PVI Water Heater Specs sheet.pdf

PDF 399 KB Posted

Attached to
Amendment 1 Purchase of one 500-Gallon Gas Fired Water Heater at FDC Honolulu.
Solicitation number
15BH0N24Q00000004
Issued by

About this file

This document provides details for a federal contract opportunity to replace a 500-gallon gas fired water heater at the Federal Detention Center in Honolulu, Hawaii. The Bureau of Prisons is soliciting quotations for the purchase, delivery, and initial training for a 500-gallon gas-fired water heater. Offerors must meet the specifications in the attached documents, including the specifications sheet and statement of work. The solicitation will be set aside for total small businesses and utilize FOB Destination pricing. The award will be made to the responsible offeror providing the best value to the government based on past performance and price, with price being more important than past performance. The solicitation number is 15BH0N24Q00000004 and the Department of Justice Bureau of Prisons is the contracting agency.

View the file

Other files

File Type Posted
UPDATED Replace Water Heater SOW.pdf PDF
Water Heater Cover letter.pdf PDF
07 - 24Z6AN9 Replace Water Heater SOW.pdf PDF
Residency Requirement Certification Form.pdf PDF
Pictures.pdf PDF
15BH0N24Q00000004.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.

"J" dimension is for the burner housing only. Gas train may exceed this dimension.

Models with “TPL” suffix are less than 55 ppm NOx. SCAQMD models 2TPL (200MBH), 3TPL (300MBH) and 4TPL (400MBH).

* The information presented is for Natural gas 0.6 S.G.— For operation with propane (LP gas), consult factory.

** Consult the factory.

Dimensions are in inches unless otherwise specified.

For standard and optional equipment, see form PV 8050.

Model Number

Recovery gph Input Btu/h

* Min. Inlet

Flow Gas Pressure

"W.C.

Dimensions (inches) Blower Motor Shipping

Weight lbs 40°- 120°F 40°- 140°F A B C J K HP

Volt/Ph/ Amps

250 L 500A-TPL 250 200 199,000 4.5 21 4 3/4 10-1/4 43 1/6 115/1/3 1815

375 L 500A-TPL 375 300 300,000 4.5 21 4 3/4 10-1/4 43 1/6 115/1/3 1825

500 L 500A-TPL 500 400 399,000 4.5 21 5 3/4 10-1/4 43 1/6 115/1/3 1835

750 L 500A-TP 750 600 600,000 6.0 28-1/2 6 1 16 43 1/3 115/1/8 1915

1000 L 500A-TP 1000 800 800,000 6.0 28-1/2 8 1-1/4 16 43 1/3 115/1/8 1955

1250 L 500A-TP 1250 1000 1,000,000 6.0 36-1/2 8 2 16 43 1/2 115/1/10 2210

1500 L 500A-TP 1500 1200 1,200,000 6.5 36-1/2 8 2 16 43 1/2 115/1/10 2220

2000 L 500A-TP 2000 1600 1,600,000 9.0 51-1/2 10 2 27 43 1-1/2 115/1/20 2655

2500 L 500A-TP 2500 2000 2,010,000 10.5 51-1/2 10 2-1/2 27 43 1-1/2 115/1/20 2675

PV 8058 11-2016

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

(800) 784-8326 (817) 335-9531 www.pvi.com

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN

AND SPECIFICATION WITHOUT NOTICE.

TURBOPOWER

GAS PACKAGED WATER HEATER

AquaPLEX STORAGE TANK (UNLINED DUPLEX ALLOY)

TANK SERIES 500 GALLONS

STANDARD ELECTRICAL REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.

MOTOR VOLTAGE:

208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL REQUIRE A

SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN OPTIONAL CONTROL

CIRCUIT TRANSFORMER.

VENTING REQUIREMENTS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE)

CATEGORY I, TYPE B VENTING

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE

VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER SIZING, CONSULT

THE NATIONAL FUEL GAS CODE UNDER “FAN-ASSISTED.”

* GAS PRESSURE REQUIREMENTS

SEE TABLE ABOVE FOR MINIMUM PRESSURE BY MODEL NUMBER.

MAXIMUM STATIC INLET PRESSURE:

10.5" W.C. for 199,000 - 399,000 AND 14” W.C. for > 399,000.

File details come from the government source that posted it. Updated .