2 - Amendment 3 Att 1 - Specification Addendum.pdf

PDF 56 KB Posted

Attached to
FMC Rochester - Replace Bldg. 2, 4 & 10 Roofs Federal contract opportunity
Solicitation number
15BFA024B00000022
Issued by
Department of Justice Bureau of Prisons Field Acquisition Office

About this file

This document is an Addendum to the Specification for a federal construction contract opportunity to replace the roofs on Buildings 2, 4, and 10 at the Federal Medical Center (FMC) Rochester in Rochester, Minnesota.

The key details are: The addendum changes the specification to require only fully adhered single-ply membrane roofing systems, and prohibits ballasted roofing systems. The overall contract opportunity is for a firm-fixed-price construction contract to remove and replace the existing built-up roofs, install new R-44 insulation sloped to roof drains, and install a new .060" EPDM roofing membrane. The solicitation number is 15BFA024B00000022, the NAICS code is 238160 (Roofing Contractors) with a $19 million small business size standard, and the estimated project magnitude is between $1,000,000 and $5,000,000. The contract is a 100% small business set-aside, and interested bidders must be registered in SAM.gov. A pre-bid site visit is scheduled for September 11, 2024, and bids must be submitted electronically.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FMC ROCHESTER

PROJECT 24Z4AT4

REPLACE BLDG. 2, 4 & 10 ROOFS

ADDENDUM TO SPECIFICATION

The following changes are made to the specifications:

Page 07 50 00-2 section H. Specification

H. Only mechanically fastened single-ply membrane roofing systems shall be used. Fully Adhered and Ballasted single-ply membrane roofing systems are prohibited. Ballasted roofing systems are prohibited.

Should read:

H. Only fully adhered single-ply membrane roofing systems shall be used. Ballasted roofing systems are prohibited.