This document is a product specification sheet for the CLX OnLine Residual Chlorine Monitor manufactured by HF scientific. The device is designed for monitoring chlorine levels in drinking water, wastewater, industrial, and marine applications, utilizing colorimetric DPD chemistry technology. Key features include a rugged NEMA 4X enclosure, user-selectable cycle times between 110 seconds and 10 minutes, a removable sample cuvette, and microprocessor-based technology.

The specifications detail a measurement range of 0-10 mg/l with ±5% accuracy for 0-6 mg/l and ±10% accuracy for 6-10 mg/l. The monitor includes standard 4-20 mA and RS-485 with Modbus outputs, two user-selectable alarm relays, and operates in temperatures from 0°C to 40°C. It is certified to CE, UL, and CSA standards, with dimensions of 325.74 x 311.11 x 128.50 mm and a shipping weight of 8 lbs. The catalog number for the complete monitor is 20040, with various accessories and reagent options available separately.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Reliable Chlorine Monitoring

Specifications HF scientific developed the CLX OnLine Residual Chlorine Monitor specifically for drinking water, wastewater, industrial and marine residual chlorine monitoring applications.

The CLX OnLine Residual Chlorine Monitor is manufactured using microprocessor based technology making it the most reliable and cost efficient instrument for monitoring residual chlorine.

Colorimetric DPD chemistry technology provides a proven, stable and reliable reading along with the most economical method available.

Features

• Colorimetric DPD Chemistry

Proven reliable and economical, colorimetric DPD (N,N-diethyl-p-phenylenediamine) chemistry is the most accurate method for measuring free or total residual chlorine.

• Rugged Enclosure The CLX's small footprint and corrosion resistant NEMA 4X (IP66) enclosure allows for a simple installation that will fit in almost any space.

• Optical Design New optical design uses similar optics to the hand held portable Chlorine Photometer. The new design increases accuracy and allows for comparable and precise readings between the OnLine Monitor and hand held portable instruments.

• Removeable Sample Cuvette A removeable sample cuvette allows for simple cleaning and maintenance. Viewable sample chamber allows a clear view of the sample cuvette while the instrument is sampling.

• Cycle Times User selectable cycle times allow the user to set the cycle time from 110 seconds up to 10 minutes (optional 60 seconds to 10 minutes). Low volume reagent and sample chamber allow for affordable reagent costs and decreases water consumption.

• Certification Listed or Certified to CE, UL, CSA (ETL,ETLc)

ES-HF-CLX

Online Chlorine Monitoring Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location ––––––––––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––

HF scientific product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact HF scientific Technical Service. HF scientific reserves the right to change or modify product design, construc-tion, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on HF scientific products previously or subsequently sold.

Changing the Sample Cuvette

Sample Specifications The Residual Chlorine Monitor shall be able to measure free or total chlorine using the DPD colorimetric method. The Chlorine Monitor shall have a measurement range of 0-10 mg/l. The Chlorine Monitor shall include the power supply, sensor and display in one NEMA 4X (IP66) corrosion resistant enclosure. The Chlorine Monitor shall have readings consistent with laboratory and portable Chlorine Photometers. The Chlorine Monitor shall have standard 4-20 mA outputs and RS-485 with Modbus Protocol. The 4-20 mA output shall be standard or reversible.

The Chlorine Analyzer shall have a removable sample cuvette.

The sensor shall have a clear view to the optical chamber allowing viewing of the sample and reaction of the reagents, before, during and after a reading. Accuracy shall be ±5% with a resolution of 0.01 mg/l for the range of 0-6 mg/l and ±10% with a resolution of 0.01 mg/l for the range of 6-10 mg/l.

The Chlorine Monitor shall have a user selectable cycle time between 110 seconds and 10 minutes (optional 60 seconds to 10 minutes). The Chlorine Monitor shall be capable of 30 days of unattended operation. The Chlorine Monitor shall take a zero reading before each reading to compensate for color in the sample. The Chlorine Monitor shall have microprocessor based technology. The Monitor shall have two user selectable alarm relays.

Range: 0 - 10 mg/l.

Cycle Time: User Selectable: 110 seconds to 10 minutes. (optional 60 seconds to 10 minutes)

Resolution: 0.01 mg/l

Accuracy: 0 - 6 mg/l - ±5% or 0.03 mg/l of Cl2 whichever is greater.

6 - 10 mg/l - ±10%

Method: USEPA accepted DPD method of analysis for measuring Free or Total Residual Chlorine

Standard Outputs: 4-20 mA and RS-485 with Modbus.

User Alarms: 2 User Selectable Alarms for Sample Concentration (Form C 240VAC 2A)

Operating Temperature: 0°C to 40°C (32°F to 104°F)

Input Pressure: 5 - 150psi

Enclosure: ABS Plastic, NEMA 4X, IP66

Power: 100 - 240 Volt Auto Switchable 47-63hz

Certifications: CE, UL, CSA, (ETL, ETLc)

Shipping Dimensions: 16" x 16" x 10" (41cm x 41cm x 26cm)

Shipping Weight 8lbs (3.6kg)

Ordering Information Catalog No. Description 20040 CLX OnLine Residual Chlorine

Monitor for Free or Total Chlorine Complete with operating manual. Re-agents must be purchased separately.

If the application combines high humidity with cold sample water, purchase a #09944 desiccant cartridge separately.

Accessories 09950 Replacement tubing/cuvette kit 25018S Flow through cuvette CLX 28316 Low pressure adapter

Changing the Reagents

J.A.W.* Liquid

Free Chlorine 30 day supply 09951 09947

Total Chlorine 30 day supply 09952 09948

Catalog No.

** User must add Sulfuric Acid, Soduim Hydroxide and supplied DPD reagent before use

*Just Add Water

All Dimensions are in millimeters (inches).

These 4 holes will accept up to 8 MM (5/16 inch) hardware

219.05 (8.625)

298.45 (11.75)

128.50 (5.06)

325.74 (12.82)

311.11 (12.25)

Rear View Side View

Front View

Dimensions

ES-HF-CLX 1726 © 2017 HF scientific

USA: T: (239) 337-2116 • Toll-Free (888) 203-7248 • F: (239) 332-7643 • HFscientific.com Latin America: T: (52) 81-1001-8600 • F: (52) 81-8000-7091 • HFscientific.com

Inlet Tube

1/4" NPT

Drain 1/2 inch I.D.

drain tubing

Buffer Reagent Bottle

Indicator Solution Bottle

Sample Cuvette Backlit - Reaction fully visible even with cover in place

LCD

Display

Pressure Regulator

RS-485 & 4-20 mA

Alarm Relays

Power

Latch

CLX with cover removed

Job Name field:
Job Location field:
Engineer field:
Approval field 1:
Contractor field:
Approval field 2:
Contractor P:
O:
No:
field:

Representative field:

File details come from the government source that posted it. Updated .