62NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
SECTION 4.6:
UNIQUE REQUIREMENTS
GENERAL REQUIREMENTS
Building / Site Requirements
• The selected facility must have an emergency generator. A ground-level generator will require perimeter fencing and CCTV monitoring. The generator and fuel supply must be at least 25 feet from building entries, parking areas, and loading dock(s). Natural gas is preferred. Spaces / components to be connected to the generator include:
» Server Room » Communications Room » Security Suite » Infrastructure Closets (large and small) » The multi-purpose room and AV room » Secure conference room (second fl oor) » Both medium conference rooms
» IRC
» Safeguards Room / HSDN Room » Building Physical Access Control System (PACS)
» CCTV
» Activation/Enrollment Room (new addition) » Package X-ray Room exhaust fan (new edition) » All PACS and IDS panels must be located in a room(s) connected to the generator » IT Lab » Select building demarc outlets that support NRC infrastructure requiring power
• Consider only facilities that do not store or process hazardous materials on-site.
• NRC RIII currently has 13 reserved parking spaces and one reserved parking spot for the government vehicle.
• As possible, NRC RIII would like to have space adjacent to the loading dock to support temporary holding of items delivered to the agency.
63NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
SECTION 4.6: Unique Requirements
Building Exterior / Perimeter
• Parking: surface parking is preferred. Additional security considerations and countermeasures are required if the building has underground parking.
• Depending on the size of the building, a vehicle barrier system may be required. Counter measures are most easily applied to one and two-story buildings while buildings of three or more stories require increased mitigations for blast effects / progressive collapse. Refer to the “Uncontrolled R3 Baseline Countermeasure Requirements” for more information.
• While exterior landscaping is a positive design feature, it can have negative security implications. Ideal for the selected building to have limited landscaping around the perimeter of the building.
• Exterior lighting in parking lots, at entry points, etc. is important for safety and security.
• Blast fi lm on the exterior windows is a requirement on the fi rst fl oor, regardless of who occupies the fl oor (8mm fi lm per standard industry practice).
• Ground fl oor openings (windows or other penetrations within 18’ of the ground) should be non-operable.
• Perimeter doors need to be equipped with high security locks and non-removable hinges.
Interior Confi guration
• If the NRC RIII occupies more than one fl oor, it is ideal to have the ability to go between the two fl oors without leaving controlled space (e.g., internal stair or controlled elevator lobby).
• NRC RIII requires secured access to mechanical, electrical, and telephone rooms along with controlled access to the roof. The approach to roof access will depend on the selected building.
Systems Requirements
• Ideal for air handlers / air intakes to be located on the roof rather than on the ground.
• Filtration requirements:
» HVAC System: minimum effi ciency for a Level 3 facility is MERV 10 particulate fi lter. If not achievable based on the existing system, there are other options.
» Mail Room: MERV 13 particulate fi lters.
• Internal Security System:
» NRC Region III access control and detection systems require NRC-cleared, certifi ed technicians to install and confi gure.
» An open offi ce plan will require more motion detectors; an enclosed versus open ceiling system is preferred by the security team. Cleanly and aesthetically placing devices in an exposed ceiling is more diffi cult.
General Requirements (continued)
64NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
Incident Response Center (IRC)
• Response Director Team + Communication Hub with seating for 10 and projection / display wall.
Locate Proactive Measures Team and Reactor Safety Team areas on either side of the hub, separated by glass walls and sliding glass doors.
• Team areas to include two workstations facing into the Hub, a table with two additional chairs to support meetings of up to four within the space, and two display monitors.
• Incorporate a Copy / Map / Equipment Room and Safeguards Offi ce within the IRC.
• Spaces directly adjacent / nearby the IRC:
» Two (2) Focus Rooms » One (1) six-seat Conference Room to support the ERM Team » Safeguards Room » HSDN Room
• Ideal for additional meeting spaces to be nearby to support of staging and overfl ow activities.
• Wall construction: full-height acoustical wall with insulation.
HSDN Equipment Room
• Wall construction: full-height acoustical wall with insulation; 1-hour fi re rated.
• Ensure adjoining spaces, especially those above, do not have plumbing.
• Provide cipher lock to ensure restricted access to room.
Safeguards Room The Safeguards Room shall be built to the following specifi cations to protect for sound:
• Three layers ⅝ inch-thick gypsum wallboard (GWB), one layer on the uncontrolled side of the SCIF and two on the controlled side of the SCIF, to provide adequate rigidity and acoustic protection (Sound Class 3).
• Wallboard shall be attached to 3 ⅝ inch-wide 16 Gauge metal studs or wooden 2 x 4 studs placed no less than 16” on center (o.c.).
• 16 Gauge continuous track (top & bottom) w/ anchors at 32” o.c. maximum) – bed in continuous bead of acoustical sealant.
• The interior two layers of wallboard shall be mounted so that the seams do not align (i.e., stagger joints).
• Acoustic fi ll 3 ½“ (89mm) sound attenuation material, fastened to prevent sliding down and leaving void at the top.
• The top and bottom of each wall shall be sealed with an acoustic sealant where it meets the slab.
• Fire safe non-shrink grout, or acoustic sealant in all voids above/below track both sides of partition.
• Entire wall assembly shall be fi nished and painted from true fl oor to true ceiling.
MISSION CRITICAL SPACES
65NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
SECTION 4.6: Unique RequirementsMission Critical Spaces (continued)
Additional requirements:
• Provide cipher lock to ensure restricted access to room; room is also alarmed.
• Provide mail slot with secure drop box for delivery of classifi ed documents.
• Support secure video conference capabilities and storage of secure materials.
LAN / IDF Rooms
• Wall construction: full height acoustical with insulation, 1-hour fi re rated
• Supplemental air
• Fire suppression system
• Badge readers at all access points.
Offi ce of Investigations Suite
• Restricted badge access entry into suite.
• Main entry with buzzer connected to the OI phone system with audio to confi rm who is at the door and provide access.
• Evidence / Storage Room
» Wall construction: full-height acoustical wall with insulation and metal mesh; partition to meet NIJ Level 3 requirements.
» Secure storage with badge access for storage of unique items (e.g., law enforcement training equipment, weapons, weapons discharge area, ammunition, polygraph chair and equipment, etc.).
• Room includes workspace with LEADS Terminal (provided by the state to support criminal history checks).
Security Suite / Entry Lobby
• Welcoming, professional space with glazed double doors (enforced tempered glass).
• Work with NRC HQ Security Team to incorporate all design requirements, including:
» 6’ tall ballistic enclosure around security desk (bullet resistant glass clad polycarbonate).
» Clear ballistic panel in front of security desk with speak-through hardware.
» Sliding transaction drawer.
X-Ray Room
• Construction requirements: full-height CMU wall with gypsum wall board ceiling and venting to the exterior.
• Direct adjacency to the IM Center.
66NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
Badging + Enrollment Room
• Badge access reader at entry.
• Two workstations with complimentary working tables; scanning equipment located on the worktables.
• Photo area with backdrop and space for approximately 6’ between the employee and camera.
• Safe or locking fi ling cabinet to store IDs that are being held, offi ce supplies, and building keys.
• Locate in the DRMA space to support staff convenience.
• Request for separation between the workstations (panel) based on COVID.
• At times, process multiple people at once; ideal to have seating area nearby to support overfl ow.
Copy / Print / Work Rooms
• Include shredder and shred bins in each space.
• Provide counter space with upper and lower cabinets to support materials supply.
• Incorporate mail slots into millwork.
Drug Testing Restrooms
• ADA compliant
• Near the elevators or exit doors to minimize the number of escorts needed; contractors administering the tests are not cleared so optimal to have doors open to a non-secure area.
• One room for males, one for females. Would prefer these to be gender specifi c.
• Currently have a shower in each drug testing room; maintain this functionality to support people who exercise during the day and want to clean up before returning to work.
• A small sink is required with a countertop or small vanity.
• Provide vestibule for the test administrators; each with a wall mounted, drop writing surface.
• Ideal to have adjacent seating area and water access to support people with shy bladders. Required to have a water fountain or water source (e.g., bottled water). Chilled water preferred.
• Do not put drug testing room on top of rooms with important technology or fi les below.
IM Center / Mail Room
• Locate directly adjacent to the X-Ray Room.
• Provide storage space for supplies.
• Provide counter workspace and layout space for large items.
• Room includes two (2) large plotters and copy / print equipment to support specialty printing needs.
• Provide space for mail sorting and postage meters.
• Provide safe for storage of classifi ed documents.
• Include a transaction window with counter along circulation path.
SUPPORT SPACES
67NRC REGION III WORKPLACE RECOMMENDATIONSDLR GROUP | 2021
SECTION 4.6: Unique RequirementsSupport Spaces (continued)
Mothers Room
• Sink with hot and cold-water controls with goose-neck faucet.
• Provide microwave and under-counter refrigerator.
• Incorporate two shelves / worksurfaces to support work while seated or standing when in the room.
Shelves to also support equipment storage.
• Provide a laptop table for use when seated in the lounge chair.
Supply Storage Rooms
• Provide a double door with badge access into the Storage Room.
• Provide perimeter adjustable shelving with central open space for storage of pallets, boxes, miscellaneous items
MISCELLANEOUS
Example AED (Automated External Defi brillators) Locations Confi rm fi nal locations and wall-mounted vs portable (no power required) during DID development.
• Security Suite
• Work Café
• Second Floor Focus Room
Example Digital Clock Locations Confi rm fi nal locations during DID development.
• Hard-wired digital clocks to be located (1) in each multi-purpose room, (3) in the IRC, and (1) in the Safeguards Room.
• Need hardwire whip or plug for power (TBD).
• Clocks to be provided by NRC.