KITTRELL
Job Corps Center Kittrell, NC
Facility Planning Report Volume II
Supporting Data
Final March 2015
Department of Labor/ Office of Job Corps
KITTRELL
Job Corps Center Kittrell, NC
Facility Planning Report Volume II
Supporting Data
Final March 2015
View of Admin/Vocational Building 2
VOLUME I - PLANNING STRATEGY
Acronyms and Abbreviations Defi nition of Terms Executive Summary Existing Site Plan Center Statistics Facility Survey Assessment Results and Recommendations
1.0 INTRODUCTION
• Objective and Scope
• Report Contents
2.0 EXISTING CONDITIONS
• Background
• Ownership
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Facility Assessment by Function
• Environmental Management
• Resource Use/Conservation
• Sustainability
• Accessibility Standards
• Completed and Current Projects
• Health and Life Safety Issues
• Defi ciency Summary
3.0 PLANNING ANALYSIS
• Space Utilization Analysis
• Federal Real Property Asset Management
• Defi ciency Analysis
• Facility Condition Summary
• Building Condition by Function
• Planning Analysis Results and Conclusions
4.0 RECOMMENDATIONS
• Status of Previous Plan
• Proposed Plan
• Funded Not Corrected (FNC) Defi ciencies
• Summary of Proposed Plan
• Proposed Site Plan
• Implementation Plan
• Summary List of National Projects
• Project Data Sheets
VOLUME II - SUPPORTING DATA
Acronyms and Abbreviations Defi nition of Terms Executive Summary
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Appendix E.
• FRPC Performance Measures Matrix
Acronyms and Abbreviations
ACRONYMS AND ABBREVIATIONS
A Amperage ABAAS Architectural Barriers Act Accessibility Standard ACM Asbestos-Containing Materials AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 BTU British Thermal Units\ CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television CDC Child Development Center CDC Centers for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Feet per Minute CIS Center Information System CMA Certified Medical Assistant CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CAN Certified Nursing Assistant CO Carbon Monoxide CO Contracting Officer COR Contracting Officer’s Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CTP Career Transition Period CTS Career Transition Services
CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])
CW Cold Water CWA Clean Water Act DDC Direct Digital Controls DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician
EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPMD Ethylene Propylene Diene Terpolymer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallons per Hour GSA General Services Administration GSF Gross Square Feet HID High Intensity Discharge HP Horsepower HSD High School Diploma HTW Hazard and Toxic Waste HVAC Heating, Ventilating, and Air Conditioning HW Hot Water IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code KBTU Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Amps kw Kilowatt JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook kWh Kilowatt Hours LAN Local Area Network LED Light Emitting Diode LF Linear Feet MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch NEC National Electric Code NEMA National Electrical Manufacturers Association NEPA National Environmental Protection Act NFPA National Fire Protection Association NMD Not Mission Dependent NSF Net Square Feet OA Outreach and Admissions OBS On Board Strength OCM Office of Contract Management OIG Office of Inspector General O&M Operations and Maintenance OSHA Occupational Safety and Health Administration PA Public Address pCi Picocurie PV Photovoltaic PVC Polyvinyl Chloride RCRA Resource Conservation and Recovery Act RTU Rooftop Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Feet SPCC Spill Prevention, Control and Countermeasure SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency)
T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories USDA U. S. Department of Agriculture V Volt VCR Video Cassette Recorder VST Vocational Skills Training W Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board
Defi nition of Terms
DEFINITION OF TERMS
Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.
Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).
Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.
Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.
Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required
Construction Type: The International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.
Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:
Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.
Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)
Building: Building deficiencies indicate adverse conditions at the building level.
This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.
Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:
Class IA - Deficiencies which address imminent life safety and health hazards.
Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.
A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.
B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.
C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.
Class III - Deficiencies which address facility repair, replacement or maintenance.
A - Deficiencies which if not corrected may result in an interruption of center operations.
B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.
Class IV – Deficiencies which address programmatic needs.
A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.
B - Deficiencies which if corrected are desirable enhancements.
Deficiency Funding Status: The status of the deficiency included the following categories:
Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.
Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.
Proposed deficiencies have been assigned to a proposed future National project.
Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.
Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:
Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.
Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.
Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.
No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.
Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.
Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).
Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):
Mission Critical - – Without constructed asset or parcel of land, mission is compromised.
Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.
Not Mission Dependent (NMD) – Mission unaffected
Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).
National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.
Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).
On Board Strength (OBS): The actual number of students on Center on a day to day basis.
Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).
Property Type: Indicates the asset as one of the following categories of real property:
land, building, structure.
Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.
In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:
ESCIS FRPC
Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility
Systems, or Other Land Institutional
* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.
Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).
Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.
Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.
Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".
Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”
Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).
Executive Summary
The facility survey for the Kittrell Job Corps Center (JCC) was completed October 06 to October 10, 2014. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
KITTRELL
JOB CORPS CENTER
KITTRELL, NORTH CAROLINA
KITTRELL JCC
10 MI5 0
2.0 - Descriptions
2.0 DESCRIPTIONS
In this section, the following information on the Center and its buildings and structures is presented in tabular format:
Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
The overall building/structure condition is rated in one of three categories: good, fair, or poor.
Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.
Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.
Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of
1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.
Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;
natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.
Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;
electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.
BUILDINGS AND STRUCTURES
00406 KITTRELL 03/12/2015
1Page: of Date:
0001 - VOCATIONAL/EDUCATIONAL
0002 - ADMIN/VOCATIONAL
0003 - MEDICAL/DENTAL/CPP
0004 - GYMNASIUM
0005 - FOOD SERVICE/CULINARY ARTS
0006 - DORMITORY
0007 - DORMITORY
0009 - STUDENT TRAINING CENTER
0010 - FACILITY MAINT OFFICE
0011 - STUDENT LIFE
0016 - FACILITY MAINTENANCE AND
CONSTRUCTION LAB
0018 - LAUNDRY
0020 - ADVANCE CAREER
TRAINING/WORK BASE LEARNING
0021 - SECURITY
0025 - VOCATIONAL BUILDING
0026 - STUDENT GOVERNMENT
0027 - EDUCATION
0014 - STP STORAGE (8Ft x 10Ft) 0014A - STP TANK 1 (12Ft DIAMETER) 0014B - STP TANK 2 (8Ft x 20Ft) 0014C - STP TANK 3 (4Ft x 10Ft) 0017 - FACILITY MAINT. STORAGE (8Ft x 10Ft) 0023 - PAVILION (8Ft x 10Ft) 0025A - SAND PIT (10Ft x 20Ft) 0028 - STORAGE (10Ft x 12Ft)
0029 - HAZARDOUS MATERIAL
STORAGE (15Ft x 14Ft) 0032 - RESIDENTIAL STORAGE (20Ft x 20Ft) 0033 - GAZEBO (20Ft x 9Ft) 0034 - VEHICLE SHELTER (38Ft x 20Ft)
Name GSF
14,020 13,230 8,833
16,830 16,165 19,175 19,175 1,510 1,368 2,260 1,066
1,800
1,734 12,100
13,980
Active Active Active Active Active Active Active Active Active Active Active
Active Active
Active Active Active Active Active Active Active Active Active
Active Active Active Active
Active
Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building
Building Building
Building Building Building Building Structure Structure Structure Structure Structure
Structure Structure Structure Structure
Structure
Structure Structure
Use Group Built Flrs Const
Business Business Business Assembly Assembly Residential Residential Business Business Business Business
Storage Business
Business Business Business Business Storage Utility/Misc.
Utility/Misc.
Utility/Misc.
Storage
Assembly Business Storage Storage
Storage
Assembly Utility/Misc.
Good Good Good Good Good Good Good Good Fair
Good Good
Good Good
Good Good Fair
Good Good Good Good Good Good
Good Good Good Good
Good
Good Good
ConditionAsset Number
0040600002 0040600003 0040600004 0040600005 0040600006 0040600007 0040600008 0040600010 0040600011 0040600012 0040600022
0040600014 0040600020
0040600023 0040600027 0040600028 0040600026 0040600017 0040608093 0040608094 0040608095 0040600019
0040600025 0040608096 0040600030 0040600029
0040608089
0040608090 0040608092
17 144,866
12 2,435
29 147,301
Buildings
Structures
Total
GSF
GSF
GSF
Summary
03/12/2015
Space Utilization By Function 00406 Kittrell Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 300 Non Residents 50
350Total Students
(300)
(350)
(350)
DIFFERENCE
32,400
17,350
6,300
26,472
42,416
7,604
Lounge Other Shower/Toilet Sleeping excl. SPD(93 rooms; 328 beds) Storage
Academic (350) Non-Academic
40 -- ACT (Off-Ctr) 25 -- Brick Masonry + 25 -- Culinary Arts + 25 -- Facilities Maint. and Const. + 60 -- Nursing Assistant + 30 -- Office Administration 60 -- Technical Trades (Off-Ctr)
Vocational Theory (135)
Dining (2 Servings) Food Preparation Food Storage
3,505 2,523 2,881
16,213 1,350
8,347 11,961
5,824 5,458 4,787 1,963 2,898
1,178
3,682 2,777 1,145
3,000 2,400 3,600
21,600 1,800
3,500 3,500
1,875 1,500 1,875 2,400 1,350
1,350
2,800 2,100 1,400
-719
-5,387 -450
4,847 8,461
3,949 3,958 2,912
-437 1,548
-172
-255
Vocations
-5,928
25,066
1,304
03/12/2015
Space Utilization By Function 00406 Kittrell Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 251.06 87,870 105,440
(350)
(350)
(350)
(350)
(0)
DIFFERENCE
144,866
0.73
TOTAL GSF
NET TO GROSS RATIO
15,750
2,070
7,000
14,897
2,600
5,447
4,107
1,897
Aerobics/Exercise Arts & Crafts Concession Stand/Restroom Gymnasium Hair Salon Pool Hall Recreation Hall Recreation Office Recreation Room Recreation Storage Snack Bar/Corpsmembers Store T.V. Room Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Under Renovation - Education Vacant
5.91
9,046
1,292
1,012
2,600
5,447
2,567 1,540
2,070
2,800 4,200
9,046
1,292
1,012
-1,553
-233 -2,660
RESIDENT
NON-RESIDENT
(300)
(50) 15
50 15,000
-853
-1,553
-2,893
1,897
17,570
Net Square Footage By Building Date: 03/12/2015 Page: 1
Center: KITTRELL (00406) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
7,838 8,375
1,553 1,952
1,251 1,630
1,019
0006 - DORMITORY
0007 - DORMITORY
0007 - DORMITORY
0006 - DORMITORY
0006 - DORMITORY
0007 - DORMITORY
0018 - LAUNDRY
0006 - DORMITORY
0007 - DORMITORY
0018 - LAUNDRY
0007 - DORMITORY
0006 - DORMITORY
Bldg Name Actual NSF Difference
16,213
3,505
1,350
2,881
2,523
Sub Total: 26,472
21,600
3,000
1,800
3,600
2,400
32,400
-5,387
-450
-719
( 300
-5,928
46 rooms; 160 beds 47 rooms; 168 beds
Page: 2
Center: KITTRELL (00406) of 4
EDUCATION
Academic
Vocational Theory (135)
Culinary Arts
Facilities Maint. and Const.
Non-Academic
Nursing Assistant
Brick Masonry
Office Administration
Function Suggested
NSF
4,835
1,172 1,178
5,458
3,626
3,266 1,552
1,525
1,100
1,963
5,824
2,898
0027 - EDUCATION
0027 - EDUCATION
0027 - EDUCATION
0027 - EDUCATION
0027 - EDUCATION
0025 - VOCATIONAL BUILDING
0001 - VOCATIONAL/EDUCATIONAL
0005 - FOOD SERVICE/CULINARY ARTS
0025 - VOCATIONAL BUILDING
0002 - ADMIN/VOCATIONAL
0001 - VOCATIONAL/EDUCATIONAL
0027 - EDUCATION
0001 - VOCATIONAL/EDUCATIONAL
0027 - EDUCATION
0027 - EDUCATION
0001 - VOCATIONAL/EDUCATIONAL
0003 - MEDICAL/DENTAL/CPP
0011 - STUDENT LIFE
0001 - VOCATIONAL/EDUCATIONAL
0002 - ADMIN/VOCATIONAL
0020 - ADVANCE CAREER TRAINING/WORK BASE LEARNIN
0025 - VOCATIONAL BUILDING
0002 - ADMIN/VOCATIONAL
0009 - STUDENT TRAINING CENTER
0001 - VOCATIONAL/EDUCATIONAL
0001 - VOCATIONAL/EDUCATIONAL
0025 - VOCATIONAL BUILDING
0001 - VOCATIONAL/EDUCATIONAL
Bldg Name Actual NSF Difference
8,347
1,178
5,458
4,787
11,961
1,963
5,824
2,898
Sub Total: 42,416
3,500
1,350
1,500
1,875
3,500
2,400
1,875
1,350
17,350
4,847
-172
3,958
2,912
8,461
-437
3,949
1,548
( 350
25,066
Page: 3
Center: KITTRELL (00406) of 4
FOOD SERVICE
RECREATION
Dining (2 Servings)
Food Preparation
Food Storage
Recreation Hall
Arts & Crafts
Gymnasium
Weight Room
Pool Hall
Aerobics/Exercise
Snack Bar/Corpsmembers Stor
Hair Salon
Recreation Room
Concession Stand/Restroom
T.V. Room
Recreation Storage
Recreation Office
Function Suggested
NSF
3,682
2,777
1,145
9,046
1,292
1,012
0005 - FOOD SERVICE/CULINARY ARTS
0005 - FOOD SERVICE/CULINARY ARTS
0005 - FOOD SERVICE/CULINARY ARTS
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0006 - DORMITORY
0026 - STUDENT GOVERNMENT
0004 - GYMNASIUM
0004 - GYMNASIUM
0004 - GYMNASIUM
0026 - STUDENT GOVERNMENT
0004 - GYMNASIUM
0026 - STUDENT GOVERNMENT
Bldg Name Actual NSF Difference
3,682
2,777
1,145
9,046
1,292
1,012
Sub Total:
Sub Total:
7,604
14,897
2,800
2,100
1,400
6,300
15,750
-255
1,304
-853
Page: 4
Center: KITTRELL (00406) of 4
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Medical/Dental
Administration
Warehouse
Operations & Maintenance
Vacant
Under Renovation - Education
Function Suggested
NSF
2,600
1,360 4,087
1,540
1,190 1,377
0003 - MEDICAL/DENTAL/CPP
0021 - SECURITY
0002 - ADMIN/VOCATIONAL
0002 - ADMIN/VOCATIONAL
0010 - FACILITY MAINT OFFICE
0001 - VOCATIONAL/EDUCATIONAL
0002 - ADMIN/VOCATIONAL
0007 - DORMITORY
0006 - DORMITORY
0016 - FACILITY MAINTENANCE AND CONSTRUCTION LAB
Bldg Name Actual NSF Difference
2,600
5,447
1,540
2,567
Sub Total:
Sub Total:
Sub Total:
Sub Total:
2,600
5,447
4,107
1,897
2,070
7,000
4,200
2,800
2,070
7,000
7,000
-1,553
-2,660
-233
-1,553
-2,893
1,897
Environmental Management Report Center: KITTRELL (00406)
Page: 1 Date: 03/12/2015 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building #15 (Paint Storage), Buildings #4, 6, 10, 18, 25
Organic solvent (5 gals), propane tanks (5 x 1000 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance1
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
1 Near Building 1 10,000Petroleum - Heating Oil
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Industries, Inc.
No N/A
N/A N/A Commercial Hazardous Waste Disposal Service
Stericycles
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
04/11/1990 Friable/Non-Friable Lawrence Pulley 03/21/2005 Yes No N/A Yes Yes
Yes Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
Petroleum - Gasoline
Petroleum - Diesel Fuel
Near Building 10
Near Building 14
Yes
Yes
Yes
Yes
Tank Status Active
Active
Active Tank Status
Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 03/12/2015Center : Kittrell (00406) Page: 1 of 1
Floor Finishes Floor Finishes Floor Finishes
Heating Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes Heating
Floor Finishes Water Plumbing Floor Finishes Floor Finishes
Floor Finishes
Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
9x9 floor tile, gray 9x9 floor tile, various Mastic beneath 9x9 tile
Pipe fitting insulation Mastic beneath 9x9 tile 9x9 floor tile (covered)
9x9 floor tile, white 12x12 floor tile, brown Mastic beneath 9x9 tile Pipe insulation
Mastic beneath 9x9 tile Pipe fitting insulation Mastic beneath 9x9 tile, green 9x9 floor tile, various
12x12 floor tile, gray
Mastic beneath 12x12 tile
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Health occupations Carpentry room, hall Beneath asbestos VFT
Basement crawlspace 1st floor 1st floor
1st floor, stairwell Basement foyer 1st floor, stairwell Basement perimeter
Dining rm., game rm.
Kitchen plenum Food storage, stairs Dining rm., game rm.
Throughout
Throughout
14900
14900
Building :
Building :
Building :
Building :
Building :
Building :
0001 - VOCATIONAL/EDUCATIONAL
0002 - ADMIN/VOCATIONAL
0003 - MEDICAL/DENTAL/CPP
0005 - FOOD SERVICE/CULINARY ARTS
0006 - DORMITORY
0007 - DORMITORY
Radon
Page: 1 of 1
0001 - VOCATIONAL/EDUCATIONAL
0002 - ADMIN/VOCATIONAL
0003 - MEDICAL/DENTAL/CPP
0004 - GYMNASIUM
0005 - FOOD SERVICE/CULINARY ARTS
0006 - DORMITORY
0007 - DORMITORY
0009 - STUDENT TRAINING CENTER
0010 - FACILITY MAINT OFFICE
0011 - STUDENT LIFE
0016 - FACILITY MAINTENANCE AND CONSTRUCTI
0018 - LAUNDRY
0020 - ADVANCE CAREER TRAINING/WORK BASE L
0021 - SECURITY
0025 - VOCATIONAL BUILDING
0026 - STUDENT GOVERNMENT
0027 - EDUCATION
Bldg Name
05/09/1990
05/09/1990
05/09/1990
05/09/1990
05/09/1990
05/09/1990
05/09/1990
03/15/2004
03/15/2004
03/15/2004
05/09/1990
05/09/1990
05/09/1990
03/15/2004
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Radon Testing
< 4 pCi
< 4 pCi
4 - 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
4 - 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
Yes
N/A
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation
08/12/1992
08/12/1992
Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial view of the Center
Page: 1 Date: 03/12/2015 of 5
Comments:
Paving Type for Roads & Parking
Segments of the main roadway (asphalt) and bus parking area are deteriorating and need to be resurfaced.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterKittrell Water AssociationPublic Water Authority
None 0None
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 4None Municipal
The nearest Kittrell Volunteer Fire Station is about 3/4 mile from the center and the response time is 4 minutes. A Henderson Fire Department station is about 8 miles from the center and approximately 10 minutes response time.
Number of Deficiencies = 2
Number of Deficiencies = 1SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures17 12Terraced
Surrounding
Outdoor Recreation
Residential, Rural
Basketball, Soft/Baseball, Volleyball Light Commerecial
Entrance
South and West sides
Storage Area
Wrought Iron
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Number of Deficiencies = 1
Fencing
Other Features
Page: 2 Date: 03/12/2015 of 5
Sewage Treatment Flow
Center
DOL Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Duke Energy Progress
There is one 13.2 kV primary overhead service entrance to the Center from U.S. Highway 1. Once on center, the overhead lines continue along the center main road running east-west. Power poles along this road deliver services to buildings located on both sides of the road. Most major buildings secondary services are underground with pad-mounted transformers while other smaller buildings are overhead with pole-mounted transformers. Buildings 4, 5, 6, and 7 are provided with 480/277V, 3-phase power, Buildings 1, 2, 3 , 25 and 27 are provided with 120/208V, 3-phase power, and Buildings 9, 10, 11, 16, 18, 20, 21, and 26 are provided with 120/240V, 1-phase power. The utility company owns and maintains all pole- and pad-mounted transformers. Individual meters are installed either on the transformers or on the building exterior walls. The only exceptions are Buildings 1 and 2, and Buildings 10 and 26 served by the same utility transformers and metered by the same meters. Food Service/Culinary Arts Building 5 and Sewage Treatment Plant Structure 14 are supported by a 200 kW diesel generator with a 600A automatic transfer switch (ATS) and a 20 kW diesel generator with a 100A ATS respectively. All major buildings have a lightning protection system installed on the roof and TVSS units located in the buildings (Titan T200 BPF, 200 kA per phase by EFI).
Pole and Pad Utility
Utility Utility
No
13.2 kV, 3-Phase
120/208V, 120/240V and 277/480V , 1&3-PhaseOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 1
Drain Type On-Site Storm Water Management
Underground/Surface Runoff N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
ATS MTS
Yes No
5. Fuel Distribution System: None
6. Central Plant: None
Metering Individual
Page: 3 Date: 03/12/2015 of 5
Comments:
Telephone Company
On-site Line Owner
The main telephone DEMARC point and Center’s data closet are housed in the server room located in Building 2 first floor. The service is provided by 6 T1 lines, one of which dedicated to VoIP. There are 20 analog Fax lines and 135 VoIP phone lines. The long distance calls are processed by JCDC and local calls are processed by Century Link/Verizon. By replacement of existing Cisco 3800 series routers with Cisco 3900 series routers the internet speed was increased from 10 to 50 megabytes. The telephone and data communication equipment is supported by a 10 kW APC UPS module providing power backup. The MC houses a Cisco Catalyst 6506 main switch connected by fiber optic to the rest of the buildings. Two Cisco 3900 series routers controls network traffic, voice and video services. A Cisco 4400 wireless LAN controller provides wireless connection. The buildings on the Center are provided with stand-alone fire alarm systems. The last fire alarm inspection report was done by BFPE International (1-800-849-8886) at 2/26/2014. There are CCTV cameras on site, but they are not in use. Cable TV is provided in dormitories, gymnasium and other recreational facilities (Buildings 1-7). Audible door alarms are provided in Buildings 3-7, 25 and 27.
Century Link/Verizon
Maint. Responsibility
Center Center
CCTV cameras
9. Electrical (Communication/Alarm/Security)
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Comments: Except the building-mounted exterior lights and solar powered lights on top of brick columns along the wrought iron fence, all pole-mounted lights on the center are owned and maintained by the utility company.
Number of Deficiencies = 14
Fire Alarm Security
Page: 4 Date: 03/12/2015 of 5
01/05/1965
01/01/1999
01/01/1999
01/01/1999
01/01/1999
01/01/1999
01/01/1999
01/01/1999
01/01/1999
01/01/1992
01/01/1999
01/01/1999
01/01/1999
Center
Private
Private
Private
Private
Private
Private
Private
Center
Center
Private
Private
Private
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Underground, Regulated
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Near Building 1
Near Building 4
Near Building 7
Near Building 18
Near Building 25
Near Building 10
Near Building 26
Near Building 27
Near Building 10
Near Building 14
Near Building 5
Near Building 5
Near Building 3
The 10,000 gallon heating oil underground storage tank next to Building 1 was installed in 1970. The tank has exceeded its useful life expectancy.
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Petroleum - Heating Oil
Propane
Propane
Propane
Propane
Propane
Propane
Propane
Petroleum - Gasoline
Petroleum - Diesel Fuel
Propane
Propane
Propane
STORAGE TANKS
Comments:
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
10000
Heating
Heating
Heating
Heating
Heating
Heating
Heating
Heating
Equip/Veh Fueling
Generator
Heating
Heating
Heating
Purpose
Page: 5 Date: 03/12/2015 of 5
ACCESSIBILITY
Yes
Three buildings are in total compliance.Comments:
UnknownNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Low Medium LowHigh MediumIBC Medium
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 12
Accessible Parking: Accessible Slope:
No
Curb Cuts:
Yes
Ramps:
YesNo
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
Roads and paving are in poor condition; site drainage is poor in numerous areas, and a UST is past its useful life.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
Yes
NO
Yes
Yes
Yes
Yes
Yes
17 %
Building Descriptions and Structures
BUILDING 1 - VOCATIONAL/EDUCATIONAL
Building Descriptions
Page: 1 of 83
Building: 0001 - VOCATIONAL/EDUCATIONAL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 14,020 8,988 2 Owned 1952 Not Evaluated
Comments: The main entrance is approximately 2' above grade. The ramps at the east secondary entrance/exit substantially exceeds 1:12 slope. The lower level is used as a warehouse, has independent grade level access and does not need elevator access from the upper floor.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
No
No
Yes
Yes
Yes
No
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Gutters and Downspouts 2001 7 Flat Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 83
Building: 0001 - VOCATIONAL/EDUCATIONAL
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Drywall
Aluminum Storefront - Aluminum Frame Metal Unit - Metal Frame
Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Ramp
Comments: The stairs lead to a partial basement on the north side of the building and are also used as the secondary means of egress. Concrete ramp is at the south end of the building.
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Sky light - Metal Frame; Double Glazing;
Acoustical Tile Plaster
Number of Deficiencies = 2
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Hot water for heating in this building and Building 2 is provided by a propane-fired boiler located in the basement mechanical room in this building. The water boiler is Weil-McLain model 788. The burner is a Webster Cyclonetic gas burner with a gas input of 2,049 MBH. Hot water is circulated by a Taco model FE2510E2F1F2L0 end-suction pump (9.25 motor HP, 245 GPM at 90 FT. head and manufactured in 12/99) and is piped to fan coil units in each room in Buildings 1 and 2. Note: The finned tube radiators seen in every room along the perimeter of the building are remnants of a long discontinued heating system and were abandoned-in-place.
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Fan Coil Two-Pipe Electric Mechanical None Entire Building
Ceilings
Page: 3 of 83
Building: 0001 - VOCATIONAL/EDUCATIONAL
Mechanical
Mechanical
Restroom
Entire Building
Comments:
Comments: An S&P model SQB15QH35 supply fan with a Warren model CBK 16kW electric heater is a part of the engineered HVAC system and provides tempered fresh air to the individual fan coil unit throughout the building.
Domestic hot water is supplied by a 40-gallon, 4.5 kW electric water heater, model 82V40-2 manufactured by Rheem in 2008.
Comments:
Cast-Iron None Cast-Iron
Electric Water Cooler Emergency Eye Wash Hose…