This document is an Issued for Bid package for a new community clubhouse prepared by MKSD, LLC Architects for the Wild Acres Lakes Property and Homeowners Association (WALPOA) located at 100 Clubhouse Lane, Dingmans Ferry, Pennsylvania 18328. The project involves construction of approximately 9,900 square feet of new clubhouse facilities featuring an indoor swimming pool, meeting room, and gathering spaces for approximately 418 occupants. The facility is classified as Assembly Group A-3 occupancy (community hall and indoor swimming pool without spectator seating) and is designed as one-story, non-sprinklered construction with a maximum height of 30 feet. The project includes comprehensive architectural, structural, mechanical, plumbing, electrical, and aquatics design documents prepared as of June 16, 2025, with issuance for permit on that same date.
The structure is engineered to Pennsylvania Uniform Construction Code requirements based on the 2018 International Building Code and includes concrete foundations with wood and steel framing, concrete masonry unit construction, and metal deck systems. Design loads include 20 PSF roof live load, 15 PSF floor live load, and 50 PSF ground snow load with 43 PSF design roof snow load. The facility provides required plumbing fixtures including five water closets and five urinals for men, five water closets and five urinals for women, four lavatories for each gender, two service sinks, and two drinking fountains. All construction materials, reinforcement specifications, welding standards, concrete mix designs, and installation procedures are detailed in comprehensive technical notes and schedules, with requirements for shop drawing submittals, special inspections, and compliance with various ASTM and industry standards throughout the construction process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-2025.11.17 - WALPOA - DIV 00-01 Specs - Issued for Bid.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING PARTITION
TO REMAIN
EXISTING PARTITION
TO BE DEMOLISHED
NEW PARTITION &
TYPE SYMBOL
1t
CEILING TYPE
CEILING HEIGHT
BUILDING SECTION
DESIGNATION
A101
1 Ref
R ef
1 Ref
R ef
SHEET REFERENCE
ELEVATION NAME/NUMBER
Room name
150 SF
Symbols Legend Abbreviations
CLG CEILING
COL COLUMN
CONC CONCRETE
CONST JT CONSTRUCTION JOINT
CONT CONTINUOUS
CPT CARPET
CTR CENTER
D
D.F. DRINKING FOUNTAIN
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DN DOWN
DR DOOR
DTL DETAIL
DWG DRAWING
E
E EAST
E.I.F.S. EXTERIOR INSULATION FINISH SYSTEM
E.J. EXPANSION JOINT
E.W.C. ELECTRIC WATER COOLER
EA EACH
ELEC ELECTRIC(AL)
ELEV ELEVATOR
A/C AIR CONDITIONING
A.C.M. ALUMINUM COMPOSITE MATERIAL
A.C.T. ACOUSTICAL CEILING TILE
A.F.F. ABOVE FINISHED FLOOR
A.W.C. ACOUSTIC WALL COVERING
ABV ABOVE
ADD'L ADDITIONAL
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE(LY)
AVG AVERAGE
B
BD BOARD
BLDG BUILDING
BRG BEARING
BSMT BASEMENT
BTM BOTTOM
BTWN BETWEEN
BUR BUILT-UP ROOFING
BW BOTH WAYS
C
C.I.P. CAST-IN-PLACE
C.J. CONTROL JOINT
C.L. CENTER LINE
C.M.T. CERAMIC MOSAIC TILE
C.M.U. CONCRETE MASONRY UNIT
C.T. CERAMIC TILE
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
F.F.E. FINISH FLOOR ELEVATION
FD FLOOR DRAIN
FDN FOUNDATION
FIN FL FINISH FLOOR
FL FLOOR
FT (') FOOT
FTG FOOTING
G
G.W.B. GYPSUM WALLBOARD
GALV GALVANIZED
H
H.M. HOLLOW METAL
HCP HANDICAP(PED)
HT HEIGHT
HORIZ HORIZONTAL
I
IN INCH(ES)
INCL INCLUDE(S)
INFO INFORMATION
INSUL INSULATION (INSULATED)
INT INTERIOR
J
JAN JANITOR
JT JOINT
L
LAV LAVATORY
LTG LIGHTING
M
M.B. MARKER BOARD
M.O. MASONRY OPENING
MAINT MAINTENANCE
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MR MOISTURE RESISTANT
MTD MOUNTED
MTL METAL
N
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
P
P LAM PLASTIC LAMINATE
P.B. PIN BOARD
PERF PERFORATED
PERIM PERIMETER
PL PLATE
PLAS PLASTER
PLBG PLUMBING
PLWD PLYWOOD
PNL PANEL
PREFAB PREFABRICATED
PREFIN PREFINISHED
PT PAINT
PTD PAINTED
Q
Q.T. QUARRY TILE
QLTY QUALITY
QTY QUANTITY
R
R RISERS (STAIR)
r RADIUS
R.D. ROOF DRAIN
R.O. ROUGH OPENING
R.W.C. RAIN WATER CONDUCTOR
REINF REINFORCE(D)(ING)(MENT)
REQ'D REQUIRED
REV REVISION, REVISED
RFRIG REFRIGERATOR
RM ROOM
RUB RUBBER
S
S.A.B. SOUND ATTENUATION BLANKET
S.G.T. STRUCTURAL GLAZED TILE
S.P.R. SINGLE- PLY ROOFING
S.S.M. SOLID SURFACE MATERIAL
SCHED SCHEDULE
SECT SECTION
SEP SEPARATE
SF SQUARE FOOT
SHWR SHOWER
SIM SIMILAR
SPEC SPECIFICATIONS
SPEC'D SPECIFIED
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPEND(ED)
T
T TREAD
T & G TONGUE AND GROOVE
T.E.S. TACTILE EXIT SIGN
T/ TOP OF
T/CONC TOP OF CONCRETE
T/FTG TOP OF FOOTING
T/JST TOP OF JOIST
T/STL TOP OF STEEL
T/WALL TOP OF WALL
TB TACK BOARD
T.B.R. TO BE REMOVED
THRES THRESHOLD
TLT TOILET
T.S. TACK STRIP
TYP TYPICAL
TZ TERRAZZO
U
U.H. UNIT HEATER
U.O.N. UNLESS OTHERWISE NOTED
U/S UNDERSIDE OF
V
V.T. VINYL TILE
VAR VARIES
VAT VINYL ASBESTOS TILE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
V.I.F. VERIFY IN FIELD
VWC VINYL WALL COVERING
W
W.B. DRY ERASE WHITE BOARD
W.C. WATER CLOSET
W.W.F. WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
WD WOOD
WGT WEIGHT
WIN WINDOW
Y
YD YARD
VIEW REFERENCE SYMBOLS
DETAIL
WALL SECTION DESIGNATION
INTERIOR ELEVATION
SHEET REFERENCE
DETAIL NUMBER
SHEET REFERENCE
DETAIL NUMBER
SHEET REFERENCE
DETAIL NUMBER
A101
SHEET REFERENCE
ELEVATION NAME/NUMBER
BUILDING ELEVATION
Ref
1R ef
1 R ef
Ref
DRAWING SYMBOLS
ROOM IDENTIFICATION
ROOM NUMBER
AREA (WHERE
APPLIES)
DOOR SYMBOL & NUMBER
WINDOW TYPE INDICATOR
WINDOW TYPE
DESIGNATION
CEILING IDENTIFICATION
A.F.F.
1i
1'-0"
PARTITIONS
NEW DOOR/FRAME
1i
PARTITION TYPE
DESIGNATION
STRUCTURAL GRID IDENTIFICATION
0 GRIDLINE
DESIGNATION
LEVEL ELEVATION
LEVEL NAME
VERTICAL
DATUM
T.O.S. HP: 40'-0"
POINT ELEVATION
VERTICAL
DATUM
DESCRIPTION
EXISTING DOOR/FRAME
EXISTING DOOR
TO BE DEMOLISHED
DOORS
A
A300
A350
A500
D R
AW
N
B Y
Project Number
Drawing Number c M
KS
D
, L
LC
MKSD, LLC
1209 Hausman Road Suite A Allentown, PA 18104
610.366.2081 mksdarchitects.com
Silvia A. Hoffman, AIA Todd O. Chambers, AIA Jill P. Hewes, AIA Jessica E. Klocek, AIA a r c h i t e c t s
Project
Client
Project Team
Date
Drawing Title
Revisions
Structural Engineer Barry Isett & Associates, Inc.
5420 Crackersport Rd Allentown, PA 18104 Project Contact: Ty Cunningham, SE, PE P: (484) 866-4835 E: tcunningham@barryisett.com
MEP Engineer Barry Isett & Associates, Inc.
5420 Crackersport Rd Allentown, PA 18104 Project Contact: Rebecca Schleicher,EIT P: (484) 225-5021 E: rschleicher@barryisett.com
Aquatics Consultant Vincent Aquatics 1823 Deep Run Road Pipersville, PA 18947 Project Contact: Matt Long P: (215) 778-1912 E: mlong@vincentpools.com
/1
7/
:0 9:
A
M
.1
W
AL
PO
A
N ew
C lu bh ou se _R
_C en tra l_ de ta ch ed .rv t
G001
Cover Sheet
Wild Acres Lakes Property and Homeowners Association
WALPOA - New Community Clubhouse
M
KS
D
06.16.25
20.193
100 Clubhouse Ln, Dingmans Ferry, PA 18328
06/16/2025 - Issued for Permit
Wild Acres Lakes Property and Homeowners Association New Community Clubhouse
Owner:
WILD ACRES LAKES PROPERTY
AND HOMEOWNERS ASSOCIATION
116 WILD ACRES DRIVE,
DINGMANS FERRY, PA 18328
CONTACT: LAURA M. JONES
TELEPHONE: (570) 828-7511
EMAIL: doo@wildacreslakes.org
Architect:
MKSD, LLC
1209 HAUSMAN RD., SUITE A
ALLENTOWN, PA 18104
CONTACT: NICK HEWES
TELEPHONE: (610) 366-2081
FAX: (610) 366-8399
EMAIL:nick@mksdarchitects.com
MEP Consultant
100 Clubhouse Ln, Dingmans Ferry, PA 18328
Drawing List: Location Map: Site / Campus Map:
BARRY ISETT & ASSOCIATES, INC
5420 CRACKERSPORT RD
ALLENTOWN, PA 18104
CONTACT: REBECCA SCHLEICHER, EIT
TELEPHONE: (484) 225-5021
EMAIL: rschleicher@barryisett.com
PROJECT LOCATION PROJECT LOCATION
Structural Consultant
BARRY ISETT & ASSOCIATES, INC
5420 CRACKERSPORT RD
ALLENTOWN, PA 18104
CONTACT: ROSS SOTAK, PE
TELEPHONE: (484) 866-4871
EMAIL: rsotak@barryisett.com
Aquatics Consultant
VINCENT AQUATICS
1823 DEEP RUN RD
PIPERSVILLE, PA 18947
CONTACT: MATT LONG
TELEPHONE: (215) 766-7541 X 103
EMAIL: mlong@vincentpools.com
G001 Cover Sheet G002 Code Information & Life Safety Plan
S100 Notes S101 Foundation Plan & Schedules S102 Foundation Details S103 Roof Framing Plan & Schedules S104 Framing Details S300 Wall Sections S301 Unnamed
A001 Architectural Specifications A002 Architectural Specifications A003 Architectural Specifications A004 Architectural Specifications A005 Architectural Specifications A006 Architectural Specifications A100 Overall Floor Plan A100A Floor Plan - Zone A A100B Floor Plan - Zone B A102 Attic , Mezzanine, and Patio Plan A103 Roof Plan A200 Exterior Elevations A300 Building Sections A310 Wall Sections A312 Wall Sections A400 Reflected Ceiling Plan A511 Section Details A512 Plan Details A601 Finish Plan, Legend & Schedule A611 Door & Window Schedule A700 Interior Elevations & Details A702 Equipment Plan
M000 Mechanical Information Sheet M100 First Floor Plan - Mechanical M101 Roof Plan - Mechanical M400 Mechanical Details M500 Mechanical Schedules M600 Mechanical Specifications
P000 Plumbing Information Sheet P100 First Floor Plan - Domestic Water P101 First Floor Plan - Plumbing P102 Roof Plan - Plumbing P400 Plumbing Details P500 Plumbing Diagrams & Schedules P600 Plumbing Specifications
E000 Electrical Information Sheet E010 Site Plan - Electrical E100 First Floor Plan - Lighting E200 First Floor Plan - Power E201 Roof Plan - Power E400 Electrical Details and Schedules E500 Electrical Details E600 Electrical Specifications E601 Electrical Specifications
SP-0 Pool Area Plan SP-1 Pool Layout & Sections SP-2 Piping Schematic Filter Room, Hydraulic & Poping Schematics SP-3 Details SP-4 Electrical Schematic and Bonding
No. Date Description
DW
F.E.C.
F.E.C
F.
E.
C
165 SF
Bonus Room
277 SF
Kitchen
604 SF
Lobby
Main Room
Fireside Room
75 SF
Storage
131 SF
Pool Equipment
1089 SF
Pool 107A
168 SF
Women's
170 SF
Men's
131 SF
Sauna
260 SF
Storage
173 SF
Storage
135 SF
Men's
137 SF
Women's
370 SF
Activities
214 SF
Mechanical
64 SF
Corridor
EXIT
1,011 SF @ 15 SF/Occ.
= 67 Occupants
2 occs.
2 Occs.
8 occupants
1,162 SF @ 7 SF/Occ.
= 166 Occs.
1 Occ.
22 occupants
2,031 SF @ 15 SF/Occ.
= 135 occupants
3 Occs.
1 Occ.
170 max
78 occs.
EXIT
Allowable Egress
Actual Egress
EXIT
340 max
42 occs.
EXIT
170 max
2 occs.
EXIT
170 max
41 occs.
EXIT
170 max
41 occs.
EXIT
340 max
43 occs.
2025 SF
Pool Deck
EXIT
340 max
78 occs.
EXIT
340 max
81 occs.
H
R . R td . F ire W al l
H
R . R td . F ire W al lFE
1 Occ.1 Occ.
Fire Area 1 5,720sf 249 occupants
Fire Area 2 4,179sf 160 occupants
Fire Area 1 5,720sf 249 occupants
Fire Area 2 4,179sf 160 occupants
Fire extinguisher provided by contractor
5/8" GWB, both sides
Wood Stud
- 18 ga Steel 2-1/2" semi-recessed cabinet w/ white baked enamel finish
- Aluminum full glass (acrylic) door w/loc. and aluminum trim with rolled edges
- Provide black vinyl lettering vertically on face of glazing - "fire extinguisher"
- All aluminum has clear satin anodized finish
- Provide standard bracket for mounting of multi-purpose dry chemical extinguisher (2A:60B:C - 10lb), Basis of Design: Potter Roemer, Model 3010
Fire Extinguisher Cabinet Basis of Design: Potter Roemer, Model 7038
-Where no cabinet is scheduled for housing extinguisher, mount fire extinguisher on bracket @ 3' - 6" above finish floor.
TO
T
O P
O F
C
AB
IN
ET
4'
0"
Finish Floor
F I R E
E X T I N G U I S H E R
D R
AW
N
B Y
Project Number
Drawing Number c M
KS
D
, L
LC
MKSD, LLC
1209 Hausman Road Suite A Allentown, PA 18104
610.366.2081 mksdarchitects.com
Silvia A. Hoffman, AIA Todd O. Chambers, AIA Jill P. Hewes, AIA Jessica E. Klocek, AIA a r c h i t e c t s
Project
Client
Project Team
Date
Drawing Title
Revisions
Structural Engineer Barry Isett & Associates, Inc.
5420 Crackersport Rd Allentown, PA 18104 Project Contact: Ty Cunningham, SE, PE P: (484) 866-4835 E: tcunningham@barryisett.com
MEP Engineer Barry Isett & Associates, Inc.
5420 Crackersport Rd Allentown, PA 18104 Project Contact: Rebecca Schleicher,EIT P: (484) 225-5021 E: rschleicher@barryisett.com
Aquatics Consultant Vincent Aquatics 1823 Deep Run Road Pipersville, PA 18947 Project Contact: Matt Long P: (215) 778-1912 E: mlong@vincentpools.com
/1
7/
:0 9:
A
M
.1
W
AL
PO
A
N ew
C lu bh ou se _R
_C en tra l_ de ta ch ed .rv t
G002
Code Information & Life Safety Plan
Wild Acres Lakes Property and Homeowners Association
WALPOA - New Community Clubhouse
AH
S
06.16.25
20.193
100 Clubhouse Ln, Dingmans Ferry, PA 18328
06/16/2025 - Issued for Permit
CODE INFORMATION: Municipality: Delaware Township
Project Summary:
This project includes the construction of the new Wild Acre Lakes Property Owner's Association clubhouse. At approximately 9,900 SF, the new clubhouse will feature a new meeting room, indoor swimming pool, and gather spaces.
PLUMBING FIXTURE COUNT
The occupant loads for the facility are calculated by using IBC Table 1004.1.2
OCCUPANTS:
TOTALS : (A-3) = 418 occs = 209 M , 209 F
PLUMBING FIXTURE REQUIREMENTS:
WC LAV FTN SERVICE SINK
(A-3) 1/125 1/65 1/200 1/500 1 2 M , 4 F 2 M , 2 F 2 1
PROVIDED FIXTURE COUNT :
WC : 5M, 5F
URINAL : 3
LAV : 4M, 4F
SERV. SINK : 1
FTN : 2
IBC 2015 Code Review
Review No. Code Information Section No. Requirement
0 - PROJECT DATA
0.01 Occupancy Group 302 / 304 Assembly Group A-3 Community Hall, Indoor Swimming pool without spectators seating
0.02 Construction Type 602 / T 601 VB
0.03 Automatic Sprinkler Systems 903 Not Required in Assembly Group A-3 Occupancy
1 - BUILDING CONSTRAINTS
1.01 Building Height, Allowable 504 / T 504.3 40 feet ( non sprinklered, VB construction)
1.02 Building Height, Proposed 30 feet
1.03 Number of Stories, Allowable 504 / T 504.3 1 story
1.04 Number of Stories, Proposed 1 story
1.05 Building Area, Allowable 506.2.3 Aa = [At + (NS x If)] x Sa
1.06 T 506.2 At = 9,500SF
1.07 T 506.2 NS = 9,500 SF
1.08 If = 0.75
1.09 Sa = 1
1.10 Aa = [9,500+(9,500x0.75 ] x 1
1.11 Aa = 16,625 SF
1.12 Frontage, Increase 506.3 If = 100 [F/P - 0.25] W/30
1.13 F = 468 feet
1.14 P = 468 feet
1.15 W = 30 feet
1.16 If = 0.75
1.17 Building Area, Proposed
1.18 First Floor - 9,896 SF
2 - FIRE RESISTANCE RATINGS
2.01 Fire Wall T 706.4 2 HR
2.02 Fire Barriers between Building Areas T 707.3.10 2 HR; not applicable
2.03 Separation of Occupancies T 508.4 Not Applicable
2.04 Structural Frame T 601 0 HR
2.05 Bearing Wall, Exterior T 601 0 HR
2.06 Bearing Wall, Interior T 601 0 HR
2.07 Non-Bearing Wall, Exterior T 601 0 HR
2.08 Fire Separation Distance T 602 >30'
2.09 Non-Bearing Partition, Interior T 601 0 HR
2.10 Floor Construction T 601 0 HR
2.11 Roof Construction T 601 0 HR
2.12 Shafts, Required Enclosure 713 Shafts required to protect openings and penetrations through floor/ceiling and roof/ceiling assemblies
2.13 Shafts, Rating 713.4 Not < 1 hr., connecting 4 stories or less, not < than the floor being penetrated; max 2 hours
2.14 Corridor Fire-Resistance Rating T 1020.1 0 HR w/ sprinkler system
2.15 Minimum Corridor Width T 1020.2 44 inches or 36 inches if serving an occupant load of less than 50
2.16 Vertical Exit, Rating 1023.2 not < 1 hr., connecting 4 stories or less, not < than the floor being penetrated; max 2 hours
2.17 Exterior Area of Rescue Assistance 1009.7
3 - OCCUPANCY
3.00 See Life Safety Plan for detailed Occupancy Count
3.01 Occupancy Load Total T 1004.1.1 Total - 448 Occupants
4 - EGRESS
4.01 Minimum number of exits T 1006.3.1 2 exits min. per floor (1-500 occupants); 3 exits min. per floor (501-1000 occupants); 4 exits min. per floor (>1000 occupants)
4.02 Spaces with One Exit T 1006.2.1 Assembly Group A-3 Occupancy - spaces with 49 or less occupants
4.03 Maximum Common Path of Egress Travel Distance T 1006.2.1 75 ft. travel distance in Assembly Group A-3 (Non Sprinklered, OL<30)
5 - EGRESS WIDTH
5.01 Doorways, per Occupant served 1005.3.2 0.2" per occupant (36” door allows 170 occupants and 72” opening allows 340 occupants)
5.02 Doors, minimum size 1010.1 32” clear width = 34" door
5.03 Corridors, per Occupant served 1005.3.2 0.2” per occupant
5.04 Corridors, minimum size 1020.2 44" unless exceptions apply
5.05 Stairs, per Occupant served 1005.3.1 0.3” per occupant served
5.06 Stairs, minimum size 1011.2 44”
5.07 Stairs, Accessible egress 1009.3 48" min. clear between handrails
5.08 Area of Refuge 1009.3, Exception 5 Not Req'd in stariways in sprinklered bldg.
5.09 Two-way Communication 1009.8 Required at each landing serving each elevator on each accessible floor that is >1 stories above or below level of exit discharge
6 - EGRESS ACCESS DISTANCES
6.01 Exit Access Travel Distance
6.02 Most remote point to exit T 1017.2 200’ without sprinkler system
6.03 Common path Egress travel 1006.2.1 75’ without spinkler system
6.04 Dead End corridors 1020.4 20’ max
7 - INTERIOR FINISHES
7.01 Vertical Exits T 803.11 Class A
7.02 Exit Corridors T 803.11 Class A, Class B -Lobby
7.03 Rooms / Enclosed Spaces T 803.11 Class C
8 - FIRE PROTECTION
8.01 Where Required, by Use Group 903.2 Not required in Use Group A-3 Occupancy
9 - EMERGENCY PROVISIONS
9.01 Fire Alarm (by Use Group) 907.2.1 Manual req'd. for occupancy > 300 Group A
9.02 Emergency Lighting 1008 Required; 1 foot-candle average, 0.1 fc min.; exit access corridors, aisles in rooms requiring 2 exits, portion of exterior exit discharge immediately adjacent to the exit discharge doorways in buildings required to have 2 exits.
9.03 Emergency Lighting 1008.3 Illumination of means of egress, including exit discharge
9.04 Fire Extinguishers 906, T 906.3 1- 2A per 3,000 sf. max. floor area per unit of A
9.05 Fire Extinguishers 906, T 906.3 11,250 sf. max. floor area for fire extinguisher
9.06 Fire Extinguishers 906, T 906.3 75' max. travel distance to fire extinguisher
10 - HAZARDOUS AREAS
10.01 Furnace Rooms > 400,000 BTUH Output T 509 1 hr. separation or automatic sprinkler system, N/A
10.02 Boiler Rooms > 15 psi and 10hp T 509 1 hr. separation or automatic sprinkler system N/A
10.03 Laundry Rooms > 100sf T 509 1 hr. separation or automatic sprinkler system N/A
11 - ACCESSIBILITY
11.01 Scoping requirements 1103.1 All buildings, including associated sites, shall be accessible, unless specifically exempted.
11.02 Scoping requirements 1103.2.2 Work areas – 300 sq ft or less & elevated 7” + above f.f. where the elevation is essential to the function of the space shall be exempt from all requirements.
11.03 Scoping requirements 1103.2.9 Spaces frequented only by personnel for maintenance, repair or monitoring of equipment are not required to be accessible.
11.05 Accessible Route 1104.1 Site arrival point, see civil drawings
11.06 Accessible Route 1104.2 At least one accessible route shall connect accessible elements on the same site
11.07 Accessible Route 1104.3 Accessible route can not pass through kitchens, storage rooms, restrooms, closets, etc.
11.09 Accessible Route 1104.3.1.1 Common use circulation paths within employee work areas shall be accessible routes.
11.10 Accessible Entrances 1105.1 At least 60 % of all public entrances shall be accessible, All entrances used for emergency egress to be accessible
11.11 Parking & Passenger Loading 1106 Where parking is provided accessible parking shall be provided
11.12 Number of Parking Spaces T 1106.1 1 HC per 25
11.13 Van Accessible Spaces 1106.5 1 van accessible per 6 HC
11.14 Location 1106.6 Shortest route to accessible entry
11.18 Unisex Toilet 1109.3 At least 5% but not less than one sink provided in accessible spaces shall comply with ICC A117.1-2003
1/8" = 1'-0"1 Level 1 - Life Safety Plan
Room Schedule
Number Name Area Function of Space Load Factor Occupancy M Plumb.
Fixture Count W Plumb.
Fixture Count
100 Lobby 604 SF Circulation 0 0 0 0 101 Women's 137 SF Toilet 0 0 0 0 102 Men's 135 SF Toilet 0 0 0 0 103 Corridor 64 SF Circulation 0 0 0 0 104 Men's 170 SF Toilet 0 0 0 0 105 Women's 168 SF Toilet 0 0 0 0 106 Sauna 131 SF Business area 100 gross 2 0.04 0.04 107 Pool Deck 2025 SF Assembly
(unconcentrated) 15 net 136 0.91 1.7
107A Pool 1089 SF Swimming pools 50 gross pool/15 gross deck 112 0.1 1.4 108 Storage 173 SF Accessory Storage 300 1 0.01 0 109 Pool Equipment 131 SF Accessory Storage 300 gross 1 0.01 0 110 Main Room 1996 SF Assembly
(unconcentrated) 15 net 106 0.42 0.82
111 Storage 260 SF Gaming floors 11 gross 2 0.01 0.01 112 Mechanical 214 SF Accessory 0 0 113 Activities 370 SF Business area 100 gross 4 0.02 0.02 114 Fireside Room 1011 SF Assembly
(unconcentrated) 15 net 48 0.32 0.32
115 Kitchen 277 SF Business area 100 gross 3 0.06 0.06 116 Storage 75 SF Accessory Storage 300 gross 1 0.01 0.01 117 Bonus Room 165 SF Business area 100 gross 2 0.04 0.04 Totals 418 1.95 4.42
N
All construction has been designed to meet the provisions of the Pennsylvania Uniform Construction Code (UCC). The UCC Administration and Enforcement regulation has adopted the following codes for use throughout the Commonwealth of Pennsylvania, effective 2/14/2022.
Pennsylvania Uniform Construction Code
International Building Code 2018 (IBC 2018) excluding chapter 1 (most of its requirements are incorporated in Chapter 403 of the UCC regulation). Chapter 27 (Electrical) requires that all electrical components, equipment and systems in buildings and structures covered by the IBC comply with the requirements of NFPA 70-2017, National Electrical Code
Chapter 11, International Building Code 2018 Accessibility Requirements
International Energy Conservation Code 2018 (IECC 2018)
International Fire Code 2018 (IFC 2018) only to the extent referenced in Chapter 35 of the IBC 2018
International Mechanical Code 2018 (IMB 2018)
International Plumbing Code 2018 (IPC 2018)
American National Standard Accessible and Usable Buildings and Facilities 2009 (ICC A117.1-2009)
1 1/2" = 1'-0"2 Fire Extinguisher Cabinet Detail
DESIGN LOADS:
DESIGN FLOOR LIVE LOADS
ROOF LIVE LOAD 20 PSF
ROOF 20 PSF
FLOOR 15 PSF
SEISMIC IMPORTANCE FACTOR (Ie) 1.25
ADDITIONAL NOTES:
a. THE CONTRACTOR IS CAUTIONED AS TO NOT STORE ANY
CONSTRUCTION MATERIALS OR UNDERTAKE ANY CONSTRUCTION
OPERATION WILL EXCEED THE DESIGN LIVE LOAD CAPACITIES NOTED.
b. THE STRUCTURE HAS BEEN DESIGNED FOR THE DEAD AND LIVE
LOADS INDICATED ABOVE, ANY INCREASE OF LOADS DUE TO CHANGE
IN USAGE OR CONSTRUCTION MATERIALS, ETC. SHALL HAVE THE
WRITTEN APPROVAL OF THE ENGINEER.
c. THE STABILITY OF THE STRUCTURE IS DEPENDENT UPON THE
DIAPHRAGM ACTION OF THE ROOFS. THE CONTRACTOR IS
COMPLETELY RESPONSIBLE FOR THE METHODS OF CONSTRUCTION
AND SHALL PROVIDE ALL GUYS, BRACING AND SHORING REQUIRED TO
ACCOMMODATE ALL INTERIM LOADING CONDITIONS THROUGHOUT
THE CONSTRUCTION PHASE.
d. WEIGHT OF EQUIPMENT SHOWN ON THE STRUCTURAL DRAWINGS
HAVE BEEN CONSIDERED IN THE DESIGN OF THE FRAMING. ANY
ADDITIONAL EQUIPMENT NOT SHOWN ON THE STRUCTURAL
DRAWINGS AND EXCEEDING 300 POUNDS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER FOR APPROVAL PRIOR TO
INSTALLATION.
GOVERNING DESIGN CODE
2018 INTERNATIONAL BUILDING CODE
ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
BUILDING RISK CATEGORY
DESIGN ROOF LIVE LOADS
DESIGN DEAD LOADS - NOT INCL. STRUCTURE SELF WEIGHT
SEISMIC DESIGN DATA
DESIGN WIND LOAD PARAMETERS
MECHANICAL UNIT LOADS SEE MECH DWGS
STAIRS AND EXITS 100 PSF
HANDRAILS, GUARDS AND GRAB BARS PER 1607.8
GROUND SNOW LOAD (Pg) 50 PSF
DESIGN ROOF SNOW LOADS
FLAT ROOF SNOW LOAD (Pf) 43 PSF
SNOW EXPOSURE FACTOR (Ce) 1.0
SNOW LOAD IMPORTANCE FACTOR (Is) 1.10
THERMAL FACTOR (Ct) 1.10
SNOW DRIFT SEE DIAGRAM
UNBALANCED ROOF SNOW LOADS
ROOF SLOPE FACTOR (Cs) 1.0
SLOPED ROOF SNOW LOAD 43 PSF
WINDWARD SNOW LOAD 13 PSF
LEEWARD SNOW LOAD EXTENDING 8'-0" FROM RIDGE 74 PSF
III
LEEWARD SNOW LOAD 8'-0" FROM RIDGE EXTENDING TO EAVE 43 PSF
MINIMUM UNIFORM DESIGN SNOW LOAD (NOT REDUCIBLE) 43 PSF
ULTIMATE DESIGN WIND SPEED (Vult) 119 MPH
ALLOWABLE STRESS DESIGN WIND SPEED (Vasd) 93 MPH
INTERNAL PRESSURE COEFFICIENT +/- 0.18
WIND EXPOSURE CATEGORY - PLAN WEST-EAST B
MAPPED SPECTRAL ACCELERATION (Ss)
MAPPED SPECTRAL ACCELERATION (S1)
SITE CLASS
DESIGN SPECTRAL RESPONSE COEFF. (Sds)
DESIGN SPECTRAL RESPONSE COEFF. (Sd1)
SEISMIC DESIGN CATEGORY
PLAN NORTH-SOUTH DIRECTION
SEISMIC FORCE RESISTING SYSTEM
DESIGN BASE SHEAR (V)
0.19
0.05
D
0.20
0.09
B
LIGHT FRAME WOOD
SHEAR WALLS
7.5 KIPS
ANALYSIS PROCEDURE EQUIV. LATERAL FORCE
RESPONSE MODIFICATION COEFF. (R)
SEISMIC RESPONSE COEFF. (Cs) 0.0385
PLAN WEST-EAST DIRECTION
SEISMIC FORCE RESISTING SYSTEM
DESIGN BASE SHEAR (V) 7.5 KIPS
RESPONSE MODIFICATION COEFF. (R) 6.5
SEISMIC RESPONSE COEFF. (Cs) 0.0385
WIND EXPOSURE CATEGORY - PLAN NORTH-SOUTH B
ROOF RAIN LOADS
INTENSITY (i) 3.0 IN/HR
LIGHT FRAME WOOD
SHEAR WALLS
6.5
ATTIC 40 PSF
GENERAL NOTES
1. THE CONTRACTOR IS ADVISED THAT ALL PLANS, DIMENSIONS, AND DETAILS DEPICT
FIELD CONDITION AS SHOWN. MINOR VARIATIONS ARE TO BE EXPECTED AND ANY
DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE APPROVED BY THE
ARCHITECT IN WRITING PRIOR TO PROCEEDING.
2. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND
ELEVATIONS OF EXISTING WORK PRIOR TO FABRICATION OF ANY NEW MATERIALS.
IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE
WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION
WITH THEIR PROPOSED MODIFICATION OF THE DETAILS GIVEN ON THE CONTRACT
DOCUMENTS. DO NOT COMMENCE WORK UNTIL CONDITION IS RESOLVED AND
MODIFICATION IS APPROVED BY THE ENGINEER.
3. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE LOCATION OF
UTILITIES IN THE IMMEDIATE VICINITY OF CONSTRUCTION SO AS TO PREVENT
DAMAGE TO THEM. SHOULD DAMAGE TO SUCH UTILITIES OCCUR, THE CONTRACTOR
SHALL BE REQUIRED TO REPAIR SUCH DAMAGE AT THEIR OWN EXPENSE AND TO
THE SATISFACTION OF THE OWNER.
4. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT
DOCUMENTS MUST BE SUBMITTED BY THE GENERAL CONTRACTOR AND REVIEWED
BY THE ENGINEER. IF THE CONTRACTOR OR OWNER FAILS TO OBTAIN ENGINEER'S
REVIEW OF THE SHOP DRAWINGS, THE ENGINEER WILL NOT BE RESPONSIBLE FOR
THE STRUCTURAL CERTIFICATION AND DESIGN OF THE PROJECT. SHOP DRAWINGS
ARE REVIEWED BY THE ENGINEER AS A CONVENIENCE TO THE GENERAL
CONTRACTOR AND ARE NOT A CONTRACT DOCUMENT.
5. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE PLACED ON THE
STRUCTURE. A CONCRETE STRUCTURE MAY NOT SUPPORT IT'S DESIGN LIVE LOAD
FOR 28 DAYS. CONTRACTOR SHALL SUPPORT ADJACENT STRUCTURES, UTILITIES,
AND EXCAVATIONS AS REQUIRED. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
FOR ALL TEMPORARY FORM WORK, SHEETING, SHORING AND UNDERPINNING
SEALED BY A PROFESSIONAL ENGINEER AS A PART OF THE CONTRACTOR'S WORK.
6. THE CONTRACTOR SHALL CONSULT THE ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS FOR THE QUANTITY, LOCATION, AND DIMENSION OF HOLES
THROUGH FLOOR AND ROOF: CHASES, INSERTS, OPENINGS, SLEEVES, WASHERS,
DRIPS, REVEALS, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS. REFER TO
ARCHITECTURAL DRAWINGS FOR THE FOLLOWING INFORMATION:
a. LOCATION AND THICKNESS OF MASONRY PARTITIONS
b. FULL EXTENT OF MASONRY INFILL AREAS
c. LOCATION AND THICKNESS OF STUD PARTITIONS
d. LOCATION AND SIZE OF WINDOWS, DOORS AND WALL OPENINGS
e. STAIRS, FLOOR AND WALL FINISHES
f. DETAIL DIMENSIONS AND SECTION DETAILS AS REQUIRED
7. THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND STABLE
AFTER THE CONSTRUCTION OF THE BUILDING IS TO BE COMPLETED. THE STABILITY
OF THE STRUCTURE PRIOR TO COMPLETION IS SOLELY THE RESPONSIBILITY OF
THE CONTRACTOR. THIS RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF
THE CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION
METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, FORMS, SHORING, USE OF
EQUIPMENT AND SIMILAR CONSTRUCTION PROCEDURES.
8. THE CONTRACTOR SHALL BE RESPONSIBLE TO DETERMINE ALLOWABLE
CONSTRUCTION LOADS AND TO PROVIDE DESIGN AND CONSTRUCTION OF
FALSEWORK, FORMWORK, STAGING, BRACING, SHEETING, SHORING, AND
UNDERPINNING AS NECESSARY TO PREVENT ANY LATERAL OR VERTICAL
MOVEMENTS TO, AND TO INSURE THE STRUCTURAL INTEGRITY OF EXISTING
BUILDINGS, STREETS, AND ANY EXISTING UTILITY LINES.
9. BRACING, SHEETING, SHORING, ETC., REQUIRED TO INSURE THE STRUCTURAL
INTEGRITY OF THE EXISTING BUILDINGS OR NEW CONSTRUCTION, SIDEWALKS,
UTILITIES ETC., SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER ENGAGED BY
THE CONTRACTOR. DETAILED SIGNED AND SEALED SHOP DRAWINGS SHALL BE
PREPARED INDICATING ALL WORK TO BE PERFORMED. SUBMIT THE SHOP
DRAWINGS IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS.
SHOP DRAWINGS
1. DUPLICATION/PHOTOCOPYING OF THESE STRUCTURAL DRAWINGS SHALL NOT BE
PERMITTED FOR SHOP DRAWINGS. THIS INCLUDES PARTIAL AND/OR COMPLETE
DUPLICATION OF PLAN SHEETS AS BACKGROUNDS FOR SHOP DRAWINGS. ALL
SECTIONS INCLUDED IN THESE CONTRACT DRAWINGS MAY NOT BE
DUPLICATED/PHOTOCOPIED ON ANY SHOP DRAWINGS.
2. ORIGINAL SHOP DRAWINGS SHALL BE SUBMITTED FOR THE ARCHITECT/ENGINEER
REVIEW FOR THE FOLLOWING ITEMS AND AS PER THE SPECIFICATIONS:
a. CONCRETE AND MASONRY REINFORCING
b. SLAB ON GRADE CONTROL JOINT LAYOUT
c. CONCRETE MIX DESIGNS
• FOUNDATIONS
• RETAINING WALLS
• ELEVATED SLABS
• SLAB ON GRADE LISTING FIBER MESH REINFORCEMENT & DOSAGE RATE
d. MASONRY CERTIFICATIONS AND GROUT DESIGN
e. STEEL JOIST AND DECKING
f. STRUCTURAL STEEL
g. LIGHT GAGE METAL FRAMING
h. PRECAST CONCRETE
3. CONTRACTOR SHALL SUBMIT, FOR REVIEW, DRAWINGS AND CALCULATIONS FOR
ALL PERFORMANCE ASSEMBLIES IDENTIFIED IN THE GENERAL NOTES AND SPECIFIC
MATERIAL NOTES AS WELL AS LISTED BELOW: THE DESIGN OF THESE ASSEMBLIES
IS THE RESPONSIBILITY OF THE CONTRACTOR'S ENGINEER REGISTERED IN THE
PROJECT'S JURISDICTION. ALL SUBMITTALS SHALL BEAR THIS ENGINEER'S SEAL
AND SIGNATURE. REVIEW SHALL BE FOR GENERAL CONFORMANCE WITH THE
PROJECT REQUIREMENTS AS INDICATED ON THE DRAWINGS AND IN THE GENERAL
NOTES.
a. METAL STAIRS AND METAL RAILINGS: DESIGNS SHALL TAKE INTO ACCOUNT
ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING
CODES. WHERE HEADERS OR OTHER TYPES OF STRUCTURAL MEMBERS
HAVE BEEN DESIGNATED BY THE STRUCTURAL ENGINEER OF RECORD TO
SUPPORT THE STAIRS, THE CONNECTIONS FROM THE STAIRS SHALL BE
DESIGNED SO THAT NO ECCENTRIC OR TORSIONAL FORCES ARE INDUCED
IN THESE STRUCTURAL MEMBERS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR FURNISHING AND INSTALLING HARDWARE AS REQUIRED
BY THE STAIR DESIGN.
CONTRACTOR SHALL VERIFY ALL CONDITIONS
AND DIMENSIONS FOR THE ENTIRE PROJECT
BEFORE PROCEEDING WITH THE WORK.
A.F.F. Above Finish Floor BCX Bottom Chord Extension B.O.F. Bottom of Footing B.S. Brick Shelf Elevation (plans) B.S. Both Sides (sections) CANT. Cantilever CJ Control Joints CL Center Line CMU Concrete Masonry Units CONT. Continuous DIA. Diameter DBA Deformed Bar Anchor E.E. Each End E.F. Each Face E.S. Each Side E.W. Each Way EXIST Existing F.F. Finish Floor F.S. Flat Strap GA Gage GALV Galvanized HORIZ Horizontal HSS Hollow Structural Section L Angle
ABBREVIATION LIST
LG Long LLH Long Leg Horizontal LLV Long Leg Vertical LSH Long Side Horizontal LSV Long Side Vertical N.T.S. Not To Scale o.c. On Center PL Plate REINF. Reinforcing REM. To Remain S.F. Step Footing STIFF PL Stiffener Plate T.B.R. To Be Removed T&B Top and Bottom T.F. Top of Footing T.O.S. Top of Steel T.O.W. Top of Wall T.P. Top of Pier TYP Typical U.N.O. Unless Noted Otherwise VERT. Vertical V.I.F. Verify In Field WWF Welded Wire Fabric XE Extended End - Type R
CONTRACTOR NOTE
CONCRETE WALL SHALL BE IN PLACE A MINIMUM OF 14 DAYS
BEFORE BACKFILLING. AT CONTRACTOR'S OPTION, BACKFILL MAY
BE PLACED AGAINST WALL THAT HAS BEEN TEMPORARILY SHORED;
HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING
ANY MOVEMENT OF WALL DUE TO BACKFILLING.
FOUNDATIONS AND BACKFILL
1. SOIL BEARING CAPACITY OF 2,000 PSF WAS UTILIZED IN THE DESIGN OF THE
FOUNDATION SYSTEM.
2. SLAB ON GRADE DESIGN BASED ON MODULUS OF SUBGRADE REACTION OF 100 PCI.
3. PLACE EXTERIOR FOOTINGS AND FROST WALLS EXPOSED TO WEATHER AT LEAST
48" BELOW THE ADJACENT OUTSIDE FINISHED GRADE TO PROTECT FROM FROST
DAMAGE.
4. THE OWNER SHALL ENGAGE THE SERVICES OF A REGISTERED PROFESSIONAL
GEOTECHNICAL ENGINEER OR CERTIFIED INSPECTION FIRM TO MONITOR AND
INSPECT ALL EARTH WORK AND TO PERFORM THE SPECIAL INSPECTIONS
REQUIRED BY THE SCHEDULE OF SPECIAL INSPECTIONS. THE GEOTECHNICAL
ENGINEER SHALL SUPERVISE THE PLACING OF THE COMPACTED FILL AND ALL THE
MATERIALS AND EQUIPMENT USED FOR THIS PURPOSE. THE GEOTECHNICAL
ENGINEER SHALL CERTIFY, BY SEAL AND SIGNATURE, THAT THE EARTH-WORK IS IN
ACCORDANCE WITH THE GEOTECHNICAL REPORT, PLANS AND SPECIFICATIONS.
5. THE SUB-FLOOR MATERIALS SHALL CONSIST OF AT LEAST FOUR TO SIX INCHES OF
GRAVEL OR CRUSHED STONE. THE SUB-FLOOR MATERIALS SHALL BE COMPACTED
BY AT LEAST FOUR COVERAGES OF A HEAVY-DUTY VIBRATORY ROLLER OR UNTIL
NO FURTHER COMPACTION IS OBSERVED. SEE THE DRAWINGS AND
SPECIFICATIONS FOR THE VAPOR BARRIER SIZE, TYPE AND LOCATION.
6. PRIOR TO CONCRETE PLACEMENT THE FOUNDATION BOTTOM SHALL BE
COMPACTED USING A WALK BEHIND VIBRATORY ROLLER OR GAS-POWERED
TAMPER.
7. IF SOIL OF THE BEARING CAPACITY NOTED ABOVE IS NOT ENCOUNTERED AT THE
ELEVATIONS SHOWN ON PLAN, UNSUITABLE SOILS SHALL BE REMOVED AND
REPLACED WITH STRUCTURAL FILL IN ACCORDANCE WITH THE GEOTECHNICAL
ENGINEER'S DIRECTION.
8. IF BEDROCK IS ENCOUNTERED AT OR ABOVE FOUNDATION SUBGRADE ELEVATION,
THE BEDROCK SURFACE SHALL BE OVER EXCAVATED A MINIMUM OF SIX INCHES
AND BACKFILLED WITH CRUSHED STONE TO THE SUBGRADE ELEVATION.
9. THE GEOTECHNICAL ENGINEER SHALL APPROVE SAMPLES OF ALL CONTRACTOR
PROPOSED COMPACTED FILL MATERIAL. IMPORTED STRUCTURAL FILL SHALL BE
FREE OF ORGANIC MATTER, ASH, CINDERS AND DEMOLITION DEBRIS.
10. CONTROL OF MOISTURE FOR PLACING FILL WILL BE BASED ON THE RESULTS OF
ASTM D-1557 MODIFIED PROCTOR TESTS.
11. ALL COMPACTED FILL SHALL HAVE A DENSITY OF AT LEAST 98% OF MAXIMUM DRY
DENSITY AS DETERMINED BY THE ASTM D-1557 MODIFIED PROCTOR TEST. PLACING
OF FILL WITH MOISTURE CONTENT OUTSIDE THE LIMITS FOR PROPER COMPACTION
SHALL NOT BE PERMITTED.
12. THE EXISTING SUBGRADE IN ALL FILL AND CUT AREAS SHALL BE COMPACTED TO A
FIRM, STABLE CONDITION AS DETERMINED BY THE GEOTECHNICAL ENGINEER,
PRIOR TO PLACEMENT OF FILLS AND EXCAVATION FOR FOOTINGS.
13. FILL MATERIAL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS
AND SHALL BE MIXED, SPREAD, AND PLACED IN SUCH A WAY AS TO PRODUCE A
UNIFORM THICKNESS OF MATERIAL AFTER PLACING.
14. EACH LAYER OF FILL MATERIAL SHALL BE COMPACTED ON ALL PORTIONS OF THE
SURFACE OF EACH LIFT OF FILL BY RUBBER TIRE ROLLERS, SHEEP'S FOOT
ROLLERS, VIBRATORY ROLLERS, ETC. AS NECESSARY TO ATTAIN THE MAXIMUM DRY
DENSITY NOTED ABOVE AND AS APPROVED BY THE GEOTECHNICAL ENGINEER.
15. WHENEVER IN PLACE DENSITIES ARE FOUND TO BE BELOW LIMITS ACCEPTABLE TO
THE GEOTECHNICAL ENGINEER, ADDITIONAL ROLLING TO PRODUCE THE SPECIFIED
DENSITIES SHALL BE REQUIRED.
16. PLACING OF FILL WHEN FREE WATER IS STANDING ON THE EXISTING SURFACE
SHALL NOT BE PERMITTED.
17. PLACING OF FILL IN A FROZEN CONDITION OR ON TOP OF FROZEN MATERIAL SHALL
NOT BE PERMITTED.
18. SUBGRADE SUITABILITY SHALL BE VERIFIED BY GEOTECHNICAL ENGINEER WITHIN
24 HOURS PRIOR TO PLACING CONCRETE FOUNDATIONS AND CONCRETE SLABS ON
GRADE TO CONFIRM THAT NO DETERIORATION HAS OCCURRED SUBSEQUENT TO
TESTING PERFORMED AT TIME OF FILL PLACEMENT. UNSUITABLE CONDITIONS
SHALL BE CORRECTED PER GEOTECHNICAL ENGINEER'S RECOMMENDATION.
19. EXCAVATIONS SHOULD BE BACKFILLED OR HAVE CONCRETE PLACED AS SOON AS
POSSIBLE DURING CONSTRUCTION TO MINIMIZE ADVERSE AFFECTS TO SUBGRADE
CONDITIONS. GRADING DEPRESSIONS SHOULD BE AVOIDED.
20. WATER SHALL BE PREVENTED FROM ENTERING OPEN EXCAVATIONS. ANY
ACCUMULATED WATER SHALL BE REMOVED AS SOON AS POSSIBLE. IT IS
RECOMMENDED THAT CONCRETE BE PLACED THE SAME DAY THE EXCAVATION IS
MADE.
21. THE CONTRACTOR SHALL PROVIDE FOR DEWATERING AS REQUIRED DURING
EXCAVATION AND CONSTRUCTION.
CONCRETE
1. ALL WORK SHALL CONFORM TO THE "SPECIFICATIONS FOR STRUCTURAL
CONCRETE" (AMERICAN CONCRETE INSTITUTE, ACI 301) AND THE "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318), LATEST EDITIONS, UNLESS
NOTED OTHERWISE IN THE DRAWINGS OR PROJECT SPECIFICATIONS.
2. CONSTRUCTION TOLERANCES SHALL CONFORM TO THE "SPECIFICATION FOR
TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" (ACI 117), LATEST
EDITION.
3. SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE "GUIDE TO
PRESENTING REINFORCING STEEL DESIGN DETAILS" (ACI 315) AND THE "ACI
DETAILING MANUAL" (SP-066), LATEST EDITIONS.
4. CONCRETE MATERIALS SHALL BE PROVIDED IN ACCORDANCE WITH THE
FOLLOWING SPECIFICATIONS:
• PORTLAND CEMENT ASTM C150
• HYDRAULIC CEMENT ASTM C1157
• FLY ASH AND NATURAL POZZOLAN ASTM C618
• SLAG CEMENT ASTM C989
• SILICA FUME ASTM C1240
• NORMAL WEIGHT AGGREGATE ASTM C33
• LIGHTWEIGHT AGGREGATE ASTM C330
• MIXING WATER ASTM C1602
• ADMIXTURES
• WATER REDUCTION AND SETTING TIME MODIFICATION ASTM C494
• PRODUCING FLOWING CONCRETE ASTM C107
• AIR ENTRAINMENT ASTM C260
• INHIBITING CHLORIDE-INDUCED CORROSION ASTM C1582
5. REINFORCING MATERIALS:
• REINFORCING BARS PLAIN-STEEL ASTM A615, GRADE 60, DEFORMED
• REINFORCING BARS LOW-ALLOY-STEEL ASTM A706, DEFORMED
(WELDABLE)
• REINFORCING BARS EPOXY-COATED ASTM A775
• WELDED WIRE FABRIC ASTM A1064
• EPOXY-COATED WELDED WIRE FABRIC ASTM A884, CLASS A COATING
6. REINFORCING SHALL COMPLY WITH ACI FOR FABRICATING, PLACING, AND
SUPPORTING REINFORCEMENT, AND THE FOLLOWING:
• BAR SPLICE LOCATIONS SHALL CONFORM TO ACI 318
• HORIZONTAL REINFORCING BARS IN WALLS AND FOOTINGS SHALL BE
CONTINUOUS AROUND CORNERS.
• UNLESS DETAILED CALCULATIONS ARE PROVIDED, REINFORCING BARS
DEVELOPMENT LENGTHS, EMBEDMENT DEPTHS AND LAP SPLICE DISTANCES
FOR f'c = 4000psi, NORMAL-WEIGHT CONCRETE, SHALL BE PER BELOW
7. EMBEDDED AND MISCELLANEOUS STEEL SHALL COMPLY WITH ASTM A36.
8. ALL EXPOSED CONCRETE CORNERS SHALL BE CHAMFERED 3/4" AT 45 DEGREES
UNLESS NOTED OTHERWISE.
9. SHALLOW INTERIOR FOUNDATIONS AND SLABS ON GRADE ARE NOT DESIGNED FOR
OR INTENDED TO BE EXPOSED TO FREEZE/THAW CYCLING OR RESIST FROST
HEAVE FORCES. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AND
PROVIDE INTERIOR FOOTINGS BELOW FROST PENETRATION AS REQUIRED FOR
WINTER CONSTRUCTION.
10. PROVIDE CONSTRUCTION / CONTROL JOINT INSTALLATION PLAN AND PLACEMENT
SEQUENCE PLAN SUBMITTALS FOR REVIEW OF STRUCTURAL ENGINEER OF
RECORD PRIOR TO PLACING CONCRETE.
11. PROVIDE WALL AND SLAB THRU-SLEEVE PLAN SUBMITTALS FOR REVIEW OF
STRUCTURAL ENGINEER OF RECORD PRIOR TO PLACING CONCRETE.
12. CORE-DRILLING CONCRETE WALLS, SLABS, BEAMS OR COLUMNS WITHOUT
REINFORCING LOCATION SCANS AND PRIOR APPROVAL OF STRUCTURAL ENGINEER
OF RECORD SHALL NOT BE PERMITTED.
13. CONDUITS AND PIPES SHALL NOT BE EMBEDDED IN ELEVATED CONCRETE SLABS
SUPPORTED BY METAL DECK OR CONCRETE SLABS ON GRADE.
14. FIBER REINFORCED CONCRETE SHALL COMPLY WITH "GUIDE TO DESIGN WITH
FIBER-REINFORCED CONCRETE" (ACI 544.4), LATEST EDITION. DESIGN
CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES AND
SPECIFICATIONS.
15. NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107 AND ACHIEVE A MINIMUM 28
DAY COMPRESSIVE STRENGTH OF 8,000 psi.
16. STRUCTURAL ADHESIVES SHALL ONLY BE USED WITH PRIOR PERMISSION OF THE
STRUCTURAL ENGINEER OF RECORD OR AS SHOWN ON CONSTRUCTION
DOCUMENTS. THE BASIS OF DESIGN FOR ADHESIVES IS HY-200 BY "HILTI" OR SET BY
"SIMPSON" - THE USE OF ANY OTHER STRUCTURAL ADHESIVES SHALL BE SUBJECT
TO REVIEW BY THE EOR PRIOR TO INSTALLATION.
17. MINIMUM WIRE WELDED FABRIC REQUIREMENTS FOR SLABS:
• 3-1/2" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9
• 5" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9
• 4" FLOOR SLAB ON GRADE 66-W2.9xW2.9
• 5" FLOOR SLAB ON GRADE 44-W4.0xW4.0
18. COLD-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 306R. THE USE OF CALCIUM CHLORIDE, SALT, AND OTHER MATERIALS
CONTAINING ANTI- FREEZE AGENTS OR CHEMICAL ACCELERATORS SHALL NOT
BE PERMITTED UNLESS ACCEPTED IN THE MIX DESIGN.
19. HOT-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 305.
20. MINIMUM CONCRETE CLEAR COVER SHALL BE PROVIDED FOR REINFORCEMENT
PER ACI AND THE FOLLOWING:
• CONCRETE CAST AGAINST EARTH & PERMANENTLY 3"
EXPOSED
• CONCRETE EXPOSED TO EARTH OR WEATHER
#6 & LARGER 2"
#5 & SMALLER 1-1/2"
• CONCRETE NOT EXPOSED TO WEATHER OR GROUND
SLABS, WALLS, AND JOINTS 3/4"
BEAMS AND COLUMNS 1-1/2"
BAR LOCATION
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
BAR SIZE
#3 ld ls ldh
20" 25" 8"
15" 19" 8"
#4 ld ls ldh
25" 33" 10"
19" 25" 10"
#5 ld ls ldh
32" 41" 12"
24" 31" 12"
REBAR LAP SPLICE LENGTHS
20" 25" 8" 25" 33" 10" 32" 41" 12"
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
#6 ld ls ldh
38" 50" 15"
29" 38" 15"
#7 ld ls ldh
55" 71" 17"
42" 54" 17"
#8 ld ls ldh
62" 81" 19"
47" 62" 19"
38" 50" 15" 55" 71" 17" 62" 81" 19"
NOTE:
• VALUES ABOVE ARE FOR NORMAL WEIGHT CONCRETE ONLY.
• ld = MINIMUM TENSION DEVELOPMENT LENGTH
• ldh = MINIMUM 90 DEGREE HOOKED BAR DEVELOPMENT LENGTH
• ls = MINIMUM LENGTH OF LAP SPLICES IN TENSION
BAR SIZE
CONCRETE MIX DESIGN CRITERIA
FOOTINGS AND
FOUNDATION WALLS
INTERIOR SLABS ON
GRADE
EXPOSURE
CLASS
F1,S0,W0,C1
MAX. w/c
RATIO
0.55
MIN. f'c
3,500
AIR
CONTENT
5%
CEMENT
TYPE
I or II
INTERIOR ELEVATED
SLABS
EXTERIOR SLABS
F0,S0,W0,C1 0.50 4,000 N/A I or II
F0,S0,W0,C1 0.50 4,000 N/A I or II
F3,S0,W0,C2 0.40 5,000 6% I or II
STRUCTURAL STEEL
1. DESIGN, FABRICATION AND ERECTION OF THE STRUCTURAL STEEL SHALL COMPLY
WITH THE LATEST EDITION OF THE FOLLOWING STANDARDS, EXCEPT WHERE MORE
STRINGENT REQUIREMENTS ARE SHOWN:
• AISC "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF
STRUCTURAL STEEL FOR BUILDINGS", INCLUDING THE "COMMENTARY" AND
SUPPLEMENTS THERETO AS ISSUED.
• AISC "SPECIFICATIONS FOR ARCHITECTURALLY EXPOSED STRUCTURAL
STEEL".
• AISC "SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A-325 OR
A-490 BOLTS".
• AMERICAN WELDING SOCIETY (AWS) D1.1 "STRUCTURAL WELDING CODE-
STEEL"
• AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
• ACI 318-"BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
2. THE OWNER SHALL ENGAGE A TESTING AND INSPECTION AGENCY TO PERFORM
THE SPECIAL INSPECTIONS REQUIRED BY THE SCHEDULE OF SPECIAL
INSPECTIONS.
3. ALL CONNECTIONS SHALL BE DESIGNED BY THE FABRICATOR'S ENGINEER FOR THE
FORCES INDICATED. ALL FORCES NOTED ON THE DRAWINGS ARE ASD VALUES.
DESIGN CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES
AND SPECIFICATIONS.
4. STEEL MATERIALS SHALL BE PROVIDED IN ACCORDANCE WITH THE FOLLOWING
SPECIFICATIONS
• WIDE FLANGE STEEL SHAPES ASTM A-992
• OTHER ROLLED STEEL SHAPES ASTM A-36
• HSS (TUBULAR SHAPES ) ASTM A-500 GRADE B
• STEEL PIPE ASTM A-53, TYPE E OR S, GRADE B
• BOLTS ASTM F3125, GRADE F1852, TYPE 1
• ANCHOR RODS ASTM F1554 GR36
• SHEAR STUDS ASTM A29, TYPE A
5. SEAMS OF HSS SECTIONS SHALL BE MADE WITH CONTINUOUS FULL PENETRATION
BUTT WELDS.
6. MEMBERS INDICATED AS AESS STEEL ON THE PLANS SHALL CONFORM TO THE
SPECIFICATIONS FOR ARCHITECTURALLY EXPOSED STRUCTURAL STEEL.
CONTRACTOR SHALL VERIFY WITH ARCHITECT IF MOCK UPS ARE REQUIRED
BEFORE PROCEEDING WITH FABRICATION AND / OR ERECTION.
7. PROVIDE CONTINUOUS MINIMUM SIZED FILLET WELDS PER AISC. FILLER MATERIALS
SHALL HAVE A MINIMUM YIELD STRENGTH OF 58 KSI. EXPOSED WELDS SHALL BE
GROUND SMOOTH.
8. ALL EXTERIOR EXPOSED STRUCTURAL STEEL SHALL BE GALVANIZED UNLESS
NOTED OTHERWISE.
9. STRUCTURAL STEEL SURFACE PREPARATION SHALL CONFORM TO SSPC-SP3.
MEMBERS SHALL BE PAINTED WITH A SHOP PRIMER UNLESS NOTED OTHERWISE.
10. SHOP AND FIELD HOLES SHALL BE PUNCHED OR DRILLED.
11. GENERAL CONTRACTOR SHALL VERIFY ALL ROOFTOP EQUIPMENT SIZES, WEIGHTS
AND LOCATIONS AND COORDINATE FRAMING FOR EQUIPMENT AND ROOF
PENETRATION OPENINGS WITH THE STEEL FABRICATOR AND M.E.P. CONTRACTOR.
(+/-0'-0") W00X00S [00] c=0.00 in (+/-0'-0")
T.O.S.
ELEVATION
AT BEAM END
MEMBER TYPE
AND SIZE
NUMBER OF
LONG SHEAR
STUDS WELDED
TO TOP OF BEAM
CAMBER
EXAMPLE: SLOPING W33x118, 80 STUDS, CAMBER 0.75 IN (-0'-10") W33x118s [80] c=0.75 in (0'-4")
W00X00 [00] c=0.00 in
SLOPING
T.O.S.
ELEVATION
AT BEAM END
MEMBER TYPE
AND SIZE
NUMBER OF LONG SHEAR STUDS
WELDED TO TOP OF BEAM
CAMBER
(+/-0'-0")
T.O.S.
ELEVATION
EXAMPLE: W33x118, 80 STUDS, CAMBER 0.75 IN W33x118 [80] c=0.75 in
(-1'-4")
WOOD
1. DESIGN OF ALL WOOD FRAMING SHALL BE BASED UPON ALLOWABLE STRESS
DESIGN, IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATION FOR WOOD
CONSTRUCTION, LATEST EDITION
2. FABRICATION, ERECTION, AND BRACING SHALL BE IN ACCORDANCE WITH THE
NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, LATEST EDITION.
3. ALL LUMBER SHALL HAVE GRADE IDENTIFIED ON THE LABEL OF AN APPROVED
LUMBER GRADING AGENCY COMPLYING WITH DOC PS20 OR EQUIVALENT.
4. ALL STEEL TIMBER FASTENINGS AND JOIST HANGERS SHALL BE A MINIMUM OF 16
GA. GALVANIZED STEEL WITH A RATED LOAD CAPACITY EQUAL TO OR EXCEEDING
THE IMPOSED LOADING REQUIREMENTS.
5. ALL WOOD MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE TREATED LUMBER UNLESS NOTED OTHERWISE.
6. ANCHOR ALL SILL PLATES WITH 1/2" ANCHOR BOLTS WITH 3" HOOK AND MIN. 7"
EMBEDMENT SPACED AT 48" o.c. OR 1/2" SIMPSON TITEN HD WITH MIN. 5" EMBEDMENT SPACED AT 48" o.c. OR EQUAL
7. PROVIDE SOLID BRIDGING OR A CONTINUOUS HEADER AT THE BEARING OF ROOF
OR FLOOR JOISTS ON SILL PLATES.
8. PROVIDE DOUBLE JOISTS ON EACH SIDE OF ANY ROOF OR FLOOR JOIST WHICH IS
INTERRUPTED BY AND OPENING OR OTHER CONSIDERATIONS. UNLESS NOTED
OTHERWISE, NO MORE THAN ONE ROOF OR FLOOR JOIST SHALL BE INTERRUPTED
WITHOUT CONSULTING THE ENGINEER.
9. ALL DOUBLE JOISTS SHALL BE SPIKED TOGETHER WITH 2 ROWS OF 10d NAILS @ 16" o.c.
10. ALL WOOD BEAMS MADE UP OF 3 OR MORE MEMBERS SHALL BE BOLTED TOGETHER
WITH 1/2" BOLTS @ 16" o.c. STAGGERED TOP & BOTTOM.
11. PROVIDE A MINIMUM OF TWO POSTS TO SUPPORT ALL WOOD HEADERS, POST
DEPTH SHALL MATCH WALL CONSTRUCTION.
12. WOOD MEMBERS SHALL BE DESIGNED TO ACCOMMODATE AND SUPPORT
MECHANICAL UNITS AS SHOWN ON THE MECHANICAL DRAWINGS.
13. WOOD STRUCTURAL PANELS SHALL CONFORM TO THE REQUIREMENTS FOR ITS
TYPE IN DOC PS 1 OR PS 2.
14. WOOD SHEATHING SHALL MEET THE REQUIREMENTS OF THE PLYWOOD DESIGN
SPECIFICATION PUBLISHED BY THE APA, LATEST EDITION.
15. ALL WOOD SHEATHING SHALL BE APA RATED.
16. ALL FLOOR AND ROOF SHEATHING SHALL BE CONTINUOUS OVER A MINIMUM OF 3
SPANS.
17. WOOD TRUSS JOISTS AND GLULAM BEAMS ARE TO BE DESIGNED BY THE
MANUFACTURER TO THE LOADS AND DEFLECTIONS SPECIFIED. DESIGN
CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES AND
SPECIFICATIONS.
18. ALL HOLES IN WOOD JOISTS SHOULD BE COORDINATED WITH MECHANICAL AND
VERIFIED TO ME ACCEPTABLE BY MANUFACTURER DOCUMENTATION.
19. MINIMUM WOOD FASTENINGS SHALL CONFORM TO IBC TABLE 2304.10.1 UNLESS
NOTED OTHERWISE.
20. MINIMUM WOOD MEMBER DESIGN VALUES SHOWN IN TABLE BELOW:
MINIMUM WOOD DESIGN VALUES (PSI)
SAWN LUMBER (2"-4" THICK)
STRUCTURAL COMPOSITE
LUMBER (PSL)
Fb
1,000
2,600
FC
Parallel
1,450
2,510
FC
Perpendicular
FV
E
1,600,000
2,000,000
MOISTURE
CONTENT
19%
16%
WOOD TRUSSES
1. WOOD TRUSSES ARE TO BE MANUFACTURED IN ACCORDANCE WITH ANSI/TPI 1
"NATIONAL DESIGN STANDARD FOR METAL-PLATE-CONNECTED WOOD TRUSS
CONSTRUCTION", LATEST EDITION.
2. SIGNED AND SEALED SHOP DRAWINGS AND DESIGN CALCULATIONS SHALL BE
SUBMITTED AS PER THE SHOP DRAWING NOTES AND SPECIFICATIONS.
CALCULATIONS SHALL INCLUDE, BUT ARE NOT LIMITED TO:
a. DESCRIPTION OF THE DESIGN CRITERIA
b. ENGINEERING ANALYSIS DEPICTING STRESS AND DEFLECTION
REQUIREMENTS FOR EACH TRUSS APPLICATION
c. SELECTION OF TRUSS COMPONENTS AND ACCESSORIES
d. VERIFICATION OF ATTACHMENT TO STRUCTURE AND/OR ADJACENT
FRAMING COMPONENTS
e. NOTE: TRUSS CONFIGURATIONS SHOWN ON PLANS ARE APPROXIMATE
3. CUTTING, DRILLING, OR NOTCHING ANY OF THE TRUSS MEMBERS IS NOT
PERMITTED WITHOUT APPROVAL FROM THE TRUSS DESIGNER.
4. PERMANENT INDIVIDUAL TRUSS MEMBER RESTRAINT/BRACING AND THE METHOD
OF ANCHORING OR RESTRAINING TO PREVENT LATERAL MOVEMENT OF ALL TRUSS
MEMBERS SHALL BE ACCOMPLISHED AT MINIMUM BY DETAILS IN ACCORDANCE
WITH BCSI-B3 "PERMANENT RESTRAINT/BRACING OF CHORDS & WEB MEMBERS"
AND/OR BCSI-B7 "TEMPORARY & PERMANENT RESTRAINT/BRACING FOR PARALLEL
CHORD TRUSSES"
5. ANY BRACING REQUIRED IN EXCESS OF BCSI-B3 OR BCSI-B7 SHALL BE PROVIDED BY
THE TRUSS DESIGNER.
6. WOOD TRUSSES SHALL BE CONFIGURED TO ACCOMMODATE MECHANICAL UNIT
LOCATIONS, DUCTWORK RUNS, CATWALKS & STORAGE LOCATIONS. COORDINATE
WITH MECHANICAL & ARCHITECTURAL DRAWINGS.
7. WOOD TRUSSES TO BE DESIGNED FOR CRITERIA IN TABLE BELOW.
WOOD TRUSS DESIGN
CRITERIA
TCLL (PSF)
TCDL (PSF)
ATTIC
ROOF
BREAKDOWN
BCLL (PSF) 40 --
BCDL (PSF) 10 10
TOTAL (PSF) 108 68
LL DEFLECTION (TYP.) L/480 L/480
LL DEFLECTION (@ TILE) L/720 --
TL DEFLECTION (TYP.) L/240 L/240
L00-0a
STUD SIZE
EXAMPLES:
SINGLE WALL, LOAD
BEARING, 2x6 STUD,
(2) STUDS, IDENTIFIER a
DOUBLE WALL, LOAD
BEARING, 2x4 STUD,
(3) STUDS, IDENTIFIER c
SINGLE WALL, SHEAR
WALL, 2x6 STUD, (2) STUDS, IDENTIFIER c
DOUBLE WALL, SHEAR
WALL, 2x4 STUD,
(1) STUDS, IDENTIFIER a
WOOD WALL IDENTIFICATION
WALL TYPE
2L00-0a
STUD SIZEWALL TYPE
NUMBER OF
WALLS
LOAD BEARING
S00-0a
STUD SIZEWALL TYPE
2S00-0a
STUD SIZEWALL TYPE
NUMBER
OF WALLS
SHEAR
L26-2a
2L24-3c
S26-2c
2S24-1a
NUMBER OF STUDS
WALL IDENTITY
(SEE SCHEDULE)
NUMBER OF STUDS
WALL IDENTITY
(SEE SCHEDULE)
NUMBER OF STUDS
WALL IDENTITY
(SEE SCHEDULE)
NUMBER OF STUDS
WALL IDENTITY
(SEE SCHEDULE)
CONCRETE MASONRY
1. ALL MATERIALS AND CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF
TMS 402/ACI 530/ASCE 5: BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES LATEST EDITION.
2. THE OWNER SHALL ENGAGE A TESTING AND INSPECTION AGENCY TO PERFORM
THE SPECIAL INSPECTIONS REQUIRED BY THE SCHEDULE OF SPECIAL
INSPECTIONS.
3. HOLLOW MASONRY UNITS SHALL BE GRADE N-1 CONFORMING TO ASTM C-90,
UNLESS NOTE OTHERWISE WITH A MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI
(MASONRY ASSEMBLY F'm = 2,000 PSI).
4. ALL FILL FOR MASONRY WALLS SHALL BE PEA GRAVEL CONCRETE OR GROUT
CONFORMING TO ASTM C476 WITH A MINIMUM GROUT STRENGTH OF 3,000 PSI AT 28
DAYS. FILL SHALL BE PLACED IN 5'-0" LIFTS IN ACCORDANCE TO INTERNATIONAL
MASONRY INSTITUTE GUIDELINES AND ACI 530.1 / ASCE 6 FOR LOW LIFT GROUTING.
5. ALL MORTAR SHALL BE TYPE "M" CONFORMING TO ASTM C270 WITH A MINIMUM
COMPRESSIVE STRENGTH OF 2,500 PSI AT 28 DAYS.
6. ALL MORTAR FOR MASONRY OTHER THAN VENEER SHALL BE PORTLAND CEMENT
LIME MORTAR, NOT MASONRY CEMENT.
7. VERTICAL WALL REINFORCING SHALL BE INTERMEDIATE GRADE DEFORMED BARS
OF NEW BILLET STEEL CONFORMING TO ASTM A-615, GRADE 60.
8. JOINT REINFORCING SHALL BE 0.148" RODS MIN. CONFORMING TO ASTM A-951.
9. ALL MORTAR JOINTS IN MASONRY WALLS (HORIZONTAL AND VERTICAL) SHALL BE
FULL MORTAR BEDDING.
10. ALL SECTIONS OF BEARING WALLS HAVING A HORIZONTAL PLAN DIMENSION OF 2'-0"
OR LESS SHALL BE OF SOLID (CONCRETE FILLED) MASONRY CONSTRUCTION FOR
THE FULL HEIGHT OF THE WALL SECTION.
11. PROVIDE A MINIMUM OF ONE COURSE OF SOLID BLOCK UNDER ALL JOIST AND SLAB
BEARING ENDS FOR THE FULL WIDTH OF THE WALL, UNLESS NOTED OTHERWISE.
12. BRACE AND SHORE ALL NEW MASONRY WALLS AS REQUIRED UNTIL ROOF AND
FLOOR DECKS HAVE BEEN COMPLETELY INSTALLED.
13. THE TOP OF ALL MASONRY WALLS SHALL BE BRACED TO THE STEEL FRAMING. SEE
TYPICAL DETAILS ON FRAMING SECTIONS AND DETAIL DRAWINGS.
14. BACKFILL AGAINST MASONRY WALLS SHALL BE PLACED AT EQUAL HEIGHTS ON
EACH SIDE OF WALL UP TO FINAL GRADE.
15. QUALITY ASSURANCE PROGRAM TO BE PROVIDED PER SECTION 3.1 OF TMS 402/ACI
16. FILL ALL BLOCK CORES SOLID FROM FOUNDATION TO SLAB ON GRADE.
17. BOND BEAMS WITH HORIZONTAL REINFORCEMENT NOT LESS THAN (2) #5 REBAR
SHALL BE PROVIDED CONTINUOUSLY AT STRUCTURALLY CONNECTED ROOF AND
FLOOR LEVELS, AT THE TOP OF WALLS, AT THE BOTTOM OF WALLS OR IN THE TOP
OF THE FOUNDATION WHEN DOWELING INTO THE WALL.
18. ALL MASONRY WORK TO BE EXECUTED IN HOT OR COLD WEATHER SHALL BE IN
CONFORMANCE WITH THE RECOMMENDATIONS FOR COLD WEATHER
CONSTRUCTION FOUND IN TMS 402/ACI 530 WITH THE FOLLOWING ADDITIONS: FOR
ALL CONDITIONS WHEN TEMPERATURES FALL BELOW 40 DEGREES F, THE
TEMPERATURE OF THE NEWLY LAID MASONRY OR NEWLY GROUTED MASONRY
SHALL BE MAINTAINED ABOVE 30 DEGREES F FOR A MINIMUM OF 24 HOURS USING
THE METHODS DESCRIBED IN TMS 402/ACI 530.
19. UNLESS NOTED OTHERWISE ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE
FOLLOWING MINIMUM REINFORCING SHALL BE USED. ALL CORES WITH
REINFORCING SHALL BE GROUTED SOLID.
MINIMUM WALL REINFORCING
BENEATH STEEL BEAMS
BENEATH STEEL OR CONCRETE LINTELS
REINFORCING
(2) #5 BARS - (1) PER CORE
(1) #5 BAR
LOCATION
INTERIOR NON-LOAD BEARING WALLS
VERTICAL
HORIZONTAL
CORNERS, EA. SIDE OF EA. OPENING, ENDS OF
WALLS, EA. SIDE OF EXPANSION/CRACK
CONTROL JOINTS
TOP OF WALL, BOTTOM AND TOP OF EA.
OPENING
#4 BARS @ 48" o.c.
JOINT REINFORCING @ 16" o.c.
(1) #5 BAR
(1) #5 BAR - EXTEND 24" OR 40
BAR DIAMETERS PAST OPENING
BAR SIZE
LAP SPLICE LENGTH *
#3 #4 #5
REBAR LAP SPLICE LENGTHS
22" 29" 36" 44" 51" 58"
#6 #7 #8
* UNLESS NOTED OTHERWISE
WALL
THICKNESS
STEEL LINTEL SCHEDULE FOR NON-LOADBEARING
AND LOADBEARING MASONRY WALLS
CLEAR SPAN
4'-0" or Less
L3 1/2x3 1/2x5/16"
(2) L3 1/2x2 1/2x3/8" -or- WT7x11
W8x10 w/ 1/4"x0'-9" PL.
(3) L4x3 1/2x3/8" (LLV) -or- W8x10 w/
1/4"x0'-9" PL.
4'-1" to 6'-0"
L4x3 1/2x5/16" (LLV)
(2) L3 1/2x2 1/2x3/8" -or- WT7x11
W8x10 w/ 1/4"x0'-9" PL.
(3) L4x3 1/2x3/8" (LLV) -or- W8x10 w/
1/4"x0'-9" PL.
6'-1" to 8'-0"
L5x3 1/2x5/16" (LLV)
(2) L3 1/2x2 1/2x3/8" -or- WT7x11
W8x10 w/ 1/4"x0'-9" PL.
(3) L5x3 1/2"x5/16" (LLV) -or- W8x10 w/
1/4"x0'-11" PL.
8'-1" to 10'-0"
L5x3 1/2x5/16" (LLV)
WT7x11
W8x10 w/ 1/4"x0'-7"
PL.
W8x10 w/ 1/4"x0'-9"…