ST LOUIS
Job Corps Center St. Louis, MO
Facility Planning Report Volume II
Supporting Data
Final April 2017
Department of Labor/ Office of Job Corps
ST LOUIS
Job Corps Center St. Louis, MO
Facility Planning Report Volume II
Supporting Data
Final April 2017
Recreation Building 102
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The facility survey for St. Louis Job Corps Center (St. Louis JCC) was conducted 17 – 25 October 2016. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal; and active warranties
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
ST LOUIS
JOB CORPS CENTER
ST LOUIS, MISSOURI
ST LOUIS JCC
10 MI50
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00703 ST LOUIS 04/04/2017
1Page: of Date:
0101 - WELCOME CENTER
0102 - RECREATION CENTER
0103 - CAFETERIA/CULINARY ARTS
0104 - DORMITORY A FEMALE DORM
0105 - DORMITORY B MALE DORM
0106 - DORMITORY C MALE DORM
0208C - SECOND WELDING SHOP
0222 - MEDICAL/DENTAL
0223A - VACANT
0223B - EDUCATION BUILDING
0225A - BUNKER STORAGE A
0225B - BUNKER STORAGE B
0228 - GYMNASIUM
0232A-H - VOC TRAINING SHOPS
0234 - ADMIN/WAREHOUSE
0234A - EDUCATION TRAILER
0235 - ORIENTATION BUILDING
0244 - WELDING/BRICKLAYER SHOP
0300 - OUTREACH & ADMISSIONS
0302 - LINDELL VOC TRAINING
0307 - CARPENTRY STORAGE
0232 - FLAMMABLE STORAGE (30Ft x 20Ft) 0233 - GROUNDS EQUIPMENT (16Ft x 12Ft)
0234B - MISCELLANEOUS STORAGE
(40Ft x 20Ft)
0234C - MISCELLANEOUS STORAGE
(16Ft x 12Ft) 0234D - VEHICLE STORAGE (20Ft x 20Ft) 0244A - MASONRY STORAGE (20Ft x 14Ft) 0305 - ORIENTATION GAZEBO (12Ft
DIAMETER)
0311 - CARPORT (30Ft x 20Ft) 0315 - CARPORT (30Ft x 20Ft) 0316 - GREENHOUSE (48Ft x 24Ft) 0321 - PICNIC PAVILION (20Ft x 20Ft) 0322 - CONTAINER (40Ft x 8Ft) 0323 - CONTAINER (40Ft x 8Ft)
Name GSF
1,324 12,489 14,827 31,140 30,856 25,658 2,407
12,940 72,320 17,780 2,687 5,036
12,057 23,396 47,814
1,699 7,290 1,750
18,046 1,440
1,152
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active
Active
Active Active
Active
Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure
Structure
Structure
Structure
Structure Structure
Structure
Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business Assembly Assembly Residential Residential Residential Factory/Ind.
Business Residential Business Storage Storage Assembly Business Mixed Use Business Business Factory/Ind.
Business Business Storage Storage
Storage
Storage
Storage
Storage Storage
Assembly
Assembly Utility/Misc.
Utility/Misc.
Assembly Storage Storage
Good Good Good Fair
Good Good Good Fair Poor Fair
Good Good Good Good Fair
Good Good Fair
Good Good Good Good
Good
Fair
Fair
Good Good
Good
Good Good Good Good Good Good
ConditionAsset Number
0070308055 0070308056 0070308066 0070308075 0070308076 0070308077 0070300002 0070300003 0070300004 0070300005 0070308057 0070308058 0070300006 0070300008 0070300009 0070308054 0070300022 0070300011 0070300013 0070300019 0070308060 0070300018
0070300021
0070308063
0070308064
0070308080 0070308059
0070300025
0070308071 0070308073 0070308074 0070308081 0070308082 0070308083
21 343,641
13 5,976
34 349,617
Buildings
Structures
Total
GSF
GSF
GSF
Summary
04/04/2017
Space Utilization By Function 00703 St Louis Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 440 Non Residents 80
520Total Students
(440)
(520)
(520)
DIFFERENCE
42,240
38,990
9,360
60,513
57,814
11,731
Lounge Other Sleeping excl. SPD(116 rooms; 440 beds) Storage
Academic (520) Non-Academic
12 -- ACT (Off-Ctr) 20 -- Bricklayer + 40 -- Carpentry + 20 -- Cement Masonry + 30 -- Cert. Nursing Asst.
60 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 54 -- Material Handler 30 -- Office Administration 20 -- Painting + 30 -- Pharmacy Tech + 20 -- Plastering + 30 -- Security Officer 50 -- TCU Transportation 24 -- Welding +
Vocational Theory (258)
Dining (2 Servings) Food Preparation Food Storage
8,312 4,438
47,151
8,501 10,101
3,327 4,997 2,247 1,183 2,321 5,109
4,279 1,180 2,207 1,485 2,785 4,436
2,030
6,349 3,950 1,432
4,400 3,520
31,680 2,640
5,200 5,200
1,500 3,000 1,500 1,200 3,600 1,800 3,510 1,350 1,500 1,350 1,500
1,500 1,800
2,580
4,160 3,120 2,080
3,912
15,471 -2,028
3,301 4,901
1,827 1,997
-17
-1,279 3,309 -2,795
-439 2,779
-170
1,285 2,636
-550
2,189 -648
Vocations
18,273
18,824
2,371
04/04/2017
Space Utilization By Function 00703 St Louis Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 264.88 137,735 219,799
(520)
(520)
(520)
(520)
(0)
DIFFERENCE
343,641
0.64
TOTAL GSF
NET TO GROSS RATIO
23,200
3,145
10,400
17,524
3,246
7,711
17,010
44,250
Arts & Crafts Gymnasium Meeting Room Miscellaneous Recreation Multipurpose Room Recreation Office Recreation Room Recreation/Snack Bar Snack Bar Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
6.05
1,264 7,135
3,139
2,014 1,118
3,246
7,711
2,088 14,922
44,250
3,145
4,160 6,240
1,264 7,135
3,139
2,014 1,118
-2,689
-2,072 8,682
44,250
RESIDENT
NON-RESIDENT
(440)
(80) 15
50 22,000 1,200
-5,676
-2,689
6,610
44,250
82,064
Net Square Footage By Building Date: 04/04/2017 Page: 1
Center: ST LOUIS (00703) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Other
Function Suggested
NSF
16,643 13,861 16,647
2,549 2,554 3,209
1,376 1,685 1,377
0104 - DORMITORY A FEMALE DORM
0106 - DORMITORY C MALE DORM
0105 - DORMITORY B MALE DORM
0104 - DORMITORY A FEMALE DORM
0105 - DORMITORY B MALE DORM
0106 - DORMITORY C MALE DORM
0106 - DORMITORY C MALE DORM
0105 - DORMITORY B MALE DORM
0104 - DORMITORY A FEMALE DORM
0105 - DORMITORY B MALE DORM
0104 - DORMITORY A FEMALE DORM
0106 - DORMITORY C MALE DORM
Bldg Name Actual NSF Difference
47,151
8,312
4,438
Sub Total: 60,513
31,680
4,400
2,640
3,520
42,240
15,471
3,912
-2,028
( 440
18,273
40 rooms; 152 beds 36 rooms; 136 beds 40 rooms; 152 beds
Page: 2
Center: ST LOUIS (00703) of 5
EDUCATION
Academic
Vocational Theory (258)
Carpentry
Cement Masonry
Culinary Arts
Welding
Painting
Plastering
Bricklayer
Facilities Maint. and Const.
Non-Academic
Function Suggested
NSF
1,898 2,150 1,786 2,260
1,161
1,330 3,667
2,247
1,871
1,464 2,972
4,279
2,207
2,599
4,381
1,463
2,217
4,229
0223B - EDUCATION BUILDING
0223B - EDUCATION BUILDING
0223B - EDUCATION BUILDING
0223B - EDUCATION BUILDING
0223B - EDUCATION BUILDING
0244 - WELDING/BRICKLAYER SHOP
0232A-H - VOC TRAINING SHOPS
0208C - SECOND WELDING SHOP
0307 - CARPENTRY STORAGE
0232A-H - VOC TRAINING SHOPS
0232A-H - VOC TRAINING SHOPS
0103 - CAFETERIA/CULINARY ARTS
0223B - EDUCATION BUILDING
0208C - SECOND WELDING SHOP
0244 - WELDING/BRICKLAYER SHOP
0232A-H - VOC TRAINING SHOPS
0232A-H - VOC TRAINING SHOPS
0225B - BUNKER STORAGE B
0244 - WELDING/BRICKLAYER SHOP
0225B - BUNKER STORAGE B
0232A-H - VOC TRAINING SHOPS
0223B - EDUCATION BUILDING
0235 - ORIENTATION BUILDING
0223B - EDUCATION BUILDING
0302 - LINDELL VOC TRAINING
0300 - OUTREACH & ADMISSIONS
0232A-H - VOC TRAINING SHOPS
0302 - LINDELL VOC TRAINING
0234 - ADMIN/WAREHOUSE
Bldg Name Actual NSF Difference
8,501
2,030
4,997
2,247
2,321
4,436
4,279
2,207
3,327
5,109
10,101
5,200
2,580
3,000
1,500
3,600
1,800
1,500
1,500
1,500
1,800
5,200
3,301
-550
1,997
-1,279
2,636
2,779
1,827
3,309
4,901
( 520 )
Page: 3
Center: ST LOUIS (00703) of 5
EDUCATION
FOOD SERVICE
Security Officer
TCU Transportation
Material Handler
Pharmacy Tech
Office Administration
Cert. Nursing Asst.
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
1,485
2,785
1,180
1,183
5,183 1,166
3,950
1,432
0302 - LINDELL VOC TRAINING
0302 - LINDELL VOC TRAINING
0234 - ADMIN/WAREHOUSE
0302 - LINDELL VOC TRAINING
0223B - EDUCATION BUILDING
0302 - LINDELL VOC TRAINING
0103 - CAFETERIA/CULINARY ARTS
0302 - LINDELL VOC TRAINING
0103 - CAFETERIA/CULINARY ARTS
0103 - CAFETERIA/CULINARY ARTS
Bldg Name Actual NSF Difference
1,485
2,785
1,180
1,183
6,349
3,950
1,432
Sub Total:
Sub Total:
57,814
11,731
1,500
3,510
1,350
1,350
1,200
4,160
3,120
2,080
38,990
9,360
1,285
-2,795
-170
-439
-17
2,189
-648
( 520
18,824
2,371
Page: 4
Center: ST LOUIS (00703) of 5
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Multipurpose Room
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Miscellaneous Recreation
Recreation/Snack Bar
Recreation Room
Meeting Room
Recreation Office
Medical/Dental
Administration
Function Suggested
NSF
3,139
1,264
7,135
1,118
2,014
3,246
5,222
0102 - RECREATION CENTER
0102 - RECREATION CENTER
0102 - RECREATION CENTER
0228 - GYMNASIUM
0228 - GYMNASIUM
0228 - GYMNASIUM
0102 - RECREATION CENTER
0102 - RECREATION CENTER
0102 - RECREATION CENTER
0228 - GYMNASIUM
0102 - RECREATION CENTER
0222 - MEDICAL/DENTAL
0234A - EDUCATION TRAILER
0101 - WELCOME CENTER
0234 - ADMIN/WAREHOUSE
0302 - LINDELL VOC TRAINING
0225B - BUNKER STORAGE B
Bldg Name Actual NSF Difference
3,139
1,264
7,135
1,118
2,014
3,246
7,711
Sub Total:
Sub Total:
Sub Total:
17,524
3,246
7,711
3,145
10,400
23,200
3,145
10,400
-2,689
-5,676
-2,689
Page: 5
Center: ST LOUIS (00703) of 5
STORAGE/SUPPORT
VACANT
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
12,746 1,466
2,522 41,728
0234 - ADMIN/WAREHOUSE
0225B - BUNKER STORAGE B
0225A - BUNKER STORAGE A
0225A - BUNKER STORAGE A
0302 - LINDELL VOC TRAINING
0225B - BUNKER STORAGE B
0222 - MEDICAL/DENTAL
0223A - VACANT
Bldg Name Actual NSF Difference
14,922
2,088
44,250
Sub Total:
Sub Total:
17,010
44,250
6,240
4,160
10,400
8,682
-2,072
44,250
6,610
44,250
Environmental Management Report Center: ST LOUIS (00703)
Page: 1 Date: 04/04/2017 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 232 - Flammable Storage Building
Organic solvent (5 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Management, Inc.
Yes Organic Solvent (5 gals/month)
Conditionally Exempt Small Quantity Generator N/A Not Reported
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
02/08/1990 Friable/Non-Friable Ronald Moore 01/09/2001 Yes No N/A Yes Yes
CO, Ozone
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 04/04/2017Center : St Louis (00703) Page: 1 of 1
Heating Heating
Heating Floor Finishes Heating
Water Plumbing Floor Finishes Heating Floor Finishes
Plumbing (Bldg)
Heating Heating Floor Finishes Floor Finishes Roof Repair/Replacement Floor Finishes
Heating
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Tank insulation Pipe insulation
Pipe fitting insulation Spark Proof VFT (bottom layer) Pipe insulation
Tank Insulation Debris/Contaminated Soil Pipe Insulation Spark Proof VFT (bottom layer)
Tank Insulation
Pipe fitting insulation Pipe insulation Spark Proof VFT(Bottom Layer) Debris/contaminated soil Roof flashing 12x12 floor tile (covered)
Tank insulation
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Lin. Ft.
Ea.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Basement Basement
Crawlspace First Floor Crawlspace
Crawlspace Crawlspace Crawlspace Throughout Building
Mechanical Mezzanine
Crawlspace Crawlspace Throughout Crawlspace Throughout Cafeteria
Basement
48920
20850
20850
43650
Building :
Building :
Building :
Building :
Building :
Building :
0222 - MEDICAL/DENTAL
0223A - VACANT
0223B - EDUCATION BUILDING
0228 - GYMNASIUM
0234 - ADMIN/WAREHOUSE
0244 - WELDING/BRICKLAYER SHOP
Radon
Page: 1 of 2
0101 - WELCOME CENTER
0102 - RECREATION CENTER
0103 - CAFETERIA/CULINARY ARTS
0104 - DORMITORY A FEMALE DORM
0105 - DORMITORY B MALE DORM
0106 - DORMITORY C MALE DORM
0208C - SECOND WELDING SHOP
0222 - MEDICAL/DENTAL
0223A - VACANT
0223B - EDUCATION BUILDING
0225A - BUNKER STORAGE A
0225B - BUNKER STORAGE B
0228 - GYMNASIUM
0232A-H - VOC TRAINING SHOPS
0234 - ADMIN/WAREHOUSE
0234A - EDUCATION TRAILER
0235 - ORIENTATION BUILDING
0244 - WELDING/BRICKLAYER SHOP
0300 - OUTREACH & ADMISSIONS
0302 - LINDELL VOC TRAINING
0307 - CARPENTRY STORAGE
Bldg Name
05/14/1990
05/14/1990
08/12/1992
05/14/1990
05/14/1990
05/14/1990
05/14/1990
05/14/1990
05/14/1990
05/14/1990
Test Date
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Road between dormitories and Voc. Training Shops Building 232A-H
Page: 1 Date: 04/04/2017 of 5
Comments:
Paving Type for Roads & Parking
There is a combination of new and old sidewalks and roads. Sections of older and deteriorated roads and parking areas have not been repaired, but will be improved as part of a National Project.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. There is a wood fence at the transformer and a combination of chain link and decorative fencing around the perimeter of the site property line.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterCity of St. LouisPublic Water Authority
None 0None
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 2None Municipal
The Center is served by the St. Louis Municipal Fire Department, which is located approximately two miles from the Center and has a response time of approximately five minutes. Fire hydrants are located at adequate intervals to provide protection for the Center facilities.
Number of Deficiencies = 1
Number of Deficiencies = 1
Number of Deficiencies = 5
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures21 13Flat
Surrounding
Outdoor Recreation
Light Industrial, National Guard Station, Residential
North Perimeter
South and East Perimeter
West Perimeter
West Perimeter
Metal Decorative
Chain Link
Chain Link
Metal Decorative
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Fair
Number of Deficiencies = 1
Fencing
Other Features
Page: 2 Date: 04/04/2017 of 5
Sewage Treatment Flow
Utility
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Natural gas usage is measured at a master meter. Each building is provided with a sub-meter.
Laclead Gas Company
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Ameren/Union Electric Company
Service is brought from primary overhead lines along Strattford Avenue at the center northern boundary. Service enters the center at multiple points from Strattford Avenue with overhead lines running southward. The secondary service to older buildings on center are overhead except Admin/Warehouse Building 234. This building's overhead service has been recently converted to underground with a new pad-mounted transformer located in the back.
Recreation Center Building 102, Cafeteria/Culinary Arts Building 103, Dormitory Buildings 104, 105 & 106 also have underground services with a pad-mounted transformer located in the back of each respective building. All buildings services are 120/208V, 3 phase, 4 wire except Building 208C which has 480/277V, 3 phase, 4 wire service. The vast majority of buildings on center have their own meter. Buildings 102 and 228 share the same meter. Buildings 234, 234A and 235 also share a meter. Building 232 A-H has five overhead service drops with a separate meter for each of the five hard vocation bays.
Pole and Platform Utility
Utility Utility
No
4,160 Volts, 3-Phase
120/208V, 3-Ph, 4 Wire; 480/277V, 3-Ph, 4 WireOverhead & Underground
OverheadPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 3
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
6. Central Plant: None
Metering Individual
Page: 3 Date: 04/04/2017 of 5
Comments:
Telephone Company
On-site Line Owner
Southwestern Bell provides four T1 lines to the Center which terminate in the main telephone and data/communication room in Admin/Warehouse Building 234. Standard analog phone system is converted to digital voice over internet protocol (VoIP) by way of Cisco IP phones with RJ-45 Ethernet connectors and internet connection. The Job Corps Data Center (JCDC) provides and installs all network cabling, couplers and devices necessary for network connectivity to the VoIP phone and data/communication systems. Optical fiber cabling is used for inter-building connections. Three T1 lines are dedicated to VoIP, Internet and data/communication respectively, and the fourth T1 line is reserved as backup. The building fire alarm system center wide is stand alone. Some buildings have audio/visual fire alarm devices installed on the exterior. The security system includes interior and exterior CCTV cameras, black & white monitors, door alarm contacts, motion sensors and a metal detector. Satellite dish is provided in dormitory, recreation, education and administration buildings.
Southwestern Bell Telephone Co.
Maint. Responsibility
Utility Utility
Cameras, Black and White Monitors, Door Alarms, Motion Detectors
9. Electrical (Communication/Alarm/Security)
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Good
Comments: The site lighting system includes pole-mounted and building-mounted exterior lights. The pole-mounted lights are owned and maintained by the utility company. The center owns and maintains the building-mounted exterior lights.
Number of Deficiencies = 10
STORAGE TANKS: None
Fire Alarm Security
Page: 4 Date: 04/04/2017 of 5
ACCESSIBILITY
Yes
Comments:
UnknownYesYes
DOL entered into a Memorandum of Agreement with the Missouri State Preservation Officer SHPO to perform a HABS III level recordation, to publish historic narrative and to design an interpretive signage in order to keep alive the history of the Center and its contribution to the war effort during WWII and to commemorate its association with the birth of the Labor movement in the US. The recordation will include Buildings 208C, 222, 223A, 223B, 225A, 225B, 232A-H, 234, and 244.
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low LowMedium HighIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 6
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Yes
Yes
NO
NO
Yes
Yes
NO
NO
38 %
Page: 5 Date: 04/04/2017 of 5
SATELLITE SITE DESCRIPTION
Location:
Description:
Ownership Maintenance Responsibility
3860 Lindell BLVD., St. Louis, MO
The Lindell Site contains one building, Lindell VOC Training Building 302. This is a three story concrete and limestone building used for off site vocational training.
DOL Center
Rating The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Good Fair Poor
X
SATELLITE SITE CONDITION
Building Descriptions and Structures
BUILDING 101 - WELCOME CENTER
Building Descriptions
Page: 1 of 106
Building: 0101 - WELCOME CENTER
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Brick EIFS
Wall Roof Rigid Batt
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 1,324 732 1 Owned 2004 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
N/A
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
There is ponding on the corner of the roof above the mechanical room.
There is a gutter with downspouts over the entrance side of the metal roof.
Drainage Year Life
Remaining Type Area Served
EPDM
Metal
Gutters and Downspouts
Surface Run-off
Flat
Pyramid
Entire Building
Vestibule
Number of Deficiencies = 1
Comments:
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 106
Building: 0101 - WELCOME CENTER
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall
Metal Unit - Metal Frame
Mechanical Restroom
Comments: This rooftop fan (Penn #DX08B) also ventilates the janitor's closet.
Ventilation Area Served
VERTICAL CIRCULATION
Curb Cuts Comments: There are curb cuts in the sidewalks around the building.
Awning Units - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Single Glazing; Fixed - Metal Frame; Single Glazing;
Acoustical Tile Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The furnace was built by Carrier (#58MCA080, 74 MBH output, direct vent, 5/2004).Comments:
HVAC
Heat1.
Gas-Fired Furnace
Single Duct None Electric Natural None Entire Building
Ventilation2.
Ceilings
Page: 3 of 106
Building: 0101 - WELCOME CENTER
The 20 gallon electric water heater was built by State Industries, model CPE201CMSA.Comments:
None None None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electric Natural None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
All of the equipment was built by Carrier. The furnace (#58MCA080, 5/2004) has a DX coil (#CT4842C210, 6/2004) set on its discharge that is provided cooling by a condensing unit (#38BRG0423, 3-1/2 ton, 11/2003).
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 4 of 106
Building: 0101 - WELCOME CENTER
Comments: Overhead service is provided from a 25 kVA pole-mounted transformer on Starttford Avenue. Service enters the building through a 200A weatherproof main disconnect switch fused at 200A and located on the west exterior wall adjacent to the utility meter. This switch energizes a 250A main-lug-only panelboard located in the mechanical room.
FIRE ALARM
Comments: Various building security systems including magnetic door alarms and motion detectors and CCTV cameras are interconnected to the building for monitoring. The center's security surveillance system includes a color monitor, located in this building which monitors all exterior and interior cameras installed throughout the center, except cameras that are associated with the recreation center and cafeteria. A metal detector is also installed in the lobby of this building. A wireless radio system for staff communication is also provided.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Smoke Detector-Battery operated
Connected to Main System Cameras, Color Monitor Connected to Main System TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels during the 2013 Survey include natural light contribution.
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 5 of 106
Building: 0101 - WELCOME CENTER
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The roof is leaking at one corner.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after construction of a new Welcome Center. the replacement will be due to location and programmatic reasons.
DEMOLITION RECOMMENDATION
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 102 - RECREATION CENTER
Page: 6 of 106
Building: 0102 - RECREATION CENTER
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick CMU Masonry
Wall Roof Rigid Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Assembly 12,489 8,656 1 Owned 2004 Not Evaluated
Comments: Urinals in the men's room are not accessible.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
Roof leaks above the entry lobby.
The age and estimated remaining roof life is based on visual observation during the October 2016 Facility Survey.
Drainage Year Life
Remaining Type Area Served
EPDM
Steel
Scuppers and Downspouts
Surface Run-off
Flat
Flat
Entire Building
Snack Bar Stack Space
Number of Deficiencies = 1
Comments:
Comments:
3. Roof
Page: 7 of 106
Building: 0102 - RECREATION CENTER
INTERIOR FINISH
Ceramic Tile Concrete Glass Block Vinyl Tile
CMU Metal Toilet Partitions
Metal Unit - Metal Frame Metal Unit with Glass - Metal Frame
Metal Overhead Shutter - Steel Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder Ramp Wood Stairs Comments: There is a vertical metal ladder to the roof hatch. Concrete stairs and a concrete ramp leading to the entry. Wood stairs lead to the stage in the multi-purpose room.
Metal Unit - Metal Frame Metal Unit with Glass - Metal Frame
Fixed - Aluminum Frame; Double Glazing; Fixed - Vinyl Frame; Double Glazing;
Hopper - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Ceiling Grid Exposed Structure Gypsum Board
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The building has five gas-fired rooftop HVAC units (four Carrier 48HJ series, from 59 to 148 MBH output and a 48HGF016, 328 MBH output serving the multi-purpose room) all built in 2004.
Comments:
HVAC
Heat1.
Gas-Fired Single Duct None Electric Mechanical None Entire Building
Page: 8 of 106
Building: 0102 - RECREATION CENTER
Mechanical
Mechanical
Mechanical
Kiln Area
Restroom/Janitor's Closet
Paint Storage
Comments:
Comments:
Comments:
Ventilation is by a rooftop fan (Penn #DX11B).
Ventilation is by a rooftop fan (Penn #DX08B).
Ventilation is by a rooftop fan (Penn #DX06R).
The 50 gallon electric water heater was built by State Industries, model CPE522ORTA.Comments:
Cast Iron/PVC Indoor None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Service Sink Sink Two Compartment Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Comments:
None None ABC Type Fire Extinguisher
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical Economizer Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
The building has five DX rooftop HVAC units (four Carrier 48HJ series, from 5 to 7-1/2 ton and a 48HGF016, 15 ton serving the multi-purpose room) all built in 2004. The economizer mode for the largest unit is furnished with power relief.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
The gas used by Building 228 and Building 102 is metered as it enters Building 228.
Page: 9 of 106
Building: 0102 - RECREATION CENTER
Comments: Underground service is provided from a 3x75 kVA pole-mounted utility-owned transformer bank located south of the building. Service terminates in a 1000A main switchboard with a 1000A main circuit breaker and built-in voltmeter/ammeter located in the electrical/mechanical room. The adjacent Gymnasium Building 228 is also served from this switchboard. A utility meter and a CT cabinet are installed on the electrical/mechanical room exterior wall.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex 4010 located in the manager office. This panel also backfeeds and monitors the existing Simplex 2001 system in the adjacent gymnasium. The Simplex remote annunciator panel is located in the main lobby adjacent to the entrance.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels during the 2013 Survey include natural light contribution. Recessed light fixtures with compact fluorescent lamps located in the suspended ceiling supplement ambient lighting by linear fluorescent fixtures in the main lobby and the seating area. Track lighting is also utilized in the multi-purpose room.
Comments: Combination emergency light/exit signs are also provided.
High Intensity Discharge (HID) Comments: Exterior building-mounted light fixtures are controlled by time clock and photocell.
T8 - Fluorescent
T8 - Fluorescent
Compact and T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Compact and T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Lounges
Reception
Toilets
Recreation
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard, Loadcenter Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 2
LIGHTING
Page: 10 of 106
Building: 0102 - RECREATION CENTER
Comments: The building is connected to the center LAN system. The building security system includes exterior and interior CCTV cameras, a colored monitor, a security keypad, motion detectors and door alarms.
Ceiling speakers are provided and connected to the central PA system in Building 234. Outlets for data, phone and cable television are also provided.
Connected to Main System Color Monitor, Cameras Connected to Main System Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 103 - CAFETERIA/CULINARY ARTS
Page: 11 of 106
Building: 0103 - CAFETERIA/CULINARY ARTS
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry Metal Siding Window Wall
Wall Roof Rigid Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Assembly 14,827 12,436 1 Owned 2007 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
EPDM
Metal
Gutters and Downspouts
Surface Run-off
Flat
Barrel
Entire Building
Vestibule
3. Roof
Page: 12 of 106
Building: 0103 - CAFETERIA/CULINARY ARTS
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Vinyl Tile
Brick CMU Ceramic Tile FRP
Metal Rollup - Metal Frame Metal Unit - Metal Frame
Stainless Bi-swing - Metal Frame Metal Overhead Grille - Steel Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder Ramp Comments: There is a vertical metal ladder to the roof hatch. There are concrete stairs and concrete ramps leading to the entrance.
Metal Unit - Metal Frame Metal Unit with Glass - Metal Frame
Fixed - Aluminum Frame; Double Glazing; Fixed - Metal Frame; Single Glazing;
Hopper - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Ceiling Grid Exposed Structure Gypsum Board
Exterior Doors5.
Windows6. Number of Deficiencies = 1
Floors1.
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 2
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are five Trane rooftop HVAC units (all built 7/2006) serving the building with heat (RTU-1&2, both #YDC211C, 203 MBH output; RTU-3&4, both #YCD151CD, 203 MBH output; RTU-6, #YCH063, 108 MBH output) and a Carrier unit (RTU-5, #48TDF012, 144 MBH output).
There are four gas-fired heated makeup air units (AbsolutAire) for the kitchen exhaust.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Gas-Fired
Single Duct
Makeup Air Unit
None
None
Electric
Electric
Mechanical
Mechanical
None
None
Entire Building
Kitchen
Page: 13 of 106
Building: 0103 - CAFETERIA/CULINARY ARTS
Mechanical Kitchen/Restrooms
Comments: There are eight rooftop exhaust fans built by Carnes and Penn Ventilator. Four of the fans ventilate two 15'x12' kitchen hoods.
There are two A. O. Smith gas-fired water heaters model #BTH-400A, (both built 8/2007), 130 gallon capacity, 399.9 MBH input and 465.3 recovery GPH.
Comments:
Cast Iron/PVC Outdoor and Indoors None
Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Multi-Hand Wash Sink Service Sink Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
None
Refrigerant
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Electronic Equipment
Room
PLUMBING
Exhaust Ventilation
There are five Trane rooftop HVAC units (all built 7/2006) serving the building with cooling (RTU-1&2, both #YDC211C, 17-1/2 ton; RTU-3&4, both #YCD151CD, 12-1/2 ton; RTU-6, #YCH063, 5 ton) and a Carrier unit (RTU-5, #48TDF012, 10 ton).
The cooling is provided by a condensing unit ( York #TCGD18S41S1A,1.5 ton serving center telep.
switch room).
Comments:
Comments:
Number of Deficiencies = 1
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 14 of 106
Building: 0103 - CAFETERIA/CULINARY ARTS
Wet None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: Underground service is provided from a 500 kVA pad-mounted transformer located in the back of the building. Service terminates in a 2000A two-section switchboard located in the mechanical/electrical room. The switchboard has a 2000A main circuit breaker and is protected by a TVSS device. A pull box, a CT cabinet and a meter are installed on the mechanical/electrical room across from the transformer.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels during the 2013 Survey include natural light contribution. Day lighting control is utilized for serving and dining areas. Day lighting control equipment includes day lighting controller, photocell and electronic switches. Parabolic fluorescent fixtures with dimmable ballasts are utilized in the dining area. This lighting is supplemented by recessed downlights with compact fluorescent lamps and dimmable ballasts. Recessed downlights with compact fluorescent lamps are also utilized in the serving area.
Compact Fluorescent High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact and T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Equipment Rooms (Elec/Mech)
Toilets
Dining/Lunch Rooms
Dishwashing
Food Preparation
Storage Rooms
Classrooms
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Number of Deficiencies = 2FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Location UL300 Compliance Status Kitchen
Culinary Arts
Compliant
Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 15 of 106
Building: 0103 - CAFETERIA/CULINARY ARTS
FIRE ALARM
Comments: The fire alarm control/annunciator panel Fire Lite Alarms/Honeywell model MS-92000UDLS, located in the culinary arts director office. The Fire Lite remote annunciator panel is located in the vestibule. Audio/visual (A/V) alarm devices are installed on the exterior of the building for added protection.
Comments: The building houses a telephone closet, that according to the long range plan will be utilized as the main telephone/data closet for the whole center. Currently the systems are in the transition stage; the data closet in this building and the main data closet located in the Building 234 are interconnected by fiber optic cable and independently monitored from JCDC. The building security system includes exterior and interior CCTV cameras and a color monitor located in the data closet. Ceiling speakers are provided and connected to the central PA system in Building 234. Outlets for data, phone and cable television are also provided.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Exterior Tamper Switch Exterior V/A Device Flow Switch Heat Detector Magnetic Door Holder Remote Annunciator Panel Smoke Detector Tamper Switch Visual Alarm
Connected to Main System Color Monitor, Cameras Connected to Main System Local Cable Company
Telephone Security Public Address Television
Comments:
Battery Backup Battery Backup Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Emergency /Exit Lighting3. Number of Deficiencies = 2
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 104 - DORMITORY A FEMALE DORM
Page: 16 of 106
Building: 0104 - DORMITORY A FEMALE DORM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete
Concrete
Loadbearing Masonry/Steel
Loadbearing Masonry\Steel
Wood
Steel
Brick Masonry EIFS
Wall Roof Rigid Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Residential 31,140 21,095 2 Owned 2011 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
No
Yes
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2.
Insulation4.
Material
A truss joint has failed. Roof leaks onto the second floor lounge.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles
Single Ply
Gutters and Downspouts
Gutters and Downspouts
Hip
Flat
Dorm Rooms
Common Area\Canopy
Number of Deficiencies = 1
Comments:
3. Roof
Dorm Rooms
Common Area\Canopy
Page: 17 of 106
Building: 0104 - DORMITORY A FEMALE DORM
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Drywall
Metal Unit - Metal Frame Metal Unit with Glass - Metal Frame
Mechanical Restroom
Comments: There is a general exhaust fan in the building.
Ventilation Area Served
VERTICAL CIRCULATION
Metal Pan w/Concrete Stairs Comments: Metal pan with concrete stairs lead to the second floor.
Metal Unit - Metal Frame Storefront - Storefront Frame
Awning Units - Aluminum Frame; Double Glazing; Double Hung - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Double Glazing; Fixed - Metal Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exhaust Ventilation
Exterior Doors5.
Windows6. Number of Deficiencies = 3
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
Gas-Fired Furnace
Single Duct None Electric Natural None Entire Building
Ventilation2. Number of Deficiencies = 3
Page: 18 of 106
Building: 0104 - DORMITORY A FEMALE DORM
Galvanized Steel Outdoor None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Shower/Bathtub
Gas (Natural)
Wet None ABC Type Fire Extinguisher
Comments: Underground service is provided from a pad-mounted transformer located in the back of the building.
Service terminates in a 1000A two-section switchboard located in the mechanical/electrical room. The switchboard has a 1000A main circuit breaker and is protected by a TVSS device. A pull box, a CT cabinet and a meter are installed on the exterior of the mechanical/electrical room.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Split Direct Expansion (Air
Source)
Single Duct None Electric Mechanical None Entire Building
High Intensity Discharge (HID) Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
There are Carrier split systems serving the entire building.Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 2FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Page: 19 of 106
Building: 0104 - DORMITORY A FEMALE DORM
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Gamewell/FCI E3 series, located in the RA office. A remote annunciator panel of the same model is located in the vestibule.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Tamper Switch Visual Alarm
Connected to Main System Closed Circuit TV None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels during the 2013 Survey include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Laundry Room
Housing Lounge
Shower
Sleeping Rooms
Study Room
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup Emergency Exit
Number of Deficiencies = 2
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
COMMUNICATION
Electric Water Gas No YesYes
BUILDING UTILITY METERING
Type Location None None
CARBON MONOXIDE DETECTION
Detection Required Yes
Number of Deficiencies = 1
Page: 20 of 106
Building: 0104 - DORMITORY A FEMALE DORM
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
A roof truss hanger has failed. Related rooms are unsafe for occupancy.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting…