PVI Water Heater Specs sheet.pdf
PDF 399 KB Posted
- Solicitation number
- 15BH0N24Q00000004
About this file
This document provides details for a federal contract opportunity to replace a 500-gallon gas fired water heater at the Federal Detention Center in Honolulu, Hawaii. The Bureau of Prisons is soliciting quotations for the purchase, delivery, and initial training for a 500-gallon gas-fired water heater. Offerors must meet the specifications in the attached documents, including the specifications sheet and statement of work. The solicitation will be set aside for total small businesses and utilize FOB Destination pricing. The award will be made to the responsible offeror providing the best value to the government based on past performance and price, with price being more important than past performance. The solicitation number is 15BH0N24Q00000004 and the Department of Justice Bureau of Prisons is the contracting agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UPDATED Replace Water Heater SOW.pdf | ||
| Water Heater Cover letter.pdf | ||
| 07 - 24Z6AN9 Replace Water Heater SOW.pdf | ||
| Residency Requirement Certification Form.pdf | ||
| Pictures.pdf | ||
| 15BH0N24Q00000004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
"J" dimension is for the burner housing only. Gas train may exceed this dimension.
Models with “TPL” suffix are less than 55 ppm NOx. SCAQMD models 2TPL (200MBH), 3TPL (300MBH) and 4TPL (400MBH).
* The information presented is for Natural gas 0.6 S.G.— For operation with propane (LP gas), consult factory.
** Consult the factory.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form PV 8050.
Model Number
Recovery gph Input Btu/h
* Min. Inlet
Flow Gas Pressure
"W.C.
Dimensions (inches) Blower Motor Shipping
Weight lbs 40°- 120°F 40°- 140°F A B C J K HP
Volt/Ph/ Amps
250 L 500A-TPL 250 200 199,000 4.5 21 4 3/4 10-1/4 43 1/6 115/1/3 1815
375 L 500A-TPL 375 300 300,000 4.5 21 4 3/4 10-1/4 43 1/6 115/1/3 1825
500 L 500A-TPL 500 400 399,000 4.5 21 5 3/4 10-1/4 43 1/6 115/1/3 1835
750 L 500A-TP 750 600 600,000 6.0 28-1/2 6 1 16 43 1/3 115/1/8 1915
1000 L 500A-TP 1000 800 800,000 6.0 28-1/2 8 1-1/4 16 43 1/3 115/1/8 1955
1250 L 500A-TP 1250 1000 1,000,000 6.0 36-1/2 8 2 16 43 1/2 115/1/10 2210
1500 L 500A-TP 1500 1200 1,200,000 6.5 36-1/2 8 2 16 43 1/2 115/1/10 2220
2000 L 500A-TP 2000 1600 1,600,000 9.0 51-1/2 10 2 27 43 1-1/2 115/1/20 2655
2500 L 500A-TP 2500 2000 2,010,000 10.5 51-1/2 10 2-1/2 27 43 1-1/2 115/1/20 2675
PV 8058 11-2016
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
(800) 784-8326 (817) 335-9531 www.pvi.com
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.
TURBOPOWER
GAS PACKAGED WATER HEATER
AquaPLEX STORAGE TANK (UNLINED DUPLEX ALLOY)
TANK SERIES 500 GALLONS
STANDARD ELECTRICAL REQUIREMENTS
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL REQUIRE A
SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN OPTIONAL CONTROL
CIRCUIT TRANSFORMER.
VENTING REQUIREMENTS
-.02" TO -.06" W.C. (NEGATIVE PRESSURE)
CATEGORY I, TYPE B VENTING
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER SIZING, CONSULT
THE NATIONAL FUEL GAS CODE UNDER “FAN-ASSISTED.”
* GAS PRESSURE REQUIREMENTS
SEE TABLE ABOVE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET PRESSURE:
10.5" W.C. for 199,000 - 399,000 AND 14” W.C. for > 399,000.