SHALL BE REPAIRED OR REPLACED AT NO EXPENSE TO THE OWNER.
8. PROTECT OR SAFELY STORE ALL BUILDING AND SITE ELEMENTS THAT ARE SCHEDULED TO REMAIN OR BE REUSED TO AVOID DAMAGE DURING THE CONSTRUCTION PROCESS. DAMAGED ITEMS SHALL BE REPAIRED OR REPLACED AT NO EXPENSE TO THE OWNER.
9. REPAIR ALL AREAS DAMAGED FROM THE CONSTRUCTION WORK. PATCH AND/OR PROVIDE NEW FINISHES AT ALL DAMAGED AREAS WITH MATERIALS AND FINISHES TO MATCH THE EXISTING CONDITIONS. NEW MATERIALS AND FINISHES SHALL BE BROUGHT TO A STOPPING POINT TO MINIMIZE DETECTION OF
REPAIR, VERIFY LOCATIONS WITH ARCHITECT.
10. ALL WORK OUTLINED IN THE PROJECT SCOPE THAT EXTENDS INTO AREAS LABELED "NIC" SHALL BE INCLUDED IN THE CONTRACTOR'S SCOPE OF WORK TO
INSURE A COMPLETE AND FULLY OPERATIONAL SYSTEM.
11. TAKE SPECIAL CARE NOT TO DAMAGE OR INTERRUPT THE EXISTING SERVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL WIRING, PNEUMATIC CONTROL LINES, SOUND SYSTEM WIRING, FIRE ALARM WIRING, COMPUTER/NETWORK CABLING, AND TEMPERATURE CONTROLS. THESE ITEMS AND THE LIKE ARE FULLY OPERATIONAL. VERIFY THE CONDITION AND OPERATION OF EACH SYSTEM BEFORE, DURING, AND AFTER CONSTRUCTION. SYSTEMS DAMAGED DURING CONSTRUCTION SHALL BE PLACED BACK INTO SERVICE PROMPTLY AND AT NO ADDITIONAL COST TO THE OWNER. REFER TO THE MEP DRAWINGS FOR
FURTHER INFORMATION.
12. COORDINATE THE SIZE AND LOCATION OF ALL NEW DUCT OPENINGS AND PENETRATIONS IN WALLS AND FLOORS WITH MECHANICAL, PLUMBING, AND ELECTRICAL TRADES PRIOR TO PERFORMING WORK. PROVIDE ALL REQUIRED LINTELS FOR THESE OPENINGS ALONG WITH FIRESTOPPING AS REQUIRED BY
THE FIRE RATING OF THE WALL.
13. DO NOT SCALE THE DRAWINGS TO DETERMINE A DIMENSION.
14. ALL PLAN DIMENSIONS ARE SHOWN AND INDICATED WITH A NOMINAL WIDTH.
15. INTERIOR DIMENSIONS ARE FROM FINISH TO FINISH UNLESS SPECIFICALLY NOTED OTHERWISE. EXTERIOR DIMENSIONS ARE TO OUTSIDE FACE OF STUD OR
MASONRY UNLESS NOTED OTHERWISE.
16. DETAILS ARE TYPICAL AND ARE NOT TO BE CONSTRUED AS LIMITED TO THOSE AREAS SPECIFICALLY INDICATED. IF IN QUESTION, VERIFY APPLICATION WITH
ARCHITECT PRIOR TO SUBMITTING A BID AND/ OR PERFORMING WORK.
GENERAL NOTES
ROOM IDENTIFICATION TAG
DOOR IDENTIFICATION TAG
ELEVATION TAG
ROOM NAME
ROOM NUMBER
DOOR LOCATION
DOOR NUMBER
DRAWING NUMBER
SHEET NUMBER
TAG NOTE
DRAWING NUMBER
SHEET NUMBER
TAG NOTE
DRAWING NUMBER
SHEET NUMBER
101-1
SECTION TAG
DETAIL TAG
MATCH LINE
AREA B
AREA A
NOTE: ARROW FILL
REMOVED WHEN
USING THE BUILDING
SECTION TAG
A101
SIM
A101
SIM
ROOM
X
SIM
AX.X
SYMBOLS LEGEND
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
ALUM ALUMINUM
APPROX APPROXIMATE
AV AUDIO/VISUAL
B/ BOTTOM OF
BD BOARD
CJ CONTROL JOINT
CMU CONCRETE MASONRY UNIT
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
DS DOWNSPOUT
DWG(S) DRAWING(S)
EJ EXPANSION JOINT
ELEC ELECTRICAL
EQ EQUALLY SPACED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EXT EXTERIOR
FBO FURNISHED BY OTHERS
FD FLOOR DRAIN
FRTW FIRE RETARDANT TREATED WOOD
FP FIRE PROTECTION
GA GAGE, GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GYP GYPSUM
HM HOLLOW METAL
INT INTERIOR
INFO INFORMATION
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL,
PLUMBING
MFR MANUFACTURE(R)
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
OC ON CENTER
OD OUTSIDE DIAMETER
OPP OPPOSITE
OZ OUNCE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
ABBREVIATIONS
QT QUARRY TILE
RCP REFLECTED CEILING PLAN
REQ'D REQUIRED
RTB RESILENT TACKBOARD
SCH SCHEDULE
SFRM SPRAY-APPLIED FIRE-
RESISTIVE MATERIALS
SIM SIMILAR
SOG SLAB ON GRADE
SPECS SPECIFICATIONS
STRUCT STRUCTURAL
T/ TOP OF
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
WP WORK POINT
W/ WITH
DEMOLITION KEYNOTE
ELEVATION KEYNOTE
DATUM TAG
WALL TYPE TAG
WALL FIRE RATING TAG
ELEVATION HEIGHT
XX
PROJECTOR UNIT -
SEE ELEC
MARKERBOARD
DISPLAY MONITOR
TACKBOARD
101 FLOOR PLAN KEYNOTE
PROJECTION SCREEN
1hr
PU
FIRE EXTINGUISHER
RECESSED FIRE
EXTINGUISHER CABINET
W/ FIRE EXTINGUISHER
AUTOMATIC EXTERNAL
DEFIBRILLATOR
RECESSED FIRE
EXTINGUISHER CABINET
W/ FIRE EXTINGUISHER
& FIRE BLANKET
COMBINATION UNIT
HANDICAP ACCESSIBLE
CEILING HEIGHT AND
TYPE TAG
BORROWED LIGHT TAG
AREA OF REFUGE
REVISION CLOUD
9'-0"
XXX-X
PS
BL-###
FINISH TAG
NORTH ARROW
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
ISSUED FOR BID
SCHOOL DISTRICT U-46
SOUTH ELGIN HIGH SCHOOL
SOUTH ELGIN HIGH SCHOOL POOL RENOVATION
760 E MAIN ST., SOUTH ELGIN, IL 60177
G0.1
SEPTEMBER 08, 2025
2024.121
TITLE SHEET
IS
S U E D F
O R B
ID
INDEX OF DRAWINGS
G0.1 TITLE SHEET
ARCHITECTURAL - DLA ARCHITECTS, LTD 847.742.4063
AM.1 FIRST FLOOR MASTER PLAN
AD1.1 FIRST FLOOR DEMOLITION PLAN
A1.1 FIRST FLOOR PLAN
A7.1 ENLARGED FLOOR PLANS, INTERIOR ELEVATIONS, & DETAILS
A8.1 FIRST FLOOR REFLECTED CEILING PLAN
P1.1 FIRST FLOOR POOL PLUMBING PLAN
E1.1 FIRST FLOOR POOL ELECTRICAL PLAN
OVEN
OVEN
OVEN
OVEN
DF
DF
DF
DF DF DF
DF
DF
DF DF
DF
DF DF
DF
DF
DF
DF
DF
DF DF DF DF
DF
DF
DF
DF
DF
DF
UP
UP UP
UP
UP
UP
UP
UP
UP
UP
UP
SR
S R
SR
FB +
SR
S R
S R
SR
SRSRSR
S R
S R
SR SR
S R
S R
S R
S R
DF DF
SR
S R
S R
SR
S R
SR
S R
SR
S R
S R
S R
FB +
F
B
FB +
FB +
+ FB
F
B
FB +
F
B
FB +
F
B
F
B
FEC
FE
F E
C
FE
FEC
FEC
F E
C
F E
C
FEC
FECFBFEC FE
FE
F E
C
FEC
FE
F E
C
FEC FECAED
R F
E C
F E
C
F E
C
FE
F E
C
F E
C
FEC
F E
C
FE
F E
C
R F
E C
FEC
FE
F E
C
FEC
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
FEC
FE
FE
AED
FEC
FEC
FEC
F E
C
FEC
F E
C
FEC
F E
C
FEC
FEC
FEC
FE
F E
C
FEC
F E
C
FEC
FEC
F E
C
FEC
F E
C
A E
D
FEC
F E
C
FEC
FEC
FEC
F E
C
FEC
F E
C
FEC
FEC
FEC
FE
FEC
X
X
X X
F E
C
FE
FEC
FEC FEC
FEC
F E
C
F E
C
FE
S ta rt in g P la tf o rm
S ta rt in g P la tf o rm
S ta rt in g P la tf o rm
S ta rt in g P la tf o rm
8 7 6
14 15 16 18 1917
4 3
25 26
MASTER PLAN LEGEND
APPROXIMATE AREA OF REMODELING - SEE FULL SET OF
ARCHITECTURAL AND PLUMBING DRAWINGS FOR FULL EXTENT OF WORK
XX EXTERIOR DOOR NUMBERS
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
AM.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR
MASTER PLAN
IS
S U E D F
O R B
ID
1/32" = 1'-0"
FIRST FLOOR MASTER PLAN
DF DF DF DF
DF
UP
S R
S R
R F
E C
F E
C
F E
C
FE
GIRLS
LOCKER
G129
CORRIDOR
C-1
JANITOR
G131
LOCKERS/SHOWER
G127B
POOL OFFICE
G127A
LAUNDRY
G133
TOILET RM
G127C
CORRIDOR
C-2
BOYS LOCKER
G135
ATHLETIC
EQUIPMENT
G137
STORAGE
G127D
POOL FILTER
G127B
POOL
G127
D03D03
D01
D02
D02
D01
D03D03
D04
D10
D06
D06
D02
D02
D02
D02
D04D04
D04D04
D04 D04
D04
D04
D04 D04
D04
D11 D11
D05
D09
D07
D07
D07
D12
D12
D08
D08
D08
D08
D05
D05
D05
D08
D08
D08
D05
NO WORK AT POOL
GENERAL DEMOLITION PLAN NOTES
DEMOLITION PLAN LEGEND
EXISTING WALLS AND PARTITIONS TO REMAIN
EXISTING WALLS AND PARTITIONS TO BE REMOVED
EXISTING DOORS AND FRAMES TO REMAIN
EXISTING DOORS AND FRAMES TO BE REMOVED
1. SEE G SHEETS FOR GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.
2. FIELD VERIFY AND COORDINATE EXACT LOCATIONS AND EXTENT OF WALL, FLOOR
AND CEILING DEMOLITION AND PATCHING REQUIRED TO COMPLETE NEW WORK.
COORDINATE EXTENT OF DEMOLITION WORK REQUIRED WITH STRUCTURAL,
CIVIL, MEP AND FIRE PROTECTION DRAWINGS.
3. PROTECT FLOORS, WALLS, AND CEILINGS TO AVOID DAMAGE THROUGHOUT
CONSTRUCTION.
4. REMOVE ALL EXISTING MISCELLANEOUS WALL MOUNTED ITEMS (E.G. SHELVES,
MIRRORS, VISUAL DISPLAY BOARDS, ETC.) AND ASSOCIATED ANCHORS AND/OR
FASTENERS WHETHER OR NOT INDICATED ON THE PLANS AS REQUIRED TO
ACCOMMODATE NEW WORK. TURN OVER ITEMS TO OWNER. DISPOSE OF ANY
ITEMS NOT WANTED BY THE OWNER.
5. WHERE REQUIRED FOR PATCHING, NEW MASONRY TO BE TOOTHED IN TO MATCH
EXISTING ADJACENT MATERIALS AND COURSING.
6. PATCH FLOORS SMOOTH WHERE WALLS, CONCRETE PADS, OR OTHER FLOOR
MOUNTED ITEMS HAVE BEEN REMOVED. GRIND CONCRETE SUBFLOOR AND/OR
PROVIDE SELF-LEVELING UNDERLAYMENT AS REQUIRED TO MATCH ADJACENT
FLOOR ELEVATIONS. SEE SPECIFICATIONS.
7. ALL ITEMS INDICATED TO BE SALVAGED FOR REINSTALLATION SHALL BE STORED
ON-SITE IN A LOCATION DESIGNATED BY OWNER.
NOTE: DEMOLITION PLANS, LEGEND AND NOTES ARE COMPLIMENTARY TO EACH
OTHER. ALL DASHED ITEMS ARE TO BE REMOVED EVEN IF DEMOLITION KEYNOTE IS
NOT PRESENT.
AREA OF WORK
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
AD1.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR
DEMOLITION PLAN
IS
S U E D F
O R B
ID
1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN
DEMOLITION PLAN KEYNOTES
D01 EXISTING GUTTER RETURN DUCT AND FACEPLATE TO REMAIN.
D02 REMOVE AND DISPOSE OF EXISTING STARTER BLOCKS FOR INSTALLATION
OF NEW ONES PURCHASED BY OWNER.
D03 EXISTING MOSAIC FLOOR TILE TO BE CLEANED AND PREPPED TO RECEIVE
NEW QUARTZ FLOORING. CONTRACTOR TO DIAMOND GRIND TILE FOR
ADHESION, PATCH IMPERFECTIONS AND TRANSITION TILE WITH CEMLACK
TM MORTAR, AND INSTALL ADDITIONAL PRIMER COAT OF RESUFLOR EOC @
3O MILS, 50 SF PER GALLON
D04 EXISTING FLOOR DRAIN COVER AND THROAT TO BE REMOVED AND
REPLACED
D05 TYPICAL AT ENTIRE PERMIETER. REMOVE 4"-6" OUT OF CERAMIC TILE FOR
FLUSH INSTALLATION OF NEW QUARTZ FLOORING SYSTEM
D06 EXISTING DIVING BOARD TO REMAIN
D07 EXISTING 2" X 2" CERAMIC TILE COVE BASE TO REMAIN AT ENTIRE
PERIMETER OF SWIMMING POOL EXCEPT FOR BUILT IN CONCRETE STEPS
AND RISERS.
D08 REMOVE EXISTING 2" X 2" CERAMIC TILE COVE BASE AND GRIND CONCRETE
SMOOTH AND PATCH AS REQUIRED FOR INSTALLATION OF NEW EPOXY
FLOORING SYSTEM TO RECEIVE NEW EPOXY FLOOR AT CONCRETE STEPS
AND RISERS.
D09 DISCONNECT AND REMOVE EXISTING WATER COOLER. REMOVE
ASSOCIATED SANITARY WASTE, VENT AND COLD WATER PIPING TO POINT
OF RECONNECTION WITH NEW.
D10 CAREFULLY REMOVE AND DISCARD OF EXISTING STAINLESS STEEL
BORROWED LITE
D11 EXISTING CONCRETE RISERS TO REMAIN. REMOVE ONLY EXISTING
ALUMINUM SEATING AND BRACKETS ANCHORED INTO IT
D12 EXISTING HANDRAILS TO BE REMOVED AND REPLACED WITH NEW
NOT TO SCALE
KEY PLAN
REFER TO NOTE D08
REFER TO NOTE D12
PHOTO OF EXISTING CONCRETE STEPS & BLEACHER SEATING
REFER TO NOTE D11
DF
DF DF DF DF
DF
UP
S R
S R
R F
E C
F E
C
F E
C
FE
GENERAL FLOOR PLAN NOTES
1. SEE G SHEETS FOR GENERAL NOTES, SYMBOLS, ABBREVIATIONS, TYPICAL
MARKERBOARD AND TACKBOARD INSTALLATION HEIGHTS AND MOUNTING
HEIGHTS OF BUILDING ELEMENTS AND EQUIPMENT CODE REFERENCE PLANS
AND FIRE RATED ASSEMBLY LOCATIONS.
2. ALL HINGE SIDE DOOR RETURNS TO BE 4" UNLESS NOTED OTHERWISE.
3. PATCH ALL AREAS DISTURBED BY CONSTRUCTION WHETHER OR NOT INDICATED
ON PLANS. PATCH OR PROVIDE NEW MATERIALS TO MATCH EXISTING ADJACENT
CONDITIONS. NEW MATERIALS AND FINISHES SHALL BE BROUGHT TO A
STOPPING POINT TO MINIMIZE DETECTION OF REPAIR.
4. PATCH ALL HOLES WHERE ITEMS HAVE BEEN REMOVED FROM WALLS. INFILL ALL
FORMER OPENINGS AFTER REMOVAL OF EXISTING DUCTS, PIPING, CONDUIT, ETC.
TO MATCH EXISTING ADJACENT CONSTRUCTION.
5. ALL ROOM NAMES AND NUMBERS INDICATED ON THE DRAWINGS ARE FOR
REFERENCE ONLY. VERIFY WITH ARCHITECT THE FINAL NAMES AND NUMBERS
TO BE USED FOR THE PROGRAMMING OF THE FIRE ALARM SYSTEM, BUILDING
AUTOMATION SYTEMS, TECHNOLOGY SYSTEMS, ETC.
6. CONTRACTOR RESPONSIBLE FOR PROTECTION OF ADJACENT SPACES FROM
CONSTRUCTION DUST & DEBRIS. CONTRACTOR TO TAKE CARE TO SECURE AND
PROTECT SPACES FOR DUST & DEBRIS WHILE DOORS ARE BEING REPLACED.
/2
100'-4 1/2"
A7.1
A7.1
G D
-1
G129-1
G135-1
G127A-1
GIRLS
LOCKER
G129
CORRIDOR
C-1
JANITOR
G131
LOCKERS/SHOWER
G127B
POOL OFFICE
G127A
LAUNDRY
G133
TOILET RM
G127C
CORRIDOR
C-2
BOYS LOCKER
G135
ATHLETIC
EQUIPMENT
G137
STORAGE
G127D
POOL FILTER
G127B
POOL
G127
A .1
A .1
B L -1
22'-1 1/2"
V.I.F.
+/- 78'-10"
NO WORK AT POOL
EL.: 0'-0" AT POOL GUTTER
EL.: 0'-0" AT
PERIMETER WALL
EL.: 0'-0" AT
PERIMETER
WALL
EL.: 0'-0"
AT POOL
GUTTER
DECK
SLOPE:
1.1"/10'
DECK SLOPE:
1.1"/10'
DECK SLOPE:
1.1"/10'
DECK
SLOPE:
1.1"/10'
EL.: 0'-0" AT
POOL GUTTER
EL.: 0'-0" AT
PERIMETER WALL
EL.: 0'-0" AT
PERIMETER WALL
EL.: 0'-0" AT POOL
GUTTER
G -2
DECK SLOPE:
1.1"/10'
DECK
SLOPE:
1.1"/10'
DECK
SLOPE:
1.1"/10'
108108
A1.1
22'-2" 22'-2"
G -4
25'-0" 25'-0"
12FT 6IN14FT 6IN8FT 11IN5FT 0IN4FT 0IN
N O
D
IV
IN
G
N O
D
IV
IN
G
F
T
IN
12FT-6IN14FT-6IN8FT-11IN5FT 0IN4FT 0IN
F
T
IN
F
T
IN
F
T
IN
AREA OF WORK
TYPE F3TYPE F1
2" 2"
SEE SCH SEE SCHEDULE
2" 2"
S E
E S
C H
E D
U L E
S E
E S
C H
E D
U L E
TYPE F2
SEE SCHEDULE
2" 2"
S E
E S
C H
E D
U L E
2"2"
EQEQ
"2
SCHEDULE
SEE
S E
E S
C H
E D
U L E
8" 8"
TYPE B
SCHEDULE
SEE
S E
E S
C H
E D
U L E
TYPE A
1. ALL DOORS TO BE 1 3/4" THICK UNLESS NOTED OTHERWISE.
2. ALL GLASS IN EXTERIOR AND INTERIOR VESTIBULE DOORS AND FRAMES TO BE 1"
THICK INSULATED TEMPERED GLASS UNLESS NOTED OTHERWISE.
3. UNLESS NOTED OTHERWISE, ALL GLASS IN INTERIOR NON-FIRE-RATED DOORS
AND FRAMES TO BE TEMPERED GLASS.
4. ALL GLASS IN INTERIOR RATED DOORS AND FRAMES TO BE UL FIRE-RATED GLASS
UNLESS NOTED OTHERWISE.
5. INSTALL GLAZING STOPS ON THE SECURE SIDE OF FRAME.
6. REFER TO SPECIFICATIONS FOR HARDWARE SETS.
TYPICAL MOUNTING HEIGHTS FOR DOOR HARDWARE
1. MORTISE OR CYLINDRICAL LOCKSETS: 38” FROM FINISH FLOOR TO CENTER OF
LEVER HANDLE.
2. PANIC EXIT DEVICE: 40” FROM FINISH FLOOR TO CENTER OF PUSH PAD.
3. DOOR PULL HANDLE: 42” FROM FINISH FLOOR TO CENTER OF PULL HANDLE.
4. DEADBOLT LOCK: 44” FROM FINISH FLOOR TO CENTER OF DEADBOLT.
5. PUSH PLATE: 44” FROM FINISH FLOOR TO CENTER OF PLATE.
6. PUSH BAR: 44” FINISH FLOOR TO CENTER OF BAR.
GENERAL DOOR & FRAME NOTES
TYPE BLF-1
SEE SCHEDULE
2" 2"2" 2" 2"
S E
E S
C H 2
S E
E S
C H
EQ EQ EQ EQ
SEE DOOR SCHEDULE
FOR DOOR TYPE
NEW ALUMINUM FRAME.
EXISTING STRUCTURAL
LINTEL TO REMAIN
EXISTING CMU WALL
CONSTRUCTION TO REMAIN
SEE PLAN
NEW ALUMINUM FRAME
SEE DOOR SCHEDULE FOR
DOOR TYPE
EXISTING CMU WALL
CONSTRUCTION TO REMAIN
ALUMINUM FRAMED SYSTEM -
SEE SPECS
CONT. SEALANT AND BACKER
ROD - TYP BOTH SIDES.
EXISTING CMU WALL
CONSTRUCTION TO REMAIN
SEALANT AND BACKER
ROD AT ENTIRE
PERIMETER OF FRAME -
TYP BOTH SIDES
ALUMINUM FRAMED
SYSTEM - SEE SPECS
SEE PLAN
EXISTING STRUCTURAL
LINTEL TO REMAIN
EXISTING CMU WALL
CONSTRUCTION TO REMAIN
6"
ALUMINUM PLANK SEAT.
COLOR: RED
METAL BRACKET ANCHORED
INTO EXISTING CMU WALL
FLOOR FINISH PLAN LEGEND
QUARTZ FLOORING - GREY
QUARTZ FLOORING - BLUE ACCENT
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
A1.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR PLAN
IS
S U E D F
O R B
ID
1/8" = 1'-0"
FIRST FLOOR PLAN
NOT TO SCALE
KEY PLAN
1/4" = 1'-0"
FRAME TYPES
1/4" = 1'-0"
DOOR TYPES
DOOR & FRAME SCHEDULE
DOOR #
FIRE
RATING
(HR)
DOOR FRAME DETAILS
REMARKSTYPE PANEL MTRL WIDTH HEIGHT TYPE MTRL WIDTH HEIGHT DEPTH HEAD JAMB SILL
A PAIR FRP/ALUM HYBRID 3' - 1" 7' - 2" F3 ALUM 0' - 0" 0' - 0" 5 3/4" 2/A1.1 3/A1.1
G127-2 A PAIR FRP/ALUM HYBRID 3' - 1" 7' - 2" F3 ALUM 6' - 8" 7' - 4" 5 3/4" 2/A1.1 3/A1.1
G127-4 B SGL FRP/ALUM HYBRID 3' - 0" 7' - 0" F3 ALUM 7' - 8" 7' - 2" 5 3/4" 2/A1.1 3/A1.1
G127A-1 B SGL FRP/ALUM HYBRID 3' - 0" 7' - 2" F1 ALUM 3' - 4" 7' - 4" 5 3/4" 2/A1.1 3/A1.1
G127D-1 A PAIR FRP/ALUM HYBRID 3' - 0" 7' - 0" F2 ALUM 6' - 4" 7' - 2" 5 3/4" 2/A1.1 3/A1.1
G129-1 A SGL FRP/ALUM HYBRID 3' - 0" 7' - 2" F1 ALUM 3' - 4" 7' - 4" 5 3/4" 2/A1.1 3/A1.1
G135-1 A SGL FRP/ALUM HYBRID 3' - 0" 7' - 2" F1 ALUM 3' - 4" 7' - 4" 5 3/4" 2/A1.1 3/A1.1
BORROWED LIGHT SCHEDULE
BL #
FRAME DETAILS
REMARKSTYPE MTRL WIDTH HEIGHT DEPTH
SILL
HEIGHT HEAD JAMB SILL
BL-1 BLF1 ALUM 12' - 8" 4' - 0" 0' - 5 3/4" 3' - 4" 4/A1.1 5/A1.1
1/4" = 1'-0"
BORROWED LIGHTS
1 1/2" = 1'-0"
HEAD DETAIL
1 1/2" = 1'-0"
JAMB DETAIL
1 1/2" = 1'-0"
JAMB DETAIL
1 1/2" = 1'-0"
HEAD DETAIL
7' - 2"
7' - 2"
6' - 6"
3' - 0"
1 1/2" = 1'-0"
DETAIL
FLOOR PLAN KEYNOTES
101 EXISTING METAL EDGE PLATE AT POOL PERIMETER TO REMAIN. PROTECT
AS REQUIRED
104 NEW WALL MOUNTED BENCH SEATING. NO BACKS.
105 REPLACE ALUMINUM SEATING WITH NEW ALUMINUM PLANK SEATING
MOUNTED TO CONCRETE RISERS. ALTERNATE # 01: PROVIDE PLASTIC
PLANK SEATING MOUNTED TO CONCRETE RISERS.
106 REPLACE EXISTING HANDRAIL WITH NEW 1 1/2" O.D. ALUMINUM HANDRAIL IN
THE SAME CONFIGURATION AS EXISTING.
107 FURNISH AND INSTALL NEW SCHLUTER TRIM PIECE AT EDGE BETWEEN
EXISTING FLOORING AND NEW QUARTZ FLOOR. SEE SPECS.
108 EXISTING DRAIN TO BE REPLACED WITH NEW COVER AND THROAT.
111 FURNISH AND INSTALL NEW WATER COOLER/BOTTLE FILLER WITH NEW
MOUNTING/HANGER BRACKETS AND HARDWARE. EXTEND AND CONNECT
EXISTING SANITARY WASTE, VENT AND COLD WATER PIPING TO NEW
WATER COOLER. SAWCUT WALL AND MODIFY EXISTING PIPING AS
REQUIRED FOR CONNECTIONS TO NEW WATER COOLER/BOTTLE FILLER.
PATCH AND PAINT TO MATCH EXISTING.
3' - 0" 7' - 2"
REMOVABLE MULLION
7' - 2"
7' - 2"
7' - 2"
7' - 4"
7' - 4"
7' - 4"
7' - 4"
7' - 4"F2
1. SEE G SHEETS FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS AND
TYPICAL MOUNTING HEIGHTS OF PLUMBING FIXTURES AND TOILET ACCESSORIES.
2. ALL EXPOSED STRUCTURE CEILINGS INCLUDING CONDUITS SHALL BE PAINTED
PT-1, UNLESS NOTED OTHERWISE. EXPOSED DUCTWORK IN EXPOSED CEILING
SPACE REMAINS UNPAINTED.
GENERAL NOTES
PT-2
PT-3
PT-1
PAINT UNDERSIDE OF EXISTING PRECAST ROOF
DECK PANELS. ANY AND ALL ASSOCIATED
PIPING, CONDUIT, ETC. SEE SPECS
COORDINATE PAINTING OF NEW POOL
DEPTHS INDICATORS.
NEW PAINTED SCHOOL GRAPHICS. FILE
PROVIDED BY ARCHITECT
NEW PAINTED SCHOOL SLOGAN SIGN, GRAPHIC
EMBLEM, GRAPHIC FILE PROVIDED BY
ARCHITECT
NEW 'OASIS' BOTTLE FILLER DRINKING
FOUNTAIN
NEW FIXED BENCH SEATING. ANCHORED TO
WALL.
31'-7 1/2" 18'-11" 12'-9 1/2" 2'-10" 12'-0 1/2"2'-9"
4 0FT IN 5 0FT IN 8 11FT IN 12 6FT IN14 6FT IN
EXISTING RAILING TO BE REPLACED WITH NEW
PAINT UNDERSIDE OF EXISTING PRECAST ROOF DECK
PANELS. ANY AND ALL ASSOCIATED PIPING, CONDUIT,
ETC. SEE SPECS
QUARTZ FLOORING OVER EXISTING CONCRETE RISERS
BLEACHER SEATS ANCHORED TO CONCRETE STEPS
TO BE REPLACED
PT-3
PT-1
COORDINATE PAINTING OF NEW POOL DEPTHS
INDICATORS.
EXISTING DUCTWORK TO REMAIN UNPAINTED. PROTECT
AS REQUIRED DURING WORK.
EXISTING WALL PADDING TO BE PROTECTED FROM
DUST & DEBRIS IN PLACE BY CONTRACTOR.
12 6FT IN 14 6FT IN 8 11FT IN 5 0FT IN 4 0FT IN
PAINT UNDERSIDE OF EXISTING PRECAST ROOF DECK
PANELS. ANY AND ALL ASSOCIATED PIPING, CONDUIT,
ETC. SEE SPECS
EXISTING SCORE BOARD TO REMAIN. PROTECT AS
REQUIRED.
EXISTING DIVING BOARDS TO REMAIN
PT-2
PT-3
PT-1
COORDINATE PAINTING OF NEW POOL DEPTHS
INDICATORS.
EXISTING DUCTWORK TO REMAIN UNPAINTED. PROTECT
AS REQUIRED DURING WORK.
LOCATION FOR CONFERENCE FLAGS
NEW PAINTED LANE NUMBERS. FILE PROVIDED BY
ARCHITECT. COORDINATE FINAL LOCATION ARCHITECT
17'-4" 16'-10"
STARTING BLOCKS PROVIDED BY THE OWNER, TO BE
INSTALLED BY CONTRACTOR. TO BE CENTERED ON
EXISTING LANE LINES - CONTRACTOR TO VERIFY.
STARTING BLOCKS TO BE GROUNDED AND BONDED.
DASHED LINES REPRESENT INSTALLATION REFERENCE
POINT. CENTER LINE OF THE BOX SURROUNDING
NUMBER SHOULD BE ALIGNED TO CENTER LINE OF
STARTING BLOCK
13 0FT IN 13 0FT IN13 0FT IN
EXISTING WALL PADDING TO BE PROTECTED FROM
DUST & DEBRIS IN PLACE BY CONTRACTOR.
PAINT UNDERSIDE OF EXISTING PRECAST ROOF
DECK PANELS. ANY AND ALL ASSOCIATED PIPING,
CONDUIT, ETC. SEE SPECS
EXISTING DUCTWORK TO REMAIN UNPAINTED.
PROTECT AS REQUIRED DURING WORK.
PT-3
PT-1
COORDINATE PAINTING OF NEW POOL DEPTHS
INDICATORS.
EXISTING WALL REGISTERS TO REMAIN.
NEW DRINKING FOUNTAINS WITH BOTTLE FILLER
FUNCTION
M A
X
M
IN
M
IN
4 0FT IN 4 0FT IN
FLOOR FINISH PLAN LEGEND
PT-1 SHERWIN WILLIAMS FIELD COLOR
PT-2 SHERWIN WILLIAMS ACCENT COLOR
PT-3 SHERWIN WILLIAMS ACCENT COLOR
XX-XX FINISH TAG
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
A7.1
SEPTEMBER 08, 2025
2024.121
ENLARGED FLOOR
PLANS, INTERIOR
ELEVATIONS, &
DETAILS
IS
S U E D F
O R B
ID
1/8" = 1'-0"
INTERIOR ELEVATION
1/8" = 1'-0"
INTERIOR ELEVATION
1/8" = 1'-0"
INTERIOR ELEVATION
1/8" = 1'-0"
INTERIOR ELEVATION
1/2" = 1'-0"
STARTING PLATFORM DETAIL
POOL WALL TO CENTER : 2'- 0"
DISTANCE BETWEEN POSTS 20"
DIAMETER OF POSTS 2"
EXISTING ANCHOR MEASUREMENTS
CEILING HEIGHT IDENTIFICATION TAG
1. SEE G SHEETS FOR GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.
2. COORDINATE LOCATIONS OF SHOWN SUPPLY DIFFUSERS, RETURN GRILLES,
LIGHT FIXTURES AND ALL OTHER ELECTRICAL/ TECHNOLOGY DEVICES.
3. LOCATE ALL SPRINKLER HEADS IN THE CENTER OF CEILING TILES.
4. PROVIDE CONTROL JOINTS 20'-0" TO 25'-0" OC IN ALL GYP BD CEILINGS AND
SOFFITS. COORDINATE LOCATIONS WITH ARCHITECT IN FIELD, UNO.
5. ALL EXPOSED CEILINGS TO BE PAINTED (PT-XX), UNLESS NOTED OTHERWISE.
PAINT ALL STRUCTURE, DECKING, CONDUIT, DUCTWORK, AND ALL OTHER
ASSOCIATED CONSTRUCTION (PT-XX), UNLESS NOTED OTHERWISE. COORDINATE
WITH OWNER AND ARCHITECT FOR ANY ITEMS THAT SHALL NOT BE PAINTED.
6. PATCH/REPAINT EXISTING CEILING SYSTEMS AS REQUIRED TO ACCOMODATE NEW
CONSTRUCTION WHETHER OR NOT INDICATED ON PLANS.
7. PROVIDE FLOOR PROTECTION FOR ANY CONSTRUCTION RELATED ACTIVITIES
INCLUDING SCAFOLDING OR LIFTS FOR PAINTING OVERHEAD.
GENERAL REFLECTED CEILING PLAN NOTES
REFLECTED CEILING PLAN LEGEND
9'-0"
EXISTING SUSPENDED LIGHT FIXTURE TO REMAIN
PAINT FINISH IDENTIFICATION TAGPT-1
CEILING FINISH LEGEND
PAINT
WHITE (FIELD)
PT-1
GIRLS
LOCKER
G129
CORRIDOR
C-1
JANITOR
G131
LOCKERS/SHOWER
G127B
POOL OFFICE
G127A
LAUNDRY
G133
TOILET RM
G127C
BOYS LOCKER
G135
ATHLETIC
EQUIPMENT
G137
STORAGE
G127D
POOL FILTER
G131
POOL
G127
804804
PT-1
AREA OF WORK
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
S C
H O
O L
D
IS
T R
IC
T
U -4
S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L S
O U
T H
E L
G
IN
H
IG
H S
C H
O O
L P
O O
L R
E N
O V
A T
IO
N
E M
A
IN
S T
S
O U
T H
E L
G
IN
IL
A8.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR
REFLECTED
CEILING PLAN
IS
S U E D F
O R B
ID
REFLECTED CEILING PLAN KEYNOTES
802 PAINT THE UNDERSIDE OF EXISTING EXPOSED CONCRETE DOUBLE TEE
CONSTRUCTION AND STRUCTURE. ANY AND ALL ASSOCIATED PIPING,
CONDUIT, ETC. SEE SPECS.
803 EXISTING ACOUSTICAL PANELS ON INSIDE FACE OF DOUBLE TEE PRECAST
ROOF DECK TO BE PROTECTED FROM DUST AND DEBRIS PRIOR TO
PAINTING.
804 EXISTING SUSPENDED LIGHT FIXTURES TO REMAIN. PROTECT AS REQUIRED
DURING PAINTING WORK
1/8" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN
NOT TO SCALE
KEY PLAN
GIRLS
LOCKER
G129
CORRIDOR
C-1
JANITOR
G131
LOCKERS/SHOWER
G127B
POOL OFFICE
G127A
LAUNDRY
G133
TOILET RM
G127C
CORRIDOR
C-2
BOYS LOCKER
G135
ATHLETIC
EQUIPMENT
G137
STORAGE
G127D
POOL FILTER
G127B
NO WORK AT POOL
AREA OF WORK
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
SC
H
O O
L D
IS
TR
IC
T
U -4
SO
U
TH
E
LG
IN
H
IG
H
S C
H O
O L
SO
U
TH
E
LG
IN
H
IG
H S
C H
O O
L
PO
O L
R
EN
O
VA
TI
O
N
E
M
AI
N S
T.
, S
O U
TH
E
LG
IN
, I L
P1.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR
POOL PLUMBING
PLAN
ISSUED FOR BID
1/8" = 1'-0"1 FIRST FLOOR POOL PLUMBING PLAN
NOT TO SCALE
A1 - KEYPLAN
PLUMBING PLAN NOTES
DISCONNECT & REMOVE EXISTING WATER COOLER & RELATED APPURTENANCES. FURNISH & INSTALL NEW BI-LEVEL WATER COOLER/BOTTLE FILLER AT SAME LOCATION. EXTEND & CONNECT EXISTING SANITARY WASTE, VENT & CW PIPING TO NEW UNIT. SAW-CUT WALL AS REQUIRED. PATCH & PAINT TO MATCH EXISTING. SEE ARCHITECTURAL DRAWINGS FOR PATCHING & FINISHED INFORMATION.
NEW BI-LEVEL WATER COOLER/BOTTLE FILLER TO BE: OASIS MODEL PGV8FEBFSL-FVF VANDAL RESISTANT, LEAD FREE, BARRIER FREE WALL MOUNTED, VANDAL RESISTANT FRONT PUSH BUTTON TO ACTIVATE WATER COOLER, TOUCHLESS SENSOR BOTTLE FILLER, STAINLESS STEEL CONSTRUCTION, BASIN WITH INTEGRAL DRAIN GRID, VANDAL RESISTANT ANTI-MICROBIAL BUBBLER, 8.0 GPH COOLING OF 50°F WATER AT 90°F AMBIENT AIR, 120 VOLT, 60 HZ, 1 PH, 5.0 F.L.A., 500 WATTS. PROVIDE WITH CANE APRON AND ALL REQUIRED MOUNTING HARDWARE. FINISH & COLOR TO BE SELECTED BY ARCHITECT.
SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION & ELEVATION.
2 EXISTING SILLCOCK SHALL BE RELOCATED SOUTH OF NEW BI-LEVEL WATER COOLER/BOTTLE FILLER. VERIFY EXACT LOCATION IN FIELD. EXTEND EXISTING PIPING TO NEW LOCATION. SAW-CUT WALL. PATCH & PAINT TO MATCH EXISTING. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION & ELEVATION.
GIRLS
LOCKER
G129
CORRIDOR
C-1
JANITOR
G131
LOCKERS/SHOWER
G127B
POOL OFFICE
G127A
LAUNDRY
G133
TOILET RM
G127C
CORRIDOR
C-2
BOYS LOCKER
G135
ATHLETIC
EQUIPMENT
G137
STORAGE
G127D
POOL FILTER
G127B
NO WORK AT POOL
NEW
STARTING
BLOCKS
NEW
STARTING
BLOCKS
NEW
STARTING
BLOCKS
NEW
STARTING
BLOCKS
NEW
STARTING
BLOCKS
NEW
STARTING
BLOCKS
EXISTING DUPLEX
RECEPTACLE TO
BE REMOVED.
NEW GFI DUPLEX
RECEPTACLE TO BE
SURFACE MOUNTED WITHIN
WATER COOLER CABINET.
AREA OF WORK
DESCRIPTION:DATE:
DATE:
PROJECT #
SHEET:
SHEET TITLE:
SC
H
O O
L D
IS
TR
IC
T
U -4
SO
U
TH
E
LG
IN
H
IG
H
S C
H O
O L
SO
U
TH
E
LG
IN
H
IG
H S
C H
O O
L
PO
O L
R
EN
O
VA
TI
O
N
E
M
AI
N S
T.
, S
O U
TH
E
LG
IN
, I L
E1.1
SEPTEMBER 08, 2025
2024.121
FIRST FLOOR
POOL ELECTRICAL
PLAN
ISSUED FOR BID
1/8" = 1'-0"1 FIRST FLOOR POOL ELECTRICAL PLAN
NOT TO SCALE
A1 - KEYPLAN
ELECTRICAL PLAN NOTES: #
1. EXISTING WATER COOLER TO BE REMOVED BY OTHER. DISCONNECT AND REMOVE GFI
RECEPTACLE, BOX, CONDUIT AND WIRING BACK TO NEAREST UNAFFECTED JUNCTION
BOX. BYPASS CONDUIT AND WIRING TO KEEP REMAINING DEVICES OPERATIONAL. SAW
CUT WALL AS REQUIRED FOR REMOVAL OF BOX AND TO EXTEND CONDUIT AND WIRING
TO NEW RECEPTACLE LOCATION.
FURNISH AND INSTALL NEW 20 AMP RATED, GFI TYPE, WEATHER RESISTANT, DUPLEX
RECEPTACLE TYPICAL TO HUBBELL #GFTWRST20 SERIES, COLOR SELECTED BY
ARCHITECT FOR NEW WATER COOLER. COVERPLATE TO BE BRUSHED STAINLESS STEEL
0.302. RECEPTACLE TO BE MOUNTED WITHIN NEW WATER COOLER CABINET,
COORDINATE EXACT MOUNTING LOCATION OF RECEPTACLE IN THE FIELD WITH THE
PLUMBING CONTRACTOR. CONNECT TO EXISTING POWER CIRCUIT PREVIOUSLY SERVING
AREA. EXTEND CONDUIT AND WIRING AS REQUIRED FOR A COMPLETE INSTALLATION.
SAW CUT WALL AS REQUIRED TO FLUSH MOUNT RECEPTACLE BOX AND CONCEAL
CONDUIT IN WALL. PATCH AND PAINT WALL TO MATCH SURROUNDING AREA,
COORDINATE WITH THE ARCHITECT.
2. EXISTING STARTING BLOCKS TO BE REMOVED BY OTHER. PRIOR TO PERFORMING ANY
WORK, CONTRACTOR SHALL MEGGER TEST EXISTING GROUNDING SYSTEM TO ENSURE
IT IS FUNCTIONAL AND COMPLIES WITH POOL GROUNDING REQUIREMENTS PER NEC
ARTICLE 680. PROVIDE A WRITTEN REPORT OF SYSTEM CONDITION AND REPORT ANY
DEFICIENCIES IN THE SYSTEM.
AT NEW STARTING BLOCK LOCATION, SAW CUT AND EXCAVATE FLOOR SLAB AREA AS
NEEDED TO REACH EXISTING POOL GROUNDING SYSTEM. ALL NEW STARTING BLOCKS
TO BE BONDED TO THE EXISTING POOL GROUNDING SYSTEM. UTILIZE MINIMUM #8
COPPER BONDING WIRE AND CONNECT TO EXISTING GROUNDING SYSTEM. CLEAN OFF
EXISTING GROUNDING WIRE BELOW DECK AND REMOVE CORROSION PRIOR TO BONDING
COPPER WIRE WITH CADWELD OR OTHER UL APPROVED (IRREVERSIBLE) FITTING
SUITABLE FOR LOCATIONS IN CONCRETE POURS. ONCE COMPLETE, TEST NEW STARTING
BLOCK GROUNDING SYSTEM IN SAME WAY AS NOTED ABOVE. IF SYSTEM PASSES
GROUNDING TEST, CONTRACTOR SHALL TERMINATE GROUNDING WIRE ON NEW
STARTING BLOCK SYSTEM. STARTING BLOCK ANCHOR SYSTEM MAY INCLUDE AN IN-
FLOOR SLEEVE WITH GROUND LUG OR AN OUT OF SLAB MOUNTING SYSTEM WITH
GROUND LUG. TERMINATE PER STARTING BLOCK MANUFACTURER’S INSTALLATION
DIRECTIONS. ONCE COMPLETE, THE DISTURBED FLOOR AREA SHALL BE BACKFILLED,
COMPACTED AND INFILLED WITH CONCRETE TO MATCH EXISTING SURROUNDING
SURFACE AREA. COORDINATE ALL WORK WITH ARCHITECT PRIOR TO REPAIRING THE
FLOOR. FLOOR NEEDS TO BE LEVEL FOR INSTALLATION OF NEW STARTING BLOCK.
ENTIRE GROUNDING INSTALLATION SHALL COMPLY WITH NEC ARTICLE 680
REQUIREMENTS.
NOTES RE: EXISTING CONDITIONS:
1. VERIFY EXISTING CONDITIONS AND LOCATIONS IN FIELD PRIOR TO SUBMITTING PROPOSAL. FAILURE TO DO SO SHALL NOT RELIEVE
CONTRACTOR FROM PERFORMING THE WORK REQUIRED UNDER THIS CONTRACT.
2. MAKE NECESSARY MODIFICATIONS AND ADJUSTMENTS TO ALL ELECTRICAL ITEMS AND EQUIPMENT, BOTH NEW AND EXISTING, AS MAY BE
REQUIRED BY THESE ALTERATIONS AND ADDITIONS.
3. DISCONNECT AT SOURCE AND REMOVE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT AND ALL OTHER ELECTRICAL ITEMS WHICH ARE RENDERED OBSOLETE BY THESE ALTERATIONS AND ADDITIONS. THESE ARE THE PROPERTY OF THE OWNER AND SHALL EITHER BE REMOVED FROM THE SITE OR RETURNED TO THE OWNER'S STOCK AT THE DISCRETION OF THE OWNER.
4. DISCONNECT, REMOVE AND RELOCATE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT, AND ALL OTHER ELECTRICAL ITEMS WHICH INTERFERE OR ARE INTERFERED WITH, OBSTRUCT OR ARE OBSTRUCTED BY THESE LOCATIONS AS DIRECTED. RECONNECT SUCH ITEMS IN
PROPER OPERATING CONDITION AT NEW LOCATIONS.
5. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE EXISTING BUILDING IN ELECTRICAL OPERATION AT ALL TIMES DURING THE ENTIRE CONSTRUCTION PERIOD. IF IT IS ABSOLUTELY NECESSARY TO SHUT DOWN THE FACILITY AT ANY TIME, THE CONTRACTOR SHALL CONSULT WITH THE OWNER AND MAKE ARRANGEMENTS TO DO SO AT THE OWNER'S CONVENIENCE. PRIOR NOTICE SHALL BE GIVEN.
6. COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICTS AND DELAYS.
7. ALL CUTTING AND PATCHING AS REQUIRED FOR NEW WORK & ABANDONED DEVICES TO BE BY THE CONTRACTOR.
8. RADAR SCAN ALL FLOORS BEFORE CORING OR SAW CUTTING. NOTIFY G.C., OWNER AND ENGINEER OF FINDINGS AND IF NEW WORK WILL CONFLICT WITH ANY EXISTING CONDUIT OR PIPING THAT MAY HAVE BEEN DISCOVERED IN THE FLOOR SYSTEM. IF RADAR SCANS ARE NOT PERFORMED, THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL REPAIR WORK NEEDED TO RETURN THE EXISTING SYSTEMS BACK TO AN OPERATIONAL CONDITION. REFER TO SPECIFICATION SECTION 260000 FOR ADDITIONAL INFORMATION.
9. WHERE EXISTING CONDUITS HAVE BEEN MADE OBSOLETE BY THESE ALTERATIONS AND ADDITIONS AND IT IS IMPRACTICAL TO REMOVE SAME, CONTRACTOR SHALL:
a. CUT CONDUITS OFF AT SLAB OR WALL LINE
b. CAP ALL OBSOLETE CONDUIT.
10. WHERE THE EXISTING WIRING & CONDUIT SERVING ANY EXISTING ELECTRICAL EQUIPMENT IN AREA OF EXISTING BUILDING NOT BE ALTERED IS INTERFERED WITH, CONTRACTOR SHALL REROUTE AND RECONNECT ALL SUCH CONDUIT & WIRING.
NOTES RE: INSPECTING EXISTING BUILDING:
1. THE CONTRACTORS SHALL VISIT AND INSPECT THE EXISTING BUILDING AND SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH ACTUAL JOB CONDITIONS BEFORE SIGNING CONTRACTS. NO EXTRAS WILL BE ALLOWED FOR WORK WHICH MIGHT HAVE BEEN REASONABLY FORESEEN BY
AN INSPECTION OF THESE PREMISES.
2. WHILE THE SIZE AND LOCATION OF NEW WORK AND EQUIPMENT IN THE EXISTING BUILDING HAS BEEN INDICATED ON THE DRAWINGS AS ACCURATELY AS POSSIBLE, CONTRACTOR SHALL ADJUST HIS WORK AS REQUIRED TO AVOID EXISTING DUCTS, PIPES, CONDUITS AND BEAMS NOT SHOWN ON PLANS. CONTRACTOR SHALL ADAPT HIS WORK TO MEET ALL ACTUAL CONDITIONS ON THE EXISTING PREMISES.
3. CONTRACTOR SHALL INSPECT THE PREMISES AND MAKE A DETAILED EXAMINATION OF ALL LOCATIONS WHERE NEW WORK IS TO BE INSTALLED
AND SHALL EXAMINE EXISTING PIPING, CONDUITS, STRUCTURAL SUPPORTING BEAMS, ETC.
4. CONTRACTOR AFTER INSPECTING THE PREMISES AND THE DRAWINGS SHALL CALL TO THE ATTENTION OF THE ARCHITECT ANY LACK OF ANY NECESSARY SPACE OR CLEARANCE REQUIRED BY THE VARIOUS EQUIPMENT BEFORE CONTRACT IS SIGNED. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL CHANGES NECESSARY IF HE NEGLECTS TO DO SO.
NOTE:
ALL DEVICES SHOWN DOTTED, DASHED, OR INDICATED WITH A PLAN NOTE (INDICATING REMOVAL) ARE EXISTING TO BE REMOVED. ALL DEVICES SHOWN SOLID ARE EXISTING TO REMAIN. IF THE CONTRACTOR DEEMS IT NECESSARY FOR A DEVICE TO BE REMOVED, THEY SHALL COORDINATE IN
FIELD WITH THE ARCHITECT/ENGINEER FOR APPROVAL.
GENERAL ELECTRICAL DEMOLITION NOTES:
GROUNDING SPECIFICATION NOTES:
1. EQUIPOTENTIAL BONDING AND GROUNDING WORK SHALL BE COMPLETED BY A COMPANY
SPECIALIZING IN POOL BONDING AND GROUNDING: HARGER LIGHTNING & GROUNDING; HLP
SYSTEMS.
2. PROVIDE ALL CONNECTIONS AS REQUIRED IN THE 2014 NATIONAL ELECTRICAL CODE 680
AND 250.
3. PROVIDE COPPER BONDING CONNECTIONS OF #8 AWG COPPER BONDED TO ALL METAL
PARTS ON AND WITHIN 5' OF THE POOL EDGE (OR AS INDICATED) INCLUDING THE STARTING
BLOCKS, ETC... PROVIDE MULTIPLE CONNECTIONS TO CONCRETE REINFORCEMENT AS
INDICATED. ALL ELECTRICAL EQUIPMENT SERVING THE POOL SHALL BE PROPERLY
GROUNDED. REFER TO POOL DRAWINGS FOR ADDITIONAL BONDING CONNECTION
INFORMATION AND CONNECTION POINTS. VERIFY AND PROVIDE BONDING TIES TO
STRUCTURAL REBAR AS NECESSARY TO SATISFY CODE REQUIREMENTS OF 680.26B.
4. ALL GROUNDING AND BONDING CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC OR
UTILIZE IRREVERSIBLE COMPRESSION CONNECTORS.
5. COORDINATE WITH IDPH TO ALLOW FOR INSPECTIONS AT DIFFERENT POINTS AS DIRECTED
BY IDPH DURING CONSTRUCTION.
ALL POOL BONDING/GROUNDING TO COMPLY WITH NEC ARTICLE 680 REQUIREMENTS.
POOL BONDING/GROUNDING NOTES:
GROUNDING SPECIFICATION
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. All equipment must be UL listed and comply with UL 467.
2. All pool equipment must comply with NEC Article 680 requirements.
3. Grounding Conductors, Cables, Connectors, and Rods:
a. Apache Grounding/Erico Inc.
b. Boggs, Inc.
c. Chance/Hubbell.
d. Copperweld Corp.
e. Erico Inc.; Electrical Products Group.
f. Framatome Connectors/Burndy Electrical.
g. Harger Lightning Protection, Inc.
h. Ideal Industries, Inc.
i. ILSCO.
j. Kearney/Cooper Power Systems.
k. O-Z/Gedney Co.; a business of the EGS Electrical Group.
l. Raco, Inc.; Division of Hubbell.
m. Robbins Lightning, Inc.
n. Superior Grounding Systems, Inc.
o. Thomas & Betts, Electrical.
p. Thompson Lightning Protection.
B. Conductors:
1. Pool Bare Copper Conductors:
a. Solid Copper Conductors: ASTM B 3.
b. Minimum size 8AWG for pool equipment bonding.
2. Insulated Copper Conductors for power grounding system:
a. Manufacture:
1) US Wire & Cable
2) Southwire
3) General Cable.
4) Essex
5) Carol Cable
6) American Insulated Wire Corp.
b. Copper Conductors: Comply with NEMA WC 70, 98 percent conductivity.
c. Conductor Insulation: Comply with NEMA WC 70 for Types THHN/THWN-2, 75 deg C wet/90 deg C dry, minimum 600 V.
d. Color: Green insulation.
e. Minimum size 12AWG THWN/THHN insulated copper for power circuit grounding conductor.
C. Pool Connectors:
1. Comply with IEEE 837 and UL 467.
2. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having jurisdiction for applications in which used, and for specific types, sizes, and combinations of conductors and other items connected.
3. Pool Use: Bolted Connectors for Conductors: Copper or copper alloy with irreversible type connection and compatible with device connecting to.
4. Pool Use: Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.
D. Power System Connectors:
1. Manufacture:
a. AFC Cable Systems, Inc.
b. AMP Incorporated/Tyco International.
c. Buchanan/Tyco.
d. FCI-Burndy.
e. Hubbell Power Systems, Inc.
f. Ideal Industries, Inc.
g. O-Z/Gedney; EGS Electrical Group LLC.
h. 3M; Electrical Products Division.
i. Thomas & Beits Corp.
j. Tyco Electronics Corp
2. Connectors for power/grounding wires shall be insulated:
a. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.
b. Bolted or screwed mechanical pressure/connector block type (insulated).
c. Compression/crimped pressure type.
d. Twist-on pressure type plastic or nylon insulator cap with internal threaded core and spring insert.
E. Installation:
1. Bond all metallic elements within 5’-0” of pool water surface to pool grounding system.
2. All pool connections must be made and finished in a way to prevent corrosion.
3. Exothermic-Welded Connections: Comply with manufacturer's written instructions. Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable.
4. Test grounding system to comply with NEC Article 680 equipotential system. Make system corrections if excessive grounding resistance is detected.
a. Qualifications: An agency, with the experience and capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction
5. Repair all surfaces disturbed to match surrounding area.
F. Warranty:
1. Minimum of 2 years on all parts and labor.
1. PRIOR TO SUBMITTING THIS BID, THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND THOROUGHLY ACQUAINT THEMSELVES WITH ALL EXISTING CONDITIONS AND DETERMINE HOW THEY EFFECTIVELY WORK. THEY SHALL INCLUDE IN THIER BID ANY ALTERATION, RELOCATION, REROUTING, ETC... OF EXISTING FACILITIES, WIRING, CONDUIT, PANELBOARDS REQUIRED FOR INSTALLATION OF NEW WORK. UNDER NO CIRCUMSTANCES WILL THE CONTRACTOR BE GIVEN CONSIDERATION FOR ADDITIONAL COMPENSATION DUE TO THEIR NEGLECT TO COMPLY WITH FOREGOING
REQUIREMENTS.
2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE FOLLOWING CODES:
2015 INTERNATIONAL BUILDING CODE
2014 NATIONAL ELECTRICAL CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FIRE CODE
ILLINOIS ACCESSIBILITY CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
IN ADDITION TO THE ABOVE, FOLLOW ALL LOCAL CODES AND AMENDMENTS, UTILITY COMPANY REQUIREMENTS AND ANY OTHER REQUIREMENTS APPLICABLE TO THIS JOB. ELECTRICAL
CONTRACTOR SHALL SUBMIT ANY REQUIRED DRAWINGS FOR APPROVAL TO ANY AGENCIES REQUIRING THEM AND OBTAIN NECESSARY PERMITS AT NO ADDITIONAL BID COSTS. ALL EQUIPMENT
SHALL BE NEMA STANDARDS AND SHALL BE U.L. LISTED.
3. THESE DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY JUNCTION BOX, FITTING, ETC... REQUIRED.
4. THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN THEIR BID ANY VARIANCES REQUIRED BY APPLICABLE CODES.
5. ALL ELECTRICAL WORK TO BE COORDINATED WITH THE OWNERS OPERATING SCHEDULE IN ORDER NOT TO DISRUPT SAME UNDER ANY CIRCUMSTANCES.
6. PROTECT EXISTING BUILDING STRUCTURE AND GROUNDS FROM ANY DAMAGE WHICH MAY OCCUR DURING INSTALLATION OF NEW WORK. ANY DAMAGE TO EXISTING FACILITIES WILL BE REPLACED OR RESTORED TO THE ORIGINAL CONDITION AND SATISFACTION OF THE WORK BY THE ARCHITECT.
7. PROTECT THE MATERIALS AND WORK OF OTHER TRADES FROM DAMAGE DURING INSTALLATION OF THE WORK. PAY PARTICULAR ATTENTION TO THE LIMITED SPACE AVAILABLE IN CERTAIN LOCATIONS OF THE PROJECT SO THAT EQUIPMENT MAY BE INSTALLED WITHOUT ANY INTERFERENCE.
8. ALL EXISTING SYSTEMS SHALL BE KEPT IN OPERATION THROUGHOUT THE CONSTRUCTION PERIOD AND SHUT DOWNS WILL ONLY BE PERMITTED WHICH HAVE BEEN REQUIRED IN WRITING TO THE
ARCHITECT/OWNER AND WILL NOT INTERFERE WITH NORMAL OPERATIONS.
9. ALL EQUIPMENT SHALL BE INSTALLED COMPLETE FURNISHING ANY REQUIRED DISCONNECTS, JUNCTION BOXES, ETC... FOR A COMPLETE AND WORKING INSTALLATION. ALL DEVICES SHALL BE U.L.
LISTED.
10. ELECTRICAL WORK SHALL BE WARRANTIED FOR BOTH MATERIALS AND LABOR FOR A PERIOD OF TWO (2) YEAR FROM DATE OF FINAL ACCEPTANCE. MANUFACTURER'S EQUIPMENT GUARANTEES OR WARRANTIES FOR PERIODS OF MORE THAN TWO (2) YEAR SHALL BE INCLUDED IN THE MAINTENANCE MANUALS.
11. VERIFY USE OF CONDUIT AND CONDUCTORS IN EXISTING AREAS BEING REMOVED. CAP AND ABANDON, REROUTE OR REPLACE AS REQUIRED.
12. REMOVE, REROUTE, RELOCATE OR EXTEND ALL ELECTRICAL WORK AS DIRECTED AND AS REQUIRED FOR CONSTRUCTION AND OPERATION OF ALL EXISTING AND NEW SYSTEMS.
13. PROVIDE ALL LABOR AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK AS SHOWN. THIS INCLUDES WORK NOT SPECIFICALLY INDICATED BUT REASONABLY INFERRED FOR PROPER
COMPLETION OF THE WORK.
14. REMOVE RUBBISH AS FAST AS IT ACCUMULATES.
15. ALL CUTTING, DRILLING AND PATCHING SHALL BE DONE BY THIS CONTRACTOR. UNDER NO CIRCUMSTANCES SHALL STRUCTURAL WORK BE CUT WITHOUT THE APPROVAL OF THE ARCHITECT.
16. UNLESS OTHERWISE SPECIFIED, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT, WIRING AND DISCONNECTS FOR ALL ELECTRICALLY OPERATED EQUIPMENT INCLUDING
FINAL CONNECTIONS TO SAME.
17. ALL PANELBOARDS AND DISCONNECT SWITCHES SHALL BE LABELED BY USE OF ENGRAVED PLASTIC LAMINATED NAME PLATE.
18. ALL CONDUITS EXPOSED TO THE ELEMENTS, DAMP LOCATIONS, HAZARDOUS AREAS, DIRECT BURIED IN EARTH, SLAB ON GRADE OR FOR SERVICE ENTRANCE RACEWAYS SHALL BE RIGID GALVANIZED METAL OR INTERMEDIATE METAL CONDUIT. FOR ALL OTHER INTERIOR INSTALLATIONS, THIN WALL (EMT) CONDUIT SHALL BE USED. CONDUIT SHALL BE AS MANUFACTURED BY ALLIED, TRIANGLE OR REPUBLIC STEEL CORPORATION. MINIMUM SIZE 3/4"C.
19. CONTRACTOR SHALL INSTALL ALL EQUIPMENT, WIRE AND CABLE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL INSTALLATION DRAWINGS AND WIRING DIAGRAMS FROM THE EQUIPMENT MANUFACTURER. ALL EQUIPMENT SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS. CONTRACTOR SHALL MAKE FINAL
CONNECTIONS AND TERMINATIONS.
20. PROTECT CONDUIT AND WIREWAY OPENINGS AGAINST THE ENTRANCE OF FOREIGN MATTER BY MEANS OF PLUGS OR CAPS, COVER FIXTURES MATERIALS, EQUIPMENT AND DEVICES FURNISHED OR INSTALLED UNDER THIS SECTION OR OTHERWISE PROTECT AGAINST DAMAGE FROM ANY CAUSE, BOTH BEFORE AND AFTER INSTALLATION. MATERIALS, EQUIPMENT OR DEVICES DAMAGED PRIOR TO FINAL ACCEPTANCE OF THEIR WORK SHALL BE RESTORED TO THEIR ORIGINAL CONDITION OR REPLACED.
21. CONTRACTOR SHALL TEST ALL CIRCUITS, EQUIPMENT, ETC... FOR POLARITY, GROUNDING CONTINUITY, GROUND FAULTS, SHORTS, ETC... PRIOR TO OPERATING ANY ELECTRICAL ITEMS OR EQUIPMENT. UPON INSTALLATION IN OPERATION, TEST FOR EACH PROPER FUNCTION, AND SHOW SYSTEMS AND EQUIPMENT TO BE FREE OF DEFECTS. RECORD AND DOCUMENT LOAD AMPERAGE AND TERMINAL VOLTAGE OF EACH PANELBOARD, MOTOR, ETC... WHERE APPLICABLE. FURNISH COPIES TO ARCHITECT.
22. WHERE EXISTING ELECTRICAL EQUIPMENT IS DESIGNATED TO BE REMOVED IT SHALL BE COMPLETELY REMOVED WITH ALL ASSOCIATED BOXES, SUPPORTS AND APPURTENANCES. WIRING AND CONDUIT SHALL BE REMOVED COMPLETELY BACK TO THE FIRST ITEM LEFT UNAFFECTED BY THE REMOVAL. CONDUIT WHICH IS BURIED OR OTHERWISE UNACCEPTABLE SHALL BE ABANDONED.
23. FIELD VERIFY EXISTING UTILITIES IN FLOOR BEFORE CORING/SAW CUTTING. FIREPROOF ALL CORES MADE AS REQUIRED. RADAR SCAN FLOORS IN LOCATIONS OF ALL UNDER FLOOR WORK.
24. WITH THE APPROVAL OF THE ARCHITECT/ENGINEER AND WITHOUT ADDITIONAL COST TO THE OWNER, MAKE MINOR MODIFICATIONS IN THE WORK, INCLUDING REROUTING AS REQUIRED BY INTERFERENCES WITH STRUCTURAL GENERAL AND WORK OF OTHER TRADES OR FOR THE PROPER EXECUTION OF THE WORK.
25. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING EXISTING RECEPTACLE CIRCUITS FROM WHICH EXISTING RECEPTACLES HAVE BEEN REMOVED. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REROUTING AND RECONNECTION TO EXISTING CIRCUIT THE EXISTING RECEPTACLES WHICH ARE TO REMAIN.
GENERAL ELECTRICAL SPECIFICATION NOTES: