GRAFTON
Job Corps Center North Grafton, MA
Facility Planning Report Volume II
Supporting Data
Preliminary November 2015
Department of Labor/ Office of Job Corps
GRAFTON
Job Corps Center North Grafton, MA
Facility Planning Report Volume II
Supporting Data
Preliminary November 2015
Historic Building 2
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The facility survey for the Grafton JCC was completed July 13, 2015 – July 17, 2015.
The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
GRAFTON
JOB CORPS CENTER
NORTH GRAFTON, MASSACHUSETTS
GRAFTON JCC
10 MI5 0
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00104 GRAFTON 01/11/2016
1Page: of Date:
0001 - PINES A HEALTH & BUSINESS
CLERICAL
0002 - PINES B RECREATION
0006 - CULINARY ARTS VOCATION
0007 -
VOCATIONS/LOGISTICS/WAREHOUSE/M
AINT
0008 - CONSTRUCTION TRADES
0008A - VOCATIONAL SUPPORT
0009 - BASIC EDUCATION
0010 - WILLOWS A (CPP)
0013 - FORMER WEP/OAP (VACANT)
0014 - GATE HOUSE/SECURITY
0015 - STORAGE
0016 - STORAGE
0017 - DORM/ADMIN/MED/DENT
0018 - GYMNASIUM
0025 - CAFETERIA
0007A - FLAMMABLE STORAGE SHED (10
ft x 10 ft) 0007B - SAND STORAGE SHED (20 ft x 26 ft) 0008B - CONSTRUCT TR STRG SHED (6 ft 8 in x 12 ft) 0018A - GYM STORAGE SHED (9 ft x 12 ft) 0019 - SEWER BUILDING (14 ft 8 in x 14 ft 8 in) 001A - MAINTENANCE STORAGE (18 ft 8 in x 20 ft) 0022 - GAZEBO 2 (12 ft x 15 ft 8 in) 0023 - EMERGENCY GENERATOR 2 (8 ft x 12 ft) 0024 - EMERGENCY GENERATOR (10 ft x 12 ft) 0028 - BUS STOP (4 ft x 12 ft)
Name GSF
14,475
21,750 24,850 22,613
12,180 1,480
11,500 6,550
11,545
2,800 1,700
57,100 9,520
13,000
Active
Active Active Active
Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active
Active Active
Active
Active Active
Active
Active
StatusType
Building
Building Building Building
Building Building Building Building Building Building Building Building Building Building Building Structure
Structure
Structure
Structure Structure
Structure
Structure Structure
Structure
Structure
Use Group Built Flrs Const
B
A-3 B B,S-2
B,F-1 B B B Business B S-2 S-2 R-2,B A-3 A-2 H
S-2
S-2
S-2 Utility/Misc.
S-2
U U
U
Utility/Misc.
Good
Good Fair Fair
Fair Poor Fair Fair Poor Good Fair Fair Poor Good Good Good
Good
Good
Good Good
Good
Good Good
Good
Good
ConditionAsset Number
0010400002
0010400003 0010400006 0010400007
0010400008 0010400020 0010400009 0010400010 0010400013 0010400014 0010400016 0010400017 0010400018 0010400021 0010408132 0010408142
0010408143
0010408141
0010408140 0010408128
0010400019
0010408131 0010408135
0010408136
0010408144
15 211,663
10 2,071
25 213,734
Buildings
Structures
Total
GSF
GSF
GSF
Summary
01/11/2016
Space Utilization By Function 00104 Grafton Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 206 Non Residents 31
237Total Students
(206)
(300)
(237)
DIFFERENCE
22,248
19,190
4,266
36,140
36,668
9,405
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (300) Non-Academic
24 -- Carpentry + 30 -- Culinary Arts + 24 -- Electrical + 20 -- Emergency Med Techn 24 -- Facilities Maint. and Const. + 24 -- Health Occupations + 0 -- Human Services Worker 30 -- Medical Assistant 13 -- Medical Office Support 24 -- Plumbing + 24 -- Security Services
Vocational Theory (150)
Dining (2 Servings) Food Preparation Food Storage
7,120 2,550 3,680
19,600 3,190
4,245 9,968
4,000 2,695 2,295 1,675 2,600 1,780 1,030
1,040 2,530
1,180
5,365 3,035 1,005
2,060 1,648 2,472
14,832 1,236
3,000 3,000
1,800 1,800 1,200
1,800
1,200
1,500
1,896 1,422
5,060
1,208 4,768 1,954
1,245 6,968
2,200
1,095
1,030
1,330
-130
-320
3,469 1,613
Vocations
13,892
17,478
5,139
01/11/2016
Space Utilization By Function 00104 Grafton Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 284.36 67,394 150,570
(237)
(237)
(237)
(237)
(0)
DIFFERENCE
211,663
0.71
TOTAL GSF
NET TO GROSS RATIO
10,765
1,445
4,740
14,813
3,220
4,770
12,499
33,055
Arts & Crafts Gymnasium Miscellaneous Recreation Multipurpose Room Pool Hall Recreation Office Recreation Storage Student Store Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
6.10
8,400 1,100
1,995
2,015
3,220
4,770
9,857 2,642
33,055
1,445
1,896 2,844
8,400 1,100
1,995
2,015
1,775
7,961 -202
33,055
RESIDENT
NON-RESIDENT
(206)
(31) 15
50 10,300
4,048
1,775
7,759
33,055
83,176
Net Square Footage By Building Date: 01/11/2016 Page: 1
Center: GRAFTON (00104) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
19,600
7,120
3,190
3,680
2,550
0017 - DORM/ADMIN/MED/DENT
0017 - DORM/ADMIN/MED/DENT
0017 - DORM/ADMIN/MED/DENT
0017 - DORM/ADMIN/MED/DENT
0017 - DORM/ADMIN/MED/DENT
Bldg Name Actual NSF Difference
19,600
7,120
3,190
3,680
2,550
Sub Total: 36,140
14,832
2,060
1,236
2,472
1,648
22,248
4,768
5,060
1,954
1,208
( 206
13,892 rooms; beds
Page: 2
Center: GRAFTON (00104) of 4
EDUCATION
Academic
Vocational Theory (150)
Carpentry
Electrical
Plumbing
Health Occupations
Culinary Arts
Facilities Maint. and Const.
Medical Assistant
Security Services
Non-Academic
Medical Office Support
Function Suggested
NSF
1,200
1,750
1,500 2,500
1,495
2,130
1,780
2,695
2,600
4,705
1,040
0009 - BASIC EDUCATION
0009 - BASIC EDUCATION
0009 - BASIC EDUCATION
0009 - BASIC EDUCATION
0006 - CULINARY ARTS VOCATION
0008 - CONSTRUCTION TRADES
0016 - STORAGE
0008 - CONSTRUCTION TRADES
0015 - STORAGE
0008 - CONSTRUCTION TRADES
0008 - CONSTRUCTION TRADES
0015 - STORAGE
0001 - PINES A HEALTH & BUSINESS CLERICAL
0006 - CULINARY ARTS VOCATION
0008 - CONSTRUCTION TRADES
0001 - PINES A HEALTH & BUSINESS CLERICAL
0002 - PINES B RECREATION
0001 - PINES A HEALTH & BUSINESS CLERICAL
0002 - PINES B RECREATION
0010 - WILLOWS A (CPP)
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0009 - BASIC EDUCATION
0001 - PINES A HEALTH & BUSINESS CLERICAL
0009 - BASIC EDUCATION
0001 - PINES A HEALTH & BUSINESS CLERICAL
0009 - BASIC EDUCATION
0009 - BASIC EDUCATION
0001 - PINES A HEALTH & BUSINESS CLERICAL
Bldg Name Actual NSF Difference
4,245
1,180
4,000
2,295
2,530
1,780
2,695
2,600
9,968
1,040
3,000
1,500
1,800
1,200
1,200
1,800
1,800
3,000
1,245
-320
2,200
1,095
1,330
-130
6,968
( 300 )
Page: 3
Center: GRAFTON (00104) of 4
EDUCATION
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Human Services Worker
Emergency Med Techn
Dining (2 Servings)
Food Preparation
Food Storage
Multipurpose Room
Arts & Crafts
Gymnasium
Weight Room
Student Store
Miscellaneous Recreation
Pool Hall
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
1,030
1,675
5,365
3,035
1,005
8,400
2,015
1,100
1,995
3,220
0001 - PINES A HEALTH & BUSINESS CLERICAL
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0025 - CAFETERIA
0025 - CAFETERIA
0025 - CAFETERIA
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0018 - GYMNASIUM
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0002 - PINES B RECREATION
0017 - DORM/ADMIN/MED/DENT
Bldg Name Actual NSF Difference
1,030
1,675
5,365
3,035
1,005
8,400
2,015
1,100
1,995
3,220
Sub Total:
Sub Total:
Sub Total:
Sub Total:
36,668
9,405
14,813
3,220
1,896
1,422
1,445
19,190
4,266
10,765
1,445
1,030
3,469
1,613
1,775
17,478
5,139
4,048
1,775
Page: 4
Center: GRAFTON (00104) of 4
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
4,000
2,642
8,232 1,150
1,100 6,410 2,920 4,000
13,750 4,875
0017 - DORM/ADMIN/MED/DENT
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0014 - GATE HOUSE/SECURITY
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0001 - PINES A HEALTH & BUSINESS CLERICAL
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0015 - STORAGE
0008A - VOCATIONAL SUPPORT
0013 - FORMER WEP/OAP (VACANT)
0001 - PINES A HEALTH & BUSINESS CLERICAL
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0006 - CULINARY ARTS VOCATION
0002 - PINES B RECREATION
Bldg Name Actual NSF Difference
4,770
2,642
9,857
33,055
Sub Total:
Sub Total:
Sub Total:
4,770
12,499
33,055
4,740
2,844
1,896
4,740
4,740
-202
7,961
33,055
7,759
33,055
Environmental Management Report
Center: GRAFTON (00104) Page: 1 Date: 01/11/2016 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
No Building 7
Organic solvent (55 gallons) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
All buildings have non-permitted gas boilers Minor Source - Exempt
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
Near building # 7
Near building #7
Near building #7
20,000
20,000
20,000
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Services, Inc.
Yes Organic solvent (55 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service Information not provided
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
Yes No
07/21/2000 Friable/Non-Friable Dan Block
No No N/A No No
CO, Ozone
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Abandoned
Abandoned
Abandoned
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 01/11/2016Center : Grafton (00104) Page: 1 of 2
Floor Finishes Floor Finishes Heating Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Floor Finishes
Floor Finishes
Floor Finishes Water Plumbing Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Mastic beneath 9x9 tile 9x9 floor tile Pipe insulation, air-cell 9x9 floor tile Mastic beneath 9x9 tile
12x12 floor tile Mastic beneath 9x9 tile 9x9 floor tile (covered) Mastic beneath 9x9 tile 9x9 Floor tile, grey/white Mastic beneah 12x12 tile 9x9 Floor tile (covered) Mastic beneath 9x9 tile
Mastic beneath 9x9 tile 9x9 floor tile, green
12x12 floor tile (covered)
Mastic beneath 9x9 tile Pipe insulation 9x9 floor tile (covered)
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
2nd floor 1st floor Sub-basement 2nd floor 1st floor
1st floor hallway 2nd fl. stairwell 2nd fl., north hall 2nd fl., north hall 2nd fl. stairwell 1st floor hallway Health services area Health services area
Basement storage rm.
Basement storage rm.
1st floor restroom
Ground/1st floors Plumbing chases Ground/1st floors
Building :
Building :
Building :
Building :
Building :
0001 - PINES A HEALTH & BUSINESS CLERICAL
0002 - PINES B RECREATION
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0008 - CONSTRUCTION TRADES
0009 - BASIC EDUCATION
Asbestos-Containing Materials Inventory
Page: 2 of 2
Floor Finishes Floor Finishes Floor Finishes Floor Finishes Heating Heating
Heating
Heating
Bldg System
Bldg System
Bldg System
Mastic beneath 9x9 tile 9x9 floor tile 9x9 floor tile Mastic beneath 9x9 tile Pipe insulation Pipe insulation
Pipe insulation
Pipe insulation
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Location
Unit
Unit
Unit
Quantity
Quantity
Quantity
Stairwell, east wing Stairwell, east wing Boiler room Boiler room 1st floor ceilings Basement crawlspace
Sub-basement tunnel
Steam tunnels
Building :
Building :
Building :
0010 - WILLOWS A (CPP)
0013 - FORMER WEP/OAP (VACANT)
SITE
Radon
Page: 1 of 1
0001 - PINES A HEALTH & BUSINESS CLERICAL
0002 - PINES B RECREATION
0006 - CULINARY ARTS VOCATION
0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
0008 - CONSTRUCTION TRADES
0008A - VOCATIONAL SUPPORT
0009 - BASIC EDUCATION
0010 - WILLOWS A (CPP)
0013 - FORMER WEP/OAP (VACANT)
0014 - GATE HOUSE/SECURITY
0015 - STORAGE
0016 - STORAGE
0017 - DORM/ADMIN/MED/DENT
0018 - GYMNASIUM
0025 - CAFETERIA
Bldg Name
03/18/1991
08/18/1992
03/18/1991
03/18/1991
03/18/1991
07/09/2007
03/18/1991
07/09/2007
Test Date
N/A
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
N/A
N/A
N/A
Yes
No
No
Radon Testing
< 4 pCi
4 - 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Aerial View of Center
Page: 1 Date: 01/11/2016 of 5
Comments:
Paving Type for Roads & Parking
Paved areas are deteriorated and need repaving. Approximately 1/2 of the sidewalks are deteriorated, cracking and becoming trip hazards. This is due to the extreme winter weather that the Center has experienced recently.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. The chain link fencing encompasses most of the site and separates deteriorated Buildings 3, 4, and 5 that are not used by the center. The main entry area near Building 14 is not fenced.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterGrafton Water DistrictPublic Water Authority
None 0None
Water supply to the center, from the Town of Grafton, is provided by one dead end 10" line. Water distribution on the site is with a looped system.
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 0 5None Municipal
Number of Deficiencies = 3
Number of Deficiencies = 2
Number of Deficiencies = 1SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures15 10Terraced
Surrounding
Outdoor Recreation
Forest, Light Commercial
Field, Soft/Baseball RR Tracks, Smoke Stacks
Most Of The Site Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Fair
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 01/11/2016 of 5
Comments:
Sewage Treatment Flow
Sewage flows through an 8" PVC sewer line by gravity to a lift station near Building 8. From the lift station, it is pumped through a force main to a siphon structure, owned by the Town of Grafton, located east of Building 4.
Sewage flows from this point under the railroad tracks to a 15" diameter gravity sewer off site. Reported by Green International Affiliates, Inc., May 14, 1998, and confirmed by successive facility surveys.
Utility
Publicly Owned Treatment Works
Center
Gravity and Lift Stations
Maintenance ResponsibilityOwnership
Eversource/Sprague
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 3
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Lessor Yes GoodCenter
Comments: Storm water system is comprised of catch basins, underground drain line, surface drainage, and concrete gutters.
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
6. Central Plant: None
Page: 3 Date: 01/11/2016 of 5
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Direct Energy
Overhead primary power enters the site from a pole located south of Building 7 and is fed underground to the switchgear located in the basement of Building 7. Primary power is distributed underground from this switchgear to a 2300-208/120V, 112.5 kVA transformer in Building 7 electrical room, and to additional pad-mounted transformers located at Buildings 1, 2, 6, 8 and 17 (300 kVA, 225 kVA, 500 kVA, 75 kVA, and 500 kVA). The overhead 2300V power is provided to Building 13 (75 kVA). Building 6 provides 120/208V power to Buildings 10 and 14 and 480/277V power to Building 9. Building 25 has a service entrance from an overhead 2300V primary line (originated at Building 7) to a 300 kVA exterior located pad-mounted transformer. A 200 kW standby diesel generator (by Kohler ) with a 400A manual transfer switch is utilized as backup power for the essential loads in Building 17. A 24 kW standby diesel generator (by Kohler) with a 100A automatic transfer switch is utilized for the sewage pump station located northwest of Building 8. A single meter located on Pine Street provides metering for the entire center. Building 17 has a multimeter connected to the internet and providing remote monitoring capabilities. The transformer in Building 8 contains PCB.
Pad Center
Center Center
Yes
2,300V, 3-Phase, 3 Wire
208/120V, 3-Phase, 4 WireUnderground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
7. Electrical (Service)
Transformer Maint Resp
Center
System Capacity Adequate System Condition
Yes Fair
Generator
Diesel
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Pole
Photocell, Time Clock Time Clock Photocell, Time Clock Photocell, Time Clock Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: Pole-mounted site lighting belongs to the center and is controlled by photocells and time clocks. Perimeter site lighting (15' poles with shoe type HID light fixtures) starting at the back of Building 18 feeds from Buildings 2, 18, 25 and 13, and is controlled by time clocks and photocells at the respective buildings. Pole-mounted lighting (15' high pole with globes), routed along the center entrance line starting at Building 14, is feed from Building 1 and controlled by a time clock. Road lighting routed along Buildings 15 and 16 toward the ball field is feed from Building 15 and controlled by a time clock.
ATS MTS
Yes Yes
Metering Master
Page: 4 Date: 01/11/2016 of 5
Comments:
Telephone Company
On-site Line Owner
Demarcation point for the analog telephone lines (200-pair cable) is located in the ground level of vacant Building 13. Three emergency "land lines" utilized by the center are provided by Verizon. Five T1 lines (48-Strand) are provided by AT&T through the IT closet in Building 13 (no termination) to the campus central data closet located in the wellness center in Building 17. Buildings on the center are connected to the server equipment room by fiber utilizing VoIP for both data and telephone communications. The system hardware is manufactured by Cisco. Local fire alarm panels provide detection and notification within respective buildings. The fire alarm inspection for all buildings with the exception of Building 17 was done January 2012 by American Alarm and Communication Inc. (phone: (781) 641-2000). Motion sensors and local security panels provide detection in the respective buildings and are connected to the exterior located sirens. Door hardware with door alarms are provided at the dormitory wing exits. Cable TV terminates in Building 13, than is routed to the data closet in Building 17, where it is distributed to Dormitory Building 17, Pines B Recreation Building 2 and Cafeteria Building 25.
Verizon
Maint. Responsibility
Center Center
Motion detectors are provided at selected locations.
Unknown
Unknown
Unknown
Lessor
Lessor
Lessor
Abandoned
Abandoned
Abandoned
Underground, Non-regulated
Underground, Non-regulated
Underground, Non-regulated
Near building # 7
Near building #7
Near building #7
All underground storage tanks have been closed-in-place in accordance with State and Federal closure guidelines.
No
No
No
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
STORAGE TANKS
Comments:
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
20000
20000
20000
9. Electrical (Communication/Alarm/Security)
Heating
Heating
Heating
Purpose
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
FairYes
Number of Deficiencies = 7
Fire Alarm Security
Page: 5 Date: 01/11/2016 of 5
ACCESSIBILITY
Yes
Comments:
UnknownYesYes
The complex was a former Massachusetts State Mental Hospital that was established in 1905.
Yes
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low MediumHigh LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 2
Accessible Parking: Accessible Slope:
No
Curb Cuts:
Yes
Ramps:
NoNo
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
There is some road and hillside erosion. There are some drainage problems as well. The site is attractive with large trees, landscape plantings and wooded surroundings. A few trees are leaning excessively, one towards the new gym, and should be monitored or removed.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
NO
NO
NO
Yes
Yes
Yes
Yes
25 %
Building Descriptions and Structures
BUILDING 1 - PINES A HEALTH & BUSINESS CLERICAL
Building Descriptions
Page: 1 of 78
Building: 0001 - PINES A HEALTH & BUSINESS CLERICAL
BUILDING ENVELOPE
Foundation RoofBuilding
Stone Masonry Loadbearing Masonry Wood
The lower level floor is concrete slab on grade.
Brick Masonry Stone Masonry
Comments: The wall system is comprised of stone at the lower floor and brick on the upper levels.
Wall Roof None None
Metal Unit with Glazing - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 14,475 10,164 3 Leased 1905 Contributing
Comments: There are no audio/visual devices in the basement level toilet room. The elevator has been taken out of commission by the State of Massachusetts Elevator Inspector.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
No
No
Yes
Yes
Yes
Yes
No
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 2
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Type Area Served
Asphalt Shingles Surface Run-off 2001 6 Hip Entire Building
3. Roof
Entire Building
Area Served
Comments:
Page: 2 of 78
Building: 0001 - PINES A HEALTH & BUSINESS CLERICAL
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile Wood
Brick Drywall Plaster Stone
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs (exterior and interior) Elevator
Double Hung - Vinyl Frame; Double Glazing; Fixed - Metal Frame; Double Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Number of Deficiencies = 1
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 3
Interior Walls2. Number of Deficiencies = 1
3. Number of Deficiencies = 1
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The boiler was built by Burnham (1673 MBH input) and is furnished with a Taco circulator (#121A3N1, 1/3 HP) and two Taco hot water pumps (3 HP) that circulate hot water to the 32 fan coil units.
Additional heating is provided in the two stairwells and women's restroom by hot water convecters. A Carrier air handling unit (#39MN06B) delivers tempered OA to the fan coils.
These units serve stairwells and restrooms.
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Fan Coil
Baseboard Convector
Two-Pipe
Two-Pipe
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Common Area
Ceilings
Page: 3 of 78
Building: 0001 - PINES A HEALTH & BUSINESS CLERICAL
Mechanical Restroom
The water heater (Bradford White #LD50S33C110, 50 gallon, 11 kW) is located in the basement mechanical equipment room.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Service Sink Shower/Bathtub Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: The former wet fire standpipe and sprinkler systems are abandoned in place.
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Chiller Fan Coil Two-Pipe Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
An air-cooled chiller (Carrier #30RAN040, 37 ton, scroll, R-22, mfd. 10/2004) produces cooling for the building. Two Taco pumps (#FI1509E2) circulate chilled water to the 32 fan coil units. An air handling unit (Carrier #39MN06B, mfd. 3/2004) located in the basement mechanical equipment room delivers tempered OA to the larger rooms.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
3. Air Conditioning
Page: 4 of 78
Building: 0001 - PINES A HEALTH & BUSINESS CLERICAL
Comments: Located in the basement electrical room, there is a 2300V, 200A main metal enclosed disconnect switch (5 kV, fuse rating 100E) fed from Building 7, a 300 kVA mid voltage dry type step down transformer (5.11%) and a 1200A switchboard with a 1200A fused main switch. All distribution equipment is manufactured by GE and is dated 03/2004. The main switchboard has one 125A and five 200A fused switches and one 100A spare switch, and serves a 600A (from a 200A switch) motor control center MCC located in the mechanical room, a chiller (from a 200A switch), three 225A MLO panelboards (from (3) 200A switches located one at each floor) and one 100A MLO panel in the basement (from a 125A switch). The elevator (5 HP) is also provided.
FIRE ALARM
Comments: The fire alarm panel is a Notifier NFS-640, located at the first floor vestibule.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. T8-fluorescent lighting is utilized at the first and second floors of the building, renovated at 2006. T12-fluorescent lighting is utilized only in the vacant areas at the basement level.
Comments: Selected fluorescent light fixtures with battery backup are utilized in the corridors and classrooms.
High Intensity Discharge (HID) Incandescent Lights Comments: Building-mounted and pole-mounted site lighting is controlled by a photocell and a time clock.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Classrooms
Vacant
N/A
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/208V, 3-Phase, 4 Wire Switchboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 2
LIGHTING
Page: 5 of 78
Building: 0001 - PINES A HEALTH & BUSINESS CLERICAL
Comments: The building is connected to the center's LAN system. Motion detectors are connected to a local security alarm system reporting to a key pad security panel (by Gemini). A siren for the security system is mounted on the building exterior, and an annunciator panel is provided in the first floor vestibule. The data room has one 6500 Cisco Catalyst switch (WAN) and one 1700 Cisco Catalyst switch (Ethernet).
Connected to Main System Motion Detector None TV with VCR
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Chiller has failed. All HVAC controls are disconnected and operated manually and inefficiently.
COMMUNICATION Number of Deficiencies = 1
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Poor Electrical: Good
This building has been recommended for renovation in the Long Range Development Plan after Entry canopy needs to be added to protect from natural elements, especially in the winter.
RENOVATION RECOMMENDATION
Type Location None None
There are no CO detectors in this building.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 2 - PINES B RECREATION
Page: 6 of 78
Building: 0002 - PINES B RECREATION
BUILDING ENVELOPE
Foundation RoofBuilding
Stone Masonry Loadbearing Masonry, Steel
Wood
Brick Masonry Stone Masonry
Wall Roof None Batt
Metal Unit - Metal Frame Storefront - Storefront Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3 21,750 12,163 3 Leased 1905 Contributing
Comments: The elevator has been taken out of commission by the State of Massachusetts elevator inspector.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 2
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Asphalt Shingles Surface Run-off 2000 5 Hip Entire Building
Number of Deficiencies = 13. Roof
Entire Building
Page: 7 of 78
Building: 0002 - PINES B RECREATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Earth Rubber Tile Terrazzo Vinyl Tile Wood
Ceramic Tile Drywall Paneling Plaster
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs (exterior and interior) Elevator Comments: The elevator has been taken out of commission by the State of Massachusetts Elevator Inspector.
Double Hung - Wood Frame; Double Glazing; Fixed - N/A Frame; Glass Block Glazing;
Acoustical Tile Exposed Structure Plaster
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 2
Interior Walls2.
3.
Interior Doors4.
Page: 8 of 78
Building: 0002 - PINES B RECREATION
Mechanical
Mechanical
Restroom
Janitor's Closet
Comments: The two in-line fans are located in the attic.
Ventilation Area Served
Chiller
Chiller
Fan Coil
Single Duct
Two-Pipe
Two-Pipe
Electric
Electric
Natural
Mechanical
None
None
Recreation Area
Recreation Area
Exhaust Ventilation
Chilled water is produced by a McQuay air-cooler chiller (#AGZ055AS42, 50 ton) and circulated to 35 fan coil units (Carrier) throughout the building by two pumps (Taco, 5 HP).
Two air handlers (McQuay #CAH006FDAC) in the attic serve 100% outdoor air to the first and second floor spaces. This air is cooled by the chilled water system and each AHU is equipped with a circulating pump (Taco #1611C3N1, 1/4 HP).
Comments:
Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heat is produced by a Weil-McLain unit (#788, 1419 MBH output) and circulated through the boiler by two pumps (Taco, 1-1/2 HP) and circulated to 35 fan coil units (Carrier) throughout the building by two pumps (Taco, 5 HP).
Two air handlers (McQuay #CAH006FDAC) in the attic serve 100% outdoor air to the first and second floor spaces. This air is heated by the hot water system and each AHU is equipped with a circulating pump (Taco #1611C3N1, 1/4 HP).
Additional heating is provided by hot water unit heaters by Rosemex (basement, #H58 and attic, #H80) and convectors (restrooms and basement).
There is an electric unit heater in the basement electrical room.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Electric Resistance
Fan Coil
Single Duct
Unit Heater
Unit Heater
Two-Pipe
Two-Pipe
Two-Pipe
None
Electric
Electric
Electric
Electric
Natural
Mechanical
Natural
Natural
None
None
None
None
Entire Building
Entire Building
Entire Building
Equipment Room
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Page: 9 of 78
Building: 0002 - PINES B RECREATION
The heater was built by Rheem (#ES8518G, 85 gallon, 18kW).Comments:
Comments:
Cast Iron None None
The service sink in the arts and crafts room is furnished with a solid waste interceptor.
Electric Water Cooler Hose Bibb Lavatory Mop Sink Service Sink Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: The former wet fire standpipe and sprinkler systems are abandoned in place.
Comments: Located in the basement electrical room, there is a 2300V, 200A main metal enclosed disconnect switch (5 kV, 200A fuse) fed from Building 7, a 225 kVA mid voltage, dry type, step down transformer (5.33%) and an 800A two-section switchboard (65 kA) with an 800A fused main switch. All distribution equipment is manufactured by GE and is dated 12/2000. The main switchboard serves a chiller (from a 225A CB), Gym Building 18 (from a 300A CB), an elevator (from a 150A CB), a water heater (from 70A CB) and two 225A/150 MCB panelboards (from (3) 150A CB) at the first floor and one panel in the basement. The switchboard has one 100A spare CB. Two 125A MLO panels serving the second floor are fed from the first floor panels. A 20 HP hydraulic elevator is also provided.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: Building-mounted site lighting is controlled by a time clock and a roof-mounted photocell through the lighting contactor located in the electrical room.
Main Disconnect Switch 120/208V, 3-Phase, 4 Wire Switchboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 10 of 78
Building: 0002 - PINES B RECREATION
FIRE ALARM
Comments: The fire alarm panel (Cerberus Pyrotronics MXL-IQ by Siemens) and voice and tone alarm emergency system (Cerberus Pyrotronics VoiceCom by Siemens) are located in the main electrical room. The panel also serves fire alarm devices and a annunciator panel in Building 18.
Comments: The building is connected to the center's LAN system. Motion detectors are connected to a local security alarm system reporting to a key pad security panel (by Gemini). A siren for the security system is mounted on the building exterior. Speakers are also provided and currently are not in use.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Motion Detector Not Connected to Main System
Local Cable Company
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. Pendant light fixtures and cove lighting are provided in the second floor multi-purpose room.
Comments: Selected cove light fixtures at the second floor weight room are also provided with emergency ballasts.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Study Room
Recreation
Recreation
Storage/Warehouse-Active
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Emergency Exit
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Type Location None None
There are no CO detectors in this building. Detectors are required by DOL Directive Information Notice 12- 27 and NFPA 720, 2012.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
Page: 11 of 78
Building: 0002 - PINES B RECREATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
All exhaust fans are inoperable. Electronic HVAC controls have been abandoned. Two air handlers in the attic are inoperable due to freeze damage.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Poor Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 6 - CULINARY ARTS VOCATION
Page: 12 of 78
Building: 0006 - CULINARY ARTS VOCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete, Stone Masonry Loadbearing Masonry Wood
Brick Masonry
Wall Roof None Perlite, Blown
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B 24,850 16,845 2 Leased 1905 Contributing
Comments: Audio/visual devices are provided through the occupied building portion, which houses the culinary arts program. There is a ramp at the former queue line.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
The gutters and downspouts are extremely deteriorated or missing.
Drainage Year Life
Type Area Served
Slate
EPDM with Ballast
Gutters and Downspouts
Interior Roof Drains
Hip
Flat
Kitchen and Dining
Storage and Queue
Comments:
3. Roof
Page: 13 of 78
Building: 0006 - CULINARY ARTS VOCATION
INTERIOR FINISH
Carpet Concrete Quarry Tile Rubber Vinyl Tile
Brick Drywall Fiberglass Reinforced Plastic Glazed Block Plaster Wood Panel
Metal Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs (exterior and interior) Elevator Metal Ladder Comments: There is a vertical ladder to the attic mechanical equipment. The elevator is not in operation.
Metal Unit - Metal Frame
Double Hung - Wood Frame; Single Glazing; Sliding - Aluminum Frame; Single Glazing;
Acoustical Tile Plaster
Number of Deficiencies = 1
Number of Deficiencies = 1
Exterior Doors5.
Windows6. Number of Deficiencies = 2
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two Weil-McLain gas-fired boilers (2713 MBH each) provide hot water for unit heaters. Three in-line pumps circulate the water throughout the building.
These units serve culinary arts spaces.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Electric Resistance
Unit Heater
Baseboard Convector
Two-Pipe
None
Electric
Electric
Natural
Natural
None
None
Entire Building
Classrooms and Offices
Page: 14 of 78
Building: 0006 - CULINARY ARTS VOCATION
Mechanical
Mechanical
Mechanical
Restroom
Kitchen
Dining Hall
Comments:
Comments:
The kitchen hoods have associated utility set type exhaust fans located in the attic.
The dining hall is ventilated by an in-line exhaust fan located in the attic.
The heater was built by Raypack. A circulator (Taco, 1/6 HP) pumps water to two storage tanks (Rudd #RST1204, 115 gallon each). There is also an electric water heater (Rheem #GE50MBA, 50 gallon,
4.5 kW, built 01/03).
Comments:
Cast Iron/PVC/Copper Outdoor None
Fixed Emergency Eyewash Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired Building Water Softener Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Cooled)
Fan Coil
Window Unit
Refrigerant
None
Electric
Electric
Natural
Mechanical
None
None
Common Area
Dining Hall
PLUMBING
Exhaust Ventilation
The split system serves the banquet room and the condensing unit (Ducane #AC10B60A, 5 ton) is on the roof.
Comments:
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 15 of 78
Building: 0006 - CULINARY ARTS VOCATION
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: This building is supplied by a 2300V feeder from Building 7. A 500 kVA transformer located in the basement steps voltage down to 208/120V. A 1600A main switchboard with a 1600A main circuit breaker is located in the basement electrical room. Building 9 is fed from a 200A CB at the distribution switchboard) through a 150 kVA step-up transformer, which steps the 208V power to 480V for transmission between the buildings. Buildings 10 (from 150A CB at the distribution switchboard) and 14 (from 100A CB at panel B1 in the basement electrical room) are served 208/120V power directly from this building.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. The spaces related to the former kitchen/dining area are currently vacant and lighting in most of these spaces is disconnected. Lighting levels for these spaces (at the interior lighting table starting from the dining/lunch room until the end of the table) are left unchanged from the previous survey.
High Intensity Discharge (HID) Comments: Building-mounted site lighting is controlled by a time clock.
T12 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
Incandescent
T12 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
Incandescent
Offices
Equipment Rooms (Elec/Mech)
Equipment Rooms (Elec/Mech)
Toilets
Dining/Lunch Rooms
Dining/Lunch Rooms
Food Preparation
Storage Rooms
Storage/Warehouse-Active
Vacant
N/A
Area Recommended Recorded Light Type
Main Circuit Breaker 120/208V, 3-Phase, 4 Wire Switchboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Location UL300 Compliance Status Kitchen Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 16 of 78
Building: 0006 - CULINARY ARTS VOCATION
FIRE ALARM
Comments: The fire alarm panel is a Silent Knight SK-5208 (06/2012) located in the culinary arts dining room. The panel is controllserves fire alarm devices only in the occupied area and in the basement utility rooms (the electrical room and the mechanical room).
Comments: The building is connected to the center's LAN system. Motion detectors are connected to a local security alarm system.
Audible Alarm Control/Annunciator Panel Exterior Audio/Visual Device Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Motion Detector None TV with VCR
Telephone Security Public Address Television
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Building 6 is proposed to be not included in the revised lease agreement with the state of Mass.
Building finishes are worn and the basement gets flooded. It has minimal operable HVAC. Lighting is poor, and ductwork is past its useful life. The building also smells from undetermined sources and the attic has leaking exhaust vented into it. Windows are at the end of their useful life. All secondary electrical panels are old and deteriorated. The main distribution equipment for the building is fairly new and dated year 1995.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesNo
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Poor Mechanical: Poor Electrical: Fair
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 7 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
Page: 17 of 78
Building: 0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Stone Masonry
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B,S-2 22,613 17,758 2 Leased 1905 Contributing
Comments: The building has entrances on the upper and lower levels that are at grade and therefore contains no elevators or ramps. The third level of this building is not used, is inaccessible, and has about 12" of blown-in insulation on the floor. The lower level is occupied by facility maintenance. The existing fire alarm system is deteriorated and not operational.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
N/A
Yes
Yes
No
N/A
Yes
No
N/A
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2.
Page: 18 of 78
Building: 0007 - VOCATIONS/LOGISTICS/WAREHOUSE/MAINT
Wall Roof Unknown Blown-In
Comments: The attic floor of this building is vacant. The floor has been covered by 6 to 9 inches of blown in cellulose insulation.
Metal Overhead - Metal Frame Metal Unit - Metal Frame Wood Unit - Wood Frame
Double Hung - Wood Frame; Double Glazing;
Insulation4.
Exterior Doors5. Number of Deficiencies = 2
Windows6.
Material
The built-up roof over the boiler room is inaccessible due to the deteriorated condition of that portion of the building.
Drainage Year Life
Type Area Served
Asphalt Shingles
EPDM
Built-up Roofing
Single Ply
Gutters and Downspouts
Interior Roof Drains
Interior Roof Drains
Interior Roof Drains
Hip
Flat
Flat
Flat
Classrooms, Offices, &
Storage
Shop Area
Mechanical Room
Storage
3. Roof
Page: 19 of 78
Building: 0007 -…
This is the start of the file's text. The full file is on GovTribe.