Elmwood Academy Lower Level HVAC Bid Set - Mechanical and Electrical Information Sheet

This document is a mechanical and electrical information sheet and bid set for the Mechanicsburg Area School District's Elmwood Academy Lower Level HVAC Upgrade project located at 100 East Elmwood Avenue, Mechanicsburg, Pennsylvania 17055. The project involves the installation of new mechanical equipment to provide temperature and climate control for the lower-level storage space, including a heat pump air handling unit (TRANE PVA-AA24NL), a condensing unit (TRANE PUZ-AK24NLHZ 2-ton), a dehumidification unit (QUEST 4044590), two circulation fans (QUEST 4042250-06), and a condensate pump (QUEST 4022220). The contract specifications require all work to comply with the International Mechanical Code, International Plumbing Code, International Energy Code, NEC 2020, IBC 2021, and IECC 2021, with contractors responsible for shop drawings, coordination drawings, and as-built documentation. Sealed bids are due April 21, 2026, at 12:00 p.m. via PennBid, with a pre-bid meeting scheduled for April 1, 2026, at 3:00 p.m. at the project site. Questions may be submitted through PennBid until April 10, 2026, at 3:00 p.m., and bidding documents became available on March 19, 2026, at 2:00 p.m. The District reserves the right to accept or reject any or all bids and may withhold award for up to 60 days.

Bidders must submit a bid bond with corporate surety authorized to do business in Pennsylvania in the amount of 10 percent of the total bid amount, with the successful bidder required to furnish a Performance Bond equal to 100 percent of the contract value. Pennsylvania Prevailing Wage Rates apply to all work. The electrical panel load analysis indicates total connected load of 42 amps with 15.1 kVA total demand, distributed across the existing Square D NQ panelboard with specific circuit allocations for the heat pump (40-amp, 2-pole GFCI breaker), air handling unit (60-amp, 2-pole breaker), dehumidification system (20-amp, 1-pole GFCI breaker), and circulation fan receptacles (20-amp, 1-pole breaker). All equipment must be installed per manufacturer recommendations, all ductwork and piping concealed except in mechanical rooms, and all systems guaranteed for one year from acceptance. The contractor is responsible for coordination with all trades, provision of adequate clearances, proper sequencing, and delivery of complete and functional systems upon project completion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE:

NOT ALL ABBREVIATIONS AND SYMBOLS INDICATED

MAY APPEAR ON THESE CONTRACT DRAWINGS.

THIS IS FOR REFERENCE ONLY.

ABBREVIATIONS

A/C

AFF

AFG

AMB

AMP

AP

APROX

ARR

ATC

AUTO

AUX

AVG

BF

BHP

BOD

BOP

BOT

BP

BSMT

BTU

CA

CAP

CF

CFM

CL

CO

COL

CONC

CONN

CONT

CTR

D

DB

DDC

DEG

DET

DIA

DISC

DN

DWG

EA

EAT

EER

EFF

EJ

EL

ELEC

ENT

ESP

EVAP

EWT

EXH

EXP

EXST

EXT

F&T

FC

FDW

FLA

FLR

FO

FPM

FPS

FS

FT

GA

GAL

GALV

GND

GPH

GPM

GR

HD

HG

HGT

HMD

HORIZ

HP

HTD

HTR

AIR CONDITIONING

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AMBIENT

AMPERE

ACCESS PANEL

APPROXIMATE

ARRANGEMENT

AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC

AUXILIARY

AVERAGE

BOILER FEED

BRAKE HORSEPOWER

BOTTOM OF DUCT

BOTTOM OF PIPE

BOTTOM

BACK PRESSURE

BASEMENT

BRITISH THERMAL UNIT

COMPRESSED AIR

CAPACITY

CUBIC FOOT (FEET)

CUBIC FOOT (FEET) PER MINUTE

CENTER LINE

CLEANOUT

COLUMN

CONCRETE OR CONCENTRIC

CONNECT OR CONNECTION

CONTINUATION

CENTER

DRAIN OR DEEP

DRY BULB

DIRECT DIGITAL CONTROL

DEGREE

DETAIL

DIAMETER

DISCONNECT

DOWN

DRAWING

EACH

ENTERING AIR TEMPERATURE

ENERGY EFFICIENCY RATIO

EFFICIENCY

EXPANSION JOINT

ELEVATION

ELECTRICAL

ENTERING

EXTERNAL STATIC PRESSURE

EVAPORATOR

ENTERING WATER TEMPERATURE

EXHAUST

EXPANSION

EXISTING

EXTERNAL

FLOAT & THERMOSTATIC

FLEXIBLE CONNECTION

FEED WATER

FULL LOAD AMPS

FLOOR

FUEL OIL

FOOT (FEET) PER MINUTE

FOOT (FEET) PER SECOND

FLOW SWITCH

FOOT (FEET)

GAUGE

GALLONS

GALVANIZED

GROUND

GALLONS PER HOUR

GALLONS PER MINUTE

GRAIN

HEAD

HOT GAS

HEIGHT

HUMIDITY

HORIZONTAL

HORSEPOWER

HEATED

HEATER

Hz

INSUL

INTL

LAT

LBS

LIN

LP

LRA

LVL

LVR

LWT

MAN

MAX

MBH

MIN

MOD

MTD

MU

NA

NC

NEG

NIC

NO

NTS

OA

OED

OFCI

OV

PCR

PD

PG

PL

PNEU

PRESS

PROP

PSIG

QTY

REF

REQD

REV

RL

RM

RS

RTN

S

SCH

SD

SEC

SENS

SEP

SEQ

SER

SERV

SHT

SOL

SP

SPLY

SS

STL

SUCT

TD

TEMP

TH

THK

TSP

TYP.

UON

V

VAC

VAV

VB

VEL

VERT

VIB

VOL

VSD

VTR

W

WB

WMS

WP

HERTZ

INSULATION

INTERNAL

LEAVING AIR TEMPERATURE

POUNDS

LINEAL

LOW PRESSURE

LOCKED ROTOR AMPS

LEVEL

LOUVER

LEAVING WATER TEMPERATURE

MANUAL

MAXIMUM

THOUSAND BRITISH THERMAL UNITS PER HOUR

MINIMUM

MODEL

MOUNTED

MAKEUP

NOT APPLICABLE

NORMALLY CLOSED

NEGATIVE

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

OUTSIDE AIR

OPEN END DUCT

OWNER FURNISHED CONTRACTOR INSTALLED

OUTLET VELOCITY

PUMPED CONDENSATE RETURN

PRESSURE DROP

RESSURE GAUGE

PLATE

PNEUMATIC

PRESSURE

PROPELLER

POUNDS PER SQUARE INCH GAUGE

QUANTITY

REFERENCE

REQUIRED

REVISION

REFRIGERANT LIQUID

ROOM

REFRIGERANT SUCTION

RETURN

SWITCH

SCHEDULE

SMOKE DAMPER

SECONDARY SECONDS

SENSIBLE

SEPARATE

SEQUENCE

SERIES

SERVICE

SHEET

SOLENOID

STATIC PRESSURE

SUPPLY

STAINLESS STEEL

STEEL

SUCTION

TEMPERATURE DIFFERENTIAL

TEMPERATURE

THERMOMETER

THICK

TOTAL STATIC PRESSURE

TYPICAL

UNLESS OTHERWISE NOTED

VENT OR VOLT

VACUUM

VARIABLE AIR VOLUME

VACUUM BREAKER

VELOCITY

VERTICAL

VIBRATION

VOLUME

VARIABLE SPEED DRIVE

VENT THRU ROOF

WATT, WIDTH OR WIDE

WET BULB

WIRE MESH SCREEN

WEATHER PROOF

24x36

DOUBLE LINE

24x36

SINGLE LINE

NEW WORK

SUPPLY AIR DOWN

SUPPLY AIR UP

EXISTING TO BE REMOVED

EXISTING TO REMAIN

DESCRIPTION

EXHAUST OR RETURN AIR UP

EXHAUST OR RETURN AIR DOWN

DUCTWORK SYMBOLS

RECTANGULAR DUCT SIZE SHOWN IN

INCHES (FIRST FIGURE-SIDE SHOWN)

DUCT SMOKE DETECTOR SDT

VOLUME DAMPER

POINT OF CONNECTION-NEW TO EXISTING

DRAWING NOTE SYMBOL

REVISION SYMBOL

MISCELLANEOUS SYMBOLS

POINT OF DEMOLITION CONCLUSION

D

GENERAL MECHANICAL NOTES:

1. ALL WORK AND EQUIPMENT SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES, AND

REQUIREMENTS; OF ALL AUTHORITIES HAVING JURISDICTION, INCLUDING BUT NOT

LIMITED TO THE INTERNATIONAL MECHANICAL CODE, THE INTERNATIONAL PLUMBING

CODE, THE INTERNATIONAL ENERGY CODE, THE LOCAL FIRE MARSHALL, UNDERWRITERS

LABORATORY, IRI, FM, OSHA, AND THE NATIONAL ELECTRICAL CODE. MODIFICATIONS

REQUIRED BY THE ABOVE AUTHORITIES IN ORDER TO BRING THE PROJECT INTO CODE

COMPLIANCE SHALL BE MADE AT NO ADDITIONAL COST TO OWNER. IF CONTRACT

DOCUMENTS ARE MORE STRINGENT THAN CODE REQUIREMENTS, THE CONTRACT

DOCUMENTS SHALL GOVERN.

2. ALL SPECIFICATIONS AND DRAWINGS ARE COMPLIMENTARY AND MUST BE USED IN

COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. ANY CONFLICTING

INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER, AND WORK

SHALL CEASE ON THAT PORTION OF THE PROJECT UNTIL CLARIFICATIONS ARE ISSUED.

3. HEATING CONTRACTOR (H.C.) AND MECHANICAL CONTRACTOR (M.C.) TERMINOLOGY IS

INTERCHANGEABLE.

4. CONTRACTOR SHALL CONFIRM THE REQUIREMENTS FOR PREMIUM TIME OR SPECIAL

PROCEDURES WITH THE OWNER. CONTRACTOR SHALL INCLUDE LONG LEAD EQUIPMENT

SUBMITTALS WITH BID PROPOSALS.

5. CONTRACTOR SHALL COORDINATE, PREPARE AND SUBMIT SHOP DRAWINGS TO THE

ARCHITECT AND ENGINEER FOR APPROVAL. SHOP DRAWINGS TO BE SUBMITTED

INCLUDE: SHEET METAL, DIFFUSERS, GRILLES, REGISTERS, FIRE DAMPERS, AND ALL

EQUIPMENT. SHEET METAL SHOP DRAWINGS SHALL BE COORDINATED AND SHOW DUCT

ELEVATIONS. INCLUDE RISES, DROPS, AND OFFSETS TO PROVIDE A COMPLETE AND

FUNCTIONAL SYSTEM. AREAS OF POTENTIAL CONFLICT SHALL BE BROUGHT TO THE

ENGINEER'S ATTENTION.

6. A SET OF MEP RECORD/COORDINATION DRAWINGS SHALL BE MAINTAINED BY THE

CONTRACTOR AT THE JOB SITE. ACTUAL LOCATIONS OF ALL EQUIPMENT, PIPING,

DUCTWORK, AND ALL OTHER ITEMS INCLUDED IN THIS CONTRACT, AND ALL DEVIATIONS

OF THE WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS SHALL BE MARKED

ON THE RECORD/COORDINATION DRAWINGS. EACH TRADE SHALL REVIEW THE

COORDINATION DRAWINGS AND RESOLVE ANY POTENTIAL CONFLICTS WITH OTHER

TRADES PRIOR TO INSTALLING ANY PORTION OF THEIR WORK.

7. THE MECHANICAL CONTRACTOR SHALL SUBMIT TO THE ARCHITECT/ENGINEER AS-BUILT

DRAWINGS AND OPERATION AND MAINTENANCE MANUALS INCLUDING ALL NAMEPLATE

DATA, WIRING DIAGRAMS, MAINTENANCE INSTRUCTIONS, AND PARTS LIST UPON PROJECT

COMPLETION.

8. WORK SHALL BE EXECUTED IN A GOOD WORKMANLIKE MANNER USING MECHANICS IN

THEIR RESPECTIVE TRADES. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL

CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES FOR

COORDINATING THE WORK UNDER THIS CONTRACT. UPON COMPLETION OF

CONSTRUCTION, THE CONTRACTOR SHALL DELIVER COMPLETE AND FUNCTIONAL

SYSTEMS AS ENCOMPASSED BY THE CONTRACT. ALL EQUIPMENT SHALL BE INSTALLED

PER MANUFACTURER'S RECOMMENDATIONS AND CODE REQUIREMENTS.

9. THE HVAC CONTRACTOR SHALL ARRANGE THE PROGRESS OF HIS WORK SO AS TO

CONFORM TO THE PROGRESS OF THE TRADES AND SHALL COMPLETE THE ENTIRE

INSTALLATION AS SOON AS THE CONDITION OF THE PROJECT WILL PERMIT.

10. ALL AUTOMATIC TEMPERATURE CONTROL SYSTEM WORK AND INSPECTION SHALL BE

ACCOMPLISHED BY THIS CONTRACTOR. WIRING OF ALL MOTORIZED OPERATORS ,

REGARDLESS OF VOLTAGE, ARE THE RESPONSIBILITY OF THE MECHANICAL

CONTRACTOR.

11. FOR ALL SENSOR/DEVICES FURNISHED AND INSTALLED BY OTHERS TO INTERFACE WITH

THE BAS, BAS CONTRACTOR SHALL COORDINATE INSTALLATION LOCATIONS, AVAILABLE

INPUTS, AND SENSOR REQUIREMENTS. BAS CONTRACTOR SHALL FURNISH AND INSTALL

ALL CONTROL WIRING FROM THE DEVICE TO THE BAS CONTROLLER AND PROVIDE ALL

TERMINATIONS UNLESS NOTED OTHERWISE.

12. M.C. AND BAS CONTRACTOR SHALL COORDINATE ALL SENSOR MOUNTING LOCATIONS.

13. THE CONTRACTOR SHALL PROVIDE ADEQUATE CLEARANCE FOR ALL UNIT CONTROLS.

14. THE CONTRACTOR SHALL MAKE ALL FINAL EQUIPMENT CONNECTIONS AND PROVIDE THE

NECESSARY ADAPTERS, FITTINGS, VALVES, AND DEVICES FOR A COMPLETE OPERABLE

SYSTEM. COORDINATE REQUIREMENT FOR PROVISION OF CONTACTORS AND CONTROL

WIRING FOR PROPER FUNCTIONING SYSTEM WITH ELECTRICAL CONTRACTOR. MOTOR

STARTERS, COMBINATION MOTOR STARTERS, AND DISCONNECTS ARE TO BE PROVIDED

BY THIS CONTRACTOR FOR INSTALLATION BY OTHERS.

15. FURNISH AND INSTALL ALL EQUIPMENT ELECTRICAL DISCONNECTS UNLESS INDICATED

OTHERWISE. DISCONNECTS SHALL BE PROVIDED BY EQUIPMENT MANUFACTURER AND

SHALL BE IN ACCORDANCE WITH SPECIFICATION SECTION 262816.

16. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE RELATION OF PIPING,

DUCTWORK, CONNECTIONS, AND EQUIPMENT. CONTRACTOR SHALL TAKE ALL

INTERFERENCES INTO CONSIDERATION. PROVIDE ALL NECESSARY OFFSETS OR

TRANSITIONS WITH EQUIVALENT AREAS TO MATCH DUCT SIZES AS INDICATED ON

DRAWINGS. ALL PIPING AND DUCTWORK TO BE CONCEALED IN CEILINGS AND WALLS,

EXCEPT IN MECHANICAL ROOMS, SPACES WITHOUT CEILINGS, OR WHERE NOTED

OTHERWISE.

17. ALL DIMENSIONS AND PIPE SIZES ARE IN INCHES UNLESS NOTED OTHERWISE.

18. BAS CONTRACTOR SHALL COORDINATE AND INSTALL ALL CONTROL PANELS. BAS SHALL

FURNISH AND INSTALL ALL MATERIALS AND PROVIDE ALL LABOR FROM THE BREAKER TO

ATC CONTROL PANEL.

19. CLEAN ALL MECHANICAL EQUIPMENT AND DUCTWORK OF ALL CONSTRUCTION DUST AT

PROJECT COMPLETION. REPLACE ALL FILTERS PRIOR TO AIR BALANCING. PROVIDE ONE

SPARE SET OF FILTERS FOR EACH PIECE OF EQUIPMENT TO OWNER. NEWLY INSTALLED

HVAC EQUIPMENT SHALL NOT BE USED AT ANY TIME FOR TEMPORARY CONDITIONING OF

THE SPACE DURING CONSTRUCTION.

20. CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS,

EQUIPMENT, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF

ACCEPTANCE BY OWNER.

21. THE EXISTING CONDITIONS ON THESE DRAWINGS ARE FROM HISTORICAL DOCUMENTS.

CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE SITE PRIOR TO

COMMENCING WORK. WHERE DISCREPANCY EXISTS, NOTIFY ENGINEER IN WRITING.

S

S

S

M

JB

T

30/3/NF/12

FVNR/SIZE1/3R

PANELBOARDS

EXISTING PANELBOARD

NEW PANELBOARD

CIRCUITING

JUNCTION BOX

BRANCH CIRCUIT NUMBER FOR ALL ITEMS IN THIS

ROOM UNLESS OTHERWISE INDICATED - (*)

INDICATES CONNECTION TO CIRCUIT NUMBER

SHOWN NEXT TO DEVICE

CONTROL EQUIPMENT

MANUAL MOTOR STARTER - OVERLOADS SIZED TO ACCOMMODATE

MOTOR - 4'-0" AFF UNLESS OTHERWISE NOTED

COMBINATION MOTOR STARTER - TYPE/SIZE/NEMA ENCLOSURE AS

INDICATED - MOUNT 4'-6" AFF TO CENTERLINE OF OPERATING HANDLE

PROVIDE OVERCURRENT AND OVERLOADS IN ACCORDANCE WITH

MANUFACTURERS RECOMMENDATIONS FOR MOTOR HP

MOTOR - HORSEPOWER AS INDICATED

DISCONNECT SWITCH - AMPS/POLES/FUSES/NEMA ENCLOSURE AS

INDICATED - MOUNT 4'-6" AFF TO CENTERLINE OF OPERATING HANDLE

TRANSFORMER

SIGNAL SYSTEM

STANDARD MOUNTING HEIGHTS

9" BELOW

FINISHED

CEILING

WALL-MOUNTED CLOCKS, PROGRAM BELLS, (OR AS SHOWN

ON ARCHITECTURAL DETAIL)

6" ABOVE DOOR NURSE CALL DOME LIGHT

6" ABOVE FIRE

HOUSE

CABINET

RED SIGNAL LIGHT

10'-0"

BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED

LIGHT HEADS (OR 1'-0" BELOW FINISHED CEILING OF TOP

UNIT).

8'-6" PENDANT-HUNG INDUSTRIAL AND STRIP LIGHTING FIXTURES.

7'-8"+

TELEVISION OUTLET AND SERVICE RECEPTACLE-FOR

SHELF MOUNTED T.V. IN BEDROOMS.

7'-6" OR 6" BELOW FINISHED CEILING, WHICHEVER IS LOWER.

CENTER ABOVE

DOOR OR WINDOW

OPENING

WARNING AND SIGNALING FIXTURES/SIGNS.

6'-8"

OR 6" BELOW FINISHED CEILING WHICHEVER IS LOWER.

FIRE ALARM SIGNAL DEVICES AND ILLUMINATED FIRE

SIGNALS.

6'-6"

TOP OF FLUSH AND SURFACE MOUNTED ELECTRICAL

LIGHTING OR POWER PANELBOARDS AND TELEPHONE

CABINETS.

6'-3"

TOP OF BACK-MOUNTED WALL EXIT FIXTURES (NOT

MOUNTED ABOVE DOORS).

6'-0"

TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT

SWITCHES, MAGNETIC STARTERS, CONTACTORS.

4'-6"

CENTERLINE OF OPERATING HANDLE FOR WALL MOUNTED

DISCONNECT SWITCHES AND MOTOR STARTERS; WALL

MOUNTED TELEPHONE AND PAY STATIONS (3'-6" AT HANDICAP

LOCATIONS VERIFY EXACT HEIGHT PRIOR TO ROUGH IN)

3'-10"

WALL PHONE, ELECTRICAL DEVICE LIGHTING SWITCHES, MANUAL

MOTOR STARTERS, SECURITY CARD, AND GFI RECEPTACLES IN

TOILET ROOMS OR FOR SEPERATE SINKS NOT IN CASEWORK.

3'-6" FIRE ALARM PULL STATIONS

2'-0"

ELECTRICAL RECEPTACLES WITHIN MECHANICAL

SPACES, ELECTRICAL AND ELEVATOR ROOMS.

1'-6"

ELECTRICAL RECEPTACLES, TELEPHONE OUTLETS, DATA

OUTLETS, TELEPHONE/DATA OUTLETS

0" FINISHED FLOOR

CT

W

MOUNTING HEIGHT NOTES:

1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY

CONSTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST

BLOCK OF BRICK COURSING.

2. THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED

OTHERWISE ON THE DRAWING OR SPECIFICATIONS.

3. A '+' BESIDE A DEVICE INDICATES THAT DEVICE IS MOUNTED ABOVE A COUNTER OR CASEWORK.

COORDINATE WITH ARCHITECTURAL ROOM ELEVATIONS, DETAILS AND CASEWORK CONTRACTOR.

P-1

ROOM #

ROOM NAME

M

M

THE ELECTRICAL SYSTEMS PRESENTED ON THE SUBSEQUENT

DRAWINGS WERE DESIGNED IN ACCORDANCE WITH THE

FOLLOWING APPLICABLE CODES AND STANDARDS:

THE NATIONAL ELECTRICAL CODE (NEC), 2020

INTERNATIONAL BUILDING CODE (IBC), 2021

INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2021

WIRING DEVICES

DUPLEX RECEPTACLE - NEMA 5-20R, MOUNT 1'-6"

AFF UNLESS OTHERWISE NOTED

GFI DUPLEX RECEPTACLE - MOUNT AT 1'-6" AFF UNLESS

OTHERWISE NOTED

1. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING TO ALL ITEMS WHICH REQUIRE

ELECTRICAL CONNECTIONS. WHERE BRANCH CIRCUIT WIRING IS NOT SHOWN,

CONTRACTOR SHALL CONNECT ITEMS TO THE CIRCUITS INDICATED. EXACT ROUTING OF

CONDUITS AND WIRING SHALL BE DETERMINED BY THE CONTRACTOR IN ACCORDANCE

WITH THE NATIONAL ELECTRICAL CODE AND SPECIFICATIONS.

2. CONTRACTOR SHALL USE ONLY THOSE WIRING METHODS ALLOWED IN THE

SPECIFICATIONS.

3. A MAXIMUM OF 3 CIRCUITS SHALL BE RUN IN ONE CONDUIT, CIRCUITS MUST BE ON

SEPARATE PHASES. CIRCUITS SHALL NOT SHARE A COMMON NEUTRAL.

4. MINIMUM WIRE SIZE SHALL BE #12AWG. MINIMUM CONDUIT SIZE SHALL BE 3/4".

5. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND

CONDITIONS AT THE SITE.

6. ALLOW CLEAR SPACE IN FRONT OF ALL PANELBOARDS, SWITCHBOARDS, ELECTRICAL

EQUIPMENT, ETC., AS REQUIRED BY NEC.

7. ELECTRICAL CONTRACTOR TO SUPPLY ALL GROUNDING & BONDING REQUIREMENTS PER

NEC.

8. ELECTRICAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING IN EXISTING

BUILDING RELATED TO THE NEW ELECTRICAL WORK.

9. ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL

MATERIALS EQUIPMENT AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE

OF ACCEPTANCE BY OWNER

10. THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ENGINEER AS-BUILT DRAWINGS

AND OPERATION AND MAINTENANCE MANUALS INCLUDING ALL NAMEPLATE DATA,

WIRING DIAGRAMS, MAINTENANCE INSTRUCTIONS AND PARTS LIST UPON PROJECT

COMPLETION.

11. ELECTRICAL CONTRACTOR SHALL MAINTAIN A CLEAN AND SAFE WORK AREA AT ALL

TIMES. ALL SAFETY PROCEDURES AND ENFORCEMENT IS THE RESPONSIBILITY OF THE

CONTRACTOR. THE CONTRACTOR SHALL CONFORM TO ALL OSHA STANDARDS.

GENERAL ELECTRICAL NOTES:

DEMOLITION DRAWING LINETYPE DESIGNATIONS

EXISTING TO REMAIN

EXISTING TO BE REMOVED

S

D

NOTE:

NOT ALL ABBREVIATIONS AND

SYMBOLS INDICATED MAY APPEAR ON

THESE CONTRACT DRAWINGS. THIS IS

FOR REFERENCE ONLY.

SMOKE DETECTOR

DUCT MOUNTED SMOKE DETECTOR

DUPLEX RECEPTACLE - NEMA 5-20R, AT CEILING OR

EXPOSED STRUCTURE, UNLESS OTHERWISE NOTED

GFI DUPLEX RECEPTACLE WITH WEATHERPROOF

WHILE IN USE COVER- MOUNT AT 2'-0" AFF/AFG UNLESS

OTHERWISE NOTED

WP

DSGN:

JOB:

CHK:

DRAWN: APPRD:

DATE:

SCALE:

P MGR:

COPYRIGHT 2026

SHEET:

F

IL

E N

A M

E

AB

R E

V

IS

IO

N

S D

A T

E

A u to d e s k D o c s /1

.0

E lm w o o d A c a d e m y L o w e r_

L e v e l_

H V

A C

R

/M E

P -1

.0

E lm w o o d

A c a d e m y

L o w e r_

L e v e l_

H V

A C

R

.r v t

NO SCALE

M E

C H

A N

IC

A

L A

N D

E L

E C

T R

IC

A

L I

N F

O R

M A

T

IO

N S

H E

E T

L O

W E

R L

E V

E L S

T O

R A

G E

H V

A C

P R

O J E

C T

F O

R

RWR/GLM

RWR/GLM03/19/2026

1011522.002

ME0.1

JBL

JBL

M E

C H

A N

IC

S

B U

R G

A R

E A

S C

H O

O L

D

IS

T R

IC

T

E

E L

M W

O O

D A

V E

M

E C

H A

N

IC

S B

U R

G

P A

E L M

W O

O D

A C

A D

E M

Y

RWR

MECHANICAL DRAWING LIST

ME0.1 MECHANICAL AND ELECTRICAL INFORMATION SHEET

ME1.1 LOWER LEVEL PLAN - UNIT A - MECHANICAL AND ELECTRICAL

T

T

T

T

T

T

STORAGE

A027

WORK CENTER

A018

ELECTRICAL

A014

PRINT CENTER

A013

IT RECEIVING

A016

CORRIDOR

A017 STAIR A3

A015

STAIR

A011

OFFICE

A022

OFFICE

A021

IT RECEIVING

A016

CORRIDOR

A017

CONFERENCE

A019

TOILET

A025

OFFICE

A020

STORAGE

A023

CUST

A024

CL

A026

CP-1

DH-1

CF-2

CF-1

AH-1

HP-1

10x6

SSR

10x6

SSR

10x6

SSR

10x6

SSR

x

12x12 x

INSTALL GRILLES IN SIDE OF DUCT

WITH 22° BLADE DEFLECTION

DOWNWARD. (TYP. 4)

INSTALL DUCTWORK AT

APPROX. 8'-0" TO CENTER

HANG FROM STRUCTURE

AT APPROX. 8'-0"

HANG FROM STRUCTURE

AT APPROX. 8'-0"

DPFLP2

PP2

WP

PP2-56

PP2-56

PP2-56

PP2-56

PP2-58

60/2/40/3R

PP2 - 65,67

60/2/NF/1

PP2 - 66,68

B

CA

DSGN:

JOB:

CHK:

DRAWN: APPRD:

DATE:

SCALE:

P MGR:

COPYRIGHT 2026

SHEET:

F

IL

E N

A M

E

AB

R E

V

IS

IO

N

S D

A T

E

A u to d e s k D o c s /1

.0

E lm w o o d A c a d e m y L o w e r_

L e v e l_

H V

A C

R

/M E

P -1

.0

E lm w o o d

A c a d e m y

L o w e r_

L e v e l_

H V

A C

R

.r v t

1/8" = 1'-0"

L O

W E

R L

E V

E L

P L

A N

U

N

IT

A

M E

C H

A N

IC

A

L A

N D

E L

E C

T R

IC

A

L

L O

W E

R L

E V

E L S

T O

R A

G E

H V

A C

P R

O J E

C T

F O

R

RWR/GLM

RWR/GLM3/19/2026

1011522.002

ME1.1

JBL

JBL

M E

C H

A N

IC

S

B U

R G

A R

E A

S C

H O

O L

D

IS

T R

IC

T

E

E L

M W

O O

D A

V E

M

E C

H A

N

IC

S B

U R

G

P A

E L M

W O

O D

A C

A D

E M

Y

RWR

SCALE: 1/8" = 1'-0"

LOWER LEVEL PLAN - UNIT A - MECHANICAL AND ELECTRICAL1

REMARKS:

1. PROVIDE UNIT WITH NEMA 5-15P POWER CORD.

2. PROVIDE WITH 5-YEAR WARRANTY.

3. SUSPEND FROM STRUCTURE ABOVE PER MANUFACTURERS WRITTEN RECOMMENDATIONS.

4. PROVIDE ACCESSORY HUMIDISTAT CONTROL AND ASSOCIATED LOW-VOLTAGE WIRING.

5. ROUTE CONDENSATE DRAIN PIPING TO CONDENSATE PUMP AT AIR HANDLER.

CONDENSATE PUMP SCHEDULE

SYMBOL MANUFACTURER MODEL

GALLONS

PER HOUR

AMPS V/P/H REMARKS

CP-1 QUEST 4022220 55 1.5 120/1/60 1,2,3

CIRCULATION FAN SCHEDULE

SYMBOL MANUFACTURER MODEL DRIVE RPM

BLADE

HEIGHT

(A.F.F.)

CONTROLS

ELECTRICAL DATA

WEIGHT

(LBS.)

REMARKS

AMPS V/P/H

CF-1 QUEST 4042250-06 DIRECT 1,015 8'-0" WALL SWITCH BY E.C. 1.1 120/1/60 16 1,2,3

CF-2 QUEST 4042250-06 DIRECT 1,015 8'-0" WALL SWITCH BY E.C. 1.1 120/1/60 16 1,2,3

CONDENSING UNIT SCHEDULE

SYMBOL MANUFACTURER MODEL

NOMINAL

TONS

TOTAL

CAPACITY

(MBH)

REFRIGERANT

AIR ON

CONDENSER

(°F)

ELECTRICAL DATA

WEIGHT (LBS) REMARKS

MCA MOP V/P/H

HP-1 TRANE PUZ-AK24NLHZ 2 24.0 R454B 95 24 39 208-230/1/60 235 1

DEHUMIDIFICATION UNIT SCHEDULE

SYMBOL MANUFACTURER MODEL

AIRFLOW

(CFM)

E.S.P. (IN.

WG.)

PINTS PER

DAY

REFRIGERANT FILTRATION

ELECTRICAL DATA

WEIGHT

(LBS.)

REMARKS

AMPS V/P/H

POWER CORD

TYPE

DH-1 QUEST 4044590 280 0.0 70 R-454B MERV-8 5.0 120/1/60 STANDARD 60 1,2,3,4,5

REMARKS:

1. INSTALL ADJACENT TO UNIT SERVED.

2. PIPE DISCHARGE TO GRADE. ROUTE TUBING WITH REFRIGERANT LINESET.

3. PROVIDE WITH 6' 3-CONDUCTOR CORD WITH GROUND.

REMARKS:

1. PROVIDE UNIT WITH NEMA 5-15P POWER CORD. E.C. SHALL PROVIDE RECEPTACLE AT CEILING CONTROLLED BY WALL SWITCH.

ONE CIRCUIT SHALL CONTROL BOTH FANS.

2. PROVIDE WITH 1-YEAR WARRANTY.

3. SUSPEND FROM STRUCTURE ABOVE PER MANUFACTURERS WRITTEN RECOMMENDATIONS.

REMARKS:

1. SET UNIT ON GRADE WITH CONCRETE HOUSEKEEPING PAD. PAD TO BE 6" LARGER THAN EQUIPMENT ON ALL SIDES.

HEAT PUMP AIR HANDLING UNIT SCHEDULE

SYMBOL MANUFACTURER MODEL

SUPPLY DATA COOLING DATA HEATING DATA ELECTRICAL DATA

WEIGHT

(LBS.)

REMARKS

CFM HP ESP (IN. WC.) TOTAL MBH LAT DB (°F) MBH LAT (°F)

AUX. HEAT

(KW)

MCA MOP V/P/H

AH-1 TRANE PVA-AA24NL 875 0.5 0.3 13.6-24.0 55.0 26.0 95.0 7.5 49.3 / 56.2 50 / 60 208-230/1/60 145 1,2,3

REMARKS:

1. PROVIDE UNIT WITH BOTTOM FILTER RACK AND FLOOR SUPPORT TO ELEVATE UNIT.

2. RETURN SHALL BE OPEN BOTTOM WITH FILTER ABOVE FLOOR.

3. ROUTE CONDENSATE DRAIN TO CONDENSATE PUMP. PUMP DISCHARGE TUBE SHALL BE ROUTED TO GRADE WITH LINESET.

TOTAL AMPS PANEL 42

TOTAL KVA PANEL 15.1

TOTAL KVA/PHASE 7.8 0.2 7.1 EXISTING SQUARE D NQ PANELBOARD TO REMAIN; # EXISTING CIRCUIT TO REMAIN;

## UTILIZE SPARE BREAKER FOR NEW CIRCUIT; ### PROVIDE NEW BREAKER IN

EXISTING SPACE(S). MATCH EXISTING PANEL AIC RATING. FIELD VERIFY.

83 PREPARED SPACE 1 -- -- -- 84

81 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 82

79 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 80

77 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 78

75 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 76

73 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 74

71 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 72

69 PREPARED SPACE 1 -- -- -- -- -- -- 1 PREPARED SPACE 70

67 2.2 5.0 68

### HP-1 (GFCI) 2 40 2-#8, 1-#8, 1-#10 1"

2.2 5.0

1-1/4" 2-#4, 1-#4, 1-#10 60 2 ### AH-1

63 SPARE (OFF) 1 20 -- 0.0 0.0 -- 20 1 SPARE (OFF) 64

61 SPARE (OFF) 1 20 -- 0.0 0.0 -- 20 1 SPARE (OFF) 62

59 SPARE (OFF) 1 20 -- 0.0 0.0 -- 20 1 SPARE (OFF) 60

57 SPARE (OFF) 1 20 -- 0.0 0.2 3/4" 1-#12, 1-#12, 1-#12 20 1 ## RECEPT - AT HEAT PUMP 58

55 SPARE (OFF) 1 20 -- 0.0 0.7 3/4" 1-#12, 1-#12, 1-#12 20 1 ### DEHUMIDIFICATION SYSTEM (GFCI) 56

53 # 1 20 -- 0.0 0.0 54

51 # 1 20 -- 0.0 0.0 -- 20 2 #

49 # 1 20 -- 0.0 0.0 50

47 # 1 20 -- 0.0 0.0 -- 20 2 #

45 # 1 20 -- 0.0 0.0 46

43 # 1 20 -- 0.0 0.0 -- 20 2 #

41 SPARE (OFF) 1 20 -- 0.0 0.0 42

39 # 1 20 -- 0.0 0.0 -- 20 2 #

37 # 1 20 -- 0.0 0.0 -- 20 1 # 38

35 # 1 20 -- 0.0 0.0 -- 20 1 # 36

33 0.0 0.0 34

# 2 15 --

0.0 0.0 -- 50 2 #

29 0.0 0.0 30

# 2 15 --

0.0 0.0 -- 15 2 #

25 0.0 0.0 26

# 2 15 --

0.0 0.0 -- 15 2 #

21 # 1 30 -- 0.0 0.0 22

19 0.0 0.0 -- 30 2 #

# 2 50 --

0.0 0.0 -- 20 1 # 18

15 # 1 20 -- 0.0 0.0 -- 20 1 # 16

13 # 1 20 -- 0.0 0.0 -- 20 1 # 14

11 # 1 20 -- 0.0 0.0 -- 20 1 # 12

9 # 1 20 -- 0.0 0.0 -- 20 1 # 10

7 # 1 20 -- 0.0 0.0 -- 20 1 # 8

5 # 1 20 -- 0.0 0.0 -- 20 1 # 6

3 # 1 20 -- 0.0 0.0 -- 20 1 # 4

1 # 1 20 -- 0.0 0.0 -- 20 1 # 2

NO SZ NO SZ NO SZ NO SZ NO SZ NO SZ

P AMP A B C AMP P

CKT CIRCUIT DESCRIPTION

BREAKER

WIRE GND

COND

KVA/PH

COND

WIRE GND

BREAKER

CIRCUIT DESCRIPTION CKT

MOUNTING: Surface PHASE: 3 WIRE: 4 VOLTAGE: 120/208 AIC: EXISTING

PANEL: PP2 BUS AMP: 175 A AMPS MAIN BREAKER: 175 A

Sheets
ME0.1 - MECHANICAL AND ELECTRICAL INFORMATION SHEET
ME1.1 - LOWER LEVEL PLAN - UNIT A - MECHANICAL AND ELECTRICAL

File details come from the government source that posted it. Updated .