This document is a comprehensive component condition assessment for a 1-million-gallon potable water tank located at Mountain Home Air Force Base, Idaho. The detailed inspection report systematically evaluates various exterior and interior components, marking their condition as Not Applicable (NA), Excellent, Good, Fair, or Poor, with specific comments highlighting issues such as coating failures, corrosion, and daylighting. Notable findings include coating failures with corrosion on roof vents, interior walls, ceiling, and support columns, as well as a light skiff of sediment on the interior floor.

The assessment is directly linked to a Sources Sought announcement for a water tank rehabilitation project, with the government intending to issue a firm-fixed price contract set aside for small businesses. The project is estimated to cost between $100,000 and $250,000, with an anticipated solicitation issuance date of 15 July 2025 and proposal due date of 6 August 2025. The rehabilitation scope involves repairing all identified coating failures, corrosion, and structural issues. Small businesses, including Small Disadvantaged Businesses, HUBZone firms, and Service-Disabled Veteran-Owned Small Businesses, are encouraged to respond by 1:00 p.m. MST on 3 July 2025.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

800.479.1558 (P)

800.238.0217 (F) www.midcodiving.com info@midcodiving.com

PO Box 513, Rapid City, SD. 57709 – 605.791.3030 This document is copyright protected by Midco Diving & Marine Services, Inc. ©

N/A - Not applicable Excellent (Ex) - Like new condition, no maintenance needed.

Good - Cosmetic only problems, maintenance if wanted.

Fair - Minor problems, maintenance needed, not immediate.

Poor - Major problems, structural or like, immediate maintenance needed.

Component Condition Comments NA Ex. Good Fair Poor

Site Security X

Gate X

Fence X

Locks X

Alarm X

Reservoir Exterior X

Coating X

Cleanliness X

Seams/Joints X

Foundation X

Exterior Roof X

Coating X

Cleanliness X

Seams/Joints X

Exterior Ladder X Width: 16”

Coating X

Caged X

Safety Climb X Type: Notch

Roof Vent X Size: 42” Height: 8”

Coating X Coating Failure with Corrosion Noted

Screen X

Side Vent X Size: 12”

Coating X Areas of Coating Failure Noted

Screen X Unable to Evaluate

Exterior Telemetry X

Coating X

Functioning X www.midcodiving.com info@midcodiving.com

PO Box 513, Rapid City, SD. 57709 – 605.791.3030 This document is copyright protected by Midco Diving & Marine Services, Inc. ©

Component Condition Comments NA Ex. Good Fair Poor

Manual Level Indicator X

Tag X

Cable X

Indicator X

Pulleys X

Base X

Ext. Man Entry (x2) X Size: 31”

Coating X Areas of Coating Failure Noted

Gasket X

Exterior Inlet X Size: 9”

Coating X

Valve X

Exterior Outlet X Size: 16”

Coating X

Valve X

Exterior Drain/ Scour X

Coating X

Valve/Screen X

Exterior Water Tap X

Coating X

Valve X

Exterior Overflow X Size: ~19”

Coating X

Stand-offs X

Screen X Type: Screen

Access Hatch X Size: 39” x 39” Height: 4”

Weather Stripping X

Coating X

Hinges X

Lock X

Safety Rail/ Catwalk X Height: 42” – Areas of Coating Failure Noted www.midcodiving.com info@midcodiving.com

PO Box 513, Rapid City, SD. 57709 – 605.791.3030 This document is copyright protected by Midco Diving & Marine Services, Inc. ©

Component Condition Comments NA Ex. Good Fair Poor

Interior Ladder X

Coating X

Safety Climb X

Telemetry Sensor X

Functioning X

Float X

Guide Wires X

Interior Floor X

Coating X

Seams/Joints X

Sediment X Depth: Light Skiff of Sediment Noted

Interior Walls X

Coating X Coating Failure with Corrosion Noted

Seams/Joints X

Interior Ceil ing X Daylighting Noted

Coating X Coating Failure with Corrosion Noted

Seams/Joints X

Rafters X

Int. Man Entry (x2) X Size: 34”

Coating X Areas of Coating Failure with Corrosion Noted

Gasket X

Support Column X # of Columns: 1

Coating X Areas of Coating Failure with Corrosion Noted

Base X

Top X

Cathodic Protection X

Anodes X

Wires X

Sacrificial Anodes X www.midcodiving.com info@midcodiving.com

PO Box 513, Rapid City, SD. 57709 – 605.791.3030 This document is copyright protected by Midco Diving & Marine Services, Inc. ©

Component Condition Comments NA Ex. Good Fair Poor

Interior Overflow P ipe X

Coating X

Top/Cap X

Connections/Flange X

Interior Inlet X Size: 9”

Coating X

Riser/Sump X

Interior Outlet X Size: 16”

Coating X

Riser/Sump X

Interior Drain/ Scour X Size: 6”

Coating X Coating Failure with Corrosion Noted

Sump X

Interior Water Tap X

Coating X

Valve X

Water M ixer X

Hardware X

Functioning X

Manufacturer X

File details come from the government source that posted it. Updated .