18230 ADD 4 Attachment #3 -REVISED Civil Specification Page 61.pdf
PDF 119 KB Posted
- Attached to
- Paulette Burdick Park
- Solicitation number
- IFB 410 18230 6
- Issued by
- Palm Beach County, Florida
About this file
This is a Civil Specification document for Palm Beach County's Paulette Burdick Park project, dated June 21, 2024, establishing concrete proportioning and testing requirements for the 100% Bid Set. The specification requires contractors to proportion concrete mixes using either laboratory trial batch or field experience methods in compliance with ACI 211.1 standards. All testing services must be provided by the contractor and submitted to the Architect/Engineer for approval at least 15 days prior to work commencement. Contractors are prohibited from beginning production until concrete mixes receive written approval from the Architect/Engineer.
The concrete mix design report must include total weights of water, cement, coarse and fine aggregates, admixtures, slump measurements, air content percentages, and compression test results from six cylinders tested at 7, 14, and 28 days, along with grain size curves for both aggregates. When using field experience methods, proportions shall comply with ACI 301-72, requiring certified production facility records of at least 30 consecutive tests or statistical averages from two groups totaling 30 or more tests with similar materials and project conditions. The required concrete strength is specified at 3,250 pounds per square inch, with proportions determined according to ACI 211.1 "Recommended Practice for Selection Proportions for Normal and Heavy Weight Concrete."
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Palm Beach County 100% Bid Set Paulette Burdick Park June 21, 2024
PART 4 - EXECUTION
4.1. GENERAL
A. Proportioning
1. Proportion mixes by either laboratory trial batch or field experience methods, using materials to be employed on the project for each class of concrete required, complying with the latest edition of ACI 211.1.
2. Contractor shall provide all testing services for approval of mixes.
3. The Contractor shall furnish the Architect/Engineer for approval a mix design for each class of concrete at least 15 days prior to start of work.
B. Report to Include
1. Total weight of water, cement, coarse aggregate fine aggregate and admixtures to be used.
2. Slump.
3. Percent of Air.
4. Results of Compression Test for 6 cylinders cast and broken 7, 14 and 28 days.
5. Grain size curves for both aggregates.
C. Do not begin production until mixes have been approved by Architect/Engineer.
D. When field experience methods are used to select concrete proportions, establish proportions as specified in ACI 301-72. Strength data for establishing standard deviation will be considered suitable if the concrete production facility has certified records consisting of at least 30 consecutive tests in one group or the statistical average for 2 groups totaling 30 or more tests, representing similar materials and project conditions.
E. The proper proportions of cement, aggregate and water to obtain the required strength shall be determined from ACI 211.1 "Recommended Practice for Selection Proportions for Normal and Heavy Weight Concrete".
1. Strength requirements shall be 3250 pounds per square inch.