18230 ADD 4 Attachment #2 -REVISED Civil Specification Page 34.pdf
PDF 121 KB Posted
- Attached to
- Paulette Burdick Park
- Solicitation number
- IFB 410 18230 6
- Issued by
- Palm Beach County, Florida
About this file
This document is a Civil Specification page from Palm Beach County's 100% Bid Set for Paulette Burdick Park, dated June 21, 2024. The specification outlines concrete mix design and execution requirements for the project. The testing laboratory is required to design concrete mixes for each strength and type in accordance with ACI 301-Chapter 3, Method 2, establishing water-cement ratios based on strength test records of 30 or more tests from the past year. Mix designs must account for placement methods, including gravity and pumping (when approved by the Architect/Engineer), and four copies of proposed designs must be submitted to the Architect/Engineer for approval no later than five working days prior to concrete placement. All concrete shall achieve minimum compressive strength as indicated on project drawings, with a default minimum of 3,250 psi at 28 days unless otherwise designated. Once a source, type, kind, or brand of each constituent is established and accepted, it cannot be changed throughout the concreting duration, and all constituents including admixtures must be batched at a central batch plant.
The specification does not contain pricing information, set-asides, incumbent contractor details, or funding source information within this excerpt. The document serves as a technical requirement section governing concrete material specifications and testing protocols for the Paulette Burdick Park project. The testing laboratory and Architect/Engineer maintain supervisory authority over mix design approval and quality control throughout construction execution.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Palm Beach County 100% Bid Set Paulette Burdick Park June 21, 2024 testing laboratory or engineer to continue with the design, control or supervision work herein specified, if he believes it is in the interest of the Owner.
PART 3 - EXECUTION
3.1 CONCRETE MIX DESIGN:
A. The laboratory shall design mixes for each strength and type of concrete, in accordance with ACI 301 - Chapter 3, Method 2.
1. Ability to produce the required average strength calculated in accordance with Section 3.8.2.3 of ACI 01 shall be determine on the basis of the strength test record of 30 or more tests made during the past year which will permit establishing directly or by interpolation, the water-cement ratio corresponding to the required average strength.
2. Mixes shall be designed according to placement methods in addition to the criteria specified above.
a. Placement by gravity.
b. Placement by pumping (if method is approved by the Architect/
Engineer for use).
3. The testing laboratory shall submit in writing to the Architect/Engineer four (4) copies of proposed mix designs. Final recommended job mixtures shall be presented to the Architect/Engineer for approval as soon as possible and no later than five (5) working days prior to commencing concrete placement.
B. All concrete shall have a minimum compressive strength as indicated on the drawings. Concrete not so designated shall have a minimum compressive strength of 3250 psi at 28 days.
C. When a source, type, kind or brand of each constituent has been established and accepted for job mixtures, this source, type, kind or brand shall not be changed throughout the duration of the concreting.
D. Batch all constituents, including admixtures, at the central batch plant.