2._DSH-Atascadero_Med_Units_-_SFM_Approved_Specs.pdf
PDF 1 MB Posted
- Attached to
- Medication Dispensing Unit Installation
- Solicitation number
- 0000033682
- Issued by
- San Luis Obispo County, San Luis Obispo City, California
About this file
This document contains electrical specifications and standards approved by the Office of the State Fire Marshal (OSFM) on 09/01/24 for a Medication Dispensing Unit Installation project at DSH-Atascadero, prepared by J.C. Chang & Associates Inc. for the California Department of State Hospitals. The specifications detail comprehensive requirements for electrical and communications systems installation, including low-voltage power conductors, conduits, boxes, surface raceways, identification systems, wiring devices, and communications copper horizontal cabling. The project involves installing infrastructure to support medication dispensing units, with detailed requirements for Category 6a twisted pair cable installation, testing, and certification.
The specifications outline strict quality assurance requirements, including the need for BICSI-certified installers and Level IV testers, as well as detailed testing and documentation procedures. The document establishes specific product requirements from approved manufacturers like Allied Tube, Republic Conduit, Belden, and Superior Essex. While no direct pricing information is provided, the specifications require contractors to furnish extra materials for maintenance, including spare connecting blocks and patch panels. The document emphasizes coordination with existing building systems and includes requirements for protection of completed work, grounding systems, and firestopping of penetrations through rated assemblies.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11 January 2024 100% Submittal
JCCA #23790-8
MEDICATION DISPENSING UNIT INSTALLATION
DSH-ATASCADERO
ELECTRICAL SPECIFICATIONS
Prepared for:
DEPARTMENT OF STATE HOSPITALS
1215 O Street , 2ND Floor
Sacramento, California 95814
Phone: (916) 562-2314
Prepared by:
Architects � Engineers
385 Van Ness Avenue, Suite 208
Torrance, California 90501
Phone: (310) 212-7644 www.jccainc.com
OFFICE OF THE STATE FIRE MARSHAL
APPROVED FIRE AND PANIC ONLY
09/01/24
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans shall be available on the project site at all times.
24-0448 http://www.jccainc.com
J.C. Chang & Associates, Inc. Medication Dispensing Unit Installation JCCA No. 23790-8 DSH-Atascadero
TABLE OF CONTENTS 1
TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
Contractor to obtain Division 00 from the Owner.
000105 Certifications Page
DIVISION 01 - GENERAL REQUIREMENTS
Contractor to obtain Division 01 from the Owner.
DIVISION 26 - ELECTRICAL
260519 Low-Voltage Electrical Power Conductors and Cables 260529 Hangers and Supports for Electrical Systems
260533.13 Conduits for Electrical Systems
260533.16 Boxes and Covers for Electrical Systems
260533.23 Surface Raceways for Electrical Systems
260553 Identification for Electrical Systems 262726 Wiring Devices
DIVISION 27 - COMMUNICATIONS
270010 Supplemental Requirements for Communications 270528 Pathways for Communications Systems 271513 Communications Copper Horizontal Cabling
END OF TABLE OF CONTENTS
CERTIFICATIONS PAGE 000105 - 1
DOCUMENT 000105
CERTIFICATIONS PAGE
PROJECT TITLE: Medication Dispensing Unit Installation
CLIENT AGENCY: Department of State Hospitals
LOCATION: Department of State Hospitals - Atascadero
10333 El Camino Real Atascadero, CA 93422
PROJECT NUMBER: JCCA #23790-8
OWNER: STATE OF CALIFORNIA
PROJECT DIRECTOR: Joshua Kaiser
Chief Construction Manager
Department of State Hospitals
Phone: (916) 248-0015
Email: joshua.kaiser@dsh.ca.gov
CONSULTANT: J.C. Chang & Associates, Inc.
Sevag Avanessian, P.E.
ELECTRICAL ENGINEER
Date Signed: 1/11/24
CERTIFICATIONS PAGE 000105 - 2
THIS PAGE IS INTENTIONALLY LEFT BLANK
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1
SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Copper building wire.
2. Connectors and splices.
B. Related Requirements:
1. Section 271513 "Communications Copper Horizontal Cabling" for twisted pair cabling used for data circuits.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Copper building wire.
2. Connectors and splices.
B. Product Schedule: Indicate type, use, location, and termination locations.
1.3 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
PART 2 - PRODUCTS
2.1 COPPER BUILDING WIRE
A. Manufacturers:
1. Southwire.
2. Alpha Wire.
3. General Cable.
4. Or approved equal.
B. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2
C. Standards:
1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
2. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide."
D. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors.
E. Conductor Insulation:
1. Type THWN-2. Comply with UL 83.
F. Shield:
2.2 CONNECTORS AND SPLICES
A. Manufacturers:
1. 3M.
2. NSI Industries.
3. ILSCO.
4. O-Z/Gedney.
5. Or approved Equal.
B. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
C. Jacketed Cable Connectors: For steel and aluminum jacketed cables, zinc die-cast with set screws, designed to connect conductors specified in this Section.
D. Lugs: One piece, seamless, designed to terminate conductors specified in this Section.
1. Material: Copper.
2. Type: Two hole with long barrels.
3. Termination: Compression.
PART 3 - EXECUTION
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Branch Circuits:
1. Copper:
a. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3
b. Solid for No. 12 AWG and smaller; stranded for No. 10 AWG and larger.
B. ASD Output Circuits Cable: Extra-flexible stranded for all sizes.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND
WIRING METHODS
A. Exposed Branch Circuits, Including in Crawlspaces: Type THWN-2, single conductors in raceway.
B. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THWN-2, single conductors in raceway.
C. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:
Type THWN-2, single conductors in raceway.
D. ASD Output Circuits: Type XHHW-2 in metal conduit.
3.3 INSTALLATION, GENERAL
A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.
B. Complete raceway installation between conductor and cable termination points in accordance with Section 260533.13 "Conduits for Electrical Systems" prior to pulling conductors and cables.
C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.
F. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."
3.4 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A-486B.
B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 4
C. Wiring at Outlets: Install conductor at each outlet, with at least 12 inch of slack.
3.5 IDENTIFICATION
A. Identify and color-code conductors and cables according to Section 260553 "Identification for Electrical Systems."
B. Identify each spare conductor at each end with identity number and location of other end of conductor, and identify as spare conductor.
3.6 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and Cabling."
3.7 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to drawings.
3.8 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. After installing conductors and cables and before electrical circuitry has been energized, test conductors feeding the following critical equipment and services for compliance with requirements:
a. Medication Dispensing Units.
2. Perform each of the following visual and electrical tests:
a. Inspect exposed sections of conductor and cable for physical damage and correct connection according to the single-line diagram.
b. Test bolted connections for high resistance using one of the following:
1)A low-resistance ohmmeter.
2)Calibrated torque wrench.
3)Thermographic survey.
c. Inspect compression-applied connectors for correct cable match and indentation.
d. Inspect for correct identification.
e. Inspect cable jacket and condition.
f. Insulation-resistance test on each conductor for ground and adjacent conductors.
Apply a potential of 500 V(dc) for 300 V rated cable and 1000 V(dc) for 600 V rated cable for a one-minute duration.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 5
g. Continuity test on each conductor and cable.
h. Uniform resistance of parallel conductors.
B. Cables will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports to record the following:
1. Procedures used.
2. Results that comply with requirements.
3. Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.
END OF SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 6
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1
SECTION 260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Support, anchorage, and attachment components.
2. Fabricated metal equipment support assemblies.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for the following:
a. Slotted support systems, hardware, and accessories.
b. Clamps.
c. Hangers.
d. Sockets.
e. Eye nuts.
f. Fasteners.
g. Anchors.
h. Saddles.
i. Brackets.
2. Include rated capacities and furnished specialties and accessories.
B. Shop Drawings: For fabrication and installation details for electrical hangers and support systems.
1. Hangers. Include product data for components.
2. Slotted support systems.
3. Equipment supports.
1.3 INFORMATIONAL SUBMITTALS
A. Welding certificates.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2
PART 2 - PRODUCTS
2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. Steel Slotted Support Systems: Preformed steel channels and angles with minimum 13/32 inch diameter holes at a maximum of 8 inch on center in at least one surface.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. B-Line.
b. Caddy.
c. Unistrut.
2. Standard: Comply with MFMA-4 factory-fabricated components for field assembly.
3. Material for Channel, Fittings, and Accessories: Galvanized steel.
4. Channel Width: Selected for applicable load criteria.
5. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA- 4.
B. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.
C. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for nonarmored electrical conductors or cables in riser conduits. Plugs must have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body must be made of malleable iron.
D. Structural Steel for Fabricated Supports and Restraints: ASTM A36/A36M steel plates, shapes, and bars; black and galvanized.
E. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:
1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
a. Manufacturers:
1) Hilti.
2) ITW Ramset/Redhead.
3) MKT Fastening.
2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in hardened portland cement concrete, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
http://www.specagent.com/LookUp/?ulid=1736&mf=&src=wd http://www.specagent.com/LookUp/?ulid=1742&mf=&src=wd
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3
a. Manufacturers:
1) Hilti.
2) ITW Ramset/Redhead.
3) MKT Fastening.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units are similar to MSS
Type 18 units and comply with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58 units are suitable for attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM F3125/F3125M, Grade A325 (Grade A325M).
6. Toggle Bolts: All steel springhead type.
7. Hanger Rods: Threaded steel.
PART 3 - EXECUTION
3.1 SELECTION
A. Comply with the following standards for selection and installation of hangers and supports, except where requirements on Drawings or in this Section are stricter:
1. NECA NEIS 101
B. Comply with requirements in drawings for firestopping materials and installation for penetrations through fire-rated walls, ceilings, and assemblies.
C. Comply with requirements for raceways specified in Section 260533.13 "Conduits for Electrical
Systems."
D. Comply with requirements for boxes specified in Section 260533.16 "Boxes and Covers for
Electrical Systems."
E. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.
1. Secure raceways and cables to these supports with two-bolt conduit clamps.
F. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1-
1/2 inch and smaller raceways serving branch circuits and communication systems above suspended ceilings, and for fastening raceways to trapeze supports.
3.2 INSTALLATION OF SUPPORTS
A. Comply with NECA NEIS 101 for installation requirements except as specified in this article.
http://www.specagent.com/LookUp/?ulid=1742&mf=&src=wd
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4
B. Raceway Support Methods: In addition to methods described in NECA NEIS 1, EMT may be supported by openings through structure members, in accordance with NFPA 70.
C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits.
Minimum static design load used for strength determination must be weight of supported components plus 200 lb.
D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:
1. To Wood: Fasten with lag screws or through bolts.
2. To New Concrete: Bolt to concrete inserts.
3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units.
4. To Existing Concrete: Expansion anchor fasteners.
5. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock washers and nuts may be used in existing standard-weight concrete 4 inch thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than
4 inch thick.
6. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts.
7. To Light Steel: Sheet metal screws.
8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that comply with seismic-restraint strength and anchorage requirements.
E. Drill holes for expansion anchors in concrete at locations and to depths that avoid the need for reinforcing bars.
3.3 PAINTING
A. Touchup:
1. Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
a. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A780.
END OF SECTION 260529
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 1
SECTION 260533.13
CONDUITS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Type EMT-S duct raceways and elbows.
2. Type ERMC-S duct raceways, elbows, couplings, and nipples.
3. Fittings for conduit, tubing, and cable.
4. Electrically conductive corrosion-resistant compounds for threaded conduit.
B. Products Installed, but Not Furnished, under This Section:
1. See Section 260553 "Identification for Electrical Systems" for electrical equipment labels.
C. Related Requirements:
1. Section 260519 "Low-Voltage for Electrical Power Conductors and Cables" for nonmetallic underground conduit with conductors (Type NUCC).
1.2 DEFINITIONS
A. Conduit: A structure containing one or more duct raceways.
B. Duct Raceway: A single enclosed raceway for conductors or cable.
C. Duct Bank: An arrangement of conduit providing one or more continuous duct raceways between two points.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Type EMT-S duct raceways and elbows.
2. Type ERMC-S duct raceways, elbows, couplings, and nipples.
3. Fittings for conduit, tubing, and cable.
4. Electrically conductive corrosion-resistant compounds for threaded conduit.
1.4 INFORMATIONAL SUBMITTALS
A. Manufacturers' Published Instructions:
1. Type EMT-S duct raceways and elbows.
2. Type ERMC-S duct raceways, elbows, couplings, and nipples.
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 2
3. Fittings for conduit, tubing, and cable.
4. Electrically conductive corrosion-resistant compounds for threaded conduit.
PART 2 - PRODUCTS
2.1 TYPE EMT-S DUCT RACEWAYS AND ELBOWS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN FJMX; including UL 797.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL FJMX - Steel Electrical Metal Tubing (EMT-S) and Elbows:
1. Manufacturers:
a. Allied Tube and Conduit.
b. Republic Conduit.
c. Western Tube.
d. Or approved equal.
2. Material: Steel.
3. Options:
a. Exterior Coating: Zinc.
b. Interior Coating: Zinc with organic top coating.
c. Minimum Trade Size: Metric designator 21 (trade size 3/4).
2.2 TYPE ERMC-S DUCT RACEWAYS, ELBOWS, COUPLINGS, AND NIPPLES
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DYIX; including UL 6.
B. Source Quality Control:
http://www.specagent.com/LookUp/?ulid=13807&mf=&src=wd
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 3
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DYIX - Galvanized-Steel Electrical Rigid Metal Conduit (ERMC-S-G), Elbows, Couplings, and Nipples:
1. Manufacturers:
a. Allied Tube and Conduit.
b. Republic Conduit.
c. Western Tube.
d. Or approved equal.
2. Exterior Coating: Zinc.
3. Options:
a. Interior Coating: Zinc with organic top coating.
b. Minimum Trade Size: Metric designator 21 (trade size 3/4).
2.3 FITTINGS FOR CONDUIT, TUBING, AND CABLE
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DWTT - Fittings for Type ERMC Duct Raceways:
1. Manufacturers:
a. Allied Tube and Conduit.
b. Republic Conduit.
c. Western Tube.
d. Or approved equal.
2. Listing Criteria: UL CCN DWTT; including UL 514B.
3. Options:
a. Material: Steel.
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 4
b. Coupling Method: Compression coupling.
c. Expansion and Deflection Fittings: UL 651 with flexible bonding jumper.
D. UL FKAV - Fittings for Type EMT Duct Raceways:
1. Manufacturers:
a. Allied Tube and Conduit.
b. Republic Conduit.
c. Western Tube.
d. Or approved equal.
2. Listing Criteria: UL CCN FKAV; including UL 514B.
3. Options:
a. Material: Steel.
b. Coupling Method: Compression coupling.
c. Expansion and Deflection Fittings: UL 651 with flexible bonding jumper.
2.4 ELECTRICALLY CONDUCTIVE CORROSION-RESISTANT COMPOUNDS FOR
THREADED CONDUIT
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN FOIZ; including UL Subject 2419.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL FOIZ - Electrically Conductive Corrosion-Resistant Compound for Threaded Conduit:
1. Manufacturers:
a. Allied Tube and Conduit.
b. Republic Conduit.
c. Western Tube.
d. Or approved equal.
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 5
PART 3 - EXECUTION
3.1 SELECTION OF CONDUITS FOR ELECTRICAL SYSTEMS
A. Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with NFPA 70 for selection of duct raceways. Consult Architect for resolution of conflicting requirements.
B. Indoors:
1. Exposed and Subject to Severe Physical Damage: ERMC. Locations include the following:
a. Loading docks.
b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.
c. Mechanical rooms.
d. Gymnasiums.
2. Exposed and Subject to Physical Damage: ERMC. Locations include the following:
a. Locations less than 2.5 m (8 ft) above finished floor.
b. Stub-ups to above suspended ceilings.
3. Exposed and Not Subject to Physical Damage: EMT.
4. Concealed in Ceilings and Interior Walls and Partitions: EMT.
5. Damp or Wet Locations: ERMC.
C. Duct Fittings: Select fittings in accordance with NEMA FB 2.10 guidelines.
1. ERMC: Provide threaded-type fittings unless otherwise indicated.
3.2 INSTALLATION OF CONDUITS FOR ELECTRICAL SYSTEMS
A. Comply with manufacturer's published instructions.
B. Reference Standards for Installation: Unless more stringent installation requirements are specified in Contract Documents or manufacturers' published instructions, comply with the following:
1. Type EMT-S: Article 358 of NFPA 70 and NECA NEIS 101.
2. Type ERMC-S: Article 344 of NFPA 70 and NECA NEIS 101.
3. Expansion Fittings: NEMA FB 2.40.
4. Consult Architect for resolution of conflicting requirements.
C. Special Installation Techniques:
1. General Requirements for Installation of Duct Raceways:
a. Complete duct raceway installation before starting conductor installation.
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 6
b. Provide stub-ups through floors with coupling threaded inside for plugs, set flush with finished floor. Plug coupling until conduit is extended above floor to final destination or a minimum of 2 ft above finished floor.
c. Install no more than equivalent of three 90-degree bends in conduit run. Support within 12 inch of changes in direction.
d. Make bends in duct raceway using large-radius preformed ells except for parallel bends. Field bending must be in accordance with NFPA 70 minimum radii requirements. Provide only equipment specifically designed for material and size involved.
e. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines.
f. Support conduit within 12 inch of enclosures to which attached.
g. Install duct sealing fittings at accessible locations in accordance with NFPA 70 and fill them with listed sealing compound. For concealed duct raceways, install fitting in flush steel box with blank cover plate having finish similar to that of adjacent plates or surfaces. Install duct sealing fittings in accordance with NFPA 70.
h. Install devices to seal duct raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal interior of duct raceways at the following points:
1) Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces.
2) Where an underground service duct raceway enters a building or structure.
3) Conduit extending from interior to exterior of building.
4) Conduit extending into pressurized duct raceway and equipment.
5) Conduit extending into pressurized zones that are automatically controlled to maintain different pressure set points.
6) Where otherwise required by NFPA 70.
i. Do not install duct raceways or electrical items on "explosion-relief" walls or rotating equipment.
j. Do not install conduits within 2 inch of the bottom side of a metal deck roof.
k. Keep duct raceways at least 6 inch away from parallel runs of flues and steam or hot-water pipes. Install horizontal duct raceway runs above water and steam piping.
l. Cut conduit perpendicular to the length. For conduits metric designator 53 (trade size 2) and larger, use roll cutter or a guide to make cut straight and perpendicular to the length. Ream inside of conduit to remove burrs.
m. Install pull wires in empty duct raceways. Provide polypropylene or monofilament plastic line with not less than 200 lb tensile strength. Leave at least 12 inch of slack at both ends of pull wire. Cap underground duct raceways designated as spare above grade alongside duct raceways in use.
n. Install duct raceways square to the enclosure and terminate at enclosures without hubs with locknuts on both sides of enclosure wall. Install locknuts hand tight, plus one-quarter turn more.
1) Termination fittings with shoulders do not require two locknuts.
o. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to metric
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 7
designator 35 (trade size 1-1/4) and insulated throat metal bushings on metric designator 41 (trade size 1-1/2) and larger conduits terminated with locknuts..
2. Types ERMC:
a. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound that maintains electrical conductivity to threads of duct raceway and fittings before making up joints. Follow compound manufacturer's published instructions.
3. Duct Raceways Embedded in Slabs:
a. Run duct raceways larger than metric designator 27 (trade size 1) below concrete slab.
b. Arrange duct raceways to cross building expansion joints with expansion fittings at right angles to the joint.
c. Arrange duct raceways to ensure that each is surrounded by minimum of 1 inch of concrete without voids.
d. Do not embed threadless fittings in concrete unless locations have been specifically approved by Architect.
4. Stub-ups to Above Recessed Ceilings:
a. Provide EMT or ERMC for duct raceways.
b. Provide a conduit bushing or insulated fitting to terminate stub-ups not terminated in hubs or in an enclosure.
5. Duct Raceway Terminations at Locations Subject to Moisture or Vibration:
a. Provide insulating bushings to protect conductors, including conductors smaller than 4 AWG.
6. Duct Fittings: Install fittings in accordance with NEMA FB 2.10 guidelines.
a. EMT: Provide compression fittings. Comply with NEMA FB 2.10.
7. Expansion-Joint Fittings:
a. Install in runs of aboveground ERMC and EMT conduit that are located where environmental temperature change may exceed 100 deg F and that have straight-run length that exceeds 100 ft.
b. Install type and quantity of fittings that accommodate temperature change listed for the following locations:
1) Indoor Spaces Connected with Outdoors without Physical Separation:
125 deg F temperature change.
2) Attics: 135 deg F temperature change.
c. Install fitting(s) that provide expansion and contraction for at least 0.00041 inch per foot of length of straight run per deg F of temperature change for PVC conduits. Install fitting(s) that provide expansion and contraction for at least
0.000078 inch per foot of length of straight run per deg F of temperature change for metal conduits.
d. Install expansion fittings at locations where conduits cross building or structure expansion joints.
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 8
e. Install expansion-joint fitting with position, mounting, and piston setting selected in accordance with manufacturer's published instructions for conditions at specific location at time of installation. Install conduit supports to allow for expansion movement.
8. Duct Raceways Penetrating Rooms or Walls with Acoustical Requirements: Seal duct raceway openings on both sides of rooms or walls with acoustically rated putty or firestopping.
9. Identification: Provide labels for conduit assemblies, duct raceways, and associated electrical equipment.
a. Provide warning signs.
D. Interfaces with Other Work:
1. Coordinate installation of new products for medical dispensing units with existing conditions.
2. Coordinate with drawings for installation of firestopping at penetrations of fire-rated floor and wall assemblies.
3. Coordinate with Section 260529 "Hangers and Supports for Electrical Systems" for installation of conduit hangers and supports.
3.3 PROTECTION
A. Protect coatings, finishes, and cabinets from damage and deterioration.
1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.
2. Repair damage to paint finishes with matching touchup coating recommended by manufacturer.
END OF SECTION 260533.13
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 1
SECTION 260533.16
BOXES AND COVERS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Metallic outlet boxes, device boxes, rings, and covers.
2. Junction boxes and pull boxes.
3. Cover plates for device boxes.
B. Products Installed, but Not Furnished, under This Section:
1. See Section 260553 "Identification for Electrical Systems" for electrical equipment labels.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Metallic outlet boxes, device boxes, rings, and covers.
2. Junction boxes and pull boxes.
3. Cover plates for device boxes.
1.3 INFORMATIONAL SUBMITTALS
A. Manufacturers' Published Instructions:
1. Metallic outlet boxes, device boxes, rings, and covers.
2. Junction boxes and pull boxes.
3. Cover plates for device boxes.
PART 2 - PRODUCTS
2.1 METALLIC OUTLET BOXES, DEVICE BOXES, RINGS, AND COVERS
A. Performance Criteria:
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 2
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN QCIT; including UL 514A.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL QCIT - Metallic Outlet Boxes and Covers:
1. Description: Box having pryout openings, knockouts, threaded entries, or hubs in either the sides of the back, or both, for entrance of conduit, conduit or cable fittings, or cables, with provisions for mounting outlet box cover, but without provisions for mounting wiring device directly to box.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
3. Options:
a. Material: Sheet steel.
b. Sheet Metal Depth: Minimum 2.5 inch.
D. UL QCIT - Metallic Conduit Bodies:
1. Description: Means for providing access to interior of conduit or tubing system through one or more removable covers at junction or terminal point. In the United States, conduit bodies are listed in accordance with outlet box requirements.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
E. UL QCIT - Metallic Device Boxes:
1. Description: Box with provisions for mounting wiring device directly to box.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 3
c. Raco Taymac Bell.
3. Options:
a. Material: Sheet steel.
b. Sheet Metal Depth: minimum 2.5 inch.
F. UL QCIT - Metallic Extension Rings:
1. Description: Ring intended to extend sides of outlet box or device box to increase box depth, volume, or both.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
G. UL QCIT - Metallic Floor Boxes and Floor Box Covers:
1. Description: Box mounted in floor with floor box cover and other components to complete floor box enclosure.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
H. UL QCIT - Metallic Raised-Floor Boxes and Floor Box Covers:
1. Description: Box mounted in raised-floor with floor box cover and other components to complete floor box enclosure.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
I. UL QCIT - Metallic Recessed Access-Floor Boxes and Recessed Floor Box Covers:
1. Description: Floor box with provisions for mounting wiring devices below floor surface and floor box cover with provisions for passage of cords to recessed wiring devices mounted within floor box.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 4
c. Raco Taymac Bell.
J. UL QCIT - Metallic Concrete Boxes and Covers:
1. Description: Box intended for use in poured concrete.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
2.2 JUNCTION BOXES AND PULL BOXES
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. Listing Criteria: UL CCN BGUZ; including UL 50 and UL 50E.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL BGUZ - Indoor Sheet Metal Junction and Pull Boxes:
1. Description: Box with a blank cover that serves the purpose of joining different runs of raceway or cable.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
3. Options:
a. Degree of Protection: Type 1.
D. UL BGUZ - Indoor Cast-Metal Junction and Pull Boxes:
1. Description: Box with a blank cover that serves the purpose of joining different runs of raceway or cable.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 5
a. Crouse-Hinds.
b. Pass & Seymour.
c. Raco Taymac Bell.
3. Options:
a. Degree of Protection: Type 1.
2.3 COVER PLATES FOR DEVICES BOXES
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. Listing Criteria: UL CCN QCIT or UL CCN QCMZ; including UL 514D.
3. Wallplate-Securing Screws: Metal with head color to match wallplate finish.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL QCIT or QCMZ - Metallic Cover Plates for Device Boxes:
1. Options:
a. Damp and Wet Locations: Listed, labeled, and marked for location and use.
Provide gaskets and accessories necessary for compliance with listing.
b. Wallplate Material: 0.032 inch thick, Type 302/304 non-magnetic stainless steel with brushed finish.
D. UL QCIT or QCMZ - Nonmetallic Cover Plates for Device Boxes:
1. Options:
a. Damp and Wet Locations: Listed, labeled, and marked for location and use.
Provide gaskets and accessories necessary for compliance with listing.
b. Wallplate Material: 0.060 inch thick, high-impact thermoplastic (nylon) with smooth finish and color matching wiring device.
c. Color: Ivory.
PART 3 - EXECUTION
3.1 PREPARATION
A. Shop Drawings: Prepare and submit the following:
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 6
1. Shop Drawings for Floor Boxes: Show that floor boxes are located to avoid interferences and are structurally allowable. Indicate floor thickness where boxes are embedded in concrete floors and underfloor clearances where boxes are installed in raised floors.
3.2 SELECTION OF BOXES AND COVERS FOR ELECTRICAL SYSTEMS
A. Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with NFPA 70 for selection of boxes and enclosures. Consult Architect for resolution of conflicting requirements.
B. Degree of Protection:
1. Indoors:
a. Type 1 unless otherwise indicated.
b. Damp or Dusty Locations: Type 12.
c. Surface Mounted in Kitchens and Other Locations Exposed to Oil or Coolants:
Type 12.
d. Flush Mounted in Kitchens and Other Locations Exposed to Oil or Coolants:
Type 12.
e. Locations Exposed to Airborne Dust, Lint, Fibers, or Flyings: Type 4.
f. Locations Exposed to Hosedown: Type 4.
g. Locations Exposed to Brief Submersion: Type 6.
h. Locations Exposed to Prolonged Submersion: Type 6P.
i. Locations Exposed to Corrosive Agents: Type 4X.
j. Locations Exposed to Spraying Oil or Coolants: Type 13.
C. Exposed Boxes Installed Less Than 2.5 m (8 ft) Above Floor:
1. Provide cast-metal boxes.
2. Provide exposed cover. Flat covers with angled mounting slots or knockouts are prohibited.
3.3 INSTALLATION OF BOXES AND COVERS FOR ELECTRICAL SYSTEMS
A. Comply with manufacturer's published instructions.
B. Reference Standards for Installation: Unless more stringent installation requirements are specified in Contract Documents or manufacturers' published instructions, comply with the following:
1. Outlet, Device, Pull, and Junction Boxes: Article 314 of NFPA 70.
2. Consult Architect for resolution of conflicting requirements.
C. Special Installation Techniques:
1. Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting of devices or fixtures.
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 7
2. Mount boxes at heights indicated on Drawings. If mounting heights of boxes are not individually indicated, give priority to ADA requirements. Install boxes with height measured to top of box unless otherwise indicated.
3. Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block, and install box flush with surface of wall. Prepare block surfaces to provide a flat surface for a raintight connection between box and cover plate or supported equipment and box, whether installed indoors or outdoors.
4. Horizontally separate boxes mounted on opposite sides of walls so they are not in the same vertical channel.
5. Locate boxes so that cover or plate will not span different building finishes.
6. Support boxes in recessed ceilings independent of ceiling tiles and ceiling grid.
7. Support boxes of three gangs or more from more than one side by spanning two framing members or mounting on brackets specifically designed for purpose.
8. Fasten junction and pull boxes to, or support from, building structure. Do not support boxes by conduits.
9. Set metal floor boxes level and flush with finished floor surface.
10. Set nonmetallic floor boxes level. Trim after installation to fit flush with finished floor surface.
11. Do not install aluminum boxes, enclosures, or fittings in contact with concrete or earth.
12. Do not rely on locknuts to penetrate nonconductive coatings on enclosures. Remove coatings in the locknut area prior to assembling conduit to enclosure to ensure a continuous ground path.
13. Boxes and Enclosures in Areas or Walls with Acoustical Requirements:
a. Seal openings and knockouts in back and sides of boxes and enclosures with acoustically rated putty.
b. Provide gaskets for wallplates and covers.
14. Identification: Provide labels for boxes and associated electrical equipment.
a. Identify field-installed conductors, interconnecting wiring, and components.
b. Provide warning signs.
c. Label each box with engraved metal or laminated-plastic nameplate.
D. Interfaces with Other Work:
1. Coordinate installation of new products with existing conditions.
3.4 CLEANING
A. Remove construction dust and debris from boxes before installing wallplates, covers, and hoods.
3.5 PROTECTION
A. After installation, protect boxes from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.
BOXES AND COVERS FOR ELECTRICAL SYSTEMS 260533.16 - 8
END OF SECTION 260533.16
SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS 260533.23 - 1
SECTION 260533.23
SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Surface metal raceways and fittings.
2. Strut-type channel raceways and fittings.
3. Wireways and auxiliary gutters.
B. Products Installed, but Not Furnished, under This Section:
1. See Section 260553 "Identification for Electrical Systems" for electrical equipment labels.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Surface metal raceways and fittings.
2. Strut-type channel raceways and fittings.
3. Wireways and auxiliary gutters.
1.3 INFORMATIONAL SUBMITTALS
A. Manufacturers' Published Instructions:
1. Surface metal raceways and fittings.
2. Strut-type channel raceways and fittings.
3. Wireways and auxiliary gutters.
PART 2 - PRODUCTS
2.1 SURFACE METAL RACEWAYS AND FITTINGS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS 260533.23 - 2
2. Listing Criteria: UL CCN RJBT; including UL 5.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL RJBT - Surface Metal Raceways and Fittings with Metal Covers:
1. Options:
a. Galvanized steel base with snap-on covers.
b. Manufacturer's standard enamel finish.
c. Wiring Channels: Single. Multiple channels must be capable of housing a standard 20 to 30 A device flush within the raceway.
2.2 STRUT-TYPE CHANNEL RACEWAYS AND FITTINGS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria:
a. UL CCN RIUU; including UL 5B.
b. UL 94, V-0 requirements for self-extinguishing characteristics.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
3. Samples:
a. Strut-Type Channel Raceway Nonmetallic Covers for Initial Selection:
Manufacturer's standard color sheets, showing full range of available colors for each type, 12 inch long.
C. UL RIUU - Strut-Type Channel Raceways and Fittings with Metallic Covers:
1. Options:
a. Manufacturer's standard enamel finish.
SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS 260533.23 - 3
D. UL RIUU - Strut-Type Channel Raceways and Fittings with Nonmetallic Covers:
1. Additional Characteristics: UL 94, V-0 requirements for self-extinguishing characteristics.
2.3 WIREWAYS AND AUXILIARY GUTTERS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria:
a. UL CCN ZOYX; including UL 870.
b. UL 94, V-0 requirements for self-extinguishing characteristics.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
3. Samples:
a. Nonmetallic Wireway and Auxiliary Gutter Samples for Initial Selection:
Manufacturer's standard color sheets, showing full range of available colors for each type, 12 inch long.
C. UL ZOYX - Metal Wireways and Auxiliary Gutters:
1. Additional Characteristics:
a. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.
b. Finish: Manufacturer's standard enamel finish.
2. Options:
a. Degree of Protection: Type 1 unless otherwise indicated.
b. Wireway Covers: Hinged type unless otherwise indicated.
PART 3 - EXECUTION
3.1 INSTALLATION OF SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
A. Comply with manufacturer's published instructions.
SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS 260533.23 - 4
B. Reference Standards for Installation: Unless more stringent installation requirements are specified in Contract Documents or manufacturers' published instructions, comply with the following:
1. Auxiliary Gutters: Article 366 of NFPA 70.
2. Surface Metal Raceway: Article 386 of NFPA 70.
3. Surface Nonmetallic Raceway: Article 388 of NFPA 70.
4. Consult Architect for resolution of conflicting requirements.
C. Special Installation Techniques:
1. Install surface raceways only where indicated on Drawings.
2. Install surface raceway with a minimum 2 inch radius control at bend points.
3. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inch and with no less than two supports per straight raceway section.
Support surface raceway in accordance with manufacturer's published instructions. Tape and glue are unacceptable support methods.
4. Identification: Provide labels for surface raceways and associated electrical equipment.
a. Identify field-installed conductors, interconnecting wiring, and components.
b. Provide warning signs.
D. Interfaces with Other Work:
1. Coordinate installation of new products for with existing conditions.
3.2 CLEANING
A. Remove construction dust and debris from surface raceways before installing covers.
3.3 PROTECTION
A. After installation, protect surface raceways from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.
END OF SECTION 260533.23
IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553 - 1
SECTION 260553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Labels.
2. Bands and tubes.
3. Tapes and stencils.
4. Tags.
5. Signs.
6. Cable ties.
7. Miscellaneous identification products.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for electrical identification products.
B. Delegated-Design Submittal: For arc-flash hazard study.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Comply with ASME A13.1 and IEEE C2.
B. Comply with NFPA 70.
C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145.
D. Comply with ANSI Z535.4 for safety signs and labels.
IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553 - 2
E. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969.
F. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes.
1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
2.2 COLOR AND LEGEND REQUIREMENTS
A. Raceways and Cables Carrying Circuits at 600 V or Less:
1. Black letters on an orange field.
B. Color-Coding for Phase Identification, 600 V or Less: Use colors listed below for ungrounded service and feeder conductors.
1. Color shall be factory applied.
2. Colors for 208/120-V Circuits:
a. Phase A: Black.
b.