USP McCreary 25Z1AE6 Boilers Solicitation Amend 0002.pdf
PDF 18 MB Posted
- Attached to
- USP McCreary 25Z1AE6 Food Service Boilers
- Solicitation number
- 15BFA025Q00000151
About this file
This document is an Amendment of Solicitation (Standard Form 30) for Solicitation Number 15BFA025Q00000151, issued by the Federal Bureau of Prisons Field Acquisition Office for USP McCreary. Amendment 0002, dated 05/02/2025, provides additional information requested during a site visit for a project to supply and install a new combination boiler for the Food Service Department. The solicitation requires a boiler with a minimum of 30 HP, 1,000 MBH output, capable of producing steam for six steam kettles and hot water, with Cleaver Brooks Hawk 1000 controls, an Allen-Bradley 7" Touchscreen HMI, Modbus tie-in capability, and a maximum operating pressure of 15 psig. Attachments include technical diagrams and specifications for the boiler system, such as a Unilux ZF150HS boiler diagram, steam kettle quantity and layout, and Lochinvar water heater details.
The amendment includes multiple technical documents showing boiler specifications from manufacturers like Unilux, Cleveland, and Lochinvar, with detailed technical information such as dimensions, input ratings, gas pressures, and installation requirements. The attachments provide comprehensive technical documentation to support the boiler replacement project, including installation clearances, steam kettle configurations, and equipment certifications. The solicitation is being handled by the Federal Bureau of Prisons Field Acquisition Office, located in Grand Prairie, Texas, with the primary contact being Anne Bradley, who can be reached at (771) 474-6749 or abradley1@bop.gov.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
15BFA025Q00000151/0002 Page 1 of 3
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE PAGE OF PAGES
1 3
2. AMENDMENT/MODIFICATION NUMBER
3. EFFECTIVE DATE
05/02/2025
4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
BFAOCODE
Federal Bureau of Prisons Field Acquisition Office U.S. Armed Forces Reserve Complex 346 Marine Forces Drive Grand Prairie, TX 75051
Anne Bradley
(O) 771-474-6749 abradley1@bop.gov
6. ISSUED BY 15B120CODE
Federal Bureau of Prisons USP McCreary
330 FEDERAL WAY
Pine Knot, KY 42635
7. ADMINISTERED BY (If other than Item 6)
9A. AMENDMENT OF SOLICITATION NUMBER
15BFA025Q00000151
CODE FACILITY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, country, state and ZIP Code) (X)
X 9B. DATED (SEE ITEM 11)
04/17/2025
10A. MODIFICATION OF CONTRACT/ORDER
NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X XThe above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning ____copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
ORDER NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return _______ copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
The purpose for this amendment is to provide information additional information requested at the site visit.
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
Darrell McKeel
(Signature of person authorized to sign)
15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED
By (Signature of Contracting Officer)
16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243
15BFA025Q00000151/0002 Page 2 of 3
Table of Contents
Section Description Page Number
1 Solicitation/Contract Form 2 Commodity or Services Schedule 3 Contract Clauses 4 List of Attachments 5 Solicitation Provisions
15BFA025Q00000151/0002 Page 3 of 3
Section 2 - Commodity or Services Schedule
Supply and installation of a new combination boiler for the Food Service Department at USP McCreary in accordance with the SOW.
Unique Entity ID: _____________________________
CAGE: __________________________
Email: ___________________________
SCHEDULE OF SUPPLIES/SERVICES
CONTINUATION SHEET
Aggregate Total: $_______________________________
Estimated calendar days to complete project: _____________
Section 3 - Contract Clauses
No Clauses
Section 4 - List of Attachments
No Clauses
Identifier Title Number of Pages
4 Diagram-High-Pressure-Steam-Model-150.pdf - ADDED 1 5 USP McCreary - Boiler and DA Tank Pictures.pdf - ADDED 3 6 USP McCreary Steam Kettle Specs and Layout.pdf - ADDED 3 7 Lochinvar Water Heaters1.pdf - ADDED 2 8 Lochinvar Water Heaters2.pdf - ADDED 3
Section 5 - Solicitation Provisions
No Clauses
UNILUX
UNILUX ADVANCED MFG., LLC.
NISKAYUNA, NY 12309
Ph: (518) 344-7490 Fax: (518) 344-7495
THIS DRAWING EMBODIES A CONFIDENTIAL PROPRIETARY DESIGN. ALL RIGHTS FOR REPRODUCTION, MANUFACTURING OR PATENTS ARE RESERVED BY UNILUX BOILER CORP.
ZF 150HS
RIZ RACAZA 05AUG09
DAVID RAMSON 05AUG09
QB00000
JB00000
NTS
SUPPLY PSI
ELECTRIC
Drawn By :
Checked By
BURNER
File No. :
Drawing No.
PROJECT:
LOCATION:
Model Sizes
30 COMMERCE PARK DRIVE
Date :
Date :
REV.:
Scale
K
M
C
FRONT VIEW SIDE VIEW REAR VIEW
W
LL
IMPORTANT
1. ADEQUATE BOIL OUT PROCEDURES MUST BE
IMPLEMENTED BEFORE BOILER PLACED IN SERVICE.
SEE OPERATION MANUAL.
2. PROPER WATER TREATMENT PROGRAM IS CRITICAL TO
THE OPERATION OF THIS BOILER.
3. WARRANTIES, EXPRESSED OR IMPLIED, WILL BE RENDERED
NULL & VOID IF PROPER WATER TREATMENT PROGRAM IS
NOT IMPLEMENTED AND MAITAINED. CONSULT LOCAL
WATER TREATMENT SPECIALISTS FOR DESIGN AND SUPPLY
OF REQUIRED WATER TRREATMENT SYSTEM
NAT'L BD. NO.
CERTIFIED BY:
UNILUX
MANUFACTURING INC.
FLEXIBLE WATER TUBE BOILER
MODEL NO.
SERIAL NO.
CRN
MAX. W.P. STEAM
WATER
SAFETY RELIEF VALVE
MAX. STEAMING CAPACITY
HEATING SURFACE
YEAR BIULT
SUPPLY CIRCUIT
CONTROL CIRCUIT
NATURAL GAS/OIL
GAS MBH
MAX. MANIFOLD PRESSURE
REGULATOR INLET PRESSURE
FUEL OIL
OL G.P.H. US
NOZZLE ANGLE
NOZZLE PATTERN
PUMP PRESSURE
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS
TOP SIDE REAR FRONT
FLOOR NON COMBUSTIBLE VENT
J
A
D
N
F E
B
S
T
U
G
P Q
X
V
FLUE GAS OUTLET
PRESSURETROLHoneywell
PSIPSI
3.5
2.5
1.5
.5
MAINDIFF
.1 .2 .3 .4 .5 .6 .7 .8
PRESSURETROLHoneywell
PSIPSI
3.5
2.5
1.5
.5
MAINDIFF
.1 .2 .3 .4 .5 .6 .7 .8
6 1.5
PSI
.4
.3
.2 .1
.5
PSI
MAINDIFF
.8
.7
.6
.5
2.5
3.5 50
H
R
UNILUX
NOTE: DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE
CONSULT FACTORY FOR CERTIFIED DIMENSIONS.
O
PLAN
X
W
A
C
CENTER OF LOWER DRUM TO BOTTOM
CENTER OF BURNER OPENING TO BOTTOM
CENTER OF FLUE GAS OUTLET TO REAR
DRUM CLEARANCE FROM BASE, FRONT
TUBE REMOVAL CLEARANCE FROM BASE
CTR. LOWER DRUM TO CTR. UPPER DRUM
DRUM CLEARANCE FROM TOP, FRONT
DRUM CLEARANCE FROM BASE, REAR
CENTER OF TOP DRUM TO TOP OF OUTLET
CENTER OF OUTLET TO ENCLOSURE FRONT
INLET, 3000 PSI ASA HALF COUPLING
OVERALL BOILER LENGTH W/ BURNER
OVERALL BOILER LENGTH
FEEDWATER INLET FROM BASE
X W V
T U
S
E
UPPER DRUM, OD, NPS
LOWER DRUM, OD, NPS
OUTLET FLANGE CLASS 300
FLUE GAS OUTLET, I.D.
BURNER DIMENSION
BLOWDOWN, NPTQ
R
P
N O
M
H
K L
J
G F
LENGTH OF BASE
WIDTH OF BASE
BOILER MODEL - ZF150HS
LENGTH OF SUPPORT FROM BASE
HEIGHTB
D C
A1 A
43 9/16
111 3/8 95 7/8
14 1/2 30 1/2
2439 9/16
1 1/2 35 1/8
8 5/8
19 5/8
13 3/4
25 7/8
INCHES
76 9/16 35 1/2
63 1/4
METRIC
SURFACE
BLOWDOWN
CHEMICAL
FEED
NOTE: "X" DIMENSION MAY VARY BASED ON BURNER
CHIMNEY FLANGE DIMS:
O.D. = 13" I.D. = 8-1/4" B.C.D = 10-1/2"
NO. OF HOLES = 6
HOLE DIAMETER = 0.53"
ZF0150HS
Cleveland Project _________ _
Item _________ _
TRI-LEG/PEDESTAL, DIRECT STEAM
Quantity ________ _
FCSI Section 1140,~-------
STATIONARY, 213 STEAM JACKETED Approved ________ _
25, 40, 60, 80, 100, 125, 150, 200 OR 250 GALLONS
(100, 150, 225, 300, 375, 475, 575, 760 OR 950 LITERS
Date _________ _
Models
• KDL-25 • KDL-80 • KDL-150 • KDP-40
• KDL-40 • KDL-100 • KDL-200 • KDP-60
• KDL-60 • KDL-125 • KDL-250 • KDP-80
• KDP-100
Shown with optional Steam Control Kit
Short Form Specifications Shall be CLEVELAND, Direct Steam Kettle, Tri leg or Pedestal stationary, Model KD _ -__ . 2t3 Steam Jacketed, 50 psi Steam Jacket Rating on 80 - 100 gallon, 35 psi on 125 gallon and larger. Supports to be Stainless Steel. Includes spring-assisted, Domed Cover and 2" Tangent Draw-off Valve; heavy re-enforced Rolled Rim.
To operate, connect d irectly to a steam source supplying from 5 to 45 psi steam. 316 Stainless Steel Interior.
Standard Features Spring-assisted Cover: domed, hinged, one piece rotatable (not available on KDL-250)
Type 316 Stainless Steel Interior
2" diameter Tangent Draw-off Valve with Drain Strainer
SO psi Steam Jacket Rating on 25 - 100 gal.
models, 35 psi Steam Jacket Rating on 125 - 250 gal. models
50 psi chrome plated Safety Va lve on 25 - 100 gal. models,35 psi chrome plated Safety Valve on 125 - 250 gal. models
Condensate Drain Valve with insulated handle
Tel 1.216.481.4900 Fax 1.216.481 .3782
For Tri-leg Models: Tri-leg supports of 1 .63" O.D., Type 304 Stainless Steel tubu lar construction, wit h level adj ustable Flanged Feet for Floor Bolting
For Pedestal Models: Pedestal support of Type 304 Stainless Steel with .75" thick floor plate, (level adjustable for sloping floors), comes with Stainless Steel Collar for sealing
Faucet Mounting Bracket
Steam Control Inlet Valve
Typical approvals include NSF and ASME
Options & Accessories Lift-off Covers (CL)
Chrome plated Steam Control Kit includes: Steam Traps, Condensate Strainers, Check Valves, nipples and fitt ings, factory assembled and mounted on kettle (SCKl)
100 psi Pressure Option (PO) (for 125 gallons and larger)
Cooking Baskets and Tri-Basket Supports (BS and TBS)
Measuring Strips (MS)
Gallon Markings (KM)
Kettle Accessory Kit (KAK) includes:
• Clean-up Brush (CB)
• 36" Kettle Paddle (KP)
• 36" Kettle Whip (KW)
• 36" Kettle Brush (KB)
• Draw-off Brush (DB)
• 24 oz. Ladle (KL)
Pressure Reducing Valve for regulating incoming steam pressure of over 45 psi (PRV-K)
Hot and cold or cold only Kettle Filler with 60"' Hose (DKF-K or
SKF-K)
Automatic Water Meter (GMF or LMF)
Drain Strainers (DS-)
Water Meter Stand (SWM)
3" diameter Tangent Draw-Off Valve w/Strainer (TD3)
3" diameter Butterfly Valve (BV3)
Pre-Rinse Spray Head and Hose (PRSK)
Correctional Packages
Insulated Outer Jacket (IOJ) www.clevelandrange.com Section 7, Page 1 7
KE004046--49
760 Beta Drive, Unit D Mayfield Village, Ohio 44143
Email steam@clevelandrange.com Timeless Quailty, Trusted For Life ®
5647A 02 I 2021
(D n r-+ l/) r-+ (D
OJ
(D r-+ r-+ (D V')
V) cu +---' cu
E co cu V)
+---' u cu
Cleveland
B1
WITH
SPRING
ASSIST
COVER
f------ A ------I
C1
WITH
SPRING O
ASSIST
C2 COVER
NO
COVER
FLOOR DRAIN
12" (305mm) long x 12" (305mm) wide
4' (102mm)
RECOMMENDED
t
RECOMMENDED
FLOOR SLOPE
1' (26 mm) per 4' (1220 mm) t ' - - ·- 1.=-p;;E_ D:RAIN RECOMMENDED
mm. valve size plus 1· (26 mm)
1-- N
M
CAPACITIES: (in 8 oz. servings, other sizes may be calculated.)
25 Gallon / 100 liters . 400 servings 40 Gallon / 150 liters . 640 servings 60 Gallon / 225 liters . . 960 servings 80 Gallon / 300 liters ... 1280 servings
100 Gallon / 375 liters ... 1600 servings 125 Gallon / 475 liters . .. 2000 servings 150 Gallon / 575 liters .. . 2400 servings 200 Gallon / 760 liters . . . 3200 servings 250 Gallon / 950 liters . .. 4000 servings
4" (102mm)
MINIMUM CLEARANCE SPRING ASSIST COVER FOR
80 GALLON KETTLES AND UP
D
E
DIMENSIONS
GALSJ
LITERS A
25 IN 261 /2
100 mm 674
J,,, ---,,,~ I 14.25" I I- (362mm) -i
B1 B2 C1
32 29 3/16 26 7/8 813 742 683
G
C2 D E F G H
241/8 59 37 221 /8 141/2 7 613 1499 940 639 369 178 a
J K L
143/4 221/2 6 3/8 375 572 162
M
UNIT SHOWN WITH
2" TANGENT DRAW-OFF
VALVE, SPRING ASSIST
COVER, HOT AND COLD
WATER FAUCET AND
STEAM CONTROL KIT.
N 0 PI.D. a 19 13/16 8 3/4 22 3/1 6 21 121/2
504 223 564 534 318
7/16" (1 1mm)0 4 7/8" 3 HOLES ON 124 0 mm
31/8" (80mm)~·) B.C.D. c •
120°
TYP
1 5/8"(42:::_:it_i r--'°'·'•"'7 1· (25mm) 9/16"
MAX.ADJUSTMENT 14mm
FLANGED FOOT DETAIL
Shipping Weights & Dimensions
40 IN 311/8 35 7/8 331 /16 31 3/16 28 7/16 621/8 36 7/8 221/2 121/2 711/32 171/4 27 5/32 613/32 23 9/16 111/4 26(7/16 26 101/2 !\,1Qgfil- 150 mm 791 912 408 793 723 1578 937 572 318 187 362 690 163 599 286 672 661 267 KDL-25 Weight • 170 lbs 60 IN 345/8 38 7/8 36 1/8 34 1/8 31 3/8 69 3/4 39 21 7/8 111/8 7 SIB 19 30 1/8 63/8 261 /4 13 29 3/8 291 /2 9 1/8 Width - 38" 225 mm 879 988 918 867 797 1772 991 556 283 194 483 766 162 667 331 747 750 232 Depth· 38" 80 IN 38 1/8 411 /4 381 /2 361/2 333/4 747/8 407/8 23 11 7 3/4 20 3/4 33 3/4 63/8 28 3/4 14 3/4 31 3/4 33 9 Height - 54" 300 IN 969 1048 978 928 858 1902 1039 585 280 197 528 858 162 731 375 807 839 229 KDL-40 Weight • 241 lbs 100 IN 40 5/8 43 1/8 40 3/8 38 3/8 35 5/8 79 3/8 43 23 7/8 111/8 8 22 36 6 3/8 30 3/4 16 33 5/8 351/2 9 1/8 Width· 44" 375 mm 1032 1096 1023 975 905 2017 1093 607 283 204 559 915 162 782 407 855 902 232 Depth - 44" 125 IN 451/8 46 5/8 431/2 41 7/8 38 3/4 831/4 43 24 7/8 10 7/8 81 /4 241 /4 40 1/4 6 3/8 34 181/4 36 3/4 40 8 7/8 Height - 54" 475 mm 1147 1185 1105 1064 985 211 5 1092 632 277 210 616 1023 162 864 464 934 1016 225 KDL-60 Weight - 269 lbs 150 IN 451/8 46 5/8 431 /2 41 7/8 38 3/4 88 3/8 47 7/8 24 7/8 10 7/8 81/4 241 /4 40 1/4 6 3/8 34 181/4 36 3/4 40 8 7/8 Width - 48" 575 mm 1147 1185 1105 1064 985 2245 1217 632 277 210 616 1023 162 864 464 934 1016 225 Depth· 48" 200 IN 501/8 46 5/8 43 3/8 41 7/8 38 3/4 94 49 1/4 293/8 105/8 7718 26 3/4 45 5/8 71/4 34 3/8 20 3/4 36 3/4 45 8 5/8 Height - 54" 760 mm 1274 1185 1102 1064 985 2388 1251 747 270 201 680 1159 185 874 528 934 1143 219 250 IN 531/8 48 7/8 45 5/8 441 /8 39 1/4 104 1/4 54 32 3/4 101/4 8 1/8 28 1/4 48 3/8 71 /4 36 7/8 22 1/4 371/4 48 8 1/4 950 mm 1350 1242 1159 1121 997 2648 1372 82 261 207 718 1229 185 937 566 947 1220 210
Leveling Bolts (4) 1
DIRECT STEAM @ DRAINAGE @) WATER QJ)~ CLEARANCE ~ Sealing
Steam Supply: 'II" NP!' Condensate Qj) 112 • NPT Hot Water RIGHT • o· i - _ __ _ _ . / . Collar
• Furnish !¼" IPS Retum with Strainer and Inlet LEFT • o· n , - ~ '" minimum line. Trap.
~ 'II" NP!' Cold Water REAR • 4.00" : i 1v Secure base to floor with 1/,. "
• Operating Pressure Inlet 1 . (20mm) Cast-in Stud or Lag Bolt
5 to 45 psi.
When ordered with d.tb (supplied by Contractor} optional faucet. LEVEL ADJUSTABLE BASE
MOUNTING DETAIL
NOTES:
Cleveland Range reserves right of design improvement or modification, as warranted.
Many regional , state and local codes exist and it is the responsibility of the owner and installer to comply with the codes.
Installation of backflow preventers, vacuum breakers and other specific coder requirements is the responsibility of the owner and installer.
Cleveland Range equipment is buitt to comply with applicable standards for manufacturers. Included among those approval agencies are U.L., A.G.A., NSF, ASME/N.Bd., CSA, CGA, ETL and others . (NOTTO SCALE)
760 Beta Drive, Unit D Mayfield Village, Ohio 44143
Tel 1.216.481.4900 Fax 1.216.481.3782 Email steam@clevelandrange.com www.clevelandrange.com
Section 7, Page 18
02 I 202 1
Timeless Quahty, Trusted For Life ®
Steam Kettle Quantity & Layout
I
| USP McCreary 25Z1AE6 Boilers Solicitation Amend 0002 |
| Diagram-High-Pressure-Steam-Model-150 |
| USP McCreary - Boiler and DA Tank Pictures |
| USP McCreary Steam Kettle Specs and Layout |
| Lochinvar Water Heaters1 |
| Lochinvar Water Heaters2 |
File details come from the government source that posted it. Updated .