BAS_System_Point_List.pdf

PDF 291 KB Posted

Attached to
EUR/Athens - Maintenance of Building Automation System
Solicitation number
19GR1026Q0036
Issued by

About this file

This is a System Point List that specifies building automation and HVAC monitoring requirements for a federal facility contract. The document establishes detailed points to be captured, monitored, and alarmed across multiple building systems including air handlers, chilled water (CHW) systems, hot water (HW) systems, variable air volume (VAV) terminal units, and miscellaneous systems.

For air handling systems, the specification requires analog monitoring of temperatures, humidity, pressure, and airflow, along with binary status signals for fan operation, valve positions, and filter differential pressures. Critical alarming is mandated for high static pressure fan cutouts, return air smoke detection, and space differential pressure conditions exceeding five-minute thresholds. CHW and HW system monitoring must include pump status, VFD performance, supply/return temperatures with high and low alarms, and differential pressure tracking, with hardwired connections required for chiller and boiler enable/disable functions and general alarm signals. VAV terminal unit specifications call for zone temperature monitoring with high and low alarms for critical spaces (telecom, electrical, computer rooms), valve control feedback, CFM tracking, and group temperature/flow analysis. Additional systems requiring monitoring include exhaust and pressurization fans, fan coil units, computer room air conditioning, generators with fuel level and runtime totalization, fuel systems with leak detection, water filtration and booster pumps with pH and chlorine level monitoring, power and water metering on compound and per-building bases, elevators, laboratory fume hoods, fire alarm integration, and sewage pump status. The specification emphasizes that certain critical functions must be hardwired rather than communicated and designates specific alarm reporting locations (Post 1 and Post 2) for system failures affecting building operations.

View the file

Other files

File Type Posted
19GR1026Q0036_QsandAs.pdf PDF
19GR1026Q0036.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYSTEM POINT LIST

SYSTEM POINT DESCRIPTION NOTES

AIR HANDLERS

VAV AIR HANDLERS X Diagramatic system graphic (each)

FAN START/STOP X

FAN STATUS X X X

FAN VFD SPEED X

FAN VFD SPEED FEEDBACK X

FAN VFD FAIL X X

HIGH STATIC PRESSURE FAN CUTOUT X Hard wired to fan starter

CHW VALVE X

OA / RETURN AIR DAMPER X

DISCHARGE TEMPERATURE X

DISCHARGE HUMIDITY X

DUCT STATIC PRESSURE X

OUTSIDE AIR FLOW MONITOR X

MIXED AIR HUMIDITY X X

RETURN AIR TEMPERATURE X

RETURN AIR HUMIDITY X

RETURN AIR CO2 X X

RETURN AIR SMOKE DETECTOR X X

PRE-FILTER DIFFERENTIAL PRESSURE X X

HEPA FILTER DIFFERENTIAL PRESSURE X X

HEGA FILTER DIFFERENTIAL PRESSURE X X

SPACE CO2 (EACH) X X

SPACE DIFFERENTIAL PRESSURE (EACH) X X X NOTE 1

SPACE RELIEF AIR DAMPER X

SPACE SMOKE EXHAUST DAMPER X

AIRFLOW (OA AND DISCHARGE AIR) X X Discharge airflow monitor from AHU manufacturer

SA/RA SMOKE DETECTOR X X X

FIRE ALARM SYSTEM X X

OUTSIDE AIR HANDLER X DIAGRAMMATIC SYSTEM GRAPHIC

OUTSIDE TEMPERATURE X

OUTSIDE HUMIDITY X

OUTSIDE AIR DAMPER W/ ENDSWITCH X X

PRE FILTER DIFFERENTIAL PRESSURE X X

CARBON FILTER DIFFERENTIAL PRESSURE X X

HEATING COIL VALVE X

COOLING COIL VALVE X

LOW TEMPERATURE LIMIT X X

FAN START/STOP X

FAN STATUS X X X

FAN VFD SPEED X

FAN VFD SPEED FEEDBACK X

FAN VFD FAIL X X

HIGH STATIC PRESSURE FAN CUTOUT X Hard wire to fan starter

DUCT STATIC PRESSURE X

DISCHARGE TEMPERATURE X X

DISCHARGE HUMIDITY X X

GENERAL NOTES:

NOTE 1: ALARM AT POST 1, POST 2 IF IN ALARM FOR MORE THAN 5 MINUTES

ALARMSBINARYANALOG

SYSTEM POINT DESCRIPTION ANALOG NOTES

CHW System

Diagramatic system graphic

CHW PUMPS X USE FOR ALL VARIABLE SPEED PUMPS

CHW PUMP START/STOP X

CHW PUMP STATUS X X X ALARM AT POST 1, POST 2 IF ALL PUMPS FAIL

CHW PUMP SPEED X

CHW PUMP SPEED FEEDBACK X

CHW PUMP VFD FAIL X X X ALARM AT POST 1, POST 2 IF ALL PUMPS FAIL

CHW SUPPLY TEMPERATURE X X NOTES 1,(HIGH AND LOW TEMP ALARM)

CHW RETURN TEMPERATURE X X NOTES 1,(HIGH AND LOW TEMP ALARM)

CHW BYPASS VALVE X

CHW DIFFERENTIAL PRESSURE X X

CH FLOW X X

CHILLER (EACH) x Diagramitic system graphic

CHILLER ENABLE/DISABLE X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER STATUS X X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER GENERAL ALARM X X X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER KW/TON X MAY BE COMMUNICATED

COMPRESSOR FAILURE (EACH) X X MAY BE COMMUNICATED

CHILLER POWER USAGE X KWH MAY BE COMMUNICATED

CHILLER RLA X AMPS MAY BE COMMUNICATED

CHILLER RUNTIME X MAY BE COMMUNICATED

HEAT EXCHANGER x

HX SUPPLY TEMPERATURE (BUILDING SIDE) X X

HX RETURN TEMPERATURE (BUILDING SIDE) X

HX ISOLATION VALVES (ALL) X

CHEMICAL TREATMENT GEN ALARM X X X

BOILERS X DIAGRAMMATIC SYSTEM GRAPHIC

BOILER ENABLE DISABLE X MUST BE HARDWIRED, NOT COMMUNICATED

BOILER STATUS X X MUST BE HARDWIRED, NOT COMMUNICATED

BOILER PUMP START/STOP X

BOILER PUMP STATUS X

HWS SUPPLY AND RTETURN TEMPERATURE X X HIGH AND LOW TEMP ALARM

HWS FLOW X X

GENERAL NOTES:

1. SETPOINT CONTROL FROM CHILLER PANEL

BINARY ALARMS

HW System

Diagramatic system graphic

HW PUMPS X USE FOR ALL CONSTANT VOLUME PUMPS

HW PUMP START/STOP X

HW PUMP STATUS X X X ALARM AT POST 1, POST 2 IF ALL PUMPS FAIL

HW PUMPS W/ VFD x USE FOR ALL VARIABLE SPEED PUMPS

HW PUMP START/STOP X

HW PUMP STATUS X X X ALARM AT POST 1, POST 2 IF ALL PUMPS FAIL

HW PUMP SPEED X

HW PUMP SPEED FEEDBACK X

HW PUMP VFD FAIL X X X ALARM AT POST 1, POST 2 IF ALL PUMPS FAIL

HW SUPPLY TEMPERATURE X X HIGH AND LOW TEMP ALARM

HW RETURN TEMPERATURE X X HIGH AND LOW TEMP ALARM

HW DIFFERENTIAL PRESSURE X X

HW FLOW X X

BOILER (EACH) x

BOILER ENABLE/DISABLE X MUST BE HARDWIRED, NOT COMMUNICATED

BOILER STATUS X X MUST BE HARDWIRED, NOT COMMUNICATED

BOILER GENERAL ALARM X X X MUST BE HARDWIRED, NOT COMMUNICATED

BOILER FUEL USAGE X

BOILER TYPE OF FUEL X NATURAL GAS OR FUEL OIL

BOILER EFFICIENCY X BTUH MAY BE COMMUNICATED

OUTSIDE AIR TEMPERATURE X

CHEMICAL TREATMENT GEN ALARM X X X

DEDICATED HEAT RECOVERY CHILLER X IF INSTALLTED ON PROJECT

CIRCULATING PUMPS (EACH) X

PUMP START/STOP X

PUMP STATUS X X

CHW SUPPLY TEMPERATURE X

CHW RETURN TEMPERATURE X

HW SUPPLY TEMPERATURE X

HW RETURN TEMPERATURE X

ISOLATION VALVES (EACH) X

CHILLER ENABLE/DISABLE X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER STATUS X X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER GENERAL ALARM X X MUST BE HARDWIRED, NOT COMMUNICATED

CHILLER KW/TON X MAY BE COMMUNICATED

COMPRESSOR FAILURE (EACH) X X MAY BE COMMUNICATED

CHILLER POWER USAGE X KWH MAY BE COMMUNICATED

CHILLER RLA X AMPS MAY BE COMMUNICATED

CHILLER RUNTIME X MAY BE COMMUNICATED

GENERAL NOTES:

VARIABLE AIR VOLUME TERMINAL UNITS

VAV SYSTEMS X Diagramatic system graphic (floor by floor)

VAV TERMINAL UNITS (EACH) X Diagrammatic graphic for each unit

ZONE TEMPERATURE X X X HIGH AND LOW ALARMS (NOTE 1)

COOLING SETPOINT X

HEATING SETPOINT X

AIR VALVE X

HW VALVE X X BO IF TRI-STATE VALVE

ELECTRIC HEAT X X BO IF STEP HEATERS

CFM X X

MIN CFM X

MAX CFM X

HEATING MIN CFM X

HEAT STATUS X

AUX DISCHARGE TEMPERATURE X

UNOCCUPIED COOLING SETPOINT X

UNOCCUPIED HEATING SETPOINT X

VALVE OVERRIDE X

HEAT OVERRIDE X

MAX ZONE TEMP GROUP X X

MIN ZONE TEMP GROUP X X

AVERAGE ZONE TEMP GROUP X

TOTAL GROUP FLOW X

GENERAL NOTES:

Note 1: Alarm High and Low Temp alarms at Post 1 and Post 2 for all critical spaces (telecom, electrical, computer room)

MISCELLANEOUS SYSTEMS

EXHAUST FANS/PRESSURIZATION FANS (EACH) X Diagramatic system graphic

FAN START/STOP X

FAN STATUS X X X NOTE 1

FAN SPEED X

FAN SPEED FEEDBACK X

VFD FAIL X X X NOTE 1

DUCT STATIC PRESSURE X

DAMPER (2-POS) X

DAMPER (MODULATING) X

CHW PUMP VFD FAIL X

FAN COIL UNITS X Diagramatic system graphic

FAN START/STOP X

FAN STATUS X X

CHILLED WATER VALVE X

SPACE TEMPERUATURE X X

COMPUTER ROOM A/C X Diagramatic system graphic

SPACE TEMPERUATURE X X X

GENERAL ALARM X X X

SPLIT SYSTEM A/C X Diagramatic system graphic

SPACE TEMPERUATURE X X

GENERAL ALARM X

LOBBY/PAA SPECIAL SYSTEMS X

SYSTEM STATUS X X X

DAMPER POSISTION (EACH) X

GENERAL NOTES:

Note 1: Alarm Pressurization fans failures at Post 1 and Post 2

MISCELLANEOUS SYSTEMS

GENERATORS X Diagramatic system graphic

GENERAL ALARM X X X

TANK FUEL LEVEL (EACH) X X X HIGH AND LOW LEVEL

FUEL PUMP STATUS (EACH) X X X

GENERATOR STATUS (ON/OFF) (EACH) X X X TOTALIZE RUN TIME

FUEL SYSTEM X

FUEL TANK LEVEL (EACH) X X X HIGH AND LOW LEVEL

LEAK DETECTION (EACH) X X X

ENABLE/DISABLE X

PUMP STATUS (EACH) X X

GENERAL ALARM X X X

WATER FILTRATION/BOOSTER PUMPS X Diagramatic system graphic

GENERAL ALARM X X X

PH LEVEL X X

CHLORINE LEVEL (EACH) X X

TANK LEVEL (EACH TANK, POTABLE, DAY, FIRE) X X X HIGH AND LOW LEVEL

PUMP STATUS (EACH) X X X

POWER METERING X Diagramatic system graphic

POWER CONSUMPTION X COMPOUND AND PER BUILDING

WATER METERING X Diagramatic system graphic

WATER CONSUMPTION X COMPOUND AND PER BUILDING

FUEL METERING X Diagramatic system graphic

FUEL CONSUMPTION (fuel oil and gas) X COMPOUND AND PER BUILDING

ELEVATORS X

GENERAL ALARM X X EACH BUILDING

LABORATORY FUME HOOD (EACH) X

ENABLE/DISABLE X

STATUS X X

FIRE ALARM X

POINTS AS NEEDED X X POINTS AS NEEDED FOR SMOKE SEQUENCES

SEWAGE PUMPS X

STATUS (EACH) X X

ALARM X X X

POWER MONITORING SYSTEM X

POINTS AS NEEDED COMMUNICATED POINTS PER SPECS

GENERAL NOTES: