Questions and Answers.pdf
PDF 387 KB Posted
- Attached to
- Air Cooled Chiller Replacement Federal contract opportunity
- Solicitation number
- 15F06724Q0000231
About this file
This document is a set of Questions and Answers related to a federal contract opportunity for the replacement of an air-cooled chiller at the Federal Bureau of Investigation (FBI) Criminal Justice Information Services (CJIS) Division facility in Clarksburg, West Virginia.
The key details include:
- The chiller is enabled when the outside air temperature is greater than 55°F and can be operated year-round if necessary.
- The government will be responsible for modifying the existing maintenance rack if it does not fit the new chiller.
- The government will handle the Siemens control system integration and will provide the programming requirements to the contractor.
- The requested chiller specifications include BACnet IP, evaporator heater, GFI, hot gas bypass, high efficiency fans, and other options.
- The required chiller performance details such as cooling capacity, flow rates, temperatures, and pressure drop are provided.
- Photos from the site visit will be uploaded to SAM.gov.
- Quotes are due by 4:00 PM ET on August 26, 2024 and must remain valid for 60 calendar days.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 15F06724Q0000231 - SF1449 - 08.23.24.pdf | ||
| SF30 - 15F06724Q0000231.pdf | ||
| Chiller Replacement Picture 1.jpg | JPG image | |
| Chiller Replacement Picture 3.pdf | ||
| Chiller Replacement Picture 5.pdf | ||
| Chiller Replacement Picture 4.jpg | JPG image | |
| Chiller Replacement Picture 2.jpg | JPG image | |
| Service Center Chiller Replacement SOW.pdf | ||
| RFQ - Chiller Replacement for CJIS - 08.06.2024.pdf | ||
| 15F06724Q0000231 - SF1449.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
# Description Date Requested Status RFI Clarifications Response Date FBI Response
Is the chiller used seasonally and turned off in the winter or is it used year round?
8/14/2024 8/15/2024 Chiller is enabled when Outside air temp is greater than 55F. We can/have ran it in the winter if necessary via operators bypassing the outside air enable.
If the maintenance rack does not fit the new chiller, should it be modified for the new chiller or turned over to the owner?
8/14/2024 8/15/2024 If it does not fit it shall be the responsibility of the government for modification and install. If it does fit it shall be the responsibility of the contractor.
Should we include the cost of the Siemen’s integration to the control system? The Government could use its service/maintenance contract for the integration and provide to the Contractors the programming requirements to ensure the unit is ready for integration.
8/14/2024 8/15/2024 No, since multiple vendors brought this up at the site visit the decision has been made that the government will be responsible for control changes.
If Siemen’s integration remains under this SOW, who is a contact at Siemens to secure requirements and pricing? A contact which has previously supported work at this project location and been approved for access
8/14/2024 8/15/2024 N/A, the Siemens control work is no longer covered under the scope of this project.
Can you provide a list of all requested options for the new chiller? 8/14/2024 8/15/2024 -BACnet IP -Evaporator Heater (Freeze Protection) -4-amp GFI (Ground Fault Interrupt) -Hot Gas Bypass -65 kA SCCR -Suction Line Insulation -Suction Service Valve -Standard Scroll Compressor -Micro Channel Condenser Coil -High-Efficiency Variable Condenser Fans -Non-Fused Disconnect -Shell-and-Tube Direct Expansion (DX) -Single Point Power -Coil Trim Panels -Coil Face Shipping Protection (CFSP) -Low Sound - Includes Aero-Acoustic Fans -No hydronic Package
FBI CJISD Service Center Chiller Request for Information
# Description Date Requested Status RFI Clarifications Response Date FBI Response
FBI CJISD Service Center Chiller Request for Information
Can you provide the requested performance for the new chiller, including Flow (GPM), Entering and Leaving temps, Design ambient, Max Pressure drop with 40% Glycol?
8/14/2024 Pulled from Chiller model called out in SOW
8/15/2024 Performance Information:
Cooling Capacity Tons 125.4 Pump Power kW 5.187 Total Compressor Power kW 127.1 Chiller Pressure Drop ft wg 19 Total Fan Motor Power kW 14.46 Total Unit Power (without pump) kW 142.2 Minimum Capacity % 10 Capacity Control Steps 6 Energy Efficiency Ratio (EER) Btu/(W-hr) 10.59 IPLV.IP Btu/(W-hr) 17.31 Flow (GPM):
Fluid Flow gpm 299.2 Min. Fluid Flow gpm 156.0 Min. Part Load Fluid Flow gpm 112.3 Entering and Leaving temps:
Leaving the temperature °F 44.00 Entering Temperature °F 54.00 Design ambient:
Without modification, shall be capable of starting and running at outdoor ambient temperatures from 0°F (-17.8°C) to 125.6°F (52°C) Max Pressure drop with 40% Glycol:
Pressure Drop ft wg 12.5
7 Will the photos taken during the site visit be uploaded to SAM.gov? 8/14/2024 8/15/2024 Yes they will be posted to SAM.gov
Quote is due by 4:00 PM ET on August 26, 2024. The quote shall remain valid for 60 calendar days from the RFQ due date. Will a revised SF1449 with block 8 completed be issued for our use in our submission?
8/14/2024 8/15/2024 No, please utilize the SF1449 dated 08/06/2024