17- Location 17 Reference Only.xlsx

XLSX spreadsheet 180 KB Posted

Attached to
Fire Protection Assessment Report & Risk Management Surveys at Multiple Region 5 Locations (Amended 2)
Solicitation number
47PF0021Q0102
Issued by

View the file

Other files

File Type Posted
Amendment 0002.pdf PDF
RFQ_Fire Protection Facility Assessment Reports and Surveys-Revised.pdf PDF
Amendment 0001.pdf PDF
12- Location 12 Reference Only.xlsx XLSX spreadsheet
14- Location 14 Reference Only.xlsx XLSX spreadsheet
3- Location 3 Reference Only.xlsx XLSX spreadsheet
5- Location 5 Reference Only.xlsx XLSX spreadsheet
9- Location 9 Reference Only.xlsx XLSX spreadsheet
2- Location 2 Reference Only.xlsx XLSX spreadsheet
SF18.pdf PDF
20- Fire Protection Program Policy Document.pdf PDF
10- Location 10 Reference Only.xlsx XLSX spreadsheet
6- Location 6 Reference Only.xlsx XLSX spreadsheet
13- Location 13 Reference Only.xlsx XLSX spreadsheet
19- FLS Contractor Quote Sheet.xlsx XLSX spreadsheet
1- Location 1 Reference Only.xlsx XLSX spreadsheet
15- Location 15 Reference Only.xlsx XLSX spreadsheet
8- Location 8 Reference Only.xlsx XLSX spreadsheet
FAR52204 Representations.pdf PDF
RFQ_Fire Protection Facility Assessment Reports and Surveys.pdf PDF
16- Location 16 Reference Only.xlsx XLSX spreadsheet
4- Location 4 Reference Only.xlsx XLSX spreadsheet
18- Location 18 Reference Only.xlsx XLSX spreadsheet
7- Location 7 Reference Only.xlsx XLSX spreadsheet
11- Location 11 Reference Only.xlsx XLSX spreadsheet
Combined Synopsis-Solicitation.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RAC Summary GSA Risk Management Survey Fire Protection Survey

RAC Summary
5459EDITABLEN
Means of Egress6
Fire Detection and Alarm6
Fire Suppression6
Smoke Control6
Other6
6
Overall RAC6

IRIS Building Profile GSA Risk Management Survey

Questions Response Findings/Observations

IRIS Building Profile
Region5864441516926001
GSA Building NumberIN0300ZZ864441616926011
GSA Building NameU.S. COURTHOUSE864441716926021
Building Street Address5400 Federal Plz864441816926031
Date of Building Construction2002864440916925941
Building CityHAMMOND864441316925981
Building StateIN864441416925991
Building Size (RSF)86444081
Building Size (GSF)280802864441016925951
Total Number of Floors Above Grade0864441116925961
Total Number of Floors Below Grade5864441216925971
5459N864

Building Information GSA Risk Management Survey

Questions Response Findings/Observations

Building Profile
Date(s) of Onsite Survey86644191
Name of Surveyor86649571
Surveyor Company Name and Contact Information86649581
Date(s) of Assessment86649591
Building occupancy classification per latest edition of IBC86649601
Building construction type per latest edition of IBC86649611
Approximate gross square footage per floor86649621
Specific floors the Government occupies - include the specific Government agency names86649631
Identify the different type of occupancies on each floor the Federal government occupies86649641
Height from lowest level of fire department vehicle access to the highest Government occupied floor of the building (in feet).86649651
Height from the lowest level of fire department vehicle access to the roof of the building (in feet)86649661
High-rise Building (Yes/No)86649674
Estimated total number of Federal occupants in the building86649681
Estimated total number of Federal occupants in the building by floor86649691
Identify and describe the location of the nearest fire department and the approximate distance from the building86649701
Identify by location and describe hazardous/significant fuel load areas that when ignited would produce significant adverse effects to the building and its occupants86649711
Identify by location and describe potential fire ignition sources. The proximity of the fuel source and the ignition source shall be described86649721
Describe the fire exposures on the north, south, east and west sides of the building, including the distance from the building86649731
Means of Egress System Information
Identify and describe the number of means of egress from each floor. Include for each stair the width, tread length, riser height, and handrail specifics.98249741
Identify and describe the arrangement of means of egress from each floor (e.g., exit remoteness)98249751
Identify and describe the location of where each exit discharges and terminates.98249761
Describe the calculated occupant load and exit capacity by floor98249771
Sprinkler System Information
Identify the automatic sprinkler coverage: Full/Total, Partial, None98349783
Identify the area of automatic sprinkler coverage (Percentage)98349793
Identify the type(s) and describe the location of automatic sprinkler system(s) (e.g., wet, dry, etc.)98349801
Identify the type(s) of sprinklers (e.g., manufacturer, model, date of manufacturer for each type of sprinkler)98349811
Identify the type(s) of sprinkler piping98349821
Standpipe System Information
Identify by location and describe the type(s) of standpipe systems and fire department connections98449831
Fire Pump Information
Identify the location of fire pump98549841
Identify the size of fire pump (__ gpm at __ psi)98549851
Identify the type of power for the fire pump98549861
Identify the fire pump rating98549871
Portable Fire Extinguisher Information
Identify by location and describe the type of fire extinguishers98649881
Fire Alarm System Information
Identify the location of main fire alarm control unit98749891
Identify the date the fire alarm system was installed98749901
Identify the age of fire alarm system98749911
Identify the control unit manufacturer98749921
Identify the control unit model number98749931
Identify the control unit date manufactured98749941
Identify the software/firmware and revision number (if applicable)98749951
Smoke Control System Information
Identify and describe the number of pressurized exit stairs98849961
Identify and describe the number of pressurized elevator hoistways98849971
Identify and describe the location of the fire fighter's smoke control panel98849981
Elevator System Information
Identify the number of passenger elevators98949991
Identify the number of freight elevators98950001
Identify the number of fire service access elevators98950011
Identify the number of occupant evacuation elevators98950021
Identify the firefighter's emergency operation provided (Phase I emergency recall operation and/or Phase II emergency in-car operation)98950031
Emergency Power System Information
Identify and describe the source(s) of emergency power for the building99050041
Identify all systems connected to the emergency power system99050051
Preventative Records of the Fire Protection and Life Safety Equipment and Systems
Describe the general conditions of the fire protection and life safety equipment and systems in the building99150061
Describe the preventative records of the fire protection and life safety equipment and systems reviewed99150071
Fire Safety Evaluation System (FSES) Scoring
FSES Completion Date:99250081
Fire Control:99250091
Egress Provided:99250101
General Fire Safety:99250111
Building Fire Risk Index (BFRI)99250121
Occupant Emergency Plan
Date of most current OEP99350131
Date of last fire drill or training drill99350141
Describe the procedures to evacuate persons with mobility disabilities99350151
Describe the procedures to evacuate occupants after hours99350161
5459EDITABLEN993

Means of Egress GSA Risk Management Survey

Means of Egress

Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/ObservationsRegulatory CitationProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Means of Egress Components
Are doors in compliance? If no, identify and describe the circumstances in the findings section.
: Consider all doors associated with the means of egress. Keep in mind door hardware, fire ratings, and operation.Not PossibleNo Impact688345134
Are stairs in compliance? If no, identify and describe the circumstances in the findings section.
: Consider all stairs involved in an elevation change. Keep in mind tread and risers, and width.Not PossibleNo Impact688345144
Are handrail/guards in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688345154
Are ramps in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688345164
Are horizontal exits in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688345174
Are exit passageways in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688345184
Capacity of Means of Egress
Is the means of egress capacity based on occupant load for floor and area adequate?Not PossibleNo Impact688545224
Means of Egress Minimum Width
Is the means of egress minimum width maintained (i.e. 44" or 36" where permitted)?Not PossibleNo Impact687945054
Number of Exits
Are the required number of exits provided for floor or area?Not PossibleNo Impact688145074
Are there interlocking or scissor stairs present (if yes, counts as 1 exit)?Not PossibleNo Impact688145084
Arrangement of Means of Egress
Are exits readily accessible? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688245094
Are common path of travel and dead end arrangements in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688245104
Are exits arranged to be remote per code? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688245114
Are travel distances in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688245124
Discharge of Means of Egress
Is the exit discharge in compliance? If no, identify and describe the circumstances in the findings section.
: Consider arrangement, lighting, and marking of exit discharge.Not PossibleNo Impact688045064
Illumination of Means of Egress
If emergency lighting is provided, is there adequate coverage? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688445204
Marking Means of Egress
Are adequate markings of means of egress provided? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688745284
Is the illumination of the markings of means of egress in compliance? If no, identify and describe the circumstances in the findings section.Not PossibleNo Impact688745294
Other Findings
Other Findings 1Not PossibleNo Impact687844951
Other Findings 2Not PossibleNo Impact687844961
Other Findings 3Not PossibleNo Impact687844971
Other Findings 4Not PossibleNo Impact687844981
Other Findings 5Not PossibleNo Impact687844991
Other Findings 6Not PossibleNo Impact687845001
Other Findings 7Not PossibleNo Impact687845011
Other Findings 8Not PossibleNo Impact687845021
Other Findings 9Not PossibleNo Impact687845031
Other Findings 10Not PossibleNo Impact687845041
Overall RAC
Overall RAC687744925
User Adjusted RAC

: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.

: Consider all doors associated with the means of egress. Keep in mind door hardware, fire ratings, and operation.

: Consider all stairs involved in an elevation change. Keep in mind tread and risers, and width.

: Consider arrangement, lighting, and marking of exit discharge.87744936
Explanation of User Adjusted RAC87744941
5459EDITABLEN877
66N

Fire Detection and Alarm GSA Risk Management Survey

Fire Detection and Alarm

Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/ObservationsRegulatory CitationProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Fire Detection and Alarm
If there is a fire alarm system installed, is the system operational and functioning correctly?Not PossibleNo Impact690445944
Initiating Devices
Are there manual pull station issues? If yes, please describe in the findings section.Not PossibleNo Impact690245824
Are there smoke detectors issues? If yes, please describe in the findings section.Not PossibleNo Impact690245834
Are there duct detectors issues? If yes, please describe in the findings section.Not PossibleNo Impact690245844
Are there heat detectors issues? If yes, please describe in the findings section.Not PossibleNo Impact690245854
Are there water flow switches issues? If yes, please describe in the findings section.Not PossibleNo Impact690245864
Are there valve supervision issues? If yes, please describe in the findings section.Not PossibleNo Impact690245874
Are there any other initiating devices with issues? If yes, please describe in the findings section.
: Consider elevator recall, smoke removal, etc.Not PossibleNo Impact690245884
Notification Devices
Are there any visual device problems? If yes, please describe problems and date of test and maintenance report in the findings section.
: Consider strobes and any other forms of visual communication for mass notification.Not PossibleNo Impact690145804
Are there any audibility problems? If yes, please describe in the findings section.Not PossibleNo Impact690145814
Other Findings
Other Findings 1Not PossibleNo Impact690045701
Other Findings 2Not PossibleNo Impact690045711
Other Findings 3Not PossibleNo Impact690045721
Other Findings 4Not PossibleNo Impact690045731
Other Findings 5Not PossibleNo Impact690045741
Other Findings 6Not PossibleNo Impact690045751
Other Findings 7Not PossibleNo Impact690045761
Other Findings 8Not PossibleNo Impact690045771
Other Findings 9Not PossibleNo Impact690045781
Other Findings 10Not PossibleNo Impact690045791
Overall RAC
Overall RAC689945675
User Adjusted RAC

: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.

: Consider strobes and any other forms of visual communication for mass notification.89945686
Explanation of User Adjusted RAC89945691
5459EDITABLEN899
66N

Fire Suppression GSA Risk Management Survey

Fire Suppression

Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/ObservationsRegulatory CitationProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Automatic Sprinklers
Are there any identified fire sprinkler issues? If yes, please explain in the findings section.
: Verify that the sprinkler design is adequate for the level of protection required for that area.Not PossibleNo Impact690846164
Standpipes
Are there any standpipe issues? If yes, please explain in the findings section.Not PossibleNo Impact690946194
Fire Pumps
Are there any fire pump issues? If yes, please explain in the findings section.Not PossibleNo Impact691046244
Other Suppression Systems
Are there identified issues? If yes, please explain in the findings section.Not PossibleNo Impact691246314
Other Findings
Other Findings 1Not PossibleNo Impact690746011
Other Findings 2Not PossibleNo Impact690746021
Other Findings 3Not PossibleNo Impact690746031
Other Findings 4Not PossibleNo Impact690746041
Other Findings 5Not PossibleNo Impact690746051
Other Findings 6Not PossibleNo Impact690746061
Other Findings 7Not PossibleNo Impact690746071
Other Findings 8Not PossibleNo Impact690746081
Other Findings 9Not PossibleNo Impact690746091
Other Findings 10Not PossibleNo Impact690746101
Overall RAC
Overall RAC690645985
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.90645996
Explanation of User Adjusted RAC90646001
5459EDITABLEN906
66N

Smoke Control GSA Risk Management Survey

Smoke Control

Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/ObservationsRegulatory CitationProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Smoke Control
Are there any smoke control issues? If yes, please explain in the findings section.Not PossibleNo Impact687544914
Other Findings
Other Findings 1Not PossibleNo Impact687444781
Other Findings 2Not PossibleNo Impact687444791
Other Findings 3Not PossibleNo Impact687444801
Other Findings 4Not PossibleNo Impact687444811
Other Findings 5Not PossibleNo Impact687444821
Other Findings 6Not PossibleNo Impact687444831
Other Findings 7Not PossibleNo Impact687444841
Other Findings 8Not PossibleNo Impact687444851
Other Findings 9Not PossibleNo Impact687444861
Other Findings 10Not PossibleNo Impact687444871
Overall RAC
Overall RAC687344755
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.87344766
Explanation of User Adjusted RAC87344771
5459EDITABLEN873
66N

Other GSA Risk Management Survey

Other

Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/ObservationsRegulatory CitationProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Fire and Smoke Barriers
Are penetrations properly maintained? If no, please describe in the comments section.Not PossibleNo Impact689545584
Are opening protective's properly maintained? If no, please describe in the comments section.Not PossibleNo Impact689545594
Are all other fire barriers properly maintained? If no, please describe in the comments section.Not PossibleNo Impact689545604
Emergency Power
Are there any identified issues? If yes, please explain in the findings section.Not PossibleNo Impact689645654
Interior Finishes
Are interior finishes compliant with the occupancy use? If no, please describe in the findings section.Not PossibleNo Impact689745664
Fire Planning and Prevention
Are there any other overall fire prevention issues? If yes, please describe in the findings section.Not PossibleNo Impact689445544
Other Findings
Other Findings 1Not PossibleNo Impact689045331
Other Findings 2Not PossibleNo Impact689045341
Other Findings 3Not PossibleNo Impact689045351
Other Findings 4Not PossibleNo Impact689045361
Other Findings 5Not PossibleNo Impact689045371
Other Findings 6Not PossibleNo Impact689045381
Other Findings 7Not PossibleNo Impact689045391
Other Findings 8Not PossibleNo Impact689045401
Other Findings 9Not PossibleNo Impact689045411
Other Findings 10Not PossibleNo Impact689045421
Overall RAC
Overall RAC688945305
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.88945316
Explanation of User Adjusted RAC88945321
5459EDITABLEN889
66N

RAC Guidance Risk Management Survey Severity and Probability Assessment Guidance

SEVERITY ASSESSMENT GUIDANCE
SCOPE and APPLICABILITY
Environmental RiskFire Protection RiskSafety & Health Risk
Contamination of air, water soil, and biota or non-compliance with environmental regulationsEffects to occupants or facility as a result of a condition or potential event.Adverse health effects or injury to facility occupants, contractors or visitors in response to a condition or event
SEVERITY LEVEL DEFINITIONS
CATASTROPHICIrreversible long-term impacts.(1) Death, permanent disability or irreversible health effect to occupants or (2) a loss of an entire facility.Permanent disability, irreversible health effect or death.

SEVERE Reversible long-term damage (5+ years to remediate). (1) Severe injury, potential long-term health effect or (2) major loss or impact to a facility. Potential long-term health effect or severe injury.

SIGNIFICANT Reversible medium-term damage (1-5 years to remediate). (1) Minor injury or reversible health effect or (2) damage to a portion of a facility requiring an extended period of time to repair. Reversible health effect or minor injury.

MODERATE Reversible short-term impact (<1 year to remediate). (1) First aid, no lost time or (2) damage to a facility requiring a minimal amount of time to repair. First aid or no lost time.

MINOR De minimis regulatory violation. De minimis code violation. De minimis code violation.

NO IMPACTNo risk of impact.No risk of impact to the occupants or facility.No risk of impact.
PROBABILITY ASSESSMENT GUIDANCE
PROBABILITY LEVEL DEFINITIONS
LikelyImminent

or

1 in 10
ProbableProbable

or

1 in 100
PossiblePossible

or

1 in 1000
RemoteRemote

or

1 in 10,000
UnlikelyUnlikely

or

1 in 100,000
Not PossibleNon-existent

Help Text

RAC Summary
RAC Summary
IRIS Building Profile
IRIS Building Profile
Region
GSA Building Number
GSA Building Name
Building Street Address
Date of Building Construction
Building City
Building State
Building Size (RSF)
Building Size (GSF)
Total Number of Floors Above Grade
Total Number of Floors Below Grade
Building Information
Building Profile
Date(s) of Onsite Survey
Name of Surveyor
Surveyor Company Name and Contact Information
Date(s) of Assessment
Building occupancy classification per latest edition of IBC
Building construction type per latest edition of IBC
Approximate gross square footage per floor
Specific floors the Government occupies - include the specific Government agency names
Identify the different type of occupancies on each floor the Federal government occupies
Height from lowest level of fire department vehicle access to the highest Government occupied floor of the building (in feet).
Height from the lowest level of fire department vehicle access to the roof of the building (in feet)
High-rise Building (Yes/No)
Estimated total number of Federal occupants in the building
Estimated total number of Federal occupants in the building by floor
Identify and describe the location of the nearest fire department and the approximate distance from the building
Identify by location and describe hazardous/significant fuel load areas that when ignited would produce significant adverse effects to the building and its occupants
Identify by location and describe potential fire ignition sources. The proximity of the fuel source and the ignition source shall be described
Describe the fire exposures on the north, south, east and west sides of the building, including the distance from the building
Means of Egress System Information
Identify and describe the number of means of egress from each floor. Include for each stair the width, tread length, riser height, and handrail specifics.
Identify and describe the arrangement of means of egress from each floor (e.g., exit remoteness)
Identify and describe the location of where each exit discharges and terminates.
Describe the calculated occupant load and exit capacity by floor
Sprinkler System Information
Identify the automatic sprinkler coverage: Full/Total, Partial, None
Identify the area of automatic sprinkler coverage (Percentage)
Identify the type(s) and describe the location of automatic sprinkler system(s) (e.g., wet, dry, etc.)
Identify the type(s) of sprinklers (e.g., manufacturer, model, date of manufacturer for each type of sprinkler)
Identify the type(s) of sprinkler piping
Standpipe System Information
Identify by location and describe the type(s) of standpipe systems and fire department connections
Fire Pump Information
Identify the location of fire pump
Identify the size of fire pump (__ gpm at __ psi)
Identify the type of power for the fire pump
Identify the fire pump rating
Portable Fire Extinguisher Information
Identify by location and describe the type of fire extinguishers
Fire Alarm System Information
Identify the location of main fire alarm control unit
Identify the date the fire alarm system was installed
Identify the age of fire alarm system
Identify the control unit manufacturer
Identify the control unit model number
Identify the control unit date manufactured
Identify the software/firmware and revision number (if applicable)
Smoke Control System Information
Identify and describe the number of pressurized exit stairs
Identify and describe the number of pressurized elevator hoistways
Identify and describe the location of the fire fighter's smoke control panel
Elevator System Information
Identify the number of passenger elevators
Identify the number of freight elevators
Identify the number of fire service access elevators
Identify the number of occupant evacuation elevators
Identify the firefighter's emergency operation provided (Phase I emergency recall operation and/or Phase II emergency in-car operation)
Emergency Power System Information
Identify and describe the source(s) of emergency power for the building
Identify all systems connected to the emergency power system
Preventative Records of the Fire Protection and Life Safety Equipment and Systems
Describe the general conditions of the fire protection and life safety equipment and systems in the building
Describe the preventative records of the fire protection and life safety equipment and systems reviewed
Fire Safety Evaluation System (FSES) Scoring
FSES Completion Date:
Fire Control:
Egress Provided:
General Fire Safety:
Building Fire Risk Index (BFRI)
Occupant Emergency Plan
Date of most current OEP
Date of last fire drill or training drill
Describe the procedures to evacuate persons with mobility disabilities
Describe the procedures to evacuate occupants after hours
Means of Egress
Means of Egress Components
Are doors in compliance? If no, identify and describe the circumstances in the findings section.Consider all doors associated with the means of egress. Keep in mind door hardware, fire ratings, and operation.
Are stairs in compliance? If no, identify and describe the circumstances in the findings section.Consider all stairs involved in an elevation change. Keep in mind tread and risers, and width.
Are handrail/guards in compliance? If no, identify and describe the circumstances in the findings section.
Are ramps in compliance? If no, identify and describe the circumstances in the findings section.
Are horizontal exits in compliance? If no, identify and describe the circumstances in the findings section.
Are exit passageways in compliance? If no, identify and describe the circumstances in the findings section.
Capacity of Means of Egress
Is the means of egress capacity based on occupant load for floor and area adequate?
Means of Egress Minimum Width
Is the means of egress minimum width maintained (i.e. 44" or 36" where permitted)?
Number of Exits
Are the required number of exits provided for floor or area?
Are there interlocking or scissor stairs present (if yes, counts as 1 exit)?
Arrangement of Means of Egress
Are exits readily accessible? If no, identify and describe the circumstances in the findings section.
Are common path of travel and dead end arrangements in compliance? If no, identify and describe the circumstances in the findings section.
Are exits arranged to be remote per code? If no, identify and describe the circumstances in the findings section.
Are travel distances in compliance? If no, identify and describe the circumstances in the findings section.
Discharge of Means of Egress
Is the exit discharge in compliance? If no, identify and describe the circumstances in the findings section.Consider arrangement, lighting, and marking of exit discharge.
Illumination of Means of Egress
If emergency lighting is provided, is there adequate coverage? If no, identify and describe the circumstances in the findings section.
Marking Means of Egress
Are adequate markings of means of egress provided? If no, identify and describe the circumstances in the findings section.
Is the illumination of the markings of means of egress in compliance? If no, identify and describe the circumstances in the findings section.
Other Findings
Other Findings 1
Other Findings 2
Other Findings 3
Other Findings 4
Other Findings 5
Other Findings 6
Other Findings 7
Other Findings 8
Other Findings 9
Other Findings 10
Overall RAC
Overall RAC
User Adjusted RACOnce the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Explanation of User Adjusted RAC
Fire Detection and Alarm
Fire Detection and Alarm
If there is a fire alarm system installed, is the system operational and functioning correctly?
Initiating Devices
Are there manual pull station issues? If yes, please describe in the findings section.
Are there smoke detectors issues? If yes, please describe in the findings section.
Are there duct detectors issues? If yes, please describe in the findings section.
Are there heat detectors issues? If yes, please describe in the findings section.
Are there water flow switches issues? If yes, please describe in the findings section.
Are there valve supervision issues? If yes, please describe in the findings section.
Are there any other initiating devices with issues? If yes, please describe in the findings section.Consider elevator recall, smoke removal, etc.
Notification Devices
Are there any visual device problems? If yes, please describe problems and date of test and maintenance report in the findings section.Consider strobes and any other forms of visual communication for mass notification.
Are there any audibility problems? If yes, please describe in the findings section.
Other Findings
Other Findings 1
Other Findings 2
Other Findings 3
Other Findings 4
Other Findings 5
Other Findings 6
Other Findings 7
Other Findings 8
Other Findings 9
Other Findings 10
Overall RAC
Overall RAC
User Adjusted RACOnce the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Explanation of User Adjusted RAC
Fire Suppression
Automatic Sprinklers
Are there any identified fire sprinkler issues? If yes, please explain in the findings section.Verify that the sprinkler design is adequate for the level of protection required for that area.
Standpipes
Are there any standpipe issues? If yes, please explain in the findings section.
Fire Pumps
Are there any fire pump issues? If yes, please explain in the findings section.
Other Suppression Systems
Are there identified issues? If yes, please explain in the findings section.
Other Findings
Other Findings 1
Other Findings 2
Other Findings 3
Other Findings 4
Other Findings 5
Other Findings 6
Other Findings 7
Other Findings 8
Other Findings 9
Other Findings 10
Overall RAC
Overall RAC
User Adjusted RACOnce the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Explanation of User Adjusted RAC
Smoke Control
Smoke Control
Are there any smoke control issues? If yes, please explain in the findings section.
Other Findings
Other Findings 1
Other Findings 2
Other Findings 3
Other Findings 4
Other Findings 5
Other Findings 6
Other Findings 7
Other Findings 8
Other Findings 9
Other Findings 10
Overall RAC
Overall RAC
User Adjusted RACOnce the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Explanation of User Adjusted RAC
Other
Fire and Smoke Barriers
Are penetrations properly maintained? If no, please describe in the comments section.
Are opening protective's properly maintained? If no, please describe in the comments section.
Are all other fire barriers properly maintained? If no, please describe in the comments section.
Emergency Power
Are there any identified issues? If yes, please explain in the findings section.
Interior Finishes
Are interior finishes compliant with the occupancy use? If no, please describe in the findings section.
Fire Planning and Prevention
Are there any other overall fire prevention issues? If yes, please describe in the findings section.
Other Findings
Other Findings 1
Other Findings 2
Other Findings 3
Other Findings 4
Other Findings 5
Other Findings 6
Other Findings 7
Other Findings 8
Other Findings 9
Other Findings 10
Overall RAC
Overall RAC
User Adjusted RACOnce the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Explanation of User Adjusted RAC

RAC_VALUE_HELPER

PossibleMinor4
ProbableCatastrophic1
ImminentModerate3
Not PossibleSignificant6
UnlikelyModerate5
RemoteModerate4
PossibleNo Impact6
PossibleSevere3
ImminentMinor3
Not PossibleModerate6
Not PossibleNo Impact6
RemoteCatastrophic3
ProbableSevere2
ProbableModerate3
ImminentNo Impact6
PossibleCatastrophic2
RemoteNo Impact6
RemoteSevere3
UnlikelySignificant4
Not PossibleSevere6
ImminentSignificant2
PossibleModerate4
UnlikelyCatastrophic3
UnlikelySevere4
ImminentCatastrophic1
ProbableNo Impact6
RemoteSignificant4
Not PossibleMinor6
UnlikelyMinor5
RemoteMinor5
ImminentSevere1
ProbableSignificant3
ProbableMinor4
Not PossibleCatastrophic6
UnlikelyNo Impact6
PossibleSignificant3

Microsoft_Excel_Worksheet.xlsx

GSA National Consolidated Risk Management Survey Environmental Survey

RAC Summary

448 EDITABLE N

Documentation 1

Air Programs 1

Fuel Storage Tanks 1

Hazardous Materials 1

Hazardous Waste 1

PCBs 1

Solid Waste 1

Water Pollution 1

Overall RAC 1

GSA National Consolidated Risk Management Survey

Questions Response Finding & Observation

IRIS Building Profile

Region 11 63 342 834236 1

GSA Building Number DC0010ZZ 63 343 834237 1

GSA Building Name LYNDON B. JOHNSON FEDERAL BLDG 63 344 834238 1

Building Street Address 400 MARYLAND AVE SW 63 345 834239 1

Building City WASHINGTON 63 346 834240 1

Building State DC 63 347 834241 1

Date of Building Construction 1959 63 348 834242 1

Building Size (GSF) 640332 63 349 834243 1

Building Size (RSF) 63 350 834244 1

Total Number of Floors Above Grade 7 63 351 834245 1

Total Number of Floors Below Grade 1 63 352 834246 1

448 N 63

GSA National Consolidated Risk Management Survey

Questions Response Finding & Observation

Building Profile

Date(s) of Onsite Survey 65 366 834260 1

Surveyor 65 367 834261 1

Type of Occupancies Business 65 368 834262 3

Building Point(s) of Contact for Surveys 65 369 834263 1

Date of Building Construction 1959 65 370 834264 1

Date of Last Major Building Renovation 65 371 834265 1

Has any work been done since the last survey (e.g., any tenant fit-outs, changes in occupancy, etc.)? If yes, please describe in the findings section. Yes 65 372 834266 4

Property Type Border Station 65 373 834267 3

What is the tenant breakdown? Multiple 65 374 834268 3

Primary Tenants 65 375 834269 1

Is there a law enforcement tenant in this facility? Yes 65 376 834270 4

Name of O&M or Facilities Management Services Contractor 65 377 834271 1

Name of Custodial Services Contractor 65 378 834272 1

Identify any Unique Space Type(s). If "other" is chosen, please describe the "other" unique space in the comments section. Cafeteria 65 379 834273 3

Building Size (GSF) 640332 65 380 834274 1

Building Size (RSF) 65 381 834275 1

Total Number of Floors Above Grade 7 65 382 834276 1

Total Number of Floors Below Grade 1 65 383 834277 1

Is the building a highrise according to Rexus? Yes 65 384 834278 4

Is the building a highrise according to FPE? Yes 65 385 834279 4

What is the building construction classification (IBC Code)? IA 65 386 834280 3

What is the pitch of roof? 65 387 834281 1

Are there photovoltaic (PV) cells on the roof? Yes 65 364 834258 4

Type of Roof Anchoring System Davit 65 365 834259 3

Are there antennas? Yes 65 388 834282 4

How many elevators are there? 65 353 834247 1

Identify Fuel Fired Equipment 65 354 834248 1

What are the fuel types? 65 355 834249 1

How many confined spaces are there? 65 356 834250 1

What type of confined spaces are there? Manholes 65 357 834251 3

How many permit-required confined spaces are there? 65 358 834252 1

What is the potable water source? Municipal 65 359 834253 3

Is there asbestos containing material(s)? Yes 65 360 834254 4

Is there lead paint or other lead material(s)? Yes 65 361 834255 4

Is there PCB containing material(s)? Yes 65 362 834256 4

What energy sources are used onsite? (select all that apply) Fossil Fuels 65 363 834257 3

Above-Ground Storage Tanks (ASTs)

Are there any ASTs? Yes 66 389 834283 4

If yes, how many are there? 66 390 834284 1

What is their total value? 66 391 834285 1

Tank Size (gallons) 66 392 834286 1

Type 66 393 834287 1

Tank Location 66 394 834288 1

Fuel Type 66 395 834289 1

Installation Date 66 396 834290 1

Underground Storage Tanks (USTs)

Are there any USTs? Yes 67 397 834291 4

If yes, how many are there? 67 398 834292 1

What is their total value? 67 399 834293 1

Tank Size (gallons) 67 400 834294 1

Type 67 401 834295 1

Tank Location 67 402 834296 1

Fuel Type 67 403 834297 1

Installation Date 67 404 834298 1

Occupant Emergency Plan (OEP)

Is there an OEP? Yes 68 405 834299 4

Date of plan 68 406 834300 1

Are persons in plan current? Yes 68 407 834301 4

Is there OEP training for designated persons? Yes 68 408 834302 4

Are there procedures for evacuation of disabled persons? Yes 68 409 834303 4

Are there procedures for after-hours emergencies? Yes 68 410 834304 4

Is there a fire department pre-fire plan? Yes 68 411 834305 4

448 EDITABLE N 68

Documentation

GSA National Consolidated Risk Management Survey

Documentation

Questions Response Finding & Observation Regulatory Citation Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action

Water

Does the facility have a welI that requires a permit? Yes Test Test Imminent Catastrophic 1 No Test 164 690 834368 4

If the well requires a permit, is the permit onsite? Yes Test1 Test1 Imminent Catastrophic 1 No Test1 164 691 834369 4

Is a NPDES/SPDES issued to the facility? Yes Finding Citation Imminent Catastrophic 1 No Location 164 692 834370 4

Is a waste water pretreatment permit/registration issued to the facility? If yes, provide key requirements description in findings section. Yes Imminent Catastrophic 1 No 164 693 834371 4

Hazardous Materials

Is documentation available that shows the facility has coordinated with state and/or local emergency planning commitees? If yes, describe in the findings section. Yes Imminent Catastrophic 1 No 163 694 834363 4

If required to do so, has the facility filed a Tier II Report? Yes Imminent Catastrophic 1 No 163 695 834364 4

Is there a complete (e.g. all occupants) facility chemical inventory available? Please identify the sources of the inventory in the findings section. Sources can include O&M contractors, custodial contractors, and tenants.

: The building inventory should reflect all chemicals stored on-site regardless of ownership (e.g., tenant, GSA, contractor, etc.) Yes Imminent Catastrophic 1 No 163 696 834365 4

Are Safety Data Sheets (SDS) maintained for materials stored at the building? Compare materials/chemicals observed during site visit to inventory. Specify discrepancies in the findings section.

: SDS is the updated terminology for MSDS. Yes Imminent Catastrophic 1 Yes Test Action834366 163 697 834366 4

Are there any findings of non-compliance with PCBs recordkeeping? If yes, describe in the findings section. Yes Imminent Catastrophic 1 No 163 698 834367 4

Solid Waste

Does the facility maintain records of solid waste disposed and recycled? Yes Imminent Catastrophic 1 No 160 699 834353 4

Does the facility have an EPA or State ID number assigned to GSA? Yes Imminent Catastrophic 1 Yes Test Action834354 160 700 834354 4

Fuel Storage Tanks

If FSTs (ASTs or USTs) are on-site, are they on GSA's National Tanks Inventory? Yes Imminent Catastrophic 1 No 166 701 834379 4

Are required tank permits and/or registration on file? Describe non-compliance with permit/registration requirements in the findings section. Please include the expiration dates in findings section as well. Yes Imminent Catastrophic 1 No 166 702 834380 4

Are UST(s) automatic leak detection system maintenance records properly maintained? Yes Imminent Catastrophic 1 No 166 703 834381 4

Are UST manual inventory controls records maintained (fill/consumption, dipstick, etc.)? Yes Imminent Catastrophic 1 No 166 704 834382 4

Are three any lack of records or other issues regarding any leak detection system? If yes, please describe in the findings section. Yes Imminent Catastrophic 1 No 166 705 834383 4

If underground tanks were closed in place, is there a closure report or No Further Action (NFA) letter on file? If no, provide additional details in the findings section. Yes Imminent Catastrophic 1 Yes Test Action834384 166 706 834384 4

Does staff have the appropriate level of UST Owner/Operator Training (levels A/B/C) as required by the Energy Policy Act of 2005 and are certifications/training records available for review? Yes Imminent Catastrophic 1 No 166 707 834385 4

Does the facility have written or verbal procedures for product or waste transfers? If yes, please describe in the findings section. Yes Imminent Catastrophic 1 No 166 708 834386 4

Spill Response and Prevention

If required, does the facility have a Spill Prevention, Control and Countermeasures (SPCC) Plan? If yes, provide the title for the plan, the date the plan was written, and note when the last annual SPCC training was conducted. Yes Imminent Catastrophic 1 No 162 709 834359 4

Does the SPCC Plan reflect the actual situation at the facility (number of ASTs, number of 55 gallon drums, location of spill control equipment)? Yes Imminent Catastrophic 1 Yes Test Action834360 162 710 834360 4

Does the SPCC Plan meet all regulatory requirements? Yes Imminent Catastrophic 1 No 162 711 834361 4

Do personnel comply with all sections of the SPCC Plan? Descibe any non-compliance or violations with the SPCC requirements in the findings section. Yes Imminent Catastrophic 1 No 162 712 834362 4

Air

Are air permits issued to the facility? Yes Imminent Catastrophic 1 Yes Test Action834372 165 713 834372 4

Are permits/registration documents on file for individually permitted/registered emissions generating equipment? Review the air permits. Give brief description of permit conditions in the findings section. Describe emission sources/equipment listed in the permit, allowable throughout in gallons for ASTs, recordkeeping requirements discrepancies, etc. in the findings section. Yes Imminent Catastrophic 1 No 165 714 834373 4

Are there other sources/equipment requiring air permits? This may include laboratory vents, generators, fuel storage tanks, maintenance activities and operations such as welding, and firing ranges. If yes, please describe in the findings section. Yes Imminent Catastrophic 1 No 165 715 834374 4

If there is an Emergency Generator, does the Generator require a permit or plan for the state/country/local air district? Yes Imminent Catastrophic 1 No 165 716 834375 4

If required, does the boiler have a permit? Where applicable, review permit and results of any boiler emissions test. Provide a brief descritpion of permit conditions in the findings section. Descriptions should include allowable NOX, SOX, PM, and other restrictions, etc. Yes Imminent Catastrophic 1 No 165 717 834376 4

Are chiller maintenance records, including replacement refrigerants, registration of recovery units, etc. up to date? Yes Imminent Catastrophic 1 No 165 718 834377 4

Are training certificates for GSA staff and contractors performing maintenance on chillers, replacement refrigerants, registration of recovery units up-to-date? Yes Imminent Catastrophic 1 Yes Test Action834378 165 719 834378 4

Shipping Documents

Does the facility maintain hazardous waste manifests or bills of lading? Yes Imminent Catastrophic 1 No 161 720 834355 4

Are there incomplete or illegible waste manifests or evidence of exceeding hazardous waste generator status? If yes, describe in the findings section. Yes Imminent Catastrophic 1 No 161 721 834356 4

Does the facility maintain required shipping documents for asbestos waste, lead-contaminated, or lead based paint wastes? Yes Imminent Catastrophic 1 No 161 722 834357 4

Does facility maintain shipping documents for recycled materials? Yes Imminent Catastrophic 1 No 161 723 834358 4

Overall RAC

Overall RAC 1 159 615 834350 5

User Adjusted RAC 159 616 834351 6

Explanation of User Adjusted RAC 159 617 834352 1

448 EDITABLE N 159

1 1 N

Air Programs

GSA National Consolidated Risk Management Survey

Air Programs

Questions Response Finding & Observation Regulatory Citation Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action

Permit Compliance

If an air permit exists, do the facility operations comply with the air permit?

: Review the permit for compliance with the sulfur content for diesel fuel, run time, etc. and other aspects of the operation. Yes Imminent Catastrophic 1 No 148 724 834320 4

If an air permit exists, is the emergency generation operation compliant with the sulfur content for diesel fuel, run time, etc. and other aspects of the permit? If not, describe in the findings section. Yes Imminent Catastrophic 1 No 148 725 834321 4

Emergency Generator

Is there an Emergency Generator for the site? If yes, please provide the Total Output Rated Capacity (KW) in the findings section. Yes Imminent Catastrophic 1 No 145 726 834309 4

What type of fuel does the Emergency Generator use? Diesel Imminent Catastrophic 1 No 145 727 834310 3

Are there any outstanding deficiencies associated with the Emergency Generator? If yes, please describe in the findings section. Yes Imminent Catastrophic 1 No 145 728 834311 4

Boilers

Are there any boilers in this facility? If yes, please list the BTU capacity in the findings section. Yes Imminent Catastrophic 1 Yes Test Action834312 146 729 834312 4

What is the fuel used? Gasoline Imminent Catastrophic 1 No 146 730 834313 3

If required to have a permit, are facility boiler operations compliant with the permit? Including allowable NOX, SOX, PM, and other restrictions, etc. Yes Imminent Catastrophic 1 No 146 731 834314 4

Cooling Systems

Are there operating cooling systems at this facility? If yes, please provide the size of the cooling system in the findings section. Yes Imminent Catastrophic 1 No 147 732 834315 4

If there is a cooling system at the facility, please list the refrigerants that are in use or stored onsite in the findings section. Refrigerants listed in findings section Imminent Catastrophic 1 No 147 733 834316 3

Is there evidence of leaks and/or lack of system re-certification? Review chiller records (invoices, work orders, logs). If yes, please describe in the findings section. Yes Imminent Catastrophic 1 No 147 734 834317 4

Is used chiller oil taken off-site for disposal/recycling by the maintenance service contractor? If not, describe in the findings section. Yes Imminent Catastrophic 1 Yes Test Action834318 147 735 834318 4

Were any findings during this assessment a repeat from a previous assessment? If yes, provide details in the findings section. Yes Imminent Catastrophic 1 No 147 736 834319 4

Overall RAC

Overall RAC 1 144 603 834306 5

User Adjusted RAC 144 604 834307 6

Explanation of User Adjusted RAC 144 605 834308 1

448 EDITABLE N 144

1 1 N

Fuel Storage Tanks

GSA National Consolidated Risk Management Survey

Fuel Storage Tanks

Questions Response Finding & Observation Regulatory Citation Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action

Underground Storage Tanks

Does the facility have any underground storage tanks (USTs)? Yes Imminent Catastrophic 1 No 170 737 834393 4

Is the UST(s) corrosion protection system properly maintained? Check records. If no, describe in the findings section. Yes Imminent Catastrophic 1 No 170 738 834394 4

Are tank and piping tightness tests conducted? If yes, describe frequency of testing, the date of the last test(s) and the results in the findings section. Yes Imminent Catastrophic 1 No 170 739 834395 4

Does the facility use methods of leak detection other than automatic leak detection? Yes Imminent Catastrophic 1 Yes Test Action834396 170 740 834396 4

Are the spill buckets for the UST dry and intact (not cracked)? Describe any issues with spill buckets and loading/unloading procedures and operations in the findings section. Yes Imminent Catastrophic 1 No 170 741 834397 4

Is any UST more than 15 years old? If yes, please list the age of each in the findings section. Yes Imminent Catastrophic 1 No 170 742 834398 4

Does the facility/staff monitor loading/unloading operations? If yes, describe in the findings section.

: Loading refers to re-fueling. Yes Imminent Catastrophic 1 No 170 743 834399 4

Have any underground tanks been closed at the facility? If yes, verify records. Yes Imminent Catastrophic 1 No 170 744 834400 4

Has…

This is the start of the file's text. The full file is on GovTribe.