2.2.1 Attachment 6_GMP_CONUS July 2021.pdf
PDF 852 KB Posted
- Attached to
- CONUS Generator Maintenance Services Federal contract opportunity
- Solicitation number
- 70FB7022R00000008
- Issued by
- Federal Emergency Management Agency
About this file
This document contains a federal contract opportunity solicitation for on-site generator maintenance services. FEMA is seeking a single-award contract for maintenance including annual services, quarterly services, return to storage, and repairs for generators across the continental United States. The contract term is for up to five years with firm fixed pricing. Services include inspection, testing, repair, replacement of parts and filters, and load bank testing. The NAICS code is 811310 and PSC code is J030. The solicitation number is 70FB7022R00000008 with a response due date of August 19, 2022. This requirement is set aside for small businesses to respond. Interested parties must register in SAM and complete online representations and certifications through that system.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SIZE (kW):
MANUFACTURE:
DATE OF THIS SERVICE:
LOCATION OF SERVICE:
CURRENT READINESS STATUS
CURRENT PHYSICAL CONDITION
(SELECT):
LEVEL OF SERVICE (SELECT):
Quarterly Annual
& RTS
Every 3 Years
(Annual)
DISCONNECT Battery Cables / Master Battery Cutoff Switch P P
CHECK/CLEAN Battery terminals / battery hold down P P
CHECK/CLEAN Air filter(s) P P
INSPECT Coolant Leak P P
INSPECT Loose/worn belts/hoses P P
INSPECT Oil Leak P P
INSPECT
Turbocharger damage, mounts, connections, leaks, noises, wastegate P P
INSPECT
Turbo Charge Air Cooler piping leaks, signs of oil P P
INSPECT
Fuel Tank damage, leaks, caps/vents, hoses, quick-disconnects, sensor connectors P P
INSPECT Fuel Leak P P
INSPECT
Internal Fuel Tank - Drain if Fuel is present (if applicable) P P
INSPECT
All filters marked with date and run hours at replacement P P
INSPECT All gauges/meters P P
INSPECT Breaker(s)/lugs P P
INSPECT Frayed/Corroded Wiring P P
INSPECT Housing: damage, proper FEMA identification P P
INSPECT Loose Bolts/linkage/etc. Replace if missing P P
INSPECT Missing Parts/Nuts/Bolts P P
INSPECT Trailer/Chassis for damage P P
TEST Panel Lights P P
TEST Radiator Cap (Annual Pressure Test) P
LUBE/ADJUST Various linkages P P
CHECK Tension on belts P P
CHECK Exhaust components P P
CHECK Lube oil level P P
CHECK Silencer isolator mount P P
CHECK / ADD (IF NEEDED) Coolant fill level - add recharge if necessary P P
CHECK/ADJUST Output voltage/phase configuration P P
CHECK/ADJUST Governor P P
CLEAN Clean/remove all dirt/debris from gen/chassis P P
DRAIN Fuel / water separator P P
For CAT XQ1140, TWO GMP's are to be completed, indicating each engine either as Engine "A" (BC:
XXXXX-A) or Engine "B" (BC:
XXXXX-B)
NOTES
GENERATOR MAINTENACE PROFILE
IDENTIFICATION / CURRENT MAINTENANCE DATA
BARCODE (FEMA):
STATION OF ORIGIN (SELECT):
HOUR METER READING (@ START OF
SERVICE):
RUN UP HOUR METER READING (END):
CURRENT PHYSICAL CONDITION (SELECT)
Pre-existing damage:
GENERATOR MAINTENACE CHECKLIST - (TO BE COMPLETED AS SERVICES ARE RENDERED)
FEMA PWS REQUIRED GENERATOR MAINTNEANCE CHECKS & SERVICES - As per PWS Section 6: Services
CODE: (OK= No Problem; CS=Corrected to spec;
TF=Temporary Fix; PF=Permanent Fix; NA=Not Applicable;
XP=No replacement part available; XF=FEMA Waived
Repair; XX=Uncorrectable damage)
ACTION ITEM
LEVEL OF SERVICE REQUIRED
RFP: 70FB7022R00000008
Attachment 6: Generator Maintance Profile Sheet CONUS Generator Maintenance - October 2021
BARCODE (FEMA):
Quarterly Annual
& RTS
Every 2 or 3 Years
(Annual) FEMA
Will Advise
Timeline
DRAIN & REPLACE Lube Oil P
REPLACE Fuel filter(s) P
REPLACE Fuel/Water Separator P
REPLACE Oil filter(s) P
REPLACE
Air cleaner element(s) EVERY 2 Years OR as dictated by Fleet Management P
TEST, CHANGE IF NECESSARY
Coolant EVERY 3 Years OR as dictated by Fleet
Management P
ACTION ITEM
CODE
(OK= No Problem; CS=Corrected to spec; TF=Temporary
Fix; PF=Permanent Fix; NA=Not Applicable; XP=No replacement part available; XF=FEMA Waived Repair;
XX=Uncorrectable damage)
NOTES
INSPECT Power Balance Connections P P Re-torque only if deployed/used to manufacture specifications
TEST DEF Fluid Concentration P
TEST / DRAIN / REPLACE
DEF Fluid (test new DEF Fluid concentration
PRIOR to replacing in generator) P
CHANGE During Coolant Change - Bleed EGR Coolant
CLEAN Clean out Coolant Strainer P
CLEAN DEF Filter P
REPLACE Crankcase filter
BATTERY STATUS:
ESTOP STATUS:
BATTERY REPLACEMENT DATE:
FUEL FILTER PRIMARY: CRANKCASE (TIER 4 ONLY): 1,000 hours
LUBE OIL PRIMARY: Diesel Exhaust Fluid (DEF) (TIER 4 ONLY):
AIR (Every 2 years) PRIMARY:
COOLANT (IF NEEDED) / (Every 3 Years)
PRIMARY:
FUEL / WATER SEPARATOR PRIMARY:
DEF CONCENTRATION (TIER 4 ONLY) SET POINT:
CODE: SET POINT:
Communication Test between Generator & External Tank
PASS FAIL
INSPECT: DRAIN CODE:
ACTION
VOLTAGE CONFIGURATION AT TIME
OF LOAD TEST
STARTS (HOURS):
1-PHASE BREAKER FUNCTIONALITY STOP (HOURS):
3-PHASE BREAKER FUNCTIONALITY PASS
OUTPUT VOLTAGE STABILITY FAIL
OVERALL GENERATOR READINESS
FUEL TANK (EXTERNAL COMMUNICATION) (if applicable)
GOVERNMENT FINAL Q/A INSPECTOR:
NOTE ALL NEW DAMAGE / REPAIRS/ LOAD TEST FAILURES / NO-START
LOAD TEST RESULTS (CONDUCTED AT MAX CAPACITY)
Follow guidelines as stated in Section 6 of the PWS
SIGNATURE OF CONTRACTOR AND GOVERNMENT REPRESENATIVE
CONTRACTOR FINAL Q/A INSPECTOR:
NOTES
CODE: (OK= No Problem; CS=Corrected to spec;
TF=Temporary Fix; PF=Permanent Fix; NA=Not Applicable;
XP=No replacement part available; XF=FEMA Waived
Repair; XX=Uncorrectable damage)
LOAD BANK TESTED (90 MINUTES)CODE / VOLTAGE CONFIGURATION
SECONDARY:
SECONDARY:
TIER 4 SERVICE REQUIREMENT (APPLICABLE GENERATORS)
LEVEL OF SERVICE REQUIRED
BATTERY / ESTOP STATUS COOLANT / LUBE OIL
NEW COOLANT:
Every 1,000 hours
Coolant CHANGE ONLY
FILTERS (PART & MFG) TIER 4FINAL FILTERS ONLY:
LOAD TEST DETAILS (PERFORMED & COMPLETED UPON COMPLETION OF ALL OTHER SERVICES) CAT XQ1140's will have two (2) Load Bank Sheets completed & two (2) GMP's completed
FUEL TANK (EXTERNAL) (if applicable)
Readings:
SECONDARY:
COOLANT PROTECTION (Every 90 days)
NEW LUBE OIL (15w40):
GENERATOR MAINTENACE PROFILE (CONT)
ACTION ITEM
LEVEL OF SERVICE REQUIRED
OUTPUT VOLTAGE READINGS (Every 90 days) adjust if needed
SECONDARY:
SECONDARY:
FUEL TANK (INTERNAL)
FREEZE POINT:INSPECT: DRAIN
RFP: 70FB7022R00000008
Attachment 6: Generator Maintance Profile Sheet CONUS Generator Maintenance - October 2021
| Text4: |
| Text5: |
| Date2_af_date: |
| Dropdown3: [] |
| Dropdown4: [] |
| Dropdown5: [] |
| Dropdown6: [] |
| Dropdown7: [] |
| Dropdown8: [] |
| Dropdown9: [] |
| Date9_af_date: |
| Dropdown10: [] |
| Text11: |
| Check Box12: Off |
| Check Box13: Off |
| Check Box14: Off |
| Text15: |
| Text16: |
| Text17: |
| Text18: |
| Dropdown18: [] |
| Text19: |
| Text20: |
| Text21: |
| Text22: |
| Text23: |
| Text24: |
| Text25: |
| Text26: |
| Text27: |
| Text28: |
| Text29: |
| Text30: |
| Dropdown25: [] |
| Text31: |
| Text32: |
| Text33: |
| Text34: |
| Dropdown29: [] |
| Dropdown28: [] |
| Dropdown30: [] |
| Dropdown31: [] |
| Dropdown33: [] |
| Dropdown32: [] |
| Dropdown34: [] |
| Dropdown35: [] |
| Dropdown36: [] |
| Dropdown37: [] |
| Dropdown38: [] |
| Dropdown39: [] |
| Dropdown40: [] |
| Dropdown41: [] |
| Dropdown42: [] |
| Dropdown43: [] |
| Dropdown45: [] |
| Dropdown44: [] |
| Dropdown46: [] |
| Dropdown47: [] |
| Dropdown48: [] |
| Dropdown49: [] |
| Dropdown50: [] |
| Dropdown51: [] |
| Dropdown52: [] |
| Dropdown54: [] |
| Dropdown53: [] |
| Dropdown55: [] |
| Dropdown56: [] |
| Dropdown57: [] |
| Dropdown58: [] |
| Dropdown59: [] |
| Dropdown60: [] |
| Dropdown61: [] |
| Dropdown62: [] |
| Dropdown63: [] |
| Dropdown64: [] |
| Dropdown65: [] |
| Dropdown66: [] |
| Dropdown67: [] |
| Dropdown68: [] |
| Dropdown69: [] |
| Dropdown70: [] |
| Dropdown71: [] |
| Dropdown73: [] |
| Dropdown74: [] |
| Check Box15: Off |
| Dropdown72: [] |
| Dropdown75: [] |
| Text35: |
| 0: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 8: |
| 9: |
| 10: |
| 11: |
| 12: |
| 13: |
| 14: |
| 15: |
| 16: |
| 17: |
| 18: |
| 19: |
| 20: |
| 21: |
| 22: |
| 23: |
| 24: |
| 25: |
| 27: |
| 28: |
| 29: |
| 1: |
| 26: |
| Text36: |
| Text37: |
| Text38: |
| Text39: |
| Text40: |
| Text41: |
| Text42: |
| Text43: |
| Text44: |
| Text46: |
| Text45: |
| Text47: |
| Text48: |
| Text49: |
| Clear: |
| Technican Name: |
| Text50: |
| Text2: |
| Text3: |
| Size (kW): |
| Text51: |
File details come from the government source that posted it. Updated .