2-Drawings - John Marshall HS Greenhouse Replacement Final CDs Drawings.pdf
PDF 8 MB Posted
- Attached to
- John Marshall High School Greenhouse Replacement
- Solicitation number
- Bid 030426
- Issued by
- Olmsted County, Minnesota
About this file
John Marshall High School Greenhouse Replacement - Construction Documents
These are construction drawings and specifications prepared by CRW Architecture + Design Group for the Rochester Public Schools John Marshall High School Greenhouse Replacement project in Rochester, Minnesota (Project #25-070). The project involves the complete replacement of the main greenhouse structure, updates to existing masonry walls, mechanical and electrical infrastructure improvements, minor site modifications, and retention of certain existing conditions. The scope encompasses demolition of the existing greenhouse glazing and structure, removal of the top three courses of existing concrete masonry units (CMU) down to the foundation, replacement of heating systems including two condensing boilers with a capacity of 379.3 MBH each, installation of new hydronic piping and unit heaters, electrical panel upgrades from a 60-amp to 100-amp service, plumbing modifications including relocation of a reduced pressure zone backflow preventer, site grading and drainage improvements, and restoration of landscape areas. The construction documents package includes architectural floor plans and elevations, structural details, mechanical systems plans with piping layouts, plumbing diagrams, and electrical power and lighting plans. The documents were issued for bidding on February 12, 2026, and represent 100-percent construction documents with detailed specifications for all trades.
The project includes several mechanical and electrical upgrades with specific equipment schedules. Mechanical systems include two Riello Condexa Pro 117 gas-fired condensing boilers, Grundfos circulation pumps, Modine unit heaters with varying capacities, a Taco 5900 Plus hydraulic separator, and finned tube radiation elements for heating distribution. Electrical work includes installation of a new 120/208V, 3-phase, 100-amp panelboard (GH-1) supplied from the existing distribution panel B08 in the boiler room, grow lighting circuits, and exterior security lighting. The project accommodates several base bid and alternate items, including optional removal versus storage and reinstallation of existing work tables, optional insect screens for greenhouse vents, optional automatic sun shade installation, and optional grow lights. The construction documents emphasize coordination between trades, field verification of existing conditions, compliance with the 2020 Minnesota State Building Code and 2024 International Building Code, and extensive demolition requirements with protection of items designated for retention or salvage.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
MECHANICAL ENGINEER
ARCHITECT
STRUCTURAL ENGINEER
SITE DESIGN
ROCHESTER PUBLIC SCHOOLS
615 7TH ST SW
ROCHESTER, MINNESOTA 55902
CONTACT: BILL BURT
PHONE NUMBER: (507) 993-2968
EMAIL: william.burt@rochesterpublicschools.org
CRW ARCHITECTURE + DESIGN GROUP
211 ELEVETH AVENUE NORTHWEST
ROCHESTER, MINNESOTA 55901
CONTACT: VERONICA KINGSTON
PHONE NUMBER: (507) 206-6201
EMAIL: vkingston@crwarchitecture.com
DUNHAM ENGINEERING
421 FIRST AVENUE SW, SUITE 201W
ROCHESTER, MINNESOTA 55902
CONTACT: STEVE HARMON
PHONE NUMBER: (507) 424-3350
EMAIL: steve.harmon@dunhameng.com
BOLTON & MENK, INC.
2900 43RD ST NW #100
ROCHESTER, MN 55901
CONTACT: DEREK OLINGER, PE.
PHONE NUMBER: (507) 525-2685
EMAIL: derek.olinger@bolton-menk.com
SEH, INC.
3428 LAKERIDGE PL NW STE 100
ROCHESTER, MINNESOTA 55901
CONTACT: BENJAMIN WOLF, PE.
PHONE NUMBER: (507) 316-6648
EMAIL: bwolf@sehinc.com
ELECTRICAL ENGINEER
DUNHAM ENGINEERING
421 FIRST AVENUE SW, SUITE 201W
ROCHESTER, MINNESOTA 55902
CONTACT: BLYTHE WALDEMAR
PHONE NUMBER: (507) 271-8389
EMAIL: blythe.waldemar@dunhameng.com
N O
R T
HSITE
N O
R T
H
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
CONSTRUCTION DOCUMENT PACKAGE
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/2601
A u to d e s k D o c s /R
P S
J M
G re e n h o u s e /2
-0
R P
S J
M G re e n h o u s e
.r v t
/1
/2
:1
:4
P
M
G0.00
JASON WOODHOUSE
44421 02/12/2026
COVER SHEET
R O
C H
E S
T E
R
M
IN
N
E S
O T
A
R P
S
JO
H
N M
A R
S H
A L L H
IG
H
S C
H O
O L
G R
E E
N H
O U
S E
R E
P L A
C E
M E
N T
25-070
02/12/2026
VLK
JW
RPS - JOHN MARSHALL HIGH
SCHOOL GREENHOUSE
REPLACEMENT
ROCHESTER MINNESOTA
PLANS ISSUED:02/12/2026
1-GENERAL INFORMATION
G0.00 COVER SHEET
2-CIVIL
C1.01 SITE PLAN
3-ARCHITECTURAL DEMO
AD1.00 DEMO PLAN AND ELEVATIONS
4-ARCHITECTURAL
A1.00 LEVEL 1 - FLOOR PLAN
A2.00 BUILDING ELEVATIONS
A3.00 SECTIONS AND DETAILS
5-STRUCTURAL
S1.00 STRUCTURAL DETAILS
6-MECHANICAL
M0.00 MECHANICAL SYMBOLS AND ABBREVIATIONS
M2.01 LOWER LEVEL HVAC MECHANICAL PLANS
M3.01 LOWER LEVEL HVAC PIPING PLANS
M5.01 MECHANICAL SCHEDULES AND DETAILS
P2.00 UNDERFLOOR PLUMBING PLANS
P2.01 LOWER LEVEL PLUBING PLANS
P3.00 PLUMBING RISERS
7-ELECTRICAL
E0.00 ELECTRICAL TITLE SHEET
E2.01 POWER & SIGNAL PLAN
E2.03 ELECTRICAL LIGHTING PLAN
E6.01 ELECTRICAL SCHEDULES
ME7.01 MECHANICAL AND ELECTRICAL SCHEDULES
PE7.01 PLUMBING & ELECTRICAL SCHEDULES
QC003 ELECTRICAL QC SCHEDULES
CODE INFORMATION: SHEET INDEXSITE LOCATION MAP
BUILDING LEGEND
NOT TO SCALE
2024 INTERNATIONAL BUILDING CODE
2020 MINNESOTA STATE BUILDING CODE
2020 MINNESOTA ACCESSIBILITY CODE
2020 MINNESOTA CONSERVATION CODE FOR EXISTING BUILDINGS
PROPOSED PROJECT SUMMARY:
REPLACEMENT OF MAIN GREENHOUSE STRUCTURE ALONG WITH UPDATES TO EXISTING
INFRASTRUCTURE, MINOR SITE MODIFICATIONS, AND OTHER CONDITIONS THAT WILL REMAIN.
OCCUPANCY CLASSIFICATION (CHAPTER 3):
USE NOT CHANGED
OCCUPANCY LOAD:
OCCUPANCY LOAD NOT CHANGED.
MEANS OF EGRESS
2 EXITS (NOT CHANGED)
ACCESSIBILITY
MINOR SITE REWORK TO ALLOW FOR ZERO STEP ENTRANCE INTO GREENHOUSE ON LOWER
LEVEL.
ACCESS TO UPPER LEVEL BUS STOP WAITING AREA NOT CHANGED.
NO. REVISIONS DATE
FF=1024.82
FF=1025.14
CB
R=1024.21
NW
SE 1018.44
1018.58
INV:INV:INV:INV:INV:
INV:
E
E
E
E
E
E
E
E
E
E
E
G
G
G
G
G
G
G
G
G
G
G
G
G
G
1025.14
1025.14
1024.98
1024.72
1024.95
1025.14
1024.36
1024.24 1024.82
1024.49
1024.43
1025.00
1.51%
1.95%
4.21%
3.08%
CONC
CONC
TURF
TURF
TURF
12" RCP
STM
" R
CP
ST
M
STM
WOOD
MULCH
WOOD
MULCH
RAISED
PLANTERS
BLOCK
RET
WALL
GREENHOUSE
BUILDING
ENTRANCE
9.78%
FF=1024.82
FF=1025.14
CB
R=1024.21
NW
SE 1018.44
1018.58
INV:INV:INV:INV:INV:
INV:
E
E
E
E
E
E
E
E
E
E
E
G
G
G
G
G
G
G
G
G
G
G
G
G
G
CONC
CONC
TURF
TURF
TURF
12" RCP
STM
" R
CP
ST
M
STM
WOOD
MULCH
WOOD
MULCH
RAISED
PLANTERS
BLOCK
RET
WALL
GREENHOUSE
BUILDING
ENTRANCE
R
FEETSCALE
0 10 20
HORZ.
R
FEETSCALE
0 10 20
HORZ.
PROPOSEDEXISTING
GREENHOUSE
GRADE FOR POSITIVE DRAINAGE, TOPSOIL PREP AND SOD ALL DISTURBED AREAS
PROTECT TREE AND ROOT SYSTEM. REPORT ANY UNAVOIDABLE DAMAGE TO ROOTS
TO OWNER PRIOR TO BACKFILLING, IF APPLICABLE
NEW ELECTRICAL CONDUIT FROM GREENHOUSE TO TUNNEL - SEE ELECTRICAL
DRILL & GROUT (3) #4 EPOXY BAR @ 18" OC, WHERE TYING INTO OTHER WALKS
SALVAGE AND REINSTALL BLOCK RETAINING WALL AS NECESSARY TO
ACCOMMODATE STRUCTURAL WORK
REMOVE CONCRETE WALK
KEYNOTES:
5" CONCRETE WALK
REMOVE MULCH. FURNISH AND INSTALL NEW HEAVY DUTY LANDSCAPING FABRIC &
WOOD MULCH (TYPE AND COLOR TO BE VERIFIED WITH OWNER)
EXCAVATE DOWN TO FLOOR LEVEL TO ALLOW FOR REPLACEMENT OF EXIST
MASONRY WALL. REMOVE VEGETATION AS NECESSARY TO COMPLETE WORK.
BACKFILL, COMPACT AND RESTORE GRADE AFTER STRUCTURAL WORK IS COMPLETE
INLET PROTECTION (CONTRACTOR TO SELECT MOST APPROPRIATE BMP FOR INLET
AND PROPOSED WORK. DEVICE MUST HOLD POTENTIAL ERODED DEPOSITS FROM
ENTERING INLET, BUT STILL PREVENT ANY FLOODING/BACKUPS INTO THE ADJACENT
BUILDINGS.
NEW ELECTRICAL CONDUIT
SAWCUT CONCRETE
LEGEND:
SITE & GRADING PLAN NOTES:
1. ALL FILL REQUIRED TO RAISE SIDEWALK GRADES SHALL BE AGGREGATE BASE, CL-5
2. REPLACEMENT PLANTINGS, BEYOND TURF, WILL BE FURNISHED AND INSTALLED BY THE OWNER AFTER
CONSTRUCTION.
3. ALL TIE IN SLOPES IN GREEN SPACE SHALL BE 1:6 OR LESSER GRADE. VERIFY FINAL GRADES TO ENSURE
SMOOTH TRANSITIONS AND POSITIVE DRAINAGE TOWARD SURFACE INLET(S).
4. ALL DISTURBED AREAS OUTSIDE THE BUILDING PAD(S) WHICH ARE NOT DESIGNATED TO BE PAVED SHALL
RECEIVE AT LEAST 6" OF TOPSOIL AND SOD.
5. ALL SIDEWALKS, ACCESS ROUTES, AND PEDESTRIAN RAMPS SHALL COMPLY WITH CURRENT ADA
STANDARDS. SIDEWALKS ARE DESIGNED WITH 1.5% CROSS SLOPE UNLESS OTHERWISE NOTED.
6. THE CONTRACTOR SHALL ADJUST TO GRADE ALL MANHOLES STRUCTURES AND APPURTENANCES THAT FALL WITHIN THE LIMITS OF THIS CONTRACT. THE CONTRACTOR SHALL KEEP ALL SAID EXISTING UTILITIES AND THEIR APPURTENANCES FREE OF DEBRIS AND OPERABLE AT ALL TIMES DURING CONSTRUCTION.
EXISTING CONDITION & REMOVAL NOTES:
1. EXISTING UTILITY INFORMATION SHOWN ON THIS PLAN HAS BEEN PROVIDED BY
THE UTILITY OWNER. THE CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS
PRIOR TO COMMENCING CONSTRUCTION AS REQUIRED BY STATE LAW. NOTIFY
GOPHER STATE ONE CALL, 1-800-252-1166 OR 651-454-0002.THE SUBSURFACE
UTILITY INFORMATION IN THIS PLAN IS UTILITY QUALITY LEVEL D UNLESS
OTHERWISE NOTED. THIS UTILITY LEVEL WAS DETERMINED ACCORDING TO THE
GUIDELINES OF CI/ASCE 38-02, ENTITLED "STANDARD GUIDELINES FOR THE
COLLECTION AND DEPICTION OF EXISTING SUBSURFACE UTILITY DATA."
2. CONTRACTOR IS RESPONSIBLE FOR DESIGNING, FURNISHING AND INSTALLING
ALL ADDITIONAL AND NECESSARY EROSION CONTROL BMPs AND CONSTRUCTION
METHODS TO MEET CITY AND MPCA STANDARDS. BEYOND THE INLET
PROTECTION, NO ADDITIONAL BMPs ARE IDENTIFIED ON THE PLAN. ALL BMPs
MUST BE IN PLACE PRIOR TO REMOVALS.
3. PROTECT EXISTING CONCRETE WALKS FROM EQUIPMENT DAMAGE WITH
RUBBER MATS.
4. CONCRETE WALK REPLACEMENT LIMITS ARE APPROXIMATE. ADJUST AS
NECESSARY TO ALIGN WITH EXISTING JOINT PATTERN WHILE MAINTAINING
SLOPES.
5. BMPS AND INLET PROTECTION FOR ALL EXISTING STORM SEWER INLETS SHALL BE
IN PLACE PRIOR TO BEGINNING OF ANY REMOVALS. SEE SHEET C204 FOR
EROSION CONTROL PLAN.
6. CONTRACTOR SHALL PROTECT ALL ITEMS NOT DESIGNATED FOR REMOVAL.
CONTRACTOR SHALL PROTECT ALL ITEMS DESIGNATED FOR SALVAGE AND
PROVIDE APPROPRIATE STORAGE UNTIL REINCORPORATED INTO THE PROJECT.
DAMAGED ITEMS SHALL BE REPLACED UNLESS REPAIRS ARE APPROVED BY THE
ENGINEER.
7. CONTRACTOR SHALL LOCATE AND VERIFY DEPTHS OF EXISTING UNDERGROUND
UTILITIES PRIOR TO PAVEMENT REMOVAL & EXCAVATION. IF UTILITIES FOUND
TO BE IN CONFLICT WITH PROPOSED IMPROVEMENTS, COORDINATE WITH
ENGINEER & UTILITY OWNER FOR POTENTIAL RELOCATION.
5" CONCRETE WALK (2521)
6" (MIN) AGGREGATE BASE, CL 5 (2211) OR EXIST BASE (PROVIDED MIN DEPTH PROVIDED)
SUBGRADE PREPARATION (2112)
C1.01
CONCRETE WALK
NOT TO SCALE
NOTE: SAW CUT CONTROL JOINTS AT SPACING AND
PATTERN CONSISTENT WITH EXISTING CONCRETE
EXISTING CONTOUR MINOR
EXISTING CONTOUR MAJOR
PROPOSED CONTOUR MINOR
PROPOSED CONTOUR MAJOR
C1.01
SHEET NUMBER
SITE PLAN
100% CDs 02/12/261
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
DEREK P. OLINGER
54287 02/12/2026
RO
CH
ES
TE
R, M
IN
NE
SO
TA
RO
CH
ES
TE
R
JO
HN
M
AR
SH
AL
L
GR
EE
NH
OU
SE
25-070
02/12/2026
DPO
DPO
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
NO. REVISIONS DATE
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
UP
DEMOLITION NOTES:
GENERAL DEMOLITION NOTES:
1. DASHED LINES REPRESENT EXISTING ITEMS TO BE REMOVED.
2. PROVIDE ALL WORK TO COMPLETE DEMOLITION AS MAY BE REQUIRED
TO ACCOMPLISH WORK AS SHOWN ON THE DRAWINGS UNLESS
NOTED OTHERWISE. ALL AS INDICATED OR REQUIRED RELATING TO
THE EXISTING BUILDING AND NOT OTHERWISE ASSIGNED IS INCLUDED
UNDER THE RESPONSIBILITY OF THE CONTRACTOR.
3. CONTRACTOR TO VERIFY EXISTING ELECTRICAL & PLUMBING
LOCATIONS PRIOR TO DEMOLITION. EXISTING PLUMBING AND
ELECTRICAL MAY REQUIRE MODIFICATION TO ACCOMPLISH THE NEW
DESIGN AS SHOWN ON THESE PLANS.
4. MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS SHALL
TERMINATE ALL APPROPRIATE SERVICES TO EXISTING CONSTRUCTION
WHICH ARE TO BE PERMANENTLY DISCONNECTED. THEY SHALL
FURTHER MAKE ALL TEMPORARY SERVICE TERMINATIONS INDICATED
OR REQUIRED TO ACCOMPLISH THE DEMOLITION AND/OR NEW
REVISED OR REPLACED SERVICES AS PART OF WORK UNDER ALL
CONTRACTS. ALL PERMANENT TERMINATIONS SHALL BE REMOVED
BACK TO THE SOURCE. NO VACANT SERVICES SHALL BE LEFT IN
PLACE.
5. CONTRACTORS ARE TO BE RESPONSIBLE FOR REMOVING AND
HAULING OF ALL DEMOLITION DEBRIS.
6. AT CONCLUSION OF DEMOLITION, ALL SURFACES SHALL BE READY TO
RECEIVE NEW FINISHES.
7. OWNER TO REMOVE/ RELOCATE ALL FURNITURE, FIXTRUES AND
EQUIPMENT PRIOR TO START OF CONSTRUCTION, COORDINATE
PROJECT SCHEDULE WITH GENERAL CONTRACTOR.
8. REMOVE AND DISPOSE ALL THE EXISTING SIGNAGE ON THE WALL NEXT
TO DOORS U.N.O.
1 REMOVE AND DISPOSE OF EXISTING GREENHOUSE GLAZING AND
STRUCTURE IN IT'S ENTIRETY.
2 REMOVE AND DISPOSE OF TOP THREE COURSES OF EXISTING
CMU, DOWN TO TOP OF EXISTING SLAB/FOUNDATION.. PREPARE
EXISTING FOUNDATION FOR NEW CMU BLOCK.
(NOT ALL DEMOLITION NOTES APPEAR ON EVERY SHEET)
3 REMOVE AND DISPOSE OF EXISTING DOOR, FRAME IN ITS
ENTIRETY.
4 BASE BID: REMOVE, STORE, AND REINSTALL EXISTING WORK
TABLES
ALTERNATE A-1: REMOVE AND DISPOSE OF EXISTING WORK
TABLES.
5 REMOVE AND DISPOSE OF EXISTING STAINLESS STEEL SHELF IN
ITS ENTIRETY
6 REMOVE AND DISPOSE OF DAMAGED CEILING AREA.
CONTRACTOR TO VERIFY EXTENT OF DAMAGE.
7 CUT NEW HOLE IN EXISTING CMU WALL FOR MECHANICAL. SEE
MECHANICAL FOR SIZING.
8 REMOVE AND DISPOSE OF EXISTING FASCIA IN IT'S ENTIRETY
9 REMOVE EXISTING ROCK/SOIL TO 3" BELOW TOP OF SLAB - TYP.
10 REMOVE AND SALVAGE EXISTING STEEL SHELF BRACKETS TO
OWNER - TYP.
11 DEMO CONCRETE SLAB FOR CONNECTION TO PIPES. VERIFY
WITH MECH. FOR LOCATION AND SIZING.
A2.00
A2.00
AD1.00
AD1.00
10' - 7" 4' - 2" 10' - 7"
8' - 8"
AD1.00
4 4
4 4
4 4
4 4
MECHANICAL
GREENHOUSE
EXISTING CONCRETE SLAB
ON GRADE TO REMAIN
DEMO EXISTING CONCRETE SIDEWALK - SEE ARCH SITE PLAN AND CIVIL
AD1.00
EXISTING COUNTERS
TO REMAIN
9 9
2' - 3" 3' - 6"
3' - 1" 2' - 0" 2' - 0"
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
ROOF
122' - 2 3/8"
T.O. EXISTING FOOTING
96' - 0"
EXIST. GRADE
EXISTING BUILDING TO REMAIN
EXIST. FOUNDATION
TO REMAIN
REMOVE EXISTING SHINGLES
AND UNDERLAYMENT
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
ROOF
122' - 2 3/8"
T.O. EXISTING FOOTING
96' - 0"
EXIST. GRADE
EXISTING BUILDING TO REMAIN
EXIST. FOUNDATION
TO REMAIN
T.O. SLAB/FOUNDATION
100' - 0"
T.O. EXISTING FOOTING
96' - 0"
EXISTING FOUNDATION
TO REMAIN
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
REMOVE EXISTING SHINGLES
AND UNDERLAYMENT
REMOVE AND DISPOSE OF
DAMAGED CEILING
EXISTING STRUCTURE
TO REMAIN
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
ROOF
122' - 2 3/8"
EXISTING FLUE AND GUY WIRES TO
BE REMOVED.
EXIST. FOUNDATION
TO REMAIN
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/2601
A u to d e s k D o c s /R
P S
J M
G re e n h o u s e /2
-0
R P
S J
M G re e n h o u s e
.r v t
/1
/2
:1
:5
P
M
AD1.00
JASON WOODHOUSE
44421 02/12/2026
DEMO PLAN AND
ELEVATIONS
R O
C H
E S
T E
R
M
IN
N
E S
O T
A
R P
S
JO
H
N M
A R
S H
A L L H
IG
H
S C
H O
O L
G R
E E
N H
O U
S E
R E
P L A
C E
M E
N T
25-070
02/12/2026
VLK
JW
3/8" = 1'-0"
LEVEL 1 DEMO PLAN
1/4" = 1'-0"
EAST ELEVATION DEMO
1/4" = 1'-0"
WEST ELEVATION DEMO
N O R
TH
1/2" = 1'-0"
DEMO WALL SECTION
3/8" = 1'-0"
ROOF DEMO SECTION
1/4" = 1'-0"
SOUTH ELEVATION DEMO
UP
1. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE OWNER. EACH TRADE CONTRACTOR SHALL BE
RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL
SAFETY PROCEDURES, PRECAUTIONS AND PROGRAMS IN CONNECTION
WITH THEIR WORK.
2. THE GENERAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL REQUIRED
PERMITS, LETTERS OF SATISFACTORY COMPLETION AND CERTIFICATES
OF OCCUPANCY FROM THE LOCAL BUILDING OFFICIALS.
3. ALL EQUIPMENT SHOWN AS DASHED IS BY THE OWNER. ELECTRICAL
CONTRACTOR TO VERIFY POWER REQUIREMENTS FOR OWNER'S
EQUIPMENT. MECHANICAL CONTRACTOR TO VERIFY PLUMBING AND
HVAC REQUIREMENTS OF OWNER'S EQUIP.
4. REFER TO THE MECHANICAL, ELECTRICAL DRAWINGS FOR ADDITIONAL
WORK REQUIRED UNDER THIS CONTRACT.
5. THE GENERAL CONTRACTOR AND/OR MECHANICAL CONTRACTOR SHALL
COORDINATE ALL MECHANICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
6. THE GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR SHALL
COORDINATE ALL ELECTRICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
GENERAL NOTES:
FLOOR PLAN NOTES:
1 NEW STAINLESS STEEL WALL MOUNTED
SHELF TO MATCH EXISTING.
2 REPLACE CEILING TO MATCH EXISTING.
CONTRACTOR TO VERIFY THE EXTENT OF
WORK.
3 DOWEL NEW CMU INTO EXISTING CMU
4 EXISTING 16" x 16" FOUNDATION PIER BELOW.
NEW REINFORCED CMU WALL TO BE
DOWELED INTO EXISTING PIER. SEE STRUCT.
5 NEW MAIN STRUCTURAL FRAME FOR
GREENHOUSE TO BEAR ON NEW REINFORCED
CMU WALL AT 102' - 0". SEE STRUCT.
6 INFILL CONCRETE SLAB AS NEEDED TO
MATCH EXISTING CONSTRUCTION. SEE DETAIL
3/A1.00.
7 NEW CONCRETE HOUSEKEEPING PAD.
CONFIRM FINAL SIZE WITH MECH. SEE DETAIL
4/A1.00
A2.00
A2.00
A2.00
A3.00
A3.00
8' - 8"
10' - 8" 4' - 0" 10' - 8"
1' - 4"
MECHANICAL
GREENHOUSE
EDGE OF EXISTING CONC SLAB TO REMAIN
A3.00
/4
/4
/4
EXISTING COUNTERS
TO REMAIN 7
5" 3
1' - 6"
D-1
FLUSH
SCHEDULE
SEE
S E
E S
C H
E D
U L E
D-6
FULL LITE
SCHEDULE
SEE
S
E S
C H
E D
U L E
6" 6"
F-1 F-2
2" 2"
WIDTH
DOOR
D O
O R
H E
IG
H
T
2" 2"
WIDTH
DOOR
D O
O R
H E
IG
H
T
TYPICAL TYPICAL MASONRY
A3.00
A3.00
/8
/2
2" 4' - 0" 2" 4' - 0" 2" 4' - 0"
2" 2"
4' - 0" 2" 4' - 0" 2" 4' - 0" 2"
A3.00
NEW SHINGLES AND UNDERLAYMENT
6" / 12"
6" / 12"6" / 12"
INSTALL NEW METAL FASCIA - TYP.
HARDWARE GROUPS:
GROUP 1: LOCKED CLASSROOM FUNCTION
EACH DOOR SHALL HAVE:
• HINGES
• ONE LOCKSET D70PD
• FUNCTION: OUTSIDE LEVER LOCKED AND UNLOCKED BY KEY. INSIDE
LEVER ALWAYS UNLOCKED.
• ONE STOP
GROUP 2: LOCKED STOREROOM FUNCTION
EACH DOOR SHALL HAVE:
• HINGES
• ONE LOCKSET D80PD
• FUNCTION: OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE
LEVER ALWAYS UNLOCKED.
• ONE STOP
EMBED
3"
EPOXY DOWEL INTO EXIST. SLAB
AT 3' - 0" O.C. - MIN. 1 PER SIDE
COMPACTED GRANULAR FILL TO
DEPTH OF EXIST GRANULAR
NEW CONC. SLAB
EXIST. SLAB ON GRADE
EXIST COMPACTED
GRANULAR FILL
#4 REBAR AT 12" O.C.
EACH WAY AT TOP
#4 REBAR TIE - BOTTOM
CURED/EXISTING SLAB -
INFILLED WHERE NEEDED
3/4" CHAMFER
ALL AROUND
TYPICAL
1/2" CLEAR COVER
ROUGHEN TO PROVIDE SOUND CONCRETE WITH 1/4"
AMPLITUDE, THOROUGHLY CLEAN AND APPLY
BONDING AGENT PRIOR TO POURING BASE CONCRETE
#4 REBAR DOWELS AT 12" O.C. ALL AROUND
PERIMETER - DRILL AND EPOXY GROUT (3" MIN. EMBED)
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/2601
A u to d e s k D o c s /R
P S
J M
G re e n h o u s e /2
-0
R P
S J
M G re e n h o u s e
.r v t
/1
/2
:1
:5
P
M
A1.00
JASON WOODHOUSE
44421 02/12/2026
LEVEL 1 - FLOOR PLAN
R O
C H
E S
T E
R
M
IN
N
E S
O T
A
R P
S
JO
H
N M
A R
S H
A L L H
IG
H
S C
H O
O L
G R
E E
N H
O U
S E
R E
P L A
C E
M E
N T
25-070
02/12/2026
VLK
JW
N O R
TH
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
DOOR FRAME TYPE
3/8" = 1'-0"
T.O. SLAB/FOUNDATION
COMMON DOOR SCHEDULE
D o o r
N u m b e r
R o o m
N a m e
L e a f Q ua n tit y
Door Frame
S id e lig h t W id th
F ir e R a tin g
G la ss F ir e
R a tin g
H a rd w a re
G ro u p
In su l D o o r
T h re sh ol d
W 'S tr ip pi n g
C o m m e n ts
W id th
H e ig h t
T h ic kn es s
T yp e
M a te ria l
F in is h
T yp e
M a te ria l
F in is h
100 MECHANICAL 1 3' - 0" 6' - 8" 1 3/8" D-1 HM F-2 H.M. PT-1 2 DOOR AND HARDWARE BY
GREEHOUSE VENDOR
101 GREENHOUSE 1 4' - 0" 8' - 0" 2" D-6 HM F-1 H.M. 1 DOOR AND HARDWARE BY
GREEHOUSE VENDOR
3/8" = 1'-0"
ROOF
N O R
TH
1" = 1'-0"
SLAB ON GRADE INFILL DETAIL
1" = 1'-0"
CONCRETE EQUIPMENT PAD DETAIL
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
ROOF
122' - 2 3/8"
A3.00
T.O. EXISTING FOOTING
96' - 0"
T.O. GREENHOUSE WALL
110' - 0"
T.O. MASONRY
102' - 8"
4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 2' - 11"
MOTORIZED RIDGE VENTS
MOTORIZED SIDEWALL VENTS
BASE BID: NO INSECT SCREENS
ALTERNATE A-2: PROVIDE INSECT
SCREENS
NEW SHINGLES AND UNDERLAYMENT
16 mm ACRYLIC GLAZING, TYP.
ALUMINUM FRAMING PER GREENHOUSE
MANUFACTURER/INSTALLER, TYP.
NEW METAL FASCIA 1X BLOCKING
EXISTING ASPHALT
SHINGLE ROOF TO REMAIN
EXISTING ALUMINUM
STOREFRONT TO REMAIN
EXISTING MASONRY WALL TO REMAIN
EXISTING MASONRY WALL TO REMAIN
NEW ELBOW EXHAUST - SEE MECH.
T.O. SLAB/FOUNDATION
100' - 0"
ROOF
122' - 2 3/8"
T.O. EXISTING FOOTING
96' - 0"
T.O. GREENHOUSE WALL
110' - 0"
T.O. MASONRY
102' - 8"
A3.00
4' - 2" 4' - 2" 4' - 2" 4' - 2" 4' - 2" 4' - 2"
NEW SHINGLES AND UNDERLAYMENT
16mm ACRYLIC GLAZING, TYP.
ALUMINUM FRAMING PER GREENHOUSE
MANUFACTURER/INSTALLER, TYP.
INSTALL NEW WEATHERTIGHT
COLLAR WITH NEW ROOFING
EXISTING STOREFRONT SYSTEM TO REMAIN
NEW METAL FASCIA W/ 1x BLOCKING
EXISTING FOUNDATION TO REMAIN
T.O. SLAB/FOUNDATION
100' - 0"
ROOF
122' - 2 3/8"
A3.00
T.O. EXISTING FOOTING
96' - 0"
T.O. GREENHOUSE WALL
110' - 0"
T.O. MASONRY
102' - 8"
2' - 11" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0"
MOTORIZED RIDGE VENTS
MOTORIZED SIDEWALL VENTS
BASE BID: NO INSECT SCREENS
ALTERNATE A-2: PROVIDE INSECT SCREENS
NEW SHINGLES AND UNDERLAYMENT
16mm ACRYLIC GLAZING, TYP.
ALUMINUM FRAMING PER GREENHOUSE
MANUFACTURER/INSTALLER, TYP.
EXISTING ASPHALT SHINGLE
ROOF TO REMAIN
EXISTING ALUMINUM
STOREFRONT TO REMAIN
EXISTING MASONRY
WALL TO REMAIN
NEW METAL FASCIA W/ 1x BLOCKING
EXISTING MASONRY WALL TO REMAIN
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/2601
A u to d e s k D o c s /R
P S
J M
G re e n h o u s e /2
-0
R P
S J
M G re e n h o u s e
.r v t
/1
/2
:1
:5
P
M
A2.00
JASON WOODHOUSE
44421 02/12/2026
BUILDING ELEVATIONS
R O
C H
E S
T E
R
M
IN
N
E S
O T
A
R P
S
JO
H
N M
A R
S H
A L L H
IG
H
S C
H O
O L
G R
E E
N H
O U
S E
R E
P L A
C E
M E
N T
25-070
02/12/2026
Author
Checker
1/4" = 1'-0"
EAST ELEVATION
1/4" = 1'-0"
SOUTH ELEVATION
1/4" = 1'-0"
WEST ELEVATION
T.O. SLAB/FOUNDATION
100' - 0"
T.O. EXISTING FOOTING
96' - 0"
T.O. GREENHOUSE WALL
110' - 0"
T.O. MASONRY
102' - 8"
A3.00
6"
12"
6"
12"
TRUSS BY GREENHOUSE SUPPLIER/INSTALLER
BASE BID: NO AUTOMATIC SUN SHADE
ALTERNATE A-3: AUTOMATIC SUN SHADE BY OTHERS
HANGING PLANT POLES
MOTORIZED RIDGE VENTS
MOTORIZED SIDEWALL VENTS
BASE BID: NO INSECT SCREENS
ALTERNATE A-2: PROVIDE INSECT
SCREENS
INSTALL NEW LANDSCAPE
FABRIC WITH 3" OF WASHED
RIVER ROCK - TYP.EXISTING CONCRETE SLAB TO REMAIN
A3.00
RESTORE GRADE AND
LAWN/PLANTINGS
T.O. SLAB/FOUNDATION
100' - 0"
LEVEL 2
108' - 10"
A3.00
T.O. EXISTING FOOTING
96' - 0"
T.O. GREENHOUSE WALL
110' - 0"
T.O. MASONRY
102' - 8"
16mm ACRYLIC GLAZING, TYP.
ALUMINUM FRAMING PER GREENHOUSE
MANUFACTURER/INSTALLER, TYP.
MOTORIZED SIDEWALL VENTS
BASE BID: NO INSECT SCREENS
ALTERNATE A-2: PROVIDE INSECT
SCREENS
EXISTING GRAVEL TO
REMAIN. INSTALL ADDITION
2" OF GRAVEL - TYP.EXISTING CONCRETE SLAB TO REMAIN
NEW SCORED CMU
EXISTING FOUNDATION
TO REMAIN - TYP.
PROVIDE POSITIVE
DRAINAGE AWAY FROM
GREENHOUSE
RESTORE EXISTING
GRADE AND PLANTINGS
TERMINATE WATERPROOFING
BELOW GRADE
NEW GRANULAR BACKFILL
INSTALL WATERPROOFING ON
NEW CMU. EXTEND DOWN ONTO
EXISTING WATERPROOFING.
TYPICAL AT LOCATIONS WHERE
GRADE EXTENDS ABOVE THE
TOP OF SLAB
T.O. SLAB/FOUNDATION
100' - 0"
T.O. EXISTING FOOTING
96' - 0"
/8
CONNECTION OF NEW GREENHOUSE
SHELL TO EXISTING WALL PER
GREENHOUSE SUPPLIER/INSTALLER
NEW SHINGLES AND UNDERLAYMENT
NEW ANODIZED ALUMINUM
STEPPED FLASHING. REGLET
INTO EXISTING CMU JOINTS
GASKETING FOR WATERTIGHT
CONNECTION BY GREENHOUSE INSTALLER
EXISTING SCORED BLOCK FACE TO BE
GROUTED TO PROVIDE A LEVEL SURFACE
FOR GREENHOUSE CONNECTION
EXISTING WOOD DECKING
NEW ANODIZED ALUMINUM
FASCIA W/ 1x BLOCKING
EXISTING SCORED CMU WALL
EXISTING CONCRETE
SLAB TO REMAIN
EXISTING FOUNDATION
TO REMAIN
T.O. SLAB/FOUNDATION
100' - 0"
T.O. EXISTING FOOTING
96' - 0"
T.O. MASONRY
102' - 8"
NEW ANODIZED ALUMINUM
SILL W/ DRIP EDGE
NEW ANODIZED ALUMINUM
SILL W/ DRIP EDGE
DOWEL INTO EXISTING CMU
FOUNDATION. SEE STRUCT.
NEW SCORED CMU
EXISTING FOUNDATION TO REMAIN
PREFINISHED METAL TRIM
CLOSURE BY MECH.
FINTUBE AND PIPING -
SEE MECH.
GALVANIZED STEEL CHANNEL BY G.C.
NEW GREENHOUSE STRUCTURE
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/2601
A u to d e s k D o c s /R
P S
J M
G re e n h o u s e /2
-0
R P
S J
M G re e n h o u s e
.r v t
/1
/2
:1
:5
P
M
A3.00
JASON WOODHOUSE
44421 02/12/2026
SECTIONS AND DETAILS
R O
C H
E S
T E
R
M
IN
N
E S
O T
A
R P
S
JO
H
N M
A R
S H
A L L H
IG
H
S C
H O
O L
G R
E E
N H
O U
S E
R E
P L A
C E
M E
N T
25-070
02/12/2026
VLK
JW
1/2" = 1'-0"
BUILDING SECTION
1/2" = 1'-0"
BUILDING SECTION
1" = 1'-0"
WALL SECTION
1" = 1'-0"
WALL SECTION
EXISTING CONCRETE PIER 8" BELOW
GRAVEL FLOOR (99'-4")
REMOVE EXISTING FLUTED FACE
BLOCK TO EL.100'-0"
REMOVE BLOCK AT PIER
TO EL. 99'-4"
1'-0" 2'-0" 1'-0"
(6) #4 REBAR VERT.
#4 REBAR TO EXISTING CORE
AT 24" OC, TYP.
OFFSET DOWELS AT BASE AND
BEND AT BOTTOM IN NECESSARY
TO MAINTAIN EDGE DISTANCE AT
CONNECTION TO CONCRETE PIER
GRAVEL FLOOR - REPLACE
100'-0"
TOP OF WALL AND PIER
102'-8"
8" CMU 12" CMU PIER 8" CMU
POUR THRU BOND BEAM
EXISTING 8" CMU
TO REMAIN
EXISTING CONCRETE PIER - EST. 16" SQ. ±
(CONTRACTOR VERIFY)
APPROX.
99'-4"
EXISTING CONCRETE PIER 8" BELOW
GRAVEL FLOOR (99'-4")
EST. 16" x 16" (CONTRACTOR VERIFY)
REMOVE EXISTING BLOCK
TO EL. 100'-0"
REMOVE BLOCK AT
PIER TO EL. 99'-4"
1/4" S.S. TIES AT 8" OC
IN EACH JOINT
(4) #4 REBAR VERT.(4) #4 REBAR VERT.
#4 REBAR TO EXISTING
CORE AT 24" OC
1/4" S.S. TIES AT 8" OC
IN EACH JOINT
#4 REBAR TO EXISTING
CORE AT 24" OC
OFFSET DOWELS AT BASE AND
BEND AT BOTTOM IF
NECESSARY TO MAINTAIN EDGE
DISTANCE AT CONNECTION TO
CONCRETE PIER
GRAVEL FLOOR - REPLACE
100'-0"
TOP OF WALL
102'-8"
APPROX.
99'-4"
4" PREFERRED
2 1/2" MIN. (TYP)
4 1/2" EMBEDMENT
12" CMU PIER AT GREENHOUSE
POSTS - GROUTED SOLID
(2) #5 REBAR CONTINUOUS
WITH 8" TOP BOND BEAM
GREENHOUSE POST MOUNTED
TOP OF WALL
(6) #4 REBAR
(2 PER CORE)
APPROX.
99'-4"
16" CMU PIER
AT CORNERS
1/4" S.S. TIES
(4) #4 REBAR AT
16" DIA. PIER
4" PREFERRED
2 1/2" MIN. (TYP)
#4 LAP BAR
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.4621 www.crwarchitecture.com
CLIENT
100% CDs 02/12/261
Au to de sk
D oc s:
//R
PS
J
M G re en ho us e/
-0
R
PS
J M
G re en ho us e
.rv t
2/
/2
:0 1:
A
M
S1.00
02/13/2026
STRUCTURAL DETAILS
RO
CH
ES
TE
R M
IN
NE
SO
TA
RP
S
- J
OH
N M
AR
SH
AL
L
HI
GH
S
CH
OO
L
GR
EE
NH
OU
SE
R
EP
LA
CE
M
EN
T
25-070
02/12/2026
BW
NO. REVISIONS DATE
JS
A INTERMEDIATE WALL REMOVAL
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
B INTERMEDIATE WALL REPLACEMENT WITH PIERS
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
C INTERMEDIATE WALL ELEVATION
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
E CORNER WALL REMOVAL
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
F CORNER WALL RELACEMENT WITH PIERS
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
D 12 INCH CMU TO EXISTING CONCRETE PIER
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
G CORNER CMU TO EXISTING CONCRETE PIER
ORIGINAL SCALE: 3/4" = 1'-0"S1.00
GENERAL STRUCTURAL NOTES
1. These notes do not replace the specifications but are to be read in conjunction with them. Any discrepancies or conflicts between the two shall be brought to the attention of the Structural Engineer of Record (SER) for resolution.
2. These drawings are for the RPS John Marshall High School Greenhouse Replacement project (CRW #25-070) and no other use is authorized. Contact SER, Benjamin A. Wolf at SEH 507-316-6648.
GOVERNING BUILDING CODE:
2020 Minnesota State Building Code 2018 International Building Code as adopted and amended by the state building code
DESIGN CODES AND STANDARDS:
ACI Manual of Concrete Practice ACI 318, 301 Building Code Requirements & Specifications for Structural Concrete ACI 530 / TMS 402 / ASCE 5 Building Code Requirements & Specifications for Masonry Structures AISC 360, 303 Specification for Structural Steel Buildings
DESIGN LOADS PER ASCE 7-16
Risk category II (occupied accessory structure outside main school building)
1. Live load:
Roof live load 20 PSF
2. Dead load:
Superimposed roof load 5 PSF
3. Snow loads:
Ground snow load 50 PSF Importance factor 1.0 Roof snow load 42 PSF + drifting & unbalanced Snow exposure factor 1.0 Thermal factor 1.2
(considering occasionally unheated) Rain loads n/a
4. Wind loads:
Wind speed (3 sec gust) 109 mph Wind exposure C Mean roof height 20 feet Kd 0.85 Kzt 1.0 G 0.85 (rigid building) Structure is: Enclosed Internal press coef +/-0.18
5. Seismic loads:
Site class D Ss 0.048 g S1 0.036 g Fa 1.6 Fv 2.4 Sds 0.051 g Sd1 0.058 g Ie 1.0 Seismic design category A
6. Soil criteria:
Allowable soil bearing pressure 1,500 PSF (assumed) Frost depth 42 inches (heated building)
DESIGN / CONSTRUCTION CRITERIA
1. The contractor shall verify dimensions and conditions before construction and notify the engineer of any discrepancies, inconsistencies, or difficulties affecting the work before proceeding.
2. All material, workmanship, and details shall be in accordance with typical competent construction practices, current manufacturer's recommendations, and all applicable codes and government regulations.
3. The contractor shall coordinate all disciplines, verifying size and location of all openings, whether shown on structural drawings or not, as called for on process, architectural, mechanical, electrical or other drawings. All conflicts, inconsistencies, or other difficulties affecting structural work shall be called to the architect and engineer's attention for direction before proceeding.
4. Equipment and structural anchor rod sizes, types, embedment, and patterns shall be verified with the manufacturer or fabricator. All anchor patterns shall be templated to ensure accuracy of placement.
5. The contractor shall supply all necessary temporary bracing, shoring, guying, or other means to avoid excessive stresses and to hold structural elements in place during construction.
6. Job site safety (including excavations) is the sole responsibility of the general contractor and their subcontractors.
7. The engineer is not responsible for construction means, methods, techniques or practices.
8. Standard or typical structural details are intended to illustrate design concepts and to specify material and required physical dimensions matching or similar to the referenced locations in the drawing set. Standard details apply whether or not they are cut on the drawings.
9. There is no provision for future vertical or horizontal expansion in the design.
EXISTING CONSTRUCTION
1. Before proceeding with any work within the existing facility, the contractor shall familiarize themself with existing structural and other conditions. It shall be the contractor's responsibility to design, provide, and erect all necessary bracing, shoring and other safeguards to maintain all parts of the existing work in a safe condition during the process of demolition and construction and to protect from damage those portions of the existing work which are to remain.
2. The contractor shall field verify the dimensions, elevations, etc. necessary for the proper construction and alignment of the new portions of the work to the existing work. The contractor shall make all measurements necessary for fabrication and erection of structural members. Any discrepancy shall be immediately brought to the attention of the engineer.
3. Any existing construction damaged in the removal of adjacent elements shall be replaced at the contractor's expense.
4. Where existing concrete elements are to be demolished and reinforcing is not required to remain, cut existing reinforcing flush with concrete to remain and coat with epoxy, unless covered with concrete in final construction.
FOUNDATIONS
1. CAUTION: Existing underground utilities may exist anywhere on the site. Notify owner and Gopher One-Call (800)
252-1166 (Minnesota) prior to disturbing any grade or excavation.
2. Structural foundations are existing foundation elements supporting an existing greenhouse building with the same general structural configuration. No significant change to foundation pressures is proposed.
3. Grading: where not specifically shown on the plans, it is intended that all excavated and backfilled areas shall be graded to slope away from buildings and other structures.
REINFORCING STEEL
1. All concrete is reinforced concrete unless specifically called out as unreinforced. Reinforce all concrete not otherwise shown with same steel as in similar sections or areas. All reinforcing steel shall be detailed, fabricated, and installed in accordance with the following standards and codes:
· ACI 315 "Details and detailing of concrete reinforcing”
· ACI 318 "Building code requirements for reinforced concrete"
· MSP2 "CRSI manual of standard practice"
2. All reinforcing steel shall conform to the requirements of ASTM A615 grade 60 steel. Reinforcing steel shall not be welded.
3. Clear minimum cover of concrete over reinforcing steel shall be as follows unless specifically noted otherwise:
· 3" Concrete placed against earth
· 3” Top mat of base slabs to receive waterstops at wall joint
· 2" All other concrete
4. Bar lap lengths in concrete and 90 degree end hooks shall be in accordance with the table below unless noted otherwise. This table lists class 'B' laps. For epoxy coated reinforcing steel, increase lap length by 50% with c-c bar spacing < 6db and cover to center of bar <3db, otherwise increase by 20%. For masonry reinforcing, use fc' = 3000 psi values.
5. Bars marked continuous, corner bars, and all vertical steel shall be lapped in accordance with table above at splices and embedments, unless shown otherwise. Splice top bars near midspan and splice bottom bars over supports, unless noted otherwise.
CONCRETE MASONRY
1. Concrete block used in exterior walls or load bearing walls shall meet the following minimum requirements:
· Masonry assembly f'm = 2,000 PSI
· Concrete masonry units: ASTM C90-11A 2,000 PSI
· Mortar, ASTM C-270-10 Type S UNO
· Grout, ASTM C-476-10 f'g = 3,000 PSI, Slump: 8-11 inches
2. The contractor shall provide adequate temporary bracing for all masonry walls during construction.
3. Concrete block shall be laid in running bond pattern typical unless noted otherwise. No vertical (head) joint shall be continuous for more than one block height. Lay hollow concrete masonry units with full mortar coverage on horizontal and vertical face shells. Bed webs in mortar in starting course on footings and foundation walls and in all courses of piers, columns and pilasters, and where adjacent to cells or cavities which are to be reinforced or to be filled with concrete or grout.
4. Masonry piers shall be laid up in running bond in each direction to provide a monolithic unit.
5. All joints shall be concave tooled joints above and below grade.
6. Masonry walls shall be reinforced with hot dipped galvanized truss horizontal reinforcing (per ASTM A153) with 9 gage side and cross rods. Reinforcing shall be continuous in horizontal joints every other block course (16 inches OC) in walls, every course (8 inches OC) in parapets, with prefabricated corner and tee sections.
7. Continuous horizontal bars shall be included per section or detail in bond beam where noted. Where not detailed, use (2) #5 continuous. Where bond beams are continuous at corners of walls, supply corner bars matching size of horizontal bars. All bond beam reinforcing shall have standard laps or hooked development reinforcing bars at wall corners and intersections.Vertical reinforcing shall be a minimum of (1) #5 bar in 6" and 8" walls and (2) #4 bars in 10" and 12" walls at 4'-0" on center.
8. Grouting and reinforcing: all masonry, grouting, and reinforcing work shall be performed by mason craft workers who have successfully completed the International Masonry Institute (1-800-IMI -0988) training course for grouting and reinforced masonry construction, or equal
9. When grouting is stopped for more than one hour, stop grout approximately 1 ½ inches below top of CMU to provide key.
10. Masonry block cells with vertical reinforcing and bond beams with horizontal reinforcing shall be grouted solid.
Mortar is not an acceptable corefill. Provide a cleanout hole at the base of all grouted cells where grout lift exceeds 5'-4”. Account for fly ash in grout during winter construction by protecting and heating as required to assure set and strength gain.
11. Unless otherwise covered on architectural plans or specifications, vertical control joints in masonry construction shall be 3/8" wide, full height of wall. Joints shall be spaced at a maximum of 16' -0" on center and coordinated with the architect/engineer. Install control joints in locations as required and as directed by engineer/architect.
12. All horizontal joint reinforcing shall be discontinuous at control joints in masonry. All bond beam horizontal reinforcing shall be continuous through control joints.
13. Walls shall be anchored at bottom by dowels to existing hollow concrete masonry cores in existing masonry foundation below grade. Clean mortar, corefill insulation, and debris from cores to be reinforced and grouted. If grouted existing cores are encountered, shift new reinforcing by 8” either direction to provide average spacing indicated in details.
14. Masonry piers shall be anchored at bottom by adhesive anchors dowels to existing concrete foundation below grade. See details for minimum edge distance required at adhesive anchors.
15. Continuity bond beams may be, and upper courses of multi-course bond beams shall be, flow through block.
POST INSTALLED ANCHOR RODS AND DOWELS
1. Unless noted otherwise, anchors and reinforcing dowels installed in concrete or concrete masonry shall be as noted below. Anchors not shown or noted on the drawings, those required by the contractor solely for his means and methods, or those required by mechanical/electrical and carrying less than 100 pounds of non-safety-related items, do not require special inspection.
2. Approved manufacturers are: HILTI, ITW / Redhead, Simpson, and Powers / Rawl. Submit product data and current ICC ES report or IAPMO report showing product is compliant with project code requirements for review.
Contractor shall arrange for manufacturer's rep to train all installers on the complete installation process. A letter of procedure stating method of drilling, the product for use, the complete installation procedure, manufacturer training date and a list of the personnel trained on anchor installation shall be submitted to the engineer.
3. Permanent anchors exposed to earth, weather, or corrosive environments and anchors engaging stainless steel or aluminum members, shall be stainless steel type 304 or 316. Reinforcing dowels shall be of the same size (U.N.O.), material and coating (if any) as the continuing reinforcing.
4. Where expansion anchors are called for, contractor may substitute screw type anchors with self-tapping threads or adhesive anchors of the same size and embedment, subject to review of capacity by the engineer for the product substituted. Where adhesive anchors are called for, other types shall not be substituted. Screw type anchors shall not be re-used on permanent work.
5. Adhesive shall have a current ICC ES report. Use high viscosity adhesive and placement devices in consultation with the manufacturer for overhead work. Overhead installation shall be subject to continuous special inspection during installation and shall only be performed by certified adhesive anchor installers. Use low temperature formulations for cold weather work. Do not apply significant load to anchors until their capacity has been assured.
6. Anchors installed in concrete masonry and precast hollow core concrete shall be installed in cores grouted solid.
Minimum grout strength f'g = 3,000 PSI. Minimum 12 inches of grout each way along horizontal cores from anchor.
Vertical cores shall be grouted full height. Anchors installed in masonry shall not be installed within 1 1/2 inches of any head joint unless block are square end and mortared across full width of head joint, or filled bond beam.
7. Holes shall be drilled, cleaned, and maintained until installation in accordance with manufacturer's recommendations using standard rotary-impact bits and oil-free compressed air; diamond core bits shall not be used unless specifically approved by the manufacturer. Locate and avoid reinforcing bars and PT tendons.
Maintain spacing (minimum 8 inches) and edge/corner distances (minimum 4 inches) as recommended by manufacturer unless specifically noted otherwise in the drawings.
8. Unless noted otherwise, anchors shall be installed to the following embedments:
Diameter CIP Concrete Grouted CMU
Expansion/screw: 1/2 inch 3 1/2 inches 4 1/2 inches 5/8 inch 4 inches 5 inches 3/4 inch 5 inches 6 inches
Adhesive: 1/2 inch 4 1/2 inches 5 1/2 inches 5/8 inch 5 inches 6 inches 3/4 inch 6 inches 7 inches (6” in 8” CMU)
9. Except as noted, all anchors shall have intermittent special structural inspection by one of the following.
a. Expansion and screw anchors:
· Witness installation with torque wrench according to manufacturer's recommendations and requirements of ICC report;
· Test all anchors with torque wrench after installation (including load test of 5 percent of installed anchors); or
b. Adhesive anchor rods and dowels:
· Witness installation according to manufacturer's recommendations and requirements of ICC report; or
FABRICATED ENGINEERED STRUCTURES (GREENHOUSE)
1. Provide rigid-frame or braced frame aluminum greenhouse structure according to drawings, specifications, the
State Building Code. Where any of these conflict, the more stringent criteria shall be applied. General contractor shall supply full set of architectural and structural drawings to pre-engineered structure supplier.
2. Unless galvanized, all metal shall be aluminum.
3. Building manufacturer shall provide all girts, purlins, wall and roof frames and glazing, flashing, bracing, and other components required for a complete system; with the exception of anchor rods, which shall be supplied and installed by the General Contractor.
4. Maximum lateral deflection under load combinations including full code wind load (before factoring per ASCE-7) shall not exceed height/120 at eave. Deflection calculations shall use only the stiffness of the bare frame and bracing.
5. Manufacturer shall provide final vertical and horizontal reactions to the engineer prior to proceeding with fabrication.
6. Greenhouse manufacturer shall review architectural and structural foundation drawings and shall design structural mainframe anchors with minimum 4” clear distance from edges of masonry piers. Secondary components may be secured with minimum 2” clear distance from edges of masonry wall.
SHOP DRAWING REVIEW
1. Short Elliott Hendrickson Inc. (SEH) will review the general contractor's (GC) shop drawings and related submittals
(as indicated below) with respect to the ability of the detailed work, when complete, to be a properly functioning integral element of the overall structural system designed by SEH. In general, submittals will not be reviewed for correct quantities or construction considerations. SEH shall review shop drawings and related materials with comments provided that each submission has met the requirements herein. SEH shall return without comment unrequired material or submissions without GC approval stamp
2. Any items requiring submittal of calculation packages shall have calculations submitted prior to or as part of the shop drawing submittal they accompany. Shop drawings submitted prior to submittal of required calculations will be rejected. All calculations shall be sealed and signed by an engineer licensed in the state of the project. The supplier's engineer must provide calculations for all systems and connections that differ from the drawings. Design shall comply with the requirements in these notes, the drawings and the specifications.
3. Prior to submittal of a shop drawing or any related material to SEH, the GC shall:
· Review each submission for conformance with the means, methods, techniques, sequences and operations of construction and safety precautions and programs incidental thereto, all of which are the sole responsibility of the GC.
· Review and approve each submission.
· Stamp each submission as approved.
4. SEH shall assume that no submission comprises a variation from the contract documents unless the GC advises SEH with written documentation. Should SEH require more than ten (10) working days to perform the review, SEH shall so notify the GC. Submittals shall include drawings and related material (if any) as indicated below.
· Masonry grout designs and material certificates including admixtures, compounds applied to the concrete after placement, and associated product data.
· Aggregate tests and concrete test history for each mix design, with the submission of masonry grout mix designs.
· Concrete masonry (CMU) block material certifications and samples for review by architecture. Structural steel and metal fabrication shop drawings including erection drawings and piece details.
· Fabricated engineered structure drawings and design calculations.
SPECIAL INSPECTION
1. Special Iinspection and testing is required according to the table below. Refer to specification section 01 45 10 for responsibilities. Contractor shall coordinate with SER, testing agency and geotechnical engineer throughout the project.
· Special Inspections shall be performed in accordance with IBC Chapter 17.
· Special Inspection of reinforcing steel and anchor rod placement shall be performed prior to concrete or grout placement or during anchor rod installation for adhesive anchors.
· Continuous inspection during masonry rebar installation and grouting is required. Inspector will confirm that existing cores are clear of debris prior to grouting.
· Continuous inspection of post-Installed anchors and rebar is required.
· It is assumed that shop welding will be performed on the premises of a fabricator registered and approved to perform such work without Special Inspection. G/C shall submit fabricator documents, standards, and procedures in accordance with IBC 1705.2.
· Reports of Special Inspections shall be provided, at the frequency noted above, to the Owner, Contractor, and Engineer of Record by the firm contracted to perform Special Inspections.
· Special Inspection criteria presented above and in specification shall apply to all footings and foundation walls, but does not apply to non-structural slab on grade and site work concrete.
#3
#4
#5
#6
#7
#8
#9
#10
#11
19 IN
25 IN
31 IN
37 IN
54 IN
62 IN
70 IN
78 IN
86 IN
24 IN
32 IN
40 IN
48 IN
70 IN
80 IN
90 IN
102 IN
113 IN
28 IN
37 IN
46 IN
56 IN
81 IN
93 IN
104 IN
117 IN
130 IN
36 IN
48 IN
60 IN
72 IN
105 IN
120 IN
135 IN
152 IN
169 IN
6 IN
8 IN
10 IN
12 IN
14 IN
16 IN
18 IN
20 IN
22 IN
REINF.
BAR SIZE BAR LAP * TOP BAR
90 DEGREE
END HOOKBAR LAP * TOP BAR
BEAMSWALL, COLUMN OR SLAB
* Denotes top bar splices: Horizontal reinforcement placed such that more than 12 inches of concrete is cast in the member below the splice.
METAL CONSTRUCTION
1. WELDING
2. DETAILS: BRACING, LOCATIONS, ETC.
3. BOLTING
4. OPEN-WEB STEEL JOISTS AND JOIST GIRDERS
5. STEEL DECK INCLUDING WELDING OR MECHANICAL FASTENING
6. COMPOSITE CONSTRUCTION INCLUDING HEADED STUD ANCHORS
CONCRETE CONSTRUCTION
3. INSPECT ANCHORS CAST IN CONCRETE
5. VERIFY USE OF REQUIRED DESIGN MIX (GROUT)
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS
FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT
TESTS, AND DETERMINE THE TEMPERATURE OF THE CONCRETE
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
1. INSPECT REINFORCEMENT
4. INSPECT ANCHORS POST-INSTALLED IN CONCRETE
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES
9. INSPECT PRESTRESSED CONCRETE MEMBERS
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS
11. VERIFY IN-SITU CONCRETE STRENGTH PRIOR TO
POST-TENSIONING CONCRETE AND PRIOR TO REMOVAL OF
SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED
MASONRY CONSTRUCTION - LEVEL A
MASONRY CONSTRUCTION - LEVEL B
1. VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS
2. PRISMS
1. REINFORCEMENT: SIZE AND SPACING
3. DETAILS: GROUTING, LINTELS, ETC.
X X X
X
X X
X X
X X X
X X X
X
X X
X X
X
X
X X X
X X
XX
X
X X
7. COLD FORMED STEEL TRUSSES SPANNING > 60FT
2. REINFORCING BAR WELDING
X
X
X
DESCRIPTION OF WORK PER IBC CHAPTER 17
INSPECTION
FREQUENCY
CO
NT
IN
UO
US
PE
RI
OD
IC
TESTING
YES NO
N/A
REQUIRED SPECIAL INSPECTION AND TESTS
BENJAMIN A. WOLF
40807
MECHANICAL SYMBOLS LEGEND
DESIGNATIONSSYMBOLDESIGNATIONSSYMBOLDESIGNATIONSSYMBOL DESIGNATIONSSYMBOL
PLUMBING
ACID VENT
ACID WASTE
DEIONIZED WATER SUPPLY
FILTERED WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. INDICATED)
DOMESTIC RECIRC. HOT WATER
HARD COLD WATER
OVERFLOW STORM DRAIN
REVERSE OSMOSIS WATER
SANITARY VENT
SANITARY WASTE
SOIL DRAINAGE TILE
SOFTENED COLD WATER
SOFTENED HOT WATER
TEMPERED WATER
STORM DRAIN
WELL WATER
AV
AW
DIS
HARD
SDT
RO
V
W
SOFT
SHW
TW
OSD
SD
WW
NPCW NON-POTABLE COLD WATER
NPHW NON-POTABLE HOT WATER
FW
HW
RHW
GW GREASE WASTE
DOMESTIC COLD WATERCW
CLEAR WATER VENTCWV
CLEAR WATER WASTECWW
DOM. RECIRC. HOT WATER (TEMP. INDICATED)140 RHW
PUMPED ACID WASTEPAW
PUMPED STORMPSD
PUMPED WASTEPW
COMPRESSED AIR (PSI INDICATED)10#A
MECHANICAL PIPING
BOILER FEED
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FUEL OIL FILL
GLYCOL SUPPLY
GLYCOL RETURN
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
LIQUIFIED PETROLEUM GAS
NATURAL GAS (PSI INDICATED)
PUMPED CONDENSATE
RADIATION WATER SUPPLY
RADIATION WATER RETURN
REFRIGERANT LIQUID
BF
CWS
CWR
CD
FOS
GS
GR
HRS
HRR
HWR
HWS
LPG
2#G
FOF
PC
RADS
CS
CR
FOR
FOV
RADR
RL
REFRIGERANT SUCTION
REFRIGERANT HOT GAS BYPASS
REHEAT WATER SUPPLY
REHEAT WATER RETURN
REMOTE RADIATOR SUPPLY
REMOTE RADIATOR RETURN
SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURN
SNOW MELT SUPPLY
SNOW MELT RETURN
STEAM SUPPLY (PSI INDICATED)
STEAM CONDENSATE (PSI INDICATED)
RRS
RS
RHG
RHR
RHS
RRR
SHWS
SHWR
SMS
SMR
10#STM
10#SC
PIPE FITTINGS
ELBOW DOWN
PIPE CAP
ELBOW UP
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, TOP
ECCENTRIC REDUCER
CONCENTRIC REDUCER
MEDICAL GAS
MEDICAL VACUUM
WASTE ANESTHETIC GAS DISPOSAL
CARBON DIOXIDE
OXYGEN
NITROGEN
NITROUS OXIDE
MEDICAL AIR
WAGD
CO2
O
N
MV
N2O
MA
PIPE UNION
PIPE FLANGE
ELBOW
TEE
FIRE PROTECTION
DFP
F FIRE PROTECTION
FIRE PROTECTION (DRY SYSTEM)
POST INDICATOR VALVE (PIV)
RECESSED FIRE DEPT CABINET
SURFACE MOUNTED FIRE DEPT CABINET
FIRE PROTECTION RISER
UPRIGHT SPRINKLER HEAD W/GUARD
PENDANT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
BUTTERFLY VALVE W/TAMPER SWITCH
DETECTOR CHECK W/BYPASS METER
GRADE FIRE DEPT CONNECTION
FLUSH FIRE DEPT CONNECTION
FIRE DEPT VALVE W/CAP AND CHAIN
O.S. & Y. VALVE W/TAMPER SWITCH
DRY PIPE VALVE
PREACTION VALVE
TS
FDVC
FDVC
FDV
TS
ANNOTATION
(4)A-12"ø
GRILLE, REGISTER, &
DIFFUSER IDENTIFICATION
QUANTITY
CFM
TYPE
SIZE
X X
X X
X X
X X
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
EQUIP DESIGNATION
EQUIP NUMBER
POINT OF CONNECTION, NEW TO EXISTING
POINT OF DISCONNECTION
FTR/RP 01
6'-5"
0.5
HYDRONIC FINNED TUBE
RADIATION & RADIANT
PANEL IDENTIFICATION
TYPE ACTIVE
ELEMENT
LENGTHGPM
EBR 01
6'-5"
ELECTRIC BASEBOARD
RADIATION
IDENTIFICATION
ACTIVE
ELEMENT
LENGTH
ZONE VALVE BOXZVB
AREA ALARM PANELAAP
COMBINATION AREA/MASTER ALARM
PANEL
CAP
TYPE
INTERRUPTIBLE GASIG
PROCESS AND LABORATORY
LABORATORY AIR
LABORATORY VACUUM
ARGON
PROCESS WASTE
NITROGEN
HOUSE VACUUM
LV
AR
PRW
LA
N
HV
PROCESS VACUUMPV
INSTRUMENT AIRIA
ATMOSPHERIC STEAM SUPPLY
ATMOSPHERIC STEAM CONDENSATE
ATM STM
ATM SC
CONNECTION, BOTTOM
DARK DASHED LINE WEIGHT INDICATES
EXISTING ITEM TO BE DEMOLISHED.
GENERAL
LIGHT SOLID LINE WEIGHT INDICATES
EXISTING ITEM TO REMAIN.
DARK SOLID LINE WEIGHT INDICATES
NEW ITEM OR NEW LOCATION.
ROUND
12x12
12ø 12/12
RECTANGULAR (WxH)
FLAT-OVAL (W/H)
DUCT
DIMENSIONS
LIQUID NITROGENLN
MASTER ALARM PANELMAP
XXXX #-## EXISTING EQUIP NUMBER
EXISTING EQUIP DESIGNATION
MECHANICAL ABBREVIATIONS
AD AREA DRAIN
A.F.F. ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ANB ACID NEUTRALIZING BASIN
AP ACCESS PANEL
ARCH ARCHITECT
AS AIR SEPARATOR
BD BUTTERFLY DAMPER
B/G BELOW GRADE
BTU BRITISH THERMAL UNIT
BWV BACKWATER VALVE
CCF HUNDRED CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CO CLEAN OUT
CONTR CONTRACTOR
CONV CONVECTOR
CUH…